Sei sulla pagina 1di 20

Medium voltage products

PB/F type PowerCube


Fixed parts for medium voltage
circuit-breakers and contactors

Index

1. General characteristics

2. Main components

12

3. Types available and apparatus

18

4. Electric circuit diagram

1. General characteristics

The PowerCube type PB/F fixed parts


allow construction of medium voltage
air insulated switchgear divided into
compartments, with the same rated
current as that of the fixed part.
The rated currents of the fixed parts
refer to the versions tested in the ABB
UniSafe switchgear.
The PowerCube type PB/F fixed parts
are available with or without earthing
switch with making capacity.
Their compact dimensions and limited weights make the
PowerCube type PB/F fixed parts the ideal solution for
replacing fixed circuit-breakers with withdrawable circuitbreakers, for retrofitting activities and for upgrading obsolete
switchgear to the new Standards.

Front view of PowerCube type PB/F fixed part.

Fixed part electrical characteristics


PowerCube type

PB1/F - PB1/FL

PB2/F

Panel width (mm)

600

750

Contact diameter (mm)

35

35

79

12 kV

17.5 kV

28 kV

38 kV

75 kV

95 kV

25 kA for 3s

31.5 kA for 3s

63 kA

80 kA

630 A

1250 A

Rated voltage

PB4/F
750

24 kV
Test voltage at power frequency

50 kV
Impulse withstand voltage

125 kV
Short-time withstand current
Peak current

Rated currents

35

1600 A

2000 A

The PowerCube type PB/F fixed parts are factory-assembled


and tested and, where applicable, comply with IEC 62271200 and IEC 60694 Standards.
The fixed parts allow construction of arc proof switchgear
- classification LSC2B-PM IAC BFLR or LSC2B-PM AFLR
according to IEC 62271-200 (in accordance with IEC 60694
Standards for general characteristics).
The following apparatus can be installed in the PowerCube
type PB/F fixed parts:
VD4, VM1, eVM1 and Vmax series vacuum circuit-breakers
HD4 series gas circuit-breakers
V-Contact series vacuum contactors
All apparatus operations are carried out from the front of the
fixed part .

Rear view of PowerCube type PB/F fixed part.

Electrical characteristics of earthing switch (if provided)


PowerCube type

PB1/F

PB2/F

PB4/F

Panel width (mm)

600

750

750

25 kA

31.5 kA

Rated voltage
Impulse withstand voltage
Short-time withstand current
Short-circuit time

17.5 kV

24 kV
95 kV

125 kV

3 s

Note: the earthing switch is not available for PB1/FL units.

1. General characteristics

Interlocks
The PowerCube type PB/F fixed parts are fitted with the
interlocks needed to prevent incorrect operations which might
jeopardise safety of the personnel in charge of running the
installation, or the efficiency and reliability of the apparatus.
In particular, locking devices are provided to prevent the
following operations:
circuit-breaker closing in the intermediate position
racking-out of closed circuit-breaker
racking-in of closed circuit-breaker

Key locks on the earthing switch.

The following are also available for the units provided with
earthing switch:
lock to prevent earthing switch closing with the circuitbreaker in the connected or intermediate position
lock to prevent circuit-breaker racking-in with the earthing
switch closed
key locks on the earthing switch.
Note: some of the interlocks listed above are supplied on request or are only
available for some versions.

Lock on circuit-breaker racking-in with earthing switch closed.

Quality System
Complies with ISO 9001 Standards, certified by an
independent external organisation.

Test laboratory
Complies with ISO 45001 Standards, accredited by an
independent external organisation.

Environmental Management System


Complies with ISO 14001 Standards, certified by an
independent external organisation.

Health and Safety Management System


Complies with OHSAS 18001 Standards, certified by an
independent external organisation.

PowerCube fixed part


Width (mm)
Rated voltage

PB1/F

PB1/FL

PB2/F

PB4/F

600

600

750

750

12 kV

17.5 kV

24 kV
Standard fittings

Accessories to be
specifiedat the time
of ordering (assembly
by ABB)

Circuit-breaker anti-racking-in lock

Earthing switch

4
5

Accessories on request
(assembly by customer)

Plug socket with anti-racking-in lock for circuit- breakers with lower
rated current than that of the unit or for apparatus not foreseen l
for the unit itself

Key lock in open or closed position or in open and closed position,


for earthing switch
Electromechanical lock for earthing switch
(24-30-48-60-110-125-220-250 Vdc; 110-220 Vac 50Hz)

Earthing switch auxiliary contacts (5 or 10)

Safety device for metal shutters (Fail Safe)

Anti-condensation heater (110-220 Vac 50 Hz)

Padlock for metal shutters (top or bottom or top and bottom)

10

Earthing switch operating lever, extra in relation to normal supply (*)

11

Apparatus transport and racking-in truck

(*) The normal supply consists of one operating lever for every 10 fixed parts.

Overall dimensions
B

Module

PB1/F
PB1/FL
PB2/F
PB4/F

Rated
voltage

Rated
current

Isc
Icw

Table
of dimensions

Weight

[mm]

[mm]

[mm]

[kg]

596

1061

900

(*)

[kV]

[A]

[kV]

12

630 - 1250

31.5

1VCD003382

17.5

630 - 1250
31.5

1VCD003614

596

1015

787

(*)

31.5

1VCD003383

746

1061

1106

(*)

31.5

1VCD003384

746

1338

1236

(*)

12

630 - 1250

17.5

630 - 1250

12

630...2000

17.5

1250...2000

24

630 - 1250

(*) Ask ABB.

2. Main components

Circuit-breakers

HD4 series SF6 Circuit-breakers

The PowerCube units can be fitted with HD4 series SF6


withdrawable and VD4, VM1, eVM1 and Vmax series vacuum
circuit-breakers.
The circuit-breakers are fitted with a truck which allows their
racking-in and out of the switchgear with the door closed.
Both types have a compact and light structure which ensures
great sturdiness and excellent mechanical reliability.
The operating mechanism and poles are fixed to the metal
structure which also acts as a support for the moving contact
actuation kinematics.

The HD4 series of medium voltage circuit-breakers use


sulphur hexafluoride gas (SF6) to extinguish the electric arc
and as the insulating medium.
The breaking principle of HD4 circuit-breakers is based
on compression and self-blast techniques to obtain top
performances at all service current values, with gradual arc
extinction, no restriking, operating overvoltages or chopped
currents.
These characteristics guarantee long electrical life for the
circuit-breaker and limited dynamic, dielectric and thermal
stresses on the installation.
The circuit-breaker poles, which make up the interruption
part, are sealed for life pressure systems (IEC 62271-100
Standards) and are maintenance-free.
The stored energy mechanical operating mechanism has free
trip and allows opening and closing operations independent of
the operators actions.

VD4, VM1 and eVM1 series vacuum


circuit-breakers

HD4 series gas circuit-breaker.

VD4 series vacuum circuit-breaker.


8

The VD4, VM1 and eVD4 circuit-breakers use vacuum as the


interruption and insulating medium.
Thanks to the advanced techniques used for their
construction, the vacuum circuit-breakers ensure high
performances under all service conditions.
The vacuum interrupters are embedded in the poles made
of epoxy resin. This construction means the interrupters are
unaffected by shocks, humidity and environmental pollution.
The circuit-breaker poles, making up the interruption part, are
sealed for life pressure systems (IEC 62271-100 Standards)
and are maintenance-free.
The VD4 and eVD4 circuit-breakers use a mechanical type
of operating mechanism, the VM1 circuit-breakers use an
operating mechanism with a magnetic actuator.
They are both stored energy operating mechanisms with free
trip and allow opening and closing operations independent of
the operators actions.
The eVD4 circuit-breakers are also fitted with an integrated
measurement and protection system which can be configured
by means of a personal computer, directly by the customer
using some simple software.

Vmax/W series vacuum circuit-breakers


Vmax circuit-breakers are made up of an insulating monobloc
in which three vacuum interrupters are fixed. The monobloc
and the operating mechanism are fixed to a frame.
The vacuum interrupters house the contacts and make up the
interruption chambers of the circuit-breaker.
Vmax circuit-breakers use a mechanical stored energy
operating mechanism with free trip which allows opening and
closing operations independent of the operators actions. The
mechanical operating mechanism is of simple concept and
use and can be personalised with a wide range of easily and
rapidly installed accessories.
This simplicity characterised the apparatus for its reliability,
duration and limited maintenance.
Vmax circuit-breakers are used in power distribution for
control and protection of cables, overhead lines, transformer
and distribution substations, motors, transformers, generators
and capacitor banks.
The circuit-breaker vacuum interrupters, which make up the
interruption part, are sealed for life pressure systems (IEC
62271-100 Standards) and are maintenance-free.

eVD4 series vacuum circuit-breaker.

V-Contact VSC/P series vacuum


contactors
Use of V-Contact series withdrawable contactors is foreseen in
the PB1 PowerCube units up to 12 kV.
The contactors are suitable for controlling alternating current
users which require a high number of operations.
They consist of a resin monobloc where the vacuum
interrupters, moving equipment, operating mechanism,
multivoltage feeder and auxiliary accessories are housed.
The monobloc is also the support for installation of the fuses.
Fuses according to DIN or BS Standards of different
dimensions can be used thanks to special adapters.
The type of fuseholder (BS or DIN) must be specified when
ordering.
Contactor closing is prevented when even a single fuse is
missing. Opening is automatic when one of the three fuses
blows.
They are of compact and sturdy construction and guarantee
very long electrical and mechanical life.

Vmax/W series vacuum circuit-breaker.

V-Contact series vacuum contactors VSC/P


9

2. Main components

Earthing switches
The PB/F type PowerCube units can be fitted with an earthing
switch. The earthing switch is fitted with short-circuit making
capacity.
On request, the opening and closing operations can be
locked by means of key locks.

Earthing switch control is carried out from the front of the


module with manual operation suitably interlocked with the
circuit-breaker position.
For availability of the accessories, please see the table on
page 5.

Earthing switch closed.

Earthing switch open.

Certain signalling of the earthing switch


position (open/closed) visible from the
front of the enclosure.

10

Monoblocs and shutters


The monoblocs consist of insulator bushings containing the
top and bottom power connections of the circuit-breaker
compartment, towards the feeder and busbar compartments
respectively.
The shutters are of the metal type and are activated
automatically during movement of the circuit-breaker from

Padlocks on the shutters (padlocks provided by the customer).

the test/isolated position to the connected position and vice


versa.
They can be fitted with a fail-safe safety device (optional)
to prevent their manual opening with the circuit-breaker
removed.
Each shutter can be locked by means of two independent
padlocks (optional).

Safety device on the shutters (fail safe).

11

3. Types available and apparatus

Apparatus which can be combined

HD4 withdrawable circuit-breaker


Rated current of the apparatus racked
into the fixed part

kV

12-17.5

24

W =
P =
u/l =
H =
=

12

W=600

W=750

W=750

W=750

p=150

p=210

p=210

p=210

u/l=205

u/l=310

u/l=310

u/l=310

H=260

H=280

H=280

H=325

=35

=35

=79

=35

Apparatus which can be combined with


the fixed part

Isc
(kA)

Icw
(kA)

16

16

630

HD4/W 12.06.16 p150

HD4/W 17.06.16 p150

20

20

630

HD4/W 12.06.20 p150

HD4/W 17.06.20 p150

Type of apparatus

PowerCube

25

25

630

HD4/W 12.06.25 p150

HD4/W 17.06.25 p150

31.5

31.5

630

HD4/W 12.06.32 p150

HD4/W 17.06.32 p150

PB1/F

16

16

1250

HD4/W 12.12.16 p150

HD4/W 17.12.16 p150

PB1/FL

20

20

1250

HD4/W 12.12.20 p150

HD4/W 17.12.20 p150

25

25

1250

HD4/W 12.12.25 p150

HD4/W 17.12.25 p150

31.5

31.5

1250

HD4/W 12.12.32 p150

HD4/W 17.12.32 p150

16

16

630

HD4/W 12.06.16 p210

HD4/W 17.06.16 p210

20

20

630

HD4/W 12.06.20 p210

HD4/W 17.06.20 p210

25

25

630

HD4/W 12.06.25 p210

HD4/W 17.06.25 p210

31.5

31.5

630

HD4/W 12.06.32 p210

HD4/W 17.06.32 p210

16

16

1250

HD4/W 12.12.16 p210

HD4/W 17.12.16 p210

20

20

1250

HD4/W 12.12.20 p210

HD4/W 17.12.20 p210

25

25

1250

HD4/W 12.12.25 p210

HD4/W 17.12.25 p210

31.5

31.5

1250

HD4/W 12.12.32 p210

HD4/W 17.12.32 p210

20

20

1600

HD4/W 12.16.20 p210

HD4/W 17.16.20 p210

25

25

1600

HD4/W 12.16.25 p210

HD4/W 17.16.25 p210

31.5

31.5

1600

HD4/W 12.16.32 p210

HD4/W 17.16.32 p210

20

20

2000

HD4/W 12.20.20 p210

HD4/W 17.20.20 p210

25

25

2000

HD4/W 12.20.25 p210

HD4/W 17.20.25 p210

31.5

31.5

2000

HD4/W 12.20.32 p210

HD4/W 17.20.32 p210

16

16

630

HD4/W 24.06.16 p210

20

20

630

HD4/W 24.06.20 p210

25

25

630

HD4/W 24.06.25 p210

16

16

1250

HD4/W 24.12.16 p210

20

20

1250

HD4/W 24.12.20 p210

25

25

1250

HD4/W 24.12.25 p210

Width of fixed part.


Horizontal centre distance between circuit-breaker poles.
Distance between top and bottom terminal.
Distance between bottom terminal and earth.
Diameter of the contacts in the PB type PowerCube unit monobloc.

PB2/F

PB4/F

VD4 withdrawable circuit-breaker


Rated current of the apparatus racked
into the fixed part

kV

12-17.5

24

W =
P =
u/l =
H =
=

W=600

W=750

W=750

W=750

p=150

p=210

p=210

p=210

u/l=205

u/l=310

u/l=310

u/l=310

H=260

H=280

H=280

H=325

=35

=35

=79

=35

Apparatus which can be combined with


the fixed part

Isc
(kA)

Icw
(kAx3 s)

16

16

630

VD4/P 12.06.16 p150

VD4/P 17.06.16 p150

20

20

630

VD4/P 12.06.20 p150

VD4/P 17.06.20 p150

Type of apparatus

PowerCube

25

25

630

VD4/P 12.06.25 p150

VD4/P 17.06.25 p150

31.5

31.5

630

VD4/P 12.06.32 p150

VD4/P 17.06.32 p150

PB1/F

16

16

1250

VD4/P 12.12.16 p150

VD4/P 17.12.16 p150

PB1/FL

20

20

1250

VD4/P 12.12.20 p150

VD4/P 17.12.20 p150

25

25

1250

VD4/P 12.12.25 p150

VD4/P 17.12.25 p150

31.5

31.5

1250

VD4/P 12.12.32 p150

VD4/P 17.12.32 p150

16

16

630

VD4/W 12.06.16 p210

VD4/W 17.06.16 p210

20

20

630

VD4/W 12.06.20 p210

VD4/W 17.06.20 p210

25

25

630

VD4/W 12.06.25 p210

VD4/W 17.06.25 p210

31.5

31.5

630

VD4/W 12.06.32 p210

VD4/W 17.06.32 p210

16

16

1250

VD4/W 12.12.16 p210

VD4/W 17.12.16 p210

20

20

1250

VD4/W 12.12.20 p210

VD4/W 17.12.20 p210

25

25

1250

VD4/W 12.12.25 p210

VD4/W 17.12.25 p210

31.5

31.5

1250

VD4/W 12.12.32 p210

VD4/W 17.12.32 p210

20

20

1600

VD4/P 12.16.20 p210

VD4/P 17.16.20 p210

25

25

1600

VD4/P 12.16.25 p210

VD4/P 17.16.25 p210

31.5

31.5

1600

VD4/P 12.16.32 p210

VD4/P 17.16.32 p210

20

20

2000

VD4/P 12.20.20 p210

VD4/P 17.20.20 p210

25

25

2000

VD4/P 12.20.25 p210

VD4/P 17.20.25 p210

31.5

31.5

2000

VD4/P 12.20.32 p210

VD4/P 17.20.32 p210

16

16

630

VD4/P 24.06.16 p210

20

20

630

VD4/P 24.06.20 p210

25

25

630

VD4/P 24.06.25 p210

16

16

1250

VD4/P 24.12.16 p210

20

20

1250

VD4/P 24.12.20 p210

25

25

1250

VD4/P 24.12.25 p210

PB2/F

PB4/F

Width of fixed part.


Horizontal centre distance between circuit-breaker poles.
Distance between top and bottom terminal.
Distance between bottom terminal and earth.
Diameter of the contacts in the PB type PowerCube unit monobloc.

13

3. Types available and apparatus

VM1 withdrawable circuit-breaker

Rated current of the apparatus racked


into the fixed part

kV

12-17.5

24

W=600

W=750

W=750

W=750

p=150

p=210

p=210

p=210

u/l=205

u/l=310

u/l=310

u/l=310

H=260

H=280

H=280

H=325

=35

=35

=79

=35

Isc
(kA)

Icw
(kAx3 s)

16

16

630

VM1/P 12.06.16 p150

VM1/P 17.06.16 p150

20

20

630

VM1/P 12.06.20 p150

VM1/P 17.06.20 p150

Type of apparatus

PowerCube

25

25

630

VM1/P 12.06.25 p150

VM1/P 17.06.25 p150

31.5

31.5

630

VM1/P 12.06.32 p150

VM1/P 17.06.32 p150

PB1/F

16

16

1250

VM1/P 12.12.16 p150

VM1/P 17.12.16 p150

PB1/FL

20

20

1250

VM1/P 12.12.20 p150

VM1/P 17.12.20 p150

25

25

1250

VM1/P 12.12.25 p150

VM1/P 17.12.25 p150

31.5

31.5

1250

VM1/P 12.12.32 p150

VM1/P 17.12.32 p150

16

16

630

VM1/W 12.06.16 p210

VM1/W 17.06.16 p210

20

20

630

VM1/W 12.06.20 p210

VM1/W 17.06.20 p210

25

25

630

VM1/W 12.06.25 p210

VM1/W 17.06.25 p210

31.5

31.5

630

VM1/W 12.06.32 p210

VM1/W 17.06.32 p210

16

16

1250

VM1/W 12.12.16 p210

VM1/W 17.12.16 p210

20

20

1250

VM1/W 12.12.20 p210

VM1/W 17.12.20 p210

25

25

1250

VM1/W 12.12.25 p210

VM1/W 17.12.25 p210

31.5

31.5

1250

VM1/W 12.12.32 p210

VM1/W 17.12.32 p210

20

20

1600

VM1/P 12.16.20 p210

VM1/P 17.16.20 p210

25

25

1600

VM1/P 12.16.25 p210

VM1/P 17.16.25 p210

31.5

31.5

1600

VM1/P 12.16.32 p210

VM1/P 17.16.32 p210

20

20

2000

VM1/P 12.20.20 p210

VM1/P 17.20.20 p210

25

25

2000

VM1/P 12.20.25 p210

VM1/P 17.20.25 p210

31.5

31.5

2000

VM1/P 12.20.32 p210

VM1/P 17.20.32 p210

16

16

630

PB2/F

VM1/P 24.06.16 p210

20

20

630

VM1/P 24.06.20 p210

25

25

630

VM1/P 24.06.25 p210

16

16

1250

VM1/P 24.12.16 p210

20

20

1250

VM1/P 24.12.20 p210

25

25

1250

VM1/P 24.12.25 p210

W = Width of PowerCube module.


P = Horizontal centre distance between circuit-breaker poles.
u/l = Distance between top and bottom terminal.
H = Distance between bottom terminal and earth.
= Diameter of the contacts in the PowerCube module monobloc.
(*) The fixed part are not prepared for application of the motorised truk.

14

Apparatus which can be combined


with the fixed part

PB4/F

eVD4 withdrawable circuit-breaker

Rated current of the apparatus racked


into the fixed part

kV

12-17.5

W =
P =
u/l =
H =
=

W=600

W=750

W=750

W=750

p=150

p=210

p=210

p=210

u/l=205

u/l=310

u/l=310

u/l=310

H=260

H=280

H=280

H=325

=35

=35

=79

=35

Apparatus which can be


combined with the fixed part

Isc
(kA)

Icw
(kAx3 s)

16

16

630

eVD4/P 12.06.16 p150

20

20

630

eVD4/P 12.06.20 p150

eVD4/P 17.06.20 p150

25

25

630

eVD4/P 12.06.25 p150

eVD4/P 17.06.25 p150

31.5

31.5

630

eVD4/P 12.06.32 p150

eVD4/P 17.06.32 p150

Type of apparatus

PowerCube

eVD4/P 17.06.16 p150

16

16

1250

eVD4/P 12.12.16 p150

eVD4/P 17.12.16 p150

20

20

1250

eVD4/P 12.12.20 p150

eVD4/P 17.12.20 p150

25

25

1250

eVD4/P 12.12.25 p150

eVD4/P 17.12.25 p150

31.5

31.5

1250

eVD4/P 12.12.32 p150

eVD4/P 17.12.32 p150

PB1/F
PB1/FL

Width of fixed part


Horizontal centre distance between circuit-breaker poles.
Distance between top and bottom terminal.
Distance between bottom terminal and earth.
Diameter of the contacts in the PB type PowerCube unit monobloc.

15

3. Types available and apparatus

Vmax withdrawable circuit-breaker

Rated current of the apparatus


racked into the fixed part

kV

12-17.5

W =
P =
u/l =
H =
=
* =

16

W=600

W=750

W=750

W=750

p=150

p=210

p=210

p=210

u/l=205

u/l=310

u/l=310

u/l=310

H=260

H=280

H=280

H=325

=35

=35

=79

=35

Apparatus which can be combined


with the fixed part

Isc
(kA)

Icw
(kAx3 s)

16

16

630

Vmax/W 12.06.16 p150

Vmax/W 17.06.16 p150 *

20

20

630

Vmax/W 12.06.20 p150

Vmax/W 17.06.20 p150 *

Type of apparatus

PowerCube

25

25

630

Vmax/W 12.06.25 p150

Vmax/W 17.06.25 p150 *

31.5

31.5

630

Vmax/W 12.06.32 p150

Vmax/W 17.06.32 p150 *

PB1/F

16

16

1250

Vmax/W 12.12.16 p150

Vmax/W 17.12.16 p150 *

PB1/FL

20

20

1250

Vmax/W 12.12.20 p150

Vmax/W 17.12.20 p150 *

25

25

1250

Vmax/W 12.12.25 p150

Vmax/W 17.12.25 p150 *

31.5

31.5

1250

Vmax/W 12.12.32 p150

Vmax/W 17.12.32 p150 *

Width of fixed part


Horizontal centre distance between circuit-breaker poles.
Distance between top and bottom terminal.
Distance between bottom terminal and earth.
Diameter of the contacts in the PB type PowerCube unit monobloc.
For availability ask ABB.

V-Contact withdrawable contactor

Rated current of the apparatus


racked into the fixed part

kV

7.2

12

Apparatus which can be


combined with the fixed part

W=600

W=750

W=750

W=750

p=150

p=210

p=210

p=210

u/l=205

u/l=310

u/l=310

u/l=310

H=260

H=280

H=280

H=325

=35

=35

=79

=35

Isc
(kA)

Icw
(kAx3 s)

16

400

(1)

20

400

(1)

25

400

(1)

31.5

400

(1)

16

16

400

(1)

20

20

400

(1)

25

25

400

(1)

31.5

31.5

400

(1)

Type of apparatus

PowerCube

VSC7/P

PB1/F
PB1/FL
VSC12/P

(1) The rated current is subject to derating according to the rated current of the fuses.
W = Width of fixed part.
P = Horizontal centre distance between circuit-breaker poles.
u/l = Distance between top and bottom terminal.
H = Distance between bottom terminal and earth.
= Diameter of the contacts in the PB type PowerCube unit monobloc.

17

4. Electric circuit diagram

Reference designations
In compliance with IEC 61346-2 Standard and with the ABB 2NBA000001 technical standard

Designation

Description

-RL3

Electro-mechanical lock on earthing switch closing operation

-SL

Contact for the earthing switch operation lock

-SU3

Delayed pushbutton for enabling earthing switch operation


(maximum delay allowed is 1 minute) (to be provided by the customer)

Graphic symbols (in compliance with IEC 60617 and CEI EN 60617 Standards)

Mechanical, pneumatic or hydraulic connection

Delayed movement (in the direction the arc moves towards its centre)

Pushbutton actuator
Connection of conductors
Socket and plug (female and male)

Control coil (general symbol)

18

19

ABB S.p.A.
Power Products Division
Unit Operativa Sace-MV
Via Friuli, 4
I-24044 Dalmine
Tel.: +39 035 6952 111
Fax: +39 035 6952 874
E-mail: info.mv@it.abb.com

ABB AG
Calor Emag Medium Voltage Products
Oberhausener Strasse 33
Petzower Strasse 8
D-40472 Ratingen
D-14542 Glindow
Phone: +49(0)2102/12-1230, Fax: +49(0)2102/12-1916
E-mail: powertech@de.abb.com
www.abb.com

The data and illustrations are not binding. We reserve


the right to make changes without notice in the course
of technical development of the product.
Copyright 2012 ABB.
All rights reserved.

1VCP000253 - Rev. B, en - Technical Catalogue - 2012.01 (PowerCube PB/F) gs

Contact us

Potrebbero piacerti anche