Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
OF THE
UNIVERSITY OF CALIFORNIA.
Class
The D. Van
intend this
NoSlrand
book
to
be sold
Company
to the Public
and supply it to
the Trade on terms which will not allow
at the advertised price,
of reduction.
[Frontispiece.
View
of assembling
THE
DESIGN OF STATIC
TRANSFORMERS
BY
H. M.
HOBART,
INST. C.E.
NEW YORK
D.
23
MURRAY AND
27
WARREN STREETS
1911
PREFACE
THE
present treatise
is
It
the
last
edition
of the latter
work,
it
still
remains, in
my
the transformer.
My
own work
it is
set
to practice
literature
papers.
Amongst
may
be mentioned the
in June, 1909,
A
&
perusal of
Co.,
my
treatise entitled
London, 1910),
will assist to
"
"
Electricity
(Constable
an understanding of the
224493
PREFACE
viii
number
details.
Bibliography
many
a
of
essential
considerable
is given at
the end of Chapter I.
In conclusion, I wish to acknowledge
the work of my former assistant, Mr. Evelyn Good, who
me
H. M.
LONDON,
December, 1910.
HOBART,
M. INST. C.E.
TABLE OF CONTENTS
PAGE
CHAP.
FRONTISPIECE
PREFACE
LIST OF ILLUSTRATIONS
I.
II.
.,
....
IV.
VII.
.'.'',.
VIII.
IX.
X.
...
59
68
82
88
93
113
FORCED-COOLED TRANSFORMERS
.16
III.
VI.
.XI
INTRODUCTORY
RATING
V.
VJi
"
'
..
..;;..
145
155
LIST
OF ILLUSTRATIONS
1.
2.
3.
PAGE
TITLE.
FIG.
Single-phase Transformer
Outline Sketch of a Representative Design of a Shell-type
17
Single-phase Transformer
Outline Sketch of a Type of Transformer adapted from Dr.
Kittler's
Handbuch der Elektrotechnik," 1892
,
"
"
.
Diagrammatic Sketch of Berry Transformer
18
'
' '
4.
5.
6.
7.
8.
12.
Primary Voltages
"
Curves showing " Volts per Turn
of Single-phase Transformers of Different Bated Outputs and Periodicities.
Curve A 50 Cycles Curve B 25 Cycles
Saturation Curve of Bepresentative Sheet Steel
Hysteresis Loss Curves for Various Periodicities for Old High
Loss Sheet Iron
Hysteresis Loss Curves for Various Periodicities for Low Loss
13.
14.
15.
16.
9.
....
...
10.
11.
19
21
22
23
25
27
28
34
.35
35
Alloy Steel
Low
36
Sheet Iron
Periodicities
for
36
..........
High Loss
37
Steel
37
17. 18.
19.
38
44
LIST OF ILLUSTRATIONS
xii
TITLE.
FIG.
20, 21.
Types of Sections
Types of Sections
22
25.
26.
27.
28.
PAGE
.45
....
Transformer Cores
of Transformer Cores
of
30.
in Centimeters)
Section of Winding and Core of 20-kw 5000/200-volt Transformer (Dimensions in Centimeters)
Simple Concentric Winding
46
46
47
48
......51
29.
31.
Triple Concentric
32.
Sandwich Winding
33.
49
51
Winding
.52
52
34. 35.
.........
;
36.
37.
Profit to Electricity
39.
Factors
41.
.........
.......
........
of
of
20-kw Transformer
69
for
72
.73
...
44.
66
Loss=190
Loss= 360
43.
63
38.
40.
56
58
75
76
45. 46.
.....
47.
.79
48.
Curves
..........
49.
77
formers
Outline Drawing showing the Arrangement of the Windings
of the
80
.82
LIST OF ILLUSTRATIONS
50.
xiii
Sectional
former.
.83
....
Volts
25 Cycles,
50 Cycles
(c)
in
Core-type Trans-
in
Core-type
56.
57.
58.
.
.
.
former
Curve of Values for / in Formula " Percentage Reactance Drop
a "
...
former
= fb~c
59.
92
94
.95
'
100
60.
86
Trans-
'
84
101
61.
62.
63.
64.
65.
68.
69.
Arrangement
70.
Arrangement
66.
67.
former
109
of Coils in Core-type
Secondary
of Coils in
...
.111
Secondary
of Coils in Core-type
71.
Arrangement
72.
Air-cooled Transformer
73.
Secondary
74.
75.
.112
.114
LIST OF ILLUSTEATIONS
xiv
76.
PA(!E
TITLE.
FIG.
Heating Curves
of Oil Transformer.
119
77.
78.
79.
80.
120
121
121
122
in Oil
81.
82.
83.
84.
137
85.
123
142
146
147
.....
and Bottom
86.
Method
87.
88.
89.
90.
91.
Diagrammatic Sketch
92.
Air-blast Transformers
550-kva 50-cycle Air-blast Transformer by the Westinghouse
93.
91.
Bank
Case
of a
Transformer
150
153
sion
of
an
Air-blast
former
Trans-
American
of
.155
.156
General Electric
Co.'s
Co
95.
97.
157
158
of
Transformers
10 000-kva Oil-insulated Water-cooled Westinghouse Transformers
View of the Interior -,of the American General Electric Co.'s
10 000-kva 100 000-volt 60-cycle Design for a Watercooled Oil immersed Transformer before the Cooling Coils
have been Mounted
American General Electric Co.'s 10 000-kva 100 000-volt
Design with the Cooling Coils in Place
of Air-blast
96.
152
159
160
163
164
165
LIST OF ILLUSTRATIONS
xv
100.
101.
to promote Circulation
Forced Oil-cooled Transformer and Accessory Plant
98.
99.
99 A.
.172
.173
INTRODUCTORY
PAPER by Mr. George Westinghouse, entitled " The
1
Electrification of Kailways," was read at a recent meeting of
the
Institution
of Mechanical Engineers.
"As
static
pressure with a loss of only a trifle of the energy so transformed, would have been to achieve enduring fame. The facts
divide this honour
among
of millions."
At a
follows
"
I was led in 1885, to interest myself in the
:
American
S.T.
'
'
No inventions ever met with greater opposition in their commercial development than those relating to the generation,
distribution
and
The zeal displayed twenty-five years ago by Mr. Westinghouse in the matter of the introduction and the extension of
systems employing alternating electricity has continued down
to the present day, and while, in my opinion, one result has
in
scale
America.
than had
The volumes
that
at
time
to
approached in
XVII.
been
from 1888
to
1892 (Vois.
"
Transformers
v.
Accumulators,"
"
INTRODUCTORY
Capacity and
by
Self-induction,"
J.
"Some
A. Fleming;
of Alternating
Currents," by
Experimental Investigations
Alexander Siemens " Experimental Researches on Alternate;
that afforded
month
some
a
specified
number
of each transformer's
The
number and
the most usual sizes were those of but a couple of kilowatts rated
capacity.
They were nearly all for a periodicity of 125 cycles
per second, and the primaries were usually wound so that they
could be connected either for 1000 or 2000 volts, the secondaries
usually being connected to give either 52 or 104 volts on no load.
The measuring of the core loss was no part of my task indeed
;
my
detail.
acquaintance with
A year or so
static
later
me renewing
This time the
found
transformers.
scene was an instrument calibrating and experimental department. Our duties, so far as related to transformers, comprised
testing the insulation resistances between primaries and
secondaries and "to frame," of transformers of various sizes
and types.
We
The
front
and
methods and
down
"
Magnetic Induction
and Other Metals," and in ourselves making ballistic
of sheet iron and steel.
The facilities of our department
results set
in
Ewing's
in Iron
tests
remembered that
it
steel
But
material of the good quality of the occasional sample.
even our best results of that time (1890 and 1891) related to
materials which were far inferior, as regards core loss, to the
low-loss alloys at present (1910) employed, and were also much
more prone to " ageing." Contemporaneously with the testing
of magnetic materials, we were required to make tests of the
INTKODUCTOEY
circuits.
At
that time
we measured
inductance of the pressure coil by the use of very high resistances, wound non-inductively, in series with the pressure coil.
This, of course, involved weaker forces and the use of weaker
The
torsion springs.
We
mercury cups constituted an annoying source of error.
were guided through these difficulties to no inconsiderable
extent by the inspiring co-operation of Mr. Ernst Danielson,
the company by whom
I was employed.
Danielson encouraged me to study Dr.
"
"
Fleming's Alternate-current Transformer and to draw vector
Among
twice as
much
much copper
as the
more usual
for the
its
own
to
the
intervals
was
definitely
when
its
we
were
impressed
with
the
it
built.
This gave
it
We
nator was very peaked under both conditions, and (for a given
terminal pressure) had a crest pressure some 10 per cent,
" smooth-core "
alterhigher than the crest pressure of the
In other words, the form factor (defined by Fleming
nator.
"
on p, 583 of Vol, L of the 2nd edition of his Alternate-current
INTEODUCTOEY
Transformer
"
higher
machine.
mean
or average value)
was 10 per
cent,
10 per
cent, higher
The
X 1,11 =) 1,22. It is highly important that the presentshould have these points well in mind, since they
student
day
are apt to be less appreciated when read from books than
(1,10
is
wave of pressure, nevertheless various conditions temporarily occurring in electrical networks often occasion a very
sine
considerable
distortion
to
of
the
wave form.
specify that
core
It
is
certainly
shall be
decidedly important
measured from a circuit supplying a sine wave of pressure.
The
losses
in which
it
was encountered
at our
Danielson's insight.
Up to this time (1892) our transformers had almost
all been
and
125
for
a
cycles
designed for
lighting load, i.e., for
supplying incandescent lamps.
Owing to the non-inductive
character of this load, there had been no occasion to devote
to
circuit with a
minimum mean
to
on the contrary, it
secondary coils was so especially a fault
difficulties were due to the increased
;
transformers on the
60-cycle
which were
circuits,
at
first
for
power purposes.
usually employed
pressure halving the periodicity doubled the flux required in
This did not so greatly increase the
the magnetic circuit.
core loss, since the doubled density was partly offset by the
halved periodicity in fact, the core loss was only increased
;
greatly increased
saturation.
The
also in
of
power work,
in
new
for
i.e.,
coils,
so as to
the matter of so
the transformer in
oil,
INTRODUCTORY
whom
oil
Thomson)
the development of
the pressures
pressures of
2000
employed in transformers.
Up to 1892
to 3000 volts had only been exceeded in
cases, but
In
but employed
of
groups
three
single-phase
transformers.
For
installations
required
it
as
it
first
But
is
down
to
it,
10
am
of transformer
enunciation of rules,
formulas
still
affords,
and
will
for
many
and in the
may
and
tables, but
transformers.
it
The
INTRODUCTORY
11
subjects,
of these
(which are
subjected to
as
distinguished
distinct
to
definite designing
methods
is practicable,
and
I believe that I
am
after
subject,
and
am
of opinion that
will
12
On
GISBERT KAPP.
(Journ. Inst.
v.
1889.
W. M. MOEDEY.
H.
J.
EYAN.
Transformer Curves.
(Trans.
Am.
Yol. 6.)
1891.
JAMES SWINBURNE.
Transformer Distribution.
DR.
On Some
A. FLEMING.
J.
NIKOLA TESLA.
Frequency.
and Self-induction.
(Trans.
Am.
of
Yery High
1892.
ALEXANDER SIEMENS.
Currents.
of Alternate
p. 164.)
and
621.)
1893.
C. P.
(Trans.
STEINMETZ.
Am.
FREDERICK BEDELL.
Am.
of Dielectrics.
(Trans.
1895.
C. P.
(Trans.
STEINMETZ.
Am.
Theory
1896.
INTKODUCTOKY
An
K. HUGUET.
C.
13
(Trans.
Am.
1898.
W.
WHITE.
F.
Manager's View-point. (Trans. Am. Inst. Elec. Engrs., Vol. 15, p. 505.)
F. W. CARTER. The Design of Transformers. (Trans. Am. Inst. Elec.
Engrs., Vol. 15, p. 639.)
1899.
W.
L.
formers.
EOBB.
(Trans.
Series
Am.
1903.
F. 0. BLACKWELL.
or
Am.
1904.
W.
E.
EICE, JR.
Blast Transformers.
W.
S.
MOODY.
formers.
(Trans.
J. S.
Am.
The Use
PECK.
of Oil
Am.
(Trans.
(Trans.
Am.
1906.
EPSTEIN.
Construction.
H. BOHLE.
H. W. TOBEY.
formers.
J.
S.
Transformers.
C. C.
(Trans.
CHESNEY.
Oil-insulated Transformers.
Part
1, p.
835.)
(Trans.
Am.
14
Iron.
Transformers
Some
Am.
terminals.
K.
C.
(Trans.
EANDALL.
INTKODUCTOBY
15
Oils.
FRANK.
Wave Shapes of Transformers. (Proc. Am. Inst. Elec. Engrs., Yol. 29,
Number 5, p. 665.)
ADOLPH SHANE. Determination of Transformer Eegulation under
Load and Some Resulting Investigations. (Proc. Am. Inst. Elec. Engrs.,
Yol. 29, Number 7, p. 1089.)
H. W. TOBEY. Dielectric Strength of Oil. (Proc. Am. Inst. Elec.
Engrs., Yol. 29, Number 7, p. 1171.)
F. C. GREEN.
Am.
Number
(Proc.
12, p. 1919.)
191L
Number
1, p. 1.)
M. WEED.
J.
(Proc.
W.
Am.
J.
WOOLDRIDGE.
Silicon Steel.
(Proc.
H. E. WILSON.
Am.
Am.
Number
1, p.
119.)
Hysteresis and
Inst. Elec.
Commercial Problems
Number
of
Transformer Design.
1, p.
143.)
(Proc.
CHAPTEE
THE LEADING DIMENSIONS
OF
II
A TRANSFORMER OF A GIVEN
RATING
NUMBER
Most of these
design.
papers, however, are overweighted with complex formula and
are useless to the practical designer.
In the majority of
technical colleges the students
designing
nothing
is
so far
Nevertheless, like
all
The
where
it
is
applied to a large
number
necessary to
are based
on
make assumptions.
my
experience as
So
far
DIMENSIONS OF A TRANSFORMER
as
it
17
been
done.
feel
former
design
has
machinery. This
be regretted, since
cal
is to
transformers
consti-
by no means a
minor detail in electritute
cal
engineering work,
and
it is
they
important that
should be well
and
designed
well
The number
of
transformers in use
is
built.
increasing at
mous
rate.
an enor-
The most
characteristic
unique
of electricity as distin-
other
guished from
forms of energy is the
high efficiency with
which transformations
may be
effected.
Since
of static
trans-
1.
Outline sketch of a representative
design of a core-type single-phase transformer.
FIG.
formers efficiencies in
excess of 90 per cent, are customary, and since in
S.T.
some of the
C
18
now coming
is
but
little
FIG.
2.
so
high efficiency.
Even when
DIMENSIONS OF A TRANSFORMER
19
there
is
no reason why
efforts
to
standardise
periodicity, pressure or
very
far.
It is
particular case
FIG.
3.
am
that the aggregate capacity of the transformers and motor generators absorbed annually in engineering undertakings will be
many
This absolute
c 2
20
increase
now
the case.
refrain
from taking
my opinion, ill-advised,
since they will not be so well prepared to participate in the
increasing turnover in electrical machinery.
up
former
is
composed of
more or
less rectangular-shaped
windings.
copper windings.
windings
medium
of the core
type
are
exposed
to
of the
the surrounding
In Fig. 1
is
shown an
is
thus exposed.
Another type,
may be
designated the
"
circular-shell type."
The
arrange-
DIMENSIONS OF A TEANSFOEMEE
ment indicated
21
which has
its
of the
development
"
characteristic advantages
"
Berry
transformer, and
is
secondary
windings
shown diagrammatically
in Fig. 4.
is
but
circuit
the
number
of distinct groups
"
"
of core plates.
type
is
The
Berry
thoroughly discussed by
Much of a
controversial nature
is,
electrical
that,
so
far
as
is
concerned,
design
very little to choose
between the two types. It is,
there
is
however,
that
the
interesting
shell
type
to
note
FIG.
"
is
sketch of
Diagrammatic
"
4.
Berry
transformer.
rarely
Even
those manufacturers
their
who adopt
nevertheless
the
build
22
transformers.
In Fig.
transformer, and
former.
in Fig.
is
These transformers
\vere
house Company.
The absence of radical advantage
hoth built
in
\)y
the Westing-
DIMENSIONS OF A TBANSFOKMER
FIG.
6.
23
21
electrical design
Faye-Hansen
of Electrical Engineers.
to
the rectangular-core type for a rated output of 20 kilovoltamperes. I shall work out the design for a primary pressure of
5000 volts and for a secondary pressure of 200 volts. Let it be
required that the regulation at full load shall be within 2,0 per
The transformer is to be designed for use on circuits having
cent.
power
former
20 kw.
G=
Consequently the
factor of the load is 1,00, and the output of the transis in this
1,00.
Thus we have
safer, in
known
that the power factor would be, say, 0,80 and the output
20 kw., then the transformer must be designed for a current
=)/
25 kilovoltamperes.
all types of single -phase oil-cooled transformers up to the outputs shown, whether of the shell type or
of the core type, and, in fact, no error of consequence will be
1 "
Transformers
Some Theoretical and Practical Considerations," A.
Fleming and K. M. Faye-Hansen, Jour.I.E.E., Vol. XLII., p. 373.
:
P.
M.
DIMENSIONS OF A TKANSFOEMER
25
51
howing
Fig.
introduced by embarking upon the calculation of natural aircooled transformers on the basis of these preliminary efficiencies.
26
Few
make
a slight alteration
The primary
20 000
5000 X 0,971
is
4,12 amperes,
At the next
is
100 amperes. 1
large
may exist, even in equally good designs.
This factor is the " volts per turn." In general, the pressure
between each turn of the winding may be varied over a very
differences
wide range, depending partly upon the object which the designer
has in view, but more especially upon the instinct, preferences
pressures,
"
(the
the
determining
factor
for
this
for
for
quantity
DIMENSIONS OF A TRANSFORMER
27
R
tfi
^
55
I
I
flQ
so
5}
is
"
Another quantity, the
28
does,
to
very considerable
extent,
the
limit
choice
of
7.0
0.0
50
7
zo
//
/.o
2O
/oo
"
FIG.
.
is
low.
This
is
for reasons
be more apparent at a later stage in the workingout of the design. In transformers of low and of moderate
which
will
"
"
the necessity
DIMENSIONS OF A TRANSFORMER
for a large
number
29
Thus
small weights of steel and sufficiently low core losses.
would
be
the
than
case
were
lower
insulation
the values are
safety factors the only consideration,
and
practice.
less
" volts
per turn," and although there
are certain advantages attending such proportions, yet it may
occur that other (very often essential) qualities are sacrificed
given in Fig. 8 for the
Each designer
he gains in
experience, readily decide for himself in each case which of
these two tendencies he considers it best to follow; but the reader
by
their
may
employment.
prefer,
until
will,
as
my
usual values,
are
also
It
much below
may
much
values
higher
often
circular
transformers the conductors are composed of strips.
lead
to
a
conductor, to give so large a section, would
prohibitive
amount of lost space in winding the coils. These strips are
"
Some approwith the higher values of the
volts per turn."
"
priate values for the "volts per turn for these large transformers
1.
30
TABLE
1.
For our present purpose, let us take for the " volts per turn"
of the 20-kw transformer the value read from the curves in Fig. S,
namely, 1,6 volts. There will thus be required (roughly) some
/200
\
=) 125 secondary turns, and 3125 primary turns, the
[ys
which
is
some multiple
It is generally convenient, in
number
of secondary turns to a
some
way
V
where
V represents
0,0444
Too
of expressing this
is
the total
number
and although,
in
many
cases,
it
is justifiable
is
a sine
to
make
DIMENSIONS OF A TEANSFOEMEE
31
is,
in practice, often
use of the
"form factor" 1
of a curve
may be denned
mean
mean
of the curve.
factor by/,
Thus,
if
we have
rms value of ordinates
*
'"
mean
value of ordinates*
continuous electricity,
equal to one another, each being equal to the crest value of the
The form factor thus becomes equal to unity, and this
curve.
In an
is the minimum possible value which it can have.
ordinary continuous-electricity machine, however, the equation
is
0,040
>
and thus the equivalent equation for any other form of curve
having a form factor "/" may be written
V= 0,040/r'co M."
"
"
peaked curves have high form factors
curves have low "form factors" when the
and
terms
"flat"
"
"
"Alternating-current,
32
a sine
a sine-wave curve
assuming
1,11).
The
effect of
be
will actually
peaked
involving the use of the form factor, that the flux will be
"
"
of the pressure
decreased in proportion to the
peakedness
curve and consequently the core loss will also be decreased.
If the transformer is designed for a high saturation of the core
may be
quite considerable
if
the transformer
is
however,
is
very necessary
when
is flat,
in
(in cases
where there
is
is
less
factor into
at present
tions
is
of the
particular
DIMENSIONS OF A TRANSFORMER
particulars of the design at which
the formula
V
we have
we have already
0,0444
<*>
33
arrived, to
5000
Solving for
M, we
= 0,0444
3100
50
AT.
to
the
to
grade
of
laminations
which
will
be
employed in
market by various manufacturers, brands of material for transformer cores which are greatly superior to the brands formerly
employed. It is true that the price of this material, which may
be termed " alloyed steel," is relatively high, being at present
some
30 per ton as against some d13 per ton for the lesssuitable material formerly employed.
minimum
The
difference in this respect is not very pronounced.
saturation curve in Fig. 10 is based on sufficiently conservative permeability values to allow for reasonable deviations
from normal good quality.
shows
the
distinctly higher
standard
curve in
by no means exceptional
samples but in bulk, which
It is
permeability than
Fig. 10, but it is
is
indicated by
unwise
to base
tions
accompanied by disproportionate
ability.
To
variations
in the
perme-
the case
34
with manufacturers of dynamos and motors, since high permeability is of much less importance in the case of transformers
owing
to the relatively
usually worked.
/O
/$
/impere Turns
FIG.
10.
20
tier
55
circuits of very
30
35-
low
40
Cm of LengCn of (/ore
steel.
carefully specified
1
Methods
length
in
for
to its permeability.
Chapter
are as applicable to
material
DIMENSIONS OF A TRANSFORMER
It is in the matter of the loss
care
35
accompanying reversals of
must be exercised in the
8
*t
t 5
\
4.
* 3
(dOOO
[FIG. 11.
dOOO
/OOOO
/-ZCOO
/-4000
Hysteresis loss curve? for various periodicities for old high loss
sheet iron.
9
'
8
7
^
I *
4-
2
/
6OOO
FIG.
12.
/OOOO
&OOO
/4OOO
This loss
is
it
D2
36
the
"
In
fact, it is
FIG.
13.
Eddy
component
principally in virtue
22
FIG.
14.
Eddy
microhms per
centimeter
cube,
whereas
in
the
new
DIMENSIONS OF A TRANSFORMER
alleged steel this
centimeter cube,
is
and,
45 microhms per
instances, to even higher
increased to
usually
in
37
some
I
/-40OO
FIG. 15.
FIG. 16.
values.
Total loss curves for various periodicities for old high loss
sheet iron.
Total loss curves for various periodicities for low loss alloy
in the hysteresis
component
be seen by comparing
the
it
is true,
of the
curves in
also
steel.
been effected
may
38
DIMENSIONS OF A TRANSFORMER
this decrease is small
39
in
Fig.
new
may be
total
core
loss
component
older
The
in the
variety as
dotted lines in
component repro-
interesting to note
in the case of the new material,
it
is
is,
at
curves in Figs. 17 and 18, where the hysteresis and eddy losses
are, both for the old and for the new material, plotted as per-
The magnetic
in
densities
conforming with
Table 2.
present-day
standards
are
set
forth
in
40
TABLE
IN
3.
TRANSFORMERS.
For
3, will
Some
line of standard
designers
of
more iron
increased losses
1
may
unit
of weight,
but the
loss per
be
used
DIMENSIONS OF A TRANSFORMER
41
linear dimensions.
If,
therefore, the
This
quantity of
oil
air-blast transformers
cooled transformers.
The reason
Chapter X.
From Table
2,
we
20-kw transformer we
M = 0,730
Consequently the
megaline.
net cross-section of iron required in the magnetic circuit is
flux
works out at
730 000
The
the core.
It
is,
some insulation
to
42
due to insulation
it is
is less
of oxide or of varnish,
and
is
The paper
be reduced to powder under the influence of the
alternate heating and cooling of the core.
In some cases of
core plate
is
It
losses.
The
thickness of the
it is
my
employing a
less thickness
than 0,50
mm
in fact, I should be
0,025
mm
DIMENSIONS OF A TRANSFORMER
the deductions which must be
occupied by insulation
employed are as
when
set forth in
made on account
43
of the space
Table
4.
The
values
for
core plates as
representative values
when oxide
given
in
Table
4,
as also
tion are employed, are plotted in the three curves of Fig. 19.
When
Consequently we shall be
length
(An)
The
net core
length (A$).
core plate, the greater will be the percentage which the skin
of inferior magnetic quality bears to the total thickness of
it is well-known that the permeability is
lower
the
less
the thickness of the core plate, for any
usually
Furthermore the costs of the laminagiven grade of material.
tions themselves, and the outlay for the labour attending their
The most
assembly, increase with decreasing thickness.
usual thicknesses of laminations used in transformer manufacture vary between 0,35
mm
and 0,50
mm,
the latter or
44
even
still
modern alloyed
quite appropriate
with
steel.
42
FIG.
it
is
DIMENSIONS OF A TRANSFORMER
45
left bare).
plates in varnish
'onq
FIGS. 20 and 21.
Types
shall
mm thickness, and
0,50
46
the core.
In order, therefore,
must be
70,0 sq cm.
Cruciform
FIGS. 22 to 25.
The
Types
FIG. 26.
Some
coil.
have been used, and some of which are still in common use,
are indicated in Figs, 20 to 26.
Figs. 20 and 21 show the
square- and oblong-sectioned cores with similarly-shaped coils
DIMENSIONS OF A TEANSFORMEB
47
Id
/O
2O 30 JO 30 60 70 80
///
FIG. 27.
Curves showing the relation between the output and the width
of
type
is
winding space.
is
used, whereas the polygonal (Fig. 23), cruciform (Fig. 24) and an
"
"
extension of the cruciform which may be termed the stepped
48
secure
maximum
good provision
widths of the
for
The polygonal
many different
measuring 7,0
FIG. 28.
cm wide by
10,0
cm
deep.
In transformers of
values for the gross width of the winding space, i.e., the width
of the window, for various outputs and periodicities.
These
curves
may be used
means intended
On
the contrary,
it
is
by no
adhered to
It is
often necessary to
reasonable
window
of
DIMENSIONS OF A TKANSFOKMER
We
now have
all
49
The
section is
shown
in Fig. 28.
In
The reader
These mean
off.
cm
respectively.
FIG. 29.
to lay
down
rules to
primary winding
will
will
instance
former
is
as will be seen a few pages later, the transloss (at full load) in
proportioned for the same
is that,
PR
necessary to operate
S.T.
it
at a
mean
is
turn,
50
the greater
many
amount
turns and
many
layers.
greater than that through the secondary coil. The first reason
is that in this particular example the plan has been followed
of having the full-load loss in the primary coil equal to the fullload loss in the secondary coil.
The second reason relates to
is
fundamental, but
as to the
first
Had
been
more
transformer.
is
the
As applied
to
commonest form
a
shown
in plan
that
it
core-type
for this
t}
pe of
transformer,
it
is
medium,
To
it is
DIMENSIONS OF A TRANSFORMER
51
the
case
FIG.
will
30.
if
the
Simple concentric
winding.
FIG.
31.
Triple concentric
winding.
is
E2
52
wound
FIG. 32.
ment
It also affords
coils.
of
maximum
Sandwich winding.
damaged
studied out,
it will
coils.
On
"
have a low space factor."
shown a simple concentric winding with subThe arrangements shown in Figs. 32 and 33
divided primary.
In Fig. 33
is
DIMENSIONS OF A TRANSFORMER
53
Thus
if,
full
length
had consisted of a
the end turns of adjacent layers would have been eight times
as
great,
is
to
If of
full load of unity power factor.
amount we arrange that some 1,8 per cent, shall constitute
the I II drop at rated load, then the coils can be so designed
this
that the inductive drop will, for a load of unity power factor,
not increase the total drop at rated load to over the stipulated
The calculation of the inductive component of
2,0 per cent.
the total drop
is
It is often desir-
transformers, as
numbers of them
it
is
in parallel
will
same
in all of
Then
all cases.
the
X
primary winding
in
the secondary winding to
5000 =) 45,0 volts, and that
The primary and secondary
(0,009 X 200 =) 1,80 volts.
currents at full-load are respectively 4,12 and 100 amperes.
pressure drop in the
The
will
must
amount
to (0,009
therefore be equal to
ftO
if = 0,018 ol,.
The
total length
53
=)
54
164 000
0,0000020
cm
10,9
40
=)
total
the
length of
secondary conductor
is
must equal
4960 X 0,0000020
__
0,018
The
4 12
n
U,UoU
'
cm
The
secondary windings.
It will be observed that in our example we have adopted a
method by which the current density has been deduced. There
are innumerable alternative
set of
Thus
it
is
useful to have at
As
matter of
different current
fact, however, widely
in
be
ed
may
emplo}
equally good designs, since, as
we shall see later, the heating of an oil transformer is mainly a
densities
DIMENSIONS OF A TRANSFORMER
55
upon
But
for
the
TABLE
IN
5.
BATED LOADS.
We
primary winding we
shall
mm.
Consequently
for the
j
Since
4 x 3,0
3,14
1,96
mm.
to
employ
56
DIMENSIONS OF A TBANSFOEMEE
57
mm.
is
1,96
mm,
be made up
of flat strips of a suitable section, the precise dimensions of
which, however, can only be definitely and conveniently deter-
will
be 2,11
will
>
mined
3100
Primary copper
124
...
...
Secondary copper
Total section of primary and
This
total
section
winding space or
"
93
...
secondary copper
X
X
0,030
0,545
+ 67,5
= 93,0 sqcm.
= 67,5 sqcm.
160,5 sq cm.
total
as the
"
core, the type of winding, and with the pressure for which the
coils are
wound.
may
be
in Figs.
the window, as
shown
wound
in Fig. 29,
close
on
up against the
core, inside
58
This duct
coil.
the
is
included in
leads to
From
a
Fig. 34
we
find that
space
may
jare
This value
dealing.
afford
sufficient
obtaining
the
guide
total
will
to
cross-
area
will
161
0,37
435 sq cm.
We
to be about 8,5
space
may be
435
estimated at
ol cm.
8,5
FIG. 36.
The
core as thus
upon
is
determined
drawn
in Fig. 36.
CHAPTER
III
WE
The amount
the 20-kw transformer which we are designing.
of the core loss is an all-important feature of the design of a
transformer, and
it
is
is
feature.
The mean
length of the magnetic path may be readily calculated or scaled oif from a drawing such as that in Fig. 36
dimensions of the core. In our example
(p. 58), showing the
the
mean
length amounts to
The
(51
8,5)
4X7 =
147
1
-
volume of the
steel is
63,6
One cu cm
147
9350 cu cm.
0,0078
We
are
now
9350
73,0 kg.
60
and
periodicities.
2,6
78,0
190 watts,
term
to
which the
(or
energy ") efficiency may he applied. If, as
be the case for smalttransformers supplying lighting
The
a satisfactory
annual
will usually
,or
is
i.e.,
loss will
amount
to
former
that
it
cent,
is
will
of that time.
factor to be
In other words,
20 per cent.
Of course
let
load and no load are the two extreme conditions, and the trans-
former
the hours go b}r carry loads of widely varybut it simplifies the calculation and introduces
will, as
ing amounts
no unreasonable inaccuracy
;
on the
basis of these two definite loads, no load and full load, for
Thus
the
=) 360 watts
loss amounts to
20 000
PR
8750
4-UUU
;2
360
in the
At rated
loss of
transformer windings.
8750 * )2Q
lUuu
20 000
annum amounts
= 35
61
to
000 kw hr
and the input amounts to the sum of the output, the core loss
and the I 2 R losses per annum. Thus the input per annum
is
made up
of
Core loss
Copper
...
.V;
loss
hr.
630
35 000
Output
Total input...
The "annual"
efficiency) is
1660 kw.
...
...
.:'.
. ..
efficiency
...
(or,
37 290
the
preferably,
"energy"
consequently equal to
35 000
100
~-
9B 9 Per Cent
'
.8X290
'
Now
190 watts), let us in Transformer B precisely reverse these values and proportion it for
a copper loss at rated load of only 190 watts and for a core loss
cent, of the rated output
of 360 watts.
While
(i.e.,
-to
it will
conse-
surface in
62
"
Let us now study the " annual
The
I 2 B, loss per
320 kw
The
annum
efficiency of
190
is
equal to
hr.
/360
annum
is
equal to
{
kw
Transformer B.
8750 X 0,2
1000
X 8750
1000
3150
hr.
/8750
is
equal to
35 000
Thus
kw
20 000 _
annum is made up
Core loss
Copper
Output
loss
Annual"
330
.35000
(or
of:
3150 kw hr
Total input
We
hr.
"
0,20
1000
"energy")
38 480
efficiency
91 per cent.
have assumed, however, that the load factor on the transis 20 per cent.
If similar calculations are made for
former
TABLE
6.
"ANNUAL"
(OR
two transformers we
it
some 3 per
cent.,
of 20
and
Transformers
and
is
increased
to
68
is
is
It is
100
48
3Z
Load
-
Ourre
64
factor
30
/n.
Transformer
/7
\C6re,
1
Hfatts
/3^?
Core
FIG. 37.
Annual
efficiencies of
factors.
Let us continue the comparison between the two transformers from a basis of the cost of these different losses.
the assumption that the
cost
amounts
to 2d. per
electricity
kw hr
On
64
20 per
to only
311, as
assumption
annum
with Transformer
amounts
against
kw
hr
is
is
This
be variable.
cost per
kw
however,
let
kw
copper and the core losses. In fact, the circumstance that the
core loss at no load is associated with a very low power factor,
largely or fully offset the advantage that it represents a load
of 100 per cent, load factor.
Suppose that with both trans-
may
35 OOP
3 _
240
If Transformer
A is
is
The
stated, appropriately be
"
annual
"
efficiency
may, as already
efficiency, as it
is usually
This usual conception may appropriately
applied.
be termed the " power " efficiency.
Let us at this point bring together, as in Table 7 /the data
designated
and B.
we have
7.
65
8.
PEOFITS OBTAINED BY ELECTEICITY SUPPLY COMPANY AT
VAEIOUS LOAD FACTOES, AND FOE TEANSFOEMEES A AND B.
66
The
will
results in
/&
*4Q
32.
Load
^
64-
factor
^
Profit to electricity supply
Coffer
Loss /SO
company
&6
/n fercenb
/ransformer
FIG. 38.
QO
should not be designed for a still lower core loss than 190 watts.
Any considerable reduction in the core loss below the value
67
loss.
may be said, however, that (even with no limitation as
regards outlay for material) no very radical improvement can
be obtained with the grades of material at present available.
It
The
may
be
made
clear.
With
the
section of conductor
(or
is
necessary.
the time
ings, the
it is
The
mean
quite as great an extent as the watts per kilogram in the iron have
been decreased by lowering the saturation. Thus no considerable decrease in the core loss can be effected. Slight modification
may, it is true, be effected by a wider and shorter winding
space, as also by alteration in the cross-section of the magnetic
circuit,
and
it is
in obtaining the
most
suitable proportions in
these various respects that the designer's skill m-ay be disIt requires, however, not so much skill, as patient
played.
perseverance and trained instinct. It is a very tedious process
to
the temptation to
and
it
CHAPTER
IV
WHEN
when
the transformer
unloaded) there
is
is
open
(i.e.,
a certain current
is
is
Mean
magnetomotive
specific
of length
= 6,0
force
of magnetic
in
ampere
circuit
(from
p. 58)
.=
147 cm.
Total magnetomotive force required to send the flux round
(6,0 X 147 =) 890 ats.
turns.
Consequently,
=
The
0,286 ampere.
^~ =
||
at
0,202 ampere.
is
sinusoidal in form.
ETC.
69
Thus
loss, in watts,
to be
1QO
These
the
two
and
the
compocore-loss
are in quad-
component,
with
rature
0,038 ampere.
components,
magnetising
nent
one another
component (0,203
ampere),
the core-
loss
component (0,038
C is the
ampere), and
resultant
components, and
the
"
no-load
"
is
The power
FIG.
termed
current.
\/0,203
two
these
of
factor,
X
G,
39.
In this case
2
0,038'
is
amounts
to
0/205 ampere.
to the resultant or
component
no load, equal
to
0,038
0,205
It
may
when
is
is
ampere.
i.e.,
The
"
In a chapter entitled " Inductance in my little treatise " Electricity "
to
I
endeavour
(Constable, London, 1910),
explain the subjects of reactance and
impedance in a way which I conceive should be helpful to the practical engineer
who is disinclined towards mathematical methods.
1
70
reactance
in
ohms
is
=
The
reactance
is,
is
equal to
24,700 ohms.
IT
oo
l}
where
is
24 700
2^<V^O =
also have
~-
A/2
becomes equal
to
0,73
0,286
2,55 megalines.
may be found
I
We
as follows
have seen
factor,
G,
3100
-
2 550 000
-
~TO
79 henrys.
the value
G =
The power
0,185.
former increases.
is
at
(i.e.,
the
current
is
this
into
the
primary
will
it.
:
1,
be
25
This
>40 ampere.
is in
ETC.
71
The
0,438 ampere.
is
equal to
A/0,203
Consequently,
have
Similarly,
the
for
when
0,438
0,484 ampere.
power factor
the
at
one-tenth
energy component
of the
load
we
primary
is
equal to
VO,203
1,00
1,02 ampere
The
power
results of
these
factor at first
similar calculations,
energy component
power
may
factors
for
40 may be
plotted.
When
the secondary
The
in Table 9.
former
is
In the
given.
first
The
may
be obtained as shown
third
loss,
72
which, of course,
third
is
loss,
The
sum
of the
/00\
Zoad on Ts&nsfor/ner
FIG.
40.
TABLE
9.
for a
i.e.,
the
where
ETC.
73
and the
74
Table 10 the
loss of
TABLE
10.
of
laminations the
core can
same core
be worked
at
much
higher flux
grades available three or four }*ears ago. But when the core is
worked at high densities, the no-load current is considerably
Fig. 43, in which the upper
curve represents the percentage no-load current for a line of
increased.
This
is illustrated in
The
core
for designs
is
is
smaller rated outputs for the modern designs, since the low
power factors at light loads would constitute a distinctly
undesirable feature from the supply company's standpoint.
ETC.
75
same manufacturing
employed. It will be observed that for the
Curves showing the relation between the no-load current and the
rated output for transformers having (A) high grade and (B) ordinary
grade laminations.
FIG. 43.
is
This
is
circuits of periodicities
As
rule,
however,
25-cycle
circuit
requires
new
76
if
5?
f'a
V
<Q
.a
bfl
if
^k
>o
'^
|*
$
-
density
the
is
core
already high
would,
at
sso j
U0JJ-
ETC.
77
78
The
upon
influence
of the
By
in Fig. 45.
periodicity
100 cycles the core loss has been decreased from 190 watts to
125 watts, but by decreasing the periodicity to 40 cycles the
core loss has been increased to 240 watts.
The variations in
the no-load current, due to various periodicities, is still more
striking.
Fig. 46 shows the influence of supplying different
pressures to the primary terminals^ upon the core loss and the
no-load current.
is
turns
in another case
may
it is
flux, or it
may be
obtained
practice
as
relates
cost,
these
Of
quantities.
course,
the
total
this
designer's object
works
to
minimum
is to
point of view.
79
a very
occurrence (attributable to poor administration) that
common
ETC.
account.
it
is
the establishment charges mount up to a very formidable percentage of the total works cost, whereas in a very small concern
these charges are often kept down to a small percentage by the
exercise of strenuous oversight.
While
it
might
at first glance
80
on account
of the
show that
sented by establishment
AX)
"
FIG. 48.
reduction
in
the
total
corresponding
it
appear
ETC.
81
can go further
Some
shown
in Fig.
48
for
is
The
cost of
But
important to
consider the cost of the material in a transformer as made
up
plotted.
it is
of:
I.
II.
Core.
Copper.
IV.
Oil.
V. Case.
S.T.
etc.).
CHAPTER V
THE DESIGN OF THE WINDINGS AND INSULATION
in detail.
An
FlG. 49.
and insulation
The secondary
83
wound the
coils are
We
cores.
FlG. 50.
posed of four
6,8
The
flat
which
strips, each,
when
mm
mm.
2,0
6,8
54,5 sq
mm,
G2
84
Turns
'^Component Coil
\
Jj
6 ^.BareDia
*>^.lnsul.
51
for a
85
0,75
=)
46,5
cm
of the 51
cm
winding space.
"
window
(i.e.,
the
space
represented by the
as too valuable
")
winding
to be devoted to this purpose, since the values of the core loss
efficient
utilisation of the
much more
secondary coils are held at this distance from the core by wooden
corner strips, and the laminations are left bare with a view to
more
efficient
oil.
The
coils
ment which
It is an instance of an arrange-
26412 of
mm. Any of
suitably built
up
1897.
The
my
British
insulation between
the
when
000
virtual
when
suitable insulations
With
under
86
certain
On
circumstances.
the
whole,
the
progress
at
is
making
practicable to
it
work with
/OOOO
^8000
4OOO
2000
/n
FIG. 52.
M/ ///meters
less thicknesses
Fig. 52.
is
and
51.
Each
coil is
wound
in
87
nine layers with the numbers of turns per layer set forth in
Fig. 50 shows in considerable detail the
Figs. 50 and 51.
general arrangement of one primary
volts are thus divided
up
5552
o
is
coil.
into
coil,
70
volts per
volts.
Had
a smaller
number
to
insulation
between the
CHAPTER
VI
p.
78 that transformers
been designed.
For
lowered.
higher.
circuits
decrease in the core loss, but the higher flux density produces
an increase in the core loss which more than suffices to offset
is
loss.
Column C
of the
designing.
same
table con-
that
of the
much
11.
89
200-voi/r,
90
TABLE
continued.
11
91
continued.
Figs.
upon the
shown
in
clearly the
relative proportions of
the transformer.
TABLE
12.
SHOWING THE INFLUENCE OF THE PERIODICITY UPON THE
CORE Loss, WEIGHTS, ETC., OF 20-KvA TRANSFORMERS.
same I 2
92
CHAPTER
VII
OUR
If a pressure
25.
if
is on open
but unloaded, then
transformer
is in circuit
200 volts.
'-sjr
an impedance, then current will flow from the secondary winding into this external secondary circuit and the pressure at the
secondary terminals will decrease below 200 volts (except in
the unusual case that the current flowing into the external
1
The percentage by which the
secondary circuit is leading).
tion
is
196
said to be
20
(
196
100
=)
The
fall
and the
transformer
is
delivering
its
transformer
mean
that
is,
say,
when the
For a given transformer there will, for any given value of the secondary
some particular angle of lead above which the terminal pressure will
be greater when this current flows than on open circuit.
1
current, be
94
circuit
(G
The drop
in pressure is
than at no load.
(1)
the resistance
another,
the
The
are intermixed
second component
FIG. 56.
in core-type transformer.
i.e.,
it
is
main magnetic
In Fig. 56 the
the
coil
secondary
current in
is
delivering electricity to
an external
circuit, the
95
FIG. 57.
96
effective
is
much
Moreover by having
reduced.
and 55, on
p.
wound
and
when
this
arrangement
is
in
narrow winding space to the other, is very low, and this in itself
tends to low magnetic reluctance of the leakage pjath between
the primary and secondary windings.
Other things being equal, the inductance will obviously be
less the higher the magnetic density employed in the core, for
97
wound
3000 primary
for
ratio of transformation is
at its
load
rated
00 000
of
volts
T^TT
100 kw,
15.
is
(for
Its
volts.
The
secondary current,
unity
power-factor)
=)
(1
circuited through an
primary
short-circuited.
is
500 amperes.
ammeter, and
if
the
pressure
at
the
"
be said to be
may
current
is
\-=-g
=J
33,3 amperes.
=-5
v^
00,0
=1/
3,3 ohms.
The impedance
is
ohm and
0,0020
ohm
respectively.
It is
convenient at
formation.
of the
ohm
as
little treatise
S.T.
98
of the
now be
15 2
0,0020
0,45 ohm.
say that
equal to
it is
0,60 + 0,45
1,05 ohm.
"
"
The resistance drop in this transformer, when the input
is
33,3 amperes,
X 33,3
1,05
The 100
volts
35 volts.
is
calculated.
and
is
made up
of two components.
"
the "resistance drop
of 35 volts, which
short-circuited, is
nent
is
The
other component
is
94
"
the
reactance drop,"
equal to
VlOO 2
35 2
volts.
35
100
The
resistance drop
x
is
is
is
10
3- 1
p fir cent
primary
varies
and with
different
99
The method
results
is
based
=/-U /\
v
f=
oil
rated load.
I)
=
=
>
on
own
may
be found useful in
for /.
values
obtaining
shallow coils and a narrow winding window.
coils
on
come
p. 83).
quite close
up
volts),
to
one another
(as
It is
shown
/=
0,080.
turns,
"
a,"
Consequently for
value of the primary ampere-turns, we have
is
in Fig. 50,
for only
4,12
amperes.
4,12
3100
at rated
the virtual
12800.
H2
100
The
The
sq cm.
obtain
Substituting
these
values
the
in
formula,
12800
0,080
>1
11,5
we
1J5
'
0.2Z
O.t
Q2.
0*
O.J
.0.5
0.6
FIG. 58.
Curve of values
for
drop
= /
We
is
equal to 1,80
Eesistance drop
101
1 ratio of
//5
FIG. 59.
R drop
of
15 per cent.
100
volts.
at full load
be 15 per cent,
in order
it
would be
If,
102
FIG-. 60.
/R
FIG. 61.
drop.
Power
factor
unity.
cent.
in order that
<J>
we may,
secondary terminals
in
100 volts
at full load.
fall
from 119
volts at
at the
no load
Fig. 61
in
103
the
secondary terminal
/$
of 100 volts.
pressure
The current lags behind
the
pressure
Since cos 30
by 30.
0,886,
the secondary
(G
is
0,886
The
0,886).
C E
vector
the
from
supplied
direction
indicates
of
the
secondary terminal
In Figs. 59
pressure.
and 60 the single vector
C B
represented
the
terminal
secondary current
which was in phase with
the
pressure.
CD
of
FiG. 62.
is
C E representing the
90
D, which has
the vector
pressure
in phase
The resistance
current.
by a vector
The primary
is
IR
440.
is
CE
reprerepresented in
104
maximum
corresponding to the
drop.
# = 90.
Angle of lag
Cos $
0.
pressure
drop.
is
resistance drop,
BE :C E = C D
:AD.
105
90
lag.
curves
J'
Iv 30
s*
25
20
/5
/O
Q3 Q4- Q5 Q6 Q? O,8 Q9
foner factor of &econd#ry Load
O,Z
2Q
/O
&eg.
FIG.
65.
/<ag
3O 4O
JO
/,O
70 GO &0
Behind
Current
o/ >eccnd#ry,
&>
drop
is
reaches a
first
It is
seen
maximum and
then decreases.
106
secondary pressure at
it
increases.
FIG.
66.
107
D
diagram devised by Kapp )
and are respectively proportional to 87,6 and 90,0. With A
as a centre, and a radius proportional to 5000 (the constant
l
drawn
is
Radiating from
drawn.
The
CB C
,
BIO,
The
and
volts,
may be
found by dividing these results by 25, the ratio of transformaIt is seen from the diagram
tion of the actual transformer.
that the regulation lies between 1,70 per cent, and 2,56 per
cent, according to the
circuit
The
graphical
method
impracticable.
If,
however,
that
it
A D
C B 2o,
and
DC
BIO,
etc.,
The method
will
"
"
p. 174,
108
nearly parallel to
dropped from
is
67) a perpendicular
Ew
then
EIQ
will
BIQ,
i.e.)
at a
90
FlG.
67.
A BIQ
is
10 with
drawn
BQ.
parallel to
line
is
angle of lag of
drawn perpendicular_to
A BIQ.
thus obtain
EIQ,
The drop
and C.
EIQ,
A E2o,
0.4
0,3
Q5
factor of
FIG. 68.
lies
It will at
upon the
A C
be repre-
Q6
(i.e.,
midway between
equal to
109
Com-
C,J
xter/w
and 0,95
The
obtained respectively
from Figs. 66 and 67 are compared in the curves in Fig. 68,
the broken line curve representing the results obtained from
inaccuracy
is
very small.
results
Fig. 67, and the full line curve the original results obtained
by means of Fig. 66. The inaccuracy introduced by Fig. 67
will
be smaller
the
and
the
110
REGULATION
TRANSFORMERS
OF
FOR
THREE-WIRE
SECONDARY CIRCUITS
The majority
wound over
is
coils
secondary
coils.
secondary
circuit,
When
is
groups of secondary
pressure.
At
it
coils,
first sight,
way
of connecting a
and
the secondary coils on the other leg for the other side of the
three-wire circuit.
With
loaded
it
is
the pressure of the side on which the greater load exists being
below normal, while the pressure of the lightly loaded side will
That
111
and
together
intermixed.
therefore, the
pressure
on
If,
one
side of the
three-wire system is
provided by a secondary coil on
leg,
if
only one of
will
be a large
wound
secondary
on
69.
Arrangement of coils
in core-type transformer for
three- wire secondary.
whose
For full load on one
that leg
unloaded.
is
FlG.
side
much
and no
may
easily
rise of as
as 25 per
cent,
on the
in the pressure
on
the
pressure
loaded side,
the
making
unloaded
exceed
loaded
first
side greatly
on
that
pointed
S.
out and
by
investigated
W.
Moody.
inequality in the
netic
leakage
(originally
halves
the
This was
side.
Mr.
The
mag-
may
be prevented by
suggested by Mr.
of the
adopting
Moody) which
connections
distribute both
112
S may
3fS
and S% and $3
side.
Where
is
Arrangement
of
coils
aries
as
shown
in
becomes practicable
Fig. 71,
to
it
remedy
i.e.,
CHAPTER
VIII
ALTHOUGH
owing
from moving parts, the
problem of limiting the temperature rise is one of considerable
to the absence of
difficulty.
The
any ventilating
difficulties
effects
demand
for transformers
was confined
problem
arisen except for the fact that the material employed for the
magnetic circuit was at that time very poor and the losses in
were high. If the active material in a transformer only
it
amounts
to
surface per
will
it
oil
and
its
contents by the
immersed in the
oil.
number
of small coils,
and cooling
mm.
114
FIG. 72.
Air-cooled transformer.
115
and iron
is
halved by
transformer.
in the ribs,
efficiency of the
5,5-kw transformer
cent.
OlL-lMMERSED TRANSFORMERS
The
means of
former in a tank of
oil.
If the case
is
filled
with
oil
and
if
i2
116
keeping the
oil
clean,
and
free
oil.
That
16
JO
20
JO
40
SO
/fated Output n
FIG. 73.
there can
still
work
is
now almost
universally admitted.
117
Centigrade
60,
i
Af \rcn cere
50
40
30
10
23
78
IO
12
15
14
16
15
Houro
FIG.
74.
The curve
in Fig. 73 gives a
transformer.
to
118
In Vol. 38 of
FIG.
75.
The curves
74
relate to a
The
Epstein
he
his
119
and 66 per
and
As
regards the
oil
transformer
to
The lower
the thermometer
"
r
4fI
10
FIG. 76.
Heating curves of oil transformer. (See Fig. 77, for key to positions
of thermometers for curves A, B, C, and D.)
The diagram
76.
Prof.
"As
to
warmed
oil rises
temperature
first,
beginning of the
test, as
there
is
no
120
about
five
Immediately
up.
It takes prac-
oil at
heated
is
fill
it is
^\
effects, viz.,
whole volume.
The
by
complicated
of the oil-
case
transformer experiment
is
somewhat
motion
the
of
the
oil."
of
Peck had
comments
have made a large number of
" I
which had a
smooth one.
The temperature
It is well known
it
hump
in
it
at the
end of
should be a perfectly
that wide differences in tem-
curve
but I have
Fig. 76.
four hours.
seems remarkable to
oil levels,
me
as
shown
in the
same case
filled
same
with
oil.
much
FIG.
78.
121
Curve
7~ime in
"
FIG. 79.
R
13
Jn
Ar
T XX /
^/7 C///
air
and in
oil.
in case
122
Curre,
FIG. 80.
Iii
rise of
oil.
tempera-
ture rise in air, the rise after eight hours in air and the rise
in oil, for a line of oil-immersed transformers comprising
curves
the
those
are
of
the
windings as
123
plotted in
determined
by
In the
when run
A)
the results of the eight-hour tests (curve B), since the ultimate
temperatures would have been so high as to injure the
insulation.
The
and
oil
operation
is
FIG.
81.
C. at
various loads.
The
hours
loads
40
that
the transformer
its
rated
load for
rise
its
of
tem-
The
is
to
124
to 45
shall
It
oil,
to
stipulate
that the
more than 50
of
August, 1907, contains (on pp. 13 and 14) the following clauses
dealing with the temperature rise of transformers
:
"
(vn.) For alternating- current transformers, whether oil-cooled or
otherwise, in which cotton, paper and its preparations, linen, micanite,
or similar insulating materials are employed, 80 C. shall be the highest
mean temperature
"
permissible.
shall be run
They
ascertained
by
rise in
electrical
resistance, in
The
lighting loads
transformers supplying
125
In this instance
after the period corresponding to the term of full load.
the test load should not be applied until the transformer has been in
time to attain the temperature-elevation due to
for commercial lighting, the duration of
may be taken as three hours, unless otherwise
core loss.
the
With transformers
full-load
test
specified."
known
it is definitely
continuously, will
maximum
reasonable
temperature-rise,
say
40.
But commendable
their designs
will,
upon
to
carry the rated load for periods of more than a very few hours
These firms may designate as of 20 kw rated capacity
each.
a transformer which will be decidedly smaller than another
purchaser or his adviser to decide whether a certain transformer will suffice for some particular conditions of service.
When
of 20
kw
capacity he
is
undertaking (unless
it
is
otherwise
expressly specified) that the transformer will carry 20 kw continuously without exceeding a temperature rise of 40 or 45
126
15-kw or
12-kw transformer
even a
will
suffice
his
for
manufacturer.
Thus
reputation at stake
their
maximum
under what
to
to
go
ridiculous limit.
running
may
the
writer is
result
and safer
mechanical restraint
if
is
imposed upon
it,
as ageing
may
occur
for
at the
same time
is
subject to
C.
mechanical
stresses.
" There
appears to be a very considerable difference of opinion
To
as to what temperature may be permitted in a transformer.
begin with, this limit of temperature should depend upon the
class of insulation employed.
With
oil-varnishes,
and insula-
wherever
oil is
of his
own design
The
at temperatures as
127
in
C. rise
is
detrimental to
insula-
tions with mica as a basis are very often capable of resisting far
ing the
five
article is
situation.
" The
The
Effect of Temperature on Insulating Materials :
Engineering Standards Committee recently issued Report
No. 22 entitled,
Report 011 the Effect of Temperature on
'
March
9th,
"
practical tests,
made with
such investigations, it is
believed that the data published in this report will be widely
consulted, and with advantage to the industry. It is, however
should obtain in
128
many
still
so little apprecia-
tests
the
Even
latter
in
consequence
of the
charring
scales of the
of
the
mica were
cemented together.
"This experience with high temperatures further demonstrates
the wisdom of not at present exceeding the customary temperature standards.
If a thermometrically-determined temperature
increase of 40 C.
is
mean an
resistance measurements.
The
129
apparatus in which
sound materials and of keeping within as conservative temperature limits as the competitive struggle will permit.
"
as low as ever,
benefit, since
" The
temperature limit should be raised by small amounts
from year to year, keeping pace with the gradual progress made
in the development of improved insulating materials.
It will
met by
1
1
As further bearing upon this important subject of combating the tendency
to permit higher temperatures, I propose to quote Mr. E. G. Reed, who, in an
important paper on Transformers, read at the 32nd Annual Convention of
the National
follows
Electric
180
mended.
Not only
insulation
is liable
The
ture.
is
rise.
The
rise.
high temperature
A
rise
TABLE
13.
Low TEMPERATURE-
RISE TRANSFORMERS.
the case.
maximum
131
estimated from the basis of the loss per unit of external radiating
surface of the transformer case.
Thus we require to know the
rate of generation of heat in the transformer per square
by the
total
The
specific
temperature rise
is
external surface of the case, and since this quantity has a fairly
For
ture.
temperature
per
example,
rise of
dm
sq
of
temperature rise
The
if
40 C., and
if
the losses
external surface
is
equal to
transformer
certain
of
the
amount
has
to 4 watts
case, the
specific
sq
dm
ultimate rise
per sq
B.
dm
the internal
losses
Hence, for 40
may amount
C.
to 4 watts
of external surface.
With ribbed
iron
cases,
where the
radiating
surface
be some 6
to 7
dm
of external
K2
132
The temperature
taken as the rise above the temperature of the surrounding air when indicated by a thermometer placed in the oil at
the hottest part, which is usually near the top of the core of
cylindrical surface at the root of the ribs.
rise is
the transformer.
These constants
(i.e.,
for
cases
and B)
relate to
the
hours
Hence,
if
But
it is
same
The
same transformer
in the
oil.
is
increased
by the addition of ribs on the exterior of the case is fairly represented by the statement B above. The total external cooling
surface
may
The
numerous
ribs.
however, increased nearly in
cooling capacity
proportion, for the ends of the ribs are so removed from the
surface of the case as to be much less effective.
Consequently
is not,
133
for such proportions the above data will hold fairly true.
In the
heat
is
than
it
The
little
oil to
the case
much more
readily
TABLE
14.
stated.
following considerations
In the first case there
:
perature of
some 6
to
12
may
the resistances of the windings and measurements by thermometers placed in the hottest accessible part of the oil.
This difference
the
ratio
of
is,
the
maximum
temperature of the
for.
oil
Also
in
an
134
the case
may
ing large
amounts of
oil for
cooling
The
purposes.
ratio
mometers placed
The temperature
may
be the case
There
oil.
is
immersed transformers
difference
of very
the
depends upon
transformer in relation to
within which
coils is
it is
and
capacities,
the
the hottest
part
of the
this
When
placed.
large
size
windings, since
that
part
relate to
of
the
it is
more
especially
when they
are
when
calculated by
the
observed
185
is
metric measurements.
more
maximum
temperature in any
more
An
temperature.
and in small
is
rarely sufficient
objection
to the
resistance
method
maximum
method of
measurements
is
the
mean temperature
temperatures
the
mean
temperature.
which the
oil
shall circulate
Both
Figs. 49, 50, 51, 53, 54 and 55, are typical examples.
coils and core are well bathed with the circulating oil.
In the
shell type the coils are less readily cooled
valuable
circular-shell
and 4
is still
The
circular-shell
it is
significant that
it is
the exploiters
136
But
(i.e.,
transformers for 1
it is
minimum
of
material.
transformer in
oil,
the transformer.
comply with
customary heating
specifications
will
run at
needlessly-low current densities, and, except as regards pressure regulation, the rating may be considerably increased
if by any means the temperature rise may be maintained
the transformer
itself,
By
i.e.,
to
fill
on may, by
oil.
leads
Such practice
output,
if
is
kw
of
not to be excessive, or to an
if
7
\
the transformer
it
is
137
would be capable.
//O
138
employed proportions.
ing to
This is accounted
values corresponding to the other curves.
The transformers corresponding to
for by several reasons.
modern alloyed
steel laminations
which render the transformers comparatively small as compared with the older makes to which the other curves in
it is
were run at
full
load for
many
doubtful whether
if
the transformers
and
thus there
is
The transformer
is,
and cost
(for
it
139
oil.
60
nse
9 /O
//
/Z /3
7/7
FIG. 83.
Temperature curves
is
140
practical
be
O>
OJ
a*s
$
<U
'I
propositions,
rise
to
JH
=S
this
As
illustrative of the
141
in Fig. 83
was tested at
full
From
The
The
these figures
it is
The
results
must
be taken as liable to quantitative error, but as strongly confirming the correctness of the principle.
maximum which
occurs
an oil-immersed
in
all
transformer.
is
minimum
at the
bottom of the
case.
8 kw.
The
T3, are
shown
in Fig. 84.
at
T2 and
clearly the
which
the
142
This
because the
former.
is
is
the case
the top after being heated by the transthe body of the transformer which
near
T2, situated
oil rises to
losses,
presents
similar characteristic
<?
7/w^
6
//?
'/
<3
Hours
/O
S>
//
/3
/-f
><?2C
FIG.
85.
C.
8 kw.
curve.
The temperature rises very slowly at first for a connumber of hours, and then more rapidly as the entire
siderable
"
is
placed in the
XXXVIII.,
p. 49.
its
oil
Construction/'
the greater
between
difference
the
143
temperature
rise
The
obtained after a few hours run and the stationary value.
of Fig. 76 (p. 119) refer to the temperaC and
curves A, B,
shown
Fig. 77
The
(p.
in
120).
effect of
These data
single-phase
refer to a 100-kva
5000
The
first
transformer.
to
2000-volt
heating test
60-cycle
was made
with a depth of
that the
oil of
distribution
of temperature
oil,
is
circulation.
TABLE
15.
full load,
must be
144
Ventilation
Ducts.
It
is
the temperature
desirable that
In a modern trans-
maximum
of the
core
type
I usually
prefer the
53,
54,
and
55.
In
this
is
desirable to avoid
undue
local heating, as
oil.
It is
most
this conduces to
CHAPTER
IX
ANY one
of a
may be employed in
The rated output
and the appropriate mehod of
The principal materials
choice.
variety of materials
required
cases.
used are cast iron, galvanised sheet iron, sheet steel, and
For small sizes of transformers cast iron is
boiler iron.
used, both
generally
This
is for
for
several reasons.
air-cooled
The
pattern
will, for
small sizes,
not entail large outlay, and this outlay will be spread over a
iron castings
to cast, in
more
difficult it is
In
fact,
owing
when
For
this reason,
and because
much
cast iron
it is
not practicable to
make any
considerable increase
and
for the
same
146
FIG. 85A.
cannot be greatly increased without also increasing the thickness of its walls, if due regard is given to the mechanical strength
Another objection
is
shown
to the
cracks
is
147
in Figs.
employment of
Thus,
absolutely oil-tight, any flaw renders the case useless.
in the event of requiring prompt delivery of some large transformer, the loss to the manufacturer in paying penalties incident
to delay
may be
considerable
if
L2
148
To overcome
times been
made
in sections,
the
number
is
employed.
Cast iron
iron or boiler iron, and this has been put forward as an argument
in favour of cast-iron cases ; but the difference in this respect
the cost.
siderably
cases
may
be con-
are employed
and
and some 14
On
mm,
accord-
disadvantages associated with the use of cast iron for transformer cases, taken in conjunction with the liability of fracture
it
generally preferable to
149
cases, gal-
Sheet-iron Cases.
which
is
suffice
for
may
case.
this,
is
may be
expensive.
satisfactory
channel
Solder
is
is
An
since this
The
alternative
is,
constitutes a reliable
method
method
joint oil-tight.
especially
when
means
hot
oil-tight,
and the
oil after
150
lower portion of the sides into a mould, into which molten iron
is poured, and which forms the base.
The method has the
that blow-holes
FIG.
86.
Method
and bottom
of a transformer case.
The mechanical
151
be borne entirely by bolts or massive lifting-hooks. If the eyebolts or lifting-hooks are not suitably located, then considerable,
angle-iron
should be
injury
it
when
the sides.
lifted, shall
come
The
entire
weight
is
ditches
mm
the transformer.
BOILER-IKON CASES.
Boiler-iron cases are used principally for large water-cooled
(see Chapter X.), and in
is
where
required, as in portable
special types
great strength
Their advantage lies principally in the fact that
transformers.
they are stronger and more durable and are cheaper than sheetiron cases.
15
mm
and
mm in
thickness are used, with thoroughly caulked singleriveted lap-joints, and the construction provides a very satisfactory
and permanent
The maximum
size for
to be self-cooling is limited
capacity
for
by the
152
FIG. 87.
self-
cooled transformer.
of cooling tubes.
FIG. 88.
Johnson &
Phillips'
vertically,
oil
153
number
and are
immersion.
given a 90-degree bend at the top and bottom where they enter
the case.
The mechanical construction is very strong, and it
is
is practically
154
a leak.
As
and as the
air
among them,
immersed transformers
The Westinghouse
little
attendance.
Electric and
Co.
Fig.
87
is
an
illustration
of
the
design.
Of the
twelve supplied, three are for outdoor service, and nine are
installed indoors.
In Fig. 88
shown, out of its case, a three-phase, selfcooled, oil-immersed, 50-cycle transformer recently designed by
the author for Messrs. Johnson & Phillips, and of which two
is
CHAPTER X
FOKCED-COOLED TRANSFORMERS
WITH
the
FIG.
89.
increased, and
of
an
air-blast transformer.
156
7
t}
FIG-. 90.
Water-Cooled
Oil.
Transformers
and
Forced-Oil-Cooled
Transformers.
Air-Blast Transformers.
view of the
FORCED-COOLED TRANSFORMERS
coils of
157
manufacture,
is
<D
FIG. 91.
<2
Diagrammatic sketch
of
Co.'s air-blast
transformers.
rarely
employed
than 300
kw
capacity.
The
A,
and C
some 12 000
2000
volts,
are,
volts
and
for transformers
for
158
FIG. 92.
FORCED-COOLED TRANSFORMERS
TABLE
159
16.
volts
it is
not desirable to
'//////////////////////////////////,
FIG. 93.
employ
of transformers
and blowers.
for pressures
effective
Air-blast
when
may
be made
much more
transformers are,
as
shown
in
Fig.
93,
usually
installed
in rows, over
air-blast
of the
160
FORCED-COOLED TRANSFORMERS
stitute a three-phase
transforming
set,
heing supplied.
161
amount
for
all
of the load
circulating
the
required amount of air varies considerably in different installations, according to the length and size of the supply duct and
The blower rarely requires
the general arrangements adopted.
(even in small installations) to have a capacity of
1
per cent,
more than
installed,
The
velocity at
which the
air flows
the order of 1 meter per second, and the air pressure at the
some
cm
5 to 6
TABLE
Owing
to the disastrous
17,
162
ment
various
board,
undesirable
Whether due
dampers open.
siderable trouble
left
One
of these transformers.
extent of igniting
its
of
them
was
My own
The manufacturers
Even
amount
interior as
air
will
it
plant,
enabling
air.
considerable pressure
will be of
much
Compressedto
be
directed
assistance in cleaning
air-blast transformers.
is
is
deeply immersed
it,
which water
Such transformers
is
circulated.
appearance
is
are
usually
The general
external
FORCED-COOLED TRANSFORMERS
of the
Pennsylvania
FIG. 95.
163
The
boiler-
former core
is secured.
Fig. 96 is an interior view of a
transformer of the same type, built
by the American General
M2
164
In Fig. 97
96.
View, of the interior of the American General Electric Co.'s 10 000-kva
100 000- volt 60-cycle design for a water-cooled oil-immersed transformer
before the cooling coils have been mounted.
FIG.
This transformer is
for
100 000
FORCED-COOLED TRANSFORMERS
165
FIG. 97.
The
first
may
166
FIG- 98.
large current.
The transformer is
for a
primary pressure of 55
in
000 volts.
FOECED-COOLED TRANSFORMERS
167
FIG. 99.
and large
shall be
current.
shell.
Alternative
from
168
FIG. 99A.
FOKCED-COOLED TKANSFOEMEKS
the cast-iron base are indicated in various
169
of the
designs
The
minimum
water should be of
Brass
of corrosion.
the heat
more
is
effectively abstracted
of the
experience, the
amount
temperature of 15)
(entering at a
1,1
1,5
given as approximately
500-kw transformers
1000-kw
n
,,
,;
is
2000-kw
thermometer
reduce
disadvantageous to
the
oil
temperature
below the
" sweat."
It
will
be
method
of
making
To
/1000
is
100
(Constable
&
Co.,
London).
Heavy
Electrical Engineering,"
170
room
20 we may take (20 -f 30 =) 50 as the temperature of the oil in the immediate neighbourhood of the cooling
the
is
As
pipes.
not be
will
it
medium
external to
up to
the pipes.
Con-
say,
(45
31,3
45.
It will thus
rise of
hour.
5^5
tori
0,447
\ol,o
per
equal to 0,447
per minute.)
If in another instance, a temperature rise of 40 is permitted, if the room temperature is 20, if the water enters
at
15, and
if its final
temperature of the
calculated as follows
oil,
:
Temperature of room
Temperature
rise of oil
..
water
rise of
20
40
.....
Temperature
(20
(60
40
15
(53
(1>16
38
60
=)
15
=)
53
=)
38
=)
44
kelvins
...
hour
Weight
of water per
Volume
Volume
(0,319
.
(44^5
220
(^ =
=)
j
0>319 ton
70 gallons
1,17 gallons
FOKCED-COOLED TKANSFOKMERS
It is
One
second
may
1,17
X 4530
-
or
bO
If
171
we adopt
= 88
cu cm.
00
water, then the area of the pipe
must be ^ou
mm.
The
1,76 sq
cm and
thickness of the
mm
The
is
is
and
is
surface.
mean
difference of temperature
is
60
58
15
26.
^ =
360 sq
dm
66 meters of tubing.
In a paper read before the
or a total length of
[jr*-
=J
This barrier does not extend quite down to the bottom of the
The oil adjacent to the core and windings becomes
case.
172
Transformers.
As
an
alternative
to
FIG. 100.
promote circulation.
coil,
it
is
more
and pump
the
pump
forced into
through C
water which
is
by the
pump F
difference in temperature
between
The
FOKCED-COOLED TRANSFORMERS
173
when
transformer
oil is
its specific
heat
is
about 0,7s. 1
circulated is
220 =) 400
,o
FIG-. 101.
own complete
and cooling
oil-circulating
common
lowest
oil
first
from a
Although the
main.
is to
it is
p. 11
Electrical Engineering
"
(Constable
&
Co.,
p.
London).
oil
entering
it,
13 of the author's
then
"
it
Heavy
174
is
oil shall
While
was given to forcedoil-cooled transformers, and the plan was adopted on several
installations, it has often been found that the extra cost of
for a time, considerable attention
circulates.
proposition affords a
instances.
in
many
WORKS
LIST OF
ON
SCIENCE
ELECTRICAL
D.
A. V.
ABBOTT,
Circuits.
York.
Electrical Transmission
Electrical
of
Design
96
New
Fifth
of
Energy.
Manual
the
Net, $5.00
675 pp
ADDYMAN,
for
Edition,
Practical
T.
F.
X-Ray
Work.
Illustrated.
8vo.,
cloth,
200
Net, $4.00
pp
ALEXANDER,
J.
H.
tice.
ANDERSON, GEO.
Army.
Illustrated.
$3.00
pp
ARNOLD,
ASHE, SYDNEY W.
illustrations.
ASHE,
S.
I.
Vol. II.
Practically Applied.
422
Net, $2.00
cally
Vol.
Electricity
Treated.
J.
D.
Illustrated.
ATKINSON,
..Net, $1.50
Illustrated.
of
Dynamic
Electricity
$2 .00
Ptwar Transmitted by Electricity and Applied by the Electric Motor, includ n<r
Electric Railway Construction.
Illustrated.
Fourth Edition, fully revised
and new matter added. 12mo., cloth, 241 pp
$2 .00
AYRTON, ftERTHA. The Electric Arc. Illus. 8vo., cloth, 479 pp. ... Net,
W. E. Practical Electricity. A Laboratory and Lecture Course.
trated.
BEDELL, FREDERICK.
C. A. Pierce.
00
Illus-
$2 00
.
Illustrated.
$'5
8vo., cloth,
Assisted by
Net, $2 .00
250 pp
&
BEDELL,
C.
BIGGS,
W.
H.
First Principles
of Electricity
and Magnetism.
Illustrated.
$2.00
BONNEY,
BOTTONE,
S.
R.
handbook of
A Manual
enlarged.
$1 .20
the magneto
to
Illustrated.
12mo.,
cloth,
Net, $1 .00
88 pp
How Made
Electric
Motors,
168 pp
BOWKER, WM.
Engineers
Amateurs
for
Fourth Edition,
How
and
Used.
Illustrated.
R.
12mo., cloth,
75 cents
and polyphase
circuits.
pp
alternating,
130 illustrations.
Net, $2 .50
Illustrated.
Net, $5.00
CHILD, CHAS.
cloth, 140
pp
SI -00
CLARK,
D. K.
Illustrated.
COOPER, W.
Second Edition.
7.50
R.
Illustrations.
Electrician Primers.
Being a series of helpful primers on electrical
subjects, for the use of students, pupils, artisans, and general readers.
Three volumes in one. 8 vo., cloth, Net, $5.00
Illustrated.
Second Edition.
The
Vol.
Net, $2 .00
Theory
I.
Vol. II.
and Power
Net, $3.00
Net, $2 .00
Vol. III.
CROCKER,
Vol.
Vol. II.
cloth,
Illustrated.
8vo.,
$3 00
.
Electric Motors:
160 illustrations.
WHEELER,
Illustrated.
$3.00
Sixth Edition.
505 pp
and ARENDT, M.
and
entirely revised.
S. S.
pp
Net, $2.50
The Management
of Electrical Machinery.
"
Being a
232 pp
CUSHING, H.
Illustrated.
DAVIES,
DEL MAR, W.
A.
Electric
Net, $1 .00
Illustrated.
$1 .00
Net, $2 00
.
Power Conductors. 69
illustrations.
Net, $2.00
DINGER,
Lieut. H. C.
Second Edition.
Handbook
DYNAMIC ELECTRICITY;
Its
Illustrated.
in its appli-
EDGCUMBE,
cloth,
ERSKINE-MURRAY,
Practice.
J.
A Handbook
of
of Wireless Telegraphy:
electrical
PP
Illustrated.
engineers,
students,
180 illustrations.
8vo.,
Net, $2.50
Theory and
and operators.
Its
8vo., cloth,
389
Ket, $3.50
EWING, J. A.
Net $4.00
Illustrated.
FISHER, H. K.
FLEMING,
Vol.
and
C.,
DARBY, W.
ing.
C.
Illus.
pp
Net, $3.50
J.
I.:
cloth, 641
Vol.
pp
The Utilization
II.:
Net, $5.00
of
Induced Currents.
Third Issue.
pp
.Net, $5.00
Handbook
With
Illustrated.
Room.
Two Volumes.
Net, $5.00
FOSTER, H.
A.
the Collaboration of
neers'
Pocket Book.
revised
and
F.
L.
Fully Illustrated.
Size.
Leather.
of Railroads
35 illustrations.
12mo
cloth, 76
.-.
W.
Thumb
$5.00
The Protection
F.
Crossings.
GANT,
1636 pp
Indexed.
FOWLE,
enlarged.
with Diagrams.
Illustrated
Net, $2 50
.
C. H. W.
Electricity Meters; their Construction and Management.
practical manual for central station engineers, distribution engineers
and students. Illustrated. 8vo., cloth, 337 pp
Net, $4 .00
GERHARDI,
The Art
GORE, GEORGE.
GRAY,
J.
Illustrated.
Practical).
Electrical
Influence
and
Net, $3 50
pp
Development and
revised
296 pp
$2.00
Modern Forms.
GROTH,
L. A.
illustrations.
HAMMER, W.
J.
124
or Electricity.
Net, $3 .00
With a consideration of Phosphorescent .and Fluorescent Substances, the properties and applications of Selenium, and the
treatment of disease by the Ultra- Violet Light. With Engravings and
$1 .00
Plates.
8vo., cloth, 72 pp
HARRISON,
cloth,
N.
Electric
HASKINS,
12mo..
Illustrated.
SI
272 pp
its
Uses.
Illus.
Manual
-r O
for Electricians
16mo., morocco, 75 pp
$1 50
.
ALFRED.
HAY,
their
Course
327 pp
of
Introductory
cloth,
8vo.,
HEAVISIDE,
0.
Second
Edition.
$2.00
and transformation.
theory,
generation,
8vo., cloth, 319
1178 Illustrations.
Edition.
Working.
Alternating Currents;
An
Alte- nate-Current
of
Principles
lUustrated.
Continuous-Current
Second
..Net, $2.50
pp
Engineering.
Illustrated
Net, $2.50
Electromagnetic Theory.
Each
Two Volumes
vol
with
Many
Diagrams.
Net, $5 00
An
HEDGES, K.
HOBART,
H. M.
Heavy
Electrical Engineering.
Illustrated.
Net, $4.50
pp
HOBBS, W. R.
The Arithmetic
P.
HOMANS,
HOPKINS,
A B C
E.
J.
cloth,
of
of Electrical
Measurements.
the Telephone.
With numerous
Twelfth Edition.
With 269
Illustrations.
12mo.,
352 pp
N. M.
Treated.
$1 .00
Profusely
Illustrated.
8vo.,
cloth,
Net, $3.00
HOUSTON, EDWIN
12mo., cloth,
Net, $2.50
HUTCHINSON,
and IHLSENG, M. C. Electricity in Mining. Being a theoretical and practical treatise on the construction, operation, and maintenance of electrical
In Press
mining machinery. Illustrated. 12mo., cloth
(No. 53
Used.
Eleventh Edition.
Van Nostrand's
Illustrated.
Science Series.).
.50 cents
JEHL, FRANCIS.
The Manufacture
JONES,
HARRY
cloth,
8vo
Illustrated.
Purposes.
The
of
cloth, 232
and Radioactivity.
12mo.,
212 pp
$2 .00
KAPP, GISBERT.
Transmission
Electric
and
Subdivision,
Distribution.
Illustrated.
thoroughly revised.
of
Practical
Dynamos,
pp
Alternators,
and
Transformers.
Illustrated.
8vo.,
(No. 96
50 cents
cloth,
507
$4.00
KELSEY, W. R.
KEMPE,
H.
R.
R.
KENNEDY,
Modern
The
cloth, 5 vols.
8vo.
Illustrated.
Illustrated.
J.
trated.
Electrical
and
Engines
Seventh
Edition,
Testing.
8vo.. cloth, 706 pp.
.Net, $6.00
Power
Generators.
Illustrated.
Electric
of
The
B. C.
Electric
Light, Power,
The
Set, $15.00
Steel Production.
pp
8vo., cloth, 303 pp.
Continuous-Current Armatures;
79 Illustrations. 8vo., cloth, 80 pp
C.
Alternate-Current Windings;
8vo., cloth, 80 pp
I.
$1 50
.
Illus-
minster Series.)
struction.
Vol
Net, $1 .50
Illustrated.
Electrometallurgy.
4to.,
Each, $3.50
cloth, 5 vols.
8vo., cloth, 74
KINZBRUNNER,
A. E.
KENNELLY,
of
285 Illustrations.
Set, $15.00
Installations
^Electrical
KERSHAW,
Handbook
and enlarged.
revised
their
their
Net, $2 00
.
Net, $1 .50
89 Illustrations.
Net, $1 50
.
F.
Hydroelectric Developments and Engineering.
practical and
theoretical treatise on the development, design, construction, equipment and
500 illustrations.
4to.,
operation of hydroelectric transmission plants.
KOESTER,
cloth,
475 pp
Net, $5.00
Steam-Electric
light
LARNER,
E. T.
The
Engineering.
LEMSTROM,
cloth
S.
Electricity in Agriculture
and Horticulture.
Illustrated.
8vo.,
Net, $1 .50
LIVERMORE,
T. D.
A PracElectricity, Magnetism, and Electro-Telegraphy.
Guide and Handbook of General Information for Electrical Students,
Operators, arid Inspectors. Fourth Edition. Illustrated. 8vo., cloth,
374 pp ........................................................ $2.50
LOCKWOOD,
tical
LODGE, OLIVER
of the
work
cloth.
LORING,
J.
Being a description
Illustrated.
8vo..
A Handbook
A. E.
Fourth Edition,
revised.
Science
LUPTON,
MAILLOUX,
C.
O.
Traction
Electric
Machinery.
Illustrated.
cloth
8vo.,
In
Electromagnets: Their Design and Construction. Second
ICmo., cloth, 155 pp. (Van Nostrand's Science
Series No. 64.) ............................................... 50 cents
MANSFIELD,
A. K.
Illustrated.
Edition.
MAURICE, W.
C. R.
Illustrated.
Popularly Explained.
Electricc.1 Blasting
Apparatus and Explosives, with special refer8vo., clcth, 167 pp ...... Net, $3.50
Illustrated.
C. C. F. Radio Telegraphy.
173 Illustrations. 8vo., cloth, 272
pp.
(Van Nostrand's Westminster Series.) ........................ Net $2 00
MONCKTON,
MUNRO,
J.,
for the
NIPHER, FRANCIS
NOLL, AUGUSTUS.
Wiring.
OHM,
G. S.
How
to
Wire Buildings.
Fourth Edition.
The Galvanic
Translated
by
Illustrated.
Manual
With an Appendix
cloth, 94 pp.
.$1
00
Berlin,
1827
by the Editor!
16mo., cloth, 269 pp
OUDIN, MAURICE A.
PALAZ,
Second Edition.
B.A.
PARR,
G. D. A.
Fully Illustrated.
Net, $3 50
cloth,
H.
PARSHALL,
F.,
and
HOBART,
H. M.
With 140
Third Edition.
Railway Engineering.
4to., cloth, 475 pp
Tables.
Electric
.
Armature Windings
of Electric Machines.
4to., cloth,
descriptive letter-press.
Electric
$4.00
pp
Electrical Engineering
"
Electric
Being a revised and enlarged edition of
648 Illustrations. 4to, half morocco, 601 pp
Net, $12.50
Machine Design.
Generators."
F. A. C.
Conductors for Electrical Distribution: Their Manufacture
and Materials, the Calculation of Circuits, Pole-Line Construction, Underground Working, and other Uses. Second Edition. Illustrated. 8vo.,
cloth, 287 pp
Net, $3 50
PERRINE,
POPE,
F. L.
tricians
Modern Practice
and Operators.
$1 .50
234 pp
RAPHAEL,
F. C.
revised.
RAYMOND,
Illustrated.
E. B.
pp
Second Edition,
Net, $3 .00
Third
Edition, revised.
Net, $2.50
RICHARDSON,
S. S.
Measurement.
ROBERTS,
J.
Work
in Electrical Engineering
Preliminary Grade.
experiments for first- and second-year students in
Illustrated with many Diagrams.
8vo., clcth,
engineering.
Net &2.00
Laboratory
series of laboratory
electrical
218 pp
ROLLINS, W.
>
Notes
on X-Light.
400
Net, $7.50
8vo., cloth
RUHMER, ERNST.
RUSSELL, A.
The Theory
pp
of Electric
71
Illustrations.
Net, $3 .00
SALOMONS, DAVID.
Electric-Light Installations.
Practical
12mo., cloth.
Management of Accumulators.
Handbook.
Illus-
trated.
Vol
I.:
Vol. II.:
Vol. III.
Ninth Edition.
318 pp
234 pp
Seventh Edition.
Application.
178 pp
$2.50
$2 .25
$1 50
Seventh Edition.
Apparatus.
SCHELLEN, H.
Their Con-
struction and Practical Application to Electric Lighting and the Transmission of Power. Translated from the Third German Edition by N. S.
Keith and Percy Neymann, Ph.D. With very large Additions and Notes
Vol. I. With 353 Illusrelating to American Machines, by N. S. Keith.
Third Edition. 8vo., cloth, 518 pp
trations.
$5.00
G. F. Electrical Engineering Experiments and Tests on Direct-Current
Machinery. Second Edition, enlarged. With Diagrams and Figures. 8vo.,
Net, $1 .00
pamphlet, 75 pp
SEVER,
and
TOWNSEND,
SEWALL,
C.
H.
F.
Second Edition.
Illustrated.
Wireless Telegraphy.
Figures.
Lessons in Telegraphy.
T.
Second
Net, $2.00
Net, $1 .00
Illustrated.
Edition, corrected.
pp
Illustrated.
$3.00
P. E.
cially
cloth,
SHELDON,
A First- Year Course of Practical Magnetism and Electricity. Speadapted to the wants of technical students. Illustrated. 8vo.,
66 pp. interleaved for note taking
Net, $1 .00
S.,
and MASON, H.
Dynamo-Electric Machinery:
Seventh
Its
revised.
Edition,
Construction,
Illustrated.
Net, $2 .50
pp
and
HAUSMANN, E.
of
SLOANE,
T.
cloth,
O'CONOR.
G82 pp
300 Illustrations.
12mo.,
$3.00
to
W ork.
r
Mining
Second Edition.
Net, $4.00
SODDY,
F.
Radio-Activity
Disintegration Theory.
SOLOMON, MAURICE.
Electric
Lamps.
Illustrated.
8vo.,
(Van Nos-
cloth.
A.
STEWART,
Net, $2 .00
Illustrated.
pp
SWINBURNE,
(No. 109
ous Illustrations.
Van Nostrand's
SWOOPE,
C.
Science
50 cents
Series.)
WALTON.
Principles,
Experi-
THOM,
C.,
in
and JONES,
.Net, $2 .00
pp
W.
H.
Quadruplex Telegraphy.
S. P., Prof.
Dynamo-Electric Machinery. With an Introduction
and Notes by Frank L. Pope and H. R. Butler. Fully Illustrated. 16mo.,
50 cents
(No. 66 Van Nostrand's Science Series.)
cloth, 214 pp.
THOMPSON,
TOWNSEND, FITZHUGH.
paper, 32
UNDERBILL,
R.
C.
J.
Illustrated.
8vo.,
Net, 75 cents
218 Illustrations.
URQUHART,
pp
W.
12mo
Dynamo
of Engineer Constructors
cloth
cloth, 345
pp
Construction.
and Electricians
Electromagnetic Windings.
Net, $\OU
Practical
in Charge.
Handbook
Illustrated.
12mo.,
$3.00
A Handbook
Electric Ship-Lighting.
Ship's Electrical Plant, for
Electricians,
in Charge.
cloth, 308 pp
88 Illustrations.
12mo.,
S3. 00
Electrotyping.
Fifth Edition.
Illustrated.
Illustrated.
12mo., cloth,
228 pp
$2.00
$2.00
W.\DE, E.
Net, $4.00
WALKER, FREDERICK.
Wind
for
Electricity in Mining.
Fourth Edition.
on
Practical Treatise
Illustrated.
12mo.,
$2.00
Illustrated.
WALLING,
Apparatus.
to
Illustrated.
Science Series.)
Electricity in
F.
Electrical
Auxiliary
cloth, 358 pp
How
Third Edition.
Van Nostrand's
(No. 98
SYDNEY
Practical
any Output.
$3 .50
pp
pp
WALMSLEY,
Treatise
8vo.,
WATT, ALEXANDER.
Electroplating
and Refining
of
New
Metals.
Edition,
'
rewritten
by Arnold
Philip.
Fifteenth
Electro-Metallurgy.
Illustrated.
Edition.
$1.00
H. L.
WEBB,
Fifth Edition.
WEEKS,
W.
R.
The Design
New
of Alternate-Current Transformer.
Edition
in Press
MARTEN.
WEYMOUTH,
F.
Practice.)
New
Illustrated.
557 pp
YOUNG,
J.
Net, $6.00
ELTON.
8vo., cloth,
96=page
Electrical
Testing
Net, $4.00
264 pp
Catalog
subjects,
will
application.
Illustrated.
of
be
Books on
furnished
Electricity,
gratis,
postage
classified
prepaid,
by
on
**.>^r.t* 8
rj
YC 19469
224493