500 KVA 13.8/0.

231 KV SERVICE TRANSFORMER

Solidly

500

Dyn11

13.8 kV

231/133 V
500 KVA 13.8/0.231 KV SERVICE TRANSFORMER

95

38
3

5%

+/- 5%

50

55

68

As per IEC/ANSI standard


500 KVA 13.8/0.231 KV SERVICE TRANSFORMER

48

Copper

As per clause 4.3.6

IEC-60214
+2 , -2
+2 , -2
+/- 5%
Manual

Yes
500 KVA 13.8/0.231 KV SERVICE TRANSFORMER

Horizontal
R,Y,B
r,y,b

IEC-60137
SEC Approved
SEC Approved
Outdoor
Porcelain
Brown
13.8 kV
17.5 kV
95

38
250
Min:25mm / kVmax
1

*
Tinned Copper

XLPE

3Cx50 mm2
Copper
3
As Per SOW
Heat Shrinkable

IEC-60137
SEC Approved
SEC Approved
Outdoor Type
Porcelain
Brown
231

*
500 KVA 13.8/0.231 KV SERVICE TRANSFORMER

3
90

1
1600

*
*
Tinned Copper

XLPE
630
Copper
1
Min : 2
Heat Shrinkable

Steel
Min : 3 mm
IP54

*
*

SEC Approved
SEC Approved
Dial Type
Thermometer
Yes

*
IP54
0-120 ° C
500 KVA 13.8/0.231 KV SERVICE TRANSFORMER

SEC Approved
SEC Approved
Magnetic Type

*
IP54
Min,25 ° C, Max

SEC Approved
SEC Approved
Dial Type

*
IP54
*

SEC Approved
SEC Approved
Self Resetting

*
*

Pet Cock Type


Iron body with Bronze / Steel trim

20 mm

5 mm

Yes

20 mm

SEC Approved

*
500 KVA 13.8/0.231 KV SERVICE TRANSFORMER

Attached

As Per Clause 4.15

*
*
*

*
*
*
*
*

As Per IEC60076-1
Clause 10.1.3
500 KVA 13.8/0.231 KV SERVICE TRANSFORMER

Additional technical data as per attached sheet shall be complied by the


Bidder / Manufacturer.
ADDITIONAL TECHNICAL DATA 500kVA, Dyn11, 13.8/0.231kV AUXILIARY
TRANSFORMER
Sr. DESCRIPTION UNIT DATA REQUIRED DATA
No. OFFERED
1. Application standard IEC-60076
Type of design Outdoor
Number of phases No 3
Number of windings No 2
Frequency Hz 60
Cooling System ONAN
Design Max. Ambient temperature ºC 500

2 RATING
Maximum duration of overload at 50ºC with
50% initial load & without loss of life

25% Minutes 250


50% Minutes 22
100 % Minutes 0.09

Normal rated current at principal Tapping

HV A 20.92
LV A 1312.20
Impedance * % 5
Zero sequence impedance at rated voltage & Ohm/p
frequency
Induced over voltage
3
HV Winding kV.rms 2xUr
LV Winding kV.rms 2xUr
Test Frequency Hz 120
4 Constructional Features
Material of winding insulation Thermal upgraded
insulation paper
Maximum flux density T 1.6
5 Tanks
Minimum withstand pressure of the tank for 24 Kpa 25% above the
hours without leakage above the normal normal operating
operating pressure measured at the bottom of the pressure measured at
tank Tank bottom
6 OIL .

Producer

Type and trademark

Applicable Standard Specification


(Reference number &date of issue) As Per 54-TMSS-01