requirements for
LV apparatuses
Basics of Standards
Standards guidelines IEC 60947 and
60898
ABB Group
October 14, 2015 | Slide 1
Contents
ABB Group
October 14, 2015 | Slide 2
International Standard
IEC 60947
European Standard
EN 60947
TIU CHUN QUC GIA TCVN 6592-41:2009 (IEC 60947-4-1 : 2002) V THIT B
NG CT V IU KHIN H P
ABB Group
October 14, 2015 | Slide 3
IEC 60947-2
ABB Group
October 14, 2015 | Slide 4
ABB Group
October 14, 2015 | Slide 5
BREAKING
WITHSTAND
MAKING
BREAKING
Breaking Capacity
WITHSTAND
MAKING Capacity
ABB Group
October 14, 2015 | Slide 7
A device fulfills the isolating function stipulated under IEC 60947-1 when
in theOpen position the isolation at a defined withstand voltage is
assured between the open contacts of the main circuit of the switchgear.
According to IEC 60947-3, an isolator must only be able to
make and break a circuit, if either a current of negligible size is
switched on or off, or if during switching no noticeable voltage
difference between the terminals of each pole occurs.
ABB Group
October 14, 2015 | Slide 8
Changeover Switch
Switch
Switch fuse
ABB Group
October 14, 2015 | Slide 9
ATS by OTM
ABB Group
October 14, 2015 | Slide 10
ABB Group
October 14, 2015 | Slide 11
ABB Group
October 14, 2015 | Slide 12
ABB Group
October 14, 2015 | Slide 14
ABB Group
October 14, 2015 | Slide 16
ABB Group
October 14, 2015 | Slide 17
ABB Group
October 14, 2015 | Slide 18
ABB Group
October 14, 2015 | Slide 19
Example
Peak
105kA
100kA
S6L800 In800
54kA
16,8kA
10kA
10kA
ABB Group
October 14, 2015 | Slide 20
50kA
100kA
Irms
Energy limitation
Current
Energy limitation
ABB Group
October 14, 2015 | Slide 21
Time
curves
ABB Group
October 14, 2015 | Slide 22
Energy limitation
Protection against short-circuit (IEC 60364)
To protect a cable against short-circuit, the specific let-through energy of
the protective device must be lower or equal to the withstanding energy of
the cable:
Specific let through energy curve LLL
1E3MAs
100MA s
where
I2 t is the specific let-through energy of
the protective device which can be read on
the curves supplied by the manufacturer;
S is the cable cross section [mm2]; in the
case of conductors in parallel it is the cross
section of the single conductor;
k is a factor that depends on the cable
insulating and conducting material.
10MAs
1MAs
0.1MAs
1E-2MAs
0.1kA
ABB Group
October 14, 2015 | Slide 23
1kA
10k A
100k A
Choice criteria
In = 1600 A
Iu = 1600 A
Ue = 415 V
Icu= 50 KA
Ics = 50 KA
Ics = 50 KA (1s)
ABB Group
October 14, 2015 | Slide 24
Choice criteria
ABB Group
October 14, 2015 | Slide 25
Rated value Iu
ABB Group
October 14, 2015 | Slide 26
Rated value Iu
The rated uninterrupted current Iu is different from the rated
current In, which is the rated current of the thermomagnetic or
electronic trip unit and is lower or equal to Iu.
A new concept
for setting the
current In: the
rating plug
ABB Group
October 14, 2015 | Slide 27
ABB Group
October 14, 2015 | Slide 28
Rated value Iu
ABB Group
October 14, 2015 | Slide 29
Rated value Iu
ABB Group
October 14, 2015 | Slide 30
Rated value Ue
ABB Group
October 14, 2015 | Slide 31
Choice criteria
ABB Group
October 14, 2015 | Slide 32
IEC 60947-2
def. 4.3.5.2.1
ABB Group
October 14, 2015 | Slide 33
IEC 60947-2
def. 4.3.5.2.2
ABB Group
October 14, 2015 | Slide 34
Rated value Ue
ABB Group
October 14, 2015 | Slide 35
Ics Icu
The service breaking capacity Ics can be expressed as
a value of breaking current, in kA;
a percentage of Icu, rounded up
to the lowest whole number,
in accordance with the table (for
example Ics = 25% Icu).
Standard ratios between Ics and Icu
ABB Group
October 14, 2015 | Slide 36
selection criteria
IEC 60947-2
def. 4.3.5.4
ABB Group
October 14, 2015 | Slide 38
IEC 60947-2
Table 4
ABB Group
October 14, 2015 | Slide 39
IEC 60947-2
Table 4
ABB Group
October 14, 2015 | Slide 40
IEC 60947-2
Table 3
30 kA
IEC 60947-2
def. 4.3.5.1
ABB Group
October 14, 2015 | Slide 42
ABB Group
October 14, 2015 | Slide 43
Perspective
current IKLLL
10 - 100 kA
10 - 50 kA
6 - 20 kA
0,5 4,5 kA
ABB Group
October 14, 2015 | Slide 44
ABB Group
October 14, 2015 | Slide 45
IEC 60947-2
Table 2
Icm n x Icu
Example Icm - Ip
ABB Group
October 14, 2015 | Slide 47
Choice criteria
ABB Group
October 14, 2015 | Slide 48
Limit value Ui
IEC 60947-1
def. 4.3.1.2
Ui = RATED INSULATION
VOLTAGE
Ue < Ui
ABB Group
October 14, 2015 | Slide 49
IEC 60947-1
def. 4.3.1.3
ABB Group
October 14, 2015 | Slide 50
ABB Group
October 14, 2015 | Slide 51
Choice criteria
ABB Group
October 14, 2015 | Slide 52
Rated value In
Rated uninterrupted current (In):
the rated uninterrupted current of an equipment is a value of
current, stated by the manufacturer, which the equipment
can carry in uninterrupted duty, at a specified reference
ambient air temperature (30 C).
The
ABB Group
October 14, 2015 | Slide 53
Rated value Ue
Rated operational voltage (Ue):
The rated operational voltage of a circuit-breaker is the value
of voltage, assigned by the manufacturer, to which its
performances (particularly the short-circuit performance) are
referred.
ABB Group
October 14, 2015 | Slide 54
Choice criteria
ABB Group
October 14, 2015 | Slide 55
IEC 60898-1
def. 5.2.4
IEC 60898-1
def. 3.5.5.2
ABB Group
October 14, 2015 | Slide 57
- test seq. :
O - 3 min - O - 3 min CO
O - 3 min - CO - 3 min CO
ABB Group
October 14, 2015 | Slide 58
Tripping Curves
Overload characteristics
The main difference between the overload protection curve of the CBs responding to
IEC 60947 or IEC 60898 are referred to the conventional non tripping current.
The prescibed conditions are given in this table:
ABB Group
October 14, 2015 | Slide 59
Tripping Curves
Magnetic characteristics
The CBs according to IEC 60947 usually have the instantaneous threshold at 5 or 10 times
the rated current with a tolerance of + 20%.
The CBs according to IEC 60898-1 (ac applications) have different instantaneous
threshold referred to the type B , C , D as indicated in the table below:
ABB Group
October 14, 2015 | Slide 60
Tripping Curves
ABB Group
October 14, 2015 | Slide 61
Comparison (summary)
IEC 60947-2
IEC 60898-1
People
Instructed
Uninstructed
Maintenance
Possible
Not possible
40 C
30 C
Rated Voltage
(Ue)
Ambient
Temperature
No limits
Rated Current
In = 125 A
Icn = 25 kA (ac)
Icn = 10 kA (dc)