In stand-alone applications, the ASC Plant Management knows little about the surrounding environment in which it is placed. Based on
transducer power readings and hardwired feedbacks alone, the ASC Plant Management determines the power references to the PV plant. This
approach is applicable for integrating PV power in already commissioned gen- set plants, whether they are equipped with DEIF controllers or
not. Stand-alone applications support applications containing up to six gensets
Maximizing PV Penetration
The ASC Plant Management will in any operation mode automatically maximize PV penetration, depending on the total load demand to the
genset/PV hybrids without compromising constraints such as minimum genset load demand.
Spinning Reserve
The ASC Plant Management offers spinning reserve support. The spinning reserve is set in percentage and is in regards to the power being
produced by the PV plant. Hence the settings determine how much spinning reserve the genset plant should keep to compensate for a
potential decrease in PV production. Spinning reserve support applies to power management applications only.
Display
Mains
Mains
breaker
(MB)
Switch
Ethernet
Consumers
Tie
breaker
(TB)
Display
Display
Display
Busbar
CANbus
G
Diesel generator set 1
Generator
breaker
(GB 2)
PV
breaker
(PVB)
G
Diesel generator set 2
PV
B00291-180915
Generator
breaker
(GB 1)