Zelio Time
Catalogue
January
06
Contents
Selection guide
Applications
These timing relays enable simple automation cycles to be set up using wired logic.
They can also be used to complement the functions of PLCs.
Output
Solid state
Timing relays with solid state output reduce
the amount of wiring required (wired in
series). The durability of these timing relays
is independent of the number of operating
cycles.
Relay
Relay outputs provide complete isolation
between the supply and outut circuits.
It is possible to have several output circuits.
Type
Modular
Modular
Industrial
Timing ranges
7 ranges :
1 or 2 ranges,
1 s, 10 s, 1 min, 10 min, depending on model :
1 h, 10 h, 100 h
10 s, 30 s, 300 s,
60 min
Depending on model :
6 ranges :
1 s, 10 s, 1 min, 10 min,
1 h, 10 h
7 ranges :
1 s, 10 s, 1 min, 10 min,
1 h, 10 h, 100 h
Depending on model :
4 ranges :
0.6 s, 2.5 s, 20 s, 160 s
7 ranges :
1 s, 10 s, 1 min, 10 min,
1 h, 10 h, 100 h
7 ranges :
1 s, 3 s, 10 s, 30 s,
100 s, 300 s, 10 min
10 ranges :
1 s, 3 s, 10 s, 30 s,
100 s, 300 s, 30 min,
300 min, 30 h, 300 h
Relay type
RE11 Lp pp
RE9
RE11 Rp pp
RE7
Pages
16 and 17
20
24 to 27
30 to 33
Industrial
These timing relays enable simple automation cycles to be set up using wired logic.
They can also be used to complement the functions of PLCs.
Relay
Relay outputs provide complete isolation between the supply and output circuits.
It is possible to have several output circuits.
Optimum
Plug-in
Panel-mounted
Universal
Miniature
Analogue
Digital
1 range,
depending on model :
0.5 s, 3 s, 10 s, 30 s, 300 s,
30 min
7 ranges :
1 s, 10 s, 1 min, 10 min, 1 h,
10 h, 100 h
7 ranges :
0,1 s...1 s
1 s...10 s
0,1 min...1 min
1 min...10 min
0,1 h...1 h
1 h...10 h
10 h...100 h
14 ranges :
1,2 s, 3 s, 12 s, 30 s, 120 s,
300 s, 12 min, 30 min,
120 min, 300 min, 12 h, 30 h,
120 h, 300 h
Depending on model :
7 ranges :
99.99 s, 999.99 s, 99 min 59 s,
99.99 min, 999.9 min,
99 h 59 min, 999.9 h
11 ranges :
99.99 s, 999.99 s, 9999 s,
99 min 59 s, 99.99 min,
999.9 min, 9999 min,
99 h 59 min, 99,99 h,
999.9 h, 9999 h
RE8
RE 88 867 ppp
RE XLpTMpp
RE 48A ppp
RE 88 857 ppp
38 to 41
(1)
43
49
(1)
Presentation
Presentation
A timing relay is a component which is designed for timing events in industrial
automation systems by closing or opening contacts before, during or after a set
timing period.
There are two main 'families' of timing relays:
b "DIN rail mounted" relays (RE7, RE8, RE9, RE11, REXL) designed for mounting
on DIN rails in an enclosure,
521931-12-M
b "Panel mounted" relays type RE 48A, designed for mounting on the front of a
panel to give users easy access to the settings.
These relays have one, two or four outputs. Sometimes the second output can be
either timed or instantaneous.
If the power is switched off during the timing period, the relay reverts to its initial
position.
RE11
Application examples:
b opening of automatic doors,
b alarm,
b lighting in toilets,
b car park barriers ...
560904
Definitions
The following definitions will assist in understanding the operation of these relays:
b Relay output:
This is the most common type of output. When the relay is energised, the moving
armature is attracted by the coil and so actuates the contacts, which change state.
When the relay is de-energised, both the armature and the contacts revert to their
initial position.
This type of output allows complete isolation between the supply and the output.
521938-44-M
RE7 RL13BU
NC
C
NO
RE 48A
NO
532535
Presentation (continued)
Definitions (continued)
Functions
Timing functions are identified by letters.
Main timing
functions
A (2)
Complementary Definitions
functions (1)
Delay on energisation
Ac
Ad
Ah
Ak
At
Aw
B (2)
C (2)
D (2)
H (2)
He
Pulse-on de-energisation
Ht
L (2)
Lt
Safe-guard
Delayed safe-guard
Qc
Star-delta timing
Qe
Star-delta timing
Qg
Star-delta timing
Qt
Star-delta timing
Bistable relay
Tt
Selection
Selection table
Selection criteria
b Functions (On-delay or Off-delay, counter, flashing)
b Supply voltage (example: a/c 12 V240 V).
b Timing range (example: 0.05 s100 h)
b Type of output (contact or solid state) and required Number of contacts.
b Breaking capacity or Rated current of contacts, expressed in Amperes.
This is the maximum current which may flow through the contacts.
Functions
Supply voltage
c 12 V
Type of output
Relay
0.1 s100 h
0.1 s 100 h
c 24 V
0.1 s100 h
0.1 s100 h
a 24 V
0.1 s100 h
0.1 s100 h
a 120 V
0.1 s100 h
0.1 s100 h
a 230 V
0.1 s100 h
0.1 s100 h
a/c 24240 V
0.1 s10 s
0.3 s30 s
3 s300 s
40 s60 min
1 s100 h
0.02 s300 h
a/c 24 V, a 110240 V 0.05 s300 h
0.1 s3 s
0.1s10 s
0.3 s30 s
3 s300 s
2030 min
a/c 24 V, a 110240 V, 0.05 s300 h
a/c 4248 V
a 24240 V
1 s100 h
a/c 12 V
1 s100 h
a/c 12240 V
1 s100 h
1 s100 h
c 24 V, a 24240 V
1 s100 h
c 24 V, a 24240 V
1 s100 h
2
4
2
4
2
4
2
4
2
4
1
RE XL2TMJD
RE XL4TMJD
RE XL2TMBD
RE XL4TMBD
RE XL2TMB7
RE XL4TMB7
RE XL2TMF7
RE XL4TMF7
RE XL2TMP7
RE XL4TMP7
RE9 TA11MW
RE9 TA31MW
RE9 TA21MW
RE9 TA51MW
RE11 LA MW
RE 48A TM12 MW
RE7 TL11BU
RE8 TA61BUTQ
RE8 TA11BUTQ
RE8 TA31BUTQ
RE8 TA21BUTQ
RE8 TA41BUTQ
RE7 TP13BU
43
43
43
43
43
43
43
43
43
43
20
20
20
20
16
49
30
38
38
38
38
38
32
1 C/O contact
1 C/O contact
0.7 A
8A
8A
8A
8A
8A
RE11 LM BM
RE11 RM JU
RE11 RM MW
RE11 RM MWS
RE11 RM MU
RE11 RA MU
17
27
26
27
26
24
1 C/O contact
8A
RE7 TM11BU
30
A, At, B, C, D, Di, H, Ht
1 C/O contact
5A
RE11 RME MU
27
A, B, C, Di
a/c 24240 V
RE 48A ML12 MW
49
2 C/O contacts
8A
RE7 MY13BU
33
a/c 24240 V
0.05 s300 h
2 C/O contacts
8A
RE7 MY13MW
33
a 110240 V, a/c 24 V,
a/c 4248 V
a/c 24240 V
a 24240 V
a/c 24240 V
0.05 s300 h
1 C/O contact
8A
RE7 ML11BU
30
0.1 s10 s et
3 s300 s
0.02 s300 h
0.7 A
RE9 MS21MW
20
2 C/O contacts
5A
RE 48A MH13 MW
49
A, At
A, At, Aw
A, C, D, Di, H, W
A, D, Di, H
A1, A2, H1, H2
Timing range
0.02 s300 h
2
1
Rated
current
C/O contacts
5A
C/O contacts
3A
C/O contacts
5A
C/O contacts
3A
C/O contacts
5A
C/O contacts
3A
C/O contacts
5A
C/O contacts
3A
C/O contacts
5A
C/O contacts
3A
solid state output
0.7 A
0.7 A
0.7 A
0.7 A
0.7 A
timed C/O contacts 5 A
C/O contact
8A
8A
8A
8A
8A
8A
C/O contacts
8A
Page
Ac
1 C/O contact
2 C/O contacts
8A
8A
RE7 MA11BU
RE7 MA13BU
30
32
c 24 V, a 24240 V
1 C/O contact
8A
RE11 RMX MU
27
Ak
1 C/O contact
8A
RE7 MV11BU
30
1 s100 h
Selection (continued)
Supply voltage
Timing range
Type of output
Rated
current
8A
Relay
c 24 V, a 24240 V
1 s100 h
1 C/O contact
a/c 24 V
Page
RE11 RB MU
25
8A
8A
8A
8A
8A
8A
8A
8A
8A
8A
8A
0.7 A
0.7 A
0.7 A
0.7 A
0.7 A
8A
8A
8A
RE8 RA11BTQ
RE8 RA31BTQ
RE8 RA21BTQ
RE11 RC MU
RE8 RA11FUTQ
RE8 RA31FUTQ
RE8 RA21FUTQ
RE8 RA41FUTQ
RE7 RA11BU
RE7 RM11BU
RE7 RL13BU
RE9 RA11MW7
RE9 RA31MW7
RE9 RA21MW7
RE9 RA51MW7
RE11 LC BM
RE7 CL11BU
RE8 CL11BUTQ
RE7 CP13BU
38
38
38
25
38
38
38
38
31
31
32
20
20
20
20
17
31
39
33
2 C/O contacts
8A
8A
8A
8A
8A
RE7 PE11BU
RE8 PE11BUTQ
RE8 PE31BUTQ
RE8 PE21BUTQ
RE7 PP13BU
31
40
40
40
33
1 C/O contact
H, Ht
0.1 s10 s
0.3 s30 s
3 s300 s
c 24 V, a 24240 V
1 s100 h
a 110240 V
0.1 s10 s
0.3 s30 s
3 s300 s
20 s30 min
a/c 24 V, a 110240 V, 0.05 s300 h
a/c 4248 V
0.05 s300 h
0.05 s300 h
a 24240 V
0.1 s10 s
0.3 s30 s
3 s300 s
40 s60 min
1 s100 h
a/c 24 V, a 110240 V 0.05 s300 h
0.1 s10 s
a/c 24 V, a 110240 V, 0.05 s300 h
a/c 4248 V
a/c 24 V, a 110240 V 0.05 s300 h
0.1 s10 s
0.3 s30 s
3 s300 s
a/c 24 V, a 110240 V, 0.05 s300 h
a/c 4248 V
a 24240 V
1 s100 h
c 24 V, a 24240 V
1 s100 h
0.7 A
8A
RE11 LH BM
RE11 RH MU
16
24
He
1 C/O contact
8A
RE8 PT01BUTQ
41
a/c 24240 V
0.05 s10 min
a/c 24 V, a 110240 V 0.05 s0.5 s
0.1 s10 s
0.3 s30 s
a/c 24240 V
0.05 s10 min
c 24 V, a 24240 V
1 s100 h
a 24240 V
1 s100 h
a/c 12 V
1 s100 h
a/c 24240 V
0.02 s300 h
a 110240 V, a/c 24 V, 0.05 s300 h
a/c 4248 V
a/c 24 V, a 110240 V 0.1 s10 s
0.3 s30 s
3 s300 s
a/c 24 V
0.3 s30 s
a 110240 V
0.3 s30 s
a 380415 V
0.3 s30 s
a/c 24 V, a 110240 V, 0.05 s300 h
a/c 4248 V
a/c 24 V, a 110240 V, 0.05 s300 h
a/c 4248 V
a/c 24 V
0.1 s10 s
0.3 s30 s
3 s300 s
a 110240 V
0.1 s10 s
0.3 s30 s
3 s300 s
a/c 24 V, a 110240 V, 0.05 s300 h
a/c 4248 V
a/c 24 V, a 110240 V, 0.05 s300 h
a/c 4248 V
1 C/O contact
1 C/O contact
5A
8A
8A
8A
2 C/O contacts
5A
1 C/O contact
8A
1 solid state output
0.7 A
1 C/O contact
8A
2 timed C/O contacts 5 A
1 C/O contact
8A
RE7 RB11MW
RE8 RB51BUTQ
RE8 RB11BUTQ
RE8 RB31BUTQ
RE7 RB13MW
RE11 RL MU
RE11 LL BM
RE11 RL JU
RE 48A CV12 MW
RE7 CV11BU
31
39
39
39
32
25
17
25
49
31
1 C/O contact
1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC
1 NO + 1 NC
8A
8A
8A
8A
8A
8A
8A
RE8 YG11BUTQ
RE8 YG31BUTQ
RE8 YG21BUTQ
RE8 YA32BTQ
RE8 YA32FUTQ
RE8 YA32QTQ
RE7 YR12BU
41
41
41
41
41
41
33
2 C/O contacts
8A
RE7 YA12BU
33
1 C/O contact
2 C/O contacts
8A
8A
8A
8A
8A
8A
8A
RE8 PD11BTQ
RE8 PD31BTQ
RE8 PD21BTQ
RE8 PD11FUTQ
RE8 PD31FUTQ
RE8 PD21FUTQ
RE7 PD13BU
40
40
40
40
40
40
33
1 C/O contact
8A
RE7 PM11BU
31
L, Li
L, Li, Lt
Qc
Qe
Qg
Qt
W
W, Ht
1 C/O contact
1 C/O contact
1 C/O contact
2 C/O contacts
1 solid state output
1 C/O contact
2 C/O contacts
1 C/O contact
1 C/O contact
Functions
Functions
U : Supply
R : Relay or solid state output
R1/R2 : 2 timed outputs
R2 inst. :The second output is instantaneous if the right
position is selected
T : Timing period
C : Control contact
G : Gate
Ta : Adjustable On-delay
Tr : Adjustable Off-delay
Function diagram:
Relay de-energised
Relay energised
Output open
Output closed
2 outputs
R1/R2
T
R2 inst.
T
2 timed outputs (R1/R2) or 1 timed output
(R1) and 1 instantaneous output (R2 inst.).
2 outputs
R1/R2
R2 inst.
t1
t2
t'1
t'2
T = t1 + t2 +
T = t1 + t2 +
Function Ad: Timing on closing of control contact.
Functions (continued)
t1
t2
t'1
t'2
Ta = t1 + t2 +
Tr = t1 + t2 +
Function At: Delay on energisation with memory
After power-up, the first opening of control contact C starts the timing. Timing can be
interrupted each time control contact C closes. When the cumulative total of time
periods elapsed reaches the pre-set value T, the output relay closes.
t1
t2
T = t1 + t2 +
Function Aw: Off-delay on energisation or on opening of control contact
The timing period T starts on energisation.
At the end of the timing period T, the output R closes.
Closing of the control contact C makes the output R open.
Opening of control contact C restarts timing period T.
At the end of timing period T, the output R closes.
Functions
(continued)
2 outputs
R1/R2
T
R2 inst.
T
2 timed outputs (R1/R2) or 1 timed output (R1)
and 1 instantaneous output (R2 inst.).
2 outputs
R1/R2
T
R2 inst.
2 outputs
R1/R2
T
R2 inst.
2 outputs
R1/R2
T
R2 inst.
T
2 timed outputs (R1/R2) or 1 timed output (R1)
and 1 instantaneous output (R2 inst.).
10
Functions (continued)
> 80 ms T 80 ms
<T
t1
t2
T = t1 + t2 +
Function K: Delay on de-energisation (without auxiliary supply)
1 output
2 outputs
R1
T
R2
T
Function L: Asymmetrical flashing, start with output in rest position
Repetitive cycle comprises of two, independently adjustable timing periods Ta and
Tr. Each timing period corresponds to a different state of the output R.
Tr
Ta
Ta
Tr
t1
t2 t'1
t'2
Tr = t1 + t2 +
Ta = t1 + t2 +
11
Functions
(continued)
Function N: Safe-guard
After power-up and an initial control pulse C, the output R closes.
If the interval between two control pulses C is greater than the set timing period T,
timing elapses normally and the output R closes at the end of the timing period. If the
interval is not greater than the set timing period, the output R remains closed until
this condition is met.
T
Function O: Delayed safe-guard
An initial timing period T begins on energisation. At the end of this timing period, the
output R closes.
As soon as there is a control pulse C, the output R reverts to its initial state and
remains in that state until the interval between two control pulses is less than the
value of the set timing period T. Otherwise, the output R closes at the end of the
timing period T.
t<T T
P = 500 ms
Function Pt: Impulse counter (on-delay)
On energisation, timing period T starts (it can be interrupted by operating the Gate
control contact G).
At the end of this period, the output R closes for a fixed time P.
t1
t2
T = t1 + t2 +
P = 500 ms
Function Qc: Star-delta timing
On energisation, the star contact closes instantaneously and timing starts.
At the end of the timing period, the star contact opens.
After a 50 ms pause, the delta contact closes and remains in this position.
50 ms
R1
R2
12
80 ms
Functions (continued)
R1
R2
T
50 ms
R1
R2
T
50 ms
t<T
2 outputs
R1/R2
T
R2 inst.
T
2 timed outputs (R1/R2) or 1 timed output (R1)
and 1 instantaneous output (R2 inst.).
13
Characteristics
Timing characteristics
Selectable timing ranges
by selector switch on front panel
0.11
110
0.11
110
0.11
110
10100
0.5 %
Temperature
Voltage
0.05 % / C
0.2 % / V
10 % at 25 C
min
h
Repeat accuracy
(with constant parameters)
Drift
Setting accuracy
at full scale
Minimum duration
of control pulse
Maximum reset time
by de-energisation
Immunity to microbreaks
Typical
ms
50
Typical
ms
350
Typical
ms
> 10
Supply characteristics
Supply voltage
V
Frequency
Hz
Operating range
On-load factor
Maximum
power consumption
Depending on version:
a 24240
a/c 24240
50/60
85110 % Un
100 %
Depending
on model
c 24 V
c 240 V
a 240 V
W
W
VA
0.6
1.5
32
Output type
Breaking capacity
Solid state
a/c 0.7 at 20 C (0.5 A UL)
Derating
Maximum permissible current
mA
A
5 / C
20 10 ms
mA
mA
10
<5
a/c 250
3-wire 4 V - 2-wire 8 V
Output characteristics
108 operations
108 operations
Electrical life
Mechanical life
Dielectric strength
Conforming to
IEC 60664, IEC 60255-5
kV
2.5...1 mA / 1 min
Input characteristics
Input type
References :
pages 16 and 17
14
Dimensions :
page 16
Schemes :
page 17
Characteristics (continued)
General characteristics
Conforming to standards
Approvals
Ambient air temperature Storage
around the device
Operation
Creepage distance
Conforming to IEC 60664-1
and clearance
C
kV
- 20+ 60
4 kV/3
Degree of protection
conforming to IEC 60529
Terminal block
Housing
Front panel
IP 20
IP 40
IP 50
Vibration resistance
Relative humidity
without condensation
f = 1055 Hz
A = 0.35 mm
93 %
Electromagnetic
compatibility
Fixing
Clamping capacity
Housing material
References :
pages 16 et 17
30 % / 10 ms
60 % / 100 ms
95 % / 5 s
Class B
mm
35
mm2
mm2
2 x 2.5 or 1 x 4
2 x 1.5
Self-extinguishing
Dimensions :
page 16
Schemes :
page 17
15
Functions,
references,
dimensions,
schemes
Function diagrams
Function A
Function H
Delay on energisation
Timing on energisation
C
T
R
T
t1
t2
Functions
Timing ranges
Voltages
Nominal output current
Connection
Weight (kg)
7 ranges
a 24240 V
a/c 24240 V
Screw terminals
521925
521925
References
Single function
A
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
RE11 LA MW
0.7 A
p
0.060
Single function
H
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
RE11 LH BM
0.7 A
p
0.060
81
5,5
Characteristics :
pages 14 and 15
16
Schemes :
page 17
Function At
Function B
Function C
Function L
Function Li
R
Tr
t1
Ta
Tr
Ta
t2
T = t1 + t2 +
Function Ht
Function D
Function Di
Function Ac
Function Bw
Timing on energisation
with memory
U
T
C
R
R
t1
t2
R
T
521928
521927
521926
T = t1 + t2 +
Single function
C
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
RE11 LC BM
0.7 A
p
0.060
Dual function
L - Li
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
RE11 LL BM
0.7 A
p
0.060
Multifunction
A - At - B - C - H - Ht - D - Di - Ac - Bw
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
RE11 LM BM
0.7 A
p
0.060
Connection schemes
Single function relay
Functions A, H
Multifunction relay
Flashing
Functions L, Li
Function C
U
a/c
U
A1
Y1
Y1
Y2
(1)
(1)
A2
18
Y1
18
A2
Y2
A2/L
A2
A1
A1
A1
a/c
(1) Contact Y1 :
- Control for functions B, C, Ac, Bw.
- Partial stop for functions At, Ht.
- Function D if Di selected.
- Not used for functions A and H.
Characteristics :
pages 14 and 15
Dimensions :
page 16
17
Characteristics
560853
Presentation
The RE9 range of relays is designed for simple, repetitive applications with short and
intensive cycles because their solid state output provides very high electrical
durability.
Each relay has a single timing range.
Each relay has a wide voltage range from 24 to 240 V.
The range comprises 9 references with 3 model types:
b RE9 TA: function A,
b RE9 RA: function C,
b RE9 MS: multifunction A, H, L, Li.
These products have a transparent, hinged flap on their front face to avoid any
accidental alteration of the settings. This flap can be directly sealed.
Environment
Conforming to standards
Product certifications
CSA, GL pending. UL
e marking
Storage
Operation
Conforming to IEC 60721-3-3
C
C
- 40+ 85
- 20+ 60
1585 % Environmental class 3K3
a = 0.35 ms
Degree of pollution
Casing
Terminals
Conforming to IEC 60664-1
IP 50
IP 20
3
Overvoltage category
III
Conforming to IEC
Conforming to CSA
V
V
250
300
Dielectric test
Shock wave
kV
kV
2.5
4.8
Voltage limits
Frequency limits
Disconnection value
> 0.1 Uc
Mounting position
without derating
Cabling
Maximum c.s.a.
In relation to normal
vertical mounting plane
Flexible cable without cable end mm2
mm2
Flexible cable with cable end
Any position
Tightening torque
N.m
Shock resistance
Degree of protection
15 gn - 11 ms
0.851.1 Uc
Hz
50/60 5 %
2 x 2.5
2 x 1.5
0.61.1
Electromagnetic fields
Fast transients
Level 3 (2 kV)
Shock waves
Level 3 (2 kV)
CISPR11
Group 1 class A
CISPR22
Class A
References :
page 20
18
Dimensions :
page 20
Schemes :
page 21
Characteristics
(continued)
RE9 TA
On-delay
RE9 RA
Off-delay
RE9 MS
Multifunction
a/c 24240
a 24240
a/c 24240.
See page 20
In series
Between Y2 and A2
In series
Supply characteristics
Supply voltage
Voltage limits
V
Of the control circuit
0.851.1 Un
Frequency
Hz
5060 5 %
Control contact
Mechanical only
Maximum length of
connecting cable
Control input consumption
20
Input Y2
mA
Timing characteristics
Setting accuracy
< 20 %
Repeat accuracy
<1%
ms
100
ms
40
ms
ms
100
2
70
2
Temperature drift
15 for 10 ms
3 (at 0.7 A)
Leakage current
Open state
mA
2.5
2.5
mA
Without
Electrical durability
References :
page 20
Dimensions :
page 20
> 100
Schemes :
page 21
19
Functions,
references,
dimensions
Function diagrams
Function A
Delay on energisation
Function C
Timing after opening
of control contact
Function H
Timing on energisation
T
R
T
Function D
Symmetrical flashing,
start with output in rest
position
Function Di
Symmetrical flashing,
start with output in
operating position
Functions
Voltages
Timing ranges
c or a 24240 V
a 24240 V
0.1 s10 s
0.3 s 30 s
3 s300 s
40 s60 min
Weight (kg)
A
p
RE9 TA11MW
RE9 TA31MW
RE9 TA21MW
RE9 TA51MW
0.110
560855
560855
560854
References
p
RE9 RA11MW7
RE9 RA31MW7
RE9 RA21MW7
RE9 RA51MW7
0.110
A, H, D, Di
p (A)
p (H, D, Di)
RE9 MS21MW
RE9 MS21MW
0.110
Dimensions
Rail mounting
Screw fixing
78
6
78
80
89,5
82
Characteristics :
pages 18 and 19
20
Schemes :
page 21
Schemes
Terminal blocks
RE9 TA
RE9 RA
A1
RE9 MS
A1
A1
X4
Y2
A2
X1
X2
X3
RE9-TA
K
A1
Load
The timing relay is placed in series, with the load whose energisation is to be delayed on one
side and switch K on the other side. The mains supply may be a.c. or d.c. and the voltage may
be between 24 V and 240 V. See function diagram on page opposite.
Load
The timing relay is placed in series with the load whose de-energisation is to be delayed. Switch
K is connected to terminals Y2 and A2 of the timing relay, and terminal A2 is connected to the
mains supply, as indicated in the diagram opposite. The device is operated from an a.c. mains
supply whose voltage is between 24 V and 240 V. See function diagram on page opposite.
Supply a or c
RE9 RA
RE9-RA
A1
Y2
A2
Supply a
RE9 MS
Delay on energisation
Function A
Timing on energisation
Function H
Selection of the timing range
X3 X4
A1
Load
A1
A2
X1
K
A1
RE9-MS
X3 X4
Load
A1
A2
RE9-MS
Supply a or c
Supply a
Symmetrical flasher,
start with output in rest position
Function D
X1 X2 X3 X4
K
A1
Symmetrical flasher,
start with output in operating position
Function Di
X2 X3 X4
Load
A1
A2
A1
Load
A1
A2
RE9-MS
RE9-MS
Supply a
Supply a
Note : For supply voltages greater than 30 V, the rated voltage of the load is equal to the supply voltage. For a supply voltage of 24 V, the voltage drop within the
RE9 relay must be taken into account (about 3 V); a coil with a nominal voltage of 21 V must therefore be selected for the load.
Characteristics :
pages 18 and 19
Dimensions :
page 20
21
Characteristics
Timing characteristics
RE11 Rp pp
0.11
110
0.11
110
0.11
110
10100
0.5 %
Temperature
Voltage
Conforming to IEC 61812-1
0.05 % / C
0.2 % / V
10 % at 25 C
Relay type
Selectable timing ranges
by selector switch on front panel
s
min
h
Repeat accuracy
(with constant parameters)
Drift
Setting accuracy
at full scale
Minimum duration
of control pulse
Maximum reset time
by de-energisation
Immunity to microbreaks
Typical
Typical with load in parallel
Typical
ms
ms
ms
30
100
100
Typical
ms
> 10
RE11 RME MU
0.11
110
0.11
110
0.11
110
Supply characteristics
Relay type
Supply voltage
Frequency
Operating range
On-load factor
Maximum power
consumption
V
Hz
Depending
on model
a/c 12 V
c 24 V
c 240 V
a 240 V
VA/W
W
W
VA
RE11 Rp pp
a/c 12240
c 24/a 24240 depending on version
50/60
85110 % of Un
100 %
0.6
1.5
32
RE11 Rp JU
a/c 12 V
90120 % of Un
0.4
Output characteristics
RE11 Rp pp
RE11 RME MU
Relay, 1 C/O contact, AgNi (cadmium-free)
a 2000 VA, c 80 W
a 1250 VA, c 50 W
Relay type
Output type
Breaking capacity
Maximum breaking current
Minimum breaking current
A
mA
a 8, c 8
10 /c 10 V
Mechanical life
Dielectric strength
Impulse voltage
kV
kV
a 5, c 5
5 x 106 operations
2.5/1min/1 mA/50 Hz
5, wave: 1.2/50 s
Display characteristics
State indication by 1 LED
Green
Input characteristics
Input type
References :
pages 23 and 24
22
Dimensions :
pages 24 and 26
Schemes :
pages 25 and 27
Characteristics (continued)
General characteristics
Conforming to standards
Approvals
Ambient air temperature
around the device
Storage
Operation
C
C
cULus, CSA,
GL except RE11 RMX MU and RE11 RME MU
- 30+ 60
- 20+ 60
Creepage distance
and clearance
Degree of protection
conforming to IEC 60529
kV
4 kV/3
Terminal block
Housing
Front panel
IP 20
IP 40
IP 50
Vibration resistance
f = 1055 Hz
A = 0.35 mm
Relative humidity
Conforming to IEC 60068-2-3
without condensation
Electromagnetic compatibility Immunity to
electrostatic discharge,
conforming to IEC 61000-4-2
Immunity to
electromagnetic fields,
conforming to ENV 50140/204
(IEC 61000-4-3)
Immunity to
fast transients in bursts,
conforming to IEC 61000-4-4
Immunity to
surges on the power supplies,
conforming to IEC 61000-4-5
Immunity to radio frequency
interference in common mode,
conforming to ENV 50141
(IEC 61000-4-6)
Immunity to
voltage dips and breaks,
conforming to IEC 61000-4-11
93 %
Level III (Air 8 kV/Contact 6 kV)
30 % / 10 ms
60 % / 100 ms
95 % / 5 s
Class B
References :
pages 23 and 24
mm
35
mm2
mm2
2 x 2.5 and 1 x 4
2 x 1.5
mm2
mm2
1.5
2.5
Self-extinguishing
Dimensions :
pages 24 and 26
Schemes :
pages 25 and 27
23
Functions,
references,
dimensions,
schemes
Function diagrams
b
b
b
b
b
b
b
b
Function A
Function At
Delay on energisation
R
T
R
t1
t2
T = t1 + t2 +
Function H
Function Ht
Timing on energisation
C
T
R
T
t1
t2
T = t1 + t2 +
Functions
Timing ranges
Voltages
Nominal output current
Connection
Weight (kg)
7 ranges
a/ c 12 V
c 24 V / a 24240 V
Screw terminals
521929
521929
References
Dual function
A - At
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
Dual function
H - Ht
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
RE11 RA MU
8A
p
0.060
RE11 RH MU
8A
p
0.060
81
5,5
Characteristics :
pages 22 and 23
24
Schemes :
page 27
Function L
Function Li
Asymmetrical flashing,
start with output in rest position
Asymmetrical flashing,
start with output in operating position
R
Tr
Ta
Ta
Tr
Function B
Function C
C
R
R
T
Dual function
L - Li
1 s - 10 s - 1 min - 10 min - 1 h - 10 h 100 h
RE11 RL MU
8A
p
0.060
521929
521929
521930
521930
Dual function
L - Li
1 s - 10 s - 1 min - 10 min - 1 h - 10 h 100 h
RE11 RL JU
8A
p
0.060
Single function
B
1 s - 10 s - 1 min - 10 min - 1 h - 10 h 100 h
RE11 RB MU
8A
p
0.060
Single function
C
1 s - 10 s - 1 min - 10 min - 1 h - 10 h 100 h
RE11 RC MU
8A
p
0.060
Functions H and Ht
Functions L and Li
Functions B and C
Connection schemes
A2
Y1
A2
16
A2
A2
Y1
16
18
15
R
(1)
Y1
16
18
15
+
A1
Y1
16
18
+
A1
+
A1
A1
Functions A and At
18
15
R
15
R
Characteristics :
pages 22 and 23
Dimensions :
page 26
25
Functions,
references,
dimensions,
schemes
Function diagrams
Multifunction
Multi-range (6 or 7 selectable ranges)
Multivoltage
1 relay output: 5 or 8 A
Screw or spring terminals
State indication by 1 LED
Option of supplying a load in parallel
3-wire sensor control option
Function A
Function At
Delay on energisation
Function B
Delay on energisation
with memory
U
R
T
R
R
t1
t2
T = t1 + t2 +
Function C
Function H
Function Ht
Timing on energisation
Timing on energisation
with memory
U
C
T
R
R
T
t1
t2
T = t1 + t2 +
Function D
Function Di
Function Ac
U
C
R
T
T
R
T
Functions
Timing ranges
Voltages
6 or 7 ranges
a/c 12 V
c 24 V / a 24240 V
a/c 12240 V
Screw terminals
Spring terminals
Weight (kg)
521931
521931
References
Multifunction
A - At - B - C - H - Ht - D - Di - Ac - Bw
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
RE11 RM MU
8A
p
0.060
Multifunction
A - At - B - C - H - Ht - D - Di - Ac - Bw
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
RE11 RM MW
8A
p
0.060
17,9
5,5
81
5,5
Characteristics :
pages 22 and 23
26
Schemes :
page 25
RE11 RM MWS
72
17,9
81
Function Bw
Function Ad
Function Ah
Function N
Function O
Timing on closing
of control contact
"Safe-guard"
"Delayed safe-guard"
U
C
R
R
T
R
T
R
T
t<T T
Function P
Function Pt
Function T
Function Tt
Function W
Bistable relay
R
P
R
t1
t2
R
T
t<T
Multifunction
A - At - B - C - H - Ht - D - Di - Ac - Bw
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
RE11 RM MWS
8A
p
0.060
Multifunction
A - At - B - C - H - Ht - D - Di - Ac - Bw
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
RE11 RM JU
8A
p
0.060
521933
521931
521932
P = 500 ms
521931
T = t1 + t2 +
P = 500 ms
Multifunction
A - At - B - C - H - Ht - D - Di
1 s - 10 s - 1 min - 10 min - 1 h - 10 h
RE11 RME MU
5A
p
0.060
Multifunction
Ad - Ah - N - O - P - Pt - T - Tt - W
1 s - 10 s - 1 min - 10 min - 1 h - 10 h - 100 h
RE11 RMX MU
8A
p
0.060
Connection scheme
U
+
A1
Y1
A2
(1)
Y1
16
18
15
R
Characteristics :
pages 22 and 23
(1) Contact Y1 :
- Control for functions B, C, Ac, Bw, Ad, Ah, N, O, W, T, Tt.
- Partial stop for functions At, Ht and Pt.
- Function D if Di selected.
- Not used for functions A, H and P.
Dimensions :
page 24
27
Characteristics
Presentation
560872
The RE7 range of relays, with only 23 references, covers all timing applications.
These relays offer multi-range timing from 50 ms to 300 h.
They are multivoltage.
Three models combine several different functions: multifunction relays.
These products have a transparent, hinged flap on their front face to avoid any
accidental alteration of the settings. This flap can be directly sealed.
Environment
Conforming to standards
Product certifications
e marking
Ambient air temperature
around the device
Permissible relative
humidity range
Vibration resistance
Shock resistance
Degree of protection
Storage
Operation
Conforming to IEC 60721-3-3
Conforming
10 to 55 Hz
Conforming
Casing
Terminals
Conforming
Conforming
Conforming
Conforming
C
C
to IEC 6068-2-6,
a = 0.35 ms
to IEC 6068-2-27
15 gn - 11 ms
IP 50
IP 20
3
III
250
300
Degree of pollution
to IEC 60664-1
Overvoltage category
to IEC 60664-1
to IEC
Rated insulation voltage
Between contact circuit and
to CSA
power supply or between contact
circuit and control inputs
Test voltage for
Dielectric test
insulation tests
Shock wave
Voltage limits
Power supply circuit
Frequency limits
Power supply circuit
Disconnection value
Power supply circuit
Mounting position
In relation to normal
without derating
vertical mounting plane
Cabling
Flexible cable without cable end
Maximum c.s.a.
Flexible cable with cable end
Tightening torque
V
V
kV
kV
Hz
mm2
mm2
N.m
2.5
4.8
0.851.1 Uc
50/60 5 %
> 0.1 Uc
Any position
2 x 2.5
2 x 1.5
0.61.1
Conforming
Conforming
Conforming
Conforming
CISPR11
CISPR22
to IEC 61000-4-2
to IEC 61000-4-3
to IEC 61000-4-4
to IEC 61000-4-5
Consumption
Average consumption
References :
pages 30 to 33
28
a 50/60 Hz
24 V
48 V
110 V
VA
0.7
1.6
1.8
RE7-pp11BU
1.2
2
2.8
RE7-pp12BU and RE7-pp13BU VA
VA
2
2.5
3.2
RE7-ppppMW (1)
(1) RE7-RBppMW: current peak on energisation = 1 A / 30 ms.
240 V
8.5
12.5
6
W
W
W
c
24 V
0.5
0.8
2
48 V
1.2
1.6
1
110 V
3.2
240 V
Characteristics (continued)
Timing characteristics
Setting accuracy
Repeat accuracy
Influence of voltage
Influence of temperature
Immunity to microbreaks
Minimum control pulse
Reset time
10 %
0.2 %
< 0.2 %
< 0.07 %/C
3
20 (except RE7-RB1pMW: 1 s)
50
z 250
20
8 (except RE7-RBppMW: 5 A)
24 V
115 V
3
3
2
0.2
12 V/10 mA
90/10 nickel silver
(except RE7-RBppMU: gold flashed silver alloy)
V
A
A
A
250 V
3
0.1
Applicable to inputs
Y1Z2, X1Z2, X2Z2
Switching current
Maximum distance
Compatibility
mA
m
<1
50
3/4-wire PNP and NPN Telemecanique sensors or other sensors without an internal
load
Linear at 20 %
47 20 %
0.2
25 by shielded cable: shielding linked to terminal Z2
Curve 2
Reduction factor k for inductive loads (applies to
values taken from durability curve 1)
1
0,9
d.c. load
Load limit curve
Voltage in V
10
60
k
W
m
Reduction factor k
a.c. load
Curve 1
Electrical durability of contacts on resistive load
in millions of operating cycles
0,8
0,7
300
200
100
0,6
50
40
30
0,5
0,1
2
1
0,4
20
A
0,01
0,3
0
5
6
7
8
Current broken in A
0,8
10
0,1
A RE7-RBppMW
A
1
2
3
Example:
An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption
equal to 0.1 A and cos = 0.3.
For 0.1 A, curve 1 indicates a durability of approximately 1.5 million operating cycles.
As the load is inductive, it is necessary to apply a reduction coefficient k to this number of cycles as indicated
by curve 2.
A
0,2
0,5
10 20
Current in A
RE7-RBppMW
L/R = 20 ms
L/R with load protection diode
Resistive load
RE7
References :
pages 30 to 33
29
Functions,
references,
dimensions,
schemes
Function diagrams
Function A
Delay on energisation
Function At
Delay on energisation
with memory
Function Aw
Off-delay on energisation
or on opening of control
contact
R
T
R
t1
t2
T = t1 + t2 +
Function Ac
Timing after closing and
opening of control
contact
Function Ak
Asymmetrical On-delay
and Off-delay with
external control
R
t2
t1
t'1
R
t'2
t1
T = t1 + t2 +
T = t1 + t2 +
t2
t'1
t'2
Ta = t1 + t2 +
Tr = t1 + t2 +
Functions
Timing ranges
560874
560874
560873
560873
References
References
A
0.05 s300 h
10 ranges
p
p
RE7 TL11BU
A, Aw, At
0.05 s300 h
10 ranges
p
p
p
RE7 TM11BU
Ac
0.05 s300 h
10 ranges
p
p
p
RE7 MA11BU
Ak
0.05 s300 h
10 ranges
p
p
p
RE7 MV11BU
Weight (kg)
0.150
0.150
0.150
0.150
Voltages
c or a 24 V
a 110240 V
a or c 4248 V
c or a 24240 V
Screw fixing
78
6
78
80
89,5
82
Characteristics :
pages 28 and 29
30
Schemes :
pages 34 and 35
22,5
4
Function K
Delay on de-energisation
(without auxiliary supply)
Function C
Timing after opening
of control contact
Function H
Timing on energisation
Function Ht
Timing on energisation
with memory
Function W
On-delay after opening
of control contact
> 1 s (1)
U
R
T
R
t1
t2
T + t1 + t2 +
Function D
Symmetrical flashing,
start with output in
rest position
Function Di
Symmetrical flashing,
start with output in
operating position
Function L
Asymmetrical flashing,
start with output in
rest position
Function Li
Asymmetrical flashing,
start with output in
operating position
R1/R2
U
R
T
R
Tr
R2 inst.
(2)
Function Lt
Asymmetrical flashing
Ta
Ta
Tr
R
t1
t2 t1
t2
Tr = t1 + t2 +
Ta = t1 + t2 +
560877
H
0.05 s300 h
10 ranges
p
p
RE7 PE11BU
Ht, W
0.05 s300 h
10 ranges
p
p
p
RE7 PM11BU
D
0.05 s300 h
10 ranges
p
p
RE7 CL11BU
L, Li, Lt
0.05 s300 h
10 ranges
p
p
p
RE7 CV11BU
A, C, H, W, D, Di
0.05 s300 h
10 ranges
p
p
p
RE7 ML11BU
0.150
0.150
0.150
0.150
0.150
560908
560877
0.150
C
0.05 s300 h
10 ranges
p
p
p
RE7 RA11BU
RE7 RM11BU
low level contact
0.150
560876
K
0.05 s10 min
7 ranges
p
RE7 RB11MW
560876
560875
560875
(1) If the device has been stored, de-energised, for more than a month, it must be energised for about 15 seconds in order to activate it. Subsequently, it only takes
1 second to start the time delay. d If this time is not complied with, the relay remains energised indefinitely.
(2) 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.).
Connection schemes
A2
Characteristics :
pages 28 and 29
18
A2
Dimensions :
page 30
18
A2
X1
18
Z2
A2
X1
18
Y1
16
Z2
A2
18
A2
15
Z3
B1
B2
X1
18
X2
16
18
16
15
B1
B2
A1
15
16
16
A1
Z1
A2
B1
A1
15
RE7 CV11BU
18
18
15
A1
B1
B1
B2
RE7 CL11BU
A2
15
16
15
18
16
Y1
16
A1
Z1
B1
B2
A1
B1
B2
RE7 MA11BU
RE7 MV11BU
A2
15
B1
B2
A1
A1
Z1
18
15
16
RE7 TM11BU,
RE7 RA11BU
RE7 RM11BU,
RE7 PM11BU
A2
B1
A1
A2
15
16
16
15
B1
A1
16
15
RE7 PE11BU
18
A1
A1
15
16
18
16
A2
18
B1
A1
15
B1
A1
RE7 RB11MW
A2
RE7 TL11BU
Z2
A2
Schemes :
pages 34 and 35
31
Functions,
references,
dimensions,
schemes
Function diagrams
Function A
Delay on energisation
Function Ac
Timing after closing and
opening of control contact
Function C
Timing after opening
of control contact
R1/R2
R2
inst.
(1)
R1/R2
T
R1/R2
R2
inst.
(1)
R2
inst.
(1)
Function K
Delay on de-energisation
(without auxiliary supply)
> 1 s (2)
U
R1
R2
T
(1) 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.).
(2) If the device has been stored, de-energised, for more than a month, it must be energised for
about 15 seconds in order to activate it. Subsequently, it only takes 1 second to start the time
delay. d If this time is not complied with, the relay remains energised indefinitely.
Weight (kg)
0.150
Voltages
c or a 24 V
a 110240 V
a or c 4248 V
c or a 24240 V
Ac
0.05 s300 h
10 ranges
p
p
p
RE7 MA13BU
symmetrical
0.150
560904
560903
560902
References
A
0.05 s300 h
10 ranges
p
p
p
RE7 TP13BU
Functions
Timing ranges
560904
References
C
0.05 s300 h
10 ranges
p
p
p
RE7 RL13BU
low level contact
0.150
K
0.05 s10 min
7 ranges
p
RE7 RB13MW
0.150
Screw fixing
89,5
82
Characteristics :
pages 28 and 29
32
Schemes :
pages 34 and 35
22,5
78
6
78
80
Function D
Symmetrical flashing,
start with output in
rest position
Function Di
Symmetrical flashing,
start with output in
operating position
R1/R2
R1/R2
R2 inst. (1)
Function H
Timing on energisation
U
R1/R2
R2 inst. (1)
R2 inst. (1)
T T T T T T
Function Qg
Star-delta timing
Function Qt
Star-delta timing
Function W
On-delay after
opening of control contact
R1
R1
R2
R2
T
T
50 ms
R1/R2
T
50 ms
R2 inst. (1)
560908
560908
560907
560907
560906
560905
560905
(1) 2 timed outputs (R1/R2) or 1 timed output (R1) and 1 instantaneous output (R2 inst.).
H
0.05 s300 h
10 ranges
p
p
p
RE7 PP13BU
W
0.05 s300 h
10 ranges
p
p
p
RE7 PD13BU
D
0.05 s300 h
10 ranges
p
p
p
RE7 CP13BU
Qt
0.05 s300 h
10 ranges
p
p
p
RE7 YA12BU
Qg
0.05 s300 h
10 ranges
p
p
p
RE7 YR12BU
A, C, H, W, D, Di, Qg, Qt
0.05 s300 h
10 ranges
p
p
RE7 MY13BU
RE7 MY13MW
0.150
0.150
0.150
0.150
0.150
0.150
0.150
Connection schemes
Z2
A2
Z2
A2
28 (24)
18
Z2
A2
28 (24)
18
15
25
(21)
18
16
B1
B2
26
(22)
28
(24)
15
25 (21)
B1
B2
A1
25
(21)
26 (22)
16
A1
Z1
A2
15
18
16
B1
B2
26
(22)
28
(24)
15
25 (21)
B1
B2
A1
A1
Y1
A2
28
18
26
16
26
16
25
B1
B2
15
B1
B2
A1
28
18
26 (22)
16
Z2
A2
28 (24)
18
25
(21)
26
(22)
28
(24)
Y1
X1
15
15
25 (21)
18
25
(21)
26
(22)
28
(24)
Z2
A2
A1
Z1
16
15
26 (22)
16
Dimensions :
page 32
B1
Y1
18
16
A1
28 (24)
18
15
25
RE7 PP13BU
RE7 CP13BU
RE7 MY13MW
15
25 (21)
A2
28
B1
17
Characteristics :
pages 28 and 29
26
18
26
16
A1
Z1
A2
25
28
Z2
A2
RE7 MY13BU
16
A2
28
18
26
16
A1
B1
B2
B1
B2
A1
A1
28
18
A2
17
17
RE7 YR
15
A1
A2
Z2
A2
A1
15
25
18
25
(21)
26 (22)
16
RE7 YA
26
15
18
16
A2
28 (24)
18
A1
Z1
B1
B2
26
(22)
28
(24)
15
25 (21)
B1
B2
A1
A1
Z1
RE7 RB13MW
16
RE7 TP13BU
26 (22)
16
Z2
A2
Schemes :
pages 34 and 35
33
Schemes
RE7 RB
Start on de-energisation
Z2
B1
B2
A1 X1
A2
Z2
B1
A1
A1
A2
B2
Y1
A2
B1 Y1
Y1
A2
RE7 PE
Start on energisation
A2
B2
B3
A2
B1
B2
A1 X2
A2
Z2
RE7 MV
RE7 CV
Connection of potentiometers to
asymmetrical timing relays
Connection of potentiometers
A2
Z3
Z1
Z2
(4)
(5)
A2
Z3
Z1
Z2
No galvanic isolation between supply terminals A1, A2, B1, B2 and control inputs X1, Y1, Z1, Z2.
(1) a 110240 V except RE7 MY13MW : z 24240 V
(2) z 1248 V
(3) z 24 V
(4) Adjustment of the On-delay period
(5) Adjustment of the Off-delay period
(6) Start during the On-delay period : X2, Z2 linked. Start during the Off-delay period : X2, Z2 not linked
(7) Off-delay adjustment (tr) (contact 15/16 closed)
(8) On-delay adjustment (ta) (contact 15/18 closed)
Characteristics :
pages 28 and 29
34
References :
pages 30 to 33
(7)
(6)
Connection precautions
(8)
X1 or Y1 or Z1
Supply
A2
B1
(3)
A2
RE7 CV
Selection of starting phase
(1)
(2)
A1
(1)
(3)
(3)
(1)
(2)
RE7 PP
Start on energisation
Z1
Z2
Z2
B2
A1 X1
A2
RE7 RA
Start by external control
B1
B2
(3)
A1 Y1
A2
(2)
B2
(1)
(3)
B1
(3)
A1
A2
(2)
B2
(1)
(3)
(2)
(1)
B1
(2)
Start on energisation
(1)
A2
Z2
Schemes (continued)
22 25
A1
K1T
Y
Control schemes
Star-delta function with contact for switching to star connection Q
Terminal block
K1
K3
28
18
13
A1
K2
A2
K1T
U2
Z2
A2
A2
A1 21
A1
W2
26
16
14
K1
A2
U1
M1
3
A2
V1
B1
B2
K1
14
22 28
K3
A1 21
22 18
K2
V2
W1
13
17
17
54
14
K1T
F2
16
A2
53
13 22
5
6
28
18
K2
S2
6
5
4
3
K1
K3
S1
K2
17
17
B1
B2
A1
21 96
F2
26
95
A1
17
F3
L3
L2
L1
Power scheme
RE7 YR12BU
18
K3
A2
A2
K2
A2
K1
U2
A1
W2
A1 21
K1
A2
M1
3
16
A2
14
16
22 15
K3
A1 21
V1
U1
Z2
A2
K1T
V2
W1
26
16
28 13
14
14 K1 13
K1T
F2
28
18
K2
15
B1
B2
A1
21 96
13 22
5
6
S2
6
5
4
3
2
1
K1
K3
K2
S1
B1
B2
25
15
25
F2
28
95
A1
26
F3
L3
L2
L1
Power scheme
RE7 YA12BU
No galvanic isolation between supply terminals A1, A2, B1, B2 and supply terminal Z2.
This terminal must therefore never be used (factory setting).
Control of several relays with a single external control contact
Connection of a Telemecanique 3-wire NPN or PNP sensor
A1,B1 or B12
Y1 or X1
Z2
A2
A1,B1 or B12
Y1 or X1
Z2
A2
A1,B1 or B12
Y1 or X1
Z2
A2
Supply
Supply
+
A1,B1 or B12
Y1 or X1
A2 Z2
BN
BK
BU
NPN
PNP
It is advisable to follow the recommended wiring schemes detailed above and on previous pages. However, the connections below are possible if the restrictions
given are taken into account.
Connection of an external control contact without using terminal Z2:
Connection of a Telemecanique 3-wire NPN or PNP sensor without using
terminal Z2:
- possible on all RE7 relays with external control option except RE7 RA11BU,
- only possible on relay RE7ppppBU,
- d.c. supply only.
- d.c. supply only.
+
A1,B1 or B12
Y1 or X1
Z2
A2
Characteristics :
pages 28 and 29
A1,B1 or B12
Y1 or X1
A2
Z2
24
or
48 V
+
B1B2
A2
Y1
Z2
BN
BK
BU
NPN
24
or
48 V
B1B2
A2
Y1
Z2
BN
BK
BU
PNP
References :
pages 30 to 33
35
Characteristics
Presentation
560953
The RE8 range of relays is designed for simple and repetitive applications, providing
basic functions.
Each relay comprises:
- a single timing range,
- a C/O output relay.
These products have a transparent, hinged flap on their front face to avoid any
accidental alteration of the settings. This flap can be directly sealed.
Environment
Conforming to standards
Product certifications
e marking
Ambient air temperature
around the device
Permissible relative
humidity range
Vibration resistance
Shock resistance
Degree of protection
Degree of pollution
Overvoltage category
Rated insulation voltage
Test voltage for
insulation tests
Voltage limits
Frequency limits
Disconnection value
Mounting position
without derating
Connection
maximum c.s.a.
Storage
Operation
Conforming to IEC 60721-3-3
Conforming to IEC 6068-2-6,
10 to 55 Hz
Conforming to IEC 6068-2-27
Casing
Terminals
Conforming to IEC 60664-1
Conforming to IEC 60664-1
Conforming to IEC
Conforming to CSA
Dielectric test
Shock wave
Power supply circuit
Power supply circuit
Power supply circuit
In relation to normal
vertical mounting plane
Flexible cable without cable end
Flexible cable with cable end
Tightening torque
C
C
V
V
kV
kV
Hz
mm2
mm2
N.m
15 gn - 11 ms
IP 50
IP 20
3
III
250
300
2.5
4.8
0.91.1 Uc
50/60 5 %
> 0.1 Uc
Any position
2 x 2.5
2 x 1.5
0.61.1
Conforming
Conforming
Conforming
Conforming
CISPR11
CISPR22
to IEC 61000-4-2
to IEC 61000-4-3
to IEC 61000-4-4
to IEC 61000-4-5
Consumption
Consumption
RE8-TA, RA, CL, PE, PU, PT
RE8-YG, RB
RE8-YA
References :
pages 38 to 41
36
Dimensions :
pages 38 and 40
VA
VA
VA
a
24 V
0.7
0.9
0.9
Schemes :
page 39
110 V
1.8
2.5
2.5
240 V
8.5
13
13
380 V
415 V
W
W
W
c
24 V
0.5
0.5
0.7
Characteristics (continued)
Timing characteristics
Setting accuracy
Repeat accuracy
Influence of voltage
Influence of temperature
Immunity to microbreaks
Minimum control pulse
Reset time
20 %
<1 %
< 2.5 %
< 0.2 %/C
3
26 (except RE8-YG: 60)
50
V
A
A
A
z 250
20
8
24 V
3
2
12 V/10 mA
90/10 nickel silver
115 V
3
0.2
250 V
3
0.1
10
Supply voltage
< 10
50
2-wire sensors c with leakage current < 1 mA
Curve 2
Reduction factor k for inductive loads (applies to
values taken from durability curve 1)
Reduction factor k
a.c. load
Curve 1
Electrical durability of contacts on resistive load
in millions of operating cycles
mA
m
d.c. load
Load limit curve
Voltage in V
1
0,9
0,8
0,7
300
200
100
0,6
50
40
30
0,5
0,1
2
1
0,4
20
A
0,01
0,3
0
5
6
7
8
Current broken in A
0,8
0,6 0,5 0,4
0,3
Power factor on breaking (cos )
10
0,1
0,2
A RE8-RBppBUTQ
A
1
2
3
A
0,2
0,5
10 20
Current in A
RE8-RBppBUTQ
L/R = 20 ms
L/R with load protection diode
Resistive load
Example:
An LC1-F185 contactor supplied with 115 V/50 Hz for a consumption of 55 VA or a current consumption
equal to 0.1 A and cos = 0.3.
For 0.1 A, curve 1 indicates a durability of approximately 1.5 million operating cycles.
As the load is inductive, it is necessary to apply a reduction coefficient k to this number of cycles as indicated
by curve 2.
For cos = 0.3: k = 0.6
The electrical durability therefore becomes:
1.5 106 operating cycles x 0.6 = 900 000 operating cycles.
References :
pages 38 to 41
Dimensions :
pages 38 and 40
+
RE8
Schemes :
page 39
37
Functions,
references,
dimensions,
schemes
Function diagrams
Function A
Delay on energisation
Function C
Timing after opening of control contact
U
C
R
T
R
T
Functions
Voltages
Timing ranges
c or a 24 V
a 110240 V
a 380415 V
0.05 s0.5 s
0.1 s3 s
0.1 s10 s
0.3 s30 s
3 s300 s
20 s30 min
Weight (kg)
560954
560954
A
p
p
RE8 TA61BUTQ
RE8 TA11BUTQ
RE8 TA31BUTQ
RE8 TA21BUTQ
RE8 TA41BUTQ
0.110
C
p
RE8 RA11BTQ
RE8 RA31BTQ
RE8 RA21BTQ
0.110
RE8 RA11FUTQ
RE8 RA31FUTQ
RE8 RA21FUTQ
RE8 RA41FUTQ
0.110
Dimensions
Dimensions
Rail mounting
Screw fixing
89,5
82
Characteristics :
pages 36 and 37
38
Schemes :
page 39
22,5
78
6
78
80
Function K
Delay on de-energisation (without auxiliary supply)
Function D
Symmetrical flashing, start with output in rest position
> 1 s (1)
U
R
R
T
560954
560954
(9) If the device has been stored, de-energised, for more than a month, it must be energised for about 15 seconds in order to activate it. Subsequently, it only takes
1 second to start the time delay. d If this time is not complied with, the relay remains energised indefinitely.
K
p
p
RE8 RB51BUTQ
RE8 RB11BUTQ
RE8 RB31BUTQ
0.110
D
p
p
RE8 CL11BUTQ
0.110
Schemes
Connection schemes
RE8 TA, CL
RE8 RB
RE8 TA, CL
RE8 RA
+
15
B1
start
B1
18
16
A1
15
16
15
A2
A1
Y1
A2
A1
18
16
15
B1
A1
18
B1
15
A2
15
A1
B1
A1
A2
A2
A1
18
16
A2
18
16
18
A2
16
A1 Y1
A2
+
A1
Y1
A2
A1
A2
Y1
A1
Y1
If
A1
A2
Y1
A2
Characteristics :
pages 36 and 37
Dimensions :
page 38
39
Functions,
references,
dimensions,
schemes
Function diagrams
Function H
Timing on energisation
Function W
On-delay after opening of control contact
T
R
Functions
Voltages
c or a 24 V
a 110240 V
a 380415 V
0.05 s0.5 s
0.1 s3 s
0.1 s10 s
0.3 s30 s
3 s300 s
20 s30 min
Timing ranges
Weight (kg)
560968
560968
H
p
p
RE8 PE11BUTQ
RE8 PE31BUTQ
RE8 PE21BUTQ
0.110
W
p
RE8 PD11BTQ
RE8 PD31BTQ
RE8 PD21BTQ
0.110
RE8 PD11FUTQ
RE8 PD31FUTQ
RE8 PD21FUTQ
0.110
Dimensions, schemes
Dimensions
Rail mounting
Screw fixing
78
78
80
22,5
89,5
82
Schemes :
page 41
A2
18
16
A2
15
18
B1
16
18
16
15
B1
A2
A1
A1
A1
25
28
25
15
A2
15
16
15
28
A1
RE8 YG
16
B1
A2
15
18
15
16
A1
16
A1
16
Y1
RE8 YA
B1
A2
18
15
A1
A2
15
16
Characteristics :
pages 36 and 37
40
A1
18
16
A1
18
B1
RE8 PT
A2
15
B1
A2
A1
RE8 PD
18
RE8 PE
A2
Function He
Pulse-on de-energisation
Function Qc
Star-delta timing
Function Qe
Star-delta timing
R1
> 80 ms T 80 ms
>T
50 ms
R2
80 ms
He
p
p
RE8 PT01BUTQ
0.110
560969
560968
560969
Qc
p
p
RE8 YG11BUTQ
RE8 YG31BUTQ
RE8 YG21BUTQ
0.110
Qe
p
RE8 YA32BTQ
0.110
RE8 YA32FUTQ
0.110
RE8 YA32QTQ
0.110
RE8 PD
+
start
B1
A1 Y1
A2
A2
A1
RE8 YG
RE8 YA
L3
L1
L2
Q1
25
15
A1
A1
A2
A2
28
A1
A1
A2
(1)
A2
A1
A2
A1
A1
(1)
15
A2
A1
A2
W2
V2
U2
Rth
16
(1)
16
A2
W1
V1
U1
KM1
KM3
KM2
Characteristics :
pages 36 and 37
Dimensions :
page 40
41
Characteristics
Timing characteristics
Repeat accuracy (with constant parameters)
Full scale setting accuracy
Conforming to IEC/EN 61812-1
Temperature drift
Maximum reset time
During time delay period
by de-energisation
After time delay period
Immunity to microbreaks
Voltage drift
ms
ms
ms
0.5 %
10 % at 25 C
0.05 %/ C
50
250
5
0.2 % / V
Output characteristics
Output type
Relay
Rated current
Rated insulation voltage
Maximum breaking capacity (resistive)
Maximum permissible current
Minimum breaking current
Electrical life at I max a 250 V resistive
Mechanical life
Dielectric strength
To IEC/EN 61812-1 and 60601-1
A
V
A
A
mA
General characteristics
Conforming to standards
Product certifications
State indication by LED
Output in operation
Power on
Permissible voltage variation
c 12 V
c 24 V
a 24 V
a 120 V
a 230 V
Frequency
Maximum power consumption
c 12 V
c 24 V
a 24 V
a 120 V
a 230 V
Temperature limits
Operation
Storage
Insulation voltage
To standard VDE 0010
IEC 255 Group C
Degree of protection
Conforming to IEC 60529
Overvoltage protection
Fixing
Base-mounted
Vibration resistance
Conforming to IEC 60068-2-6,
10 to 55 Hz
Relative humidity
Conforming to IEC 60068-2-3
without condensation
Hz
W
W
VA
VA
VA
C
C
V
joules
Internal schemes
Relay with 4 C/O contacts
+ 14
- 13
References :
page 43
42
Dimensions :
page 43
10
1 6
2 7
+ 14
12
3 8
- 13
12
1 8
Functions,
references,
dimensions
Function diagrams
Function A
Delay on energisation
4 timed C/O contacts
13-14
13-14
1-5-9
1-5-9
2-6-10
4-8-12
T
3-7-11
4-8-12
T
Functions
Timing ranges
Relay output
Rated current
Voltages
7 switchable ranges
c
c
a
a
a
12 V
24 V (1)
24 V 50/60 Hz (1)
120 V 50/60 Hz
230 V 50/60 Hz
Weight (kg)
Sockets (2) with
mixed contact terminals (3)
532536
532535
References
Single function
A
0.1 s1 s - 1 s10 s - 0.1 min1 min - 1 min10 min - 0.1 h1 h - 1 h10 h - 10 h100 h
4 timed C/O contacts
2 timed C/O contacts
a 3A
a 5A
RE XL4TMJD
RE XL2TMJD
RE XL4TMBD
RE XL2TMBD
RE XL4TMB7
RE XL2TMB7
RE XL4TMF7
RE XL2TMF7
RE XL4TMP7
RE XL2TMP7
0.050
0.050
RXZ E2M114 (5)
RXZ E2M114 (5)
0.048
0.048
RXZ E2M114M (5)
RXZ E2M114M (5)
0.056
0.056
RXZ E2S108M (6)
RXZ E2S108M (6)
0.058
0.070
(1) For c 48 V supply, additional resistor 560 2 W / c 24 V.
For a 48 V supply, additional resistor 390 4 W / a 24 V.
(2) These products are sold in lots of 10.
(3) The inputs are mixed with the relays supply terminals, with the outputs being located on the
opposite side of the socket.
(4) The inputs and outputs are separated from the relay supply terminals.
(5) Thermal current Ith: 10 A
(6) Thermal current Ith: 12 A
Terminal referencing
RE XL4TMpp
21
3,5
21
65,5
27
27
0,55
1 2 3 4
5 6 7 8
9 101112
13
14
(-)
R
(+)
Un
59,5
RE XL2TMpp
21
27
2,8
1,2
1
5
9
13
0,3
(-)
Characteristics :
page 42
4
8
12
14
(+)
Schemes :
page 42
43
Presentation
Presentation
The range of RE 48A timing relays, in 48 x 48 housing, is specially designed for
integration in machines and equipment. It is suitable for applications requiring
frequent modification or adjustment of the timing cycles.
RE 48A relays have the following characteristics:
b All references are multivoltage 24 to 240 V a and c and are therefore suitable
for the majority of applications while at the same time reducing the number of
products to be stocked.
b The timing ranges covered are from 0.02 s to 300 h.
b These timing relays can be panel-mounted using the spring clip supplied as
standard, or DIN rail-mounted using standard sockets.
b
v
v
v
Two LED's on the front face provide immediate indication of the timing status:
power ON,
output relay state,
timing in progress.
The size of the knob and clear indication of the timing scale allow easy adjustment,
eliminating any errors during parameter setting.
In addition, in applications where only the timing cycle value is left freely accessible
to users, a protective cover can be used to block access to the other settings.
This range is comprises 4 references:
Reference
RE 48A TM12MW
Description
Single function
v On-delay
v two relay outputs
RE 48A CV12MW
Dual function
v asymmetrical flasher
v two relay outputs
RE 48A MH13MW
Multifunction
v On-delay and pulse-on energisation
v two relay outputs, of which one selectable and
instantaneous
RE 48A ML12MW (1)
Multifunction
v On-delay
v timing on impulse
v Off-delay
v symmetrical flasher
(1) This relay features control inputs which provide a wider choice of timing modes:
Start Input to control the start of timing,
Gate Input to suspend the timing in progress without cancelling it,
Reset Input to reset timing to its initial state during the cycle.
Characteristics :
pages 46 and 47
44
Function diagrams :
page 48
References :
pages 49 and 50
Dimensions :
pages 49 and 50
Mounting :
page 51
Description
521934
Description
1
RE 48A TM12 MW timing relays have the following on the front face :
1
2
3
4
5
521935
RE 48A CV12 MW timing relays have the following on the front face :
1
521936
RE 48A Mp1p MW timing relays have the following on the front face :
1
Characteristics :
pages 46 and 47
Function diagrams :
page 48
References :
pages 49 and 50
Dimensions :
pages 49 and 50
Mounting :
page 51
45
Characteristics
General characteristics
Conforming to standards
Approvals
Storage
Operation
Degree of protection
conforming to IEC 60529
Housing
Front face
IP 40
IP 50
Vibration resistance
f = 1055 Hz
A = 0.35 mm
93 %
C
C
Relative humidity
Conforming to IEC 60068-2-3
without condensation
Electromagnetic compatibility Immunity to
electrostatic discharge,
conforming to IEC/EN 61000-4-2
Immunity to
electromagnetic fields
conforming to IEC/EN 61000-4-3
Immunity to
fast transients in bursts,
conforming to IEC/EN 61000-4-4
Immunity to
surges on the power supplies,
conforming to IEC 61000-4-5
Immunity to radio frequency
interference in common mode,
conforming to IEC/EN 61000-4-6
Immunity to
voltage dips and breaks,
conforming to IEC/EN 61000-4-11
30 % / 10 ms
60 % / 100 ms
95 % / 5 s
60 % / 1 s
Class B (0.15...30 MHz)
Fixing
- 40+ 70
- 20+ 50
Connection
By socket or connector
Housing material
Self-extinguishing
Input characteristics
Type of input
by volt-free contact
Start: starts the function (only for functions A, B, C and Di on RE 48A ML12 MW)
Gate: stops timing in progress
Reset: resets the relay, output to OFF
Output characteristics
Output type
Contact type
Breaking capacity
Maximum breaking current
Minimum breaking current
Maximum switching voltage
Electrical durability
Mechanical durability
Dielectric strength
Conforming to IEC 61812-1
Electric shock resistance
Conforming to
IEC 60664-1, IEC 61812-1
Rated operational voltage
a AC-12
a AC-15
c DC-13
Presentation, description :
pages 44 and 45
46
Function diagrams :
page 48
VA
A
mA
V
kV
kV
Relay with 2 timed changeover contacts (except RE 48A MH13 MW: relay with
1 timed changeover contact and 1 instantaneous changeover contact)
AgNi (cadmium-free)
a 1250
a 5 for 250 V
100/c 12 V
a/c 250
105 operations
30 x 106 operations
1/1min
4, category 3
Ue = 240 V and Ie = 5 A
Ue = 240 V and Ie = 1.5 A
Ue = 30 V and Ie = 2 A
References :
pages 49 and 50
Dimensions :
pages 49 and 50
Mounting :
page 51
Characteristics
Supply characteristics
Supply voltage
a/c 24240
Frequency
Hz
50/60
a - 15 %...+ 10 %
c - 10 %...+ 10 %
100 %
Operating range
On-load factor
Maximum
power consumption
Depending
on model
c 24 V
a 24 V
c 240 V
a 240 V
W
VA
W
VA
0.5
1.1
1.7
4.8
0.021.2
0.053
0.212
0.530
2120
5300
0.212
0.530
2120
5300
0.212
0.530
2120
5300
Timing characteristics
Selectable timing ranges
by selector switch on front face
min
Repeat accuracy
(with constant parameters)
Drift
conforming to IEC 61812-1
Time unit
x 0.1 s
x 0.1 s
x1s
x1s
x 10 s
x 10 s
x 1 min
x 1 min
x 10 min
x 10 min
x1h
x1h
x 10 h
x 10 h
Time scale
12
30
12
30
12
30
12
30
12
30
12
30
12
30
Temperature
Humidity
Voltage
ms
20
ms
25
Delay on pick-up
ms
55
Immunity to microbreaks
ms
< 10
Display characteristics
State indication
Green LED
Yellow LED
Presentation, description :
pages 44 and 45
Function diagrams :
page 48
References :
pages 49 and 50
Dimensions :
pages 49 and 50
Mounting :
page 51
47
Functions
Function diagrams
RE 48A TM12 MW
RE 48A CV12 MW
Function A
Delay on energisation
Function L
Asymmetrical flashing, start with output in
rest position
Un
Un
Gate
Gate
2-6
Nor / Inv
2-6
Nor / Inv
Un
R
Function Li
Asymmetrical flashing, start with output in
operating position
R
Ton
Toff
Ton
Toff t1
Toff = t1+t2+t3
t2
t3
Ton
tb
ta tc
Toff
Ton
Toff
Ton = ta+tb+tc
t2
t1
tb
t3 ta
Ton = t1+t2+t3
t1
Toff = ta+tb+tc
RE 48A ML12 MW
Function A
Delay on energisation
Function B
Timing on impulse, one shot
Un
Un
Start
Start
Gate
Gate
Reset
Reset
t1
t3
t2
T = t1 + t2 + t3
Function C
Timing after opening of control contact
Function Di
Symmetrical flashing, start with output in operating position
Un
Un
Start
Start
Gate
Gate
Reset
Reset
Output
Output
t3
T t1
T TT
TT T
t1
t2
T TT
TTT
TTT T
t1t2
t2
T = t1 + t2
T = t1 + t2 + t3
RE 48A MH13 MW
Functions A1, A2
Delay on energisation
Functions H1, H2
Pulse-on energisation
Un
Un
R2
R2
R1
R1
Presentation, description :
pages 44 and 45
48
t2
T = t1 + t2 + t3
t3
t1
Characteristics :
pages 46 and 47
References :
pages 49 and 50
Dimensions :
pages 49 and 50
Mounting :
page 51
TTT
References,
dimensions
Plug-in
Functions
521939
521939
8-pin
11-pin
11-pin
8-pin
Single function
Dual function
Multifunction
Multifunction
A
L, Li
A, B, C, Di
A1, A2, H1, H2
1.2 s, 3 s, 12 s, 30 s, 120 s, 300 s, 12 min, 30 min, 120 min, 300 min, 12 h, 30 h, 120 h, 300 h
2 C/O timed contacts 2 C/O timed contacts 2 C/O timed contacts 1 C/O timed contact
1 C/O instantaneous
contact
2x5A
2x5A
2x5A
2x5A
RE 48A TM12 MW
RE 48A CV12 MW
RE 48A ML12 MW
RE 48A MH13 MW
0.140
0.140
0.140
0.140
Timing ranges
Relay output
Rated current
Voltages
Weight (kg)
521938
521937
References
a/c 24240 V
Dimensions
6,8
Presentation, description :
pages 44 and 45
64,5
96,8
15,5
Characteristics :
pages 46 and 47
48
39
44,4
RE 48A pp 1p MW
48
Mounting :
page 51
49
References,
dimensions
References
Description
Number
of pins
8
For
Sold in Unit
use with
lot of reference
RE 48A TM12 MW, 10
RUZ C2M
RE 48A MH13 MW
11
RUZ C3M
11
IP 20 socket
with screw terminal
connections on rear
face
IP 20 solder
8
connectors
RE 48A SOC11 AR
11
RE 48A TM12 MW 1
RE 48A CV12 MW
RE 48A ML12 MW
RE 48A MH13 MW
RE 48A TM12 MW 1
RE 48A CV12 MW
RE 48A ML12 MW
RE 48A MH13 MW
RE 48A IP COV
IP 20 sockets
with screw terminal
connections and
mixed contact
terminals (1)
RUZ C3M
Weight
kg
0.054
0.054
RE 48A SOC11 AR
Setting protection
cover
RE 48ASOC11 SOLD
RE 48A IP COV
(1) The inputs are mixed with the relays supply terminals, with the outputs being located on the
opposite side of the socket.
Dimensions
Common side view
8-pin socket
11-pin socket
RUZ CpM
RUZ C2M
RUZ C3M
22
24
6
22
5
12 14
4
34
32
24
2x3,1
5
4
8
75
A2
7
27
21
7
11
8
2x3,1
3
1
INPUT A1
2
INPUT A2
10
A1
1
2
11
A2 A2
2
31 21
10 10
30
11
37
A2
37
INPUT A1
2
12
10
INPUT A2
7
22 14
11 A1
6
30
38
38
11-pin socket
8-pin connector
11-pin connector
RE 48A SOC11 AR
30
46
30
20
Presentation, description :
pages 44 and 45
50
46
Function diagrams :
page 48
34
Characteristics :
pages 46 and 47
34
Mounting,
schemes
Mounting
Cover positioning and mounting
Panel cut-out
(1)
30
15
(2)
(3)
17
20
e : panel thickness
(1) IP 64 protective cover: RE 48A IP COV
(2) Panel mounting frame
(3) Locating screw
Connection schemes
RE 48A TM12 MW
RE 48A CV12 MW
Reset
4 5
1 8
Gate
4 5 6 7 8
3
2
9
10
1 11
Presentation, description :
pages 44 and 45
4 5
Start
6
R
RE 48A MH13 MW
U
3
2
RE 48A ML12 MW
Function diagrams :
page 48
Gate
3
4 5 6 7 8
3
2
R1
2
R2
7
1 8
9
10
1 11
Characteristics :
pages 46 and 47
51
A worldwide presence
Constantly available
b More than 5 000 points of sale in 130 countries.
b You can be sure to find the range of products that are right for you and which
complies fully with the standards in the country where they are used.
ART. 815131
Simply Smart !
Due to evolution of standards and equipment, the characteristics indicated in texts and images of this
document do not constitute a commitment on our part without confirmation.
Design: Schneider Electric
Photos: Schneider Electric
Printed by:
01 / 2006
DIA3ED2051205EN