Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
PRO-XXX-YYY-NN
7
Revision No: xx
dd/mm/yyyy
1 of
of
of
of
of
temperature-rise limits.
the dielectric properties.
the short-circuit strength.
the continuity of the protective
These tests may be carried out in any order and/or on different samples of the
same type.
5.1.1.2. Routine Tests:
Routine tests are intended to detect faults in materials and workmanship. They
are carried out on every new ASSEMBLY after its assembly or on each transport
unit. Another routine test at the place of installation is not required.
ASSEMBLIES which are assembled from standardized components outside the
works of the manufacturer of these components, by the exclusive use of parts
and accessories specified or supplied by the manufacturer for this purpose, shall
be routine-tested by the firm which has assembled the ASSEMBLY.
Routine tests include:
Specification limits should be as perIS 8623- part 1:
5.1.1.2.1.
Inspection of the ASSEMBLY including
inspection of wiring and, if necessary, electrical
operation test.
We have to verify the assembly of control panel as
per approved BOM, GA and schematic diagram.
PRO-XXX-YYY-NN
7
Revision No: xx
dd/mm/yyyy
2 of
Dielectric test.
Requirement of Equipments for testing:
HV tester- (0-5) KV
5.1.1.2.2.2.
Testing procedure:
The test voltage shall be applied:
5.1.1.2.2.2.1.
Between all live parts and the
interconnected exposed conductive parts of the
ASSEMBLY;
5.1.1.2.2.2.2.
Between each pole and all the other poles
connected for this test to the interconnected
exposed conductive parts of the ASSEMBLY.
The test voltage at the moment of application shall not exceed 50% of the values
given in test voltage selection table that given below. It shall then be increased
steadily within a few seconds to this full value specified in the table and
maintained for 1 min. The a.c. power sources shall have sufficient power to
maintain the test voltage irrespective of any leakage currents. The test voltage
shall have a practically sinusoidal waveform and a frequency between 45 Hz and
62 Hz.
5.1.1.2.2.3.
Results to be obtained:
PRO-XXX-YYY-NN
7
Revision No: xx
dd/mm/yyyy
3 of
PRO-XXX-YYY-NN
7
Revision No: xx
dd/mm/yyyy
4 of
Minimum cross-sectional
area of the corresponding
protective conductor S( mm2)
S
16
S/2
Revision No: xx
dd/mm/yyyy
5 of
The following measurements shall be recorded from the test data obtained
during the temperature- rise test:
V= the average r.m.s. line to line voltage drop in volts.
V12 + V23 + V31
V=
3
I= the average r. m. s. current in amperes
I1 + I2 + I3
I=
3
P = the total three- phase power in watts.
L= the length in metres from the voltmeter leads connected at the input end to
the point where the bus bars are connected together at the output end.
Calculate the impedance Z, the alternating current resistance R, and the
reactance X, in ohms per metre on line to neutral basis, as follows:
V
Z=
3 I L
P
R =
PRO-XXX-YYY-NN
7
Revision No: xx
3 I2 L
dd/mm/yyyy
6 of
X= (Z 2 R2)
0.5
Incoming Inspection shall be done as per the Incoming material site Inspection
report F-CO-QA06-02 & observation shall be recorded on it.
5.3.
Site acceptance test as per Vendor or Greenko- Inspection and test plan and
observation shall be recorded on Check list for erection of Control panel- F-COQA-16-01.
6. RECORDS:
6.1.Material Quality Inspection report
6.2.Incoming material site Inspection report 6.3.Erection Checklist of Control panel
-
PRO-XXX-YYY-NN
7
Revision No: xx
F-CO-QA06-01.
F-CO-QA06-02.
F-CO-QA-16-01.
dd/mm/yyyy
7 of