SOLUTION AIR HANDLING UNIT

PERFORMANCE SPECIFICATION
Unit Tag
UMA-02

Qty
1

Model
Solution Indoor Air Handler 39 x 33

Air Flow (CFM)


1490

Unit Sequence
Tier 2

MZ-2
T

Tier 1

MZ-1 <<< HF
T

<<< XA <<<

DI

<<<

FS

<<<

RF

<<<

IP

Basic Unit Options


Insulation Type:
Base Rail Height:
Performance:

(Refer to Each Segment)


None
High Performance

Unit Special Quotes


None
*Note:Component locations are listed as Segment Hand (Unit Hand) : ex. Left (Right)
See Submittal Drawing for additional details

Segments Listed Starting At Air Inlet


IP Inlet Plenum
Inlet Plenum Details
Opening:
Segment Air Pressure Drop (in. w.g.)

Front(Front)
0.16

Inlet Plenum Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

Project Name: Idsaa-CentroMedicoMorelos


Printed: 11/28/2012 17:18:46
Unit Folder: UMA-02

10/03/2012 12:26:49 PM

York Contract No.:


UMA-02Performance
Page 1 of
10

SOLUTION AIR HANDLING UNIT


PERFORMANCE SPECIFICATION
Unit Tag
UMA-02

Qty
1

Model
Solution Indoor Air Handler 39 x 33

Air Flow (CFM)


1490

RF High Efficiency Filter Segment


Filter Media Details
(Quantity)Filter Sizes:
Filter Area (ft)
Filter Loading:
Prefilter Depth:
Prefilter Media:
Prefilter Air Pressure Drop (in. w.g.):
Prefilter Dirty Allowance (in. w.g.):
High Eff. Filter Depth:
High Eff. Filter Media:
High Eff. Filter Air Pressure Drop (in. w.g.):
High Eff. Filter Dirty Allowance (in. w.g.):

(1)24x24
4.0
Side
2"
Pleated 30%
(MERV 7)
0.19
0.00
21" Bag
60-65% Eff,
(MERV 12)
0.27
0.00

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33H x 18W
Standard Door Latch, No Lock, Outward Opening
Optimized Filter Arrangement

Project Name: Idsaa-CentroMedicoMorelos


Printed: 11/28/2012 17:18:46
Unit Folder: UMA-02

10/03/2012 12:26:49 PM

York Contract No.:


UMA-02Performance
Page 2 of
10

SOLUTION AIR HANDLING UNIT


PERFORMANCE SPECIFICATION
Unit Tag
UMA-02

Qty
1

Model
Solution Indoor Air Handler 39 x 33

FS - Supply Fan Segment


Segment Details
Segment Air Pressure Drop (in. w.g.):
0.00
Air Flow (CFM):
1490
Altitude (ft.):
3000
TSP/ESP (in. w.g.):
3.22/ 1.00
Air Inlet:
Front(Front)
Fan Discharge:
Rear Inverted(Rear)

Air Flow (CFM)


1490

Fan Segment Options


1" Spring Isolator
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33H x 18W
Standard Door Latch, No Lock, Outward Opening

Fan Detail
Type:
Size:
Construction:
Bearing Options:
Fan RPM:
BHP:
Fan BHP w/ Belt Loss:
Outlet Velocity (ft/min):

FC
10-7
S
Permanent Seal
1869
1.30
1.42
1624

Motor Detail
Motor Type:
TECO ODP Premium Efficiency
HP
3.0
Voltage/Phase/Frequency:
230/3/60 Hz
Motor RPM:
1800
Frame Size:
182
Location:
Left(Left)
Drive Type:
Belt Drive Type:
Full Load Amps (FLA):
Efficiency:

Belt Drive
Fixed
8.60
89.5%

Project Name: Idsaa-CentroMedicoMorelos


Printed: 11/28/2012 17:18:46
Unit Folder: UMA-02

10/03/2012 12:26:49 PM

York Contract No.:


UMA-02Performance
Page 3 of
10

SOLUTION AIR HANDLING UNIT


PERFORMANCE SPECIFICATION
Unit Tag
UMA-02

Qty
1

Model
Solution Indoor Air Handler 39 x 33

Air Flow (CFM)


1490

Motor Control Supply Fan


Motor Control Details
Motor Control Type:
Variable Frequency Drive
Motor HP:

Motor Control Electrical Details


Full Load Amps (FLA):

11.8

3.0

Motor Control Options


Non Fused Disconnect
Isolated Manual Bypass with VFD service input switch
RFI/EMI EMC Filter
Swinging DC Line Choke (equivalent to 5% Input Line
Reactor)
Modbus RTU, Johnson N2, Siemens FLN, BACnet

Environmental
Ambient Temperature (F):
5 to 104
Storage Temperature (F):
-40 to 158
Humidity:
MAX 95% RH non-condensing
Altitude:
3,300 ft. without derate (1% derate
for each additional 330 ft.)
Enclosure:
NEMA 1

Rated Input Voltage:


Rated Input Current Amps:
Heat Loss in Watts 100% Load:
Efficiency (%):

Input
3 Phase 208-240 VAC +/-10% 48/63Hz +/- 5%
11.80
116.00
98.00

Output Current Amps:


Overload Current Rating:

Output
11.8
110% for 1 minute every 10 minutes

Drives are rated for use below 3,300 ft and 104F. Use Derating Charts in Air-Mod Engineering Guide Form 100.41-EG1
(704) for use above these limits.

Copper Conductors Only


DI Diffuser Segment
Diffuser Segment Details
Segment Air Pressure Drop (in. w.g.)

0.09

Diffuser Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner

Project Name: Idsaa-CentroMedicoMorelos


Printed: 11/28/2012 17:18:46
Unit Folder: UMA-02

10/03/2012 12:26:49 PM

York Contract No.:


UMA-02Performance
Page 4 of
10

SOLUTION AIR HANDLING UNIT


PERFORMANCE SPECIFICATION
Unit Tag
UMA-02

Qty
1

Model
Solution Indoor Air Handler 39 x 33

Air Flow (CFM)


1490

XA Access Segment
Access Segment Details
Segment Length:

18 "

Access Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Access Door on Left Side(Left) 33H x 18W
Multi-Point Door Latch, No Lock, Outward Opening

HF HEPA Filter Segment


Filter Media Details
(Quantity)Filter Sizes:
(1)24x12; (1)24x15
Filter Loading:
Front
Filter Depth:
11.5" HEPA
Filter Media:
99.97% Eff, (MERV 17)
Filter Area (ft):
4.5
Filter Air Pressure Drop (in. w.g.):
0.86
Filter Dirty Allowance (in. w.g.):
0.00

Filter Segment Options


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
Optimized Filter Arrangement

Project Name: Idsaa-CentroMedicoMorelos


Printed: 11/28/2012 17:18:46
Unit Folder: UMA-02

10/03/2012 12:26:49 PM

York Contract No.:


UMA-02Performance
Page 5 of
10

SOLUTION AIR HANDLING UNIT


PERFORMANCE SPECIFICATION
Unit Tag
UMA-02

Qty
1

MZ Multi-zone Segment
Segment Details
Maximum Air Pressure Drop (in. w.g.)
AHU Design Airflow (CFM):
Sum of Zone Maximum Airflows (CFM):
Discharge Location:
Cold Deck Discharge Size:
Hot Deck Discharge Size:
Damper Type:
Max. Number of Zones:
Cold Deck Coil Details
Cold Deck Coil Space :

Model
Solution Indoor Air Handler 39 x 33

Air Flow (CFM)


1490

Multi-zone Segment Options


Options Upstream of coils
Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
No Doors

0.65
1490
Rear (Rear)
8 H x 25 W
8 H x 25 W
Zoned Control
3

Options Downstream of coils


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
No Doors

10.000

Options for Cold Deck


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
19" IAQ Coil Drain Pan Left (Left)
Stainless Steel

Options for Hot Deck


Interior Galvanized Liner
Insulation: R-13 Foam Insulation
Galvanized Floor Liner STD Gauge
Exterior Galvanized Liner
UV Surface Decontamination Detail
None

Coils & Spacers Listed Starting In Direction Of Air Flow


Cold Deck Coil - 01
Coil General/Physical Details
Location:
0 Rows:
6
Tag:
AirCoil Fins Per Inch:
13
Application:
Cooling Circuit:
6
Coil Type:
DX Finned Height (in.):
30.00
Face Type:
Full Finned Length (in.):
21
Tube Diameter:
1/2" BDX Coil Face Area (ft):
4.4
Tube Material:
Copper Coil Conn. Loc.:
Left(Left)

Air Side Performance


Air Flow (CFM):
1490
Altitude (ft.):
3000
EAT-DB (F):
90.0
EAT-WB (F):
66.2
LAT-DB (F):
43.9
LAT-WB (F):
43.7
FV (ft/min):
339

Project Name: Idsaa-CentroMedicoMorelos


Printed: 11/28/2012 17:18:46
Unit Folder: UMA-02

10/03/2012 12:26:49 PM

Fluid Side Performance


Fluid Type:
R-410a
Suct Tmp(F):
40.00
RPD (PSI):
3.1
5.3
Fluid Weight(lb):
Fluid Volume(ft):
0.4

York Contract No.:


UMA-02Performance
Page 6 of
10

SOLUTION AIR HANDLING UNIT


PERFORMANCE SPECIFICATION
Unit Tag
UMA-02

Qty
1

Tube Wall Thickness:


.016"
Fin Type:
Corrugated
Fin Thickness:
.008"
Fin Material:
Aluminum
Casing Material:
Galvanized
Connection Material:
Copper
Connection Type:
Sweat
Coating:
None

Model
Solution Indoor Air Handler 39 x 33

Suct Conn Size:


Liq Conn Size:
Distributor Data:
Distributors:
Pct. Cap
Split(Inter):

1-5/8
7/8

SMBH:
TMBH:
APD (in. w.g.):

Air Flow (CFM)


1490
65.0
85.3
0.35

1
None

ARI Messages:
R410A coil - This coil is outside the scope of the AHRI certification, but is rated in accordance with AHRI Standard 410
NOTE: Auxiliary Side Connectors for hot gas bypass are provided for ONE circuit only.
Coil Dll Version: 5.4a

Electrical Circuit Summary


Short-Circuit Summary
5 kA rms Symmetrical
240 V Maximum

Circuit 1
Supply Fan Motor Control

Circuit 1 Electrical Details


Full Load Amps (FLA):
11.8
Minimum Circuit Ampacity (MCA):
14.8
Maximum Fuse Size:
25.00

Project Name: Idsaa-CentroMedicoMorelos


Printed: 11/28/2012 17:18:46
Unit Folder: UMA-02

10/03/2012 12:26:49 PM

York Contract No.:


UMA-02Performance
Page 7 of
10

SOLUTION AIR HANDLING UNIT


PERFORMANCE SPECIFICATION
Unit Tag
UMA-02

Qty
1

Model
Solution Indoor Air Handler 39 x 33

Air Flow (CFM)


1490

Static Pressure Summary


Segment

Component

IP Inlet Plenum
RF High Efficiency Filter

Supply
(in.
w.g.)

Opening Pressure Drop


2" Pleated 30% (MERV 7)
Dirty Filter Allowance - Prefilter
21" Bag 60-65% Eff, (MERV 12)
External Static Pressure - User Entered Pressure Drop
Diffuser Air Pressure Drop
11.5" HEPA 99.97% Eff, (MERV 17)
Cooling 6 rows 13 fins
CDA Opening Pressure Drop
CDA CD-60mz Galvanized (CD60MZ)

FS-DWDI Supply Fan


DI Diffuser
HF HEPA Filter
MZ-1T Multizone

Total

Return
Fan
(in. w.g.)

0.16
0.19
0.00
0.27
1.00
0.09
0.86
0.35
0.19
0.11

3.22

0.00

Air handling unit parameters vary depending on conditions. Parameters such as airflows, air pressure
drops, and coil capacities are shown for design conditions.
Dimension & Weights Summary
Width**
Length*
(in.)
(in.)

Section
IP Inlet Plenum Segment
RF High Efficiency Filter Segment
FS-DWDI Supply Fan Segment
DI Diffuser Segment
XA Variable Length Access Segment
HF HEPA Filter Segment
MZ-1T Multizone Segment
MZ-2T Multizone Segment

18
25
39
10
18
16
55
-

33
33
33
33
33
33
33
33

Height
(in.)

Weight
(lbs.)

39
39
39
39
39
39
39
27

156
177
560
69
100
104
715
560

181
33
66
2441
Overall:
*The length includes bottom tier segments only.
**The width does not include coil connection extensions or door latches that extent beyond the unit casing.
The width does not include the depth of any pipe chases.

Project Name: Idsaa-CentroMedicoMorelos


Printed: 11/28/2012 17:18:46
Unit Folder: UMA-02

10/03/2012 12:26:49 PM

York Contract No.:


UMA-02Performance
Page 8 of
10

SOLUTION AIR HANDLING UNIT


PERFORMANCE SPECIFICATION
Unit Tag
UMA-02

Qty
1

Shipping Skid

Model
Solution Indoor Air Handler 39 x 33

Air Flow (CFM)


1490

Shipping Skid Summary


Length*
Width**
(in.)
(in.)

(MZ-1T HF XA DI FS-DWDI RF IP MZ-2T)

186

53

Height***
(in.)

Weight
(lbs.)

70

2441

Ship Loose:
None
*The length includes any mounted rain-hoods, discharge flanges, tie-down brackets, shipping wood-blocks, front dampers, split
connectors, electrical/control components, out rigging HW supports, isolation dampers, inlet baskets
**The width includes any door handles, coil connections, drain connections, lifting lugs, mounted pipe-chases, electrical/control
components, tie-down brackets, side dampers
***The height includes any base-rails, shipping wood-blocks, roof peak, discharge flanges, mounted gas-furnace flue pipes

Shipping Skid Sequence

Tier 2

MZ-2

Tier 1

MZ-1

<

HF

<

XA

<

DI

Project Name: Idsaa-CentroMedicoMorelos


Printed: 11/28/2012 17:18:46
Unit Folder: UMA-02

10/03/2012 12:26:49 PM

<

FS

<

RF

<

IP)

York Contract No.:


UMA-02Performance
Page 9 of
10

SOLUTION AIR HANDLING UNIT


PERFORMANCE SPECIFICATION
Unit Tag
UMA-02

Qty
1

Model
Solution Indoor Air Handler 39 x 33

Air Flow (CFM)


1490

Sound Summary
Octave Band Sound Power Levels (dB Re. 1 picowatt)

Ducted Discharge
DISCHARGE, MZ
Return Air Front-1, IP

63
89

125
82

250
78

500
77

1000
75

2000
71

4000
65

8000
59

81

81

75

71

72

67

63

60

dBA

Sound data tested in accordance with AHRI-260 (2001), Standard for Sound
Rating of Ducted Air Moving and Conditioning Equipment.
Notes:
1. The overall A-weighted sound power level is only applicable to sound radiation outdoors and casing radiated

2.

sound. This metric does not apply to ducted components


Return air sound powers are estimated using 100% of unit flow.

Project Name: Idsaa-CentroMedicoMorelos


Printed: 11/28/2012 17:18:46
Unit Folder: UMA-02

10/03/2012 12:26:49 PM

York Contract No.:


UMA-02Performance