AQUAFLAIR Cooling portfolio

Small

Medium

Large

Uniflair LRAC
Page 6 - 7

Cooling only

Air-cooled
units

Uniflair LRAH
Page 6 - 7

Free-cooling
units

Uniflair ERAF
Page 18 - 19

Uniflair ISAF
Page 20 - 21

Uniflair ARAF
Page 22 - 23

Heat pumps

Condenserless

Cooling only

Heat pumps

Free-cooling

Units for
comfort
applications

Underfloor
terminal units

Uniflair UTAT
Fan-coil
Page 42- 43
Uniflair UTCT
Fan unit
Page 44 - 45

Uniflair ERCH
Page 34 - 35

Uniflair ISCH
Page 36 - 37

Uniflair ERCC
Page 34 - 35

Uniflair ISCC
Page 36 - 37

Units with
ducted fans

Uniflair BCEC
Page 16 - 17

Uniflair ARAH
Page 12 - 13

Cooling only
Water-cooled
and
condenserless
units

Uniflair BREC
Page 14 - 15

Uniflair ERAH
Page 8 - 9

Uniflair ISAH
Page 10 - 11

Cooling only

Uniflair ARAC
Page 12 - 13

Extra-Large

Uniflair ERAC
Page 8 - 9

Uniflair ISAC
Page 10 - 11

Heat pumps

Uniflair ERCF
Page 38 - 39

Uniflair ISCF
Page 40 - 41

Scroll Compressors

Screw compressors

Oil free compressors

Variable speed drive compressors

Uniflair BREF
Page 24 - 25

Uniflair BCEF
Page 26 - 27

Uniflair BRWC
Page 28 - 29

Uniflair BCWC
Page 30 - 31

Uniflair BRWH
Page 28 - 29

Uniflair BRRC
Page 32 - 33

Why Uniflair
Optimized management
Management of the whole system allows energy consumption to be optimized and strategies of integrated control to
be implemented which would otherwise not be possible.

The issue of energy continues to play an extremely important role regarding operating costs for modern systems.
Uniflairs range of products makes it possible to guarantee maximum service reliability while cutting energy
consumption to a minimum:

High efficiency refrigerants

Efficiency at partial loads


(tandem)

Oil-free centrifugal
compressors with
magnetic bearings

Particular attention has been paid to the management logic which is aimed at reducing the energy requirement by
means of a tracking logic for the current thermal load.
The temperature of the chilled water varies dynamically in such a way as to minimize compressor consumption and
the use of free-cooling, maintaining the desired temperature within the room.

7.0

Modularity and flexibility

Inverter driven
compressors

Optimized set-point

20

5.0

15

4.0
3.0

10

2.0

1.0
0

Double screw
compressors

25

6.0

Energy Efficiency [%]

Indirect free-cooling

Uniflair s precision air conditioning units, Active Floor modules and chillers can be linked together by a LAN,
maximising the operating parameters and the real needs of the system.

Min. Load

Medium
Load

Medium
Load

Max Load

EER
Chilled water temperature

Water temperature [C]

Efficiency and Reliability

Number of operating units

Less CO2

Acoustic Impact

Advanced controls
Uniflair produces the software for its units internally. This enables the company to equip each machine with a tailor
made control which manages all aspects of the unit.

Reduction in sound pollution is one of the most critical factors designers are called on to solve when choosing plant
systems.

Absolute control means:

Uniflair chillers offer low-noise solutions with extremely low acoustic impact thanks to:

Precision: the units use advanced algorithms to accurately control the temperature of the
chilled water
Reliability: each component is continuously monitored to guarantee it is always used
within operating limits and will signal any faults before breakdown occurs

Acousti-composite fans with high efficiency and low acoustic impact


Fans with electronically commutated motor (EC) to reduce the acoustic impact at all load conditions
Extra-large air side exchangers
Specially devised and implemented algorithms which control the rotation speed of the fans
Tested, optimised compressor insulation and housing
Uniflair unit comparision (blue
line) with its main competitors

74

Local Area Network: Aquaflair chillers can talk to each other, resulting in excellent control
of multi-unit systems, managing all the cooling resources and units on stand-by (either on a
time basis or alarm)
Connectivity: Uniflair microprocessor controls can talk to the most common supervision
systems (Building Management Systems) including: Modbus, Bacnet, LonWorks, Trend,
Metasys, TCP/IP and SNMP

Noise pressure level [db(A)]

72
70
68

Acoustic levels for a basic high


capacity unit, Tambient: 35C,
Twater in/out: 12/7C, distance
10 m, Q=2,condensing coil side

66
64
62
60
58
56

400

500

600

700

800

900

1000

1100 kW

Free-cooling

Intelligent Free-cooling
When a system is used for technological or industrial
processes which operate all year round, it is important
in terms of energy saving to use solutions which exploit
these conditions. Chillers equipped with free-cooling
devices not only reduce energy consumption compared
to traditional systems but also limit CO2 emissions into
the atmosphere, contributing therefore to reducing global
warming.
When the external temperature is low enough, the freecooling system produces chilled water using external air
only, significantly reducing energy consumption since it is
limited to the fans.

Free-cooling coil

pump

Free-cooling pump
evaporator

pump

Direct expansion mode

The need to install a stand-by unit can be exploited


to increase the free-cooling capacity.
By interconnecting the circuits of the free-cooling units
it is possible to make the water flow through all of the
available exchangers therefore further decreasing energy
consumption.
Additional annual energy saving
Compared to traditional Free-cooling: up to 7%
depending on the climate
Compared to a traditional system: up to 50%

Mixed Mode

Annual energy saving

Traditional Free-Cooling

Uniflair Free-Cooling

Free-cooling mode

Benefits

Pumps sized 24/7 to overcome resistance of Free-cooling


coil and the 3-way valve
3-way valve low reliability

Main Pumps sized only to overcome resistance of


standard evaporator
Extremely reliable free-cooling pump
No 3-way valve
Capacity with in-built free-cooling up to 1450 kW
Annual
energy
saving

1600
1400

- 41%

1200

600

Uniflair
Free-cooling

800

- 6%

Traditional
Free-cooling

1000

Standard Chiller

Annual Absorbed Power [MWh]

Limits

Energy
absorbed
(yearly)

Standard
chiller

Traditional
Freecooling

1370445

994434

969760

Energy
saving
(yearly)

38%

41%

Annual saving

- 41361

- 44075

Typical IT Installation - London 24 hours, 7 days per week


operation / 10C/15C chilled water
Payback period 8 months

Uniflair Intelligent
Free-cooling

Energy saving [kWh]

Economic saving

Frankfurt

34.560

-5%

Milan

29.132

-4%

Paris

36.954

-4%

Amsterdam

42.558

-7%

Madrid

36.743

-4%

Berlin

31.525

-4%

London

46.018

-6%

Glycol-free

Uniflair
Freecooling

MWh

Uniflair Free-cooling Vs

Created for applications where the use of antifreeze solutions are not permitted, this solution,
thanks to an intermediate heat exchanger,
isolates the principal hydraulic circuit from the
free-cooling circuit.
Careful selection of the intermediate heat
exchanger allows the delta T to be limited to
only 2C, reducing therefore the energy drops
which are intrinsic to this system.

Free-cooling coil
pump
Free-cooling pump

pump
evaporator

Air-cooled water chillers and heat pumps with axial fans designed for outdoor installation

10

LRAC-LRAH

11

Uniflair LRAC-LRAH
Range
Cooling capacity: 6 40 kW
Heating capacity: 7 43 kW
Available versions
- low noise
- Top Operating Performance
- condensing version (*)
Refrigerant R-410A
Scroll Compressor/s

Technical Data
LRAC/LRAH MODELS
Power supply

023B
V/ph/Hz

032B

041B

054A

067A

230 / 1 / 50

090A

120A

137A

180A

400 / 3 + N / 50

Cooling capacity (1)

kW

10

14

17

19

27

33

39

Absorbed power (1)

kW

1,5

2,2

2,9

4,4

4,9

6,0

8,7

10,0

12,0

4,0

3,6

3,5

3,2

3,5

3,3

3,1

3,2

3,2

kW

6,7

9,0

10,9

15,5

18,9

22,1

30,2

36,7

43,5

C.O.P. (1)
Heating capacity (2)
Absorbed power (2)

kW

1,7

2,3

2,8

3,9

4,7

5,5

8,5

10,0

11,9

Noise pressure level (3)

dB(A)

34

34

34

35

37

38

38

40

41

Fans / poles

nr.

1/6

1/6

1/6

1/6

2/6

2/6

2/6

3/6

4/6

Circuits / compressors

nr.

1/1

1/1

1/1

1/1

1/1

1/1

1/2

1/2

1/2

Compressor type

Scroll

Evaporator

Plate

Water tank

25

25

25

50

50

1. Data refer to nominal


conditions: water temperature
12/7C; external temperature
35C; R410A refrigerant
2. Data refer to nominal
conditions: water temperature
40/45C; external temperature
7C d.b. 6C w.b.; R410A
refrigerant
3. Measured in free field at 10
mt. (Q=2, front) from the unit
running in nominal conditions
4. Data refer to empty unit

50

100

100

100

Standard Features
Designed with a minimal footprint
Self-supporting frame in galvanised steel (colour
RAL7037) with panels varnished with epoxy powders in
compliance with the ASTM B117 norm
Between 1 to 2 hermetic Scroll compressors with
internal thermal protection and anti-vibration feet
Crankcase heaters (*)
Ecological refrigerant: R410A
Refrigerant circuit in compliance with EC norms (PED
97/23/ EC directive) in copper tubes mainly including
a filter dryer, water flow switch, thermostatic valve with
external equalisation (stainless steel made) and high and
low pressure switches
Metal grille panel to protect the air side heat exchanger
Cycle inversion on the refrigerant side with 4-way
reversing valve (*)
Stainless steel, brazed plate heat exchanger insulated
with closed-cell, expanded polyurethane
Anti-freeze heater on evaporator (*)
Air side heat exchanger with aluminium fins and
mechanicallyexpanded copper tubes
Axial fans, statically and dynamically balanced, with
sickleblades and with safety protection grilles
Sound-proofing polymeric impeller for each fan
Condensation control including continuous regulation of
fan speed
Electric panel conforming to EC Directive 2006 / 95 / EC
and Directive EMC 2004/108/EC with auxiliary 12V circuit,
general cut-off switch, magneto-thermal protection cut-off
switches
UTS microprocessor control system with local user
control and monitoring terminal with LCD display and LED
signals for all working parameters: chilled/hot (*) water
temperature regulation, anti-freeze
protection, compressor timing and protection, fan speed
regulation, alarm code signalling, centralization for general
alarm control and remote ON-OFF switch and remote
cycle inversion (*)
Water flow differential pressure switch

Predisposition for cooling / heating systems with heating


panels
Rubber anti-vibration feet

Total Operating Performance


Electronic expansion valve driven by the
microprocessor control
Advanced UPCOxs microprocessor control system
with specific algorithm to:
- Outlet water temperature regulation
- Advanced management of compressors run
through automatic set-point sensitivity regulation
- Advanced management of the de-frosting function
to minimise cycle inversions (*)
- Advanced anti-freeze protection on evaporator
- Integrated LAN card for local network connection
of a group of chillers (up to 10 units, with 1 or 2
stand-by units)
Moreover, the microprocessor control system
enables:
- Remote cycle inversion (*)
- The set point adjustment by a 0-10V external
signal
- The management and selection of double set-point
- Free contact for general alarm and 2 addressable
alarms
- Remote ON-OFF control
- The ability to interface with main external
communications protocols: Modbus, Bacnet,
Lonworks, Metasys, TCP/IP and SNMP

(*) Optional for LRAC, when possible

Height

mm

650

650

650

1271

1271

1271

1271

1271

1271

Depth

mm

458

458

458

458

458

458

615

615

615

Width

mm

1274

1274

1274

1273

1273

1273

2054

2054

2054

Weight (without hydronic kit)

kg

100

101

103

152

160

162

262

272

282

Weight (version with pump)

kg

104

105

107

159

167

169

273

281

291

Weight (version with water


tank and pump) (4)

kg

116

117

119

179

187

189

300

308

318

Construction Options

Options

On-board water tank and pump


High head pressure pump (*)
Condensing Unit (*)
Unit works down to - 20C
Production of glycol water mixture at low temperatures
option (down to - 10 C)
Anti-freeze protection on evaporator, water tank and
pump
RS485 serial adaptor used to communicate with Uniflair
supervisory system or to interface with external BMS
LON FTT10 serial adaptor used to communicate with
external BMS managed with LON protocol
Hot gas by-pass disposal for a constant outlet water
temperature, even with 0 to 100% charge variation
(optional; only LRAC)
TCP/IP serial adaptor used to interface with external BMS
Condensing coils equipped with safety grilles and filter

Remote user terminal for:


- display / entering of commands
- display unit status and alarms
Chilled / hot water piping filter

(*) on request

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
LRAC-LRAH 06/12

2012 Schneider Electric. All rights reserved.

DIMENSIONS AND WEIGHT

Air-cooled water chillers and heat pumps with axial fans for outdoor installations

12

ERAC - ERAH

13

Uniflair ERAC - ERAH


Cooling capacity: 50 110 kW
Available versions
- low noise
- ultra low noise
Refrigerant R410A
Scroll Compressors

Technical Data
ERAC/ERAH MODELS
Power supply

0521A

0621A

0721A

0821A

V/ph/Hz

0921A

0922A

1021A

1022A

1221A

1222A

400 / 3 + N / 50

Refrigerant circuits

nr.

Compressors

nr. x mod

Fans

nr.

Evaporator

nr.

Evaporator

mod

2
2 x Scroll

plate

ERAC - Low noise version


Cooling capacity (1)

kW

47

56

65

75

83

83

96

95

111

111

Absorbed power (1)

kW

13,8

17,6

19,7

21,9

25,9

25,9

30,2

30,2

35,1

35,2

E.E.R. (2)

3,41

3,16

3,30

3,43

3,20

3,21

3,17

3,16

3,16

3,16

E.S.E.E.R. (5)

5,23

5,16

5,40

5,44

5,26

5,10

5,49

5,28

5,38

5,37

ERAH - Low noise version

Standard Features
Self supporting frame in galvanised steel with panels
varnished with epoxy powders (colour RAL7037)
Access panel to the unit equipped with handles and fast
screws
Two hermetic scroll compressors with internal thermal
protection, anti-vibration supports and crankcase heaters
(ERAH and low ambient temperatures version)
Single refrigerant circuit (*) conforming to EC Directives
(PED 97/23/CE) in copper tubing including filter dryer,
liquid sight glass, dual flow thermostatic valve with
external equalisation, high and low pressure switches and
high pressure transducers
Environmentally friendly refrigerant R410A
Water side brazed plate heat exchanger in stainless
steel insulated with closed cell expanded polyurethane
Water flow differential pressure switch
Air side exchange coil with aluminium fins and
mechanicallyexpanded copper tubes
Refrigerant side cycle inversion with 4-way inversion
valve (ERAH)
Acousti-composite fans: Sickle-blade axial fans,
statically and dynamically balanced and made from
composite materials for high efficiency and low acoustic
impact with internal and external safety protection grilles
Modulating condensation control based on the
condensation pressure
Electrical panel conforming to EC Directives (2006/95/
EC and EMC 2004/108/EC) protection grade IP54 with
auxiliary transformer, lockable general cut off switch,
magneto-thermal cut off switches and remote control
Sequence phase control
Anti-condensation heaters for the electrical panel (ERAH
and low ambient temperature versions)
Microprocessor control system including:
- Local user terminal externally visible and accessible via
an access hatch
- Chilled/hot water temperature regulation (ERAH) on the

discharge
- Production of chilled water to -15C
- Anti-freeze protection
- Compressor timing and protection
- Compressor rotation based on FIFO logic
- Pump rotation on a timed basis for equal operation and
start-up of the stand-by pump (with alarm signal) in the
event of a breakdown
- Display of compressor operating hours
- Alarm code signal
- General alarm with clean signal contact
- ON-OFF remote control

Total Operating Performance


Electronic expansion valve directly controlled by the
unit microprocessor control
Advanced UpCO1m control for:
- Discharge water temperature regulation
- Management of the electronic thermostatic valve
- Monitoring of the refrigerant load
- Self-adjustment of the set-point regulation
- Advanced defrost operation management (ERAH)
- Integrated LAN card
- Compatibility with the most common external BMS
systems and with the Modbus protocol using only
the RS485 card
(*) ERAC models with **22A suffix are available with two
compressors on two circuits

Heating capacity (3)

kW

54

64

74

85

95

n.a.

111

n.a.

128

n.a.

Absorbed power (3)

kW

14,6

17,6

19,8

22,8

26,0

n.a.

30,7

n.a.

35,8

n.a.

1. Data refer to nominal


conditions: water temperature
12/7C; external temperature
35C; glycol 0%; R410A
refrigerant
2. Data refer to the total
absorbed power (compressors
and fans)
3. Data refer to nominal
conditions: water temperature
40/45C, external temperature
7C dry bulb, 6C wet bulb;
R410A refrigerant
4. Data measured in free
field at 10 metres from the
unit operating at nominal
conditions, coil side, Q=2
directional factor

C.O.P. (2)

3,71

3,64

3,74

3,73

3,64

n.a.

3,61

n.a.

3,58

n.a.

Noise pressure level (4) dB(A)

42,6

43,5

44,0

44,3

44,3

44,3

53,4

53,4

54,7

54,7

5. European Seasonal Energy


Efficiency Ratio
6. Data refer to an empty unit
without pump and water tank

ERAC - Ultra low noise version


Cooling capacity (1)

kW

46

53

62

73

80

80

91

92

106

107

Absorbed power (1)

kW

14,2

18,4

20,7

22,8

27,2

27,2

31,9

31,9

36,9

37,0

E.E.R. (2)

3,20

2,90

3,01

3,19

2,93

2,93

2,87

2,87

2,89

2,90

E.S.E.E.R. (5)

5,21

5,07

5,25

5,38

5,16

4,99

5,39

5,12

5,29

5,22

ERAH - Ultra low noise version


Heating capacity (3)

kW

52

62

71

82

91

n.a.

107

n.a.

124

n.a.

Absorbed power (3)

kW

14,8

17,9

20,7

23,3

26,4

n.a.

31,1

n.a.

35,7

n.a.

C.O.P. (2)

3,53

3,45

3,43

3,53

3,46

n.a.

3,43

n.a.

3,47

n.a.

Noise pressure level (4) dB(A)

39,1

39,8

40,3

40,1

40,1

40,1

49,6

49,6

51

51

Dimensions and weights


Height

mm

1560

1560

1560

1560

1560

1560

1875

1875

1875

1875

Depth

mm

1190

1190

1190

1190

1190

1190

1190

1190

1190

1190

Width

mm

2010

2010

2805

2805

2805

2805

3075

3075

3075

3075

Weight ERAC basic (6)

kg

607

612

730

760

766

777

975

974

1003

1003

Weight ERAH basic (6)

kg

632

637

760

790

797

n.a.

1019

n.a.

1047

n.a.

Construction Options
Ultra low noise version via a specific algorithm and
soundproofing of the compressors
Partial / total condensation heat recovery
Integrated hydraulic module with one or two pumps (1
+ 1 stand-by) with heat-protected circulation, expansion
vessel and safety valve
Internal water tank
Internal water tank including a pump to manage the
primary circuit
Power factor improvement compressors
Compressor Softstart
Cataphoresis treatment for the condensing coils
Shut off taps on the compressor discharge
Evaporator, water tank and pump group anti-freeze

heaters
Modification of the set point by external 0-10V signal
Condensing unit (*)
(*) on request

Options
Remote user terminal
Clock card
RS485 serial card, FTT10 or TCP/IP for connection to
the Uniflair supervision system or an external BMS
Metal filters and protection grilles for the condensing
coils
Rubber or spring anti-vibration supports

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ERAC-ERAH 06/12

2012 Schneider Electric. All rights reserved.

Range

Air cooled modulating water chillers and heat pumps for outdoor installation

14

ISAC - ISAH

15

Uniflair ISAC - ISAH


Cooling capacity: 60 120 kW
Heating capacity: 66 130 kW
Available versions
- low noise
Refrigerant R-410A
Inverter driven Scroll compressors

Technical Data
ISAC/ISAH MODELS
Power supply

0621A

0921A

V/ph/Hz

Refrigerant circuits

nr.

Compressors

nr.

1221A

400 / 3 / 50
1

1 ON/OFF + 1 inverter driven (Scroll)

Fans

nr.

Evaporator

nr.

Evaporator

mod

piastre

E.S.E.E.R. (4)

5,66

5,71

5,72

I.P.L.V. (5)

6,19

6,27

6,22

66

97

128

4. European Seasonal Energy


Efficiency Ratio
5. Integrated Partial Load Value

Cooling capacity (1)

kW

59

87

115

Absorbed power (1)(2)

kW

18,7

26,6

35,9

ISAH LOW NOISE VERSION

Self-supporting galvanized sheet steel framework with


panels painted with epoxy powder paints (colour RAL
7037) equipped with fast screws for easy and quick
access
Inverter-driven hermetic Scroll compressor, equipped
with
- Inverter speed control
- Oil by-pass valve and line
- Soft start
- Integrated power factor correction condenser
- Integrated thermal protection
- Anti-vibration supports
Inverter driver with IP54 protection grade coupled with
a specific compressor and positioned in a dedicated
housing compartment
Hermetic Scroll compressor with integrated thermal
protection and anti-vibration feet
Compressor sound-proofing with noise insulating
jackets and, only for model 1221A, soundproofing of the
compressor compartment
Vibration absorbers on the compressor discharge and
suction line (only for model 1221A)
Single refrigerant circuit in accordance with EC
standards (directive PED 97/23/CE) in copper piping
including dehydration filter, liquid sight glass, electronic
expansion valve connected to and driven by the unit
control, high and low pressure switches and transducers.
The refrigerant circuit features an exclusive patented
system for optimum lubrification management of the
tandem compressors
Continuous operation up to -20C (only ISAC)
Environmentally friendly refrigerant R410A
Crankcase heaters and inverter with oil heating function
Brazed plate water side heat exchangers in stainless
steel, insulated with closed-cell expanded polyurethane
and anti-freeze heaters
Refrigerant side cycle inversion with 4-way inversion
valve (only ISAH)
Water flow differential pressure switch

Air side exchange coil with aluminium fins and


mechanically expanded copper piping
Acousti-composite fans: Sickle-blade axial fans,
statically balanced and made from composite material
ensuring elevated efficiency and low noise, with external
and internal protection grill
Modulating condensation control by means of
continuous fan speed control
Electrical panel in accordance with EC standards
(directive 73/23/EC and directive EMC 89/336/EC) IP54
protection grade with auxiliary transformer, minimum and
maximum temperature control, general door interlock cut
off switch, protection and remote control switches
Phase sequence control
UPC1m microprocessor control including:
- Chilled / hot water temperature regulation by means of
self adaption of the set point regulation band
- Management of the electronic thermostatic valve
- Compressor management driven by inverter
- Quick start start-up procedure
- Integrated LAN card
- Integrated clock card
- Compatibility with Modbus protocol via RS485
- Compatability with the most common external BMS:
LONworks, BacNET, TCP/IP, Trend

2. Data refer to total absorbed


power (compressors and fans)
3. Data refer to nominal
conditions: water 40/45C,
external temperature dry bulb:
7C, wet bulb: 6C; inverter
compressor at 90rps R410A
refrigerant

ISAC LOW NOISE VERSION

Heating capacity (3)

Standard Features

1. Data refer to nominal


conditions: Inlet/outlet water
temperature: 12/7C; external
temperature 35C; glycol 0%;
inverter compressor at 90rps
R410A refrigerant

kW

Absorbed power (3)(2)

kW

18,1

26,2

35,9

Noise pressure level (6)

dB(A)

43,5

44,3

54,7

DIMENSIONS AND WEIGHTS


Height

mm

1560

1560

1874

Length

mm

1190

1190

1192

Width

mm

2008

2798

3075

Weight ISAC (basic version) (7)

Kg

652

810

1047

Weight ISAH (basic version) (7)

Kg

682

840

1092

Construction Options

Options

Integrated hydraulic module with one or two pumps


(1+1 in stand-by) with heat protected circulation,
expansion vessel and safety valve
Integrated hydraulic module with one or two inverter
driven pumps (1+1 in stand-by) with heat protected
circulation, expansion vessel and safety valve
Cataphoresis treatment for condensing coils
Shut-off taps on the compressor discharge
Power factor correction on compressors
Modification of the set-point by external signal 0-10V
EC fans

Remote user terminal mP20 II (up to 200 metres) for:


- entering of commands
- display unit status and alarms
RS485 serial adaptor used to communicate with the
Uniflair supervisory system or to interface with external
BMS
LON F T T10 serial adaptor used to communicate with
external BMS managed with LON protocol
TCP/IP serial adaptor used to communicate with
external BMS managed with SNMP protocol
Air side coil protection filters and grills
Rubber or spring anti-vibration supports

6. Data measured in free field


conditions at 10m from the
unit operating in nominal
conditions, coil side, directional
factor Q=2
7. Data refer to an empty unit
without pump

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ISAC-ISAH 06/12

2012 Schneider Electric. All rights reserved.

Range

Air-cooled water chillers and heat pumps with axial fans for outdoor installations

16

ARAC - ARAH

17

Uniflair ARAC - ARAH


Range
Cooling capacity: 120 260 kW
Heating capacity: 129 285 kW
Available versions
- standard
- modulating condensation control
- low-noise
Refrigerant R-407C
Scroll Compressors

R407C

Technical Data
ARAC / ARAH MODELS

0644A

0744A

Power supply

V/ph/Hz

Circuits / compressors

nr.

2/4

2/4

Fans / poles

nr.

2/6

3/6

Evaporator type

nr. x mod

0964A

1084A

1204A

2/4

2/4

2/4

3/6

4/6

4/6

400 / 3 + N / 50

1 x Shell &Tube

Cooling only (ARAC)


Cooling capacity (1)

kW

135

165

190

230

260

Absorbed power (1)

kW

49

54

73

84

95

Heating capacity (4)

kW

141

179

220

255

285

Absorbed power (4)

kW

41

64

79

84

85

Noise pressure level min/max (3)

dB(A)

50 / 57

51 / 58

51 / 58

52 / 59

52 / 59

Cooling capacity (1)

kW

128

158

180

219

245

Absorbed power (1)

kW

52

56

78

88

102

Noise pressure level (3)

dB(A)

47

48

48

50

50

Heat pump (ARAH)

Low noise version

Self-supporting frame in galvanised steel (colour


RAL7037) with panels finished in epoxy powders
Four hermetic Scroll compressors with internal thermal
protection and anti-vibration supports
Two refrigerant circuits conforming to EC norms
(PED 97/23/CE) in copper tubes mainly including: filter
dryer, flow indicator, thermostatic valves with external
equalisation, high and low pressure switches and high
and low pressure transducer
Compressor crankcase heaters (*)
Exchange of the cycle on the refrigerant side with 4-way
reversing valve (only for ARAH)
Shell & tube water/refrigerant heat exchanger with
two independent cooling side circuits and one hydraulic
circuit: the heat exchanger is insulated with closed-cell
expanded neoprene
Heat exchanger coil with aluminium fins and
mechanically-expanded copper tubes
Water flow pressure switch
Sickle-blade axial fans, statically and dynamically
balanced with safety protection grilles (internal and
external) protection grade IP54
Condensation pressure control switch ON-OFF
Electric panel conforming to EC (Directive 2006/95/EC
and Directive EMC 2004/108/EC) with anti-condensation
heater (*), auxiliary circuit, general cut-off switch,
magneto-thermal protection cutoff switches
Sequence phase control
Microprocessor control system UPC1m including:
- local user terminal mP20 II visible on unit with panel
- outlet chilled water temperature regulation
- advanced management of compressors run through
automatic set-point sensitivity regulation
- compressor rotation with FIFO system (run time,
protection and function)
- pump rotation on a time basis (settable) for equal
operation and start-up of the stand-by pump (with
alarm signal) in the event of a breakdown
- advanced anti-freeze protection on evaporator (*)

- advanced defrost function (only for ARAH)


- integrated LAN card for local network connection of
a group of chillers (up to 10 units with 1or 2 units in
stand-by)
Moreover, the microprocessor control system permits:
- an overlapped management of units as a single chiller
(up to 10)
- management of double set-point and selection
- free-contact for general alarm and 2 addressable alarms
management
- remote ON-OFF switch
- abilit y to interface with Modbus protocol directly on
RS485 serial card
- ability to interface with main external communication
protocols: Bacnet, Lonworks, Metasys, TCP/IP and
SNMP

Partial heat recovery (option)


Exchanger type

nr.

Thermal heat recovery (5)

kW

48

53

75

plate / 2
76

86

Water flow

l/h

8256

9116

12900

13072

14792

2. With pump group


3. Measured in free field
conditions, coil side, direction
factor Q=2, at 10 mt. from the
unit (at nominal conditions)
4. Data refer to nominal
conditions: water temperature
40/45C, external temperature
7C dry bulb, 6C wet bulb;
R407C refrigerant
5. Data refer to nominal
conditions: recovery water
temperature 40/45C; chilled
water temperature 12/7C;
external temperature 35C;
R407C refrigerant
6. Data refer to empty unit

Total heat recovery (option)


Exchanger type

nr.

Thermal heat recovery (5)

kW

178

207

Shell &Tube / 2
278

318

350

Water flow

l/h

30616

35600

47816

54696

60200

Height

mm

1618

2140

2140

2140

2140

Depth

mm

3807

4542

4542

5242

5242

Width

mm

1193

1344

1344

1344

1344

Weight (without hydronic kit) (6)

kg

1271

1754

2001

2182

2290

Weight (with water tank and 2 pumps)

kg

1554

2058

2321

2537

2648

Dimensions and weight

(*) Standard only for ARAH

Construction Options
Standard version with modulating condensation control
Low noise version with modulating condensation control
through special algorithm and sound-proofing of
compressor housing
Version for production of glycol water mixture at low
temperatures down to - 10 C (ARAC)
Partial / total condensation heat recovery
Integrated hydronic system with 1 or 2 pumps (1 + 1
standby), expansion vessel, safety valves, water tank
Water tank equipped with pump for primary circuit
management
High and low pressure gauges
Power phase correction capacitors (compressors + fans
+ pumpgroup)
Anti-freeze protection on evaporator, water tank and
pump group
Condensing coils equipped with safety grilles and filter
Discharge interception valves on compressor
Sound-proofing of compressor housing
Clock card
RS485 serial adapter used to communicate with Uniflair

supervision system or to interface with external BMS


Condensing coil cataphoresis treatment
R134a Refrigerant (*)
Condensing version (*)
Electronic expansion valve (*)
(*) on request

Options
Units can be supplied with the following construction
options:
Remote user terminal mP20 II (up to 200 metres) for:
- entering of commands
- display unit status and alarms
Spring anti-vibration kit
Rubber anti-vibration kit

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ARAC-ARAH 06/12

2012 Schneider Electric. All rights reserved.

Standard Features

1. Data refer to nominal


conditions: water temperature
12/7C; external temperature
35C; R407C refrigerant

Air-cooled water chillers with axial fans for outdoor installation

18

BREC

19

Uniflair BREC
Cooling capacity: 400 1200 kW
Available versions

Technical Data
BREC Model

1602A

2502A

2802A

3212A

400 / 3 / 50

Compressors/circuits

nr x mod

2 x double screw

Evaporator

nr x mod

Fans

nr

Refrigerant R-134a
Double screw compressors

Cooling capacity (1)


Absorbed power (1)

ETL certified data

2202A

V/ph/Hz

- low noise
- ultra low noise

1802A

Power Supply

3612A

4212A

481 2A

1 x Shell & Tube


6

10

10

12

12

kW

365

458

519

547

666

724

840

945

1077

kW

107,7

140,7

155,4

167,5

204,0

222,8

260,9

289,0

326,4

E.E.R.

3,39

3,25

3,34

3,27

3,23

3,25

3,22

3,27

3,3

E.S.E.E.R.

4,11

4,24

4,19

4,21

4,29

4,48

4,77

4,37

4,64

I.P.L.V.

4,68

4,83

4,78

4,82

4,94

5,20

5,50

5,00

5,35

Unit without economizer

Unit with economizer

Standard Features
Self-supporting frame in galvanized steel with panels
finished in epoxy powders (colour RAL7037)
Two semi-hermetic double screw compressors with
internal thermal protection, discharge shut-off valve, oil
heaters and antivibration supports
Two refrigerant circuits conforming to EC norms (PED
97/23/EC) in copper tubes including: filter dryer, flow
indicator, electronic expansion valve managed by the
Uniflair control system, valve on the liquid line, pressure
switches, transducers and manometers of high and low
pressure
High efficiency shell & tube single passage evaporator.
The heat exchanger is insulated with UV-resistant closedcell expanded neoprene
Air side exchange coils with aluminium fins and internally
grooved copper tubes
Water flow differential pressure switch
Acousti-composite fans: Sickle-blade axial fans,
statically and dynamically balanced, made from
composite materials for high efficiency and low acoustic
impact, with safety protection grilles
Modulating condensation control with fan speed
regulation
Electrical panel conforming to EC Norms (Directive
2006/95/EC and EMC 2004/108/EC, IP54) with general
cut-off switch, electic bars distribution for power supply,
acquisition of absorbed current, maximum internal
temperature control, magnetothermal cut-off switch on
the fans and auxiliaries, fuses for the compressors
Sequence phase, minimum and maximum power supply
monitoring
Microprocessor control system UPC1m including:
- Local user terminal with external accessibility
- Outlet chilled water temperature regulation by means of
an exclusive PID algorithm
- Electronic expansion valve managed by the control
system
- Advanced control of cooling capacity by automatic set-
point sensitivity regulation

- Refrigerant charge monitoring


- Monitoring of the absorbed current and checking of
possible malfunctions
- Advanced anti-freeze protection on evaporator
- Integrated LAN card for local network connection of a
group of chillers
- Integrated clock card
- Rotation of pump group setting functioning and start of
pump in stand-by in the event of pump breakdown
Microprocessor control system in addition allows:
- Management of double set-point from remote control
- Limiting of absorbed current on pre-set value or external
signal
- Rapid Quick Start procedure to reach total cooling
capacity within 3 minutes
- Free-contact for general alarm and 2 for addressable
alarms
- Remote ON-OFF switch
- Ability to interface with Modbus protocol directly on
RS485 serial card
- Ability to interface with main external communication
protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP
and SNMP

Cooling capacity (2)

kW

392

495

560

592

721

793

909

1020,9

1163

Absorbed power (2)

kW

119,2

158,4

173,1

188,4

237,0

258,4

294,7

322,6

362,5

E.E.R.

3,92

3,13

3,23

3,14

3,05

3,07

3,09

3,16

3,21

E.S.E.E.R

4,23

4,31

4,28

4,26

4,38

4,60

4,72

4,40

4,59

I.P.L.V.

4,78

4,91

4,85

4,89

5,00

5,20

5,55

5,05

5,40

Low noise version (3)

61,0

61,1

61,2

60,1

60,9

62,4

62,6

63,1

63,6

Ultra low noise version (3)

55,0

55,2

55,6

54,8

55,0

57,5

57,6

58,0

58,4

1. Data refer to nominal


conditions: water temperature
12/7C; external temperature
35C; glycol 0%; refrigerant
R134a
2. Data refer to unit equipped
with economizer at nominal
conditions: water temperature
12/7C; external temperature
35C; glycol 0%; refrigerant
R134a
3. Measured in free field
conditions 10 m from the unit,
coil side (Q = 2)

Noise pressure levels

Dimensions
Height

mm

2525

2525

2525

2525

2525

2525

2525

2525

2525

Length

mm

4931

4931

6357

6357

6357

8890

8890

10320

10320

Width

mm

2200

2200

2200

2200

2200

2200

2200

2200

2200

Construction Options
Double power supply with automatic integrated
management on the active line
Fans with electronic commutation motors (EC)
Power phase correction capacitors
Economizer (increase in both capacity and E.E.R.)
Operation possible with external temperature upto 50C
at full load
Low external temperature: unit works down to -20C
Ultra-low noise version with sound-proof casing and
mufflers for the compressors
Production of glycol water mixture at low temperatures
(down to -10C)
Partial condensation heat recovery
Suction shut-off valves on compressor
Integrated hydronic system with 1 or 2 circulation
pumps (1 + 1 stand-by)
Integrated hydronic system with 1 or 2 inveter-driven
circulation pumps (1+1 stand-by) (*)
Anti-freeze protection on evaporator and pump group
Condensing coils equipped with metal safety grilles and
filters

Coil manifolds protection panels


Condensing coil cataphoresis or pre-painting treatment (*)
(*) on request

Options
The units can be supplied with the following external
accessories:
Remote user terminal mP20 II (up to 200 metres with
shielded cable) for:
- Entering of commands
- Display unit status of alarms
Spring anti-vibration kit
Flanged type hydraulic connection
RS485 serial adaptor used to communicate with the
Uniflair supervisory system or to interface with external BMS
LON F T T10 serial adaptor used to communicate with
external BMS managed with LON protocol
TCP/IP serial adaptor used to communicate with
external BMS managed with SNMP protocol

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BREC 06/12

2012 Schneider Electric. All rights reserved.

Range

Air-cooled modulating water chillers with axial fans for outdoor installation

20

BCEC

21

Uniflair BCEC
Range
Cooling capacity: 400 1100 kW
Available versions
- low noise
Refrigerant R-134a
oil-free centrifugal compressors
with magnetic bearings

Technical Data
BCEC Model

0301A

Power Supply

V/ph/Hz

Compressor/s

nr x model

Cooling circuits

nr

Evaporator

nr x model

Fans

nr x model

0401A

0532A

0632A

0752A

0903A

1103A

400/3/50
1 x oil free

2 x oil free

3 x oil free

1
1 x flooded
6

10

12

14

16

Unit with asynchronous motor fans (AC)


Cooling capacity (1)

kW

296

391

530

605

750

875

1100

Absorbed power (2)

kW

91,6

120,1

158,8

181,3

218,6

261,0

325,3

E.E.R. (2)

3,23

3,25

3,34

3,34

3,43

3,35

3,38

E.S.E.E.R. (3)

5,03

4,92

5,17

5,07

5,37

5,39

5,62

I.P.L.V. (4)

5,92

5,88

5,84

5,58

6,31

6,16

6,56

52,1

52,5

53,5

54,0

55,0

55,0

55,5

Noise pressure level (5)

dB(A)

Max. ambient temperature

1. Data refer to nominal


conditions: Inlet / outlet water
temperature: 12 / 7 C; External
air temperature 35 C; glycol
0%
2. Data refer to total input
power.(compressors and fans)
3. European Seasonal Energy
Efficiency Ratio
4. Integrated Partial Load
Value
5. Measured in free-field
conditions 10 mt from the unit,
coil side (Q=2)

42

Unit with electronically COMMUTED motor fans (EC)

Self-supporting frame in galvanized steel with panels


finished in epoxy powders (colour RAL9022)
Between one to three oil free centrifugal compressors
with magnetic bearings equipped with:
- internal thermal protection
- protection and control of the rotation axis position
- brushless synchronized DC motor
- integrated control system
- speed control with inverter
- soft start start-up
- phase sequence control
- pre-rotation valve
- temperature and pressure sensors
- 2 centrifugal compression stages
- anti-vibration kit
Soundproofing enclosures for compressor/s
Single refrigerant circuit conforming to EC standards
(PED 97/23/ CE) with copper tubing including: filter dryer,
liquid sight glass, electronic expansion valve controlled
by a level sensor, discharge and suction taps on the
compressor, pressure switches, high and low pressure
transducers and gauges
By-pass line for vacuum start-up with high pressure
ratio
Flooded evaporator featuring an integrated de-mister
to prevent the formation of droplets: the exchanger is
insulated with closed-cell expanded polyurethane
Air side exchange coil with aluminium fins and internally
grooved copper tubes
Differential water pressure switch
Acoustic-composite fans: Sickle-blade axial fans,
statically and dynamically balanced, made from
composite materials for high efficiency and low acoustic
impact, with safety protection grilles
Modulating condensation control with continuous
regulation of the fans speed
Electric panel conforming to EC standards (2006/95/EC
and EMC 2004/108/EC directives) with EMC integrated
filter for protection of the harmonics, maximum internal

temperature control, absorbed current control, auxiliary


transformer, general auxiliary cut-off switch, fuses on the
compressors and remote control cut-off switches
Line reactance for each compressor to stabilize the
power supply
Phase sequence control and minimum / maximum
power supply and voltage
Microprocessor control system including:
- continuous control of the cooling capacity by means of
an inverter and IGV (Inlet Guide Vane)
- local user terminal with external display
- outlet chilled water temperature regulation by means of
an exclusive PID algorithm
- integrated LAN card for connecting more than one unit
to the local area network
- acquisition and management of main electrical data
- clock card
Microprocessor control system in addition allows:
- USB card for easy download of the operating
parameters
- management of double set-point from remote control
- free-contact for general alarm and 2 for addressable
alarms
- remote ON-OFF switch
- integrated RS485 serial card for direct connection to
external BMS
- direct interface with serial BMSs with Modbus protocol
- interface with main BMS protocols, such as Bacnet,
Lonworks, Trend, Metasys, SNMP/TCP-IP and KNX

kW

300

400

530

630

750

900

1100

Absorbed power (2)

kW

92,2

121,4

155,6

188,8

213,6

265,8

308,2

E.E.R. (2)

3,25

3,29

3,41

3,34

3,51

3,39

3,57

E.S.E.E.R. (3)

5,09

4,99

5,27

5,24

5,51

5,52

5,68

I.P.L.V. (4)
Noise pressure level (5)

dB(A)

Max. ambient temperature

6,08

5,95

5,91

5,84

6,38

6,34

6,61

52,1

52,5

53,5

54,0

55,0

55,0

55,5

45

Dimensions
Height

mm

2510

2510

2510

2510

2510

2510

2510

Length

mm

5000

5000

6430

7860

9290

10720

12150

Depth

mm

2200

2200

2200

2200

2200

2200

2200

Construction Options

Options

Double power supply with automatic integrated


management on the active line and integrated condenser
for control
Separate power supply for quick start procedure
Double power supply with automatic integrated
management on the active line and additional separate
power supply for quick start procedure
Power meter for a continuous measurement of the unit
power consumption and communication to the BMS
Acoustic-composite fans with electronic commutation
motors (EC)
Low external temperature option: unit can operate down
to -20C external temperature
Integrated hydronic system with 1 or 2 circulation
pumps
Integrated hydronic system with 1 or 2 inverter-driven
circulation pumps and pressure transducers (1 + 1 stand-by)
Anti-freeze protection on evaporator and pump/s group
Condensing coils equipped with metal safety grilles and
filters
Coil manifolds protection panels
Condensing coil cataphoresis or pre-painting treatment (*)

The units can be supplied with the following external


accessories:
Remote user terminal PDG (up to 200 meters with
shielded cable) for:
- entering of commands
- display unit status of alarms
Spring anti-vibration kit
Flanged type hydraulic connection
Additional RS485 serial adaptor used to communicate
with the Uniflair supervisory system or to interface with
external BMSs
LON FTT10 serial adaptor used to communicate with
external BMSs managed with LON protocol
TCP/IP serial adaptor used to communicate with
external BMSs managed with SNMP protocol
Lifting kit

(*) on request

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BCEC 06/12

2012 Schneider Electric. All rights reserved.

Standard Features

Cooling capacity (1)

Air-cooled water chillers with axial fans and free-cooling system

22

ERAF

23

Uniflair ERAF
Cooling capacity: 50 120 kW
Available versions
- low noise
- ultra low noise
Refrigerant R-410A
Scroll Compressors

Technical Data
ERAF MODEL
Power supply

0521A

Standard Features
E xclusive free-cooling system completely managed by
the microprocessor control
Self supporting frame in galvanised steel with panels
varnished with epoxy powders (colour RAL7037)
Access panel to the unit equipped with handles and fast
screws
Two hermetic scroll compressors with internal thermal
protection, anti-vibration supports and crankcase heaters
Single refrigerant circuit (*) conforming to EC Directives
(PED 97/23/CE) in copper tubing including filter dryer,
liquid sight glass, dual flow thermostatic valve with
external equalisation, high and low pressure switches and
high pressure transducers
Environmentally friendly R410A Refrigerant
Water side brazed plate heat exchanger in stainless
steel insulated with closed cell expanded polyurethane
Free-cooling air side exchange coil with aluminium fins
and mechanically-expanded copper tubes
Free-cooling pump driven by microprocessor control
Water flow differential pressure switch
Acousti-composite fans: Sickle-blade axial fans,
statically and dynamically balanced and made from
composite materials for high efficiency and low acoustic
impact with internal and external safety protection grilles
(motor with IP54 protection grade)
Modulating condensation control based on the
condensation pressure
Electrical panel conforming to EC Directives
(2006/95/EC and EMC 2004/108/EC) protection grade
IP54 with auxiliary transformer, lockable general cut off
switch, anti-condensation heaters, automatic magnetothermal cut off switches and remote control
Sequence phase control
Microprocessor control system including:
- Local user terminal externally visible and accessible via
an access hatch
- Chilled/hot water temperature regulation (ERAH) on the
discharge

Total Operating Performance


Electronic expansion valve directly controlled by the
unit microprocessor control
Evolved UpCO1m control for:
- Discharge water temperature regulation
- Management of the electronic thermostatic valve
- Management of Intelligent free-cooling
- Monitoring of the refrigerant load
- Self-adjustment of the set-point regulation
- Integrated LAN card
- Compatibility with the most common external BMS
systems and with the Modbus protocol using only a
RS485 card

(*)ERAF models with **22A suffix are available with two


compressors on two circuits

0721A

0821A

0921A

0922A

1021A

1022A

1221A

1222A

400 / 3 + N / 50

Fans

nr.

Refrigerant circuits

nr.

Compressors

nr. x mod

Evaporator

nr.

Evaporator

mod

2 x Scroll
1

2
Plate

ERAF - Low noise version


Cooling capacity (1)

kW

50

59

69

80

88

88

102

102

117

118

Absorbed power (1)(2)

kW

14,7

18,8

20,7

23,3

27,7

27,7

31,8

31,8

37,4

37,5

3,40

3,13

3,35

3,43

3,17

3,17

3,20

3,20

3,14

3,14

kW

35

37

43

52

53

53

62

62

71

71

E.E.R. (2)

- Anti-freeze protection
- Compressor timing and protection
- Compressor rotation based on FIFO logic
- Pump rotation on a timed basis for equal operation and
startup of the stand-by pump (with alarm signal) in the
event of a breakdown
- Display of compressor operating hours
- Alarm code signal
- General alarm with clean signal contact
- ON-OFF remote control

0621A

V/ph/Hz

Capacity in free-cooling (3)


E.E.R. (3)(4)

22,40

23,50

21,30

18,98

18,98

19,53

25,58

25,58

22,80

22,84

Noise pressure level (5) dB(A)

42,6

43,5

44,0

44,3

44,3

44,3

53,4

53,4

54,7

54,7

ERAF - Ultra low noise version


Cooling capacity (1)

kW

48

56

67

77

84

84

97

97

112

113

Absorbed power (1)(2)

kW

15,2

19,8

22,0

24,4

29,3

29,3

33,8

33,9

39,6

39,7

3,18

2,85

3,04

3,16

2,87

2,87

2,87

2,88

2,83

2,85

kW

31

32

38

46

47

47

54

54

63

63

24,29

25,29

20,51

20,02

20,51

20,51

25,91

25,91

24,63

24,29

39,1

39,8

40,3

40,1

40,1

40,1

49,6

49,6

51

51

E.E.R. (2)
Capacity in free-cooling (3)
E.E.R. (3)(4)
Noise pressure level (5)

dB(A)

1. Data refer to nominal


conditions: water temperature
10/15C; external temperature
35C; glycol 20%; R410A
refrigerant
2. Data refer to the total
absorbed power (compressors
and fans)
3. Data refer to nominal
conditions: inlet water
temperature 15C; external
temperature 5C; glycol 20%
4. Data refer to the absorbed
power of the fans and the freecooling pump
5. Data measured in free
field at 10 metres from the
unit operating at nominal
conditions, coil side, Q=2
directional factor
6. Data refer to an empty unit
without pump and water tank

Dimensions and weights


Height

mm

1560

1560

1560

1560

1560

1560

1875

1875

1875

1875

Depth

mm

1190

1190

1190

1190

1190

1190

1190

1190

1190

1190

Width

mm

2010

2010

2805

2805

2805

2805

3075

3075

3075

3075

Weight (6)

kg

700

705

855

884

890

881

1128

1107

1157

1137

Construction Options

Options

Ultra low noise version via a specific algorithm and


soundproofing of the compressors
Partial condensation heat recovery
Integrated hydraulic module with one or two pumps (1
+ 1 stand-by) with heat-protected circulation, expansion
vessel and safety valve
Internal water tank
Internal water tank including a pump to manage the
primary circuit
Power factor improvement compressors
Compressor Softstart
Cataphoresis treatment for the condensing coils
Shut off taps on the compressor discharge
Evaporator, water tank and pump group anti-freeze
heaters
Modification of the set point by external 0-10V signal

Remote user terminal mP20 II (up to 200 metres) for:


- entering of commands
- display unit status and alarms
Clock card
RS485 serial card, FTT10 or TCP/IP for connection to
the Uniflair supervision system or an external BMS
Metal filters and protection grilles for the condensing
coils
Rubber or spring anti-vibration supports

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ERAF 06/12

2012 Schneider Electric. All rights reserved.

Range

Air-cooled modulating water chillers with axial fans and free-cooling system

24

ISAF

25

Uniflair ISAF
Cooling capacity: 60 120 kW
Available versions

Technical Data
ISAF MODEL
Power supply

0621A

0921A

V/ph/Hz

1221A
400 / 3 + N / 50

- low noise

Fans

nr.

Refrigerant circuits

nr.

Refrigerant R-410A
Inverter driven Scroll compressors

Compressors

nr.

Evaporator

nr.

Evaporator

mod

1 ON/OFF + 1 inverter driven (Scroll)


1

1
Plate

ISAF Low noise version


Cooling capacity (1)

kW

62,4

92,2

122,2

Absorbed power (1)(2)

kW

20,0

28,5

38,3

Capacity in free-cooling (3)

kW

38

55

73

Absorbed power in free-cooling (3)(4)

kW

1,6

2,7

3,1

23,8

20,4

20,5

dB(A)

43,5

44,3

54,7

mm

1560

1560

1874

E.E.R. in free-cooling (4)


Noise pressure level (5)
Dimensions and weights

Standard Features
Exclusive free-cooling system completely managed by
the control system
Self-supporting galvanized sheet steel framework with
panels painted with epoxy powder paints (colour RAL
7037) equipped with fast screws for easy and quick
access
Inverter-driven hermetic Scroll compressor, equipped
with
- Inverter speed control
- Oil by-pass valve and line
- Soft start
- Integrated power factor correction condenser
- Integrated thermal protection
- Anti-vibration supports
Inverter driver with IP54 protection grade coupled with
a specific compressor and positioned in a dedicated
housing compartment
Compressor sound-proofing with noise insulating
jackets and, only for model 1221A, soundproofing of the
compressor compartment
Vibration absorbers on the compressor discharge and
suction line (only for model 1221A)
Single refrigerant circuit in accordance with EC
standards (directive PED 97/23/CE) in copper piping
including dehydration filter, liquid sight glass, electronic
expansion valve connected to and driven by the unit
control, high and low pressure switches and transducers.
The refrigerant circuit features an exclusive patented
system for optimum lubrification management of the
tandem compressors
Continuous operation up to -20C
Environmentally friendly refrigerant R410A
Crankcase heaters and inverter with oil heating function
Brazed plate water side heat exchangers in stainless
steel, insulated with closed-cell expanded polyurethane
and anti-freeze heaters
Pump for free-cooling circuit
Water flow differential pressure switch
Air side exchange coil and free-cooling coil with

aluminium fins and mechanically expanded copper piping


Acousti-composite fans: Sickle-blade axial fans,
statically balanced and made from composite material
ensuring elevated efficiency and low noise, with external
and internal protection grill
Modulating condensation control by means of
continuous fan speed control
Electrical panel in accordance with EC standards
(directive 73/23/EC and directive EMC 89/336/EC) IP54
protection grade with auxiliary transformer, minimum and
maximum temperature control, general door interlock cut
off switch, protection and remote control switches
Phase sequence control
UPC1m microprocessor control including:
- Chilled / hot water temperature regulation by means of
self adaption of the set point regulation band
- Management of the electronic thermostatic valve
- Compressor management driven by inverter
- Quick start start-up procedure
- Integrated LAN card
- Integrated clock card
- Compatibility with Modbus protocol via RS485
- Compatability with the most common external BMS:
LONworks, BacNET, TCP/IP, Trend

Height
Length

mm

1190

1190

1192

Width

mm

2008

2798

3075

Weight (basic version) (6)

Kg

751

935

1212

1. Data refer to nominal


conditions: water temperature:
15/10C; external temperature
35C; glycol 20%; inverter
compressor at 90rps R410A
refrigerant
2. Data refer to total input
power (compressors and fans)
3. Data refer to nominal
conditions: inlet water
temperature 15C, external
temperature 5C; glycol 20%;
inverter compressor at 90 rps
4. Data refer to total absorbed
power (fans and free-cooling
pump)
5. Data measured in free field
conditions at 10m from the
unit operating in nominal
conditions, coil side, directional
factor Q=2
6. Data refer to an empty unit
without pump

Construction Options

Options

Integrated hydraulic module with one or two pumps


(1+1 in stand-by) with heat protected circulation,
expansion vessel and safety valve
Integrated hydraulic module with one or two inverter
driven pumps (1+1 in stand-by) with heat protected
circulation, expansion vessel and safety valve
Intelligent free-cooling (only with onboard pumps)
Cataphoresis treatment for condensing and free-cooling
coils
Shut-off taps on the compressor discharge
Power factor correction on compressors
Modification of the set-point by external signal 0-10V
EC fans

Remote user terminal mP20 II (up to 200 metres) for:


- entering of commands
- display unit status and alarms
RS485 serial adaptor used to communicate with the
Uniflair supervisory system or to interface with external
BMS
LON F T T10 serial adaptor used to communicate with
external BMS managed with LON protocol
TCP/IP serial adaptor used to communicate with
external BMS managed with SNMP protocol
Air side coil protection filters and grills
Rubber or spring anti-vibration supports

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ISAF 06/12

2012 Schneider Electric. All rights reserved.

Range

Air-cooled water chillers with free-cooling system

26

ARAf

27

Uniflair ARAf
Cooling capacity: 130 280 kW
Available versions
- standard with modulating condensation control
- low noise
Refrigerant R-407C
Scroll Compressors

R407C

Technical Data
ARAF MODEL

0644A

0744A

Power supply

V/ph/Hz

Circuits / compressors

nr.

2/4

2/4

Fans

nr.

Condensing coil/free-cooling coil

nr.

Evaporator

nr. x mod

0964A

1084A

1204A

2/4

2/4

2/4

400 / 3 / 50

1+1/1+1
1 x Shell & Tube

Basic version
Cooling capacity (1)

kW

144

177

203

245

276

Absorbed power (1)

kW

52

57

78

90

103

Cooling capacity in free-cooling (4)

kW

85

146

152

196

202

Absorbed power in free-cooling (4)

kW

6,3

8,4

7,9

9,9

10,0

Noise pressure level (3)

dB(A)

47

48

48

50

50

Cooling capacity (1)

kW

133

167

188

228

252

Absorbed power (1)

kW

58

62

86

98

114

Cooling capacity in free-cooling (4)

kW

70

123

127

163

166

Absorbed power in free-cooling (4)

kW

5,1

6,5

6,0

7,4

7,6

Noise pressure level (3)

dB(A)

47

48

48

50

50

Low noise version

Standard Features
Exclusive free-cooling Uniflair system completely
managed by the microprocessor control
Self-supporting frame in galvanised steel (colour
RAL7037) with panels varnished with epoxy powders
Modulating condensation control with automatic
regulation of fans speed
Four hermetic Scroll compressors with incorporated
thermal protection, with anti-vibration supports and
crankcase heaters
Shell & tube evaporator insulated with closed-cell
expanded neoprene
Condensing and free-cooling coils with aluminium fins
and mechanically expanded copper tubes
Condensing coil protection filters and grilles
Axial fans, statically and dynamically balanced, with
sickleblades and with safety protection grilles
Two independent refrigerant circuits conforming to
EC norms (PED 97/23/EC directive) in copper tubing
including: filter dryer, flow indicator, thermostatic valves
with external equalization, high & low pressure switches
and high pressure transducers
Free-cooling pump regulated by microprocessor control
Electric panel conforming to EC norms (2006/95/EC
directive and EMC 2004/108/EC directive) complete with
anti-condensation heater, auxiliary circuit, general cut-off
switch, magneto-thermal protection cut-off switches for
compressors, fans and auxiliaries
Sequence phase control
Water flow differential pressure switch
Microprocessor control system UPC1m including:
- local user terminal mP20 II visible on unit with panel
- outlet chilled water temperature regulation
- advanced management of compressors run through
automatic set-point sensitivity regulation
- compressor rotation with FIFO system (run time,
protection and function)
- Pump rotation on a time basis (settable) for equal
operation and start-up of the stand-by pump (with alarm
signal) in the event of a breakdown

- advanced anti-freeze protection on evaporator


- integrated LAN card for local network connection of a
group of chillers (up to 10 units with 1or 2 units in
stand-by)
Moreover, the microprocessor control system permits:
- an overlapped management of units as a single chiller
(up to 10)
- management of double set-point and selection
- free-contact for general alarm and 2 addressable alarms
management
- remote ON-OFF switch
- ability to interface with Modbus protocol directly on
RS485 serial card
- ability to interface with main external communication
protocols: Bacnet, Lonworks, Metasys, TCP/IP and
SNMP

Partial heat recovery (option)

1. Data refer to nominal


conditions: water temperature
10/15C; external temperature
35C; glycol 20%; R407C
refrigerant
2. With pump group
3. Measured in free field
conditions, coil side, direction
factor Q=2, at 10 mt. from the
unit (at nominal conditions)
4. Data refer to nominal
conditions: inlet water
temperature 15C; external
temperature 5C; glycol 20%
5. Data refer to nominal
conditions: recovery water
temperature 40/45C; chilled
water temperature 10/15C;
external temperature 35C;
glycol 20%; R407C refrigerant
6. Data refer to empty unit

Exchanger type

nr.

plate / 2

Thermal heat recovery (5)

kW

48

53

75

76

86

Water flow

l/h

8256

9116

12900

13072

14792

Height

mm

1618

2140

2140

2140

2140

Depth

mm

3807

4542

4542

5242

5242

Width

mm

1193

1344

1344

1344

1344

Weight (only with free-cooling pump) (6)

Kg

1451

2164

2411

2682

2790

Weight (water tank, 2 + f.c. pump) (6)

Kg

1734

2468

2731

3037

3148

Dimensions and weight

Construction Options
Low noise version with modulating condensation control
through special algorithm and sound-proofing of
compressor housing
Partial condensation heat recovery
Integrated hydronic system with 1 or 2 pumps (1 + 1
stand-by), expansion vessel, safety valve, water tank
High and low pressure gauges
Power phase correction capacitors (compressors + fans
+ pump group)
Discharge interception valves on compressor
Sound-proofing of compressor housing
Clock card
RS485 serial adapter used to communicate with Uniflair
supervision system or to interface with external BMS
Condensing coil cataphoresis treatment
R134a Refrigerant (*)

Electronic expansion valve (*)


Intelligent free-cooling (*)
(*) on request

Options
Units can be supplied with the following construction
options:
Remote user terminal mP20 II (up to 200 meters with
shielded cable) for:
- entering of commands
- display unit status and alarms
Spring anti-vibration kit
Rubber anti-vibration kit

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ARAF 06/12

2012 Schneider Electric. All rights reserved.

Range

Air-cooled water chillers with axial fans and free-cooling system

28

BREF

29

Uniflair BREF
Cooling capacity: 400 1200 kW
Available versions
- Low noise
- Ultra-low noise
Refrigerant R-134a
Double screw compressors
ETL certified data

Technical Data
BREF MODEL

1602A

1802A

2202A

2502A

2802A

3212A

Power supply

V/ph/Hz

400 / 3 / 50

Compressors / circuits

nr. x mod

2 x double screw

Evaporator

nr. x mod

Fans

nr.

3612A

4212A

4812A

1 x Shell &Tube
6

10

10

12

12

Unit without economizer


Cooling capacity (1)

kW

400

481

557

590

696

782

883

1000

1143

Absorbed power (1)

kW

115,0

150,0

165,3

178,0

218,0

235,5

278

308

350,5

3,47

3,20

3,37

3,31

3,19

3,32

3,17

3,25

3,26

E.E.R. (1)
Cooling capacity
in free-cooling (3)

kW

256

308

347

351

417

510

602

711

726

Absorbed power
in free-cooling (3)

kW

16,7

17,6

23,9

24,1

25,4

28,5

29,4

38,2

38,6

15,34

17,52

14,50

14,53

16,43

17,9

20,5

18,6

18,8

E.E.R. in free-cooling (3)


Unit with economizer

Standard Features
Exclusive Uniflair free-cooling system completely
managed by the microprocessor control
Self-supporting frame in galvanized steel with panels
finished in epoxy powders (colour RAL7037)
Two semi-hermetic double screw compressors with
internal thermal protection, discharge shut-off valve, oil
heaters and antivibration supports
Two refrigerant circuits conforming to EC norms (PED
97/23/EC) in copper tubes including: filter dryer, flow
indicator, electronic expansion valve managed by the
control system, electrovalve on the liquid line, pressure
switches, transducers and manometers of high and low
pressure
Possibility of operation with external temperatures down
to -25C
High efficiency shell & tube single passage evaporator.
The heat exchanger is insulated with UV-resistant closedcell expanded neoprene
Air side exchange coils with aluminium fins and internally
grooved copper tubes
Water flow differential pressure switch
Acousti-composite fans: Sickle-blade axial fans,
statically and dynamically balanced, made from
composite materials for high efficiency and low acoustic
impact, with safety protection grilles
Modulating condensation control with fan speed
regulation
Electrical panel conforming to EC Norms (Directive
2006/95/EC and EMC 2004/108/EC, IP54) with general
cut-off switch, power supply electic bars distribution,
acquisition of absorbed current, minimum and maximum
internal temperature control, magnetothermal cut-off
switch on the fans and auxiliaries, fuses for the
compressors
Sequence phase, minimum and maximum power supply
monitoring
Free-cooling pump regulated by microprocessor control
Microprocessor control system UPC1m including:

- local user terminal with external accessibility


- outlet chilled water temperature regulation by means of
an exclusive PID algorithm
- electronic expansion valve managed by the control
system
- advanced control of cooling capacity by automatic set-
point sensitivity regulation
- refrigerant charge monitoring
- monitoring of the absorbed current and checking of
possible malfunctions
- advanced anti-freeze protection on evaporator
- integrated LAN card for local network connection of a
group of chillers
- integrated clock card
- rotation of pump group setting functioning and start of
pump in stand-by in the event of pump breakdown
Microprocessor control system in addition allows:
- management of double set-point from remote control
- limiting of absorbed current on pre-set value or external
signal
- rapid Quick Start procedure to reach total cooling
capacity within 3 minutes
- free-contact for general alarm and 2 for addressable
alarms
- remote ON-OFF switch
- ability to interface with Modbus protocol directly on
RS485 serial card
- ability to interface with main external communication
protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP
and SNMP

Cooling capacity (2)

kW

416

517

590

628

764

859

957

1085

1231,5

Absorbed power (2)

kW

124,0

165,5

184,0

197,0

251,0

275

315

350

400

3,35

3,12

3,21

3,19

3,04

3,12

3,04

3,1

3,08

E.E.R. (2)
Cooling capacity
in free-cooling (3)

kW

260

312

352

356

423

510

602

711

726

Absorbed power
in free-cooling (3)

kW

16,9

17,7

24,2

24,5

25,8

28,5

29,4

38,2

38,6

15,42

17,63

14,54

14,56

16,44

17,9

20,5

18,6

18,8

E.E.R. in free-cooling (3)

1. Data refer to nominal


conditions: water temperature
15/10C; external temperature
35C; glycol 20%; refrigerant
R134a
2. Data refer to unit equipped
with economizer in nominal
conditions: water temperature
15/10C; external temperature
35C; glycol 20%; refrigerant
R134a
3. Data refer to nominal
conditions: inlet water
temperature 15C; external
temperature 5C; glycol 20%
4. Measured in free field
conditions 10 m from the unit,
coil side (Q = 2)

Noise pressure levels


Low noise version (4)

dB(A)

61,0

61,1

61,2

60,1

60,9

62,4

62,6

63,1

63,6

Ultra low noise version (4)

dB(A)

55,0

55,2

55,6

54,8

55,0

57,5

57,6

58,0

58,4

Height

mm

2525

2525

2525

2525

2525

2525

2525

2525

2525

Length

mm

4931

4931

6357

6357

6357

8890

8890

10320

10320

Width

mm

2200

2200

2200

2200

2200

2200

2200

2200

2200

Dimensions

Construction Options
Double power supply with automatic integrated
management on the active line
Fans with electronic commutation motors (EC)
Power phase correction capacitors
Economizer (permits an increase in both capacity and
E.E.R.)
Operation possible with external temperature up to
50C at full load
Ultra-low noise version with sound-proof casing and
mufflers for the compressors
Intelligent Free-cooling for an increase in efficiency with
unit in stand-by
Glycol-free version
Partial condensation heat recovery
Suction shut-off valves on compressor
Integrated hydronic system with 1 or 2 circulation
pumps (1+1 stand-by)
Integrated hydronic system with 1 or 2 inveter-driven
circulation pumps (1+1 stand-by) (*)
Condensing and free-cooling coils equipped with metal
safety grilles and filters
Coil manifolds protection panels

Condensing and free-cooling coil cataphoresis or


prepainting treatment (*)
(*) on request

Options
The units can be supplied with the following external
accessories:
Remote user terminal mP20 II (up to 200 metres with
shielded cable) for:
- entering of commands
- display unit status of alarms
Spring anti-vibration kit
Flanged type hydraulic connection
RS485 serial adaptor used to communicate with the
Uniflair supervisory system or to interface with external
BMS
LON F T T10 serial adaptor used to communicate with
external BMS managed with LON protocol
TCP/IP serial adaptor used to communicate with
external BMS managed with SNMP protocol

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BREF 06/12

2012 Schneider Electric. All rights reserved.

Range

Air-cooled modulating water chillers with axial fans and free-cooling system

30

BCEF

31

Uniflair BCEF

Cooling capacity: 400 1100 kW


Available versions
- low noise
Refrigerant R-134a
oil-free centrifugal compressors
with magnetic bearings

Technical Data
BCEF Model

0301A

Power Supply

V/ph/Hz

Compressor/s

nr x model

Cooling circuits

nr

Evaporator

nr x model

Fans

nr x model

Exclusive Uniflair free-cooling system completely


managed by the microprocessor control
Self-supporting frame in galvanized steel with panels
finished in epoxy powders (colour RAL9022)
Between one to three oil free centrifugal compressors
with magnetic bearings equipped with:
- internal thermal protection
- protection and control of the rotation axis position
- brushless synchronized DC motor
- integrated control system
- speed control with inverter
- soft start start-up
- phase sequence control
- pre-rotation valve
- temperature and pressure sensors
- 2 centrifugal compression stages
- anti-vibration kit
Soundproofing enclosures for compressor/s
Single refrigerant circuit conforming to EC standards
(PED 97/23/ CE) with copper tubing including: filter dryer,
liquid sight glass, electronic expansion valve controlled
by a level sensor, discharge and suction taps on the
compressor, pressure switches, high and low pressure
transducers and gauges
By-pass line for vacuum start-up with high pressure
ratio
Flooded evaporator featuring an integrated de-mister
to prevent the formation of droplets: the exchanger is
insulated with closed-cell expanded polyurethane
Differential water pressure switch
Air side exchange coil with aluminum fins and internally
grooved copper tubes
Acoustic-composite fans: Sickle-blade axial fans,
statically and dynamically balanced, made from
composite materials for high efficiency and low acoustic
impact, with safety protection grilles
Modulating condensation control with continuous
regulation of the fans speed
Electric panel conforming to EC standards (2006

0632A

0752A

0903A

1103A

400/3/50
1 x oil free

2 x oil free

3 x oil free

1
1 x flooded
6

10

12

14

16

Cooling capacity (1)

kW

310

411

550

637

800

917

1213

Absorbed power (2)

kW

89,4

121,0

158,1

177,1

228,3

266,0

359,9

3,47

3,40

3,48

3,60

3,50

3,45

3,37

Free-cooling capacity (3)

kW

246

296

395

427

587

682

783

Absorbed power
in free-cooling (3)(4)

kW

16,0

17,1

24,4

28,2

32,6

41,3

45,8

15,37

17,27

16,18

15,16

18,01

16,51

17,08

Noise pressure level (5)

dB(A)

52,1

52,5

53,5

54,0

55,0

55,0

55,5

Max. ambient temperature

E.E.R. in free-cooling (3)(4)

/95 /EC and EMC 2004/108/EC directives) with EMC


integrated filter for protection of the harmonics, maximum
internal temperature control, absorbed current control
auxiliary transformer, general auxiliary cut-off switch, fuses
on the compressors and remote control cut-off switches
Line reactance for each compressor to stabilize the
power supply
Phase sequence control and minimum / maximum
power supply and voltage
Free-cooling pump regulated by microprocessor control
Microprocessor control system including:
- continuous control of the cooling capacity by means of
an inverter and IGV (Inlet Guide Vane)
- local user terminal with external display
- outlet chilled water temperature regulation by means of
an exclusive PID algorithm
- integrated LAN card for connecting more than one unit
to the local area network
- acquisition and management of main electrical data
- clock card
Microprocessor control system in addition allows:
- USB card for easy download of the operating
parameters
- management of double set-point from remote control
- free-contact for general alarm and 2 for addressable
alarms
- remote ON-OFF switch
- integrated RS485 serial card for direct connection to
external BMS
- direct interface with serial BMSs with Modbus protocol
- interface with main BMS protocols, such as Bacnet,
Lonworks, Trend, Metasys, SNMP/TCP-IP and KNX

0532A

Unit with asynchronous motor fans (AC)

E.E.R. (2)

Standard Features

0401A

1. Data refer to nominal


conditions: water temperature
10/15C; external temperature
35C; glycol 20%; refrigerant
R134a
2. Data refer to nominal
conditions: inlet water
temperature 15C; external
temperature 5C; glycol 20%;
refrigerant R134a
3. Measured in free field
conditions 10 m from the unit,
coil side (Q = 2)

40

Unit with electronically commutated motor fans (EC)


Cooling capacity (1)

kW

310

411

550

637

800

917

1213

Absorbed power (2)

kW

89,2

120,9

157,9

176,8

222,3

260,2

351,3

3,47

3,40

3,48

3,60

3,60

3,52

3,45

Free-cooling capacity (3)

kW

273

339

452

482

672

779

905

Absorbed power
in free-cooling (3)(4)

kW

19,8

21,3

30,0

34,9

41,0

51,1

57,4

13,74

15,90

15,09

13,83

16,39

15,26

15,76

Noise pressure level (5)

dB(A)

52,1

52,5

53,5

54,0

55,0

55,0

55,5

Max. ambient temperature

E.E.R. (2)

E.E.R. in free-cooling (3)(4)

43

Dimensions
Height

mm

2510

2510

2510

2510

2510

2510

2510

Length

mm

5000

5000

6430

7860

9290

10720

12150

Depth

mm

2200

2200

2200

2200

2200

2200

2200

Construction Options

Options

Double power supply with automatic integrated


management on the active line
Separate power supply for quick start procedure
Double power supply with automatic integrated
management on the active line and additional separate
power supply for quick start procedure
Power meter for a continuous measurement of the unit
power consumption and communication to the BMS
Acoustic-composite fans with electronic commutation
motors (EC)
Intelligent free-cooling
Glycol free arrangement (*)
Integrated hydronic system with 1 or 2 circulation
pumps (1 + 1 stand-by)
Integrated hydronic system with 1 or 2 Inverter-driven
circulation pumps and pressure transducers (1 + 1 stand-by)
Coils equipped with metal safety grilles and filters
Coil manifolds protection panels
Condensing coil cataphoresis or pre-painting treatment (*)

The units can be supplied with the following external


accessories:
Remote user terminal PDG (up to 200 meters with
shielded cable) for:
- entering of commands
- display unit status of alarms
Spring anti-vibration kit
Flanged type hydraulic connection
Additional RS485 serial adaptor used to communicate
with the Uniflair supervisory system or to interface with
external BMSs
LON FTT10 serial adaptor used to communicate with
external BMSs managed with LON protocol
TCP/IP serial adaptor used to communicate with
external BMSs managed with SNMP protocol
Lifting kit

(*) on request

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BCEF 06/12

2012 Schneider Electric. All rights reserved.

Range

Water cooled water chiller and heat pump

32

BRWC - BRWH

33

Uniflair BRWC - BRWH


Range

Technical Data

Cooling capacity: 300 1200 kW


Heating capacity: 370 1370 kW

BRWC/BRWH
MODELS

- basic
- sea water condersers
- high condensing water temperature (**)
Refrigerant R-134a
Double screw compressors

1602A

1802A

2002A

2202A

2502A

2802A

3202A

Power Supply

V/ph/Hz

400 / 3 / 50

Compressors

nr x mod

2 x Semi-hermetic double screw

Evaporator

nr x mod

1 x Shell & Tube

Condensers

nr x mod

2 x Shell & Tube

3602A

4202A

4802A

Cooling only (BRWC)


Cooling capacity (1)

kW

330

389

430

476

544

631

712

830

954

1077

1204

Absorbed power (1)

kW

71,8

82,2

96,9

100,2

116,6

131,5

146,0

172,8

196,3

225,9

249,0

I.P.L.V. (3)

5,10

5,52

5,00

5,52

5,88

5,50

5,68

5,63

6,03

5,50

5,63

E.S.E.E.R (4)

4,78

5,11

4,67

5,11

5,35

5,08

5,26

5,15

5,45

5,03

5,20

377

440

494

541

627

715

806

938

1091

1216

1368

Noise pressure level


basic version (5)

73,5

73,7

73,8

78,0

79,5

79,7

79,6

77,3

75,3

76,3

78,4

Noise pressure level


LN version (5)

64,0

63,9

64,6

68,5

69,6

68,7

72,4

69,3

69,1

71,8

72,5

Heat pump (BRWH)


Heating capacity (2)

kW

Noise levels

Standard Features
Self-supporting frame in galvanised steel with panels
finished in epoxy powders (colour RAL7037)
Two semi-hermetic double screw compressors with
internal thermal protection, oil heaters and anti-vibration
supports
Two refrigerant circuits conforming to EC standards
(PED 97/23/CE) in copper tubing including: filter dryer,
liquid sight glass, electronic expansion valve, discharge
shut-off valve, pressure gauges, pressure switches and
high and low pressure transducers
Shell & Tube evaporator insulated with closed-cell
expanded neoprene
Shell & Tube condenser
Water flow differential pressure switch for the evaporator
and condensers
Electric panel conforming to EC standards (2006/95/EC
and EMC 2004/108/EC directives) with maximum internal
temperature control, auxiliary transformer, auxiliary general
cut off switch, fuses for compressors, cut off switches
Phase sequence and min / max voltage control
UPC1m microprocessor control system including:
- mP20II local user terminal visible externally and
accessible through a door panel
- chilled water / hot discharge water temperature
regulation
- advanced start-up management with 8 partialization
steps with automatic set-point regulation and
compressor rotation with FIFO logic (run time counter,
inrush counter and counter threshold for programmed
maintenance)
- advanced evaporator anti-freeze protection
- integrated LAN card for connection to the local network
of a group of chillers (up to 10 units with one or two in
reserve)
- modulating condensation control (with kit: see options)
- clock card
The microprocessor control system also includes:
- external evaporator pump group management
- set point adjustment from external 0-10V signal

- double set-point management with contact selection


- general alarm contact and 2 addressable alarms
- ON-OFF remote control
- ability to interface with Modbus protocol directly on
RS485 serial card
- ability to interface with main external communication
protocols: Bacnet, Lonworks, Metasys, TCP/IP and
SNMP

Dimensions
Height

mm

2050

2050

2050

2050

2050

2060

2060

2295

2295

2295

2295

Length

mm

3660

3660

3660

3800

3800

4070

4070

4130

4130

4130

4130

Depth

mm

860

860

860

860

860

860

860

1485

1485

1485

1485

Width with heat


recovery

mm

1680

1680

1680

1680

1680

1755

1755

1660

1660

1660

1660

Weight (6)

kg

2815

2865

2930

3649

3707

3747

3818

5360

5481

5638

5719

2. Data refer to nominal


conditions: Evaporator in/
out water temperature:
12/7C; Condenser in/out
water temperature: 40/45C;
condenser fouling coefficient:
0,000043 mC/W; evaporator
fouling coefficient: 0,000043
mC/W; R134a refrigerant
3. Integrated Partial Load
Value: based on ARI conditions
4. European Seasonal Energy
Efficiency Ratio
5. Measured in free field with
Q=2 directionality factor, at a
distance of 1 mt. from the unit
6. Data refer to basic versions
without load

Construction Options
Low noise version with sound proofed housing for the
compressors
Low external temperature version with anticondensation heater for the electrical panel and heaters
for the evaporator and condensers
Condensers for sea water (*)
High condensation temperature version (**)
Partial / total integrated condensation heat recovery
Low temperature glycol water mixture production (down
to -10C)
RS485 serial card for connection to the Uniflair
supervision system or an external BMS
LON FFT10 serial card for connection to an external
BMS with LON protocol
Power phase correction condensers
Unit predisposed for outdoor installation (*)

(*) on request
(**) available only for 1402A, 2002A, 2202A, 3202A,
3602A models

Options
Pressostatic valve with integrated control for control
software
Remote control panel which allows:
- display / modification of settings
- display of activated alarms
Spring anti-vibration anti-seismic supports
Neoprene anti-vibration supports.

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BRWC-BRWH 06/12

2012 Schneider Electric. All rights reserved.

Available versions

1402A

1. Data refer to nominal


conditions: Evaporator in/
out water temperature:
12/7C; Condenser in/out
water temperature: 30/35C;
condenser fouling coefficient:
0,000043 mC/W; evaporator
fouling coefficient: 0,000043
mC/W; R134a refrigerant

Water-cooled modulating water chillers for indoor installation

34

BCWC

35

Uniflair BCWC

Cooling capacity: 300 1300 kW


Available versions
- basic
- sea water condersers (*)
Refrigerant R-134a
oil-free centrifugal compressors
with magnetic bearings

Technical Data
BCWC MODEL
Power supply

0320A

0630A

0950A

V/ph/Hz

1250A

400 / 3 / 50

Compressors

nr, x mod

Evaporator

nr, x mod

1 x centrifugal

2 x centrifugal

1 x flooded

3 x centrifugal

Condensers

nr, x mod

1 x Shell & Tube

4 x centrifugal

Cooling only
Cooling capacity (1)

kW

320

630

950

1250

Absorbed power (1)

kW

64

130

192

247

E.E.R. (1)

kW

5,0

4,9

4,9

5,1

I.P.L.V. (2)

8,85

8,74

8,84

8,86

8,34

8,16

8,31

8,32

67,3

70,3

72,1

73,3

4. Measured in free field with


Q=2 directional factor, at a
distance of 1 mt. from the unit
5. Data refers to unloaded units

Noise levels
dB(A)

Dimensions and weight

Self supporting metal frame in galvanised steel


varnished in epoxy powders (colour RAL7037)
Between one and four oil free centrifugal compressors
with magnetic bearings equipped with:
- internal thermal protection
- protection and control of the rotation axis position
- brushless synchronized DC motor
- integrated control system
- speed control with inverter
- soft start start-up
- phase sequence control
- pre-rotation valve
- temperature and pressure sensors
- 2 centrifugal compressor stages
- anti-vibration supports
Single refrigerant circuit conforming to EC standards
(PED 97/23/CE directive) with copper tubing including:
filter dryer, liquid sight glass, electronic expansion valve
controlled by a level sensor, discharge and suction taps
on the compressor, pressure switches, high and low
pressure transducers and gauges
By-pass line for vacuum start-up with high pressure
ratio
Shell & Tube evaporator featuring an integrated demister to prevent the formation of droplets: the exchanger
is insulated with closed-cell expanded polyurethane
Differential water pressure switch for the evaporator and
the condenser
Shell & Tube condenser
Electric panel conforming to EC standards (2006
/95 /EC and EMC 2004/108/EC directives) with EMC
integrated filter for protection of the harmonics, maximum
internal temperature control, auxiliary transformer, general
auxiliary cut-off switch, fuses on the compressors and
remote control cut-off switches
Line reactance for each compressor to stabilize the
power supply
Phase sequence control and minimum / maximum

power supply and voltage


UPC3m microprocessor control system including:
- continuous control of the cooling capacity by means of
an inverter and IGV (Inlet Guide Vane)
- PGD local user terminal with external display
- outlet water temperature regulation
- integrated LAN card for connecting more than one unit
to the local area network
- clock card
The control system also features:
- external pump group management for the evaporator
- set-point modification by an external 0-10V signal
- management of a double set-point with contact
selection
- general alarm contact and 2 addressable alarms
- remote ON-OFF control
- ability to interface with Modbus protocol directly on
RS485 serial card
- ability to interface with main external communication
protocols: Bacnet, Lonworks, Metasys, TCP/IP and
SNMP

2. Integrated Partial Load


Value: based on ARI conditions

E.S.E.E.R. (3)
Noise pressure level (4)

Standard Features

1. Data refers to nominal


conditions: In/out evaporator
water temperature: 12/7C;
In/out condenser water
temperature: 30/35C;
Condenser fouling coefficient:
0,000043 mC/W; Evaporator
fouling coefficient: 0,000043
mC/W; R134a refrigerant

Height

mm

2028

2130

1924

1924

Length

mm

2640

2940

3294

4591

Width

mm

1061

1022

1544

1505

Weight (5)

kg

1585

2814

3752

5760

Construction Options

Options

Condenser for sea water use (*)


RS485 serial card for connection to Uniflair Supervision
system or an external BMS
LON FFT10 serial card for connection to an external
BMS with LON protocol

Remote control panel which enables:


- the settings to be displayed / changed
- alarm status to be displayed
Neoprene anti-vibration supports

3. European Seasonal Energy


Efficiency Ratio

(*) on request

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BCWC 06/12

2012 Schneider Electric. All rights reserved.

Range

Condenserless chiller with remote condenser

36

BRRC

37

Uniflair BRRC
Range
Cooling capacity: 300 1200 kW
Available versions
- Basic
- High condensing water temperature (**)
Refrigerant R-134a
Double screw compressors

Technical Data
BRRC MODEL

1402A

1602A

1802A

2002A

2202A

2502A

2802A

3202A

3602A

4202A

4802A

1. Data refer to nominal


conditions: Evaporator in/out
water temperature: 12/7C;
Condenser temperature: 50C;
Evaporator fouling coefficient:
0,000043 m2C/W; R134a
refrigerant

Power supply

V/ph/Hz

400 / 3 / 50

Compressors

nr. x mod

2 x Semi hermetic double screw

Evaporator

nr. x mod

Cooling capacity (1)

kW

284,0

336,0

377,0

414,0

482,0

551,0

630,0

726,0

842,0

938,0

1069,0

Absorbed power (1)

kW

88,7

100,3

115,5

122,2

143,9

159,0

176,3

208,3

244,0

272,0

299,8

E.E.R.

mod

3,2

3,4

3,3

3,4

3,4

3,5

3,6

3,5

3,5

3,5

3,6

2. Measured in free field with


Q=2 directionality factor, at 1
mt. from the unit

Noise pressure level


basic version (2)

dB(A)

73,5

73,7

73,8

78,0

79,5

79,7

79,6

77,3

75,3

76,3

78,4

3. Data refer to a basic version


empty unit

Noise pressure level


LN version (2)

dB(A)

64,0

63,9

64,6

68,5

69,6

68,7

72,4

69,3

69,1

71,8

72,5

1 x Shell & Tube

Noise levels

Standard Features
Self-supporting frame in galvanised steel with panels
finished in epoxy powders (colour RAL7037)
Two semi-hermetic double screw compressors with
internal thermal protection, oil heaters and anti-vibration
supports
Two refrigerant circuits conforming to EC standards
(PED 97/23/CE) in copper tubing including: filter dryer,
liquid sight glass, electronic expansion valve, discharge
shut-off valve, pressure gauges, pressure switches and
high and low pressure transducers
Shell & Tube evaporator insulated with closed-cell
expanded neoprene
Evaporator water flow pressure switch
Electric panel conforming to EC standards (2006/95/EC
and EMC 2004/108/EC directives) with maximum internal
temperature control, auxiliary transformer, general cut off
switch, fuses for compressors, cut off switches
Phase sequence and min / max voltage control
UPC1m microprocessor control system including:
- mP20II local user terminal visible externally and
accessible through a door panel
- outlet chilled water temperature
- advanced start-up management with 8 partialization
steps with automatic set-point regulation and
compressor rotation with FIFO logic (run time counter,
inrush counter and counter threshold for programmed
maintenance)
- advanced evaporator anti-freeze protection
- integrated LAN card for connection to the local network
of a group of chillers (up to 10 units with one or two in
reserve)
- clock card

The microprocessor control system also includes:


- external evaporator pump group management
- set point adjustment from external 0-10V signal
- double set-point management with contact selection
- general alarm contact and 2 addressable alarms
- ON-OFF remote contact
- ability to interface with main external communication
protocols: Modbus, Bacnet, Lonworks, Trend, Metasys,
TCP/IP and SNMP

mm

2010

2010

2010

2010

2010

2010

2010

1870

1870

1870

1870

Length

mm

3700

3700

3700

3700

3700

3900

3900

4130

4130

4130

4130

Width

mm

850

850

850

850

850

850

850

1400

1400

1400

1400

Weight (3)

kg

2335

2385

2420

3139

3159

3191

3212

4616

4737

4858

4939

Construction Options

Options

Low-noise version with sound proofed housing for the


compressors
Low temperature water production (to -10C)
RS485 Serial card for connection to the Uniflair
supervision system or an external BMS
LON FFT10 serial card for connection to an external
BMS with LON protocol
Power phase correction condensers
Unit predisposed for outdoor installation (*)

Remote control panel which allows:


- display / modification of settings
- display of activated alarms
Spring anti-vibration supports
Neoprene anti-vibration supports

(*) on request
(**) available only for 1402A, 2002A, 2022A, 3202A,
3602A models

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BRRC 06/12

2012 Schneider Electric. All rights reserved.

Dimensions and weight


Height

Air-cooled water chillers and heat pumps with backward curved blade fans

38

ERCC - ERCH

39

Uniflair ERCC - ERCH


Range
Cooling capacity: 50 120 kW
Available versions
- low noise
- ultra low noise
Refrigerant R-410A
Scroll compressors

Technical Data
ERCC/ERCH MODELS
Power supply

0521A

0621A

0721A

0821A

V/ph/Hz

0921A

0922A

1021A

1022A

1221A

1222A

400 / 3 + N / 50

Refrigerant circuits

nr.

Compressors

nr. x mod

Fans

nr.

Evaporator

nr.

Evaporator

mod

2
2 x Scroll

Plate

ERCC - standard fans


Cooling capacity (1)

kW

48

57

66

76

84

85

97

97

113

113

Absorbed power (1)

kW

16,7

20,4

22,7

26,2

30,0

30,0

34,4

34,4

40,5

40,5

E.E.R. (2)

2,85

2,78

2,90

2,91

2,81

2,82

2,83

2,82

2,79

2,79

E.S.E.E.R. (5)

3,54

3,85

4,09

3,86

3,90

3,75

3,99

3,84

3,98

3,98

ERCH - standard fans

Self supporting frame in galvanised steel with panels


varnished with epoxy powders (colour RAL7037)
Access panel to the unit equipped with handles and fast
screws
Two hermetic scroll compressors with internal thermal
protection, anti-vibration supports and crankcase heaters
(ERCH and low ambient temperature versions)
Single refrigerant circuit (*) conforming to EC Directives
(PED 97/23/CE) in copper tubing including filter dryer,
liquid sight glass, dual flow thermostatic valve with
external equalisation, high and low pressure switches and
high pressure transducers
Environmentally friendly R410A Refrigerant
Water side brazed plate heat exchanger in stainless
steel insulated with closed cell expanded polyurethane
Water flow differential pressure switch
Free-cooling air side exchange coil with aluminium fins
and mechanically-expanded copper tubes
Refrigerant side cycle inversion with 4-way inversion
valve (ERCH)
Single suction backward curved blade centrifugal fans.
The external tri-phase rotary electric motor is directly
coupled and has an IP54 Class F equipped with internal
thermal protection (klixon). The fan impeller is
dynamically and statically balanced and the cushions are
sealed and lubricated for life
Modulating condensation control based on the
condensation pressure
Electrical panel conforming to EC Directives
(2006/95/EC and EMC 2004/108/EC) protection grade
IP54 with auxiliary transformer, lockable general cut off
switch, magneto-thermal
cut off switches and remote control
Sequence phase control
Anti-condensation heaters for the electrical panel (ERCH
and low ambient temperature versions)
Microprocessor control system including:
- Local user terminal
- Chilled / hot water temperature regulation (ERCH)

- Production of chilled water to -15C


- Anti-freeze protection
- Compressor timing and protection
- Compressor rotation based on FIFO logic
- Pump rotation on a timed basis for equal operation and
startup of the stand-by pump (with alarm signal) in the
event of a breakdown
- Display of compressor operating hours
- Alarm code signal
- General alarm with clean signal contact
- ON-OFF remote contact

kW

59

69

79

92

102

n.a.

118

n.a.

138

n.a.

kW

17,9

20,9

23,2

27,7

30,9

n.a.

35,7

n.a.

42,3

n.a.

2. Data refer to the total


absorbed power (compressors
and fans)
3. Data refer to nominal
conditions: water temperature
40/45C, external temperature
7C dry bulb, 6C wet bulb;
50Pa; R410A refrigerant
4. Data measured in free field
at 1 mt. from the ducted unit at
nominal conditions, coil side,
Q=2 directional factor

C.O.P. (2)

3,29

3,29

3,40

3,32

3,30

n.a.

3,30

n.a.

3,26

n.a.

Noise pressure level (4) dB(A)

67,5

67,6

67,5

69,1

69,1

69,1

71,2

71,2

72,5

72,5

5. European Seasonal Energy


Efficiency Ratio

48

57

66

76

84

85

97

97

113

113

6. Data refer to an empty unit


without pump and water tank

ERCC - EC Fans
Cooling capacity (1)

kW

Absorbed power (1)

kW

16,7

20,4

22,8

26,2

30,0

30,0

34,5

34,5

40,6

40,6

E.E.R. (2)

2,85

2,78

2,89

2,91

2,81

2,82

2,82

2,81

2,80

2,80

E.S.E.E.R. (5)

4,02

4,23

4,42

4,28

4,27

4,13

4,41

4,21

4,40

4,39

ERCH - EC Fans
Heating capacity (3)

kW

56

65

76

87

97

n.a.

113

n.a.

131

n.a.

Absorbed power (3)

kW

17,1

20,3

22,2

26,6

30,1

n.a.

33,7

n.a.

40,7

n.a.

C.O.P. (2)

3,25

3,23

3,41

3,29

3,22

n.a.

3,36

n.a.

3,22

n.a.

Noise pressure level (4) dB(A)

65,2

65,3

65,3

66,8

66,8

66,8

69,9

69,9

71,2

71,2

Dimensions and weights

Top Level Options


Electronic expansion valve directly controlled by the
unit microprocessor control
Single suction back ward cur ved fans with
electronically commutated motor (EC)
Evolved UpCO1m control for:
- Discharge water temperature regulation
- Management of the electronic thermostatic valve
- Monitoring of the refrigerant load
- Self-adjustment of the set-point regulation
- Evolved defrost operation management (ERCH)
- Integrated LAN card
- Compatibility with the most common external BMS
and with the Modbus protocol using only a RS485
card

(*) ERCC with (**) 22A suffix are available with two
compressors on two circuits

Height

mm

1836

1836

1836

1836

1836

1836

2146

2146

2146

2146

Depth

mm

1190

1190

1190

1190

1190

1190

1190

1190

1190

1190

Width

mm

2006

2006

2798

2798

2798

2798

3067

3067

3067

3067

Weight ERCC basic (6)

kg

773

778

921

957

963

974

1197

1196

1232

1232

Weight ERCH basic (6)

kg

797

802

951

987

994

n.a.

1241

n.a.

1276

n.a.

Construction Options
Ultra low noise version by means of sound-proofing the
compressors
Partial / total condensation heat recovery
Integrated hydraulic module with one or two pumps (1
+ 1 stand-by) with heat-protected circulation, expansion
vessel and safety valve
Internal water tank
Internal water tank including a pump to manage the
primary circuit
Power factor improvement compressors
Compressor Softstart
Cataphoresis treatment for the condensing coils
Shut off taps on the compressor discharge

Evaporator, water tank and pump group anti-freeze


heaters
Modification of the set point by external 0-10V signal
EC fans

Options
Remote user terminal
Clock card
RS485, FTT10 or TCP/IP serial card
Metal filters and protection grilles for the condensing
coils
Rubber or spring anti-vibration supports

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ERCC-ERCH 06/12

2012 Schneider Electric. All rights reserved.

Standard Features

Heating capacity (3)


Absorbed power (3)

1. Data refer to nominal


conditions: water temperature
12/7C; external temperature
35C; glycol 0%; 50Pa; R410A
refrigerant

Air-cooled modulating water chillers and heat pumps with backward curved blade fans

40

ISCC - ISCH

41

Uniflair ISCC - ISCH


Cooling capacity: 60 120 kW
Heating capacity: 66 130 kW
Available versions
- low noise
Refrigerant R-410A
Inverter driven Scroll compressors

Technical Data
ISCC/ISCH MODELS
Power supply

0621A

0921A

V/ph/Hz

Refrigerant circuits

nr.

Compressors

nr.

1221A
400 / 3 + N / 50

1 ON/OFF + 1 inverter driven (Scroll)

Fans

nr.

Evaporator

nr.

Evaporator

mod

Plate

E.S.E.E.R. (4)

3,98

4,42

4,35

I.P.L.V. (5)

5,63

5,70

5,66

67,4

98,7

131,0

4. European Seasonal Energy


Efficiency Ratio
5. Integrated Partial Load Value

Cooling capacity (1)

kW

59,7

88,1

117,0

Absorbed power (1)(2)

kW

21,4

30,8

41,4

ISCH Low noise version

Self-supporting galvanized sheet steel framework with


panels painted with epoxy powder paints (colour RAL
7037) equipped with fast screws for easy and quick
access
Inverter-driven hermetic Scroll compressor, equipped
with
- Inverter speed control
- Oil by-pass valve and line
- Soft start
- Integrated power factor correction condenser
- Integrated thermal protection
- Anti-vibration supports
Inverter driver with IP54 protection grade coupled with
a specific compressor and positioned in a dedicated
housing compartment
Compressor sound-proofing with noise insulating
jackets and, only for model 1221A, soundproofing of the
compressor compartment
Vibration absorbers on the compressor discharge and
suction line (only for model 1221A)
Single refrigerant circuit in accordance with EC
standards (directive PED 97/23/CE) in copper piping
including dehydration filter, liquid sight glass, electronic
expansion valve connected to and driven by the unit
control, high and low pressure switches and transducers.
The refrigerant circuit features an exclusive patented
system for optimum lubrification management of the
tandem compressors
Continuous operation up to -20C (only ISCC)
Environmentally friendly refrigerant R410A
Crankcase heaters and inverter with oil heating function
Brazed plate water side heat exchangers in stainless
steel, insulated with closed-cell expanded polyurethane
and anti-freeze heaters
Refrigerant side cycle inversion with 4-way inversion
valve (only ISCH)
Water flow differential pressure switch
Air side exchange coil and free-cooling coil with
aluminium fins

and mechanically expanded copper piping


Backward curved blade single aspiration centrifugal fans
with directly coupled motor. The impeller is statically and
dynamically balanced and the bearings are sealed and
lubricated for life.
Modulating condensation control by means of
continuous fan speed control
Electrical panel in accordance with EC standards
(directive 73/23/EC and directive EMC 89/336/EC) IP54
protection grade with auxiliary transformer, minimum and
maximum temperature control, general door interlock cut
off switch, protection and remote control switches
Phase sequence control
UPC1m microprocessor control including:
- Chilled / hot water temperature regulation by means of
self adaption of the set point regulation band
- Management of the electronic thermostatic valve
- Compressor management driven by inverter
- Quick start start-up procedure
- Integrated LAN card
- Integrated clock card
- Compatibility with Modbus protocol via RS485
- Compatability with the most common external BMS:
LONworks, BacNET, TCP/IP, Trend

2. Data refer to total absorbed


power (compressors and fans)
3. Data refer to nominal
conditions: water temperature
40/45C, external temperature
7C dry bulb 6C wet bulb;
inverter compressor 90rps;
R410A refrigerant; 50Pa

ISCC Low noise version

Heating capacity (3)

Standard Features

1. Data refer to nominal


conditions: water temperature:
12/7C; external temperature
35C; glycol 0%; inverter
compressor at 90rps R410A
refrigerant; 50Pa

kW

Absorbed power (3)(2)

kW

21,5

31,2

42,5

Noise pressure level (6)

dB(A)

67,6

69,1

72,5

ISCC Low noise version (EC)


Cooling capacity (1)

kW

59,8

88,2

117,1

Absorbed power (1)(2)

kW

21,4

30,8

41,4

E.S.E.E.R. (4)

3,98

4,42

4,35

I.P.L.V. (5)

5,63

5,70

5,66

ISCH Low noise version (EC)


Cooling capacity (1)

kW

67,4

98,7

131,2

Absorbed power (1)(2)

kW

21,6

31,2

42,5

Noise pressure level (6)

dB(A)

65,3

66,8

71,2

6. Data measured in free


field conditions at 1m from
the ducted unit operating at
nominal conditions, coil side,
directional factor Q=2
7. Data refer to an empty unit
without pump

Dimensions and weights


Height

mm

1560

1560

1874

Length

mm

1190

1190

1192

Width

mm

2008

2798

3075

Weight ISCC (basic version) (7)

Kg

818

1179

1277

Weight ISCH (basic version) (7)

Kg

848

1209

1322

Construction Options

Options

Integrated hydraulic module with one or two pumps


(1+1 in stand-by) with heat protected circulation,
expansion vessel and safety valve
Integrated hydraulic module with one or two inverter
driven pumps (1+1 in stand-by) with heat protected
circulation, expansion vessel and safety valve
Cataphoresis treatment for condensing coils
Shut-off taps on the compressor discharge
Power factor correction on compressors
Modification of the set-point by external signal 0-10V
Intelligent free-cooling (only with onboard pump)
EC fans

Remote user terminal mP20 II (up to 200 metres) for:


- entering of commands
- display unit status and alarms
RS485 serial adaptor used to communicate with the
Uniflair supervisory system or to interface with external
BMS
LON F T T10 serial adaptor used to communicate with
external BMS managed with LON protocol
TCP/IP serial adaptor used to communicate with
external BMS managed with SNMP protocol
Air side coil protection filters and grills
Rubber or spring anti-vibration supports

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ISCC-ISCH 06/12

2012 Schneider Electric. All rights reserved.

Range

Air-cooled water chillers with backward curved fans and free-cooling system

42

ERCF

43

Uniflair ERCF
Cooling capacity: 50 110 kW
Available versions
- low noise
- ultra low noise
Refrigerant R-410A
Scroll compressors

Technical Data
ERCF MODEL
Power supply

0521A

0621A

0721A

0821A

V/ph/Hz

0921A

0922A

1021A

1022A

1221A

1222A

400 / 3 + N / 50

Fans

nr.

Refrigerant circuits

nr.

Compressors

nr. x mod

Evaporator

nr.

Evaporator

mod

2 x Scroll
1

2
Plate

ERCC - standard fans


Cooling capacity (1)

kW

51

61

71

82

90

91

104

104

121

122

Absorbed power (1)(2)

kW

17,2

21,0

23,3

26,9

30,9

30,9

35,3

35,3

41,7

41,8

2,97

2,89

3,04

3,04

2,93

2,94

2,96

2,96

2,90

2,91

kW

39

41

47

57

59

59

68

68

80

80

E.E.R. (3)(4)

8,31

8,81

8,83

7,75

8,02

8,02

9,38

9,37

8,50

8,51

Noise pressure level (5) dB(A)

67,5

67,6

67,5

69,1

69,1

69,1

71,2

71,2

72,5

72,5

51

61

71

82

91

91

105

104

121

122

E.E.R. (2)
Capacity in free-cooling (3)

ERCF - EC fans

Standard Features
Exclusive free-cooling system managed completely by
the microprocessor control
Self supporting frame in galvanised steel with panels
varnished with epoxy powders (colour RAL7037)
Access panel to the unit equipped with fast screws
Two hermetic Scroll compressors with internal thermal
protection, anti-vibration supports and crankcase heaters
Single refrigerant circuit (*) conforming to EC Directives
(PED 97/23/CE) in copper tubing including filter dryer,
liquid sight glass, dual flow thermostatic valve with
external equalisation, high and low pressure switches and
high pressure transducers
Environmentally friendly refrigerant R410A
Water side brazed plate heat exchanger in stainless
steel insulated with closed cell expanded polyurethane
Air side free-cooling exchange coil with aluminium fins
and mechanically-expanded copper tubes
Free-cooling pump driven by the microprocessor control
Water flow differential pressure switch
Single suction backward curved blade centrifugal fans.
The external tri-phase rotary electric motor is directly
coupled and has an IP54 Class F equipped with internal
thermal protection (klixon). The fan impeller is dynamically
and statically balanced and the cushions are sealed
and lubricated for life
Modulating condensation control based on the
condensation pressure
Electrical panel conforming to EC Directives
(2006/95/EC and EMC 2004/108/EC) protection grade
IP54 with auxiliary transformer, lockable general cut off
switch, magneto-thermal cut off switches and remote
control
Sequence phase control
Microprocessor control system including:
- Local user terminal
- Chilled / hot water temperature regulation (ERCH)
- Anti-freeze protection
- Compressor timing and protection
- Compressor rotation based on FIFO logic

- Pump rotation on a timed basis for equal operation and


startup of the stand-by pump (with alarm signal) in the
event of a breakdown
- Display of compressor operating hours
- Alarm code signal
- General alarm with clean signal contact
- ON-OFF remote contact

Top Level Options


Electronic expansion valve directly controlled by the
unit microprocessor control
Single suction backward curved fans with
electronically commutated motor (EC)
Evolved UpCO1m control for:
- Discharge water temperature regulation
- Management of the electronic thermostatic valve
- Monitoring of the refrigerant load
- Self-adjustment of the setpoint regulation
- Evolved defrost operation management (ERCH)
- Integrated LAN card
- Compatibility with the most common external BMS
and with the Modbus protocol using only a RS485
card

(*) ERCC with (**) 22A suffix are available with two
compressors on two circuits

Cooling capacity (1)

kW

Absorbed power (1)(2)

kW

E.E.R. (2)
Capacity in free-cooling (3)

kW

17,1

20,8

23,3

26,7

30,7

30,7

35,2

35,2

41,4

41,4

3,00

2,91

3,04

3,07

2,95

2,97

2,97

2,96

2,93

2,94

39

42

47

58

60

60

68

68

80

80

E.E.R. (3)(4)

8,53

9,06

8,81

7,95

8,23

8,23

9,42

9,41

8,74

8,75

Noise pressure level (5) dB(A)

65,2

65,3

65,3

66,8

66,8

66,8

69,9

69,9

71,2

71,2

1. Data refer to nominal


conditions: water temperature
10/15C; external temperature
35C; glycol 20%; 50Pa; R410A
refrigerant
2. Data refer to the total
absorbed power (compressors
and fans)
3. Data refer to nominal
conditions: inlet water
temperature 15C; external
temperature 5C; glycol 20%;
50Pa
4. Data refer to the absorbed
power of the fans and freecooling pump
5. Data measured in free
field at 1 mt. from the ducted
unit operating at nominal
conditions, coil side, Q=2
directional factor
6. Data refer to an empty unit
without pump and water tank

Dimensions and weights


Height

mm

1836

1836

1836

1836

1836

1836

2146

2146

2146

2146

Depth

mm

1190

1190

1190

1190

1190

1190

1190

1190

1190

1190

Width

mm

2006

2006

2798

2798

2798

2798

3067

3067

3067

3067

Weight (6)

kg

866

871

1045

1082

1088

1099

1351

1350

1385

1385

Construction Options
Ultra low noise version by means of sound-proofing the
compressors
Partial / total condensation heat recovery
Integrated hydraulic module with one or two pumps (1
+ 1 stand-by) with heat-protected circulation, expansion
vessel and safety valve
Internal water tank
Internal water tank including a pump to manage the
primary circuit
Power factor improvement compressors
Compressor Softstart
Cataphoresis treatment for the condensing and Freecooling coils

Shut off taps on the compressor discharge


Evaporator, water tank and pump group anti-freeze
heaters
Modification of the set point by external 0-10V signal

Options
Remote user terminal
Clock card
RS485, FTT10 or TCP/IP serial card for connection to
the Uniflair supervision system of an external BMS
Metal filters and protection grilles for the condensing coil
Rubber or spring anti-vibration supports

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ERCF 06/12

2012 Schneider Electric. All rights reserved.

Range

Air-cooled modulating water chillers and heat pumps with backward curved blade fans and free-cooling system

44

ISCF

45

Uniflair ISCF
Cooling capacity: 60 120 kW
Available versions
- low noise
Refrigerant R-410A
Inverter driven Scroll compressors

Technical Data
ISCF MODEL

0621A

0921A

1221A

Power supply

V/ph/Hz

400 / 3 + N / 50

Refrigerant circuits

nr.

Compressors

nr.

Fans

nr.

Evaporator

nr.

Evaporator

mod

1 ON/OFF + 1 inverter driven (Scroll)

Plate

ISCF Low noise version


Cooling capacity (1)

kW

64,7

95,3

126,8

Absorbed power (1)(2)

kW

22,0

31,5

42,4

Capacity in free-cooling (3)

kW

43,6

62,7

84,0

Absorbed power in free-cooling (3)(4)

kW

4,6

7,3

9,2

9,5

8,6

9,1

dB(A)

67,6

69,1

72,5

Height

mm

1560

1560

1874

Length

mm

1190

1190

1192

Width

mm

2008

2798

3075

Weight (basic version) (6)

Kg

751

935

1212

E.E.R. in free-cooling (4)


Noise pressure level (5)
Dimensions and weights

Standard Features
Exclusive free-cooling system completely managed by
the control system
Self-supporting galvanized sheet steel framework with
panels painted with epoxy powder paints (colour RAL
7037) equipped with fast screws for easy and quick
access
Inverter-driven hermetic Scroll compressor, equipped
with
- Inverter speed control
- Oil by-pass valve and line
- Soft start
- Integrated power factor correction condenser
- Integrated thermal protection
- Anti-vibration supports
Inverter driver with IP54 protection grade coupled with
a specific compressor and positioned in a dedicated
housing compartment
Compressor sound-proofing with noise insulating
jackets and, only for model 1221A, soundproofing of the
compressor compartment
Vibration absorbers on the compressor discharge and
suction line (only for model 1221A)
Single refrigerant circuit in accordance with EC
standards (directive PED 97/23/CE) in copper piping
including dehydration filter, liquid sight glass, electronic
expansion valve connected to and driven by the unit
control, high and low pressure switches and transducers.
The refrigerant circuit features an exclusive
patented system for optimum lubrification management of
the tandem compressors
Continuous operation up to -25C
Environmentally friendly refrigerant R410A
Crankcase heaters and inverter with oil heating function
Brazed plate water side heat exchangers in stainless
steel, insulated with closed-cell expanded polyurethane
and anti-freeze heaters
Pump for free-cooling circuit
Water flow differential pressure switch
Air side exchange coil and free-cooling coil with

aluminium fins and mechanically expanded copper piping


Backward curved blade single aspiration centrifugal fans
with directly coupled motor. The impeller is statically and
dynamically balanced and the bearings are sealed and
lubricated for life.
Modulating condensation control by means of
continuous fan speed control
Electrical panel in accordance with EC standards
(directive 73/23/EC and directive EMC 89/336/EC) IP54
protection grade with auxiliary transformer, minimum and
maximum temperature control, general door interlock cut
off switch, protection and remote control switches
Phase sequence control
UPC1m microprocessor control including:
- Chilled / hot water temperature regulation by means of
self adaption of the set point regulation band
- Management of the electronic thermostatic valve
- Compressor management driven by inverter
- Quick start start-up procedure
- Integrated LAN card
- Integrated clock card
- Compatibility with Modbus protocol via RS485
- Compatability with the most common external BMS:
LONworks, BacNET, TCP/IP, Trend

1. Data refer to nominal


conditions: water temperature:
15/10C; external temperature
35C; glycol 20%; inverter
compressor at 90 rps; R410A
refrigerant; ESP=50Pa
2. Data refer to total absorbed
power (compressors and fans)
3. Data refer to nominal
conditions: inlet water
temperature 15C, external
temperature 5C; glycol 20%;
inverter compressor at 90 rps;
R410A refrigerant; ESP=50Pa
4. Data refer to total absorbed
power (fans and free-cooling
pump)
5. Data measured in free
field conditions at 1m from
the ducted unit operating at
nominal conditions, coil side,
directional factor Q=2
6. Data refer to an empty unit
without pump

Construction Options

Options

Integrated hydraulic module with one or two pumps


(1+1 in stand-by) with heat protected circulation,
expansion vessel and safety valve
Integrated hydraulic module with one or two inverter
driven pumps (1+1 in stand-by) with heat protected
circulation, expansion vessel and safety valve
Intelligent free-cooling (only with onboard pumps)
Cataphoresis treatment for condensing and free-cooling
coils
Shut-off taps on the compressor discharge
Power factor correction on compressors
Modification of the set-point by external signal 0-10V
EC fans

Remote user terminal mP20 II (up to 200 metres) for:


- entering of commands
- display unit status and alarms
RS485 serial adaptor used to communicate with the
Uniflair supervisory system or to interface with external
BMS
LON F T T10 serial adaptor used to communicate with
external BMS managed with LON protocol
TCP/IP serial adaptor used to communicate with
external BMS managed with SNMP protocol
Air side coil protection filters and grills
Rubber or spring anti-vibration supports

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ISCF 06/12

2012 Schneider Electric. All rights reserved.

Range

Fan coil cassette units for underfloor installations

46

UTAT

47

Uniflair UTAT

Cooling capacity: 1 2 kW
Heating capacity: 1 3 kW
Axial Fan

1 SPEED

2 SPEED

3 SPEED

Cooling capacity (1)

UTAT 0030B MODEL


kW

1,74

1,99

2, 45

Sensibile cooling capacity (1)

kW

1,28

1,47

1,92

Airflow

m3/h

221

280

438

Absorbed power (1)

25

32

40

Heating capacity (2)

kW

1,62

1,96

2,70

Noise pressure level (3)

dB(A)

30

38

44

kg

10

10

10

DIMENSIONS
Weight (basic version)

Standard Features

Options

Structure manufactured in thermoformed plastic, with


bearing parts in galvanised steel
2 rows, thermal exchange pack coil with expanded
copper tubing and aluminium fins, collectors with
threaded air outlet connectors. The coil has been tested
at a pressure of 10 bar
Four blade axial fan manufactured in PP 30% GV
stabilised to UV rays, statically and dynamically balanced
on two levels
230V/1/50Hz winding induction motor with constantly
inserted condenser. Class B insulation. Declared to
conform with electromagnetic compatibility (according to
2004/108 /EC, CE92/31, CE93/68 Directives) and low
voltage directives (Section 10, Directive 2006/95/EC),
IP44 protection level. Three rotation speeds.
CE Directive electrical panel (Directives 2006/95/EC and
EMC 2004/108/EC) with unit control card equipped with
incorporated relays
Thermoformed plastic condensation collection tray
Cleanable filter in self-extinguishing material
supplied with galvanised plate hooks
230V/1/50Hz Power supply

Self-priming condense discharge pump with heat


protection and alarm on NC resistive contact
RS485 serial adaptor
Can-bus serial adaptor
Remote user terminal
Incorporate NTC sensor for ambient temperature
adjustment
LCD display with intuitive symbols
Selection of the value to display (temperature, set-point,
offset compared with common set-point)
Selective key block (limited functions for offices,
hotels...)
Signalling of coded alarms and faults
ON-OFF timer functions
Economy-sleep function
Manual or automatic operation

1. Inlet chilled water


temperature: 7C, water
flow; 250 l/h; air ambient
temperature: 27C d.b., 19C
w.b.
2. Inlet hot water temperature:
45C, water flow; 250 l/h; air
ambient temperature: 20C
d.b.
3. Values measured at 1 mt. in
free field conditions from the
unit with Q=2 directionality
factor

Dimensioni

520
490

Electrical Panel

Air-filter around
cold/hot water coil

Inlet water 1/2


F GAS

Electrical
connection

522

230

560
Outlet water 1/2 F GAS

Condensate drainage
pump

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
UTAT 06/12

2012 Schneider Electric. All rights reserved.

Range

Technical Data

Underfloor air distribution module

48

UTCT

49

Uniflair UTCT
Technical Data
MODEL

UTCT 00600

Airflow

m3/h

400-990(modulating)

Operating mode

Max fan absorbed power

60

Max fan absorbed current

Underfloor air distribution


Ambient air recirculation
Heating mode

Electrical heater
Min free space under floor

Airflow: 400 990 m /h


3

Modulating EC fan
Modulating damper
Integrated control board

Speed

Airflow

Lw

Lp

m3/h

dB(A)

dB(A)

400

0,5

430

38

26

500

500

42

30

mm

275

580

47

35

680

54

42

DIMENSIONS AND WEIGHT


Width

mm

598

770

55

43

Depth

mm

780

850

56

44

Height

mm

265

900

57

45

Weight

kg

27

970

60

46

10

990

64

47

AMBIENT TEMPERATURES

Operating mode

Self-supporting structure in galvanized steel


Pod system designed to provide a high level of stability
and to be compatible with Uniflair UNI8 evolution structure
or other equivalent access flooring structures
Installation integrated under a raised floor. The module is
connected to the access floor structure stringers through
the four sides
Dual Electronic Commutated motor centrifugal fan,
manufactured in PP, with anti-vibration motor mounted on
both sides and thermal overload protector (TOP) internally
wired. Product complying with standard EN 60335-1.
Class F insulation. IP44 protection level. 10 rotation
speeds.
Modulating motorized air damper with 10 different
positions (from 0% to 100%)
Electric board complying with EC standards (2006 /95 /
EC and EMC 2004/108/EC directives)
No. 3 air temperature sensors onboard (inlet air from
the room, inlet air from underfloor and discharge air in the
room)
Wall-mounted remote user terminal (*) with NTC sensor
onboard for ambient temperature acquisition
Microprocessor control board for automatic or manual
operation:
- automatic regulation based on ambient temperature (*)
and room set point (defined with the TUL or by the
BMS);
- manual selection of fan regulation (10 speeds)
- manual selection of motorized air damper (10 positions)
230V/1ph/50-60Hz power supply

The unit can operate with 3 different configurations,


according to the position of the modulating damper:
Total cooling / total heating
- Damper completely open on underfloor side: air suction
from underfloor and discharge in the ambient
- Electrical heater (optional) operates in heating mode to
reach rapidly the set-point required until the underfloor
temperature is adequate
Recirculation
- Damper completely closed on underfloor side: air
suction and discharge from and in the ambient
Mixed mode
- Damper partially open on underfloor side: air suction
mixed from the ambient and from underfloor and
discharge in the ambient
The correct configuration that ensures the set-point
required is managed by the microprocessor control
board. This acquires the air temperature from both inlet
and outlet unit air side, by means of onboard temperature
sensors. According to the difference between ambient
temperature (*) and set-point (**), it automatically set the
best configuration (damper position and fan speed) in
order to guarantee the required set-point.

0/45

Storage

-40/+80

2. Data refer to UTCT in


standard configuration

Dimensioni

Grills and floor not


included

Electrical
panel side
Underfloor damper side

598

265

Standard Features

Operating

1. Values measured at 1 mt. in


free field conditions from the
unit with Q=2 directionality
factor

(*) on Master unit only


(**) acquired from remote user terminal (TUL) or from the
unit air inlet temperature probe.
(***) defined by the remote user terminal (TUL) or by the
BMS system

IN
Supply

IN/OUT
pLan user terminal

IN/OUT
BMS

518

151,5

199,5

Options

RS485 serial adaptor


Can-bus serial adaptor
Konnex serial adaptor
Wireless remote user terminal
Signaling of coded alarms and faults (*)
(*) if connected to a BMS system

780

596

The units can be supplied with the following external


accessories:
500W aluminum fins electrical heater with safety
thermostat and automatic restart
Cleanable filter in self-extinguishing material with
galvanized plate edge, suitable for high temperatures

159,5

Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
UTCT 06/12

2012 Schneider Electric. All rights reserved.

Range

FAN


Viale della Tecnica, 2

35026 Conselve (PD) Italy

Telephone: +39 049 5388211

Fax: +39 049 5388212
info@uniflair.com
schneider-electric.com
uniflair.com
Owned and directed by Schneider Electric SA
05RE0003B1A rev.1.0

2012 Schneider Electric. All rights reserved.

Uniflair SpA

Potrebbero piacerti anche