masibus

UT-94

Document Ref No. m98A/om/101

Issue No: 06
CMRR

INTRODUCTION
This is a micro-controller based Universal Transmitter which
retransmits the Universal Inputs given, into the required Voltage
or current.
This instrument provides isolation at 4 levels:
(a)
(b)
(c)
(d)

Between input and Power supply


Between output and Power supply.
Between input and output.
Output to Output.

: > 120 dB

NMRR

: > 50 dB

THERMOCOUPLE
BURN OUT

: (Programmable scaling)

OPERATING SUPPLY

: 85-265 VAC or
18-30 VDC (Optional).

POWER CONSUMPTION: < 10 W


ISOLATION

: Three port isolation I.e. between


input/ output/ power supply.

ISOLATION LEVEL

: 1500 VAC/ 500VDC@2000 Mega


ohms between input, outputs
and power supply

MOUNTING

: DIN Rail

DIMENSION

: 55 (W) x 75 (H) x 110 (D) mm

OPERATING
TEMPERATURE

: 0 to 55 deg C

DISPLAY SCALING:-1999 to 9999

OPERATING RH

: 20% to 90 % RH non-condensing.

DISPLAY RANGE
RTD
Linear
T/C

:
: -199.9 TO 850.0 C
: -1999 to 9999 (selectable)
: as per sensor

Dimensions

KEYS

: 3 Keys (ENT, SEL & ESC)

NO. OF INPUT

: One

I/P TYPES
T/C
RTD
Linear

:: E, J, K, T, B, R, S, N
: Pt100, 3-WIRE
: -10 - 20mV, 0-100mV, 0-2V, 0.4-2V,
0-5V, 0-20mA, 1-5V, 4-20 mA, 0-10 VDC

I/P ACCURACY

: 0.1% of Full Scale.

SPECIFICATIONS
MODEL

: UT-94

TYPE

: Universal Transmitter with Dual


Retransmission Output.

DISPLAY

: 4 digit, 0.3", 7- segment red LED

I/P RESOLUTION : As Per Input table.


RESPONSE TIME : 75 mSec.
LINEARIZATION
METHOD

: Through Software, using 9th order Coefficient.

Front Panel

NO OF OUTPUTS : Two (O/P-2 is Optional).


O/P TYPES

: 4 -20mA, 0 -20mA , 1-5V, 0-5V, 010VDC (Either Voltage or Current from a


channel at a time)

O/P LOAD

: 750 Ohms max (For Current O/Ps)


4000Ohms min (For Voltage O/Ps)

O/P ACCURACY

: 0.25% of Full Scale.

TRANSMITTED
: 24VDC @ 30 mA, with
POWER SUPPLY Short circuit Protection
CALIBRATION

: Through Front panel

COLD JUNCTION
COMPENSATION : By software.
OVER RANGE O/P : 5% above F.S.
(Not applicable for Voltage Inputs)
PROTECTION

: Short ckt. & Open ckt. (At output)

ENTER / SCROLL Key This key is used to start menu,


scroll through the menu and save
values.
SEL / SHIFT Key
This key is used to select the menu
options, for shifting the digit of the
selected parameters and for

Masibus Automation And Instrumentation (P) Ltd. B-30,GIDC Electronics Estate,


Gandhinagar.E Mail: sales@masibus.com
Page 1 of 4

masibus

UT-94

Document Ref No. m98A/om/101


Ambient display in Run Mode for
TC Input.

DP

Decimal Point

UNIT

Engineering Units

OPNO

Output Channel No

OPTY

Output Type

OPLO

* Percentage of the O/P Zero range

OPHI

* Percentage of the O/P Span range

T/C: E, J, K, T, B, R, S, N.
RTD: Pt100 3-WIRE.
Linear: -10 - 20mV, 0-100mV, 0-2V,
0.4-2V, 0-5V, 0-20mA, 1-5V, 4-20, 0-10V.

OPSC

Up/down Scale one sensor open

DIR

Forward/Reverse Output

FILT

Digital Filter

Input Zero Value


Input Span Value
0 - 3
C,F,K

FSET

Factory Setting

PASS

Password

ESC / INC Key

This key is used to revert back to


the parent menu from the sub
menu levels and Increment the
selected digit.

Menu Function List

inTY
INP
Zero
Span
DP
UNIT
OPNO
OPTY
CONF

OPLO
OUT
OPHI
OPSC
DIR
FILT
FSET
ADV PASS
SQRT
TOUT

1, 2
4 20mA, 0 20mA, 1-5V, 0-5V, 0-10VDC
* Percentage of Output
(O/P Low limit will be limited to this
configured 0-25 % of O/P Span)
* Percentage of output
(O/P Hi limit will be limited to this
configured 75-100 % of O/P Span)
UPSC/DNSC
DIR/REV
0 - 60 Sec
Give Default password for factory settings
Change Password
YES/NO
10-300 SEC

Square root

SQRT
TOUT

Time out From the Menu (10 to 300 Sec)

OVER

Input Signal Above Span

UNDR

Input Signal Below Zero

OPEN

Sensor Burned

WAIT

Calibration In Process

CERR

Error in Calibration

SERR

Setting Error

AERR

ADC Error

Ferr

Factory setting Error

Input Ranges
Input

AMB

Range

Resolution

SPAN
ZERO

E TC

-200 to 1000 C

J TC

-200 to 1200 C

# 0.1 C

OPNO
OUT ZERO
SPAN

K TC

-200 to 1370 C

# 0.1 C

T TC

-200 to 400 C

0.1 C

B TC

450 to 1820 C

1 C

INP
CAL

Issue No: 06

1, 2

VER 1 UT1.1

* Output will not be scaled but only limit to this


configured % of output.
Parameter Description

# 0.1 C

R TC

0 to 1750 C

1 C

S TC

0 to 1750 C

1 C

N TC

-200 to 1300 C

# 0.1 C

RTD Pt100

-200 TO 850 C

0.1 C

-10 to 20 mV

-1999 to 9999 Counts

1 Count

0 to 100 mV

-1999 to 9999 Counts

1 Count

CONF

Configuration Mode

0 to 2 V

-1999 to 9999 Counts

1 Count

CALI

Calibration Mode

0.4 to 2 V

-1999 to 9999 Counts

1 Count

INP

Input type Parameter Settings

* 0 to 20 mA

-1999 to 9999 Counts

1 Count

OUT

Output type Parameter Settings

* 4 to 20 mA

-1999 to 9999 Counts

1 Count

ADV

Advance Parameter Settings

0 to 5 V

-1999 to 9999 Counts

1 Count

VER

Software Version

1 to 5 V

-1999 to 9999 Counts

1 Count

AMB

Ambient

0 to 10 V

-1999 to 9999 Counts

1 Count

inTY

Input Type

Zero

Input Zero

Span

Input Span

Note : # Resolution 1C After 999.9 C.


* Connect 100R 0.1% Resistance at I/P.

Masibus Automation And Instrumentation (P) Ltd. B-30,GIDC Electronics Estate,


Gandhinagar.E Mail: sales@masibus.com
Page 2 of 4

masibus

UT-94

Document Ref No. m98A/om/101

Issue No: 06
o

Using Menu

To enter into the menu mode, Press the ENT key. Display will show
PASS and asking for password..
Press SEL key to enter password. Display will show 0000.
Now press SEL key to edit password. Now last digit will start blinking.
Now edit password digit by INC (ESC). In this case pressing SEL
(SHIFT) key will shift the blinking to the next digit.

Press ENT key to give password.


o
If password is correct, then display will be steady instead of
blinking. Press ENT key to enter in menu mode.
o
If password is wrong then unit will directly enter in RUN mode.

Scroll through the menu options using the ENT Key Conf , Cal

and Ver1.

Select the option by pressing the SEL key.

Scroll the sub menu options using ENT key.

Select the particular option by pressing the SEL key.

Use the ESC key to exit from the submenu, back to the parent menu levels.

To change the displayed value, press the SEL key again.

Now according to the option selected,


o
If its a text message the whole display blinks together
o
Else if its a numeric value the first digit starts blink. In this case
pressing SEL (SHIFT) key will shift the blinking to the next digit.
Change the display settings using INC (ESC) key and SHIFT (SEL) key.
Press the ENT key to save the setting.
Press the ESC key and you will be in the parent menu option.

Configuration Menu

Calibration Menu

Input Selection

Input Type Selection

Input Zero Setting

Input Span Setting
 Decimal Point Setting (Only for Linear Inputs)

Engineering Unit Setting (C, F or K, only for TC
and RTD inputs)
Output Selection

Output Channel Selection for doing Setting (1 or 2)

Output Type Selection (0 20 mA, 4-20 mA, 0-5 V,
1-5 V, 0 10 V)

Output Low Setting (Minimum 0.0 25.0 %)

Output High Setting (Maximum 75.0 - 100.0 %)

Output Upscale / Downscale Setting for OPEN input

Output direction Setting (Direct / Reverse)
Advance Options

Digital filtering (Range: 0 to 60.0 second)

Factory Setting- To retrieve the factory setting.

Password Setting

Square Root (No / YES, for Linear inputs only)

For Square Root, Output will be come as per
PV =
SQRT[ { (input reading config. IP Zero) / (config.
IP Span Config. IP Zero) } * Config. OP Span ]
+ Config. OP Zero

Time Setting for Come back to RUN mode on no key
operation (Range: 10 to 300 second)

Ambient Calibration (For TC only)


Input Calibration
o
Input Zero Calibration (For RTD only)
o
Input Span Calibration
Output Calibration
o
Output Channel Selection for calibration
o
Output Zero Calibration
o Output Span Calibration

Software Version

Version Number of the Software

Calibration Procedure
Calibration for the unit is to be carried out by an experienced
engineer only. Reference used for the calibration should be of
high accuracy (0.1% better) and good stability.
After Giving correct Password Press the Enter Key to enter into
the menu levels (Scroll along using the Enter Key itself. From it
select CAL using the SELECT Key).Here we have 3 options
Amb, INP, and OUT. Scroll along using the Enter Key and
select the required option using the SELECT Key.
Ambient Calibration:
Once you enter the ambient calibration option the ambient
temperature sensed by the device is shown. Now to calibrate it
press the Select Key that blinks the digits one by one on each
press, use the Increment Key to change the value from 0-9.
Adjust the values as required and press the Enter Key to save
the value.
Exit from the menu levels using the Inc/Esc Key. Now we
have both Input and output calibration.
Input Calibration:
Here calibration is done only after entering span value(For
RTD Zero & Span value sequentially). For this we require a
source with good stability and resolution.
Any of the inputs can be calibrated at any point within the
entered range. The Inputs are divided into Six groups.
Calibrating any of the inputs of a group will calibrate all the
other inputs of the same group.
The groups are:
Group0: ETC, JTC, KTC, TTC, NTC, and 0-100mV.
Group1: BTC, RTC, STC, -10 - 20mV.
Group2: RTD.
Group3: 0-5V, 1-5V.
Group4: 0-2V, 0.4-2V,0-20mA, 4-20mA.
Group5: 0-10V.
Now select the INP from the menu feed the Zero input
value for zero calibration (For RTD only) and enter the Zero
calibration option using the Select Key. Now change the values
as required using the select and Inc Key. Save the value using
the Enter Key and Exit one level back using the Inc/Esc Key.
Scroll to the Span calibration using the Enter key, Press
Select Key to enter into the span calibration. Feed the span
input for calibration and change the values as required and
press Enter to perform calibration, Here it show a Wait
Message until it completes the calibration Procedure. It
automatically saves and applies the calibration parameters
now. Exit the menu level using the Inc/Esc Key. (There is no
need for repetition of calibration except RTD inputs)
Output Calibration
Here calibration is done only after entering both the zero
and span values sequentially for separate channels. For this we
require a DMM of 6 1/2 Digit or more resolution. No input is
required while calibration.
Here calibration has to be done in both current and
voltage of both channels separately. Here in the menu we first
select the channel we are calibrating, monitor the output of that
corresponding channel using the DMM(Digital Multi meter).
Here both channels have separate voltage and current
terminals. Enter the zero option and correct the value you see
on the display with the value you see in the DMM. Do the same
for the Span also. Now select channel 2 and monitor the output

Masibus Automation And Instrumentation (P) Ltd. B-30,GIDC Electronics Estate,


Gandhinagar.E Mail: sales@masibus.com
Page 3 of 4

masibus

UT-94

Document Ref No. m98A/om/101


of second channel and repeat what we did with the first channel
output.

Issue No: 06

Its recommended to calibrate 0-20mA for current


and 0-10V for voltage output.

WIRING DETAIL

TERMINAL POSITION DETAIL

Note: 18-30 VDC is Optional Supply.

Masibus Automation And Instrumentation (P) Ltd. B-30,GIDC Electronics Estate,


Gandhinagar.E Mail: sales@masibus.com
Page 4 of 4