Sei sulla pagina 1di 166

APM30H&TMC11H&IBBS200D&IBBS200T

(Ver.D1&Ver.D2)
V300R003C00

product description
Issue

Draft A

Date

2012-9-15

HUAWEI TECHNOLOGIES CO., LTD.

Copyright Huawei Technologies Co., Ltd. 2012. All rights reserved.


No part of this document may be reproduced or transmitted in any form or by any means without prior written
consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions


and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and the
customer. All or part of the products, services and features described in this document may not be within the
purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information,
and recommendations in this document are provided "AS IS" without warranties, guarantees or representations
of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address:

Huawei Industrial Base


Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website:

http://www.huawei.com

Email:

support@huawei.com

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

About This Document

About This Document


Overview
This document presents the exteriors and describes the functions, technical specifications,
application scenarios, structure, components, and cable connections of the APM30H (Ver.D1),
APM30H (Ver.D2), TMC11H (Ver.D1), TMC11H (Ver.D2), IBBS200D (Ver.D), and
IBBS200T (Ver.D). It also describes the configurations, functions, and specifications of the
modules and boards, and details such as cable types, cable connections, and connector
specifications.
l

APM30H is short for advanced power module with heat exchanger.

TMC11H is short for transmission cabinet of 11 U high with heat exchanger.

IBBS200D is short for integrated battery backup system with direct cooling.

IBBS200T is short for integrated battery backup system with thermal electric cooling.

Product Version
Product Name

Product Version

APM30H Ver.D1 (APM30H for short)

V300R003C00

APM30H Ver.D2 (APM30H for short)


TMC11H Ver.D1 (TMC11H for short)
TMC11H Ver.D2 (TMC11H for short)
IBBS200D Ver.D (IBBS200D for short)
IBBS200T Ver.D (IBBS200T for short)

Intended Audience
l

Base station installation personnel

System engineers

Site maintenance personnel

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

ii

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Contents

Contents
About This Document.....................................................................................................................ii
1 Change History..............................................................................................................................1
2 APM30H Product Description....................................................................................................2
2.1 APM30H Description.........................................................................................................................................3
2.2 Technical Specifications of an APM30H (Ver.D1)............................................................................................6
2.3 Technical Specifications of an APM30H (Ver.D2)..........................................................................................11
2.4 Application Scenario of an APM30H...............................................................................................................15
2.5 APM30H Structure...........................................................................................................................................18
2.6 Components in an APM30H.............................................................................................................................23
2.6.1 AC/DC Power System.............................................................................................................................23
2.6.2 Fan Assembly..........................................................................................................................................37
2.6.3 ELU.........................................................................................................................................................37
2.6.4 Door Status Sensor..................................................................................................................................38
2.6.5 Filler Module...........................................................................................................................................39
2.6.6 (Optional) AC Heater..............................................................................................................................40
2.6.7 (Optional) SOU........................................................................................................................................40
2.7 APM30H Cables...............................................................................................................................................42
2.7.1 Cable List.................................................................................................................................................42
2.7.2 APM30H Cable Connections..................................................................................................................44
2.7.3 PGND Cable............................................................................................................................................47
2.7.4 Equipotential Cable.................................................................................................................................48
2.7.5 Power Cables...........................................................................................................................................49
2.7.6 Signal Cables...........................................................................................................................................55

3 TMC11H Product Description..................................................................................................60


3.1 TMC11H Description.......................................................................................................................................61
3.2 Technical Specifications of a TMC11H...........................................................................................................62
3.3 Application Scenarios of a TMC11H...............................................................................................................65
3.4 TMC11H Structure...........................................................................................................................................67
3.5 TMC11H Components.....................................................................................................................................72
3.5.1 DCDU-12B..............................................................................................................................................72
3.5.2 DCDU-12C..............................................................................................................................................77
3.5.3 Fan Assembly..........................................................................................................................................80
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

iii

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Contents

3.5.4 Filler Module...........................................................................................................................................80


3.5.5 Junction Box............................................................................................................................................81
3.5.6 ELU.........................................................................................................................................................83
3.5.7 Door Status Sensor..................................................................................................................................83
3.5.8 (Optional) AC Heater..............................................................................................................................84
3.5.9 (Optional) SOU........................................................................................................................................85
3.6 TMC11H Cables ..............................................................................................................................................86
3.6.1 Cable List.................................................................................................................................................86
3.6.2 TMC11H Cable Connections..................................................................................................................88
3.6.3 PGND Cable............................................................................................................................................90
3.6.4 Equipotential Cable.................................................................................................................................90
3.6.5 Power Cables...........................................................................................................................................91
3.6.6 Signal Cables...........................................................................................................................................98

4 IBBS200D Product Description...............................................................................................102


4.1 IBBS200D Description...................................................................................................................................103
4.2 Technical Specifications of an IBBS200D.....................................................................................................104
4.3 IBBS200D Structure.......................................................................................................................................106
4.4 IBBS200D Components.................................................................................................................................108
4.4.1 Fan Mounting Frame.............................................................................................................................108
4.4.2 Central Monitoring Unit Type EA (CMUEA)......................................................................................109
4.4.3 Power Distribution Box.........................................................................................................................113
4.4.4 Storage Battery......................................................................................................................................115
4.4.5 ELU.......................................................................................................................................................116
4.4.6 Heating Film..........................................................................................................................................117
4.4.7 Door Status Sensor................................................................................................................................118
4.4.8 Battery Temperature Sensor..................................................................................................................119
4.5 IBBS200D Cables...........................................................................................................................................121
4.5.1 Cable List...............................................................................................................................................121
4.5.2 IBBS200D Cable Connections..............................................................................................................122
4.5.3 PGND Cable..........................................................................................................................................124
4.5.4 Equipotential Cable...............................................................................................................................125
4.5.5 Power Cables.........................................................................................................................................125
4.5.6 Signal Cables.........................................................................................................................................129

5 IBBS200T Product Description...............................................................................................133


5.1 IBBS200T Description...................................................................................................................................134
5.2 Technical Specifications of an IBBS200T.....................................................................................................135
5.3 IBBS200T Structure.......................................................................................................................................137
5.4 IBBS200T Components..................................................................................................................................138
5.4.1 TEC........................................................................................................................................................139
5.4.2 Power Distribution Box.........................................................................................................................140
5.4.3 Central Monitoring Unit Type EA (CMUEA)......................................................................................141
5.4.4 Storage Battery......................................................................................................................................145
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

iv

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Contents

5.4.5 ELU.......................................................................................................................................................146
5.4.6 Door Status Sensor................................................................................................................................147
5.4.7 Battery Temperature Sensor..................................................................................................................148
5.5 IBBS200T Cables...........................................................................................................................................150
5.5.1 Cable List...............................................................................................................................................150
5.5.2 IBBS200T Cable Connections...............................................................................................................152
5.5.3 PGND Cable..........................................................................................................................................153
5.5.4 Equipotential Cable...............................................................................................................................154
5.5.5 Power Cables.........................................................................................................................................154
5.5.6 Signal Cables.........................................................................................................................................157

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

1 Change History

Change History

This chapter describes the changes in the APM30H&TMC11H&IBBS200D&IBBS200T


(Ver.D1&Ver.D2) Product Description.

Draft A (2012-09-15)
This is a draft.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

APM30H Product Description

About This Chapter


This chapter describes the exterior, functions, technical specifications, application scenarios,
structure, components, and cables of the APM30H.
2.1 APM30H Description
An advanced power module with a heat-exchanger (APM30H) is a power cabinet used for
Huawei wireless products outdoors. The APM30H supplies DC power to a distributed base
station or separated macro base station in outdoor scenarios and provides space for the BBU and
transmission equipment. The APM30H has a small size and therefore can be easily relocated.
2.2 Technical Specifications of an APM30H (Ver.D1)
The technical specifications of an APM30H (Ver.D1) consist of electrical specifications,
engineering specifications, surge protection specifications, and environmental specifications.
2.3 Technical Specifications of an APM30H (Ver.D2)
The technical specifications of an APM30H (Ver.D2) consist of electrical specifications,
engineering specifications, surge protection specifications, and environmental specifications.
2.4 Application Scenario of an APM30H
An APM30H can apply to a distributed base station or a separated macro base station.
2.5 APM30H Structure
The APM30H uses a modular and integrated structure, which improves its operability and
maintainability.
2.6 Components in an APM30H
An APM30H consists of the AC/DC power system, fan assembly, electronic label unit (ELU),
door status sensor, filler module, optional AC heater, and service outlet unit (SOU).
2.7 APM30H Cables
This chapter describes the PGND cables, equipotential cables, power cables, and signal cables
in an APM30H.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

2.1 APM30H Description


An advanced power module with a heat-exchanger (APM30H) is a power cabinet used for
Huawei wireless products outdoors. The APM30H supplies DC power to a distributed base
station or separated macro base station in outdoor scenarios and provides space for the BBU and
transmission equipment. The APM30H has a small size and therefore can be easily relocated.

Exterior of an APM30H
The dimensions (H x W x D) of the APM30H are 700 mm x 600 mm x 480 mm (27.56 in. x
23.62 in. x 18.90 in.) (not including the base).
Figure 2-1 shows the exterior of an APM30H.
Figure 2-1 Exterior of an APM30H

Functions of an APM30H
Table 2-1 describes the functions of an APM30H.
Table 2-1 Functions of an APM30H
Item

Description

Providing space for the


customer equipment

After an AC/DC power subrack is installed, the space for customer


equipment is as follows:
l If one BBU is configured, a space (H x W x D) of 5 U x 482.6
mm. x 380 mm (5 U x 19 in. x 14.96 in.) is reserved.
l If another BBU is installed in the APM30H (Ver.D2), a space
(H x W x D) of 3 U x 482.6 mm. x 380 mm (3 U x 19 in. x 14.96
in.) is reserved.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Item

Description

Connecting to an
external battery
cabinet

An external battery cabinet supports battery groups with power up


to 48 V 184 Ah. Two stacked battery cabinets support battery groups
with power up to 48 V 368 Ah.

Built-in PSUs

l The PSUs convert AC mains into -48 V DC power.


l The PSUs are hot-swappable.
l The PMU manages the PSUs as well as the charging and
discharging of batteries.

Built-in PMU

l The PMU provides RS485 communication ports and dry contact


alarm ports, achieving remote monitoring and unattended
operation.
l The PMU provides the battery low voltage disconnect (BLVD)
and load low voltage disconnect (LLVD) functions.
l The PMU is hot-swappable.
Supplying power

The embedded AC/DC power system supports 220 V AC singlephase, 220 V AC three-phase, and 110 V/120 V AC dual-live-wire
power inputs.

Distributing AC power

After going through the EPU, one AC power input is divided into
two AC power outputs:
l One output provides AC power for the service outlet unit (SOU).
l One is connected to the junction box on the left side of the
cabinet and divided into four AC power outputs, which are then
provided for the heater or heating film.

Distributing DC power

For details, see Table 2-2.

Surge protection for


power supply ports and
signal ports

Surge protection circuits are provided for alarm ports,


communication ports, and external surge protection modules at the
AC or DC power supply ports to ensure reliable surge protection
and inductive lightning protection.

Dissipating heat

The heat dissipation of the APM30H is performed by a heat


exchanger core as well as the inner and outer air circulation fans,
which can also avoid the invasion of dust.

Grounding mode

The general ground cable for the cabinet and the ground cables for
devices in the cabinet are all connected to the ground bar in the
cabinet.

Reporting the cabinet


type automatically

The electronic label unit (ELU) reports the cabinet type


automatically.

Table 2-2 lists the DC power distribution functions of an APM30H.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Table 2-2 DC power distribution functions of an APM30H

Applic
ation
Distrib
uted
base
station

Separat
ed
macro
base
station

Issue Draft A (2012-9-15)

Protecto
r

Powered
Device

Silkscree
n on the
Output
Terminal

Protecto
r
Specific
ation

Protecto
r
Quantit
y

DC
Output
Ports

Seven
power
output
s to
which
LLVD
is
applie
d

RFC

RFC1

Breaker

125 A

OT
terminal
(M6)

RRU

RRU0 to
RRU5

Fuse

30 A

EPC4,
EPC5, or
EPC6

Nine
power
output
s to
which
BLV
D is
applie
d

BBU

LOAD0
and
LOAD1

Fan
assembly

LOAD2

TM_0

LOAD3

TM_1

LOAD4

TM_2 or
EMUA

LOAD5

TM_3 or
BBU

LOAD6

TMC

LOAD7

IBBS

LOAD8

Batter
y
backu
p
power

BAT

BAT

Breaker

250 A

OT
terminal
(M8)

Two
power
output
s to
which
LLVD
is
applie
d

RFC

RFC 1 and
RFC 2

Breaker

125 A

OT
terminal
(M6)

DC
Outp
ut

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Applic
ation

DC
Outp
ut
Nine
power
output
s to
which
BLV
D is
applie
d

Batter
y
backu
p
power

2 APM30H Product Description

Silkscree
n on the
Output
Terminal

Protecto
r

Protecto
r
Specific
ation

Protecto
r
Quantit
y

DC
Output
Ports

BBU

LOAD0
and
LOAD1

Fuse

30 A

EPC4 or
EPC6

Fan
assembly

LOAD2

TM_0

LOAD3

TM_1

LOAD4

TM_2 or
EMUA

LOAD5

TM_3 or
BBU

LOAD6

TMC

LOAD7

IBBS

LOAD8

BAT

BAT

Powered
Device

Breaker

250 A

OT
terminal
(M8)

2.2 Technical Specifications of an APM30H (Ver.D1)


The technical specifications of an APM30H (Ver.D1) consist of electrical specifications,
engineering specifications, surge protection specifications, and environmental specifications.

Electrical Specifications of an APM30H (Ver.D1)


Table 2-3 lists the electrical specifications of an APM30H (Ver.D1).
Table 2-3 Electrical specifications of an APM30H (Ver.D1)
Item
Char
acter
istics
of
AC
input

Issue Draft A (2012-9-15)

Specifications
Typical
input
voltage

200 V AC to 240 V AC (220 V AC single-phase)


200/346 V AC to 240/415 V AC (220/380 V AC three-phase)
100/200 V AC to 120/240 V AC (110 V AC dual-live-wire)
120/208 V AC to 127/220 V AC (120 V AC dual-live-wire)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Item

2 APM30H Product Description

Specifications
Operating
voltage
range

176 V AC to 290 V AC (220 V AC single-phase)


176/304 V AC to 290/500 V AC (220/380 V AC three-phase)
90/180 V AC to 135/270 V AC (110 V AC dual-live-wire)
105/176 V AC to 150/260 V AC (120 V AC dual-live-wire)

Input
voltage
frequency

45 Hz to 65 Hz

Rated
input
current

53 A (220 V AC single-phase)
23 A (220/380 V AC three-phase)
55 A (110 V AC dual-live-wire)
52 A (120 V AC dual-live-wire)
l 220/380 V AC three-phase voltage

Input
mode

l 110 V AC dual-live-wire
l 120 V AC dual-live-wire
l 220 V AC single-phase voltage

Char
acter
istics
of
DC
outp
ut

Output
voltage
range

-43.2 V DC to -57 V DC

Output
current
range

0 A to 150 A

Typical
output
voltage

-53.5 V DC

DC
outputs

The number of DC outputs depends on the application scenario.


l A distributed base station uses 17 DC outputs
l A separated base station uses 12 DC outputs.

Prote
ction

DC
output
power

9000 W (When there is no backup PSU, the maximum power of each


PSU is 3000 W.)

Input
protectio
n

l Overvoltage protection: The system generates an alarm when the


input voltage exceeds the AC overvoltage alarm threshold (301 V by
default).
l Undervoltage protection: The system generates an alarm when the
input voltage is lower than the AC undervoltage alarm threshold (74
V by default).

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Item

2 APM30H Product Description

Specifications
Output
protectio
n

l Overvoltage protection: The system generates an alarm when the


busbar voltage exceeds the DC overvoltage alarm threshold (-59.5 V
by default).
l No undervoltage protection
l Overcurrent protection and short-circuit protection

Heat
consumption of
the cabinet

1050 W (in the ambient temperature lower than 50oC or 122oF)


(including the BBU, power system, and transmission)

Engineering Specifications of an APM30H (Ver.D1)


Table 2-4 describes the engineering specifications of an APM30H (Ver.D1).
Table 2-4 Engineering specifications of an APM30H (Ver.D1)
Item

Specifications

Remarks

Cabinet weight

68 kg (149.9 lb)

Total weight of the equipment


l Including the cabinet, inner air circulation
fan, outer air circulation fan, core of the heat
exchanger, EPU power subrack, and cables
l Excluding the BBU, customer transmission
equipment, PMU, and PSUs

87 kg (191.80 lb)

Weight with full configuration


l Including the total weight of the equipment,
one PMU, five PSUs, and one BBU
l Excluding the customer transmission
equipment

Dimensions of
the cabinet (H x
W x D)

700 mm 600 mm
480 mm (27.56 in. x
23.62 in. x 18.90 in.)

Not including the base

Dimensions of
the base (H x W
x D)

200 mm600 mm434


mm (7.87 in. x 23.62 in.
x 17.09 in.)

Space for the


customer
equipment (H x
W x D)

Configured with one


BBU: 5 U x 482.6 mm
x 380 mm (11 U x 19 in.
x 14.96 in.)

The depth includes the mounting ears of the


subrack of 280 mm (11.02 in.) away from the
back and 100 mm (3.94 in.) away from the
front.

Configured with two


BBUs: 3 U x 482.6 mm
x 380 mm (3 U x 19 in.
x 14.96 in.)

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Item

Specifications

Remarks

Cabling and
maintenance
space at the front

70 mm (2.76 in.)

Installation
mode

The APM30H
(Ver.D1) can be
installed on the ground,
pole, or wall. It can also
be stacked on the RFC,
IBBS200D, or
IBBS200T.

In stack mode, the APM30H must be installed


on the RFC, IBBS200D, or IBBS200T.

Surge Protection Specifications of an APM30H (Ver.D1)


Table 2-5 describes the surge protection specifications of an APM30H (Ver.D1).
Table 2-5 Surge protection specifications of an APM30H (Ver.D1)
Item

Specifications

Surge protection for AC


input ports

In differential mode:
l Rated through-current capacity (8/20 us): 30 kA
l Maximum through-current capacity (8/20 us): 60 kA
In common mode:
l Rated through-current capacity (8/20 us): 30 kA
l Maximum through-current capacity (8/20 us): 60 kA

Surge protection for DC


output ports

l In differential mode (8/20 us): 10 kA


l In common mode (8/20 us): 20 kA
The DC output port corresponds to the secondary load.
NOTE
The surge protection capacity of the shield layer in an RRU power cable
is 40 kA.

Surge protection for signal


ports

E1/T1 ports:
l In differential mode (8/20 us): 3 kA
l In common mode (8/20 us): 5 kA
FE ports:
l In differential mode (8/20 us): 3 kA
l In common mode (8/20 us): 5 kA

Environmental Specifications of an APM30H (Ver.D1)


The APM30H (Ver.D1) can be used outdoors. Table 2-6 describes the environmental
specifications of an APM30H (Ver.D1).
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Table 2-6 Environmental specifications of an APM30H (Ver.D1)


Item

Specifications

Remarks

Operating
temperatur
e

-40oC to + 50oC (-40oF to +122oF)

A heater is required when the


temperature is lower than -20oC
(-4oF). A sun shield is required when
the temperature is higher than 50oC
(122oF).
NOTE
A heater is required if the local average
lowest temperature of each day in the
coldest month of the year is lower than the
specified operating temperature for
configuring a heater.

Relative
humidity

5% RH to 100% RH

Altitude

-60 m to 4000 m (-196.85 ft to


13123.36 ft)

From the altitude of 1800 m (5905.51


ft), the maximum operating
temperature drops by 1oC (33.8oF)
each time the altitude increases by 220
m (721.78 ft).

Wind
speed

67 m/s

Storage
temperatur
e

-40oC to + 70oC (-40oF to +158oF)

Dustproof
and
waterproof

IP55

Noise

When the heat consumption of the


cabinet is equal to or less than 700 W,
the noise is equal to or less than 61
dBA and 67 dBA in the temperature
of 25oC (77oF) and the temperature of
45oC (113oF), respectively.

Meeting the ETS 300 753 4.1E


standard (rural level)

When the heat consumption of the


cabinet is equal to 1050 W or between
700 W and 1050 W, the noise is equal
to or less than 66 dBA and 76 dBA in
the temperature of 25oC (77oF) and
the temperature of 45oC (113oF),
respectively.

Meeting the ETS 300 753 4.1E


standard (urban level)

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

10

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

2.3 Technical Specifications of an APM30H (Ver.D2)


The technical specifications of an APM30H (Ver.D2) consist of electrical specifications,
engineering specifications, surge protection specifications, and environmental specifications.

Electrical Specifications of an APM30H (Ver.D2)


Table 2-7 describes the electrical specifications of an APM30H (Ver.D2).
Table 2-7 Electrical specifications of an APM30H (Ver.D2)
Item
Char
acter
istics
of
AC
input

Specifications
Typical
input
voltage

200 V AC to 240 V AC (220 V AC single-phase)


200/346 V AC to 240/415 V AC (220/380 V AC three-phase)
100/200 V AC to 120/240 V AC (110 V AC dual-live-wire)
120/208 V AC to 127/220 V AC (120 V AC dual-live-wire)

Operating
voltage
range

176 V AC to 290 V AC (220 V AC single-phase)


176/304 V AC to 290/500 V AC (220/380 V AC three-phase)
90/180 V AC to 135/270 V AC (110 V AC dual-live-wire)
105/176 V AC to 150/260 V AC (120 V AC dual-live-wire)

Input
voltage
frequency

45 Hz to 65 Hz

Rated
input
current

80 A (220 AC single-phase)
32 A (220/380 V AC three-phase)
80 A (110 V AC dual-live-wire)
80 A (120 V AC dual-live-wire)
l 220/380 V AC three-phase voltage

Input
mode

l 110 V AC dual-live-wire
l 120 V AC dual-live-wire
l 220 V AC single-phase voltage

Char
acter
istics
of
DC
outp
ut

Issue Draft A (2012-9-15)

Output
voltage
range

-57 V DC to -43.2 V DC

Output
current
range

0 A to 250 A

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

11

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Item

2 APM30H Product Description

Specifications
Typical
output
voltage

-53.5 V DC

DC
outputs

The number of DC outputs depends on the application scenario.


l A distributed base station uses 17 DC outputs
l A separated base station uses 12 DC outputs.

Prote
ction

DC
output
power

15000 W (When there is no backup PSU, the maximum power of each


PSU is 3000 W.)

Input
protectio
n

l Overvoltage protection: The system generates an alarm when the


input voltage exceeds the AC overvoltage alarm threshold (301 V by
default).
l Undervoltage protection: The system generates an alarm when the
input voltage is lower than the AC undervoltage alarm threshold (74
V by default).

Output
protectio
n

l Overvoltage protection: The system generates an alarm when the


busbar voltage exceeds the DC overvoltage alarm threshold (-59.5 V
by default).
l No undervoltage protection
l Overcurrent protection and short-circuit protection

Heat
consumption of
the cabinet

1500 W (in the ambient temperature lower than 50oC or 122oF)


(including the BBU, power system, and transmission)

Engineering Specifications of an APM30H (Ver.D2)


Table 2-8 describes the engineering specifications of an APM30H (Ver.D2).
Table 2-8 Engineering specifications of an APM30H (Ver.D2)
Item

Specifications

Remarks

Cabinet weight

68 kg (149.91 lb)

Total weight of the equipment


l Including the cabinet, inner air circulation
fan, outer air circulation fan, core of the heat
exchanger, EPU power subrack, and cables
l Excluding the BBU, customer transmission
equipment, PMU, and PSUs

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

12

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Item

2 APM30H Product Description

Specifications

Remarks

87 kg (191.80 lb)

Weight with full configuration


l Including the total weight of the equipment,
one PMU, five PSUs, and one BBU
l Excluding the customer transmission
equipment

Dimensions of
the cabinet (H x
W x D)

700 mm x 600 mm x
480 mm (27.56 in. x
23.62 in. x 18.90 in.)

Not including the base

Dimensions of
the base (H x W
x D)

200 mm x 600 mm x
434 mm (7.87 in. x
23.62 in. x 17.09 in.)

Space for the


customer
equipment (H x
W x D)

Configured with one


BBU: 5 U x 482.6 mm
x 380 mm (5 U x 19 in.
x 14.96 in.)

The depth includes the mounting ears of the


subrack of 280 mm (11.02 in.) away from the
back and 100 mm (3.94 in.) away from the
front.

Configured with two


BBUs: 3 U x 482.6 mm
x 380 mm (3 U x 19 in.
x 14.96 in.)
Cabling and
maintenance
space at the front

70 mm (2.76 in.)

Installation
mode

The APM30H
(Ver.D2) can be
installed on the ground,
pole, or wall. It can also
be stacked on the RFC,
IBBS200D, or
IBBS200T.

In stack mode, the APM30H must be installed


on the RFC, IBBS200D, or IBBS200T.

Surge Protection Specifications of an APM30H (Ver.D2)


Table 2-9 describes the surge protection specifications of an APM30H (Ver.D2).
Table 2-9 Surge protection specifications of an APM30H (Ver.D2)
Item

Specifications

Surge protection for AC


input ports

In differential mode:
l Rated through-current capacity (8/20 us): 30 kA
l Maximum through-current capacity (8/20 us): 60 kA

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

13

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Item

2 APM30H Product Description

Specifications
In common mode:
l Rated through-current capacity (8/20 us): 30 kA
l Maximum through-current capacity (8/20 us): 60 kA

Surge protection for DC


output ports

l In differential mode (8/20 us): 10 kA


l In common mode (8/20 us): 20 kA
The DC output port corresponds to the secondary load.
NOTE
The surge protection capacity of the shield layer in an RRU power cable
is 40 kA.

Surge protection for signal


ports

E1/T1 ports:
l In differential mode (8/20 us): 3 kA
l In common mode (8/20 us): 5 kA
FE ports:
l In differential mode (8/20 us): 3 kA
l In common mode (8/20 us): 5 kA

Environmental Specifications of an APM30H (Ver.D2)


The IBBS200T can be used outdoors. Table 2-10 describes the environmental specifications of
an APM30H (Ver.D2).
Table 2-10 Environmental specifications of an APM30H (Ver.D2)
Item

Specifications

Remarks

Operating
temperatur
e

-40oC to + 50oC (-40oF to +122oF)

A heater is required when the


temperature is lower than -20oC
(-4oF). A sun shield is required when
the temperature is higher than 50oC
(122oF).
NOTE
A heater is required if the local average
lowest temperature of each day in the
coldest month of the year is lower than the
specified operating temperature for
configuring a heater.

Relative
humidity

5% RH to 100% RH

Altitude

-60 m to 4000 m (-196.85 ft to


13123.36 ft)

From the altitude of 1800 m (5905.51


ft), the maximum operating
temperature drops by 1oC (33.8oF)
each time the altitude increases by 220
m (721.78 ft).

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

14

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Item

Specifications

Remarks

Wind
speed

67 m/s

Storage
temperatur
e

-40oC to + 70oC (-40oF to +158oF)

Dustproof
and
waterproof

IP55

Noise

When the heat consumption of the


cabinet is equal to or less than 700 W,
the noise is equal to or less than 61
dBA and 67 dBA in the temperature
of 25oC (77oF) and the temperature of
45oC (113oF), respectively.

Meeting the ETS 300 753 4.1E


standard (rural level)

When the heat consumption of the


cabinet is equal to 1500 W or between
700 W and 1500 W, the noise is equal
to or less than 66 dBA and 76 dBA in
the temperature of 25oC (77oF) and
the temperature of 45oC (113oF),
respectively.

Meeting the ETS 300 753 4.1E


standard (urban level)

2.4 Application Scenario of an APM30H


An APM30H can apply to a distributed base station or a separated macro base station.

APM30H Used in a Distributed Base Station


In a distributed base station, an APM30H is configured as follows:
l

The APM30H provides 5 U space for transmission equipment and uses an embedded power
system to feed -48 V DC power into the distributed base station, transmission equipment,
and battery groups in the battery cabinet.

When the mains are unavailable, battery groups feed -48 V DC power into the distributed
base station and transmission equipment.

Figure 2-2 shows the distributed base station where an APM30H is stacked on a battery cabinet.
NOTE

When an APM30H is configured in the distributed base station, an IBBS200D or IBBS200T can be
configured. Figure 2-2 shows the distributed base station configured with an IBBS200D.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

15

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-2 APM30H stacked on a battery cabinet in a distributed base station

APM30H Used in a Separated Macro Base Station


In a separated macro base station, an APM30H is configured as follows:
l

The APM30H provides 5 U space for transmission equipment and uses an embedded power
system to feed -48 V DC power into the BBU, RFU, transmission equipment, and battery
groups in the battery cabinet.

When the mains are unavailable, battery groups feed -48 V DC power into the BBU, RFU,
and transmission equipment.

The APM30H provides the function of reporting alarms from the fans of the RFC, door
status sensor, DCDU, and battery cabinet.

Figure 2-3 and Figure 2-4 show the separated macro base station where an APM30H is
configured.
NOTE

When an APM30H is configured in the separated macro base station, an IBBS200D or IBBS200T can be
configured. Figure 2-3 and Figure 2-4 show the separated macro base station configured with an
IBBS200D.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

16

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-3 APM30H (Ver.D1) used in a separated macro base station

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

17

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-4 APM30H (Ver.D2) in a separated macro base station

2.5 APM30H Structure


The APM30H uses a modular and integrated structure, which improves its operability and
maintainability.

Cabinet Structure
Figure 2-5 and Figure 2-6 show the APM30H (Ver.D1) and APM30H (Ver.D2), respectively.
Figure 2-5 and Figure 2-6 shows the separated macro base station with an APM30H configured.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

18

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-5 APM30H (Ver.D1)

Figure 2-6 APM30H (Ver.D2)

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

19

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

N
o.

Module

Op
tio
nal
/
Ma
nd
ato
ry

Ma
xim
um
Qu
anti
ty
Co
nfi
gur
ed
in a
Sin
gle
Cab
inet

Remarks

Outer air
circulation
assembly

Ma
nda
tor
y

The assembly is installed on the front door, providing inner


and outer air circulation and dissipating heat from the
cabinet.

Junction
Box

Ma
nda
tor
y

The junction box converts one AC input into four AC


outputs and is used in the scenario where a service outlet
unit (SOU) and multiple heating films or heaters are
configured.

Fan
assembly

Ma
nda
tor
y

The fan assembly is configured with fans and central


monitoring unit type EA (CMUEA), dissipating heat from
the cabinet

SLPU

Ma
nda
tor
y

l To provide protection for trunk signals, a signal


lightning protection unit (SLPU) is mandatory and
installed in the top 1 U space of the cabinet. It is
configured with the universal E1/T1 lightning
protection unit (UELP) or universal FE lightning
protection unit (UFLP).
l To provide protection for monitoring signals, an SLPU
is optional and installed in the 1 U space below the
BBU. It is configured with two universal signal
lightning protection unit 2 (USLP2) boards.

Door status
sensor

Ma
nda
tor
y

The door status sensor monitors whether the cabinet door


is open.

ELU

Ma
nda
tor
y

The ELU reports the cabinet type automatically to


facilitate troubleshooting.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

20

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

N
o.

Module

Op
tio
nal
/
Ma
nd
ato
ry

Ma
xim
um
Qu
anti
ty
Co
nfi
gur
ed
in a
Sin
gle
Cab
inet

Remarks

EPU

Ma
nda
tor
y

The EPU converts AC power to DC power and feeds the


DC power into the devices in the cabinet. The EPU consists
of the EPU subrack, PMU, and PSUs.

BBU3900

Opt
ion
al

A maximum of one BBU3900 can be configured in an


APM30H (Ver.D1) and two in an APM30H (Ver.D2).
l The BBU3900 provides physical ports for
communication between the BBU3900 and the BSC or
RNC, and enables interaction between the base station
and the BSC or RNC.
l The BBU3900 provides CPRI ports for communication
between the BBU3900 and RFUs.
l The BBU3900 processes uplink and downlink data.

Environme
nt
monitoring
unit type A
(EMUA)

Opt
ion
al

The EMUA monitors the equipment environment.

10

Filler
Module

Ma
nda
tor
y

A filler module is a 1-U high plastic component, which


prevents the heat reflux in the empty space below the BBU.

11

AC heater

Opt
ion
al

The AC heater ensures that components in the cabinet work


within the acceptable temperature range when the
surrounding temperature is low. It can be installed in the 1
U space at the bottom of the cabinet. If both an AC heater
and an SOU are configured, the heater is installed in the 1
U space above the SOU.

12

SOU

Opt
ion
al

The SOU can be installed in the 1 U space at the bottom


of the cabinet, transferring AC power supply to the
customer equipment.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

21

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

In the APM30H:
l

If an AC heater or an SOU is not configured and one BBU is installed, 5 U space is provided
for customer equipment.

If an AC heater or an SOU is configured, it requires 1 U space for customer equipment.

Specifications of the Customer Equipment


The customer equipment in the Huawei cabinet must meet the following specifications:
l

Dimensions
The width is 19 inch.
The depth of the customer equipment which uses natural ventilation or supports heat
dissipation from left to right, is less than or equal to 280 mm (11.02 in.). The depth of
the customer equipment which supports heat dissipation from front to rear, is less than
250 mm (9.84 in.).
The cabling space in front of the front panel is less than or equal to 100 mm (3.94 in.).

Heat dissipation
If the customer equipment is configured with fans, the fans must dissipate heat out from
left to right or from front to rear.
If the customer equipment is not configured with fans but use natural ventilation, at
least 1 U space must be reserved above and below the installed devices to dissipate heat
from the cabinet.

Temperature
Table 2-11 Specifications of the temperature in the customer equipment
Highest Environmental
Temperature

Lowest Operating
Temperature for the
Customer Equipment

Highest Operating
Temperature for the
Customer Equipment

Equal to or lower than


40oC (104oF)

Equal to or lower than


-10oC (14oF)

Equal to or higher than


55oC (140oF)

Higher than 40oC (104oF)

Equal to or lower than


-10oC (14oF)

Equal to or higher than


60oC (140oF)

Figure 2-7 shows the dimensions and heat dissipation of the customer equipment.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

22

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-7 Dimensions and heat dissipation of the customer equipment

(1) Equipment using natural


ventilation

(2) Equipment supporting heat


dissipation from left to right

(3) Equipment supporting heat


dissipation from front to rear

2.6 Components in an APM30H


An APM30H consists of the AC/DC power system, fan assembly, electronic label unit (ELU),
door status sensor, filler module, optional AC heater, and service outlet unit (SOU).

2.6.1 AC/DC Power System


The AC/DC system converts 110 V/220 V AC power to -48 V DC.

Components in the AC/DC Power System


The AC/DC power system consists of the PMU 11A, PSUs (AC/D), and EPU subrack.
Figure 2-8 shows the components in the AC/DC power system.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

23

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-8 Components in the AC/DC power system

(1) PMU 11A

(2) PSUs

(3) Filler panel

(4) EPU subrack

Table 2-12 describes the modules in the AC/DC power system.


Table 2-12 Modules in the AC/DC power system
Module

Remarks

PMU 11A

It is installed in slot 0. For details about the


PMU 11A, see PMU.

PSU

A minimum of two PSUs must be configured.


The PSUs must be installed in adjacent slots
in the sequence from slot 1 to slot 5. For
details about PSUs, see PSU (AC/DC).

Filler panel

l Three PSUs are configured in the


APM30H (Ver.D1). The PSUs are
installed in slots 1, 2, and 3. Filler panels
must be installed in slots 4 and 5.
l A maximum of five PSUs can be
configured in the APM30H (Ver.D2).
Filler panels must be installed in vacant
slots.

EPU subrack

For details, see EPU subrack.

EPU subrack
The APM30H supports four types of EPU subracks, which are used in a distributed base station
and a separated macro base station with different AC inputs, respectively. The EPU subrack
houses the PMU and PSUs. It also distributes AC input power and DC output power.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

24

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Subrack Types
Table 2-13 lists the types and applications of EPU subracks in the AMP30H.
NOTE

The APM30H (Ver.D1) is configured with three PSUs, and the APM30H (Ver.D2) is configured with a
maximum of five PSUs.

Table 2-13 EPU subrack


Type

Remarks

Application

EPU05A
-02

It is a 5 U subrack, housing a
maximum of five R4850G2
PSUs and one PMU. It
distributes large- and smallcapacity DC power.

Separated macro base station with external 220


V AC input

EPU05A
-03

It is a 5 U subrack, housing a
maximum of five R4850G2
PSUs and one PMU. It
distributes large- and smallcapacity DC power.

Distributed base station with external 220 V AC


input

EPU05A
-04

It is a 5 U subrack, housing a
maximum of five R4850G2
PSUs and one PMU. It
distributes large- and smallcapacity DC power.

Separated macro base station with external 110


V AC input

EPU05A
-05

It is a 5 U subrack, housing a
maximum of five R4850G2
PSUs and one PMU. It
distributes large- and smallcapacity DC power.

Distributed base station with external 110 V AC


input

Exterior and Components


The EPU05A-03 and EPU05A-05 apply to a distributed base station. Figure 2-9 and Figure
2-10 show the exteriors of the EPU05A-03 and EPU05A-05, respectively.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

25

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-9 Exterior of an EPU05A-03 subrack

(1) PSU

(2) AC surge protector

(3) PSU1/4 circuit breaker, (4) AC OUTPUT circuit


PSU2/5 circuit breaker,
breaker
and PSU3 circuit breaker

(5) BAT circuit breaker

(6) Circuit breaker for


RFC1

(7) Output port for the


battery

(8) RFC1 output port

(9) LOAD0 to LOAD8


output ports

(10) RRU0 to RRU5


output ports

(11) Spare fuse box

(12) AC INPUT

(13) AC OUTPUT

(14) PMU

(15) Short-circuiting bar(1) -

NOTE

(1) On an EPU subrack with 220 V AC single-phase input, a short-circuiting bar is installed on the AC
INPUT wiring terminal to connect the L1, L2, and L3 terminals. On an EPU subrack with 220 V AC threephase input, there is no short-circuiting bar on the AC INPUT wiring terminal.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

26

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-10 Exterior of an EPU05A-05 subrack

(1) PSU

(2) AC surge protector

(3) PSU circuit breaker (4) AC OUTPUT1/AC


OUTPUT2 circuit breaker

(5) BAT circuit breaker

(6) Circuit breaker for


RFC1

(7) Output port for the


battery

(8) RFC1 output port

(9) LOAD0 to LOAD8


output ports

(10) RRU0 to RRU5


output ports

(11) Spare fuse box

(12) AC INPUT

(13) AC OUTPUT

(14) PMU

The EPU05A-02 and EPU05A-04 apply to a separated macro base station. Figure 2-11 and
Figure 2-12 show the exteriors of the EPU05A-02 and EPU05A-04, respectively.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

27

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-11 EPU05A-02

(1) PSU

(2) AC surge protector

(3) PSU1/4 circuit breaker, (4) AC OUTPUT circuit


PSU2/5 circuit breaker,
breaker
and PSU3 circuit breaker

(5) BAT circuit breaker (6) Circuit breaker for RFC1 (7) Circuit breaker for
RFC2

(8) Output port for the


battery

(9) RFC1 output port

(10) RFC2 output port

(11) LOAD0 to LOAD8


output ports

(12) Spare fuse box

(13) AC INPUT

(14) AC OUTPUT

(15) PMU

(16) Short-circuiting bar(1)

NOTE

(1) On an EPU subrack with 220 V AC single-phase input, a short-circuiting bar is installed on the AC
INPUT wiring terminal to connect the L1, L2, and L3 terminals. On an EPU subrack with 220 V AC threephase input, there is no short-circuiting bar on the AC INPUT wiring terminal.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

28

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-12 EPU05A-04

(1) PSU

(2) AC surge protector

(3) PSU circuit breaker

(4) AC OUTPUT1/AC
OUTPUT2 circuit breaker

(5) BAT circuit breaker (6) Circuit breaker for


RFC1

(7) Circuit breaker for


RFC2

(8) Output port for the battery

(9) RFC1 output port

(10) RFC2 output port

(11) LOAD0 to LOAD8 (12) Spare fuse box


output ports

(13) AC INPUT

(14) AC OUTPUT

(15) PMU

Functions
The EPU distributes AC and DC power.
l

The EPU performs the following AC power distribution functions:


Providing two AC outputs. One is used for the service outlet unit (SOU). The other one
is connected to the junction box on the left of the cabinet, and divided into four AC
power outputs, which are then provided for the heater or heating film.
The AC surge protector reports AC input surge protection alarms.

The EPU provides 17 or 12 DC outputs for a distributed base station or separated macro
base station.

Table 2-14 lists the DC power distribution functions of the EPU subrack of the APM30H in a
distributed base station.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

29

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Table 2-14 DC power distribution functions of the EPU subrack in a distributed base station
DC Power
Supply
Unit

DC output
ports

Protector

Protector
Specificati
on

Protector
Quantity

DC Output
Ports

BBU

LOAD0
and
LOAD1

Fuse(1)

30 A

EPC4, EPC5,
or EPC6

Fan assembly

LOAD2

TM_0

LOAD3

TM_1

LOAD4

TM_2 or
EMUA

LOAD5

TM_3 or
BBU

LOAD6

TMC

LOAD7

IBBS

LOAD8

RRU

RRU0 to
RRU5

RFC

RFC1

BAT

BAT

Breaker

125 A

OT terminal
(M6)

250 A

OT terminal
(M8)

Table 2-15 lists the DC power distribution functions of the EPU subrack of the APM30H in a
separated macro base station.
Table 2-15 DC power distribution functions of the EPU subrack in a separated macro base station
DC Power
Supply
Unit

DC output
ports

Protector

Protector
Specificati
on

Protector
Quantity

DC Output
Ports

BBU

LOAD0 and
LOAD1

Fuse(2)

30 A

EPC4 or
EPC6

Fan
assembly

LOAD2

TM_0

LOAD3

TM_1

LOAD4

TM_2 or
EMUA

LOAD5

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

30

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

DC Power
Supply
Unit

DC output
ports

Protector

TM_3 or
BBU

LOAD6

TMC

LOAD7

IBBS

LOAD8

RFC1

RFC1

RFC2
BAT

Breaker

Protector
Specificati
on

Protector
Quantity

DC Output
Ports

125 A

OT terminal
(M6)

RFC2

125 A

OT terminal
(M6)

BAT

250 A

OT terminal
(M8)

NOTE

(1) and (2): The spare fuse box provides five 5 A fuses and three 30 A fuses, which can be replaced onsite.

Technical Specifications of an EPU Subrack


Table 2-16 lists the technical specifications of an EPU subrack.
Table 2-16 Technical specifications of an EPU subrack
Module

Specifications

Output Voltage

-58 V DC to -44 V DC

Rated Voltage

-53.5 V DC

Output Current

0 A to 250 A

PMU
The power monitoring unit 11A (PMU 11A) provides the following functions: power system
management, battery management, power monitoring, and alarm reporting.

Exterior
Figure 2-13 shows the exterior of a PMU 11A.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

31

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-13 Exterior of a PMU 11A

Functions
The PMU 11A performs the following functions:
l

Communicates with the upper-level device through an RS485 serial port.

Manages the power system and charges and discharges storage batteries.

Reports alarms related to the door status, standby Boolean values, and battery temperature.

Monitors power distribution and reports alarms.

Communicates with the battery cabinet through an RS485 serial port.

Ports
Figure 2-14 shows the ports on the front panel of the PMU 11A.
Figure 2-14 Ports on the front panel of the PMU 11A

Table 2-17 describes the ports on the front panel of the PMU 11A.
Table 2-17 Ports on the front panel of the PMU 11A
No.

Silkscreen

Connector

Remarks

GATE

2-pin connector

Connects to a door
status sensor

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

32

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

No.

Silkscreen

Connector

Remarks

TEM_BAT

2-pin connector

Monitors the battery


temperature sensor

COM_IN

RJ45 connector

BBU
communication port
which is connected to
the BBU or
communicates with
the upper-level
monitoring board

COM_OUT

RJ45 connector

Lower-level
monitoring board

COM_485

RJ45 connector

Connects to the
monitoring board in
the battery cabinet,
and receives alarm
signals from the
battery cabinet.

Indicators
Table 2-18 describes the indicators on the PMU 11A.
Table 2-18 Indicators on the PMU 11A
Silks
creen

Colo
r

Meaning

Status

Meaning

RUN

Gree
n

Running
indicator

Steady on

The PMU 11A is performing


startup, self-check, loading, and
activation.

Blinking (on for


1s and off for 1s)

The PMU 11A is functional and


communicating with the main
control board in the BBU properly.
(This status does not necessarily
mean that the PMU 11A has been
configured.)

Blinking (on for


0.125s and off for
0.125s)

The PMU 11A is functional but


unable to communicate properly.

Steady off

The PMU 11A is faulty or there is


no DC power supply.

Steady on

Alarms are generated, and the


module must be replaced.

ALM

Issue Draft A (2012-9-15)

Red

Alarm indicator

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

33

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Silks
creen

Colo
r

Meaning

2 APM30H Product Description

Status

Meaning

Steady off

No alarm is generated.

Blinking (on for


1s and off for 1s)

An alarm is generated and you


need to locate the fault before
determining whether to replace the
PMU 11A.

DIP Switch
There is a DIP switch on the left panel of the PMU 11A. The DIP switch has eight bits, where
the four least significant bits (1, 2, 3, and 4) define the monitoring address of the PMU 11A, and
the four most significant bits (5, 6, 7, and 8) are not defined but reserved for future use.
ON is indicated by 1, and OFF is indicated by 0. The monitoring address of the PMU 11A is set
to 3 by default before delivery, as shown in Figure 2-15.
Figure 2-15 DIP switch on the left panel of the PMU 11A

PSU (AC/DC)
The power supply unit (PSU) converts 110 V AC or 220 V AC power into -48 V DC.

Exterior
Figure 2-16 shows the exterior of a PSU.
Figure 2-16 Exterior of a PSU

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

34

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Functions
The PSU performs the following functions:
l

Converts 110 V AC or 220 V AC power into -48 V DC. The PMU adjusts the output voltage.

The DC output of the PSU provides protection against overcurrent, overvoltage, and
overtemperature.

Dissipates heat using its built-in fans.

Indicators
Figure 2-17 shows the indicators on the PSU panel.
Figure 2-17 Indicators on the PSU panel

(1) Power indicator

(2) Protection indicator

(3) Fault indicator

Table 2-19 describes the indicators on the PSU panel.


Table 2-19 Indicators on the PSU
Silkscr
een

Color

Status

Meaning

Power
indicato
r

Green

Steady on

The board is functional.

Blinking (on for 0.125s


and off for 0.125s)

PSU online loading

Steady off

The mains supply or PSU is faulty.

Steady off

Yes

Steady on

An alarm triggered by an external factor is


generated.

Blinking (on for 1s and


off for 1s)

The communication between the PSU and the


PMU is interrupted.

Steady off

Yes

Steady on

The PSU is faulty or shut down in an


emergency. Locate the fault before
determining whether to replace the PSU.

Protecti
on
indicato
r

Fault
indicato
r

Issue Draft A (2012-9-15)

Yellow

Red

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

35

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Junction Box
Both APM30H and TMC11H are configured with a junction box, which feeds power into the
heater or heating film.
NOTE

l The EPU subrack feeds power into the junction box in the APM30H. The power is divided into four
AC power outputs, which are then provided for the heater in the cabinet or heating film in the
IBBS200D.
l The junction box in the APM30H feeds power into the junction box in the TMC11H. The power is
divided into four AC power outputs, which are then provided for the heater or service outlet unit (SOU)
in the cabinet.

Exterior
The junction box is installed on the inside of the left wall of the APM30H or TMC11H. Figure
2-18 shows the position and exterior of the junction box in the APM30H.
Figure 2-18 Exterior of the junction box

Structure
Figure 2-19 shows the structure of the junction box.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

36

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-19 Structure of the junction box

(1) Four AC output L wiring


terminals

(2) Four AC output N wiring


terminals

(3) Four AC output PE wiring


terminals

(4) Cable holes

(5) AC input N wiring terminal

(6) AC input L wiring terminal

2.6.2 Fan Assembly


A fan assembly consists of the fan subrack, fans, and central monitoring unit type EA (CMUEA).
Figure 2-20 shows the exterior of a fan assembly.
Figure 2-20 Exterior of a fan assembly

(1) Fan subrack

(2) Fan

(3) CMUEA

For details about the ports and indicators on the CMUEA, see 4.4.2 Central Monitoring Unit
Type EA (CMUEA).

2.6.3 ELU
The electronic label unit (ELU) reports the cabinet type automatically to facilitate
troubleshooting.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

37

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

The ELU is installed on the inside of the right wall of the APM30H/TMC11H/RFC or the inside
of the left wall of the IBBS200D/IBBS200T. Figure 2-21 shows the position and exterior of an
ELU on the inside of the right wall of the APM30H or the inside of the left wall of the IBBS200D.
Figure 2-21 Exterior of an ELU

(1) Shell

(2) RJ45 port

2.6.4 Door Status Sensor


The door status sensor monitors whether the cabinet door is open.
The door status sensor consists of the magnets and switch. Figure 2-22 shows the exterior of a
door status sensor.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

38

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-22 Exterior of a door status sensor

2.6.5 Filler Module


A filler module is a 1-U high standard plastic component. If any BBU is installed in the cabinet,
filler modules must be configured in the reserved customer space below the BBU to improve
the dissipation capability of the cabinet.

Exterior
Figure 2-23 shows the exterior of a filler module.
Figure 2-23 Exterior of a filler module

Functions
The filler module is installed in the customer space below the BBU to prevent the heat reflux in
the empty space below the BBU.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

39

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

NOTE

In the APM30H and TMC11H, the filler module is configured in the customer space by default. Before
installing other modules, remove the filler module. For details about removing a filler module, see chapter
"Installing Optional Modules" in the BTS3900A (Ver.D1) Installation Guide.

2.6.6 (Optional) AC Heater


The AC heater ensures that components in the cabinet work within the acceptable temperature
range when the surrounding temperature is low. The AC heater is optional.

Exterior
An AC heater is a device with a height of 1 U. Figure 2-24 shows the exterior of an AC heater.
Figure 2-24 Exterior of an AC heater

Technical Specifications
The technical specifications of an AC heater are as follows:
l

When the temperature is lower than 1oC6oC in the cabinet, the heater starts working. When
the temperature is higher than 15oC3oC in the cabinet, the heater stops working.

The rated power of the heater is 300 W.

2.6.7 (Optional) SOU


A service outlet unit (SOU) transfers AC power to equipment. The SOU is optionally installed
in the customer space in the APM30H or TMC11H.

Exterior
An SOU is a device with a height of 1 U. Figure 2-25 shows the exterior of an SOU.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

40

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-25 Exterior of an SOU

(1) Input power port

(2) Breaker

(3) Socket (European standard)

The SOU can be configured with sockets from different countries. The sockets can be classified
into sockets complying with North American standard, European standard, Universal standard,
and British standard, as shown in Figure 2-26.
Figure 2-26 Different types of sockets

Technical Specifications
Table 2-20 lists the technical specifications of an SOU.
Table 2-20 Technical specifications of an SOU
Item

Technical Specifications

Dimensions (H x W x D)

482.6 mm91 mm55 mm (19 in. x 3.58 in.


x 2.17 in.)

Weight

1.5 kg (3.31 lb)

Input voltage range

200 V AC to 240 V AC

Maximum input current

10 A

Output voltage range

200 V AC to 240 V AC

Maximum output current

10 A

Working frequency

50 Hz or 60 Hz

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

41

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Item

Technical Specifications

Operating temperature

-40oC to +55oC (-40oF to +131oF)

Altitude

4000 m (13123.36 ft)


NOTE
From the altitude of 3000 m (9842.52 ft), the
maximum operating temperature drops by 1oC
(33.8oF) each time the altitude increases by 100 m
(328.08 ft).

Protection level

IP20

2.7 APM30H Cables


This chapter describes the PGND cables, equipotential cables, power cables, and signal cables
in an APM30H.

2.7.1 Cable List


The APM30H cables mainly consist of the PGND cables, equipotential cables, power cables,
and signal cables.

Power Cables, PGND Cables, and Equipotential Cables


Table 2-21 lists the power cables, PGND cables, and equipotential cables.
Table 2-21 Power cables, PGND cables, and equipotential cables
Catego
ry

Cable

Cables
to be
installe
d onsite

Issue Draft A (2012-9-15)

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

Input Power
Cable for the
APM30H

OT terminal

AC INPUT
port on the
EPU

Depends on
the external
power device

External
power device

2.7.3 PGND
Cable

OT terminal

Ground bar in
the APM30H

OT terminal

Ground
busbar outside
the cabinet

2.7.4
Equipotential
Cable

OT terminal

Ground bar in
the APM30H

OT terminal

Ground bar in
the lower
cabinet

DCDU-12B
Input Power
Cable

OT terminal

RFC1 output
port on the
EPU in the
APM30H

OT terminal

RTN(+) and
NEG(-) ports
on the INPUT
in the
DCDU-12B

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

42

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Catego
ry

Cable

Cables
installe
d before
deliver
y

2 APM30H Product Description

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

Power Cables
for a Fan
Assembly

EPC4 or
EPC6
connector

LOAD5 port
on the EPU in
the APM30H

3V3
connector

PWR port on
the fan
assembly in
the APM30H

Power Cable
for an AC
Heater (in the
APM30H)

OT terminal

L0, N0, and


ground bar in
the junction
box in the
APM30H

C13
connector

Input power
port on the AC
heater

SOU Power
Cable

OT terminal

M4 ground
screw, L2,
and N2 (AC
OUTPUT) on
the EPU

C13
connector

AC INPUT
port on the
SOU

Input Power
Cable for a
Junction Box
(in the
APM30H)

OT terminal

M4 ground
screw, L1,
and N1 (AC
OUTPUT) on
the EPU

OT terminal

L, N, and
ground bar in
the junction
box in the
APM30H

NOTE

The connection of the optional power cables depends on the delivery mode. Table 2-21 describes the power
cables in a macro base station.

Signal Cables
Table 2-22 describes the signal cables.
Table 2-22 Signal cables
Categ
ory

Cable

Cables
to be
install
ed
onsite

Issue Draft A (2012-9-15)

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

43

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Categ
ory

Cable

Cables
install
ed
before
deliver
y

2 APM30H Product Description

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

PMUCMUEA
Monitoring
Signal
Cable

RJ45
connector

COM_IN port on
the PMU

RJ45
connector

COM_OUT port on
the CMUEA in the
fan assembly in the
APM30H

ELU Signal
Cable

RJ45
connector

ELU

RJ45
connector

ELU port in the


CMUEA

Monitoring
Signal
Cables for a
Door Status
Sensor in
an
APM30H

2-pin
connector

GATE port on the


PMU

Bare wire

Door status sensor

Monitoring
Signal
Transfer
Cable for
the Fan on
the Front
Door

Interconne
ction
terminal

Transfer terminal
on the front door
of the APM30H

4-pin
connector

FAN_EXT port on
the CMUEA

2.7.2 APM30H Cable Connections


This chapter describes the principles for connecting power cables and signal cables.

APM30H Power Cable Connections


The section provides a figure showing the APM30H power cable connections.

Cable Connections in a Distributed Base Station


Figure 2-27 shows the power cable connections in an APM30H in a distributed base station.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

44

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-27 Power cable connections in a distributed base station

(1) Input power cable for a junction (2) Power cable for a fan assembly in (3) Input power cable for batteries
box
an APM30H
(4) Input power cable for an RFC

(5) Power cable for an SOU

(6) Power cable for an AC heater

Cable Connections in a Separated Macro Base Station


Figure 2-28 shows the power cable connections in an APM30H in a separated macro base
station.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

45

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-28 Power cable connections in a separated macro base station

(1) Input power cable for a junction (2) Power cable for a fan assembly in (3) Input power cable for batteries
box
an APM30H
(4) Input power cable for RFC1

(5) Input power cable for RFC2

(6) Power cable for an SOU

(7) Power cable for an AC heater

APM30H Signal Cable Connections


This section describes the APM30H signal cable connections.
Figure 2-29 shows the APM30H signal cable connections.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

46

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-29 APM30H signal cable connections

(1) Monitoring signal cable for the fans on the front


door

(2) Monitoring signal transfer cable for the fans on the


front door

(3) PMU-CMUEA monitoring signal cable

(4) Monitoring signal cable for the door status sensor


in the APM30H

(5) ELU signal cable

2.7.3 PGND Cable


A PGND cable connects a cabinet to a ground bar, which provides ground protection for the
cabinet. The maximum length of a PGND cable is 30 m (98.43 ft).

Exterior
Figure 2-30 shows the exterior of a PGND cable.
NOTE

When the 110 V AC dual-live-wire power is supplied for the cabinet, a green PGND cable is used.

Figure 2-30 Exterior of a PGND cable

(1) OT terminal

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

47

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Cable Description
Table 2-23 describes a PGND cable.
Table 2-23 PGND cable
Cable

Color

Cross-Sectional Area of the Core Wire and


Size of the OT Terminal

PGND cable

Green and yellow

M6, 16 mm2 (0.025 in.2)

2.7.4 Equipotential Cable


An equipotential cable connects the PGND terminals of two cabinets. It ensures equipotential
bonding between the cabinets and the safe operation of base stations.

Exterior
Figure 2-31 shows the exterior of an equipotential cable.
NOTE

When the 110 V AC dual-live-wire power is supplied for the cabinet, a green equipotential cable is used.

Figure 2-31 Exterior of an equipotential cable

(1) OT terminal

Cable Description
Table 2-24 describes an equipotential cable.
Table 2-24 Equipotential cable
Cable

Color

Cross-Sectional Area of the Core Wire and


Size of the OT Terminal

Equipotential cable
between cabinets

Green and yellow

M6, 16 mm2 (0.025 in.2)

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

48

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

2.7.5 Power Cables


This chapter describes all power cables in the APM30H.

Input Power Cable for the APM30H


An input power cable for the APM30H feeds external AC power into the power system of the
APM30H. Different power systems enable a cabinet to support power supplies of 220 V AC
single-phase, 220 V AC three-phase, and 110 V/220 V dual-live-wire.

Exterior
Figure 2-32 shows a 220 V AC single-phase input power cable.
Figure 2-32 Exterior of a 220 V AC single-phase input power cable

(1) OT terminal

NOTE

Different types of AC input power cables consist of different numbers of core wires. Figure 2-32 shows
the inner structure of a 220 V AC single-phase input power cable.

Cable Description
Table 2-25 lists the specifications of different types of AC input power cables.
Table 2-25 Specifications of an AC input power cable
Cable

Wire

Wire Color

Cross-Sectional Area
of the Core Wire and
Size of the OT
Terminal

220 V AC threephase power cable

L1 wire

Brown

L2 wire

Black

L3 wire

Gray

l APM30H (Ver.D1): 4
mm2 (0.006 in.2), M6
l APM30H (Ver.D2): 6
mm2 (0.009 in.2), M6

N wire

Blue

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

49

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Cable

Wire

Wire Color

Cross-Sectional Area
of the Core Wire and
Size of the OT
Terminal

220 V AC singlephase power cable

L wire

Brown

N wire

Blue

l APM30H (Ver.D1):
16 mm2 (0.025 in.2),
M6
l APM30H (Ver.D2):
25 mm2 (0.039 in.2),
M6

110 V/120 V AC
dual-live-wire

L1 wire

Black

L2 wire

Red

N wire

White

l APM30H (Ver.D1):
16 mm2 (0.025 in.2),
M6
l APM30H (Ver.D2):
25 mm2 (0.039 in.2),
M6

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and areas. If cables
are purchased at local markets, the cables must comply with local rules and regulations.

DCDU-12B Input Power Cable


A DCDU-12B input power cable feeds DC power into a DCDU-12B from external power
devices.

DCDU-12B Used in Distributed Base Stations


l

When AC power is used, the DCDU-12B is installed in an APM30H and obtains power
from the RFC1 output port. The maximum length of a DCDU-12B input power cable is
1.5 m (4.92 ft). Figure 2-33 shows the exterior and Table 2-26 describes the specifications
of a DCDU-12B input power cable.

When DC power is used, the second DCDU-12B is installed in a TMC11H and obtains
power from external power devices. The maximum length of a DCDU-12B power cable is
10 m (32.81 ft). Figure 2-34 shows the exterior and Table 2-27 describes the specifications
of a DCDU-12B input power cable.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

50

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-33 DCDU-12B input power cable (1)

(1) OT terminal

Table 2-26 Specifications of a DCDU-12B input power cable (1)


Cable

Wire

Wire Color

Cross-Sectional Area of
the Core Wire and Size of
the OT Terminal

DCDU-12B input
power cable (1)

RTN(+)

Black

M6, 25 mm2 (0.039 in.2)

NEG(-)

Blue

Figure 2-34 DCDU-12B input power cable (2)

(1) OT terminal

Table 2-27 Specifications of a DCDU-12B input power cable (2)


Cable

Wire

Wire Color

Cross-Sectional Area of
the Core Wire and Size of
the OT Terminal

DCDU-12B input
power cable (2)

RTN(+)

Black

NEG(-)

Blue

M6, one input: 35 mm2


(0.054 in.2), two inputs: 16
mm2 (0.025 in.2)

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

51

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

DCDU-12B Used in Separated Macro Base Stations


l

When AC power is used, the DCDU-12B is installed in an RFC and obtains power from
the RFC2 output port in an APM30H. The maximum length of a DCDU-12B input power
cable is 1.5 m (4.92 ft). Figure 2-33 shows the exterior and Table 2-26 describes the
specifications of a DCDU-12B input power cable.

When DC power is used, the second DCDU-12B is installed in a TMC11H and obtains
power from external power devices. The maximum length of a DCDU-12B power cable is
15 m (49.21 ft). Figure 2-34 shows the exterior and Table 2-27 describes the specifications
of a DCDU-12B input power cable.

SOU Power Cable


The power cable for a service outlet unit (SOU) feeds AC input power into the SOU from the
AC OUTPUT port on the EPU.

Exterior
Figure 2-35 shows the exterior of the power cable for an SOU.
Figure 2-35 Exterior of the power cable for an SOU

(1) C13 connector

(2) OT terminal (M4, 2.5 mm2 or 0.004 in.2)

Cable Description
Table 2-28 describes the wires of the power cable for an SOU.
Table 2-28 Wires of the power cable for an SOU
Wire
Number

Color

Connector

Label

W1

Brown

OT terminal

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

52

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Wire
Number

Color

Connector

Label

W2

Green and
yellow

OT terminal

PE

W3

Blue

OT terminal

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and areas. If cables
are purchased at local markets, the cables must comply with local rules and regulations.

Power Cable for an AC Heater


The power cable for an AC heater feeds AC input power into the AC heater from the junction
box. If a heater is configured in the -48 V DC input scenario, one more AC power input must
be added for the heater. In this case, the maximum length of the power cable for the heater is 15
m (49.21 ft).

Exterior
Figure 2-36 shows the exterior of the power cable for an AC heater.
Figure 2-36 Exterior of the power cable for an AC heater

(1) C13 connector

(2) OT terminal (M4, 1.5 mm2 or 0.002 in.2)

Cable Description
Table 2-29 describes the wires of the power cable for an AC heater.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

53

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Table 2-29 Wires of the power cable for an AC heater


Wire
Number

Color

Connector

Label

W1

Brown

OT terminal

W2

Green and
yellow

OT terminal

PE

W3

Blue

OT terminal

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and areas. If cables
are purchased at local markets, the cables must comply with local rules and regulations.

Power Cables for a Fan Assembly


The power cable for a fan assembly feeds -48 V DC power into the fan assembly.

Exterior
Figure 2-37 shows the exterior of the power cable for a fan assembly.
Figure 2-37 Exterior of the power cable for a fan assembly

(1) 3V3 connector

(2) EPC4 or EPC6 connector

Cable Description
Table 2-30 describes the wires of the power cable for a fan assembly.
Table 2-30 Wires of the power cable for a fan assembly
Cable

Wire

Wire Color

Power cables for a fan


assembly

RTN(+)

Black

NEG(-)

Black

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

54

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Input Power Cable for a Junction Box


The input power cable for a junction box feeds AC input power from the AC power system into
the junction box. The junction box provides four AC power outputs for the heater or heating
film.

Exterior
Figure 2-38 shows the exterior of an input power cable for a junction box.
Figure 2-38 Input power cable for a junction box

(1) OT terminal (M4, 1.5 mm2 or 0.002 in.2)

Cable Description
Table 2-31 describes the wires of an input power cable for a junction box.
Table 2-31 Wires of an input power cable for a junction box
Wire
Number

Color

One End

The Other End

Label

W1

Brown

X1

X3

W2

Blue

X2

X4

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and areas. If cables
are purchased at local markets, the cables must comply with local rules and regulations.

2.7.6 Signal Cables


This chapter describes all signal cables in the APM30H.

ELU Signal Cable


The electronic label unit (ELU) signal cable is used by the ELU to report the cabinet type to the
central monitoring unit type EA (CMUEA).
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

55

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Exterior
Figure 2-39 shows the exterior of an ELU signal cable.
Figure 2-39 Exterior of an ELU signal cable

(1) RJ45 connector

Cable Description
Table 2-32 describes the pin assignment for the wires of an ELU signal cable.
Table 2-32 Pin assignment for the wires of an ELU signal cable
X1 End

X2 End

Color

Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

X1.3

X2.3

White

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Twisted pair

Twisted pair

Twisted pair

Monitoring Signal Cables for a Door Status Sensor in an APM30H


The monitoring signal cable for a door status sensor in an APM30H transmits the alarms from
the door status sensor to the PMU. The PMU reports the alarms to the BBU.

Exterior
Figure 2-40 shows the exterior of the monitoring signal cable for a door status sensor in an
APM30H.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

56

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-40 Exterior of the monitoring signal cable for a door status sensor

The description of the monitoring signal cable for a door status sensor is as follows:
l

Cable 1 has a 2-pin straight socket at one end, which is connected to the GATE port on the
PMU. Cable 1 has a bare wire and a cord end terminal at the other end, which are connected
to a door status sensor and cable terminal block, respectively.

Cable 2 has a bare wire at one end, which is connected to a door status sensor. Cable 2 has
a cord end terminal at the other end, which is connected to a cable terminal block.

Cable 3 has a cord end terminal at each end. The two cord end terminals are connected to
the two ports on one side of the cable terminal block.

Monitoring Signal Transfer Cable for the Fan on the Front Door
The monitoring signal transfer cable for the fan on the front door feeds power to the fan on the
front door in the APM30H or TMC11H and reports fan monitoring signals to the central
monitoring unit type EA (CMUEA).

Exterior
Figure 2-41 shows the exterior of the monitoring signal transfer cable for the fan on the front
door.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

57

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-41 Exterior of the monitoring signal transfer cable for the fan on the front door

(1) 4-pin connector

(2) Interconnection terminal

Cable Description
Table 2-33 shows the pin assignment for the wires of the monitoring signal transfer cable for
the fan on the front door.
Table 2-33 Pin assignment for the wires of the monitoring signal transfer cable for the fan on
the front door
Cable

X1 End

X2 End

Color

W1

X1.1

X2.1

Black

W2

X1.2

X2.2

Black

W3

X1.3

X2.3

Black

W4

X1.4

X2.4

Black

PMU-CMUEA Monitoring Signal Cable


The PMU-CMUEA monitoring signal cable transmits the RS485 signals collected by the PMU
to the BBU through the CMUEA. This monitoring signal cable is 1.1 m (3.61 ft) long.

Exterior
The monitoring signal cable is black and has an RJ45 connector at each end, as shown in Figure
2-42.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

58

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

2 APM30H Product Description

Figure 2-42 Exterior of a monitoring signal cable

(1) RJ45 connector

Cable Description
Table 2-34 describes the pin assignment for the wires of a monitoring signal cable.
Table 2-34 Pin assignment for the wires of a monitoring signal cable
X1 End

X2 End

Description

X1.1

X2.1

Twisted pair

X1.2

X2.2

X1.3

X2.3

X1.6

X2.6

X1.4

X2.4

X1.5

X2.5

X1.7

X2.7

X1.8

X2.8

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Twisted pair

Twisted pair

Twisted pair

59

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

TMC11H Product Description

About This Chapter


This chapter describes the exterior, functions, technical specifications, application scenarios,
structure, components, and cables of the TMC11H.
3.1 TMC11H Description
A transport management cabinet with a heat-exchanger (TMC11H) is used for Huawei wireless
products outdoors. It supplies DC power to the distributed or separated macro base station in
outdoor scenarios.
3.2 Technical Specifications of a TMC11H
The technical specifications of a TMC11H consist of electrical specifications, engineering
specifications, surge protection specifications, and environmental specifications.
3.3 Application Scenarios of a TMC11H
A TMC11H can apply to a distributed base station or a separated macro base station.
3.4 TMC11H Structure
The TMC11H uses a modular and integrated structure. This allows the cabinet to be operated
and maintained easily.
3.5 TMC11H Components
An TMC11H consists of the DCDU, fan assembly, junction box, electronic label unit (ELU),
door status sensor, filler module, optional AC heater, and optional service outlet unit (SOU).
3.6 TMC11H Cables
This chapter describes the equipotential cables, power cables, and signal cables in a TMC11H.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

60

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

3.1 TMC11H Description


A transport management cabinet with a heat-exchanger (TMC11H) is used for Huawei wireless
products outdoors. It supplies DC power to the distributed or separated macro base station in
outdoor scenarios.

Exterior of a TMC11H
The exterior of a TMC11H is the same as that of an APM30H, but their components are different.
Dimensions of the TMC11H (H x W x D): 700 mm x 600 mm x 480 mm or 27.56 in. x 23.62
in. x 18.90 in. (not including the base)
Figure 3-1 shows the exterior of a TMC11H.
Figure 3-1 Exterior of a TMC11H

Functions of a TMC11H
Table 3-1 describes the functions of a TMC11H.
Table 3-1 Functions of a TMC11H
Item

Description

-48 V DC
power

A built-in DCDU-12B or DCDU-12C performs the following functions:


l Supports one -48 V DC input.
l Provides ten -48 V DC outputs (LOAD0 to LOAD9).

Space for
customer
equipment

Issue Draft A (2012-9-15)

l Provides an 11 U space for customer equipment.


l A heater (1 U) is optionally installed in the space for customer
equipment.
Huawei Proprietary and Confidential
Copyright Huawei Technologies Co., Ltd.

61

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Item

Description

Reporting
alarms

Provides dry contact alarm ports, achieving remote monitoring and


unattended operation. Dry contact port 1 is connected to the door status
sensor. An open circuit means that the connection is faulty, whereas a closed
circuit means that the connection is normal.

Reporting the
cabinet type
automatically

The electronic label unit (ELU) reports the cabinet type automatically.

3.2 Technical Specifications of a TMC11H


The technical specifications of a TMC11H consist of electrical specifications, engineering
specifications, surge protection specifications, and environmental specifications.

Electrical Specifications of a TMC11H


Table 3-2 describes the electrical specifications of a TMC11H.
Table 3-2 Electrical specifications of a TMC11H
Item
Characteristi
cs of DC
input

Specifications
Input voltage
range

-38.4 V DC to -57 V DC

Typical input
voltage

-48 V DC

Maximum input
current

The maximum input current depends on the application


scenario.
l In a distributed base station: 160 A
l In a separated macro base station: 30 A (The power
is supplied to TMC11H by the APM30H.)

Characteristi
cs of DC
output

Protection

Issue Draft A (2012-9-15)

Input mode

-48 V DC power input, supporting the one-hole M6 OT


terminals

DC distribution

Ten -48 V DC outputs: LOAD0 to LOAD9, used to


supply power to the customer equipment

Typical output
voltage

-48 V DC
Provides overcurrent protection and short-circuit
protection for the DC power.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

62

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Item

Specifications

Heat consumption of the cabinet

l TMC11H (Ver.D1) 1050 W (heat dissipation


capability in the ambient temperature lower than
50oC or 122oF)
l TMC11H (Ver.D2) 1500 W (heat dissipation
capability in the ambient temperature lower than
50oC or 122oF)

Engineering Specifications of a TMC11H


Table 3-3 describes the engineering specifications of a TMC11H.
Table 3-3 Engineering specifications of a TMC11H
Item

Specifications

Remarks

Cabinet weight

47 kg (103.62 lb)

Total weight of the equipment


l Including the cabinet, outer air
circulation assembly (heat
dissipation core and outer air
circulation fan), inner air
circulation fan assembly, direct
current distribution unit (DCDU),
and cables
l Excluding the customer
transmission equipment

Dimensions of the
cabinet (H x W x D)

700 mm x 600 mm x 480 mm


(27.56 in. x 23.62 in. x 18.90
in.)

Dimensions of the
base (H x W x D)

200 mm x 600 mm x 434 mm


(7.87 in. x 23.62 in. x 17.09
in.)

Space for the


customer equipment
(H x W x D)

11 U x 482.6 mm x 380 mm
(11 U x 19 in. x 14.96 in.)

The depth includes 100 mm (3.94 in.)


in front of the columns and 280 mm
(11.02 in.) between the columns and
the rear of the cabinet.

Cabling and
maintenance space
at the front

70 mm (2.76 in.)

Installation mode

The APM30H (Ver.D2) can


be installed on the ground,
pole, or wall. It can also be
stacked on the RFC,
IBBS200D, or IBBS200T.

In stack mode, the TMC11H must be


installed on the RFC, IBBS200D, or
IBBS200T.

Issue Draft A (2012-9-15)

The appearance and base of the


TMC11H are the same as those of the
APM30H.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

63

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Surge Protection Specifications of a TMC11H


Table 3-4 describes the surge protection specifications of a TMC11H.
Table 3-4 Surge protection specifications of a TMC11H
Item

Specifications

Surge protection for DC


input ports

l In differential mode (8/20 us): 3 kA

Surge protection for DC


output ports

l In differential mode (8/20 us): 10 kA

l In common mode (8/20 us): 5 kA

l In common mode (8/20 us): 20 kA


The DC output port corresponds to the secondary load.
NOTE
The surge protection capacity of the shield layer in an RRU power cable
is 40 kA.

Environmental Specifications of a TMC11H


The TMC11H can be used outdoors. Table 3-5 describes the environmental specifications of a
TMC11H.
Table 3-5 Environmental specifications of a TMC11H
Item

Specifications

Remarks

Operating
temperatur
e

-40oC to + 50oC (-40oF to


+122oF)

A heater is required when the temperature is


lower than -20oC (-4oF). A sun shield is
required when the temperature is higher than
50oC (122oF).
NOTE
A heater is required if the local average lowest
temperature of each day in the coldest month of the
year is lower than the specified operating
temperature for configuring a heater.

Relative
humidity

5% RH to 100% RH

Altitude

-60 m to 4000 m (-196.85 ft to


13123.36 ft)

From the altitude of 1800 m (5905.51 ft), the


maximum operating temperature drops by 1oC
(33.8oF) each time the altitude increases by 220
m (721.78 ft).

Wind
speed

67 m/s

Storage
temperatur
e

-40oC to + 70oC (-40oF to


+158oF)

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

64

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Item

Specifications

Remarks

Dustproof
and
waterproof

IP55

Noise

When the heat consumption


of the cabinet is equal to or
less than 700 W, the noise is
equal to or less than 61 dBA
in the temperature of 25oC
(77oF), and the noise is equal
to or less than 67 dBA in the
temperature of 45oC (113oF).

Meeting the ETS 300 753 4.1E standard (rural


level)

l TMC11H (Ver.D1):
When the heat
consumption of the
cabinet is equal to 1050 W
or between 700 W and
1050 W, the noise is equal
to or less than 66 dBA in
the temperature of 25oC
(77oF), and the noise is
equal to or less than 76
dBA in the temperature of
45oC (113oF).

Meeting the ETS 300 753 4.1E standard (urban


level)

l TMC11H (Ver.D2):
When the heat
consumption of the
cabinet is equal to 1500 W
or between 700 W and
1500 W, the noise is equal
to or less than 66 dBA in
the temperature of 25oC
(77oF), and the noise is
equal to or less than 76
dBA in the temperature of
45oC (113oF).

3.3 Application Scenarios of a TMC11H


A TMC11H can apply to a distributed base station or a separated macro base station.

TMC11H Used in a Distributed Base Station


The description of a TMC11H used in a distributed base station is as follows:
l

Supplied with -48 V DC power.

Combined with RRUs.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

65

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Configured with a DCDU-12B, which feeds power into RRUs and the BBU, fan assembly,
and transmission equipment in the TMC11H.

Figure 3-2 shows the scenario where a TMC11H is used in a distributed base station.
Figure 3-2 TMC11H used in a distributed base station

TMC11H Used in a Separated Macro Base Station


The description of a TMC11H used in a separated macro base station is as follows:
l

Supplied with -48 V DC power.

Stacked on the RFC.

One external -48 V DC input is supplied to the DC junction box on the inside of the left
wall of the RFC, and then distributed to the DCDUs in the RFC and TMC11H.

Figure 3-3 shows the scenario where a TMC11H is used in a separated macro base station.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

66

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-3 TMC11H used in a separated macro base station

3.4 TMC11H Structure


The TMC11H uses a modular and integrated structure. This allows the cabinet to be operated
and maintained easily.

Cabinet Structure
Figure 3-4 shows the interior of a TMC11H.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

67

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-4 Interior of a TMC11H

N
o.

Module

Outer air
circulatio
n
assembly

Ma
nda
tory

The assembly is installed on the front door of the cabinet,


dissipating heat from the cabinet.

Junction
Box

Ma
nda
tory

The junction box converts one AC input into four AC outputs


and is used in the scenario where a service outlet unit (SOU)
and multiple heating films or heaters are configured.

Issue Draft A (2012-9-15)

Op
tio
nal
/
Ma
nd
ato
ry

Ma
xi
mu
m
Qu
ant
ity
Co
nfi
gur
ed
in
a
Sin
gle
Ca
bin
et

Remarks

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

68

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

N
o.

Module

Fan
assembly

Op
tio
nal
/
Ma
nd
ato
ry

Ma
nda
tory

3 TMC11H Product Description

Ma
xi
mu
m
Qu
ant
ity
Co
nfi
gur
ed
in
a
Sin
gle
Ca
bin
et
1

Issue Draft A (2012-9-15)

The fan assembly is configured with the fan and CMUEA,


dissipating heat from the cabinet.
l To provide protection for trunk signals, a signal lightning
protection unit (SLPU) is mandatory and installed in the
top 1 U space of the cabinet. It is configured with the
universal E1/T1 lightning protection unit (UELP) or
universal FE lightning protection unit (UFLP).

Ma
nda
tory

Door
status
sensor

Ma
nda
tory

The door status sensor monitors whether the cabinet door is


open.

Electroni
c label
unit
(ELU)

Ma
nda
tory

The ELU reports the cabinet type automatically to facilitate


troubleshooting.

DCDU-1
2B or
DCDU-1
2C

Ma
nda
tory

The direct current distribution unit-12B (DCDU-12B) or


direct current distribution unit-12C (DCDU-12C) in the
TMC11H feeds DC power into all components in the
TMC11H. The height of a DCDU-12B or DCDU-12C is 1 U.
The DCDU varies with the installation scenarios.

SLPU

Remarks

l To provide protection for monitoring signals, an SLPU is


optional and installed in the 1 U space below the BBU. It
is configured with two universal signal lightning
protection unit 2 (USLP2) boards.

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

69

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

N
o.

Module

Op
tio
nal
/
Ma
nd
ato
ry

3 TMC11H Product Description

Ma
xi
mu
m
Qu
ant
ity
Co
nfi
gur
ed
in
a
Sin
gle
Ca
bin
et

Remarks

A maximum of one BBU3900 can be configured in a


TMC11H (Ver.D1) and two in a TMC11H (Ver.D2).
BBU390
0

Opt
ion
al

l The BBU3900 provides physical ports for communication


between the BBU3900 and the BSC or RNC, and enables
interaction between the base station and the BSC or RNC.
l The BBU3900 provides CPRI ports for communication
between the BBU3900 and RFUs.
l The BBU3900 processes uplink and downlink data.

10

Environ
ment
monitorin
g unit
type A
(EMUA)

Opt
ion
al

The EMUA monitors the equipment environment.

Filler
Module

Opt
ion
al

A filler module is a plastic component with a height of 1 U in


the cabinet, preventing the heat reflux in the empty space
below the BBU.

AC
heater

Opt
ion
al

The AC heater ensures that components in the cabinet work


within the acceptable temperature range when the
surrounding temperature is low. It can be installed in the 1 U
space at the bottom of the cabinet.

11

In the TMC11H:
l

If a filler module and an AC heater are not configured, 11 U space is provided for the
customer equipment.

If an AC heater is configured, it is preferentially installed in the bottom 1 U space.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

70

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Specifications of the Customer Equipment


The customer equipment in the Huawei cabinet must meet the following specifications:
l

Dimensions
The width is 19 inch.
The depth of the customer equipment which uses natural ventilation or supports heat
dissipation from left to right, is less than or equal to 280 mm (11.02 in.). The depth of
the customer equipment which supports heat dissipation from front to rear, is less than
250 mm (9.84 in.).
The cabling space in front of the front panel is less than or equal to 100 mm (3.94 in.).

Heat dissipation
If the customer equipment is configured with fans, the fans must dissipate heat out from
left to right or from front to rear.
If the customer equipment is not configured with fans but use natural ventilation, at
least 1 U space must be reserved above and below the installed devices to dissipate heat
from the cabinet.

Temperature
Table 3-6 Specifications of the temperature in the customer equipment
Highest Environmental
Temperature

Lowest Operating
Temperature for the
Customer Equipment

Highest Operating
Temperature for the
Customer Equipment

Equal to or lower than


40oC (104oF)

Equal to or lower than


-10oC (14oF)

Equal to or higher than


55oC (140oF)

Higher than 40oC (104oF)

Equal to or lower than


-10oC (14oF)

Equal to or higher than


60oC (140oF)

Figure 3-5 shows the dimensions and heat dissipation of the customer equipment.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

71

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-5 Dimensions and heat dissipation of the customer equipment

(1) Equipment using natural


ventilation

(2) Equipment supporting heat


dissipation from left to right

(3) Equipment supporting heat


dissipation from front to rear

3.5 TMC11H Components


An TMC11H consists of the DCDU, fan assembly, junction box, electronic label unit (ELU),
door status sensor, filler module, optional AC heater, and optional service outlet unit (SOU).

3.5.1 DCDU-12B
A direct current distribution unit-12B (DCDU-12B) is 1 U high and provides DC power for all
components in the cabinet.

Exterior
Figure 3-6 and Figure 3-7 show exterior of a DCDU-12B.
Figure 3-6 Front view of a DCDU-12B

(1) DC input terminal

Issue Draft A (2012-9-15)

(2) DC output terminal

(3) Spare fuse box

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

(4) Ground point

72

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-7 Rear view of a DCDU-12B

(1) Ground point

NOTE

The DCDU-12B uses the equipotential connection point and ground point in the following scenarios:
l Scenario 1: The DCDU-12B is installed on an open subrack. An equipotential cable connects the
equipotential connection point near the mounting ear of the DCDU-12B to the ground bar of the open
rack.
l Scenario 2: The DCDU-12B is installed on a wall as a standalone power distribution device. The ground
point at the rear of the DCDU-12B is connected to the ground bar in the cabinet.

Functions
The DCDU-12B provides ten -48 V DC outputs using same fuse configurations to meet the
power distribution requirements of different distributed base stations.
Table 3-7 describes the DC power distribution functions of the DCDU-12B.
Table 3-7 DC power distribution functions of the DCDU-12B
DCDU Type

DC output
ports

PowerConsuming
Device

Specificatio
n of the
Fuse

Remarks

DCDU-12B

LOAD0 to
LOAD5

RRU0 to RRU5

30 A

LOAD6

BBU or
transmission
device

l
l
l
l

LOAD7

BBU or
transmission
device

LOAD8

EMUA or
transmission
device

LOAD9

Fan assembly

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

BTS3900
BTS3900A
DBS3900
Mini NodeB

73

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

NOTE

When a second DCDU-12B is installed in a macro+distributed base station, it is recommended that the
power output terminals on the DCDU-12B be connected as follows:
l The LOAD0 to LOAD5 terminals are connected to cables with a cross-sectional area of 6 mm2 (0.009
in.2) to 10 mm 2 (0.015 in.2) to provide power for RRU 0 to RRU 5.
l The LOAD6 to LOAD8 terminals are connected to cables with a cross-sectional area of 3.3 mm2 (0.005
in.2) to 4 mm2 (0.006 in.2) to provide power for RRU 6 to RRU 8.
l The LOAD9 terminal is reserved.

Ports
Figure 3-8 shows the ports on the DCDU-12B panel.
Figure 3-8 Ports on the DCDU-12B panel

Table 3-8 shows the terminals and switches on the DCDU-12B panel.
Table 3-8 Terminals and switches on the DCDU-12B panel
N
o.

Port

Silkscreen

Matched Terminal
and Cable

Remarks

(1)

DC input
terminals

NEG(-)

One-hole OT
terminal (M6) with
two inputs. The
maximum crosssectional area of the
cable is 35 mm2
(0.054 in.2) in one
input or 25 mm2
(0.039 in.2)in two
inputs. The default
cross-sectional area
is 16 mm2 (0.025 in.
2).

Negative power input wiring


terminal

RTN(+)

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Positive power input wiring


terminal

74

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

N
o.

Port

Silkscreen

Matched Terminal
and Cable

Remarks

(2)

Fuse
block

LOAD0 to
LOAD9

It controls ports LOAD0 to


LOAD9, and therefore controls
the power supplies to the BBU,
fan assemblies, and
transmission equipment.
The indicator on the fuse block
indicates the status of the fuse.
l When the indicator is steady
on, the fuse is faulty and
needs to be replaced.
l When the indicator is steady
off, the fuse is working
properly.

(3)

DC
output
ports

LOAD0 to
LOAD9

l Figure 3-9 shows For the specifications of the DC


output, see Table 3-7.
the EPC5
connectors for
ports LOAD0 to
LOAD5. The
maximum crosssectional area of
the cable is 10
mm2 (0.016 in.2).
l Figure 3-10
shows an EPC4/
EPC6 connector,
which applies to
any one among
ports LOAD6 to
LOAD9. The
maximum crosssectional area of
the cable is 4
mm2 (0.006 in.2).
NOTE
Figure 3-10 shows an
EPC4 or EPC6
connector. An EPC4
connector must be
connected to a cable
onsite, whereas an
EPC6 connector has
been connected to a
cable before delivery.
The EPC5 connector
must be connected to
the cable onsite.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

75

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

NOTE

Fuse blocks and DC output terminals are jointly called fuse terminal blocks.

Figure 3-9 Exterior of an EPC5 connector

Figure 3-10 Exterior of an EPC4 or EPC6 connector

Technical Specifications
Table 3-9 lists the technical specifications of a DCDU-12B.
Table 3-9 Technical specifications of a DCDU-12B
Item

Specifications

Dimensions (H x W x D)

The DCDU-12B is 1 U high and can be


installed in a 19-inch cabinet or rack. Its
dimensions are as follows:
l 42 mm x 442 mm x 65 mm (1.65 in. x 17.4
in. x 2.56 in.) (without mounting ears)
l 42 mm x 482.6 mm x 65 mm (1.65 in. x
19 in. x 2.56 in.) (with mounting ears)

Surge Protection Specifications

-48 V DC power port, 10 kA (8/20 s)


differential mode
-48 V DC power port, 20 kA (8/20 s)
common mode

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

76

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

3.5.2 DCDU-12C
A direct current distribution unit-12C (DCDU-12C) is 1 U high and provides DC power input
for all components in the cabinet.

Exterior
Figure 3-11 shows the DCDU-12C.
Figure 3-11 Front view of a DCDU-12C

(1) DC input terminal

(2) DC output terminal

(3) Spare fuse box

(4) Ground point

Functions
The DCDU-12C provides ten -48 V DC outputs using same fuse configurations to meet the
power distribution requirements of distributed and separated base stations
Table 3-10 describes the DC power distribution functions of a DCDU-12C.
Table 3-10 DC power distribution functions of a DCDU-12C
DCDU Type

DC output
ports

PowerConsuming
Device

Specificatio
n of the
Fuse

Remarks

DCDU-12C

LOAD0

Transmission
device

30 A

LOAD1

Transmission
device

l BTS3900A (-48
V)
l Transmission
cabinet

LOAD2

Transmission
device

LOAD3

Transmission
device

LOAD4

Transmission
device

LOAD5

Transmission
device

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

77

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

DCDU Type

3 TMC11H Product Description

DC output
ports

PowerConsuming
Device

LOAD6

BBU or
transmission
device

LOAD7

BBU or
transmission
device

LOAD8

EMUA or
transmission
device

LOAD9

Fan assembly

Specificatio
n of the
Fuse

Remarks

Ports
Figure 3-12 shows the ports on the DCDU-12C panel.
Figure 3-12 Ports on the DCDU-12C panel

Table 3-11 describes the ports on the DCDU-12C panel.


Table 3-11 Ports on the DCDU-12C panel
N
o.

Port

Silkscreen

Matched Terminal
and Cable

Remarks

(1)

DC input
terminals

NEG(-)

Two one-hole OT
terminals (M6). The
cross-sectional area

Negative power input wiring


terminal

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

78

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

N
o.

Port

(2)

Fuse
block

3 TMC11H Product Description

Silkscreen

Matched Terminal
and Cable

Remarks

RTN(+)

of the cable is 25
mm2 (0.039) by
default.

Positive power input wiring


terminal

LOAD0 to
LOAD9

It controls ports LOAD0 to


LOAD9, and therefore controls
the power supplies to the BBU,
fan assemblies, and
transmission equipment.
The indicator on the fuse block
indicates the status of the fuse.
l When the indicator is steady
on, the fuse is faulty and
needs to be replaced.
l When the indicator is steady
off, the fuse is working
properly.

DC
output
ports

(3)

LOAD0 to
LOAD9

Figure 3-13 shows


an EPC4/EPC6
connector, which
applies to any one
among ports LOAD0
to LOAD9. The
maximum crosssectional area of the
cable is 4 mm2 (0.006
in.2).

For the specifications of the DC


output, see Table 3-10.

NOTE

Fuse blocks and DC output terminals are jointly called fuse terminal blocks.

Figure 3-13 Exterior of an EPC4 or EPC6 connector

Technical Specifications
Table 3-12 lists the technical specifications of a DCDU-12C.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

79

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Table 3-12 Technical specifications of a DCDU-12C


Item

Specifications

Dimensions (H x W x D)

The DCDU-12C is 1 U high and can be


installed in a 19-inch cabinet or rack. Its
dimensions are as follows:
l 42 mm x 442 mm x 65 mm (1.65 in. x 17.4
in. x 2.56 in.) (without mounting ears)
l 42 mm x 482.6 mm x 65 mm (1.65 in. x
19 in. x 2.56 in.) (with mounting ears)
-48 V DC power port, 10 kA (8/20 s)
differential mode

Surge Protection Specifications

-48 V DC power port, 20 kA (8/20 s)


common mode

3.5.3 Fan Assembly


A fan assembly consists of the fan subrack, fans, and central monitoring unit type EA (CMUEA).
Figure 3-14 shows the exterior of a fan assembly.
Figure 3-14 Exterior of a fan assembly

(1) Fan subrack

(2) Fan

(3) CMUEA

For details about the ports and indicators on the CMUEA, see 4.4.2 Central Monitoring Unit
Type EA (CMUEA).

3.5.4 Filler Module


A filler module is a 1-U high standard plastic component. If any BBU is installed in the cabinet,
filler modules must be configured in the reserved customer space below the BBU to improve
the dissipation capability of the cabinet.

Exterior
Figure 3-15 shows the exterior of a filler module.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

80

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-15 Exterior of a filler module

Functions
The filler module is installed in the customer space below the BBU to prevent the heat reflux in
the empty space below the BBU.
NOTE

In the APM30H and TMC11H, the filler module is configured in the customer space by default. Before
installing other modules, remove the filler module. For details about removing a filler module, see chapter
"Installing Optional Modules" in the BTS3900A (Ver.D1) Installation Guide.

3.5.5 Junction Box


Both APM30H and TMC11H are configured with a junction box, which feeds power into the
heater or heating film.
NOTE

l The EPU subrack feeds power into the junction box in the APM30H. The power is divided into four
AC power outputs, which are then provided for the heater in the cabinet or heating film in the
IBBS200D.
l The junction box in the APM30H feeds power into the junction box in the TMC11H. The power is
divided into four AC power outputs, which are then provided for the heater or service outlet unit (SOU)
in the cabinet.

Exterior
The junction box is installed on the inside of the left wall of the APM30H or TMC11H. Figure
3-16 shows the position and exterior of the junction box in the APM30H.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

81

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-16 Exterior of the junction box

Structure
Figure 3-17 shows the structure of the junction box.
Figure 3-17 Structure of the junction box

(1) Four AC output L wiring


terminals

(2) Four AC output N wiring


terminals

(3) Four AC output PE wiring


terminals

(4) Cable holes

(5) AC input N wiring terminal

(6) AC input L wiring terminal

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

82

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

3.5.6 ELU
The electronic label unit (ELU) reports the cabinet type automatically to facilitate
troubleshooting.
The ELU is installed on the inside of the right wall of the APM30H/TMC11H/RFC or the inside
of the left wall of the IBBS200D/IBBS200T. Figure 3-18 shows the position and exterior of an
ELU on the inside of the right wall of the APM30H or the inside of the left wall of the IBBS200D.
Figure 3-18 Exterior of an ELU

(1) Shell

(2) RJ45 port

3.5.7 Door Status Sensor


The door status sensor monitors whether the cabinet door is open.
The door status sensor consists of the magnets and switch. Figure 3-19 shows the exterior of a
door status sensor.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

83

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-19 Exterior of a door status sensor

3.5.8 (Optional) AC Heater


The AC heater ensures that components in the cabinet work within the acceptable temperature
range when the surrounding temperature is low. The AC heater is optional.

Exterior
An AC heater is a device with a height of 1 U. Figure 3-20 shows the exterior of an AC heater.
Figure 3-20 Exterior of an AC heater

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

84

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Technical Specifications
The technical specifications of an AC heater are as follows:
l

When the temperature is lower than 1oC6oC in the cabinet, the heater starts working. When
the temperature is higher than 15oC3oC in the cabinet, the heater stops working.

The rated power of the heater is 300 W.

3.5.9 (Optional) SOU


A service outlet unit (SOU) transfers AC power to equipment. The SOU is optionally installed
in the customer space in the APM30H or TMC11H.

Exterior
An SOU is a device with a height of 1 U. Figure 3-21 shows the exterior of an SOU.
Figure 3-21 Exterior of an SOU

(1) Input power port

(2) Breaker

(3) Socket (European standard)

The SOU can be configured with sockets from different countries. The sockets can be classified
into sockets complying with North American standard, European standard, Universal standard,
and British standard, as shown in Figure 3-22.
Figure 3-22 Different types of sockets

Technical Specifications
Table 3-13 lists the technical specifications of an SOU.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

85

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Table 3-13 Technical specifications of an SOU


Item

Technical Specifications

Dimensions (H x W x D)

482.6 mm91 mm55 mm (19 in. x 3.58 in.


x 2.17 in.)

Weight

1.5 kg (3.31 lb)

Input voltage range

200 V AC to 240 V AC

Maximum input current

10 A

Output voltage range

200 V AC to 240 V AC

Maximum output current

10 A

Working frequency

50 Hz or 60 Hz

Operating temperature

-40oC to +55oC (-40oF to +131oF)

Altitude

4000 m (13123.36 ft)


NOTE
From the altitude of 3000 m (9842.52 ft), the
maximum operating temperature drops by 1oC
(33.8oF) each time the altitude increases by 100 m
(328.08 ft).

Protection level

IP20

3.6 TMC11H Cables


This chapter describes the equipotential cables, power cables, and signal cables in a TMC11H.

3.6.1 Cable List


The TMC11H cables mainly consist of the equipotential cables, power cables, and signal cables.

Equipotential cables and power cables


Table 3-14 describes the equipotential cables and power cables.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

86

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Table 3-14 Equipotential cables and power cables


Categ
ory

Cable

Cables
to be
install
ed
onsite

Cables
install
ed
before
deliver
y

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

Input Power
Cable for a
TMC11H (AC
scenario)

EPC4 or
EPC6
connector

LOAD7 port
on the EPU

OT terminal

RTN(+) and
NEG(-) ports
on the INPUT
in the
DCDU-12C

Input Power
Cable for a
Junction Box
(TMC11H)

OT terminal

L3 and N3 on
the junction
box in the
APM30H

OT terminal

L and N on the
junction box in
the TMC11H

Input Power
Cable for a
Junction Box
(-48 V DC
scenario)

C13
connector

Input power
port on the AC
heater

Depends on
the external
power device

External
power device

3.6.4
Equipotential
Cable

OT terminal

Ground bar in
the upper
cabinet

OT terminal

Ground bar in
the lower
cabinet

DCDU-12B
Input Power
Cable

OT terminal

RTN(+) and
NEG(-) ports
on the INPUT
in the
DCDU-12B

Depends on
the external
power device

External
power device

Power Cables
for a Fan
Assembly

EPC4 or
EPC6
connector

LOAD9 port
on the
DCDU-12C

3V3
connector

PWR port on
the fan
assembly in
the TMC11H

Power Cable
for an AC
Heater

OT terminal

L0, N0, and


ground bar in
the junction
box in the
TMC11H

C13
connector

Input power
port on the AC
heater

Input Power
Cable for a
TMC11H (-48
V DC scenario)

OT terminal

Junction box
in the RFC

OT terminal

RTN(+) and
NEG(-) ports
on the INPUT
in the
DCDU-12B

NOTE

The connection of the optional power cables depends on the delivery mode. Table 3-14 describes the power
cables in a macro base station.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

87

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Signal Cables
Table 3-15 describes the signal cables.
Table 3-15 Signal cables
Categ
ory

Cable

Cables
to be
install
ed
onsite

Cables
install
ed
before
deliver
y

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

Monitoring
Signal
Cable
Between
Cascaded
CMUEAs

RJ45
connector

COM_OUT port
on the CMUEA in
the upper cabinet
(TMC,
IBBS200D,
IBBS200T, or
RFC)

RJ45
connector

COM_IN port on
the CMUEA in the
lower cabinet
(TMC, IBBS200D,
IBBS200T, or
RFC)

ELU Signal
Cable

RJ45
connector

ELU

RJ45
connector

ELU port in the


CMUEA

Monitoring
Signal
Cable for a
Door Status
Sensor

Bare wire

CMUEA/GATE

Bare wire

Door status sensor

Monitoring
Signal
Transfer
Cable for
the Fan on
the Front
Door

Interconne
ction
terminal

Interconnection
terminal on the
front door of the
TMC11H

4-pin
connector

FAN_EXT port on
the CMUEA

3.6.2 TMC11H Cable Connections


This chapter describes the principles for connecting power cables and signal cables in a
TMC11H.

TMC11H Power Cable Connections


The section provides a figure showing the TMC11H power cable connections.
Figure 3-23 shows the power cable connections in a TMC11H.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

88

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-23 Power cable connections in a TMC11H

(1) Power cable for a fan assembly in a TMC11H

(2) Power cable for an AC heater

(3) Input power cable for a TMC11H

Signal Cable Connections in a TMC11H


This section describes the signal cable routing for a TMC11H.
Figure 3-24 shows the signal cable connections in a TMC11H.
Figure 3-24 Signal cable connections in a TMC11H

(1) Monitoring signal cable for the fans on the front


door

Issue Draft A (2012-9-15)

(2) Monitoring signal transfer cable for the fans on the


front door

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

89

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

(3) ELU signal cable

(4) Monitoring signal cable for the door status sensor

3.6.3 PGND Cable


A PGND cable connects a cabinet to a ground bar, which provides ground protection for the
cabinet. The maximum length of a PGND cable is 30 m (98.43 ft).

Exterior
Figure 3-25 shows the exterior of a PGND cable.
NOTE

When the 110 V AC dual-live-wire power is supplied for the cabinet, a green PGND cable is used.

Figure 3-25 Exterior of a PGND cable

(1) OT terminal

Cable Description
Table 3-16 describes a PGND cable.
Table 3-16 PGND cable
Cable

Color

Cross-Sectional Area of the Core Wire and


Size of the OT Terminal

PGND cable

Green and yellow

M6, 16 mm2 (0.025 in.2)

3.6.4 Equipotential Cable


An equipotential cable connects the PGND terminals of two cabinets. It ensures equipotential
bonding between the cabinets and the safe operation of base stations.

Exterior
Figure 3-26 shows the exterior of an equipotential cable.
NOTE

When the 110 V AC dual-live-wire power is supplied for the cabinet, a green equipotential cable is used.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

90

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-26 Exterior of an equipotential cable

(1) OT terminal

Cable Description
Table 3-17 describes an equipotential cable.
Table 3-17 Equipotential cable
Cable

Color

Cross-Sectional Area of the Core Wire and


Size of the OT Terminal

Equipotential cable
between cabinets

Green and yellow

M6, 16 mm2 (0.025 in.2)

3.6.5 Power Cables


This chapter describes all power cables in a TMC11H.

Input Power Cable for a TMC11H


The type of the input power cable for a TMC11H depends on the power supply to the TMC11H.

Input Power Cable for a TMC11H (1)


In the BTS3900A or DBS3900 with AC power, a TMC11H is powered by the APM30H, and
the maximum length of the input power cable is 15 m (49.21 ft) or 10 m (32.81 ft). Figure
3-27 shows the exterior of the input power cable for a TMC11H.
Figure 3-27 Input power cable for a TMC11H (1)

(1) EPC4 or EPC6 connector

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

(2) OT terminal

91

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Table 3-18 lists the specifications of the cable.


Table 3-18 Specifications of the input power cable for a TMC11H (1)
Cable

Wire

Wire Color

Cross-Sectional Area of
the Core Wire and Size of
the OT Terminal

Input power cable


for a TMC11H (1)

RTN(+)

Black

M6, 4 mm2 (0.006 in.2)

NEG(-)

Blue

Input Power Cable for a TMC11H (2)


In the -48 input BTS3900A, if a TMC11H is powered by the RFC, the maximum length of the
input power cable is 15 m (49.21 ft). Figure 3-28 shows the exterior of the input power cable
for a TMC11H.
Figure 3-28 Input power cable for a TMC11H (2)

(1) OT terminal

Table 3-19 lists the specifications of the cable.


Table 3-19 Specifications of the input power cable for a TMC11H (2)
Cable

Wire

Wire Color

Cross-Sectional Area of
the Core Wire and Size of
the OT Terminal

Input power cable


for a TMC11H (2)

RTN(+)

Black

M6, 25 mm2 (0.039 in.2)

NEG(-)

Blue

Input Power Cable for a TMC11H (3)


In the DBS3900 using -48 V DC power, if a TMC11H is powered by the external power device,
the maximum length of the input power cable is 10 m (32.81 ft). Figure 3-29 shows the exterior
of the input power cable for a TMC11H.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

92

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-29 Input power cable for a TMC11H (3)

(1) OT terminal

Table 3-20 lists the specifications of the cable.


Table 3-20 Specifications of the input power cable for a TMC11H (3)
Cable

Wire

Wire Color

Cross-Sectional Area of
the Core Wire and Size of
the OT Terminal

Input power cable


for a TMC11H (3)

RTN(+)

Black

NEG(-)

Blue

M6, one input: 35 mm2


(0.054 in.2), two inputs: 16
mm2 (0.025 in.2)

Input Power Cable for a TMC11H (4)


When the TMC11H is used as a transmission cabinet, the specifications of its power cable are
as follows:
In the BTS3900A or DBS3900 using -48 V DC power, if a TMC11H is powered by the external
power device, the maximum length of the input power cable is 15 m (49.21 ft) or 10 m (32.81
ft). Figure 3-30 shows the exterior of the input power cable for a TMC11H.
Figure 3-30 Input power cable for a TMC11H (4)

(1) OT terminal (M6, 4 mm2 or 0.006 in.2)

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

93

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

DCDU-12B Input Power Cable


A DCDU-12B input power cable feeds DC power into a DCDU-12B from external power
devices.

DCDU-12B Used in Distributed Base Stations


l

When AC power is used, the DCDU-12B is installed in an APM30H and obtains power
from the RFC1 output port. The maximum length of a DCDU-12B input power cable is
1.5 m (4.92 ft). Figure 3-31 shows the exterior and Table 3-21 describes the specifications
of a DCDU-12B input power cable.

When DC power is used, the second DCDU-12B is installed in a TMC11H and obtains
power from external power devices. The maximum length of a DCDU-12B power cable is
10 m (32.81 ft). Figure 3-32 shows the exterior and Table 3-22 describes the specifications
of a DCDU-12B input power cable.

Figure 3-31 DCDU-12B input power cable (1)

(1) OT terminal

Table 3-21 Specifications of a DCDU-12B input power cable (1)


Cable

Wire

Wire Color

Cross-Sectional Area of
the Core Wire and Size of
the OT Terminal

DCDU-12B input
power cable (1)

RTN(+)

Black

M6, 25 mm2 (0.039 in.2)

NEG(-)

Blue

Figure 3-32 DCDU-12B input power cable (2)

(1) OT terminal

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

94

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Table 3-22 Specifications of a DCDU-12B input power cable (2)


Cable

Wire

Wire Color

Cross-Sectional Area of
the Core Wire and Size of
the OT Terminal

DCDU-12B input
power cable (2)

RTN(+)

Black

NEG(-)

Blue

M6, one input: 35 mm2


(0.054 in.2), two inputs: 16
mm2 (0.025 in.2)

DCDU-12B Used in Separated Macro Base Stations


l

When AC power is used, the DCDU-12B is installed in an RFC and obtains power from
the RFC2 output port in an APM30H. The maximum length of a DCDU-12B input power
cable is 1.5 m (4.92 ft). Figure 3-31 shows the exterior and Table 3-21 describes the
specifications of a DCDU-12B input power cable.

When DC power is used, the second DCDU-12B is installed in a TMC11H and obtains
power from external power devices. The maximum length of a DCDU-12B power cable is
15 m (49.21 ft). Figure 3-32 shows the exterior and Table 3-22 describes the specifications
of a DCDU-12B input power cable.

Power Cable for an AC Heater


The power cable for an AC heater feeds AC input power into the AC heater from the junction
box. If a heater is configured in the -48 V DC input scenario, one more AC power input must
be added for the heater. In this case, the maximum length of the power cable for the heater is 15
m (49.21 ft).

Exterior
Figure 3-33 shows the exterior of the power cable for an AC heater.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

95

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-33 Exterior of the power cable for an AC heater

(1) C13 connector

(2) OT terminal (M4, 1.5 mm2 or 0.002 in.2)

Cable Description
Table 3-23 describes the wires of the power cable for an AC heater.
Table 3-23 Wires of the power cable for an AC heater
Wire
Number

Color

Connector

Label

W1

Brown

OT terminal

W2

Green and
yellow

OT terminal

PE

W3

Blue

OT terminal

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and areas. If cables
are purchased at local markets, the cables must comply with local rules and regulations.

Power Cables for a Fan Assembly


The power cable for a fan assembly feeds -48 V DC power into the fan assembly.

Exterior
Figure 3-34 shows the exterior of the power cable for a fan assembly.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

96

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-34 Exterior of the power cable for a fan assembly

(1) 3V3 connector

(2) EPC4 or EPC6 connector

Cable Description
Table 3-24 describes the wires of the power cable for a fan assembly.
Table 3-24 Wires of the power cable for a fan assembly
Cable

Wire

Wire Color

Power cables for a fan


assembly

RTN(+)

Black

NEG(-)

Black

Input Power Cable for a Junction Box


The input power cable for a junction box feeds AC input power from the AC power system into
the junction box. The junction box provides four AC power outputs for the heater or heating
film.

Exterior
Figure 3-35 shows the exterior of an input power cable for a junction box.
Figure 3-35 Input power cable for a junction box

(1) OT terminal (M4, 1.5 mm2 or 0.002 in.2)

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

97

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Cable Description
Table 3-25 describes the wires of an input power cable for a junction box.
Table 3-25 Wires of an input power cable for a junction box
Wire
Number

Color

One End

The Other End

Label

W1

Brown

X1

X3

W2

Blue

X2

X4

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and areas. If cables
are purchased at local markets, the cables must comply with local rules and regulations.

3.6.6 Signal Cables


This chapter describes all signal cables in a TMC11H.

ELU Signal Cable


The electronic label unit (ELU) signal cable is used by the ELU to report the cabinet type to the
central monitoring unit type EA (CMUEA).

Exterior
Figure 3-36 shows the exterior of an ELU signal cable.
Figure 3-36 Exterior of an ELU signal cable

(1) RJ45 connector

Cable Description
Table 3-26 describes the pin assignment for the wires of an ELU signal cable.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

98

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Table 3-26 Pin assignment for the wires of an ELU signal cable
X1 End

X2 End

Color

Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

X1.3

X2.3

White

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Twisted pair

Twisted pair

Twisted pair

Monitoring Signal Cable for a Door Status Sensor


The monitoring signal cable for a door status sensor is used to inform the central monitoring
unit type EA (CMUEA) of the door status obtained from the door status sensor in the TMC11H,
RFC, IBBS200D, or IBBS200T.

Exterior
There are two wires in the monitoring signal cable for a door status sensor, both of which have
a bare wire at each end, as shown in Figure 3-37.
Figure 3-37 Exterior of the monitoring signal cable for a door status sensor

Monitoring Signal Transfer Cable for the Fan on the Front Door
The monitoring signal transfer cable for the fan on the front door feeds power to the fan on the
front door in the APM30H or TMC11H and reports fan monitoring signals to the central
monitoring unit type EA (CMUEA).

Exterior
Figure 3-38 shows the exterior of the monitoring signal transfer cable for the fan on the front
door.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

99

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-38 Exterior of the monitoring signal transfer cable for the fan on the front door

(1) 4-pin connector

(2) Interconnection terminal

Cable Description
Table 3-27 shows the pin assignment for the wires of the monitoring signal transfer cable for
the fan on the front door.
Table 3-27 Pin assignment for the wires of the monitoring signal transfer cable for the fan on
the front door
Cable

X1 End

X2 End

Color

W1

X1.1

X2.1

Black

W2

X1.2

X2.2

Black

W3

X1.3

X2.3

Black

W4

X1.4

X2.4

Black

Monitoring Signal Cable Between Cascaded CMUEAs


Monitoring signal cable between cascaded central monitoring unit type EA (CMUEA) boards
connects the CMUEAs in two cabinets and reports the RS485 signals from the CMUEA in the
lower-level cabinet to the BBU through the CMUEA in the upper-level cabinet. The monitoring
signal cable is 5 m (16.40 ft) long.

Exterior
The monitoring signal cable is black and has an RJ45 connector at each end, as shown in Figure
3-39.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

100

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

3 TMC11H Product Description

Figure 3-39 Exterior of a monitoring signal cable

(1) RJ45 connector

Cable Description
Table 3-28 describes the pin assignment for the wires of a monitoring signal cable.
Table 3-28 Pin assignment for the wires of a monitoring signal cable
X1 End

X2 End

Description

X1.1

X2.1

Twisted pair

X1.2

X2.2

X1.3

X2.3

X1.6

X2.6

X1.4

X2.4

X1.5

X2.5

X1.7

X2.7

X1.8

X2.8

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Twisted pair

Twisted pair

Twisted pair

101

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

IBBS200D Product Description

About This Chapter


This chapter describes the exterior, functions, technical specifications, application scenarios,
structure, components, and cables of the IBBS200D.
4.1 IBBS200D Description
The IBBS200D is a battery cabinet using natural ventilation. The IBBS200D uses fans to
dissipate heat from the cabinet and can provide backup power to the APM30H.
4.2 Technical Specifications of an IBBS200D
The technical specifications of an IBBS200D consist of electrical specifications, engineering
specifications, and environmental specifications.
4.3 IBBS200D Structure
The IBBS200D uses a modular and integrated structure. The power distribution equipment is
installed on the inside of the upper right wall of the cabinet, and the monitoring equipment is
installed inside the cabinet door.
4.4 IBBS200D Components
An IBBS200D consists of the fan mounting frame, central monitoring unit type EA (CMUEA),
power distribution box, batteries, heating film, electronic label unit (ELU), and door status
sensor.
4.5 IBBS200D Cables
This chapter describes the PGND cables, equipotential cables, power cables, and signal cables
in an IBBS200D.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

102

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

4.1 IBBS200D Description


The IBBS200D is a battery cabinet using natural ventilation. The IBBS200D uses fans to
dissipate heat from the cabinet and can provide backup power to the APM30H.

Exterior of an IBBS200D
Dimensions of an IBBS200D (H x W x D): 700 mm x 600 mm x 480 mm (27.56 in. x 23.62 in.
x 18.90 in.) (not including the base).
Figure 4-1 shows the exterior of an IBBS200D.
Figure 4-1 Exterior of an IBBS200D

Functions of an IBBS200D
Table 4-1 describes the functions of an IBBS200D.
Table 4-1 Functions of an IBBS200D
Item

Description

Backup power

Configured with 48 V 92 Ah battery group to provide up to 48 V 92 Ah


backup power. 48 V 184 Ah DC backup power is provided if two battery
groups are configured.

Reporting the
cabinet type
automatically

The electronic label unit (ELU) reports the cabinet type automatically.

Built-in fan

The fan promotes the inner and outer air circulation of the cabinet to ensure
that the cabinet work within an acceptable temperature range.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

103

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Item

Description

Central
monitoring

The central monitoring unit type EA (CMUEA) collects the alarm signals
from the door status sensor, smoke sensor, fans, and temperature sensor for
the battery cabinet, and reports these alarm signals to the base station.

NOTE

Two stacked battery cabinets provide up to 48 V 368 Ah backup power.

4.2 Technical Specifications of an IBBS200D


The technical specifications of an IBBS200D consist of electrical specifications, engineering
specifications, and environmental specifications.

Electrical Specifications of an IBBS200D


Table 4-2 describes the electrical specifications of an IBBS200D.
Table 4-2 Electrical specifications of an IBBS200D
Item

Specifications

Input voltage range

-38.4 V DC to -57 V DC

Maximum capacity of the


batteries

48 V, 184 Ah

Heat dissipation in the cabinet

The temperature rise in the battery cabinet must be lower


than 5oC (41oF).

Engineering Specifications of an IBBS200D


Table 4-3 describes the engineering specifications of an IBBS200D.
Table 4-3 Engineering specifications of an IBBS200D
Item

Specifications

Remarks

Cabinet weight

40 kg (88.18 lb)

Configured with monitoring


boards, power distribution box,
and cables only.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

104

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Item

Specifications

Remarks

Battery Weight

12 V 92 Ah battery: 33.5 kg (73.85


lb)

The total capacity can be expanded


to 48 V 184 Ah (two groups of 48
V 92 Ah batteries)

NOTE
Batteries from different
manufacturers have different
specifications. The above
specifications are from the commonly
used batteries.

Dimensions of the
cabinet (H x W x
D)

700 mm x 600 mm x 480 mm


(27.56 in. x 23.62 in. x 18.90 in.)

Dimensions of the
base (H x W x D)

200 mm x 600 mm x 434 mm (7.87


in. x 23.62 in. x 17.09 in.)

Installation mode

When installed on the ground, it


can be located under the TMC11H
or APM30H.

In stack mode, the IBBS200D must


be installed under the TMC11H or
APM30H.

Environmental Specifications of an IBBS200D


The IBBS200D can be used outdoors. Table 4-4 describes the environmental specifications of
an IBBS200D.
Table 4-4 Environmental specifications of an IBBS200D
Item

Specifications

Remarks

Operating
temperatur
e

-40oC to + 40oC (-40oF to +104oF)

Heating films must be used in cold


areas.

Relative
humidity

5% RH to 100% RH

Altitude

-60 m to 4000 m (-196.85 ft to


13123.36 ft)

From the altitude of 1800 m (5905.51


ft), the maximum operating
temperature drops by 1oC (33.8oF)
each time the altitude increases by 220
m (721.78 ft).

Wind
speed

67 m/s

Storage
temperatur
e

-40oC to + 70oC (-40oF to +158oF)

Dustproof
and
waterproof

IP34

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

105

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Item

Specifications

Remarks

Noise

Meeting the ETS 300 753 4.1E


standard (rural level)

4.3 IBBS200D Structure


The IBBS200D uses a modular and integrated structure. The power distribution equipment is
installed on the inside of the upper right wall of the cabinet, and the monitoring equipment is
installed inside the cabinet door.
Figure 4-2 describes the interior of an IBBS200D.
Figure 4-2 Interior of an IBBS200D

Table 4-5 describes the configurations of an IBBS200D.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

106

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Table 4-5 Configurations of an IBBS200D


No
.

Module

Option
al/
Manda
tory

Max
imu
m
Qua
ntit
y
Con
figu
red
in a
Sin
gle
Cab
inet

Remarks

Fan mounting
frame

Mandat
ory

The fan mounting frame is installed on the front


door of the cabinet, and configured with a fan.

Central
monitoring
unit type EA
(CMUEA)

Mandat
ory

The CMUEA provides the following functions:


temperature control, Boolean alarm detection, and
ELU identification of the cabinet.

Electronic
label unit
(ELU)

Mandat
ory

The ELU reports the cabinet type automatically to


facilitate troubleshooting.

Storage
battery

Mandat
ory

The storage batteries provide long-duration


backup power for a base station.

Power
distribution
box

Mandat
ory

The power distribution box is installed on the


inside of the upper right wall of the cabinet. It
transfers and distributes power to the TEC or FAN
unit and storage batteries.

Door status
sensor

Mandat
ory

The door status sensor monitors whether the


cabinet door is open.

Heating film

Optiona
l

The IBBS200D must be configured with a heating


film in cold areas. The heating film is not required
in general areas.

Junction
terminal for
the input
power cable of
the heating
film

Mandat
ory

The junction terminal provides the input power


port for the heating film

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

107

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

4.4 IBBS200D Components


An IBBS200D consists of the fan mounting frame, central monitoring unit type EA (CMUEA),
power distribution box, batteries, heating film, electronic label unit (ELU), and door status
sensor.

4.4.1 Fan Mounting Frame


The fan mounting frame is installed on the front door of the cabinet, and configured with a fan.
The fan can dissipate heat from a cabinet, and is delivered with signal cables.

Exterior
Figure 4-3 shows the exterior of a fan mounting frame. The fan promotes the inner and outer
air circulation of the cabinet to ensure that the cabinet work within an acceptable temperature
range. This allows the batteries to work properly.
Figure 4-3 Exterior of a fan mounting frame

Figure 4-4 shows the exterior of a signal cable delivered with a fan.
Figure 4-4 Signal cable delivered with a fan

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

108

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

NOTE

The signal cable delivered with a fan feeds power into the fan and monitors the fan.

Cable Description
Table 4-6 describes the pin assignment for the wires of the signal cable delivered with a fan.
Table 4-6 Pin Assignment
Wire

A
End

Color

Remarks

W1

A.1

Red

Connected to the positive power cable

W2

A.2

Yello
w

Importing PWM speed-adjusting signals

W3

A.3

Blue

Exporting alarm or speed signals

W4

A.4

Black

Connected to the negative power cable

NOTE

The color of the signal cable delivered with a fan depends on the manufacturer.

4.4.2 Central Monitoring Unit Type EA (CMUEA)


The central monitoring unit type EA (CMUEA) mainly monitors the fans, heater, and cabinet
temperature. The CMUEA can be used in an AMP30H, RFC, TMC11H, IBBS200D, or
IBBS200T.

Exterior
Figure 4-5 shows the exterior of a CMUEA.
Figure 4-5 Exterior of a CMUEA

Ports
Figure 4-6 shows the ports on a CMUEA.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

109

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Figure 4-6 Ports on a CMUEA

Table 4-7 describes the ports on a CMUEA.


Table 4-7 Ports on a CMUEA
No
.

Port

Remarks

(1)

TEMP2

Reserved port, connected to the temperature sensor

(2)

WATER

Connected to the water sensor

(3)

IFAN4

Connected to the inner circulation fan for the cabinet

(4)

IFAN3

Connected to the inner circulation fan for the cabinet

(5)

IFAN2

Connected to the inner circulation fan for the cabinet

(6)

IFAN1

Connected to the inner circulation fan for the cabinet

(7)

TEC

Connected to the TEC cooler to receive alarms related to the TEC cooler

(8)

TEMP1

l In the RFC, this port is connected to the temperature sensor at the air
intake vent of the cabinet to receive temperature alarms.
l In the IBBS200D or IBBS200T, this port is connected to the
temperature sensor to receive battery temperature alarm signals.

(9)

COM_OUT

RS485 signal port. It communicates with lower-level cascading ports


and reports monitoring information.
l In the APM30H, this port is connected to the PMU.
l In the RFC, TMC11H, or IBBS200D/IBBS200T, this port is
connected to the lower-level CMUEA.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

110

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

No
.

Port

Remarks

(10
)

COM_IN

RS485 signal port. It communicates with upper-level cascading ports


and reports monitoring information.
l In the APM30H, this port is connected to the BBU.
l In the RFC or TMC11H, this port is connected to the BBU or an
upper-level CMUEA.
l In the IBBS200T, this port is connected to the PMU or upper-level
CMUEA.

(11
)

RUN
indicator

Indicating the running status of the fans

(12
)

ALM
indicator

Indicating the alarm status of the fans

(13
)

ELU

Port connected to the ELU to report the cabinet type

(14
)

GATE

Boolean signal port connected to the door status sensor

(15
)

IN0, IN1,
and IN2

Reserved Boolean signal port

(16
)

SMOKE

Boolean signal port connected to the smoke sensor

(17
)

EFAN1

Connected to the outer circulation fan for the cabinet

(18
)

EFAN2

Connected to the outer circulation fan for the cabinet

(19
)

PWR

Power input port providing DC power input for the board

Indicators
Table 4-8 describes the indicators on the CMUEA.
Table 4-8 Indicators on the CMUEA
Silkscr
een

Color

Status

Meaning

RUN

Green

Blinking (on for 1s and


off for 1s)

The board is functional and communicating


with the BBU properly.

Blinking (on for 0.125s


and off for 0.125s)

The board is functional but fails to


communicate with the BBU or the board is
not registered.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

111

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Silkscr
een

ALM

Color

Red

4 IBBS200D Product Description

Status

Meaning

Steady on

The board is in the power-on self-check


status.

Steady off

The board is faulty.

Steady off

No alarm has been reported.

Steady on

Alarms are generated, and the board must be


replaced.

Blinking (on for 1s and


off for 1s)

An alarm is generated, and the alarm may be


caused by an associated board or port fault.
Therefore, you need to locate the fault before
determining whether to replace the board.

DIP Switch
On the CMUEA, there is a DIP switch J18, which is used to set the working mode of the CMUEA
according to the cabinet type. Figure 4-7 shows the position of a DIP switch on the CMUEA.
Figure 4-7 Position of a DIP switch on the CMUEA

In different types of cabinet, the DIP switch on the CMUEA is set in different ways, as shown
in Figure 4-8.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

112

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Figure 4-8 DIP switch setting on the CMUEA in different cabinets

NOTE

The white boxes indicate the positions of all bits in the DIP switch.

4.4.3 Power Distribution Box


The power distribution box is installed on the inside of the upper right wall of the cabinet, which
controls the two battery groups separately and controls the DC power supply to the fan assembly
or TEC.

Exterior
Figure 4-9 shows the exterior of a power distribution box.
Figure 4-9 Exterior of a power distribution box

Ports
Table 4-9 describes the ports on the power distribution box.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

113

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Table 4-9 Ports on the power distribution box


No.

Silkscreen

Module

Remarks

(1)

BAT

Input power
cable port for
batteries

It supports a one-hole OT terminal (M8)


installed on a cable with a cross-sectional area
of 35 mm2 (0.054 in.2).

(2)

BAT_SW0

Circuit breaker
for the upper
batteries

It controls the cable of the upper batteries in the


cabinet. The circuit breaker requires 250 A
current.

(3)

FAN/
TEC_OUTPU
T

Power output
port for a fan
assembly or
TEC

EPC4 connector, which requires 30 A current.

(4)

BAT_SW1

Circuit breaker
for the lower
batteries

It controls the power supply to the lower


batteries in the cabinet. The circuit breaker
requires 250 A current.

(5)

BAT

Input power
cable port for
batteries

It supports a one-hole OT terminal (M8)


installed on a cable with a cross-sectional area
of 35 mm2 (0.054 in.2).

(6)

FAN/
TEC_INPUT

Power input port


for a fan
assembly or
TEC

EPC4 connector, which requires 30 A current.

Outer Structure
Figure 4-10 shows the outer structure of a power distribution box.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

114

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Figure 4-10 Outer structure of a power distribution box

(1) RTN(+) cable for the upper


batteries

(2) Power transfer cable for a TEC or (3) NEG(-) wire for the lower
fan assembly
batteries

(4) NEG(-) wire for the upper


batteries

(5) RTN(+) wire for the lower


batteries

4.4.4 Storage Battery


This section describes the exterior, technical specifications, and configurations of the storage
batteries.
NOTE

Storage batteries from different manufacturers differ in exterior and technical specifications. In this section, a
12 V 92 Ah storage battery is described.

Exterior
Figure 4-11 shows the exterior of a 12 V 92 Ah storage battery.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

115

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Figure 4-11 12 V 92 Ah storage battery

Configurations
The cabinet supports two types of storage battery groups: 48 V 92 Ah and 48 V 184 Ah.
l

Two 48 V 92 Ah storage battery groups are connected in parallel and serve as a 48 V 184
Ah storage battery group.

Each group consists of four storage batteries.

Technical Specifications
Table 4-10 describes the technical specifications of a 12 V 92 Ah storage battery.
Table 4-10 Technical specifications of a 12 V 92 Ah storage battery
Battery Type

Dimensions of a Battery
(H x W x D)

Battery Weight

12 V 92 Ah

287 mm x 105 mm x 390 mm


(11.30 in. x 4.13 in. x 15.35
in.)

33.5 kg (73.85 lb)

287 mm x 108 mm x 393 mm


(11.30 in. x 4.25 in. x 15.47
in.)

35 kg (73.85 lb)

4.4.5 ELU
The electronic label unit (ELU) reports the cabinet type automatically to facilitate
troubleshooting.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

116

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

The ELU is installed on the inside of the right wall of the APM30H/TMC11H/RFC or the inside
of the left wall of the IBBS200D/IBBS200T. Figure 4-12 shows the position and exterior of an
ELU on the inside of the right wall of the APM30H or the inside of the left wall of the IBBS200D.
Figure 4-12 Exterior of an ELU

(1) Shell

(2) RJ45 port

4.4.6 Heating Film


This section describes the functions, exterior, and technical specifications of a heating film. The
heating film is optional.
NOTE

An IBBS200D has two heating films, which are installed on the upper and lower pallets, respectively.

Exterior
Figure 4-13 shows the exterior of the heating film.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

117

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Figure 4-13 Exterior of the heating film

Functions
The heating film functions in the low-temperature environment to provide the suitable storage
and working temperature for the batteries. When the working temperature is lower than the
temperature specification of the batteries, the battery capacity declines. Therefore, the heating
film is installed to provide the optimal working temperature for the batteries.

Technical Specifications
The technical specifications of a heating film are as follows:
l

The heating film uses the AC power and its rated voltage and rated power are 220 V AC
and 100 W.

The heating film starts to work when the operating temperature is lower than 1oC6oC
(33.8oF42.8oF) and stops working when the operating temperature is higher than 15oC
3oC (59oF37.4oF).

4.4.7 Door Status Sensor


The door status sensor monitors whether the cabinet door is open.
The door status sensor consists of the magnets and switch. Figure 4-14 shows the exterior of a
door status sensor.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

118

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Figure 4-14 Exterior of a door status sensor

4.4.8 Battery Temperature Sensor


The battery temperature sensor monitors temperature in the battery cabinet in real time and
reports related information to the central monitoring unit type EA (CMUEA).

Installation Position
Figure 4-15 and Figure 4-16 show the temperature sensor in an IBBS200D and IBBS200T.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

119

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Figure 4-15 Temperature sensor in an IBBS200D

Figure 4-16 Temperature sensor in an IBBS200T

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

120

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

4.5 IBBS200D Cables


This chapter describes the PGND cables, equipotential cables, power cables, and signal cables
in an IBBS200D.

4.5.1 Cable List


The IBBS200D cables consist of the PGND cables, equipotential cables, power cables, and
signal cables.

Power Cables, PGND Cables, and Equipotential Cables


Table 4-11 lists the power cables, PGND cables, and equipotential cables.
Table 4-11 Power cables, PGND cables, and equipotential cables
Categ
ory

Cable

Cables
to be
install
ed
onsite

Issue Draft A (2012-9-15)

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

Power Cables
in a Battery
Cabinet

OT terminal

OT terminal
OT terminal
on the BAT in
the EPU

BAT in the
power
distribution
box in the
IBBS200D or
IBBS200T

Power Cables
for the Fan in
an IBBS200D

EPC4 or
EPC6
connector

LOAD8 port
on the EPU

EPC4 or
EPC6
connector

FAN/
TEC_INPUT
port on the
power
distribution
box in the
IBBS200D

Power Cable
for a Heating
Film

OT terminal

L1 and N1 or
L2 and N2 on
the junction
box in the
APM30H

OT terminal

L and N on the
junction
terminal for
the input
power cable
for the heating
film in the
IBBS200D

4.5.3 PGND
Cable

OT terminal

Ground bar
for the cabinet

OT terminal

Ground busbar
outside the
cabinet

4.5.4
Equipotential
Cable

OT terminal

Ground bar in
the upper
cabinet

OT terminal

Ground bar in
the lower
cabinet

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

121

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Categ
ory

Cable

Cables
install
ed
before
deliver
y

4 IBBS200D Product Description

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

Signal Cables
Table 4-12 describes the signal cables.
Table 4-12 Signal cables
Categ
ory

Cable

Cables
to be
install
ed
onsite

Cables
install
ed
before
deliver
y

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

Monitoring
Signal
Cable for a
Battery
Cabinet

RJ45
connector

COM_IN port on
the CMUEA in the
IBBS200D or
IBBS200T

RJ45
connector

COM_485 port on
the PMU

Monitoring
Signal
Cable
Between
Cascaded
CMUEAs

RJ45
connector

COM_OUT port
on the CMUEA in
the upper cabinet
(TMC,
IBBS200D,
IBBS200T, or
RFC)

RJ45
connector

COM_IN port on
the CMUEA in the
lower cabinet
(TMC, IBBS200D,
IBBS200T, or
RFC)

ELU Signal
Cable

RJ45
connector

ELU

RJ45
connector

ELU port in the


CMUEA

Monitoring
Signal
Cable for a
Door Status
Sensor

Bare wire

GATE port on the


CMUEA

Bare wire

Door status sensor

4.5.2 IBBS200D Cable Connections


This chapter describes the principles for connecting the power cables and signal cables in an
IBBS200D.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

122

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

IBBS200D Power Cable Connections


The section provides a figure showing the IBBS200D power cable connections.
Figure 4-17 shows the IBBS200D power cable connections.
Figure 4-17 IBBS200D power cable connections

(1) Cable between the battery group (2) Input power cable for the fan in (3) Input power cable for batteries
and the short-circuiting copper bar the IBBS200D
(4) Cable between the battery group (5) Power cable for the heating film (6) Power transfer cable for the fan in
and the short-circuiting copper bar
the IBBS200D

IBBS200D Signal Cable Connections


This section describes the IBBS200D signal cable connections.
Figure 4-18 shows the IBBS200D signal cable connections.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

123

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Figure 4-18 IBBS200D signal cable connections

(1) Monitoring signal cable for the door


status sensor

(2) ELU signal cable (3) Monitoring signal cable for the battery
cabinet

4.5.3 PGND Cable


A PGND cable connects a cabinet to a ground bar, which provides ground protection for the
cabinet. The maximum length of a PGND cable is 30 m (98.43 ft).

Exterior
Figure 4-19 shows the exterior of a PGND cable.
NOTE

When the 110 V AC dual-live-wire power is supplied for the cabinet, a green PGND cable is used.

Figure 4-19 Exterior of a PGND cable

(1) OT terminal

Cable Description
Table 4-13 describes a PGND cable.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

124

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Table 4-13 PGND cable


Cable

Color

Cross-Sectional Area of the Core Wire and


Size of the OT Terminal

PGND cable

Green and yellow

M6, 16 mm2 (0.025 in.2)

4.5.4 Equipotential Cable


An equipotential cable connects the PGND terminals of two cabinets. It ensures equipotential
bonding between the cabinets and the safe operation of base stations.

Exterior
Figure 4-20 shows the exterior of an equipotential cable.
NOTE

When the 110 V AC dual-live-wire power is supplied for the cabinet, a green equipotential cable is used.

Figure 4-20 Exterior of an equipotential cable

(1) OT terminal

Cable Description
Table 4-14 describes an equipotential cable.
Table 4-14 Equipotential cable
Cable

Color

Cross-Sectional Area of the Core Wire and


Size of the OT Terminal

Equipotential cable
between cabinets

Green and yellow

M6, 16 mm2 (0.025 in.2)

4.5.5 Power Cables


This chapter describes all power cables in an IBBS200D.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

125

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Power Cables in a Battery Cabinet


This section describes the input power cable for a battery cabinet, power cable between the
battery group and the short-circuiting copper bar, and copper bar between the batteries.

Exterior
Figure 4-21 shows the exterior of the input power cable for the battery cabinet, of which
maximum length is 5 m (16.40 ft).
Figure 4-21 Exterior of the input power cable for the battery cabinet

(1) OT terminal (35 mm2 or 0.054 in.2 (UL3436), M8)

NOTE

One end of the input power cable is connected to the power distribution box in the battery cabinet, and the
other end is connected to the EPU in the APM30H.

Figure 4-22 shows a cable between the battery group and the short-circuiting copper bar.
Figure 4-22 Cable between the battery group and the short-circuiting copper bar

(1) OT terminal (35 mm2 or 0.054 in.2 (UL3436), M8) (2) OT terminal (35 mm2 or 0.054 in.2 (UL3436), M6)

NOTE

The M6 OT terminal is connected to the battery, and the M8 OT terminal is connected to the power
distribution box.

Copper bars between batteries are delivered with batteries. Figure 4-23 shows a copper bar
between the batteries.
Figure 4-23 Copper bar between the batteries

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

126

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Specifications
l

The RTN(+) wire of the input power cable for the battery is a red wire with a cross-sectional
area of 35 mm2 (0.054 in.2), and the NEG(-) wire is a black wire with a cross-sectional area
of 35 mm2 (0.054 in.2).

The RTN(+) wire of the power cable between the battery group and short-circuiting copper
bar is a red wire with a cross-sectional area of 35 mm2 (0.054 in.2), and the NEG(-) wire
is a black wire with a cross-sectional area of 35 mm2 (0.054 in.2).

Power Cables for the Fan in an IBBS200D


Power cables for the fan in an IBBS200D consist of the input power cable for the fan in an
IBBS200D and power transfer cable in an IBBS200D, feeding power into the fan in the
IBBS200D.

Input power cable for the fan in an IBBS200D


Figure 4-24 shows the exterior of the input power cable for the fan in an IBBS200D.
Figure 4-24 Exterior of the input power cable for the fan in an IBBS200D

(1) EPC4 or EPC6 connector

Table 4-15 lists the specifications of the cable.


Table 4-15 Specifications of the input power cable for the fan in an IBBS200D
Cable

Wire

Wire Color in Most


Regions

Wire Color in Other


Regions

Input power cable


for the fan in an
IBBS200D

RTN(+)

Black

Blue

NEG(-)

Blue

Gray

Power Transfer Cable for the Fan in an IBBS200D


Figure 4-25 shows the exterior of the power transfer cable for the fan in an IBBS200D.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

127

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Figure 4-25 Exterior of the power transfer cable for the fan in an IBBS200D

(1) 3V3 connector

(2) OT terminal (M4, 2.5 mm2 or 0.004 in.2)

Table 4-16 lists the specifications of the cable.


Table 4-16 Specifications of the power transfer cable for the fan in an IBBS200D
Cable

Wire

Wire Color in Most


Regions

Wire Color in Other


Regions

Power transfer
cable for the fan in
an IBBS200D

W1

Blue

Gray

W2

Black

Blue

Power Cable for a Heating Film


The power cable for a heating film connects an output terminal on a junction box on the inside
of the left wall of the APM30H to the AC power input wiring terminal for a heating film.

Exterior
The power cable for the heating film, whose cross-sectional area is 1.5 mm2 (0.002 in.2), is
wrapped in a black jacket and has a blue wire and a brown wire, as shown in Figure 4-26.
Figure 4-26 Power cable for the heating film

(1) OT terminal (M4, 1.5 mm2 or 0.002 in.2)

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

128

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

NOTE

The colors and structures of cables delivered by Huawei vary according to countries and areas. If cables
are purchased at local markets, the cables must comply with local rules and regulations.

4.5.6 Signal Cables


This chapter describes all signal cables in an IBBS200D.

ELU Signal Cable


The electronic label unit (ELU) signal cable is used by the ELU to report the cabinet type to the
central monitoring unit type EA (CMUEA).

Exterior
Figure 4-27 shows the exterior of an ELU signal cable.
Figure 4-27 Exterior of an ELU signal cable

(1) RJ45 connector

Cable Description
Table 4-17 describes the pin assignment for the wires of an ELU signal cable.
Table 4-17 Pin assignment for the wires of an ELU signal cable
X1 End

X2 End

Color

Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

X1.3

X2.3

White

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Twisted pair

Twisted pair

Twisted pair

129

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

Monitoring Signal Cable for a Door Status Sensor


The monitoring signal cable for a door status sensor is used to inform the central monitoring
unit type EA (CMUEA) of the door status obtained from the door status sensor in the TMC11H,
RFC, IBBS200D, or IBBS200T.

Exterior
There are two wires in the monitoring signal cable for a door status sensor, both of which have
a bare wire at each end, as shown in Figure 4-28.
Figure 4-28 Exterior of the monitoring signal cable for a door status sensor

Monitoring Signal Cable for a Battery Cabinet


The monitoring signal cable for a battery cabinet reports the monitoring signals from an
IBBS200D or IBBS200T to the PMU.

Exterior
Figure 4-29 shows the exterior of the monitoring signal cable for the battery cabinet.
Figure 4-29 Exterior of the monitoring signal cable for the battery cabinet

(1) RJ45 connector

Cable Description
Table 4-18 describes the pin assignment for the wires of the monitoring signal cable for a battery
cabinet.
Table 4-18 Pin assignment for the wires of the monitoring signal cable for a battery cabinet
X1 End

X2 End

Color

Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

130

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

X1 End

X2 End

Color

Type

X1.3

X2.3

White

Twisted pair

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Twisted pair

Twisted pair

Monitoring Signal Cable Between Cascaded CMUEAs


Monitoring signal cable between cascaded central monitoring unit type EA (CMUEA) boards
connects the CMUEAs in two cabinets and reports the RS485 signals from the CMUEA in the
lower-level cabinet to the BBU through the CMUEA in the upper-level cabinet. The monitoring
signal cable is 5 m (16.40 ft) long.

Exterior
The monitoring signal cable is black and has an RJ45 connector at each end, as shown in Figure
4-30.
Figure 4-30 Exterior of a monitoring signal cable

(1) RJ45 connector

Cable Description
Table 4-19 describes the pin assignment for the wires of a monitoring signal cable.
Table 4-19 Pin assignment for the wires of a monitoring signal cable
X1 End

X2 End

Description

X1.1

X2.1

Twisted pair

X1.2

X2.2

X1.3

X2.3

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Twisted pair
131

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

4 IBBS200D Product Description

X1 End

X2 End

X1.6

X2.6

X1.4

X2.4

X1.5

X2.5

X1.7

X2.7

X1.8

X2.8

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Description

Twisted pair

Twisted pair

132

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

IBBS200T Product Description

About This Chapter


This chapter describes the exterior, functions, technical specifications, application scenarios,
structure, components, and cables of the IBBS200T.
5.1 IBBS200T Description
An IBBS200T is an outdoor battery cabinet with a TEC. The IBBS200T can provide backup
power for the APM30H.
5.2 Technical Specifications of an IBBS200T
The technical specifications of an IBBS200T consist of electrical specifications, engineering
specifications, and environmental specifications.
5.3 IBBS200T Structure
The IBBS200T uses a modular and integrated structure. The power distribution equipment is
installed on the inside of the upper right wall of the cabinet, and the monitoring equipment is
installed inside the cabinet door.
5.4 IBBS200T Components
The IBBS200T components include the TEC, power distribution box, central monitoring unit
type EA (CMUEA), batteries, electronic label unit (ELU), door status sensor, and battery
temperature sensor.
5.5 IBBS200T Cables
This chapter describes the PGND cables, equipotential cables, power cables, and signal cables
in an IBBS200T.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

133

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

5.1 IBBS200T Description


An IBBS200T is an outdoor battery cabinet with a TEC. The IBBS200T can provide backup
power for the APM30H.
The housing material of the IBBS200T uses aluminum board. The surface is covered with acrylic
orange-figured paint to protect the IBBS200T from the damage caused by the solar radiation,
corrosion, moist heat, and mold. The coverage of the heat insulation foam is more than 75% on
the inner side of the cabinet. In this way, the cooling efficiency of the TEC can be improved.

Exterior of an IBBS200T
Dimensions of the IBBS200T (H x W x D): 700 mm x 600 mm x 480 mm or 27.56 in. x 23.62
in. x 18.90 in. (not including the base).
Figure 5-1 shows the exterior of an IBBS200T.
Figure 5-1 Exterior of an IBBS200T

Functions of an IBBS200T
Table 5-1 describes the functions of an IBBS200T.
Table 5-1 Functions of an IBBS200T
Item

Description

Backup power

Configured with one or two groups of batteries, each group providing up to


48 V 92 Ah DC backup power.

Reporting the
cabinet type
automatically

The electronic label unit (ELU) reports the cabinet type automatically.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

134

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Item

Description

Built-in TEC

Enables the IBBS200T to adapt to high ambient temperature. In this way,


the cabinet works within an acceptable temperature range.

Central
monitoring

The central monitoring unit type EA (CMUEA) collects the alarm signals
from the door status sensor, smoke sensor, fans, and temperature sensor,
and reports these alarm signals to the base station.

NOTE

Two stacked battery cabinets provide up to 48 V 368 Ah backup power.

5.2 Technical Specifications of an IBBS200T


The technical specifications of an IBBS200T consist of electrical specifications, engineering
specifications, and environmental specifications.

Electrical Specifications of an IBBS200T


Table 5-2 describes the specifications of an IBBS200T.
Table 5-2 Electrical specifications of an IBBS200T
Item

Specifications

Input voltage range

-38.4 to -57 V DC

Maximum capacity of the


batteries

48 V/184 Ah

Cooling capability

l When the ambient temperature is equal to or less than


45oC (113oF), the temperature of the air return vent for
inner circulation of the cabinet is equal to or less than
35oC (95oF).
l When the ambient temperature is equal to 50oC
(122oF) or between 45oC (113oF) and 50oC (122oF), the
temperature of the air return vent for inner circulation
of the cabinet is equal to or less than 45oC (113oF).

Engineering Specifications of an IBBS200T


Table 5-3 describes the engineering specifications of an IBBS200T.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

135

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Table 5-3 Engineering specifications of an IBBS200T


Item

Specifications

Remarks

Cabinet weight

45 kg (99.21 lb)

Configured with monitoring


boards, power distribution box,
and cables only.

Battery weight

12 V 92 Ah battery: 33.5 kg (73.85


lb)

The total capacity can be expanded


to 48 V 184 Ah (two groups of 48
V 92 Ah batteries)

NOTE
Batteries from different
manufacturers have different
specifications. The above
specifications are from the commonly
used batteries.

Dimensions of the
cabinet (H x W x
D)

700 mm x 600 mm x 480 mm


(27.56 in. x 23.62 in. x 18.90 in.)

Dimensions of the
base (H x W x D)

200 mm x 600 mm x 434 mm (7.87


in. x 23.62 in. x 17.09 in.)

Installation mode

When installed on the ground, it


can be located under the TMC11H
or APM30H.

In stack mode, the IBBS200T must


be installed under the TMC11H or
APM30H.

Environmental Specifications of an IBBS200T


The IBBS200T can be used outdoors. Table 5-4 describes the environmental specifications of
an IBBS200T.
Table 5-4 Environmental specifications of an IBBS200T
Item

Specifications

Remarks

Operating
temperatur
e

-20oC to +50oC (-4oF to +122oF)

When the temperature is higher than


50oC (122oF), a sun shield is required.

Relative
humidity

5% RH to 100% RH

Altitude

-60 m to 4,000 m (-196.85 ft to


13123.36 ft)

At the altitude from 1,800 m (5905.51


ft), the maximum operating
temperature drops by 1oC (33.8oF)
each time the altitude increases by 220
m (721.78 ft).

Wind
speed

67 m/s

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

136

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Item

Specifications

Remarks

Storage
temperatur
e

-40oC to +70oC (-40oF to +158oF)

Dustproof
and
waterproof

IP55

Noise

Meeting the ETS 300 753 4.1E


standard (rural level)

5.3 IBBS200T Structure


The IBBS200T uses a modular and integrated structure. The power distribution equipment is
installed on the inside of the upper right wall of the cabinet, and the monitoring equipment is
installed inside the cabinet door.
Figure 5-2 shows the structure of an IBBS200T.
Figure 5-2 Structure of an IBBS200T

Table 5-5 describes the configurations of an IBBS200T.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

137

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Table 5-5 Configurations of an IBBS200T


N
o.

Module

Option
al/
Manda
tory

Max
imu
m
Qua
ntit
y
Con
figu
red
in a
Sin
gle
Cab
inet

Remarks

TEC

Mandat
ory

The TEC ensures the normal operation of the


IBBS200T in high-temperature areas and dissipates
heat for the batteries.

Central
monitoring
unit type
EA
(CMUEA)

Mandat
ory

The CMUEA provides the following functions:


temperature control, Boolean alarm detection, and
electronic label unit (ELU) identification of the
cabinet.

Electronic
label unit
(ELU)

Mandat
ory

The ELU reports the cabinet type automatically to


facilitate troubleshooting.

Storage
battery

Mandat
ory

The storage batteries provide long-duration backup


power for a base station.

Power
distributio
n box

Mandat
ory

The power distribution box is installed on the inside


of the upper right wall of the cabinet. It transfers and
distributes power to the FAN or TEC and storage
batteries.

Door status
sensor

Mandat
ory

The door status sensor monitors whether the cabinet


door is open.

NOTE

For the position of the battery temperature sensor, see section "Battery Temperature Sensor."

5.4 IBBS200T Components


The IBBS200T components include the TEC, power distribution box, central monitoring unit
type EA (CMUEA), batteries, electronic label unit (ELU), door status sensor, and battery
temperature sensor.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

138

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

5.4.1 TEC
The TEC ensures the normal operation of the IBBS200T in high-temperature areas and dissipates
heat for the batteries.

Exterior
Figure 5-3 shows the exterior of the TEC.
Figure 5-3 Exterior of the TEC

(1) Outer air circulation fan

(2) Inner air circulation fan

Functions
The functions of the TEC are as follows:
l

If there is a sun shield, and the ambient temperature is 50oC (122oF) without solar radiation,
the TEC ensures that the temperature is equal to or less than 40oC (104oF) in the cabinet
when batteries are in float charge and equal to or less than 45oC (113oF) when the batteries
are in boost charge.

If there is no sun shield, and the ambient temperature is 50oC (122oF) with solar radiation
of 1120 W/m2, the TEC ensures that the temperature is equal to or less than 45oC (113oF)
in the cabinet when batteries are in float charge and equal to or less than 50oC (122oF) when
the batteries are in boost charge.

If the ambient temperature is 32oC (89.6oF), and there is no temperature difference between
the air intake vent at the hot and cold sides of the TEC, the refrigeration power of the TEC
is equal to or more than 190 W10% and the COP is equal to or more than 0.5.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

139

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

5.4.2 Power Distribution Box


The power distribution box is installed on the inside of the upper right wall of the cabinet, which
controls the two battery groups separately and controls the DC power supply to the fan assembly
or TEC.

Exterior
Figure 5-4 shows the exterior of a power distribution box.
Figure 5-4 Exterior of a power distribution box

Ports
Table 5-6 describes the ports on the power distribution box.
Table 5-6 Ports on the power distribution box
No.

Silkscreen

Module

Remarks

(1)

BAT

Input power
cable port for
batteries

It supports a one-hole OT terminal (M8)


installed on a cable with a cross-sectional area
of 35 mm2 (0.054 in.2).

(2)

BAT_SW0

Circuit breaker
for the upper
batteries

It controls the cable of the upper batteries in the


cabinet. The circuit breaker requires 250 A
current.

(3)

FAN/
TEC_OUTPU
T

Power output
port for a fan
assembly or
TEC

EPC4 connector, which requires 30 A current.

(4)

BAT_SW1

Circuit breaker
for the lower
batteries

It controls the power supply to the lower


batteries in the cabinet. The circuit breaker
requires 250 A current.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

140

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

No.

Silkscreen

Module

Remarks

(5)

BAT

Input power
cable port for
batteries

It supports a one-hole OT terminal (M8)


installed on a cable with a cross-sectional area
of 35 mm2 (0.054 in.2).

(6)

FAN/
TEC_INPUT

Power input port


for a fan
assembly or
TEC

EPC4 connector, which requires 30 A current.

Outer Structure
Figure 5-5 shows the outer structure of a power distribution box.
Figure 5-5 Outer structure of a power distribution box

(1) RTN(+) cable for the upper


batteries

(2) Power transfer cable for a TEC or (3) NEG(-) wire for the lower
fan assembly
batteries

(4) NEG(-) wire for the upper


batteries

(5) RTN(+) wire for the lower


batteries

5.4.3 Central Monitoring Unit Type EA (CMUEA)


The central monitoring unit type EA (CMUEA) mainly monitors the fans, heater, and cabinet
temperature. The CMUEA can be used in an AMP30H, RFC, TMC11H, IBBS200D, or
IBBS200T.

Exterior
Figure 5-6 shows the exterior of a CMUEA.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

141

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Figure 5-6 Exterior of a CMUEA

Ports
Figure 5-7 shows the ports on a CMUEA.
Figure 5-7 Ports on a CMUEA

Table 5-7 describes the ports on a CMUEA.


Table 5-7 Ports on a CMUEA
No
.

Port

Remarks

(1)

TEMP2

Reserved port, connected to the temperature sensor

(2)

WATER

Connected to the water sensor

(3)

IFAN4

Connected to the inner circulation fan for the cabinet

(4)

IFAN3

Connected to the inner circulation fan for the cabinet

(5)

IFAN2

Connected to the inner circulation fan for the cabinet

(6)

IFAN1

Connected to the inner circulation fan for the cabinet

(7)

TEC

Connected to the TEC cooler to receive alarms related to the TEC cooler

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

142

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

No
.

Port

Remarks

(8)

TEMP1

l In the RFC, this port is connected to the temperature sensor at the air
intake vent of the cabinet to receive temperature alarms.
l In the IBBS200D or IBBS200T, this port is connected to the
temperature sensor to receive battery temperature alarm signals.

(9)

COM_OUT

RS485 signal port. It communicates with lower-level cascading ports


and reports monitoring information.
l In the APM30H, this port is connected to the PMU.
l In the RFC, TMC11H, or IBBS200D/IBBS200T, this port is
connected to the lower-level CMUEA.

(10
)

COM_IN

RS485 signal port. It communicates with upper-level cascading ports


and reports monitoring information.
l In the APM30H, this port is connected to the BBU.
l In the RFC or TMC11H, this port is connected to the BBU or an
upper-level CMUEA.
l In the IBBS200T, this port is connected to the PMU or upper-level
CMUEA.

(11
)

RUN
indicator

Indicating the running status of the fans

(12
)

ALM
indicator

Indicating the alarm status of the fans

(13
)

ELU

Port connected to the ELU to report the cabinet type

(14
)

GATE

Boolean signal port connected to the door status sensor

(15
)

IN0, IN1,
and IN2

Reserved Boolean signal port

(16
)

SMOKE

Boolean signal port connected to the smoke sensor

(17
)

EFAN1

Connected to the outer circulation fan for the cabinet

(18
)

EFAN2

Connected to the outer circulation fan for the cabinet

(19
)

PWR

Power input port providing DC power input for the board

Indicators
Table 5-8 describes the indicators on the CMUEA.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

143

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Table 5-8 Indicators on the CMUEA


Silkscr
een

Color

Status

Meaning

RUN

Green

Blinking (on for 1s and


off for 1s)

The board is functional and communicating


with the BBU properly.

Blinking (on for 0.125s


and off for 0.125s)

The board is functional but fails to


communicate with the BBU or the board is
not registered.

Steady on

The board is in the power-on self-check


status.

Steady off

The board is faulty.

Steady off

No alarm has been reported.

Steady on

Alarms are generated, and the board must be


replaced.

Blinking (on for 1s and


off for 1s)

An alarm is generated, and the alarm may be


caused by an associated board or port fault.
Therefore, you need to locate the fault before
determining whether to replace the board.

ALM

Red

DIP Switch
On the CMUEA, there is a DIP switch J18, which is used to set the working mode of the CMUEA
according to the cabinet type. Figure 5-8 shows the position of a DIP switch on the CMUEA.
Figure 5-8 Position of a DIP switch on the CMUEA

In different types of cabinet, the DIP switch on the CMUEA is set in different ways, as shown
in Figure 5-9.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

144

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Figure 5-9 DIP switch setting on the CMUEA in different cabinets

NOTE

The white boxes indicate the positions of all bits in the DIP switch.

5.4.4 Storage Battery


This section describes the exterior, technical specifications, and configurations of the storage
batteries.
NOTE

Storage batteries from different manufacturers differ in exterior and technical specifications. In this section, a
12 V 92 Ah storage battery is described.

Exterior
Figure 5-10 shows the exterior of a 12 V 92 Ah storage battery.
Figure 5-10 12 V 92 Ah storage battery

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

145

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Configurations
The cabinet supports two types of storage battery groups: 48 V 92 Ah and 48 V 184 Ah.
l

Two 48 V 92 Ah storage battery groups are connected in parallel and serve as a 48 V 184
Ah storage battery group.

Each group consists of four storage batteries.

Technical Specifications
Table 5-9 describes the technical specifications of a 12 V 92 Ah storage battery.
Table 5-9 Technical specifications of a 12 V 92 Ah storage battery
Battery Type

Dimensions of a Battery
(H x W x D)

Battery Weight

12 V 92 Ah

287 mm x 105 mm x 390 mm


(11.30 in. x 4.13 in. x 15.35
in.)

33.5 kg (73.85 lb)

287 mm x 108 mm x 393 mm


(11.30 in. x 4.25 in. x 15.47
in.)

35 kg (73.85 lb)

5.4.5 ELU
The electronic label unit (ELU) reports the cabinet type automatically to facilitate
troubleshooting.
The ELU is installed on the inside of the right wall of the APM30H/TMC11H/RFC or the inside
of the left wall of the IBBS200D/IBBS200T. Figure 5-11 shows the position and exterior of an
ELU on the inside of the right wall of the APM30H or the inside of the left wall of the IBBS200D.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

146

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Figure 5-11 Exterior of an ELU

(1) Shell

(2) RJ45 port

5.4.6 Door Status Sensor


The door status sensor monitors whether the cabinet door is open.
The door status sensor consists of the magnets and switch. Figure 5-12 shows the exterior of a
door status sensor.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

147

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Figure 5-12 Exterior of a door status sensor

5.4.7 Battery Temperature Sensor


The battery temperature sensor monitors temperature in the battery cabinet in real time and
reports related information to the central monitoring unit type EA (CMUEA).

Installation Position
Figure 5-13 and Figure 5-14 show the temperature sensor in an IBBS200D and IBBS200T.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

148

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Figure 5-13 Temperature sensor in an IBBS200D

Figure 5-14 Temperature sensor in an IBBS200T

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

149

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

5.5 IBBS200T Cables


This chapter describes the PGND cables, equipotential cables, power cables, and signal cables
in an IBBS200T.

5.5.1 Cable List


The IBBS200T cables consist of the PGND cables, equipotential cables, power cables, and signal
cables.

Power Cables, PGND Cables, and Equipotential Cables


Table 5-10 lists the power cables, PGND cables, and equipotential cables.
Table 5-10 Power cables, PGND cables, and equipotential cables
Categ
ory

Cable

Cables
to be
install
ed
onsite

Issue Draft A (2012-9-15)

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

Power Cables
in a Battery
Cabinet

OT terminal

OT terminal
on the output
port for the
batteries in the
EPU

OT terminal

RTN(+) and
NEG(-) ports
on the BAT in
the power
distribution
box in the
IBBS200D or
IBBS200T

TEC Power
Cables

EPC4 or
EPC6
connector

LOAD8 port
on the EPU

EPC4 or
EPC6
connector

RTN(+) and
NEG(-) ports
on the fan
assembly or
TEC on the
power
distribution
box in the
IBBS200T

5.5.3 PGND
Cable

OT terminal

Ground bar
for the cabinet

OT terminal

Ground busbar
outside the
cabinet

5.5.4
Equipotential
Cable

OT terminal

Ground bar in
the upper
cabinet

OT terminal

Ground bar in
the lower
cabinet

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

150

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

Categ
ory

Cable

Cables
install
ed
before
deliver
y

5 IBBS200T Product Description

One End

The Other End

Connector

Installation
Position

Connector

Installation
Position

NOTE

(1) If there are two IBBS200Ts, connects the power cable for the TEC in the second IBBS200T to the
power distribution box in the first IBBS200T.

Signal Cables
Table 5-11 describes the signal cables.
Table 5-11 Signal cables
Categ
ory

Cable

Cables
to be
install
ed
onsite

Cables
install
ed
before
deliver
y

Issue Draft A (2012-9-15)

One End

The Other End

Connecto
r

Installation
Position

Connect
or

Installation
Position

Monitoring
Signal
Cable for a
Battery
Cabinet

RJ45
connector

COM_IN port on
the CMUEA in the
IBBS200D or
IBBS200T

RJ45
connector

COM_485 port on
the PMU

Monitoring
Signal
Cable
Between
Cascaded
CMUEAs

RJ45
connector

COM_OUT port
on the CMUEA in
the upper cabinet
(TMC,
IBBS200D,
IBBS200T, or
RFC)

RJ45
connector

COM_IN port on
the CMUEA in the
lower cabinet
(TMC, IBBS200D,
IBBS200T, or
RFC)

ELU Signal
Cable

RJ45
connector

ELU

RJ45
connector

ELU port in the


CMUEA

Monitoring
Signal
Cable for a
Door Status
Sensor

2-pin
connector

GATE port on the


CMUEA

Bare wire

Door status sensor

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

151

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

5.5.2 IBBS200T Cable Connections


This chapter describes the principles for connecting the power cables and signal cables in an
IBBS200T.

IBBS200T Power Cable Connections


The section provides a figure showing the IBBS200T power cable connections.
Figure 5-15 shows the IBBS200T power cable connections.
Figure 5-15 IBBS200T power cable connections

(1) Cable between the battery group and the (2) TEC input power cables (3) Input power cable for batteries
short-circuiting copper bar
(4) Cable between the battery group and the (5) TEC power transfer cable short-circuiting copper bar

IBBS200T Signal Cable Connections


This section describes the IBBS200T signal cable connections.
Figure 5-16 shows the IBBS200T signal cable connections.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

152

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Figure 5-16 IBBS200T signal cable connections

(1) Monitoring signal cable for the battery (2) ELU signal cable (3) Monitoring signal cable for the door
cabinet
status sensor

5.5.3 PGND Cable


A PGND cable connects a cabinet to a ground bar, which provides ground protection for the
cabinet. The maximum length of a PGND cable is 30 m (98.43 ft).

Exterior
Figure 5-17 shows the exterior of a PGND cable.
NOTE

When the 110 V AC dual-live-wire power is supplied for the cabinet, a green PGND cable is used.

Figure 5-17 Exterior of a PGND cable

(1) OT terminal

Cable Description
Table 5-12 describes a PGND cable.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

153

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Table 5-12 PGND cable


Cable

Color

Cross-Sectional Area of the Core Wire and


Size of the OT Terminal

PGND cable

Green and yellow

M6, 16 mm2 (0.025 in.2)

5.5.4 Equipotential Cable


An equipotential cable connects the PGND terminals of two cabinets. It ensures equipotential
bonding between the cabinets and the safe operation of base stations.

Exterior
Figure 5-18 shows the exterior of an equipotential cable.
NOTE

When the 110 V AC dual-live-wire power is supplied for the cabinet, a green equipotential cable is used.

Figure 5-18 Exterior of an equipotential cable

(1) OT terminal

Cable Description
Table 5-13 describes an equipotential cable.
Table 5-13 Equipotential cable
Cable

Color

Cross-Sectional Area of the Core Wire and


Size of the OT Terminal

Equipotential cable
between cabinets

Green and yellow

M6, 16 mm2 (0.025 in.2)

5.5.5 Power Cables


This chapter describes all power cables in an IBBS200T.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

154

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Power Cables in a Battery Cabinet


This section describes the input power cable for a battery cabinet, power cable between the
battery group and the short-circuiting copper bar, and copper bar between the batteries.

Exterior
Figure 5-19 shows the exterior of the input power cable for the battery cabinet, of which
maximum length is 5 m (16.40 ft).
Figure 5-19 Exterior of the input power cable for the battery cabinet

(1) OT terminal (35 mm2 or 0.054 in.2 (UL3436), M8)

NOTE

One end of the input power cable is connected to the power distribution box in the battery cabinet, and the
other end is connected to the EPU in the APM30H.

Figure 5-20 shows a cable between the battery group and the short-circuiting copper bar.
Figure 5-20 Cable between the battery group and the short-circuiting copper bar

(1) OT terminal (35 mm2 or 0.054 in.2 (UL3436), M8) (2) OT terminal (35 mm2 or 0.054 in.2 (UL3436), M6)

NOTE

The M6 OT terminal is connected to the battery, and the M8 OT terminal is connected to the power
distribution box.

Copper bars between batteries are delivered with batteries. Figure 5-21 shows a copper bar
between the batteries.
Figure 5-21 Copper bar between the batteries

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

155

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Specifications
l

The RTN(+) wire of the input power cable for the battery is a red wire with a cross-sectional
area of 35 mm2 (0.054 in.2), and the NEG(-) wire is a black wire with a cross-sectional area
of 35 mm2 (0.054 in.2).

The RTN(+) wire of the power cable between the battery group and short-circuiting copper
bar is a red wire with a cross-sectional area of 35 mm2 (0.054 in.2), and the NEG(-) wire
is a black wire with a cross-sectional area of 35 mm2 (0.054 in.2).

TEC Power Cables


TEC power cables consist of the TEC input power cable and TEC power transfer cable, feeding
power into the TEC.

TEC Input Power Cable


Figure 5-22 shows the exterior of the TEC input power cable.
Figure 5-22 Exterior of a TEC input power cable

(1) EPC4 or EPC6 connector

Table 5-14 lists the specifications of the cable.


Table 5-14 Specifications of a TEC input power cable
Cable

Wire

Wire Color in
Most Regions

Wire Color in
Other Regions

Cross-Sectional
Area of the Core
Wire and Size of
the OT Terminal

TEC input
power cable

RTN
(+)

Black

Blue

M4, 2.5 mm2 (0.004


in.2)

NEG
(-)

Blue

Gray

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

156

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

TEC Power Transfer Cable


Figure 5-23 shows the exterior of the TEC power transfer cable.
Figure 5-23 Exterior of the TEC power transfer cable

(1) 3V3 connector

(2) OT terminal (M4, 2.5 mm2 or 0.004 in.2)

Table 5-15 lists the specifications of the cable.


Table 5-15 Specifications of a TEC power transfer cable
Cable

Wire

Wire Color in Most


Regions

Wire Color in Other


Regions

TEC power transfer


cable

W1

Blue

Gray

W2

Black

Blue

5.5.6 Signal Cables


This chapter describes all signal cables in an IBBS200T.

ELU Signal Cable


The electronic label unit (ELU) signal cable is used by the ELU to report the cabinet type to the
central monitoring unit type EA (CMUEA).

Exterior
Figure 5-24 shows the exterior of an ELU signal cable.

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

157

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Figure 5-24 Exterior of an ELU signal cable

(1) RJ45 connector

Cable Description
Table 5-16 describes the pin assignment for the wires of an ELU signal cable.
Table 5-16 Pin assignment for the wires of an ELU signal cable
X1 End

X2 End

Color

Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

X1.3

X2.3

White

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Twisted pair

Twisted pair

Twisted pair

Monitoring Signal Cable for a Door Status Sensor


The monitoring signal cable for a door status sensor is used to inform the central monitoring
unit type EA (CMUEA) of the door status obtained from the door status sensor in the TMC11H,
RFC, IBBS200D, or IBBS200T.

Exterior
There are two wires in the monitoring signal cable for a door status sensor, both of which have
a bare wire at each end, as shown in Figure 5-25.
Figure 5-25 Exterior of the monitoring signal cable for a door status sensor

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

158

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Monitoring Signal Cable for a Battery Cabinet


The monitoring signal cable for a battery cabinet reports the monitoring signals from an
IBBS200D or IBBS200T to the PMU.

Exterior
Figure 5-26 shows the exterior of the monitoring signal cable for the battery cabinet.
Figure 5-26 Exterior of the monitoring signal cable for the battery cabinet

(1) RJ45 connector

Cable Description
Table 5-17 describes the pin assignment for the wires of the monitoring signal cable for a battery
cabinet.
Table 5-17 Pin assignment for the wires of the monitoring signal cable for a battery cabinet
X1 End

X2 End

Color

Type

X1.1

X2.1

White

Twisted pair

X1.2

X2.2

Orange

X1.3

X2.3

White

X1.6

X2.6

Green

X1.5

X2.5

White

X1.4

X2.4

Blue

X1.7

X2.7

White

X1.8

X2.8

Brown

Twisted pair

Twisted pair

Twisted pair

Monitoring Signal Cable Between Cascaded CMUEAs


Monitoring signal cable between cascaded central monitoring unit type EA (CMUEA) boards
connects the CMUEAs in two cabinets and reports the RS485 signals from the CMUEA in the
lower-level cabinet to the BBU through the CMUEA in the upper-level cabinet. The monitoring
signal cable is 5 m (16.40 ft) long.
Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

159

APM30H&TMC11H&IBBS200D&IBBS200T
(Ver.D1&Ver.D2)
product description

5 IBBS200T Product Description

Exterior
The monitoring signal cable is black and has an RJ45 connector at each end, as shown in Figure
5-27.
Figure 5-27 Exterior of a monitoring signal cable

(1) RJ45 connector

Cable Description
Table 5-18 describes the pin assignment for the wires of a monitoring signal cable.
Table 5-18 Pin assignment for the wires of a monitoring signal cable
X1 End

X2 End

Description

X1.1

X2.1

Twisted pair

X1.2

X2.2

X1.3

X2.3

X1.6

X2.6

X1.4

X2.4

X1.5

X2.5

X1.7

X2.7

X1.8

X2.8

Issue Draft A (2012-9-15)

Huawei Proprietary and Confidential


Copyright Huawei Technologies Co., Ltd.

Twisted pair

Twisted pair

Twisted pair

160