REFERENCES ON COMPOSIT INSULATORS

isoelectric
ENEL S.p.A. (Italian Electric Company)
FERROVIE DELLO STATO S.p.A. (Italian Railways Company)
O.N.E. (National Office of the Electricity of Morocco)
TRANSELEC (Chilean Electric Company)
ENDESA (Spanish Electric Company)
TRINIDAD and TOBAGO ELECTRICITY CO.
FIJI ELECTRIC COMPANY CO.
U.T.E. (Uruguayan Electric Company )
SAESA (Chilean Electric Company)
RENFE (Spanish Railways)
S.N.C.B. (Belgian Railways)
TEIAS (Turkish Electric Company)
R.A.T.P. (Underground of Paris)
CEMIG (Brazilian Electric Company )
LUZ y FUERZA (Mexican Electric Company)
EDELNOR (Peruvian Electric Company )
P.P.C. (Grecian Electric Company)
COELBA (Brazilian Electric Company )
CONECTIV (Delaware - USA Electric Company)
UNION FENOSA (Spanish Electric Company)
TANESCO (Tanzanian Electric Company)
MANUFACTURERS of ELECTRIC EQUIPMENTS
Note: All the above references can be proved by documents. The above list includes
the firsts insulators installed in 1985 and it is revised to JANUARY 2011,
more than 26 years !!.

isoelectric - Italy
3

09-9

SILISOL
COMPOSITE INSULATORS IN SILICONE RUBBER
SILISOL, the composite SILICONE insulator, was born through a twenty years
experience of the isoelectric, which is the market leader in epoxy resin insulators, for
indoor use and in cycloaliphatic resin insulators, for outdoor use.

isoelectric work with ISO 9001-2008 certification.


In the last 35 years the trend of using technologies making use of composite materials
has been developed. These technologies, from a first application to indoor equipment,
extended successively to outdoor equipment, especially interesting the field of line
insulators of medium and high voltage.
The isoelectric, keeping into account the problems of using organic materials,
developed a high quality product with interesting mechanical and electrical features as
well as a good pollution resistance.

WHY THIS CHOICE ?

High mechanical strength in relation to weight.


High breaking points with limited overall dimensions.
High impact resistance (even against gunshots).
Reduced weight (from 10 to 300 times in relation to the traditional insulators).
High mechanical strength in relation to weight.
Lower transport costs.
Lower packing and storage costs.
Lower installation costs.
Lighter support mechanical structures.
Wider leakage distance with the same spark gap.
Higher discharge voltage in highly polluted environments.
Higher resistance to the power arc.
Higher ultra-violet (UV) radiation resistance.

The properties of hydrophobicity and corrosion-proof of the SILICONE keep the


outer casing of the insulators clean. These properties help the cleaning action of the rain
on the insulators and help to avoid damages of the salinity, of dusts and corrosion of the
industrial smokes improving the outer casing resistivity.

isoelectric - Italy
4

09-9

CONSTRUCTIVE COMPOSITION OF THE INSULATOR


The composite silicone insulators reinforced with ECR fibreglass rod have been
introduced because of the high mechanical stresses that post, suspension, tension and
mooring insulators are subjected to, allowing greater performances.
The SILISOL composite silicone insulators are constituted by 3 main elements:
1. A central rod in ECR fibreglass (corrosion resistant) impregnated with epoxy resin or
polyester resin.
2. A coating in silicone rubber that protects the central rod from external factors
(humidity, chemical contamination, and so on).
3. External metal end fittings that are used to transmit the mechanical stresses of the
electric line to the central rod.
A special care has to be taken in connecting the ECR fibreglass rod to the metal end
fittings. isoelectric has developed a system that allows having high bending, traction,
torsion and compression loads. Moreover this system allows eliminating water
penetration which happens in the usual execution of compression end fittings.
The SILISOL insulators are made of a central rod in ECR fibreglass impregnated
with epoxy resin or polyester resin and they must have 4 essential requisites:
The capacity to withstand mechanical stresses that come from a specific use.
Sufficient insulating properties to withstand, with an adequate safety-margin, the
electrical stresses of usage and those resulting from over voltages of internal and
external origin.
Power arc resistance.
Positive results at the tests according to the standard IEC 61109, IEC 61952,
IEC 62217, IEC 62231, AS 4435.4 & ANSI C29-11.
Even though the glass or porcelain insulators fully satisfy two of the above mentioned
requirements, they are not resistant to the power arcs caused by the power-cuts on the
lines.
The phenomenon of tracking is the main drawback of insulators made only with the
ECR fibreglass rod without any special additives and subjected to a certain determined
electrical gradient on the surface. This happens as a result of the simultaneous presence
of an electrical gradient between the metal endings of the insulator and the polluted
substances full of humidity on the external surface.

isoelectric - Italy
5

09-9

Taking this phenomenon into account isoelectric has applied an external housing of
suitable shape, made of a material with excellent dielectric features, a material that is
totally resistant to chemical attack and atmospheric agents.

THE SILICONE

SILIC 1.75

The adherence of the SILICONE housing to the ECR fibreglass rod is achieved by
particular methods that allow very high shearing values. By these methods, at an
interface level with the housing in SILICONE, a one piece injection moulding
(monolithic) construction has been obtained from one end fitting to the other end
fitting.
The SILICONE mixture is made of a pure 100% silicon polymer and filler. This
mixture is characterised by a great resistance to the superficial electrical discharges,
tracking, by a surface with permanent properties of hydrophobicity as well as by a
great insulating property under high pollution.

METALLIC END FITTINGS


The metallic end fittings placed at the end of the ECR fibreglass rod must have
sufficient mechanical features to take the stresses that insulators are subjected to. These
terminals can be manufactured in different shapes and materials, according to the IEC
60120, IEC 60471, and IEC 61466-1 standard and according to the characteristics
requested by the customer or their use. The terminals can be manufactured as follows:

forged steel C 30 or C 40, worked and then hot dip galvanised


casting steel C 30 or C 40, worked and then hot dip galvanised
forged aluminium and then worked
forged aluminium - bronze and then worked
casting aluminium, aluminium bronze or other alloys and then worked.

Shapes, dimensions and materials can agree every time, according to the customers
need too.

isoelectric - Italy
6

04-2

isoelectric
COMPOSITE INSULATORS ARE PRODUCED ACCORDING TO SAME OF THE
FOLLOWING STANDARDS

STANDARD
IEC 61109
Emend. 1

IEC 61952
IEC 61466-1
IEC 61466-2
Ed. 1.1 / 2002

IEC 60707
ANSI C29.11
AS 4435.4
I.E. TE 127
ASTM E 662
ASTM G 26
CEI 20-37
DIN 57441
IEEE Std 1024
IEC 60060-1
IEC 60071-1
IEC 60120
IEC 60273
IEC 60383
IEC 60471
IEC 60507
IEC 60815

DESCRIPTION
Composite insulators for overhead lines with a nominal voltage
greater than 1000 V.
Composite line post insulators for overhead lines with a nominal
voltage greater than 1000 V.
Composite string insulator unit for overhead lines,
part 1: standard strength classes and end fittings.
Composite string insulator unit for overhead lines,
part 2: dimensional and electrical characteristics
Test for flammability
Composite suspension insulators for overhead transmission lines
with voltages greater than 1000 V.
Composite line post insulators for overhead power lines.
Composite insulators I621 for contact railways lines with 3 kV dc
Test to determine the optical density of the smokes
Ageing test by ultra-violet rays ( UV )
Test to determine the toxicity and corrosion of the smokes
Accelerated ageing test in saline fog
Recommended practice for specifying distribution composite
insulators ( suspension type )
Methods of tests in high voltage
Insulation co-ordination
Dimensions of ball & socket couplings of string insulators units
Dimensions of post insulators for lines with voltages >1000 V
Tests on porcelain and glass insulators for lines >1000 V
Dimensions of the clevis and tongue couplings of string insulators
units
Artificial pollution test on H.V. insulators to be used in a.c. system
Guide for the selection of insulators in respect of polluted
conditions

The above said standards are taken as reference for design, production and testing.
Other standards can be taken into consideration according to the customers needs.

isoelectric - Italy
7

04-2

TESTS PERFORMED ACCORDING THE STANDARD

IEC 61109
Some tests were performed on some composite insulators SILISOL of the
according to the IEC 61109 standard, as follows:

PARAG.

DESCRIPTION

REPORT

5
5.1
5.1.1
5.1.2
5.1.3
5.1.3.1
5.1.3.2
5.1.3.3
5.1.4
5.1.4.1
5.1.4.2
5.1.4.3
5.2
5.2.1
5.2.2
5.2.2.1
5.2.2.2
5.3
5.3.1
5.3.2
5.3.3
5.3.4
5.4
5.4.1
5.4.1.1
5.4.1.2
5.4.1.3
5.4.2
5.4.2.1
5.4.2.2
5.4.2.3
5.5
5.5.1
5.5.2

Design tests
Tests on interfaces and connections of metal fittings
Test specimens and preliminary tests
Dry power frequency voltage test
Pre-stressing
Sudden load release test
Thermal-mechanical test
Water immersion test
Verification test
Visual examination
Steep-front impulse voltage test
Dry power frequency voltage test
Assembled core load-time test
Test specimens
Mechanical load test
Determ. ave. failing load of the core of the assem. ins.
Control strength-time curve slope of the insulator
Test of housing : tracking and erosion test
Test specimens duration of 1.000 & 5.000 hours
Test procedure
Test conditions
Evaluation of the test
Test for the core material
Dye penetration test
Test specimens
Performance of the test
Acceptance criterion
Water diffusion test
Test specimens
Pre-stressing
Voltage test
Flammability test
Test procedure
Evaluation of the test

6
6.1
6.2
6.4

Type tests
Dry lighting impulse withstand voltage test
Wet power - frequency test
Mechanical load-time test and test of the tightness of ....

isoelectric - Italy
8

isoelectric

04-2

TESTS
REPORT
OF
RECOGNIZED
LABORATORY
ARE
AVAILABLE
IN OUR
FIRM

Internal tests at
isoelectric

TESTS COMPARABLE TO THE STANDARD

ANSI C29.11
The isoelectric composite insulators SILISOL performed some tests were
comparable to the standard ANSI C29.11 as follows :

PARAG.
7
7.1
7.1.1
7.1.2
7.1.3
7.1.4
7.1.5
7.1.6
7.1.6.1
7.1.6.2
7.1.6.3
7.2
7.2.1
7.2.2
7.2.3
7.3
7.3.1
7.3.2
7.3.3
7.3.4
7.4
7.4.1
7.4.1.1
7.4.1.2
7.4.1.3
7.4.2
7.4.2.1
7.4.2.2
7.4.2.3
7.4.2.4
8
8.1
8.2
9.

DESCRIPTION

REPORT

Prototype tests
Test on interfaces and connection of end fittings
Test specimens and preliminary test
Dry power frequency voltage test
Sudden load release test
Thermal-mechanical test
Water penetration test
Verification test
Visual examination
Steep front impulse voltage test
Dry power frequency voltage test
Core time-load test
Test specimens
Test to determine the aver. failing load of the core
Control of the load-time slope of the insulators
Housing tracking and erosion test
Test specimens duration of 5000 hours
Test chamber
Test conditions
Evaluation of the test
Core material test
Dye penetration test
Test specimens
Performance of the test
Evaluation of the test
Water diffusion test
Test specimens
Pre-stressing
Voltage test
Acceptance criterion
Design test
Lighting critical - impulse flashover test
Wet power frequency test
All acceptance tests

isoelectric - Italy
9

04-2

TESTS
REPORT
OF
RECOGNIZED
LABORATORY
ARE
AVAILABLE
IN OUR
FIRM

Internal tests at
isoelectric

TESTS PERFORMED ACCORDING THE STANDARD

IEC 61952
Some tests were performed on some composite insulators SILISOL of the
isoelectric according to the IEC 61952 standard, as follows:

PARAG.

DESCRIPTION

6
6.1
6.2
6.2.1
6.2.2
6.2.2.1
6.2.2.2
6.2.3
6.2.3.1
6.2.3.2
6.2.3.3
6.3
6.3.1
6.3.2
6.4
6.4.1
6.4.2
6.4.3
6.4.3.1 a
6.4.3.1 b
6.4.4
6.5
6.5.1
6.5.1.1
6.5.1.2
6.5.2
6.5.2.1
6.5.2.2
6.5.2.3
7
7.1
7.2
7.2.1
7.2.2
7.2.3
7.2.4
7.3
7.3.1
8

Design tests
General
Tests on interfaces and connections of end fittings
Test specimens
Pre-stressing
Thermal-mechanical pre-stressing
Water immersion test
Verification tests
Visual examination
Steep-front impulse voltage test
Dry power frequency voltage test
Assembled core load-time tests
Test for verif. the Maximum Design Cantilever Load MDCL
Tensile load test
Test of sheds and housing material
Hardness test
Accelerated weathering test
Tracking and erosion test
Test specimens duration of 1000 hours
Test specimens duration of 5000 hours annex C
Flammability test acc. to IEC 60707
Test for the core material
Dye penetration test
Test procedure
Acceptance criteria
Water diffusion test
Test specimens
Pre-stressing
Voltage test
Type tests
Verification of dimensions
Electrical tests
Mounting arrangements
Dry lighting impulse withstand voltage test
Wet power - frequency test
Wet switching impulse withstand voltage test only >300 kV
Mechanical test
Cantilever failing load test
Sample test

isoelectric - Italy
10

REPORT

04-2

TESTS
REPORT
OF
RECOGNIZED
LABORATORY
ARE
AVAILABLE
IN OUR
FIRM

Internal tests at
isoelectric

TESTS PERFORMED ACCORDING TO OTHER STANDARDS


On some composite insulators SILISOL of the isoelectric some tests were
performed according to other standards as follows:

Standard ASTM C 542 Test for flammability


Standard ASTM E 662 Test to determine the optical density of the smokes
Standard ASTM G 26 Ageing tests using ultraviolet rays UV
Standard CEI 20-37 Smoke toxicity and corrosion test
Standard DIN 57441 Accelerated ageing test in saline fog
Standard IEEE Std 1024 Accelerated ageing test in saline fog
Standard AS 4435.4
Definition, test methods and acceptance criteria for post insulators units
Standard HN 66 S02 Power arc test
Standard IE.TE. 127 Test for railways post insulators (power arc test )
Standard IEC 507 Test for artificial pollution performance in H.V. insulators
80 kg/m of salt fog ( heavy pollution as for IEC 815 )
Standard IEC 507 Test for artificial pollution performance in H.V. insulators
224 kg/m of salt fog ( very heavy pollution as for IEC 815 )
Standard IEC K-2630/1 Test for power wash in H.V. composite insulators
In the enclosure 3 & 4 there are some extracts of the complete tests.
Tests performed according to standards or specifications in force in European and
world-wide Countries are not listed above because they have only a specific interest.

isoelectric, however, has performed tests and got homologations all over the world.

isoelectric - Italy
11

04-2

LIST OF TESTS THAT CAN BE PERFORMED AT OUR


LABORATORY

Dry power frequency test up to 200 kV


Wet power frequency test up to 200 kV
Air or oil discharge test up to 200 kV
Atmospheric lighting impulse test 1,2/50 s up to 400 kV
Atmospheric lighting impulse discharge test 1,2/50 s in oil and air up to 400 kV
Partial discharges test
Measure of the insulation resistance up to 2000 M, 1000 V
Accelerated ageing test in saline fog
Water penetration test
Test to verify the galvanisation thickness
Traction test up to 350 kN
Flexion test up to 160 kN
Compression test up to 160 kN
Torsion test up to 60 kN
Hibernation test up to - 55 C
Heat test up to + 250 C
Dimensional verifications test

isoelectric - Italy
12

04-2

SOME NOT STANDARDIZED TESTS


SHOOTING RESISTANCE TEST
Opposite to the fragile porcelain or glass, the composite insulators SILISOL of
isoelectric have a high resistance to mechanical shocks.
This property gives a substantially better performance in case of a severe mechanical
impact, such as a gunshot.
To study this behaviour the shooting resistance test was performed on MV and HV
insulators using the following firearms:
Revolver cal. 9 mm , distance 10/100 m
Rifle cal. 7,5 mm , distance 10/100 m
Rifle cal. 12/70 with a small bullet (3,5 g) , distance 10 m
Tests performed with a small bullet demonstrated that the bullets that struck in the outer
casing did not damage the fibreglass rod. Also the revolver shots at a distance of 10 m
did not damaged the fibreglass rod, while the bullets that struck the insulators at an
angle of 90 damaged the rod without impairing the good working of the insulators.
Porcelain or glass insulators - taken by comparison - exploded completely as soon as
they are struck.

HIBERNATION TEST IN NATURAL ENVIRONMENT AT -25 C


As you can note on the enclosures different kind of composed insulators were mounted
on the same support.
The white colour insulator at - 25C suffered the following drawback: the lower and the
upper end fittings were short-circuited as a result of the ice. This drawback is caused by
the roughness and scarce hydrophobicity of the insulating surface; consequently it keeps
the water that at a low temperature forms stalactites of ice.
This phenomenon doesnt happen with composite insulators
SILISOL of
isoelectric, because the surface has scarce hydrophobicity (like drops of mercury on
the table forming small balls) and having sloping sheds the water slips away very easily.
As you can see in the picture the ends of the sheds are covered only with light frost.
Then the white insulators were submitted to the power frequency test and partial
discharge test giving a negative result.
Composite insulators SILISOL in SILICONE of the isoelectric, because of the
hydrophobicity and elasticity of the coating give positive result without suffering
drawbacks.

isoelectric - Italy
13

04-2

CONCLUSIONS
Composite insulators SILISOL in SILICONE SILIC 1.75 of the isoelectric
have been installing for a long time, namely since June 1985, in many Countries both
on MV and HV lines.
The insulators installed are divided as follows:

Horizontal and vertical line post insulators MV and HV


Rod insulators for switch gear MV
Suspension, tension, long rod, dead end insulators MV and HV
Suspension insulators with horns gap MV
Pin insulators MV
Phase spacer insulators
Insulators for traction railways lines
Insulators for underground

Special applications (deflectors, insulated connections, additional sheds to lengthen the


leakage line of porcelain or glass insulators, etc.) and not least the realisation of
composite insulators for transformers in Sf6 gas up to 400 kV.
By the latest laboratory tests and by working the excellent features of the SILICONE
SILIC 1.75 of isoelectric have been demonstrated as a casing material for composite
insulators that can be used on distribution line MV and HV and on traction lines
especially in high pollution conditions.
All this constitutes an important stage towards the reduction in the use of traditional
insulators in favour of an ever growing use of composite insulators in SILICONE
SILIC 1.75 of the ISOELECTRIC.
Particular attention should be given when COMPACT LINES are planning where
the compactness of the composite insulator and its lightness constitute a great advantage
both for dimensional terms of the whole structure and during the installation phase.
Some drawings will be shown on isoelectric composite insulators that are parts of
the standard production.
However we are able to offer our customer all the solutions he asks us with any
features from 1 kV to 500 kV.
We shall be pleased if you contact us for any requests you need at our web site or
e-mail address :

www.isoelectric.it

info@isoelectric.it

isoelectric - Italy
14

04-2

SAME PICTURES OF THE OUR COMPOSITE INSULATORS


Type ISI-TWA

Type ISI-CAN

isoelectric - Italy
15

04-2

COMPOSITE INSULATORS END FITTINGS


All the end fittings listed in the table below refer to what is stated in IEC 61466-1 (02-1997) standard

TYPE

Code
BALL

B
SOCKET

70 kN

120 kN

160 kN

210 kN

Size 16

Size 16

Size 20

Size 20

IEC 60120

IEC 60120

IEC 60120

IEC 60120

Size 16

Size 16

Size 20

Size 20

IEC 60120

IEC 60120

IEC 60120

IEC 60120

Size 16N Size 19N Size 19N

TONGUE

A= 14.0
B= 20.0
C= 17.5

A= 16
B= 27
C= 24

A= 16
B= 27
C= 24

Size 16N Size 19N Size 19N


CLEVIS

Size 22N
A= 22
B= 26
C= 24

Size 22N

A= 18.0
B= 8.00
C= 34.8
D= 17.5

A= 23.0
B= 11.5
C= 38.0
D= 20.0

A= 23.0
B= 11.5
C= 38.0
D= 20.0

A= 26.0
B= 15.0
C= 43.0
D= 22.0

Size 17

Size 24

Size 24

Size 25

A= 44
B= 20
C= 31
D= 45
E= 12

A= 62
B= 26
C= 52
D= 70
E= 18

A= 62
B= 26
C= 52
D= 70
E= 18

A= 70
B= 26
C= 52
D= 74
E= 22

YCLEVIS

Size 16

Size 19

Size 22

Size 22

H= 40

H= 40

H= 40

H= 40

EYE

All this end fittings are in hot dip galvanized steel.

isoelectric - Italy
16

06-10

SILICONE DEAD END INSULATOR type ISI-CIN-* class 70 kN


Specified Mechanical Load (SML IEC 61109) = 70 kN

Line Voltage

Catalogue

kV

Code

10 12 15 25 ISI-CIN-A4+3-70CT

Routine Test Load (RTL IEC 61109) = 35 kN

n of
Sheds
A
n (1)

Length
L
5
mm

Leakage
distance

Dry arc
distance

mm

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

4+3

325

440

175

85

75

135

150

1,5

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50 Weight

NOTE : This insulator is produced and tested according to IEC 61109.

SILICONE DEAD END INSULATOR type ISI-LEN-* class 70 kN


This insulators performed 80 kg/m artificial salt pollution test.
Specified Mechanical Load (SML IEC 61109) = 70 kN

Line Voltage

Catalogue

kV

Code

10 12 15 25 ISI-LEN-A3+2-70TT

Routine Test Load (RTL IEC 61109) = 35 kN

n of
Sheds
A
n (1)

Length
L
5
mm

Leakage
distance

Dry arc
distance

mm

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

3+2

395

630

260

85

80

170

180

1,9

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50 Weight

NOTE : This insulator is produced and tested according to IEC 61109.


Please, don't hesitate to contact us directly for obtaining possible explanations or different solutions.

isoelectric - Italy
17

04-2

SILICONE DEAD END INSULATOR type ISI-MIG-* class 70 kN


This insulators performed 80 kg/m artificial salt pollution test.
Specified Mechanical Load (SML IEC 61109) = 70 kN

Routine Test Load (RTL IEC 61109) = 35 kN

ATTENTION :Same dimensions of 2 glass disc insulators


fittings
Line Voltage

Catalogue

kV

Code

10 12 15 25

ISI-MIG-A5-70CT

We can made this insulator with Tongue-Tongue

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

Dry arc
distance

mm

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

3+2

292

590

240

105

75

135

150

1,5

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50 Weight

NOTE : This insulator is produced and tested according to IEC 61109.

SILICONE DEAD END INSULATOR type ISI-TWE-* class 70 kN


This insulators performed 220 kg/m artificial salt pollution test.
Specified Mechanical Load (SML IEC 61109) = 70 kN

Routine Test Load (RTL IEC 61109) = 35 kN

We can made this insulator with Clevis-Tongue fittings


Line Voltage

Catalogue

kV

Code

10 12 15 25 ISI-TWE-A4+3-70TT

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

Dry arc
distance

mm

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

4+3

395

900

330

110

100

180

200

1,9

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50 Weight

NOTE : This insulator is produced and tested according to IEC 61109.

isoelectric - Italy
18

04-2

COMPOSITE DEAD END INSULATOR


in SILICONE RUBBER type ISI-SLY-* class 70 kN
Specified Mechanical Load (SML IEC 61109) = 70 kN

Routine Test Load (RTL IEC 61109) = 35 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)

12

17

24

36

Note: we can made this insulator with SML of 45 kN


Power
frequency

n of
Sheds

Length
L

Leakage
distance

Dry arc
distance

Code ()

A
n (1)

5
mm

mm

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

ISI-SLY-*
ISI-SLY-*
ISI-SLY-*
ISI-SLY-*
ISI-SLY-*
ISI-SLY-*
ISI-SLY-*
ISI-SLY-*

2
3
4
5
6
7
8
9

245
285
325
365
405
445
485
525

200
305
410
515
620
725
830
935

75
115
155
195
235
275
315
355

65
75
85
95
110
125
140
150

55
65
75
85
100
110
120
140

105
120
135
155
185
210
235
260

120
135
150
185
215
240
270
290

2,0
2,2
2,4
2,6
2,7
2,9
3,0
3,2

Catalogue

withstand 50-60 Hz

Lightning impul.
withstand 1,2/50

Weight

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
( see page 19 ) and refer to the following table :
Ground
fitting
CLEVIS
SOCKET
EYE
EYE
EYE
CLEVIS
SOCKET
Y- CLEVIS
Y- CLEVIS

Line
fitting
TONGUE
BALL
EYE
BALL
TONGUE
BALL
EYE
TONGUE
EYE

Code
(2)
CT
SB
EE
EB
ET
CB
SE
YT
YE

Length
change (L)
0
+45
+90
+60
+45
+15
+70
+45
+90

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
70 kN
35 kN
50 N*m

The metal fittings are in galvanized steel


() Key to the catalog numbers
* Key : ISI-SLY- A(1)-70(2)
Example : ISI-SLY-A4-70CT

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

isoelectric - Italy
19

06-10

COMPOSITE DEAD END INSULATOR in SILICONE RUBBER type


ISI-TIK-* class 70 kN
Specified Mechanical Load (SML IEC 61109) = 70 kN

Routine Test Load (RTL IEC 61109) = 35 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)
12

17

24

36

Catalogue
Code ()
ISI-TIK-*
ISI-TIK-*
ISI-TIK-*
ISI-TIK-*
ISI-TIK-*
ISI-TIK-*
ISI-TIK-*
ISI-TIK-*

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

2
3
4
5
6
7
8
9

305
345
385
425
465
505
545
585

260
380
500
620
740
860
980
1100

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

95
135
175
215
255
295
335
375

65
75
85
95
110
120
140
155

55
65
75
85
100
110
120
135

100
125
160
180
200
220
240
260

105
135
165
195
230
260
285
315

2,0
2,2
2,4
2,6
2,7
2,9
3,0
3,2

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
CLEVIS
EYE
EYE
EYE
CLEVIS
SOCKET
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
TONGUE
EYE
BALL
TONGUE
BALL
EYE
TONGUE
EYE

Code
(2)
SB
CT
EE
EB
ET
CB
SE
YT
YE

Length
change (L)
0
-40
+55
+20
+5
-25
+30
+5
+50

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
70 kN
35 kN
50 N*m

The metal fittings are in galvanized steel


() Key to the catalogue numbers
* Key : ISI-TIK- A(1)-70(2)
Example : ISI-TIK- A4-70SB

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations

isoelectric - Italy
20

06-10

COMPOSITE SUSPENSION or TENSION INSULATOR


in SILICONE RUBBER type ISI-BE-* class 70 kN
Specified Mechanical Load (SML IEC 1109) = 70 kN

Routine Test Load (RTL IEC 1109) = 35 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide

Catalogue
Code ()

(Line Voltage, kV)


12

17

24

36

45

52

ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*
ISI-BE-*

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

Dry arc
distance

mm

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

290
320
350
380
410
440
470
500
530
560
590
620
650
680
710
740
770
800
830
860

175
250
325
400
475
550
625
700
780
855
930
1005
1080
1160
1235
1310
1385
1460
1535
1610

80
110
140
170
200
230
260
290
320
350
380
410
440
470
500
530
560
590
620
650

40
50
60
70
80
90
100
115
125
135
145
155
170
180
190
200
215
225
235
245

35
45
55
65
75
85
90
100
110
120
130
140
155
165
175
185
200
210
220
230

70
90
100
115
135
150
160
170
190
200
220
235
255
275
290
305
320
345
360
370

80
100
120
160
180
200
210
220
235
250
275
285
305
325
340
355
380
405
420
445

2,0
2,2
2,4
2,6
2,7
2,9
3,0
3,2
3,4
3,5
3,7
3,9
4,0
4,2
4,4
4,5
4,7
4,9
5,0
5,2

Weight

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
( see page 19 ) and refer to the following table :
Ground
fitting
SOCKET
CLEVIS
EYE
EYE
EYE
CLEVIS
SOCKET
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
TONGUE
EYE
BALL
TONGUE
BALL
EYE
TONGUE
EYE

Code
(2)
SB
CT
EE
EB
ET
CB
SE
YT
YE

Length
change (L)
0
-40
+55
+20
+5
-25
+30
+5
+50

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
70 kN
35 kN
50 N*m

The metal fittings are in galvanized steel


() Key to the catalogue numbers
* Key : ISI-BE- A(1)-70(2)
Example : ISI-BE- A7-70SB
Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations

isoelectric - Italy
21

04-2

COMPOSITE SUSPENSION or TENSION INSULATOR


in SILICONE RUBBER type ISI-NL-* class 70 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide

Catalogue

(Line Voltage, kV)


12

17

24

36

45

52

Code ()
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

295
330
365
400
435
470
505
540
575
610
645
680
715
750
785
820
855
890
925
960

300
440
580
720
865
1005
1150
1290
1430
1575
1715
1860
2000
2140
2285
2425
2570
2710
2850
2995

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

85
120
155
190
225
260
295
330
365
400
435
470
505
540
575
610
645
680
715
750

60
70
85
100
110
125
140
150
165
175
190
200
215
230
240
255
270
280
295
305

50
60
70
80
95
105
120
130
140
155
165
180
190
200
215
225
240
250
260
275

105
130
150
170
195
215
240
260
280
305
325
350
370
390
415
435
460
480
500
525

130
150
175
200
220
245
265
290
315
335
360
380
405
430
450
475
495
520
545
565

2,0
2,2
2,4
2,6
2,7
2,9
3,0
3,2
3,4
3,5
3,7
3,9
4,0
4,2
4,4
4,5
4,7
4,9
5,0
5,2

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
CLEVIS
EYE
EYE
EYE
CLEVIS
SOCKET
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
TONGUE
EYE
BALL
TONGUE
BALL
EYE
TONGUE
EYE

Code
(2)
SB
CT
EE
EB
ET
CB
SE
YT
YE

Length
change (L)
0
-40
+55
+20
+5
-25
+30
+5
+50

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
70 kN
35 kN
90 N*m

The metal fittings are in galvanized steel


() Key to the catalogue numbers
* Key : ISI-NL- A(1)-70(2)
Example : ISI-NL-A7-70SB
Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations

isoelectric - Italy
22

04-2

COMPOSITE SUSPENSION or TENSION INSULATOR


in SILICONE RUBBER type ISI-NL-* class 120 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide

Catalogue

(Line Voltage, kV)


12

17

24

36

45

52

Code ()
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*
ISI-NL-*

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

Dry arc
distance

mm

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

385
420
455
490
525
560
595
630
665
700
735
770
805
840
875
910
945
980
1015
1050

300
440
580
720
865
1005
1150
1290
1430
1575
1715
1860
2000
2140
2285
2425
2570
2710
2850
2995

85
120
155
190
225
260
295
330
365
400
435
470
505
540
575
610
645
680
715
750

60
70
85
100
110
125
140
150
165
175
190
200
215
230
240
255
270
280
295
305

50
60
70
80
95
105
120
130
140
155
165
180
190
200
215
225
240
250
260
275

105
130
150
170
195
215
240
260
280
305
325
350
370
390
415
435
460
480
500
525

130
150
175
200
220
245
265
290
315
335
360
380
405
430
450
475
495
520
545
565

2,0
2,2
2,4
2,6
2,7
2,9
3,0
3,2
3,4
3,5
3,7
3,9
4,0
4,2
4,4
4,5
4,7
4,9
5,0
5,2

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
SOCKET
EYE
EYE
EYE
CLEVIS
CLEVIS
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
EYE
EYE
BALL
TONGUE
BALL
TONGUE
TONGUE
EYE

Code
(2)
SB
SE
EE
EB
ET
CB
CT
YT
YE

Length
change (L)
0
+35
+64
+29
+27
-8
-10
+15
+52

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
120 kN
60 kN
90 N*m

The metal fittings are in galvanized steel


() Key to the catalogue numbers
* Key : ISI-NL- A(1)-120(2)
Example : ISI-NL-A7-120SB
Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations

isoelectric - Italy
23

04-2

COMPOSITE SUSPENSION or TENSION INSULATOR


in SILICONE RUBBER type ISI-CAN-* class 70 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide

Catalogue

(Line Voltage, kV)


12

17

24

36

45

52

Code ()
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

305
345
385
425
465
505
545
585
625
665
705
745
785
825
865
905
945
985
1025
1065

255
370
485
600
715
830
945
1060
1175
1290
1405
1520
1635
1800
1915
2030
2150
2265
2380
2520

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

95
135
175
215
255
295
335
375
415
455
495
535
575
615
655
695
735
775
815
855

65
75
85
100
110
120
135
150
160
175
190
215
230
250
260
280
290
300
315
330

55
60
70
85
100
110
120
130
140
155
165
180
200
220
230
250
260
270
280
300

100
130
160
180
200
220
240
260
280
305
325
340
370
410
450
480
500
520
540
570

110
140
170
200
230
250
285
315
330
355
375
395
430
465
490
520
540
560
580
615

2,0
2,2
2,4
2,6
2,7
2,9
3,0
3,2
3,4
3,5
3,7
3,9
4,0
4,2
4,4
4,5
4,7
4,9
5,0
5,2

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
CLEVIS
EYE
EYE
EYE
CLEVIS
SOCKET
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
TONGUE
EYE
BALL
TONGUE
BALL
EYE
TONGUE
EYE

Code
(2)
SB
CT
EE
EB
ET
CB
SE
YT
YE

Length
change (L)
0
-40
+55
+20
+5
-25
+30
+5
+50

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
70 kN
35 kN
90 N*m

The metal fittings are in galvanized steel


() Key to the catalogue numbers
* Key : ISI-CAN- A(1)-70(2)
Example : ISI-CAN-A7-70SB
Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations

isoelectric - Italy
24

04-2

COMPOSITE SUSPENSION or TENSION INSULATOR


in SILICONE RUBBER type ISI-CAN-* class 120 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide

Catalogue

(Line Voltage, kV)


12

17

24

36

45

52

Code ()
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

395
435
475
515
555
595
635
675
715
755
795
835
875
915
955
995
1035
1075
1115
1155

255
370
485
600
715
830
945
1060
1175
1290
1405
1520
1635
1800
1915
2030
2150
2265
2380
2520

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

95
135
175
215
255
295
335
375
415
455
495
535
575
615
655
695
735
775
815
855

65
75
85
100
110
120
135
150
160
175
190
215
230
250
260
280
290
300
315
330

55
60
70
85
100
110
120
130
140
155
165
180
200
220
230
250
260
270
280
300

100
130
160
180
200
220
240
260
280
305
325
340
370
410
450
480
500
520
540
570

110
140
170
200
230
250
285
315
330
355
375
395
430
465
490
520
540
560
580
615

2,0
2,2
2,4
2,6
2,7
2,9
3,0
3,2
3,4
3,5
3,7
3,9
4,0
4,2
4,4
4,5
4,7
4,9
5,0
5,2

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
CLEVIS
EYE
EYE
EYE
CLEVIS
SOCKET
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
TONGUE
EYE
BALL
TONGUE
BALL
EYE
TONGUE
EYE

Code
(2)
SB
CT
EE
EB
ET
CB
SE
YT
YE

Length
change (L)
0
+35
+64
+29
+27
-8
-10
+15
+52

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
120 kN
60 kN
90 N*m

The metal fittings are in galvanized steel


() Key to the catalogue numbers
* Key : ISI-CAN- A(1)-120(2)
Example : ISI-CAN-A7-120SB
Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations

isoelectric - Italy
25

04-2

Accessories for Transmission Lines Composite Insulators


Corona Rings

All our composite insulators are RIV and corona free through 170 kV, but corona shielding is necessary above 200 kV.
From 200 kV up to 300 kV is necessary to use one corona ring dia. 205 mm on the live end.
From 300 kV up to 400 kV is necessary to use two corona rings, dia. 385 mm on the live end & dia. 205 on the ground end.
From 300 kV up to 400 kV is necessary to use two corona rings, dia. 385 mm on the live end & dia. 205 on the ground end.
From 400 kV up to 500 kV is necessary to use two corona rings, dia. 385 mm on the live end & ground end.
When a corona ring is used the electrical characteristics can change.
These information are only for reference, it is necessary to verify the hardware condition to have final decision.
In this case, please, contact isoelectric.

Clamp-top Clamp

Our clamp-top clamp can be mounted on the Horizontal & Vertical line post insulators, that have the VC or the HC top end
fitting.
The clamp-top clamp is in aluminium and can be used with conductors from 10 mm up to 36 mm diameter size.
Please, don't hesitate to contact us directly for obtaining possible explanations or different solutions.

isoelectric - Italy
26

04-2

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-PAN-* class 120 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)
72 123 145 170 250 400

Catalogue
Code ()
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

7
8
10
11
12
14
15
16
17
19
20
22
23
24
25
27
28
30
31
32

870
960
1140
1230
1320
1500
1590
1680
1770
1950
2040
2220
2310
2400
2490
2670
2760
2940
3030
3120

1360
1565
1975
2180
2385
2795
3000
3205
3410
3820
4025
4435
4640
4845
5050
5460
5665
6075
6280
6485

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

620
710
890
980
1070
1250
1340
1430
1520
1700
1790
1970
2060
2150
2240
2420
2510
2690
2780
2870

240
270
340
370
405
450
480
510
540
615
625
675
710
760
810
840
855
890
905
915

210
240
265
290
325
370
400
425
450
515
525
575
605
640
675
690
710
740
750
760

400
460
560
610
650
720
760
810
880
1000
1040
1140
1210
1270
1330
1370
1415
1520
1585
1620

445
500
610
660
705
780
825
880
950
1080
1110
1230
1310
1370
1430
1470
1515
1640
1715
1750

3,7
5,2
5,7
6,2
6,7
7,2
7,7
8,2
8,7
9,2
9,7
10,2
10,7
11,2
11,7
12,2
12,7
13,2
13,7
14,2

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
SOCKET
EYE
EYE
EYE
CLEVIS
CLEVIS
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
EYE
EYE
BALL
TONGUE
BALL
TONGUE
TONGUE
EYE

Code
(2)
SB
SE
EE
EB
ET
CB
CT
YT
YE

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

Length change (L)


From 0 up to -140
From +35 up to -105
From +65 up to -75
From +30 up to -110
From +30 up to -110
From +10 up to -130
From -10 up to -150
From +15 up to -125
From +50 up to -90

SML - IEC 61109


RTL = 50% of SML
120 kN
60 kN
90 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.
() Key to the catalogue numbers
* Key : ISI-PAN- A(1)-120(2)
Example : ISI-PAN-A20-120SB
Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions.

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

isoelectric - Italy
27

04-2

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-PAN-* class 160 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)
72 123 145 170 250 400

Catalogue
Code ()
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*
ISI-PAN-*

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

7
8
10
11
12
14
15
16
17
19
20
22
23
24
25
27
28
30
31
32

870
960
1140
1230
1320
1500
1590
1680
1770
1950
2040
2220
2310
2400
2490
2670
2760
2940
3030
3120

1360
1565
1975
2180
2385
2795
3000
3205
3410
3820
4025
4435
4640
4845
5050
5460
5665
6075
6280
6485

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

620
710
890
980
1070
1250
1340
1430
1520
1700
1790
1970
2060
2150
2240
2420
2510
2690
2780
2870

240
270
340
370
405
450
480
510
540
615
625
675
710
760
810
840
855
890
905
915

210
240
265
290
325
370
400
425
450
515
525
575
605
640
675
690
710
740
750
760

400
460
560
610
650
720
760
810
880
1000
1040
1140
1210
1270
1330
1370
1415
1520
1585
1620

445
500
610
660
705
780
825
880
950
1080
1110
1230
1310
1370
1430
1470
1515
1640
1715
1750

3,7
5,2
5,7
6,2
6,7
7,2
7,7
8,2
8,7
9,2
9,7
10,2
10,7
11,2
11,7
12,2
12,7
13,2
13,7
14,2

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
SOCKET
EYE
EYE
EYE
CLEVIS
CLEVIS
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
EYE
EYE
BALL
TONGUE
BALL
TONGUE
TONGUE
EYE

Code
(2)
SB
SE
EE
EB
ET
CB
CT
YT
YE

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

Length change (L)


From 0 up to -140
From +35 up to -105
From +65 up to -75
From +30 up to -110
From +30 up to -110
From +10 up to -130
From -10 up to -150
From +15 up to -125
From +50 up to -90

SML - IEC 61109


RTL = 50% of SML
160 kN
80 kN
90 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.
() Key to the catalogue numbers
* Key : ISI-PAN- A(1)-160(2)
Example : ISI-PAN-A20-160SB
Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions.

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

isoelectric - Italy
28

04-2

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-CAN-* class 70 kN

S solution

R solution

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)
72 123 145 170 250 400

Note: It's possible to have intermediate numbers of sheds

Catalogue
Code ()
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

15
18
21
24
27
30
33
36
39
42
45
48
51
54
57
60
63
66
69
72

825
945
1065
1185
1305
1425
1545
1665
1785
1905
2025
2145
2265
2385
2505
2625
2745
2865
2985
3105

1800
2150
2520
2870
3240
3605
3950
4320
4690
5050
5410
5790
6140
6500
6860
7220
7570
7930
8290
8650

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

615
735
855
975
1095
1215
1335
1455
1575
1695
1815
1935
2055
2175
2295
2415
2535
2655
2775
2895

250
290
340
380
415
450
485
520
565
615
645
675
710
760
810
860
875
890
905
920

220
260
265
300
335
370
405
435
475
515
545
575
605
640
675
710
720
740
750
760

410
500
570
620
670
720
770
830
915
1000
1070
1140
1210
1270
1330
1390
1455
1520
1585
1650

465
540
615
670
725
780
835
900
990
1080
1155
1230
1310
1370
1430
1490
1565
1640
1715
1800

4,2
4,7
5,2
5,7
6,2
6,7
7,2
7,7
8,2
8,7
9,2
9,7
10,2
10,7
11,2
11,7
12,2
12,7
13,2
13,7

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
CLEVIS
EYE
EYE
EYE
CLEVIS
SOCKET
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
TONGUE
EYE
BALL
TONGUE
BALL
EYE
TONGUE
EYE

Code
(2)
SB
CT
EE
EB
ET
CB
SE
YT
YE

Length
change (L)
0
-40
+55
+20
+5
-25
+30
+5
+50

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
70 kN
35 kN
90 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.
() Key to the catalogue numbers
* Key : ISI-CAN- A(1)-70(2)
Example : ISI-CAN-A39-70SB

S solution = standard solution with uncovered fittings

R solution = fittings partially covered with silicone rubber


Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions.

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

isoelectric - Italy
29

04-2

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-CAN-* class 120 kN

S solution

R solution

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)
72 123 145 170 250 400

Note: It's possible to have intermediate numbers of sheds

Catalogue
Code ()
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

15
18
21
24
27
30
33
36
39
42
45
48
51
54
57
60
63
66
69
72

915
1035
1155
1275
1395
1515
1635
1755
1875
1995
2115
2235
2355
2475
2595
2715
2835
2955
3075
3195

1800
2150
2520
2870
3240
3605
3950
4320
4690
5050
5410
5790
6140
6500
6860
7220
7570
7930
8290
8650

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

615
735
855
975
1095
1215
1335
1455
1575
1695
1815
1935
2055
2175
2295
2415
2535
2655
2775
2895

250
290
340
380
415
450
485
520
565
615
645
675
710
760
810
860
875
890
905
920

220
260
265
300
335
370
405
435
475
515
545
575
605
640
675
710
720
740
750
760

410
500
570
620
670
720
770
830
915
1000
1070
1140
1210
1270
1330
1390
1455
1520
1585
1650

465
540
615
670
725
780
835
900
990
1080
1155
1230
1310
1370
1430
1490
1565
1640
1715
1800

4,2
4,7
5,2
5,7
6,2
6,7
7,2
7,7
8,2
8,7
9,2
9,7
10,2
10,7
11,2
11,7
12,2
12,7
13,2
13,7

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
CLEVIS
EYE
EYE
EYE
CLEVIS
SOCKET
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
TONGUE
EYE
BALL
TONGUE
BALL
EYE
TONGUE
EYE

Code
(2)
SB
CT
EE
EB
ET
CB
SE
YT
YE

Length
change (L)
0
-10
+64
+29
+27
-8
-10
+15
+52

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
120 kN
60 kN
90 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.
() Key to the catalogue numbers
* Key : ISI-CAN- A(1)-120(2)
Example : ISI-CAN-A39-120SB

S solution = standard solution with uncovered fittings

R solution = fittings partially covered with silicone rubber


Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions.

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

isoelectric - Italy
30

04-2

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-CAN-* class 160 kN or class 210 kN

S solution

R solution

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)
72 123 145 170 250 400

Note: It's possible to have intermediate numbers of sheds

Catalogue
Code ()
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*
ISI-CAN-*

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

15
18
21
24
27
30
33
36
39
42
45
48
51
54
57
60
63
66
69
72

925
1045
1165
1285
1405
1525
1645
1765
1885
2005
2125
2245
2365
2485
2605
2725
2845
2965
3085
3205

1800
2150
2520
2870
3240
3605
3950
4320
4690
5050
5410
5790
6140
6500
6860
7220
7570
7930
8290
8650

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

615
735
855
975
1095
1215
1335
1455
1575
1695
1815
1935
2055
2175
2295
2415
2535
2655
2775
2895

250
290
340
380
415
450
485
520
565
615
645
675
710
760
810
860
875
890
905
920

220
260
265
300
335
370
405
435
475
515
545
575
605
640
675
710
720
740
750
760

410
500
570
620
670
720
770
830
915
1000
1070
1140
1210
1270
1330
1390
1455
1520
1585
1650

465
540
615
670
725
780
835
900
990
1080
1155
1230
1310
1370
1430
1490
1565
1640
1715
1800

4,2
4,7
5,2
5,7
6,2
6,7
7,2
7,7
8,2
8,7
9,2
9,7
10,2
10,7
11,2
11,7
12,2
12,7
13,2
13,7

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
SOCKET
EYE
EYE
EYE
CLEVIS
CLEVIS
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
EYE
EYE
BALL
TONGUE
BALL
TONGUE
TONGUE
EYE

Code
(2)
SB
SE
EE
EB
ET
CB
CT
YT
YE

Length
change (L)
0
+25
+54
+19
+17
+2
0
+5
+42

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
160 kN
210 kN
80 kN
105 kN
120 N*m 120 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.
() Key to the catalogue numbers
* Key : ISI-CAN- A(1)-(160 or 210)(2)
Example : ISI-CAN-A63-(160 or 210)SB

S solution = standard solution with uncovered fittings

R solution = fittings partially covered with silicone rubber


Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions.

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

isoelectric - Italy
31

04-2

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-ROK-* class 70 kN

S solution

R solution

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)
72 123 145 170 250 400

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Catalogue
Code ()

Length
L
10
mm

Leakage
distance

mm

Dry arc
distance

mm

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Dry
kV

Wet
kV

posit.
kV

negat.
kV

Weight

kg

ISI-ROK-*
9+8
850
2270
640
275
195
460
495
4,4
ISI-ROK-*
10+9
920
2530
710
310
230
515
550
4,9
ISI-ROK-*
12+11 1060
3050
850
340
265
570
615
5,4
ISI-ROK-*
14+13 1200
3570
990
380
300
620
670
5,9
ISI-ROK-*
15+14 1270
3830
1060
415
335
670
725
6,4
ISI-ROK-*
17+16 1410
4350
1200
450
370
720
780
6,9
ISI-ROK-*
19+18 1550
4870
1340
485
405
770
835
7,4
ISI-ROK-*
21+20 1690
5390
1480
520
435
830
900
7,9
ISI-ROK-*
22+21 1760
5650
1550
565
475
915
990
8,4
ISI-ROK-*
24+23 1900
6170
1690
615
515
1000
1080
8,9
ISI-ROK-*
26+25 2040
6690
1830
645
545
1070
1155
9,4
ISI-ROK-*
27+26 2110
6950
1900
675
575
1140
1230
9,7
ISI-ROK-*
29+28 2250
7470
2040
710
605
1210
1310
10,4
ISI-ROK-*
31+30 2390
8100
2180
760
640
1270
1370
10,9
ISI-ROK-*
33+32 2530
8620
2320
810
675
1330
1430
11,4
ISI-ROK-*
35+34 2670
9180
2460
860
710
1390
1490
11,9
ISI-ROK-*
36+35 2740
9440
2530
875
720
1455
1565
12,4
ISI-ROK-*
38+37 2880
9990
2670
890
740
1520
1640
12,9
ISI-ROK-*
42+41 3160
11000
2950
920
760
1650
1800
13,9
NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table:
Ground
fitting
SOCKET
CLEVIS
EYE
EYE
EYE
CLEVIS
SOCKET
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
TONGUE
EYE
BALL
TONGUE
BALL
EYE
TONGUE
EYE

Code
(2)
SB
CT
EE
EB
ET
CB
SE
YT
YE

Length
change (L)
0
-40
+55
+20
+5
-25
+30
+5
+50

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
70 kN
35 kN
90 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.
() Key to the catalogue numbers
* Key : ISI-ROK- A(1)-70(2)
Example : ISI-ROK-A22+21-70SB

S solution = standard solution with uncovered fittings

R solution = fittings partially covered with silicone rubber

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
32

04-2

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-ROK-* class 120 kN

S solution

R solution

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)
72 123 145 170 250 400

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Catalogue
Code ()

Length
L
10
mm

Leakage
distance

mm

Dry arc
distance

mm

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Dry
kV

Wet
kV

posit.
kV

negat.
kV

Weight

kg

ISI-ROK-*
9+8
940
2270
640
275
195
460
495
4,4
ISI-ROK-*
10+9
1010
2530
710
310
230
515
550
4,9
ISI-ROK-*
12+11 1150
3050
850
340
265
570
615
5,4
ISI-ROK-*
14+13 1290
3570
990
380
300
620
670
5,9
ISI-ROK-*
15+14 1360
3830
1060
415
335
670
725
6,4
ISI-ROK-*
17+16 1500
4350
1200
450
370
720
780
6,9
ISI-ROK-*
19+18 1640
4870
1340
485
405
770
835
7,4
ISI-ROK-*
21+20 1780
5390
1480
520
435
830
900
7,9
ISI-ROK-*
22+21 1850
5650
1550
565
475
915
990
8,4
ISI-ROK-*
24+23 1990
6170
1690
615
515
1000
1080
8,9
ISI-ROK-*
26+25 2130
6690
1830
645
545
1070
1155
9,4
ISI-ROK-*
27+26 2200
6950
1900
675
575
1140
1230
9,7
ISI-ROK-*
29+28 2340
7470
2040
710
605
1210
1310
10,4
ISI-ROK-*
31+30 2480
8100
2180
760
640
1270
1370
10,9
ISI-ROK-*
33+32 2620
8620
2320
810
675
1330
1430
11,4
ISI-ROK-*
35+34 2760
9180
2460
860
710
1390
1490
11,9
ISI-ROK-*
36+35 2830
9440
2530
875
720
1455
1565
12,4
ISI-ROK-*
38+37 2970
9990
2670
890
740
1520
1640
12,9
ISI-ROK-*
42+41 3250
11000
2950
920
760
1650
1800
13,9
NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
CLEVIS
EYE
EYE
EYE
CLEVIS
SOCKET
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
TONGUE
EYE
BALL
TONGUE
BALL
EYE
TONGUE
EYE

Code
(2)
SB
CT
EE
EB
ET
CB
SE
YT
YE

Length
change (L)
0
-10
+64
+29
+27
-8
-10
+15
+52

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
120 kN
60 kN
90 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.
() Key to the catalogue numbers
* Key : ISI-ROK- A(1)-120(2)
Example : ISI-ROK-A22+21-120SB

S solution = standard solution with uncovered fittings

R solution = fittings partially covered with silicone rubber

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
33

06-10

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-ROK-* class 160 kN or class 210 kN

S solution

R solution

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)
72 123 145 170 250 400

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Catalogue
Code ()

Length
L
10
mm

Leakage
distance

mm

Dry arc
distance

mm

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Dry
kV

Wet
kV

posit.
kV

negat.
kV

Weight

kg

ISI-ROK-*
9+8
950
2270
640
275
195
460
495
4,4
ISI-ROK-*
10+9
1020
2530
710
310
230
515
550
4,9
ISI-ROK-*
12+11 1160
3050
850
340
265
570
615
5,4
ISI-ROK-*
14+13 1300
3570
990
380
300
620
670
5,9
ISI-ROK-*
15+14 1370
3830
1060
415
335
670
725
6,4
ISI-ROK-*
17+16 1510
4350
1200
450
370
720
780
6,9
ISI-ROK-*
19+18 1650
4870
1340
485
405
770
835
7,4
ISI-ROK-*
21+20 1790
5390
1480
520
435
830
900
7,9
ISI-ROK-*
22+21 1860
5650
1550
565
475
915
990
8,4
ISI-ROK-*
24+23 2000
6170
1690
615
515
1000
1080
8,9
ISI-ROK-*
26+25 2140
6690
1830
645
545
1070
1155
9,4
ISI-ROK-*
27+26 2210
6950
1900
675
575
1140
1230
9,7
ISI-ROK-*
29+28 2350
7470
2040
710
605
1210
1310
10,4
ISI-ROK-*
31+30 2490
8100
2180
760
640
1270
1370
10,9
ISI-ROK-*
33+32 2630
8620
2320
810
675
1330
1430
11,4
ISI-ROK-*
35+34 2770
9180
2460
860
710
1390
1490
11,9
ISI-ROK-*
36+35 2840
9440
2530
875
720
1455
1565
12,4
ISI-ROK-*
38+37 2980
9990
2670
890
740
1520
1640
12,9
ISI-ROK-*
42+41 3260
11000
2950
920
760
1650
1800
13,9
NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
SOCKET
EYE
EYE
EYE
CLEVIS
CLEVIS
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
EYE
EYE
BALL
TONGUE
BALL
TONGUE
TONGUE
EYE

Code
(2)
SB
SE
EE
EB
ET
CB
CT
YT
YE

Length
change (L)
0
+25
+54
+19
+17
+2
0
+5
+42

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
160 kN
210 kN
80 kN
105 kN
120 N*m 120 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.
() Key to the catalogue numbers
* Key : ISI-ROK- A(1)-(160 or 210)(2)
Example : ISI-ROK-A22+21-(160 or 210)SB

S solution = standard solution with uncovered fittings

R solution = fittings partially covered with silicone rubber

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
34

04-2

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-TWA-* class 120 kN

S solution

R solution

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)
72 123 145 170 250 400

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Catalogue
Code ()

Length Leakage Dry arc Power frequency


distance distance withstand 50-60 Hz
L
Dry
Wet
10
mm
mm
kV
kV
mm

Lightning impul.
withstand 1,2/50

posit.
kV

negat.
kV

Weight

kg

ISI-TWA-*
8+7
890
2600
590
260
180
435
470
5,2
ISI-TWA-*
9+8
965
2950
665
285
200
475
510
5,7
ISI-TWA-*
12+11 1190
4000
890
355
280
585
630
6,2
ISI-TWA-*
13+12 1265
4300
965
380
300
620
670
6,7
ISI-TWA-*
16+15 1490
5330
1190
435
355
720
760
7,2
ISI-TWA-*
17+16 1565
5680
1265
460
380
740
795
7,7
ISI-TWA-*
18+17 1640
6000
1340
485
405
770
835
8,2
ISI-TWA-*
20+19 1790
6700
1490
525
440
840
910
8,7
ISI-TWA-*
21+20 1865
7010
1565
565
475
915
990
9,2
ISI-TWA-*
23+22 2015
7720
1715
620
520
1010
1100
9,7
ISI-TWA-*
25+24 2165
8400
1865
645
545
1050
1155
10,2
ISI-TWA-*
26+25 2240
8750
1940
675
575
1140
1230
10,7
ISI-TWA-*
27+26 2315
9100
2015
715
615
1215
1310
11,2
ISI-TWA-*
29+28 2465
9780
2165
760
640
1270
1370
11,7
ISI-TWA-*
31+30 2615 10500
2315
815
680
1340
1440
12,2
ISI-TWA-*
32+31 2690 10800
2390
850
700
1370
1470
12,7
ISI-TWA-*
34+33 2840 11480
2540
875
720
1455
1565
13,2
ISI-TWA-*
36+35 2990 12200
2690
895
745
1530
1650
13,7
ISI-TWA-*
37+36 3065 12510
2765
900
745
1580
1710
14,2
ISI-TWA-*
40+39 3290 13600
2990
950
790
1700
1840
14,7
NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
SOCKET
EYE
EYE
EYE
CLEVIS
CLEVIS
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
EYE
EYE
BALL
TONGUE
BALL
TONGUE
TONGUE
EYE

Code
(2)
SB
SE
EE
EB
ET
CB
CT
YT
YE

Length
change (L)
0
-10
+64
+29
+27
-8
-10
+15
+52

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
120 kN
60 kN
90 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.
() Key to the catalogue numbers
* Key : ISI-TWA- A(1)-120(2)
Example : ISI-TWA-A21+20-120SB

S solution = standard solution with uncovered fittings

R solution = fittings partially covered with silicone rubber

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
35

06-10

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-TWA-* class 160 kN or class 210 kN

S solution

R solution

Dimensions tolerance acc. to IEC 61109

Selection Guide
(Line Voltage, kV)
72 123 145 170 250 400

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Catalogue
Code ()

Length Leakage Dry arc Power frequency


distance distance withstand 50-60 Hz
L
Dry
Wet
10
mm
mm
kV
kV
mm

Lightning impul.
withstand 1,2/50

posit.
kV

negat.
kV

Weight

kg

ISI-TWA-*
8+7
900
2600
590
260
180
435
470
5,2
ISI-TWA-*
9+8
975
2950
665
285
200
475
510
5,7
ISI-TWA-*
12+11 1200
4000
890
355
280
585
630
6,2
ISI-TWA-*
13+12 1275
4300
965
380
300
620
670
6,7
ISI-TWA-*
16+15 1500
5330
1190
435
355
720
760
7,2
ISI-TWA-*
17+16 1575
5680
1265
460
380
740
795
7,7
ISI-TWA-*
18+17 1650
6000
1340
485
405
770
835
8,2
ISI-TWA-*
20+19 1800
6700
1490
525
440
840
910
8,7
ISI-TWA-*
21+20 1875
7010
1565
565
475
915
990
9,2
ISI-TWA-*
23+22 2025
7720
1715
620
520
1010
1100
9,7
ISI-TWA-*
25+24 2175
8400
1865
645
545
1050
1155
10,2
ISI-TWA-*
26+25 2250
8750
1940
675
575
1140
1230
10,7
ISI-TWA-*
27+26 2325
9100
2015
715
615
1215
1310
11,2
ISI-TWA-*
29+28 2475
9780
2165
760
640
1270
1370
11,7
ISI-TWA-*
31+30 2625 10500
2315
815
680
1340
1440
12,2
ISI-TWA-*
32+31 2700 10800
2390
850
700
1370
1470
12,7
ISI-TWA-*
34+33 2850 11480
2540
875
720
1455
1565
13,2
ISI-TWA-*
36+35 3000 12200
2690
895
745
1530
1650
13,7
ISI-TWA-*
37+36 3075 12510
2765
900
745
1580
1710
14,2
ISI-TWA-*
40+39 3300 13600
2990
950
790
1700
1840
14,7
NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
SOCKET
EYE
EYE
EYE
CLEVIS
CLEVIS
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
EYE
EYE
BALL
TONGUE
BALL
TONGUE
TONGUE
EYE

Code
(2)
SB
SE
EE
EB
ET
CB
CT
YT
YE

Length
change (L)
0
+25
+54
+19
+17
+2
0
+5
+42

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
160 kN
210 kN
80 kN
105 kN
120 N*m 120 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.
() Key to the catalogue numbers
* Key : ISI-TWA- A(1)-(160 or 210)(2)
Example : ISI-TWA-A22+21-(160 or 210)SB

S solution = standard solution with uncovered fittings

R solution = fittings partially covered with silicone rubber

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
36

04-2

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-TWX-* class 120 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide

Catalogue

(Line Voltage, kV)


220 345 420 530 620 700 765

Code ()
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

30+29
33+32
36+35
40+39
42+41
46+45
50+49
52+51
55+54
58+57
61+60
64+63
67+66
70+69
73+72
76+75
79+78
82+81
85+84
93+92

1965
2125
2290
2505
2610
2825
3040
3150
3310
3475
3635
3800
3960
4125
4285
4450
4610
4770
4935
5365

7300
8040
8780
9760
10250
11200
12210
12700
13400
14150
14900
15640
16370
17100
17800
18580
19300
20050
20785
22500

Dry arc
distance

Power frequency Lightning impul.


withstand 50 Hz withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

1705
1865
2030
2245
2350
2565
2780
2890
3050
3215
3375
3540
3700
3865
4025
4190
4350
4510
4675
5105

610
645
700
740
815
865
900
950
1000
1040
1090
1110
1140
1170
1200
1220
1250
1280
1310
1460

510
545
595
620
660
710
750
830
900
950
1000
1030
1050
1075
1100
1130
1150
1175
1200
1310

990
1050
1200
1250
1340
1475
1570
1610
1700
1780
1860
1980
2030
2110
2220
2260
2400
2500
2590
2890

1070
1155
1300
1350
1440
1585
1720
1790
1850
1900
1950
2090
2110
2205
2300
2350
2520
2610
2720
3040

9.5
10.3
11.3
12.3
13.3
14.3
15.3
16.3
17.3
18.3
19.3
20.3
21.3
22.3
23.3
24.3
25.3
26.3
27.3
29.5

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), select the kind of fitting end you have to use (see page 19)
and refer to the following table :
Ground
fitting
SOCKET
CLEVIS
EYE
Y- CLEVIS
EYE
CLEVIS

Line
fitting
BALL
TONGUE
EYE
TONGUE
BALL
BALL

Code
(2)
SB
CT
EE
YT
EB
CB

Length
change (L)
0
-10
+70
+15
+29
-8

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
120 kN
60 kN
120 N*m

() Key to the catalog numbers


* Key : ISI-TWX- A(1)-120(2)
Example : ISI-TWX-A50-120SB

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
37

09-1

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-TWX-* class 160 kN or class 210 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide

Catalogue

(Line Voltage, kV)


220 345 420 530 620 700 765

Code ()
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*
ISI-TWX-*

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

30+29
33+32
36+35
40+39
42+41
46+45
50+49
52+51
55+54
58+57
61+60
64+63
67+66
70+69
73+72
76+75
79+78
82+81
85+84
93+92

1980
2140
2305
2520
2625
2840
3055
3165
3325
3490
3650
3815
3975
4140
4300
4465
4625
4785
4950
5380

7300
8040
8780
9760
10250
11200
12210
12700
13400
14150
14900
15640
16370
17100
17800
18580
19300
20050
20785
22500

Dry arc
distance

Power frequency Lightning impul.


withstand 50 Hz withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

1705
1865
2030
2245
2350
2565
2780
2890
3050
3215
3375
3540
3700
3865
4025
4190
4350
4510
4675
5105

610
645
700
740
815
865
900
950
1000
1040
1090
1110
1140
1170
1200
1220
1250
1280
1310
1460

510
545
595
620
660
710
750
830
900
950
1000
1030
1050
1075
1100
1130
1150
1175
1200
1310

990
1050
1200
1250
1340
1475
1570
1610
1700
1780
1860
1980
2030
2110
2220
2260
2400
2500
2590
2890

1070
1155
1300
1350
1440
1585
1720
1790
1850
1900
1950
2090
2110
2205
2300
2350
2520
2610
2720
3040

9.5
10.3
11.3
12.3
13.3
14.3
15.3
16.3
17.3
18.3
19.3
20.3
21.3
22.3
23.3
24.3
25.3
26.3
27.3
29.5

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), select the kind of fitting end you have to use (see page 19)
and refer to the following table :
Ground
fitting
SOCKET- 20
CLEVIS
EYE 25
EYE 25
CLEVIS

Line
fitting
BALL - 20
TONGUE
EYE 25
BALL 20
BALL - 20

Code
(2)
SB
CT
EE
EB
CB

Length
change (L)
0
+10
+100
+45
-8

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
160 kN
210 kN
80 kN
105 kN
120 N*m 120 N*m

() Key to the catalog numbers


* Key : ISI-TWX- A(1)-(160 or 210)(2)
Example : ISI-TWX-A50-(160 or 210)SB

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
38

09-1

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-SOR-* class 210 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide

Catalogue

(Line Voltage, kV)


115 145 170 250 345 420 500

Code ()
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

10+9
11+10
13+12
14+13
15+14
17+16
18+17
19+18
21+20
22+21
23+22
24+23
26+25
27+26
29+28
33+32
35+34
38+37
42+41
48+47

1225
1315
1495
1585
1675
1855
1945
2035
2215
2305
2395
2485
2665
2755
2935
3295
3475
3745
4110
4645

2910
3210
3805
4100
4400
5000
5295
5590
6190
6490
6785
7080
7680
7975
8570
9760
10360
11150
12400
14200

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

915
1005
1185
1275
1365
1545
1635
1725
1905
1995
2085
2175
2355
2445
2625
2985
3165
3435
3800
4335

350
380
415
455
480
525
570
610
645
685
700
740
815
845
865
900
930
960
1140
1280

275
300
335
375
400
440
480
510
545
585
595
620
660
685
710
750
780
820
1020
1100

580
620
670
725
765
840
920
990
1050
1150
1200
1250
1340
1380
1475
1670
1730
1780
2030
2400

625
670
725
785
830
910
995
1070
1155
1240
1300
1350
1440
1480
1585
1820
1860
1930
2110
2510

7,2
7,7
8,2
8,7
9,2
9,7
10,2
10,7
11,2
11,7
12,2
12,7
13,2
13,7
14,2
15,7
18.2
20.7
22.8
23.6

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
SOCKET
EYE
EYE
EYE
CLEVIS
CLEVIS
Y- CLEVIS
Y- CLEVIS

Line
fitting
BALL
EYE
EYE
BALL
TONGUE
BALL
TONGUE
TONGUE
EYE

Code
(2)
SB
SE
EE
EB
ET
CB
CT
YT
YE

Length
change (L)
0
+40
+70
+30
+40
0
+10
+20
+50

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
210 kN
105 kN
160 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.
() Key to the catalogue numbers
* Key : ISI-SOR- A(1)-210(2)
Example : ISI-SOR-A21+20-210SB
Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions.

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

isoelectric - Italy
39

04-2

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-SOR-* class 300 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide

Catalogue

(Line Voltage, kV)


115 145 170 250 345 420 500

Code ()
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*
ISI-SOR-*

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

10+9
11+10
13+12
14+13
15+14
17+16
18+17
19+18
21+20
22+21
23+22
24+23
26+25
27+26
29+28
33+32
35+34
38+37
42+41
48+47

1325
1415
1595
1685
1775
1955
2045
2135
2315
2405
2495
2585
2765
2855
3035
3395
3575
3845
4210
4745

2910
3210
3805
4100
4400
5000
5295
5590
6190
6490
6785
7080
7680
7975
8570
9760
10360
11150
12400
14200

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

915
1005
1185
1275
1365
1545
1635
1725
1905
1995
2085
2175
2355
2445
2625
2985
3165
3435
3800
4335

350
380
415
455
480
525
570
610
645
685
700
740
815
845
865
900
930
960
1140
1280

275
300
335
375
400
440
480
510
545
585
595
620
660
685
710
750
780
820
1020
1100

580
620
670
725
765
840
920
990
1050
1150
1200
1250
1340
1380
1475
1670
1730
1780
2030
2400

625
670
725
785
830
910
995
1070
1155
1240
1300
1350
1440
1480
1585
1820
1860
1930
2110
2510

7,2
7,7
8,2
8,7
9,2
9,7
10,2
10,7
11,2
11,7
12,2
12,7
13,2
13,7
14,2
15,7
18.2
20.7
22.8
23.6

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
SOCKET
CLEVIS
SOCKET
CLEVIS

Line
fitting
BALL
BALL
TONGUE
TONGUE

Code
(2)
SB
CB
ST
CT

Length
change (L)
0
0
0
0

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
300 kN
155 kN
200 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.

Socket and Ball are size 24 acc. to IEC 60120


Clevis and Tongue are size 25L acc. to IEC 60471

() Key to the catalogue numbers


* Key : ISI-SOR- A(1)-300(2)
Example : ISI-SOR-A21+20-300SB
Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions.

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

isoelectric - Italy
40

04-2

Transmission Composite Suspension - Tension Insulators


in Silicone Rubber type ISI-TEN-* class 360 kN

Dimensions tolerance acc. to IEC 61109

Selection Guide

Catalogue

(Line Voltage, kV)


220 345 420 530 620 700 765

Code ()
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*
ISI-TEN-*

Note: It's possible to have intermediate numbers of sheds

n of
Sheds
A
n (1)

Length
L
10
mm

Leakage
distance

mm

38
42
46
50
54
58
62
66
70
74
78
82
86
90
94
98
102
106
110
120

2125
2285
2450
2615
2780
2945
3105
3270
3435
3600
3765
3925
4090
4255
4420
4580
4745
4910
5075
5485

5370
5910
6450
7000
7530
8070
8610
9150
9690
10230
10770
11310
11850
12390
12930
13470
14010
14550
15090
16440

Dry arc
distance

Power frequency Lightning impul.


withstand 50-60 Hz
withstand 1,2/50

Weight

mm

Dry
kV

Wet
kV

posit.
kV

negat.
kV

kg

1720
1880
2045
2210
2375
2540
2700
2865
3030
3195
3360
3520
3685
3850
4015
4175
4340
4505
4670
5080

610
645
700
740
815
865
900
950
1000
1040
1090
1110
1140
1170
1200
1220
1250
1280
1310
1460

510
545
595
620
660
710
750
830
900
950
1000
1030
1050
1075
1100
1130
1150
1175
1200
1310

990
1050
1200
1250
1340
1475
1570
1610
1700
1780
1860
1980
2030
2110
2220
2260
2400
2500
2590
2890

1070
1155
1300
1350
1440
1585
1720
1790
1850
1900
1950
2090
2110
2205
2300
2350
2520
2610
2720
3040

9.5
10.3
11.3
12.3
13.3
14.3
15.3
16.3
17.3
18.3
19.3
20.3
21.3
22.3
23.3
24.3
25.3
26.3
27.3
29.5

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use
(see page 19) and refer to the following table :
Ground
fitting
CLEVIS
CLEVIS
TONGUE
SOCKET

Line
fitting
TONGUE
CLEVIS
TONGUE
BALL

Code
(2)
CT
CC
TT
SB

Length
change (L)
0
- 60
+65
0

Specified Mechanical Load


Routine Test Load
Specified Mechanical Load
Routine Test Load
Max torsion Load

SML - IEC 61109


RTL = 50% of SML
360 kN
180 kN
300 N*m

For voltages above 170 kV refer to page 29 for Corona


Rings, the electrical data can be change.

Socket and Ball are size 24 acc. to IEC 60120


Clevis and Tongue are size 25L acc. to IEC 60471

() Key to the catalogue numbers


* Key : ISI-TEN- A(1)-360(2)
Example : ISI-TEN-A102-360TT
Please, don't hesitate to contact us directly for obtaining
possible explanations or different solutions.

These insulators are produced and tested according to IEC 61109.


It's possible to have all the other combinations.

isoelectric - Italy
41

09-1

SAME PICTURES OF THE OUR HORIZONTAL POST


COMPOSITE INSULATORS
Type ISI-BIG

isoelectric - Italy
42

04-2

COMPOSITE PIN or VERTICAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-SAS-*

Dimensions tolerance acc. to IEC 61952

Selection Guide

Catalogue

(Line Voltage, kV)


12

17

24

36

45

52

Code ()
ISI-SAS-*
ISI-SAS-*
ISI-SAS-*
ISI-SAS-*
ISI-SAS-*
ISI-SAS-*
ISI-SAS-*
ISI-SAS-*

Specified n of Height Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
H
Load
A
Dry
Wet
posit. negat.
10
kN
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
16,7
12,9
10,8
9,0
7,7
6,6
5,9
5,3

2
3
4
5
6
7
8
9

200
240
280
320
360
400
440
480

310
445
580
715
850
985
1120
1255

135
175
215
255
295
335
375
415

60
70
80
90
110
120
135
150

50
60
70
80
100
110
120
130

90
120
145
160
165
180
200
220

160
200
240
270
280
310
340
370

1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total height of the insulator (H), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table:
Line
fitting
Fitting P1
Fitting P1
Fitting M2
Fitting P1
Fitting M1
Fitting P2
Fitting P2
Fitting P2
Fitting R

Ground
fitting
Fitting D
Fitting R
Fitting M1
Fitting M1
Fitting R
Fitting D
Fitting R
Fitting M1
Fitting R

Code
(2)
P1D
P1R
M2M1
P1M1
M1R
P2D
P2R
P2M1
RR

Height
change (H)
0
-10
-15
-5
-5
+10
0
+5
-10

Specified Cantilever Load


Max. Design Cantilever Load
Specified Tensile Load (STL)
Max design compression
Max design torsion

SCL - IEC 61952


MDCL = 65% of SCL
15 kN
15 kN
10 daN*m

The metal fittings can be in aluminium or galvanized steel.


() Key to the catalogue numbers
Key : ISI-SAS-A(1) - (2)
Example: ISI-SAS-A3-P1D (specify the screw size)

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
43

05-1

COMPOSITE PIN INSULATOR in SILICONE RUBBER type ISI-RG-*

Dimensions tolerance acc. to IEC 61952

Selection Guide
(Line Voltage, kV)
12

24

36

45

Catalogue
Code ()
ISI-RG-*
ISI-RG-*
ISI-RG-*
ISI-RG-*
ISI-RG-*
ISI-RG-*
ISI-RG-*

Specified n of Height Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
H
Load
A
Dry
Wet
posit. negat.
10
kN
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
16,2
12,5
9,8
8,2
7,4
6,6
6,0

2+1
3+2
4+3
5+4
6+5
7+6
8+7

185
245
305
365
425
485
545

335
540
750
960
1170
1380
1590

110
170
230
290
330
390
450

70
110
120
150
160
180
200

65
100
110
140
150
165
185

115
150
180
235
260
285
305

160
190
215
270
300
325
355

2,0
2,5
3,0
3,5
3,9
4,4
5,0

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total height of the insulator (H), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line
fitting
Fitting P1
Fitting P2
Fitting P1
Fitting P2
Fitting F-neck
Fitting F-neck
Fitting C
Fitting C

Ground
fitting
Fitting D
Fitting D
Fitting R
Fitting R
Fitting D
Fitting R
Fitting D
Fitting R

Code
(2)
P1D
P2D
P1R
P2R
F-neckD
F-neckR
CD
CR

Height
change (H)
0
+5
0
+20
+25
+45
+45
+100

Specified Cantilever Load


SCL - IEC 61952
Max. Design Cantilever Load
MDCL = 65% of SCL
Specified Tensile Load (STL) 15 kN
Max design compression
15 kN
Max design torsion
15 daN*m
The SCL can be increased, please contact us.
The metal fittings can be in aluminium or galvanized steel.
() Key to the catalogue numbers
Key : ISI-RG-A(1) - (2)
Example: ISI-RG-A4+3-P1D (specify the screw size)

These insulators are produced, tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining possible


explanations or different solutions.

isoelectric - Italy
44

06-10

COMPOSITE VERTICAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-Fn-*

Dimensions tolerance acc. to IEC 61952

Selection Guide

Catalogue

(Line Voltage, kV)


12

17

24

36

45

52

Code ()
ISI-Fn-*
ISI-Fn-*
ISI-Fn-*
ISI-Fn-*
ISI-Fn-*
ISI-Fn-*
ISI-Fn-*
ISI-Fn-*

Specified n of Height Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
H
Load
A
Dry
Wet
posit. negat.
5
kN
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
17,6
14,0
11,5
9,8
8,5
7,5
6,8
6,1

2
3
4
5
6
7
8
9

170
215
260
305
350
395
440
485

265
370
475
580
685
790
895
1000

150
195
240
295
330
375
420
465

65
75
85
110
120
135
150
160

60
65
75
100
110
120
130
140

100
130
150
165
180
200
220
245

180
220
250
280
310
340
370
395

2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total height of the insulator (H), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line
fitting
Fitting R
Fitting F
Fitting G
Fitting M
Fitting M
Fitting M
Fitting VC
Fitting VC
Fitting VC

Ground
fitting
Fitting R
Fitting R
Fitting G
Fitting R
Fitting G
Fitting M
Fitting R
Fitting G
Fitting M

Code
(2)
RR
FR
GG
MR
MG
MM
VCR
VCG
VCM

Height
change (H)
0
0
+160
0
+80
0
+95
+175
+95

Specified Cantilever Load


SCL - IEC 61952
Max. Design Cantilever Load
MDCL = 65% of SCL
Specified Tensile Load (STL) 15 kN
Max design compression
15 kN
Max design torsion
15 daN*m
The SCL can be increased, please contact us.
The metal fittings can be in aluminium or galvanized steel.
() Key to the catalogue numbers
Key : ISI-Fn-A(1) - (2)
Example: ISI-Fn-A4-RR

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
45

06-10

COMPOSITE VERTICAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-SCA-*

Dimensions tolerance acc. to IEC 61952

Selection Guide

Catalogue

(Line Voltage, kV)


12

17

24

36

45

52

Code ()
ISI-SCA-*
ISI-SCA-*
ISI-SCA-*
ISI-SCA-*
ISI-SCA-*
ISI-SCA-*
ISI-SCA-*
ISI-SCA-*

Specified n of Height Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
H
Load
A
Dry
Wet
posit. negat.
5
kN
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
16,2
12,2
10,0
9,0
7,8
7,1
6,2
5,7

2+1
3+2
4+3
5+4
6+5
7+6
8+7
9+8

190
240
285
335
385
430
480
525

315
465
610
760
910
1055
1205
1350

160
210
255
305
355
400
450
495

65
95
110
120
150
170
180
190

60
85
95
110
140
155
165
175

100
130
155
180
235
270
285
300

150
170
190
215
270
300
325
345

2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total height of the insulator (H), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line
fitting
Fitting M2
Fitting F
Fitting R
Fitting M2
Fitting M2

Ground
fitting
Fitting M1
Fitting R
Fitting R
Fitting R
Fitting F

Code
(2)
M2M1
FR
RR
M2R
M2F

Height
change (H)
0
+15
+15
+8
+8

Specified Cantilever Load


SCL - IEC 61952
Max. Design Cantilever Load
MDCL = 65% of SCL
Specified Tensile Load (STL) 15 kN
Max design compression
15 kN
Max design torsion
15 daN*m
The SCL can be increased, please contact us.
The metal fittings can be in aluminium or galvanized steel.
() Key to the catalogue numbers
Key : ISI-SCA-A(1) - (2)
Example: ISI-SCA-A4+3-M2M1

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
46

11-1

COMPOSITE VERTICAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-FC-*

Dimensions tolerance acc. to IEC 61952

Selection Guide

Catalogue

(Line Voltage, kV)


12

17

24

36

45

52

Code ()
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*

Specified n of Height Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
H
Load
A
Dry
Wet
posit. negat.
5
kN
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
16,2
12,2
9,8
8,2
7,1
6,2
5,5
5,0

2+1
3+2
4+3
5+4
6+5
7+6
8+7
9+8

185
245
305
365
425
485
545
605

390
585
780
975
1170
1365
1560
1755

165
225
285
345
405
465
525
585

70
110
120
150
170
180
200
225

65
100
110
140
155
165
185
210

115
150
180
235
270
285
305
345

160
190
215
270
300
325
355
405

2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total height of the insulator (H), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line
fitting
Fitting R
Fitting F
Fitting G
Fitting M
Fitting M
Fitting M
Fitting VC
Fitting VC
Fitting VC

Ground
fitting
Fitting R
Fitting R
Fitting G
Fitting R
Fitting G
Fitting M
Fitting R
Fitting G
Fitting M

Code
(2)
RR
FR
GG
MR
MG
MM
VCR
VCG
VCM

Height
change (H)
0
0
+160
0
+80
0
+95
+175
+95

Specified Cantilever Load


SCL - IEC 61952
Max. Design Cantilever Load
MDCL = 65% of SCL
Specified Tensile Load (STL) 15 kN
Max design compression
15 kN
Max design torsion
15 daN*m
The SCL can be increased, please contact us.
The metal fittings can be in aluminium or galvanized steel.
() Key to the catalogue numbers
Key : ISI-FC-A(1) - (2)
Example : ISI-FC-A4+3-FR

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining possible


explanations or different solutions.

isoelectric - Italy
47

06-10

COMPOSITE VERTICAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-FC-*

Dimensions tolerance acc. to IEC 61952

Selection Guide
(Line Voltage, kV)

72

115

150

Catalogue
Code ()
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*

Specified n of Height Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
H
Load
A
Dry
Wet
posit. negat.
5
kN
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
4,5
3,8
3,3
2,9
2,6
2,4
2,2
2,0

10+9
12+11
14+13
16+15
18+17
20+19
22+21
24+23

665
785
905
1025
1145
1265
1385
1505

1950
2340
2730
3120
3510
3900
4290
4680

645
765
885
1005
1125
1245
1365
1485

270
310
355
400
435
475
520
560

225
245
285
320
355
390
430
475

450
515
570
625
680
750
820
870

490
550
615
670
735
805
890
940

6,0
7,0
8,0
9,0
10,0
11,0
12,0
13,0

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total height of the insulator (H), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line
fitting
Fitting R
Fitting F
Fitting G
Fitting M
Fitting M
Fitting M
Fitting VC
Fitting VC
Fitting VC

Ground
fitting
Fitting R
Fitting R
Fitting G
Fitting R
Fitting G
Fitting M
Fitting R
Fitting G
Fitting M

Code
(2)
RR
FR
GG
MR
MG
MM
VCR
VCG
VCM

Height
change (H)
0
0
+160
0
+80
0
+95
+175
+95

Specified Cantilever Load


Max. Design Cantilever Load
Specified Tensile Load (STL)
Max design compression
Max design torsion

SCL - IEC 61952


MDCL = 65% of SCL
15 kN
15 kN
15 daN*m

The SCL can be increased, please contact us.


() Key to the catalogue numbers
Key : ISI-FC-A(1) - (2)
Example : ISI-FC-A16+15-FR

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining possible


explanations or different solutions.

isoelectric - Italy
48

06-10

COMPOSITE VERTICAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-BIG-*

Dimensions tolerance acc. to IEC 61952

Selection Guide

Catalogue

(Line Voltage, kV)


12

17

24

36

45

52

Code ()
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*

Specified n of Height Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
H
Load
A
Dry
Wet
posit. negat.
5
kN
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
40,0
33,0
28,0
24,2
21,5
19,2
17,3
15,8

2+1
3+2
4+3
5+4
6+5
7+6
8+7
9+8

315
375
435
495
555
615
675
735

340
530
710
900
1100
1280
1470
1660

135
195
255
315
375
435
495
555

65
80
100
125
145
170
190
215

60
75
90
110
130
155
175
200

100
135
160
190
220
255
290
320

145
180
210
240
275
310
340
380

6,5
7,0
7,5
8,0
8,5
9,0
9,5
10,0

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total height of the insulator (H), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line
fitting
Fitting G
Fitting MG
Fitting VC
Fitting G
Fitting VC

Ground
fitting
Fitting G
Fitting G
Fitting G
Fitting MG
Fitting MG

Code
(2)
GG
MGG
VCG
GMG
VCMG

Height
change (H)
0
+20
+10
+20
+75

Specified Cantilever Load


Max. Design Cantilever Load
Specified Tensile Load (STL)
Max design compression
Max design torsion

SCL - IEC 61952


MDCL = 65% of SCL
40 kN
40 kN
20 daN*m

() Key to the catalogue numbers


Key : ISI-BIG-A(1) - (2)
Example : ISI-BIG-A7+6-GG

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
49

06-10

COMPOSITE VERTICAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-BIG-*

Dimensions tolerance acc. to IEC 61952

Selection Guide
(Line Voltage, kV)

72

115

150 230

Catalogue
Code ()
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*

Specified n of Height Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
H
Load
A
Dry
Wet
posit. negat.
5
kN
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
14,6
12,6
11,1
9,9
8,9
8,2
7,5
6,9
6,0
5,3
4,7

10+9
12+11
14+13
16+15
18+17
20+19
22+21
24+23
28+27
32+31
36+35

795
915
1035
1155
1275
1395
1515
1635
1875
2115
2360

1800
2200
2600
2900
3300
3700
4100
4450
5200
5950
6700

615
735
855
975
1095
1215
1335
1455
1695
1935
2175

275
310
340
380
415
450
485
520
615
675
760

195
230
265
300
335
370
405
435
515
575
640

420
460
500
560
615
670
725
830
940
1100
1230

480
540
595
650
705
760
815
880
1040
1200
1340

11
12
13
14
15
16
17
18
22
24
26

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it, in
order to obtain the total height of the insulator (H), please, select the kind of fitting end you have to use and make
the opportune correction with reference to the following table :
Line
fitting
Fitting G
Fitting MG
Fitting VC
Fitting G
Fitting VC

Ground
fitting
Fitting G
Fitting G
Fitting G
Fitting MG
Fitting MG

Code
(2)
GG
MGG
VCG
GMG
VCMG

Height
change (H)
0
+20
+10
+20
+75

Specified Cantilever Load


Max. Design Cantilever Load
Specified Tensile Load (STL)
Max design compression
Max design torsion

SCL - IEC 61952


MDCL = 65% of SCL
40 kN
40 kN
20 daN*m

() Key to the catalogue numbers


Key : ISI-BIG-A(1) - (2)
Example : ISI-BIG-A14+13-GG

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
50

06-10

COMPOSITE VERTICAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-MAX-*

Dimensions tolerance acc. to IEC 61952

Selection Guide
(Line Voltage, kV)

115

150

220 345

Catalogue
Code ()
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*

Specified
Cantilever
Load
kN
15,0
13,5
11,2
11,1
10,2
9,4
8,1
7,7
7,2
6,4
5,7

n of Height Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Sheds
H
A
Dry
Wet
posit. negat.
5
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
14+13
16+15
18+17
20+19
22+21
24+23
28+27
32+31
38+37
43+42
46+45

1035
1155
1275
1395
1515
1635
1875
2115
2475
2775
2955

2600
2900
3300
3700
4100
4450
5200
5950
7100
8090
8600

855
975
1095
1215
1335
1455
1695
1935
2295
2595
2775

340
380
415
450
485
520
615
675
810
855
905

265
300
335
370
405
435
515
575
675
750
780

500
560
615
670
725
830
940
1100
1330
1460
1585

595
650
705
760
815
880
1040
1200
1430
1565
1715

15,5
17,5
18,5
20,0
21,0
22,5
26,5
29,5
34,5
40,0
45,0

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total height of the insulator (H), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line
fitting
Fitting G
Fitting MG
Fitting MG
Fitting VC
Fitting VC

Ground
fitting
Fitting G
Fitting G
Fitting MG
Fitting G
Fitting MG

Code
(2)
GG
MGG
MGMG
VCG
VCMG

Height
change (H)
0
+65
+130
+65
+80

Specified Cantilever Load


Max. Design Cantilever Load
Specified Tensile Load (STL)
Max design compression
Max design torsion

SCL - IEC 61952


MDCL = 65% of SCL
50 kN
50 kN
25 daN*m

() Key to the catalogue numbers


Key : ISI-MAX-A(1) - (2)
Example : ISI-MAX-A14+13-GG

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
51

06-10

COMPOSITE VERTICAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-BUL-*

Dimensions tolerance acc. to IEC 61952

Selection Guide
(Line Voltage, kV) Catalogue
1101 2002 3003 420 Code ()
70 50 62 765
ISI-BUL-*
ISI-BUL-*
ISI-BUL-*
ISI-BUL-*
ISI-BUL-*
ISI-BUL-*
ISI-BUL-*
ISI-BUL-*
ISI-BUL-*
ISI-BUL-*
ISI-BUL-*
ISI-BUL-*

Specified
Cantilever
Load
(SCL)
kN
27,7
23,3
21,2
19,4
16,3
15,2
13,3
12,2
11,2
10,5
9,0
7,5

n of
Sheds
A
n (1)
13+12
16+15
18+17
20+19
24+23
26+25
30+29
33+32
36+35
39+38
47+46
56+55

Power frequency Lightning


impulse
withstand
Similar
Height Leakage Dry arc
withstand
50 Hz
to *
H
distance distance
Weight
Dry
Wet kV 1,2/50
5
IEC 60660 kg
mm
mm
kV
kV
mm
1260
3200
1010
380
300
570
C20-550
48
1500
3950
1250
450
370
670
C20-650
58
1660
4500
1410
485
405
760
C16-750
65
1820
5000
1570
520
435
860
C16-850
72
2140
6000
1890
615
515
950
C12-850
87
2300
6500
2050
675
575
1120
C12-1050 94
2620
7550
2370
810
675
1280
C10-1175 108
2860
8300
2610
855
750
1410
C10-1300 120
3100
9050
2850
905
780
1500
C10-1425 130
3340
9800
3090
900
750
1610
C8-1550 141
3980
11840
3730
1140
1020
1930
C8-1800 170
4700
14100
4450
1280
1100
2210
C6-2100 203

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total height of the insulator (H), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line fitting
(Top)

Ground fitting
(Bottom)

Code
(2)

Height
change (H)

Specified Cantilever Load


Max. Design Cantilever Load
Specified Tensile Load (STL)
Max design compression
Max design torsion

Fitting T1
Fitting T2
0
T1T2
Fitting T1
Fitting T1
-30
T1T1
Fitting T1
Fitting T3
+30
T1T3
Fitting T1
Fitting T4
+60
T1T4
Fitting T3
Fitting T3
+90
T3T3
Fitting T3
Fitting T4
+120
T3T4
Fitting T3
Fitting T5
+120
T3T5
Fitting T3
Fitting T6
+170
T3T6
* Please consider the flexibility of the composite insulators

SCL - IEC 61952


MDCL = 65% of SCL
80 kN
100 kN
400 daN*m

() Key to the catalog numbers


Key : ISI-BUL-A(1) - (2)
Example : ISI-BUL-A16-T1T2
These insulators are produced and tested acc. to IEC 61952.
It's possible to have all the other combinations.

isoelectric - Italy
52

08-10

POST INSULATORS FIXING BASE

Galvanized steel Gain Base (GB)

Aluminium Gain Base (GB)

Galvanized steel Horizontal Base (HB)


for wooden pole

Galvanized steel Horizontal Flat Base (HB)


for steel pole

Please, don't hesitate to contact us directly for obtaining possible explanations or different solutions.

isoelectric - Italy
53

04-2

COMPOSITE HORIZONTAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-FC-*

Dimensions tolerance acc. to IEC 61952

Selection Guide

Catalogue

(Line Voltage, kV)


12

17

24

36

45

52

Code ()
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*

Specified n of Length Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
L
Load
A
Dry
Wet
posit. negat.
5
kN
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
10,0
8,4
7,2
6,3
5,5
5,0
4,5
4,2

2+1
3+2
4+3
5+4
6+5
7+6
8+7
9+8

395
450
510
570
630
690
745
805

390
585
780
975
1170
1365
1560
1755

165
225
285
340
400
460
520
575

70
110
120
150
170
180
200
225

65
100
110
140
155
165
185
210

115
150
180
235
270
285
305
345

160
190
215
270
300
325
355
405

6,5
7,0
7,5
8,0
8,5
9,0
9,5
10,0

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line
fitting
Fitting HC
Fitting HC
Fitting HC
Fitting B
Fitting B
Fitting B
Fitting C
Fitting C
Fitting C

Ground
fitting
Fitting GB
Fitting M
Fitting R
Fitting GB
Fitting M
Fitting R
Fitting GB
Fitting M
Fitting R

Code
(2)
HCGB
HCM
HCR
BGB
BM
BR
CGB
CM
CR

Length
change (L)
0
-88
-88
+7
-80
-80
-40
-125
-125

Specified Cantilever Load


SCL - IEC 61952
Max. Design Cantilever Load
MDCL = 65% of SCL
Specified Tensile Load (STL) 15 kN
Max design compression
15 kN
Max design torsion
15 daN*m
The SCL can be increased, please contact us.
The metal fittings can be in aluminium or galvanized steel.
() Key to the catalogue numbers
Key : ISI-FC-A(1) - (2)
Example : ISI-FC-A4+3-HCGB

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining possible


explanations or different solutions.

isoelectric - Italy
54

05-1

COMPOSITE HORIZONTAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-FC-*

Dimensions tolerance acc. to IEC 61952

Selection Guide
(Line Voltage, kV)

72

115

150

Catalogue
Code ()
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*
ISI-FC-*

Specified n of Length Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
L
Load
A
+/- 5
Dry
Wet
posit. negat.
kN
mm
mm
mm
kV
kV
kV
kV
+/- kg
n (1)
3,9
3,3
3,0
2,7
2,4
2,2
2,0
1,8

10+9
12+11
14+13
16+15
18+17
20+19
22+21
24+23

865
985
1100
1220
1335
1455
1575
1690

1950
2340
2730
3120
3510
3900
4290
4680

635
750
870
985
1105
1220
1335
1455

270
310
355
400
435
475
520
560

225
245
285
320
355
390
430
475

450
515
570
625
680
750
820
870

490
550
615
670
735
805
890
940

10,5
11,5
12,5
13,5
14,5
15,5
16,5
17,5

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line
fitting
Fitting HC
Fitting HC
Fitting HC
Fitting B
Fitting B
Fitting B
Fitting C
Fitting C
Fitting C

Ground
fitting
Fitting GB
Fitting M
Fitting R
Fitting GB
Fitting M
Fitting R
Fitting GB
Fitting M
Fitting R

Code
(2)
HCGB
HCM
HCR
BGB
BM
BR
CGB
CM
CR

Length
change (L)
0
-88
-88
+7
-80
-80
-40
-125
-125

Specified Cantilever Load


SCL - IEC 61952
Max. Design Cantilever Load
MDCL = 65% of SCL
Specified Tensile Load (STL) 15 kN
Max design compression
15 kN
Max design torsion
15 daN*m
The SCL can be increased, please contact us.
The metal fittings can be in aluminium or galvanized steel.
() Key to the catalogue numbers
Key : ISI-FC-A(1) - (2)
Example : ISI-FC-A16+15-HCGB

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining possible


explanations or different solutions.

isoelectric - Italy
55

05-1

COMPOSITE HORIZONTAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-BIG-*

Dimensions tolerance acc. to IEC 61952

Selection Guide

Catalogue

(Line Voltage, kV)


12

17

24

36

45

52

Code ()
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*

Specified n of Length Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
L
Load
A
Dry
Wet
posit. negat.
10
kN
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
34,5
29,8
25,6
22,5
20,2
17,6
16,6
15,3

2+1
3+2
4+3
5+4
6+5
7+6
8+7
9+8

360
410
470
530
585
645
705
760

340
530
710
900
1100
1280
1470
1660

135
195
255
315
375
435
495
555

65
80
100
125
145
170
190
215

60
75
90
110
130
155
175
200

100
135
160
190
220
255
290
320

145
180
210
240
275
310
340
380

7,0
7,5
8,0
8,5
9,0
10,0
10,5
11,0

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line
fitting
Fitting HC
Fitting HC
Fitting HC
Fitting B
Fitting B
Fitting B
Fitting MG

Ground
fitting
Fitting GB
Fitting HB
Fitting G
Fitting GB
Fitting HB
Fitting G
Fitting GB

Code
(2)
HCGB
HCHB
HCG
BGB
BHB
BG
MGGB

Length
change (L)
0
+36
+20
+9
+44
+29
-24

Specified Cantilever Load


Max. Design Cantilever Load
Specified Tensile Load (STL)
Max design compression
Max design torsion

SCL - IEC 61952


MDCL = 65% of SCL
40 kN
40 kN
20 daN*m

() Key to the catalogue numbers


Key : ISI-BIG-A(1) - (2)
Example : ISI-BIG-A8+7-HCGB

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
56

04-2

COMPOSITE HORIZONTAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-BIG-*

Dimensions tolerance acc. to IEC 61952

Selection Guide

Catalogue

(Line Voltage, kV)

72

115

150 230

Code ()
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*
ISI-BIG-*

Specified
Cantilever
Load
kN
14,0
12,0
10,8
9,6
8,8
8,0
7,4
6,8
6,0
5,3
4,7

n of Length Leakage Dry arc Power frequency Lightning impul.


distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Sheds
L
A
Dry
Wet
posit. negat.
10
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
10+9
12+11
14+13
16+15
18+17
20+19
22+21
24+23
28+27
32+31
36+35

820
940
1060
1175
1290
1410
1525
1645
1880
2115
2350

1800
2200
2600
2900
3300
3700
4100
4450
5200
5950
6700

615
735
855
975
1095
1215
1335
1455
1695
1935
2175

275
310
340
380
415
450
485
520
615
675
760

195
230
265
300
335
370
405
435
515
575
640

420
460
500
560
615
670
725
830
940
1100
1230

480
540
595
650
705
760
815
880
1040
1200
1340

11,5
12,5
13,5
14,5
15,5
16,5
17,5
18,5
22,5
24,5
26,5

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it, in
order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use and make
the opportune correction with reference to the following table :
Line
fitting
Fitting HC
Fitting HC
Fitting HC
Fitting B
Fitting B
Fitting B
Fitting MG

Ground
fitting
Fitting GB
Fitting HB
Fitting G
Fitting GB
Fitting HB
Fitting G
Fitting GB

Code
(2)
HCGB
HCHB
HCG
BGB
BHB
BG
MGGB

Length
change (L)
0
+36
+20
+9
+44
+29
-24

Specified Cantilever Load


Max. Design Cantilever Load
Specified Tensile Load (STL)
Max design compression
Max design torsion

SCL - IEC 61952


MDCL = 65% of SCL
40 kN
40 kN
20 daN*m

() Key to the catalogue numbers


Key : ISI-BIG-A(1) - (2)
Example : ISI-BIG-A14+13-HCGB

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
57

04-2

COMPOSITE HORIZONTAL LINE POST INSULATOR


in SILICONE RUBBER type ISI-MAX-*

Dimensions tolerance acc. to IEC 61952

Selection Guide
(Line Voltage, kV)

115

150

220 345

Catalogue
Code ()
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*
ISI-MAX-*

Specified
n of Length Leakage Dry arc Power frequency Lightning impul.
distance distance withstand 50-60 Hz withstand 1,2/50 Weight
Cantilever Sheds
L
Load
A
Dry
Wet
posit. negat.
5
kN
mm
mm
kV
kV
kV
kV
n (1)
mm
kg
14,5
13,0
11,6
10,7
9,8
9,0
7,8
7,3
6,9
6,2
5,5

14+13
16+15
18+17
20+19
22+21
24+23
28+27
32+31
38+37
43+42
46+45

1060
1175
1290
1410
1525
1645
1880
2115
2475
2895
2950

2600
2900
3300
3700
4100
4450
5200
5950
7100
8090
8600

855
975
1095
1215
1335
1455
1695
1935
2295
2595
2775

340
380
415
450
485
520
615
675
810
855
905

265
300
335
370
405
435
515
575
675
750
780

500
560
615
670
725
830
940
1100
1330
1460
1585

595
650
705
760
815
880
1040
1200
1430
1565
1715

15,5
17,5
18,5
20,0
21,0
22,5
26,5
29,5
34,5
40,0
45,0

NOTE : Once chosen the insulator that is the most suitable to the characteristics of the line on which you have to install it,
in order to obtain the total length of the insulator (L), please, select the kind of fitting end you have to use and
make the opportune correction with reference to the following table :
Line
fitting
Fitting HC
Fitting HC
Fitting HC
Fitting B
Fitting B
Fitting B
Fitting MG
Fitting MG
Fitting MG

Ground
fitting
Fitting GB
Fitting HB
Fitting G
Fitting GB
Fitting HB
Fitting G
Fitting GB
Fitting HB
Fitting G

Code
(2)
HCGB
HCHB
HCG
BGB
BHB
BG
MGGB
MGHB
MGG

Length
change (L)
0
+36
+20
+9
+44
+29
-24
+12
-4

Specified Cantilever Load


Max. Design Cantilever Load
Specified Tensile Load (STL)
Max design compression
Max design torsion

SCL - IEC 61952


MDCL = 65% of SCL
50 kN
50 kN
25 daN*m

() Key to the catalogue numbers


Key : ISI-MAX-A(1) - (2)
Example : ISI-MAX-A20+19-HCGB

These insulators are produced and tested according to IEC 61952.


It's possible to have all the other combinations.

Please, don't hesitate to contact us directly for obtaining


possible explanations or different solutions.

isoelectric - Italy
58

04-2

SAME PICTURES OF THE OUR COMPOSITE INSULATING


BRACKET

isoelectric - Italy
59

04-2

INSULATING BRACKET ASSEMBLY DRAWINGS

Fixed assembly with 12 inclination

Horizontal & Vertical Pivoting assembly with 12 inclination

Fixed assembly with 0 inclination

Horizontal & Vertical Pivoting assembly with 0 inclination

Base for Fixed assembly with 0 or 12 inclination

Base for Pivoting assembly with 0 or 12 inclination

Please, don't hesitate to contact us directly for obtaining possible explanations or different solutions.

isoelectric - Italy
60

04-2

INSULATING BRACKET ASSEMBLY Dimensions and Strength Ratings


FIXED ASSEMBLY with 12 inclination
Typical
Voltage
138
138
145
161
161
170
230
230
245

Component insulators
Suspension type
ISI-CAN-A27-120EE
ISI-ROK-A17+16-120EE
ISI-ROK-A18+17-120EE
ISI-ROK-A17+16-120EE
ISI-ROK-A20+19-120EE
ISI-ROK-A21+20-120EE
ISI-CAN-A48-120EE
ISI-ROK-A28+27-120EE
ISI-ROK-A30+29-120EE

Dimensions (mm)

Maximum Load* (kN)

Pollution

Post type

1*

2*

3*

4*

mm/kV

ISI-BIG-A18+17-BHB
ISI-BIG-A24+23-BHB
ISI-MAX-A24+23-BHB
ISI-BIG-A24+23-BHB
ISI-BIG-A27+26-BHB
ISI-MAX-A29+28-BHB
ISI-BIG-A31+30-BHB
ISI-BIG-A38+37-BHB
ISI-MAX-A41+40-BHB

1560
1685
1740
1685
1910
1990
2335
2450
2595

1600
1675
1745
1675
1885
1960
2410
2445
2585

1420
1775
1775
1775
1950
2065
2185
2595
2770

370
680
635
680
695
770
615
1005
1095

55
55
70
55
55
70
55
55
70

35
35
45
35
35
45
35
35
45

55
55
70
50
50
60
45
45
50

5,72
4,42
5,85
4,42
4,22
4,87
3,57
2,90
4,22

> 23
> 31
> 31
> 27
> 31
> 31
> 25
> 31
> 31

FIXED ASSEMBLY with 0 inclination ( Horizontal V )


Typical
Voltage
138
138
145
161
161
170
230
230
245

Component insulators
Suspension type
ISI-CAN-A27-120EE
ISI-ROK-A17+16-120EE
ISI-ROK-A18+17-120EE
ISI-ROK-A17+16-120EE
ISI-ROK-A20+19-120EE
ISI-ROK-A21+20-120EE
ISI-CAN-A48-120EE
ISI-ROK-A28+27-120EE
ISI-ROK-A30+29-120EE

Dimensions (mm)

Maximum Load* (kN)

Pollution

Post type

1*

2*

3*

4*

mm/kV

ISI-BIG-A18+17-BHB
ISI-BIG-A24+23-BHB
ISI-MAX-A24+23-BHB
ISI-BIG-A24+23-BHB
ISI-BIG-A27+26-BHB
ISI-MAX-A29+28-BHB
ISI-BIG-A31+30-BHB
ISI-BIG-A38+37-BHB
ISI-MAX-A41+40-BHB

1400
1490
1550
1490
1675
1735
2125
2155
2280

1600
1675
1745
1675
1885
1960
2410
2445
2585

1445
1800
1800
1800
1985
2105
2225
2645
2825

655
965
930
965
1040
1125
1015
1420
1530

50
50
65
50
50
65
50
50
65

35
35
45
35
35
45
35
35
45

55
55
70
55
55
70
55
55
70

5,50
4,20
5,60
4,20
4,00
4,60
3,30
2,70
4,00

> 23
> 31
> 31
> 27
> 31
> 31
> 25
> 31
> 31

HORIZONTAL & VERTICAL PIVOTING ASSEMBLY with 12 inclination


Typical
Voltage
138
138
145
161
161
170
230
230
245

Component insulators
Suspension type
ISI-CAN-A27-120EE
ISI-ROK-A17+16-120EE
ISI-ROK-A18+17-120EE
ISI-ROK-A17+16-120EE
ISI-ROK-A20+19-120EE
ISI-ROK-A21+20-120EE
ISI-CAN-A48-120EE
ISI-ROK-A28+27-120EE
ISI-ROK-A30+29-120EE

Post type
ISI-BIG-A18+17-BC
ISI-BIG-A24+23-BC
ISI-MAX-A24+23-BC
ISI-BIG-A24+23-BC
ISI-BIG-A27+26-BC
ISI-MAX-A29+28-BC
ISI-BIG-A31+30-BC
ISI-BIG-A38+37-BC
ISI-MAX-A41+40-BC

Dimensions (mm)

Maximum Load* (kN)

Pollution

1*

2*

3*

4*

mm/kV

1555
1680
1735
1680
1905
1985
2330
2445
2590

1600
1675
1745
1675
1920
1990
2410
2445
2585

1435
1788
1790
1790
1965
2080
2200
2610
2795

385
695
650
695
710
785
630
1020
1110

55
55
70
55
55
70
55
55
70

35
35
45
35
35
45
35
35
45

55
55
70
50
50
60
45
45
50

----------

> 23
> 31
> 31
> 27
> 31
> 31
> 25
> 31
> 31

HORIZONTAL & VERTICAL PIVOTING ASSEMBLY with 0 inclination


Typical
Voltage
138
138
145
161
161
170
230
230
245

Component insulators
Suspension type
ISI-CAN-A27-120EE
ISI-ROK-A17+16-120EE
ISI-ROK-A18+17-120EE
ISI-ROK-A17+16-120EE
ISI-ROK-A20+19-120EE
ISI-ROK-A21+20-120EE
ISI-CAN-A48-120EE
ISI-ROK-A28+27-120EE
ISI-ROK-A30+29-120EE

Post type
ISI-BIG-A18+17-BC
ISI-BIG-A24+23-BC
ISI-MAX-A24+23-BC
ISI-BIG-A24+23-BC
ISI-BIG-A27+26-BC
ISI-MAX-A29+28-BC
ISI-BIG-A31+30-BC
ISI-BIG-A38+37-BC
ISI-MAX-A41+40-BC

Dimensions (mm)

Maximum Load* (kN)

Pollution

1*

2*

3*

4*

mm/kV

1555
1680
1735
1680
1905
1985
2330
2445
2590

1600
1675
1745
1675
1920
1990
2410
2445
2585

1450
1805
1805
1805
1980
2095
2215
2625
2810

400
710
665
710
725
800
645
1035
1125

50
50
65
50
50
65
50
50
65

35
35
45
35
35
45
35
35
45

55
55
70
55
55
70
55
55
70

----------

> 23
> 31
> 31
> 27
> 31
> 31
> 25
> 31
> 31

* Maximum load are for single loads in the specified direction: 1=Vertical, 2=Tension, 3=Compression, 4=Longitudinal
Please, don't hesitate to contact us directly for obtaining possible explanations or different solutions.

isoelectric - Italy
61

04-2

62