Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
STANDARD for
UNITARY AIR=
CONDITIONING
AND AIR=
SOURCE HEAT
PUMP
EQUIPMENT
I Standard 2101240 I
AIR-CONDITIONING &
REFRIGERATION
INSTITUTE
4301 NORTHFAIRFAXDRIVE
ARLINGTON,VIRGINIA
22203
IMPORTANT
SAFETY RECOMMENDATIONS
It is strongly recommended that the product be designed, constructed, assembled and installed in accordance with
nationally recognized safety requirements appropriate forproducts covered by this standard.
ARI, as a manufacturers' trade association, uses its best efforts to develop standards employing state-of-the-art and
accepted industry practices. However,ARI does not certifyor guarantee safety of any products, components or systems
designed, tested, rated, installed or operated in accordance with thesestandards or that any tests conducted under its
standards will be non-hazardous or free from risk.
Certified Ratings
The followingCertification Programs ratings areverified by test:
A.
B.
A.
B.
Conformance to the requirements of the Maximum Operating Condition Test, VoltageTolerance Test, LowTemperature Operation Test(Cooling), Insulation Efficiency Test (Cooling), and Condensate Disposal Test (Cooling),
(see Section 6) are also verified by test.
Note:
This standard supersedes ARI Standard 210/240-89.
Price $20.00 (M) $40.00 (NM)
Printed in U.S.A.
-ams
ma\.
Registered
United States Patent and Trademark Office
TABLE OF CONTENTS
SECTION
PAGE
Section1. Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Section2. Scope
.........................................................
.....................................................
Section 3 . Definitions
...................................................
10
13
13
Section 4. Classification
3.
TABLES
Table 1.
Table 2 .
Table 3 .
Table 4.
Table 5 .
Table 6.
FIGURES
Figure 1.
..........................................
11
APPENDICES
Appendix A.
..............................
14
. . . . . . . . . . . . . . . . . 33
Appendix B.
References.
Appendix C.
UNITARY AIR-CONDITIONING
AND AIR-SOURCE HEAT PUMP EQUIPMENT
Section 1. Purpose
1.1 Purpose. The purpose of this standard is to establish,
for unitary
equipment:
definitions and
classification:
requirements for testing, rating and operating: marking and
nameplate data and conformance conditions.
1.1.1 Intent. This standardisintendedfortheguidance the
of
industry,
including
manufacturers,
engineers, installers, contractors, and users.
1.1.2 Review
and
Amendment.
subject toreviewandamendment
advances.
This standard
is
as technology
Section 2. Scope
This standard
applies
to factory-made
residential, commercial, and industrial equipment defined in
3.2 and 3.3..
2.1 Scope.
2.1.1
2.2.3
This standarddoesnotapply
to unitaryheat
pumps as defined in A R I Standard 340/360-93 with
cooling capacitiesof 135,000 Bhlh (40k W ) or greater,
nor towater-sourceheatpumps
as defined in ARI
Standard 320-93 nor to ground water-source heat pumps
as defined in A N Standard 325-93.
Section 3. Definitions
3.1 Definitions. All terms in this document will follow the
standardindustrydefinitionsinthecurrentedition
of
ASHRAE
Terminology
Hearing,
of
Ventilation,
Air
Conditioning,and Refrigeration unless otherwise definedin
this section.
tothe
Note: See Appendix A fordefinitionsthatapply
testing andcalculation procedures required by Appendix A.
3.2 Air-Source Unirary Heat Pump. An air-source unitary
Functions. Unitaryheatpumpsshallprovide
the function of air heating with controlled temperature,
and
may
include
the
functions
of air-cooling,
air-circulating,
air-cleaning,
dehumidifying
or
humidifying.
3.2.1
'
3.12 "Shall,"
"Should,"
"Recommended,"
or "It is
Recommended." "Shall," "should," "recommended" or "it is
recommended" shall be interpreted as follows:
3.12.1
if
The following typesof air to air units rated less ,than 65,000
Btuh [ 19 kWl cooling or less than 65.000 Btu/h [19 kWl
heating for heatingonly equipment shall be tested in accordance with Appendices A and C and rated at conditions
specified in Table 3 or Table 4. .
SP-A; SPY-A; RCUY-A-CB; RCU-A-C; RCU-A-CB;
HSP-A HOSP-A;
HRCU-A-CB;
HORCU-A-CB;
HRCU-AX-: HORCU-A-C
All other types and/or capacities of equipment within the
scope of thu standard shall have the capacity, EER and COP
(as required) tested in accordance with ASHRAE Standard
37-1988 and rated at conditions specified in Table 5. SEER
and/or HSPF may bedetermined on air-to-air equipment(as
application ratings) at the option of the minufacturer.
.-
Unitary
Air-Conditioners
Rejection
Heat Type
Desiqnation
ARI
I
Single Package
SP-A
SP-E
SP-w
Refrigeration
Chassis
Evap
RCH-A
Cond
RCH-E
RCH-W
Arranqement
Air
Evap Cond
Water
Air
Water
Year-Round
Single
Package
SPY-E
SPY-w
Ai r
SPY-A
Evap Cond
Water
Rem0te
Condenser
RC -A
RC-E
RC-W
Air
Evap Cond
Water
Year-Round
Rem0t e
Condenser
RCY-E
RCY-W
Ai r
RCY-A
Evap Cond
Water
Condensing
.Unit Coil
Alone
RCU-A-C
RCU-E-C
RCU-W-C
Air
Evap Cond
Water
Condensing
Unit Coil
and Blower
RCU-A-CB
RCU-E-CB
RCU-W-CB
Air
Evap Cond
Water
Year-Round
Condensing
Unit and Blower
RCUY-A-CB
RCW-E-CB
RCUY-W-CB
Air
Evap Cond
Water
w-,
EVAP
COND
pq
COMP
ICONDJ
(CONDI
COMP
Extracted by permission from Table 1, Chapter46. 1992, ASHRAE System and Equipment Handbook.
A suffix of "-0"following any of the above classifications indicates equipment not intendedfor use with field-instdled duct
systems (See 5.1.3.3b).
Designation
HOSP-A
Single Package
HeatingandHeatingOnly
HSP-A
OUTDOOR
INDOOR
HRC-A-CB
1
1
Remote Outdoor Coil
with No Indoor
Fan
HRC
System
Split System
with No Indoor
Fan
-A-
HRCU-A-CB
HORC-A-CB
~~
HORC-A-C
COMP
HORCU-A-CB
HRCU-A-C
FAN
HORCU-A-C
FAN
COMP
5.13
5.13
Capacities
BUbLYLl
Less than 20,000 [5,900]
.it&Nl
100 [30]
up
20,000 to 38,000,
[5.900 up to 11,0001
38,00065,000.
up to
[I 1,000 up to 19,0001
above.and65,000
[ 19,000 and above]
200 [60]
500 [ 1501
loo0 [300]
TEST
INDOOR UNIT
OUTDOOR UNIT
Air Entering
DB
WB
"F
["Cl
O F
["CI
80
f26.71
67
[ 19.41
80
[26.71
[19.4]
67
80
l26.71
575
80
c26.71
575
Low Temperature
Operation Cooling
67
[19.4]
[13.9]
Insulation Efficiency
80
Condensate Disposal
Conditions
82
[27.8]
65'
[ 18.31
[13.9]
82
[27.8]
65'
[ 18.31
[13.9]
82
[27.8]
65'
[ 18.31
57
67
t13.91
[19.4]
57'
[26.7]
[23.9]
75
80
[26.7]
75*
80
[26.7]
75
[23.9]
80
123.91
[26.7]
75'
80
[26.7]
67
[ 19.41
115
L23.91
[46.1]
75'
Standard Rating
Conditions
High Temperature Heating'
Steady State
70
[21.1]
60
(ma)
[ 15.61
47
L8.31
43
70
[21.1]
60
(ma)
[ 15.61
[21.1]
60
(ma)
[ 15.61
62
[ 15.61
[-8.31
17
C15.61
35
[1.7]
33
75
[23.9]
65
Maximum Operating
Conditions
HEATING
Frost Accumulation
70
60
r23.91
f6.11
116.71
i13.6156.5
[-9.41
15
(ma)
70
[21.1]
1
Maximum Operating
Conditions
80
[26.7]
60
(ma)
'
[0.6]
f18.31
I
INDOOR COIL
OUTDOOR COIL
AIR ENTERING
AIR Eb ERING
TEST
DB
WE!
95
123.91 [35.0]
75l
82
[27.8]
65'
I 18.31
82
127.81
65'
118.31
67
[ 19.41
53s
1 11.91
53.5l
[ I 1.91
[19.4]
67
87
70 115.61
121.11
"F
67
[11.9]
[20.6] 130.61
47 i6.11
18.31
[TI
[19.4]
WE!
"F
53.5'
69'
43
62
[ 16.71
56.5
113.61
62
I 16.71
56.5
[ 13.61
17
18.31
13
16.11
60
47
18.3)
53
16.11
6011.71
35
33
10.61
15
1-9.41
70 115.61
70
121.11
60
I 15.61
17
[-8.3[
All tests are performed at the outdoorfan speed and indoor blower speed Intended
for normal operatlon.
NOTES:
1. Not maintained if no condensate rejectedto outdoor coil.
2. Optional test used to determine the Designed Heating Requirement @HR). The nominal s p e d is the lesser of the cooling and heating maximum
speeds.
3. Optional equations maybe used in lieu of the maximum speed test. The intermediate speed is the same as the cooling intermediate speed.
4. Wet bulb sufficiently low that no condensateforms on evmrator.
:I
ARI STANDARD210~40-94
coefficient is used for one heating mode,it must be
used for both heating modes.
5.13.4
5.135
5.13.6
ARI STANDARD210/240-94
Table 6
I
Standard Capacity Ratings
m
h
iu
m External Resistance
(Thousands of S a ) [kw]
0.10 124.91
0.15 [37.4]
0.20 [49.8]
0.25 [62.3]
0.30 [74.7]
Cooling capacity for units with cooling function:High Temperature Heating Capacityfor heatingonlv units (See 5.1.3.3).
Interpreting this requirement, it is understood that
the most restrictive filters, supplementary heating
coils, and other equipment specified as part of the
unit be in place and.that the net external pressure
specified above is available.
5.13.7 Moismre Removal
Determination.
Indoor air moisture removed shall be determined at
StandardRatingConditions,Coolingforunits
tested in accordance with both ASHRAE Standard
37-1988 and Appendix A. The expression of the
removal rate shall be based upon the net cooling
capacity, including an allowance of 1250 Btu/h per
1,000 cfm [775 W/m2/s] fan heat for blowerless
equipment.
a.
b.
Determinethepart-loadfactor
(PLF) from
Figure 1 "Part-LoadFactor Curve" ateach
rating point (see example Appendix D).
EQG)
'
>
52.1
where:
Any water flow required for system function shall beat
waterflow ratesestablishedat(full
load) Standard
Rating Conditions.
The capacity reduction means maybe adjusted to obtain
the specified step of unloading. No manual adjustment
of indoor and outdoor air quantities from those of the
Standard Rating Conditions shall be made. However,
automatic adjustment of air quantities by system
function is permissible.
PLF =
n =
Superscript 1 =
Subscript 2; 3 etc. =
53.2 Integrated Part Load Value (IPLV). For
equipment covered by this standard, the IPLV(in EER)
shall be calculatedas follows:
Part-LoadFactor
determined from FigureI
specific capacityandEER
at part-load steps per 5.2.
63.1 Temperature
Conditions.
Temperature
conditionsshallbemaintained as shown in Tables 3 or
5.
6 2 3 Voltages. The test shall be run at the Range A
minimumutilization voltage fromARI Standard 1 10-90,
Table 1, based
upon
the
unit's
nameplate
rated
voltage(s). This voltage shall be supplied at the unit's
service connection and at rated frequency.
Procedure. Theequipmentshall be operated
for one hour at the temperature conditions and voltage
specified.
623
5.4.1
Capacify Designation.
capacity
The
designation used in published specifications, literature
or advertising,controlled bythe manufacturer, for
equipment rated underthis standard, are to be expressed
only in Btu/h [Wl at the Standard Rating Conditions
specified in 5.1.3 plus Part Load RatingConditions
specified in 5.2.1 and in the terms described in 5.1.1 and
5.1.2. Horsepower, tons or other units shall not be used
as capacity designation.
5.4.2
6.2.4
Requiremenrs. The equipment
shall
operate
continuously without interruption forany reason for one
hour.
6.2.4.1
Unitswithwater-cooledcondensersshall
be capable of operationunderthesemaximum
conditions at a water-pressure drop not to exceed
15 psi [lo3 Walt measured across the unit.
6 3 Voltage Tolerance Test. Unitaryequipmentshallbe
designed andproducedtopassthefollowingvoltage
tolerance test with acooling coil air quantity as determined
under 5.1.3.3.
63.1 Temperature Conditions.
Temperature
conditions shall be maintained at the Standard Cooling
(and/or StandardHeating, as required) steadystate
conditions as shown in Table 3, Table 4 or Table 5.
633
Voltages.
Test.
Unitary
equipmentshallbedesignedandproducedtopassthe
following maximum operating
conditions test with an indoor
coil air quantity as determined under 5.1.3.3.
6.2 Maximum Operating
Conditions
.lo
6.3.2.2 Thepower
supplied to single
phase
equipmentshall be adjusted just prior to the
shutdown period (see 6.3.3.2) so that the resulting
is percent
voltage at the unit's service connection 86
of nameplate rated voltage when the compressor
motor isonlocked-rotor.
(For 200V or 208V
nameplate rated equipment the
restart voltage shall
be set at 180V when the compressor motor is on
locked rotor). Open circuit voltage for three-phase
equipment shall not be greater than 90 percent of
nameplate rated voltage.
..
-0.12773917 X lo-''
= -0.27648713 X l o - '
=
0.50672449 x
= -0.25966636 X lo-'
=
0.69875354 x 10 - "
= -0.76859712 X l o - "
= 0.28918272 x 10- I "
=
11
6.3.32
63.4
Procedure.
Requirements.
6.3.4.1
--
6.3.4.2
653
Temperature
Conditions.
Temperature
Conditions shall be maintained as shown in Table 3 or
Table 5.
6.6.1
6.4.1
6.4.2
6.43 Requirements.
6.43.1 Duringthe
entire test,theequipment
shall operate without damage or failure of any of
its parts.
12
65.2
5.
6.62
ARI STANDARD21Oi240-94
6.7 Tolerances. ' The conditions for the tests outlined
in
13
"
APPENDIX A.
*Uniform Test Method for Measuring the Energy Consumption of Central Air-Conditioners
Foreword
an5
"F
coo-
perid i
c
o
o
?
?e-
14
'
tral air conditioner in which allthe major assemblies are enclosed in one cabinet.
A131 "Split system" means any central air
conditioner in which oneor more of the major
assemblies are separatefrom the others.
A1.22 "Steady-state test" means a test in
which all indoor and outdoor conditions are
held constant and the unit is in non-changing
operating mode.
A123 Temperature bin" means a 5 F inmement over a dry-bulb temperature range of
65 F through 104 F for the cooling cycle and
25 F through64 F for the heatingcycle.
A1.24 "Time-temperaturedefrostcontrol
system" means a systemwhch automatically
provides the defrost function a t a predetermined time interval whenever the outdoor
temperature drops below a level where frostingWillOCCUr.
Al.25 T e s t condition tolerance" means the
maximum permissible variation of the averaee of the test observations fromthe standard
oFdesired test condition as provided inA6.1.1,
A6.2.2, and A6.2.3.
Al.26 Test operating tolerance" methe
maximum permissible difference between
the
maximum and the minimum instrument observation during atest as provided in A6.1.1,
A6.2.1, A6.2.2 and A6.2.3.
A1.27 "Wet-coil test"means a t e s t conducted at a wet-bulb temperature and a drybulb temperature suchthat moisture will condense on the test unit evaporatorcoil.
A 1 3 "Central air conditioner" (DOE Covered) meansa product, other than a packaged
terminal air conditioner powered by single
phase electric current. which is air-cooled,
rated below 65,000 Btuh, not contained
within the same cabinet as a furnace, the
rated capacityof which is above 225.000 Btuh,
and is a heat pump or acooling only unit.
Al.29 "Heat pump" (DOE Covered) means a
product, other than a packaged terminal heat
pump, which consists of one or more assemblies, powered by single phase electric current, rated below 65,000 Btuh, utiliz'
indoor conditioning coil, compressor,
frigerant-to-outdoor air heat exchanger to
provide air h e a 3 . and may also provideair
amling, dehum ymg, humidifying drculating, and a m cleaning.
A130 "Coil family" means a p u p of wi
with the same basic design features that affect the heat exchanger performance. These
features are the basic c o d
tion, Le., Ashape, V-shape, slanted or E o p , the heat
transfer surfaces on refi rant and air sides
(flat tubes ys. grooyed
fin *pes),. the
tube and fin matenals. and the cod m
t
r
y
.
When a group of coils has all these features
in common. it constitutes a'
c
o
i
l
family."
32
tUEs,
A2. Testing R e q u i d
-ARI
STANDARD210/240-94
15
16
be installed
according
to the
of
Section 8.6 of ASHRAE Standad.9T48urd
Section 5.1.3.5 of AFU Stand& 9
4
Test
chamber
requirements
are tht
as
formed at the maximum s d a t e d o n s pven in Section8.1 of ASKRAE Shnfard 37Units designed for both ho1and
specified in sectionA3.1.1. E t B, a n $ h low 88.
vertical installation shall be testedt;zctheoritemperature test are performed a t &%mini- entation
which they are m o s t &en inmum speed with outdoor dry bulb. t s q e r a - stalled. Allintests
shallbe performectamhe nortures of 82 F and 67 F respectively. interresidential voltage and f m q for
mediate speed wetcoil test is peFsomred at mal
which the equipment is m e &<e&er I15
the outdoor dry bulb temperature d85E For or
230 volts and 60 hertz). Valuesocapacity
units which reject condensatet h e d a m w e t
rating purposes are to be rouded off to
bulb temperature shall be maintarmkd.,nt75 F for
nearest 100 Btuhfor capacities-Less than
835F for the
for Test A. 65 F for Tests B and Bc.
Btuh: to the nearest 200 -for
cathe low temperature test and6 9 F &
x!&e in- 20.000
between 20,000 and 37.999BtuIx and
termediate test. The indoor con&hmrjr iir all pacities
to the nearest500 Btuh for capacitiekretween
wet coil tests are the sameas t h s s
in 38.000
and 64,999 Btuh.
section A3.1.1.
A
3
.
2
.
1
conditions for U R L ~~ G t sinh
A3.1.6.2 Test conditions for ctrlr.xiitests. gle speed Testing
compressors.
Dry coil Tests C and D are conh??di& an
outdoor dry bulb temperature &Et?FE For A3.2.1.1 High temperature test rmditions.
units which reject condensate themut.itmrwet The High Temperature Test a t 47 Q shall he
bulb temperature shall be m-t
a t conducted a t a n outdoor dry-bulb-Impera53.5 F. The indoor dry bulbtempemtumeshall ture of 47 F and anoutdoor wet-bulb temperbe 80 F and the wet bulb tempemtra=shall
ature of 43 F. The High Temperarur-eTest at
be sufficiently low so no condensatim w u r s 62 F shallbe conducted at an outdoordry-bulb
on the evaporator (It
is r e c o m m e d e d t b t a n temperature of 62 F and an outdoorwet-bulb
indoor wetbulb temperatureof 57 B cn ltrss be temperature of56.5F. For both tes&s.thedqbulb air temperature enteringand?wnroundused).
ing the indoor portion of the unitsldlbe 70 F
A3.1.7 Split-type ductless systemc Tctetaon- and a maximum wet-bulb tempmature of
ditions shallbe the same as thosesgwjfiei for 60 F. The duration of the tests shall: be for a
the same single
outdoor unit compvswu-type, minimum of Yl hour.
assuming i t was matched with a smgSeiircloor A3.2.1.2 Cyclin test conditions The Cycoil.
I shall be conductat at the
cling Test at 47 !
A3.1.7.1 Interconnection. F o r qxi5ritype same dry-bulb and wet-bulb temperature as
ductless systems, all standard reti= tksts the High Temperature Test at 17 F as deshall be performed with a minimum Irsmhof scribed in A3.2.1.1. During the Cycling Test,
25 feet of interconnecting tub& IxTween the indoor fan shall cycle on and off, as the
each indoor fan-coilunit and t h e cmmmonout- compressor cycles on and off, except that
door unit. Such equipmentin whichtkteixter- the indoor fan cycling times may be delayed
due to controls that are normally installed
connection tubing is furnishedas a m . h?gral
with the unit. The compressor cycling times
part of the machine not recornm&$S+cutting to length shall be tested wrtmmzxplete shall be 6 minutes On and 24 minutes off..
length of tubing furnished, or with Z5 :Bet of The test installation shall be designed such
tubing, whichever is greater. At keas!; feet that there will be no airflow through the inof the intercnnection tubin+ s h e & :+xqosed door unit due to naturalor forced convection
<me.
In- while the indoor fan is off. This slrall be aeto the outside conditions. he 1sulation and detailsof installation .dsdi3e in complished by installing dampers upstream
accordance with the manufactwnuis Rub- and downstream of the test unit to block the
off period airflow.
lished recommendation.
A3.2.13 Frost accumulation test conditions.
A3.1.7.2 Controltestzng conditims +Flittype ductless systems. For split-type c i d e s s The dry-bulb temperature and the resultant
the
systems. a single control circuit &d.!aesub- dew-point temperature of the air entering
stituted for any multiple t h e r m o ~ . - i n m d e r outdoor portion of the unit shall be 35 F and
to maintain auniform cyclingrate &zl.;i.qgtest 30 F respectively. The indoor dry-bulb temD and the hi h temperature heabsg cyclic perature shall be 70 F and the maximum indoor wet-bulb temperature shallbe 60 F. 1:e
test. During t i e steady-state tesw.,aCi +hermostats shallbe shunted resltingixcaI3 d o o r Frost Accumulation Test requires t h t the
unit undergo a defrost prior to
the actual test.
fan-coil units being in operation.
test then begms a t defrost termination
A3.1.7.3 Split-typeductless ~ S & . W T ~.uith The
and ends at the next defrost termination. Demultiple coils or multiple dtsckmge cadets
termination occurs when the controls
shall have short plenums attached ~9 w d w u t - frost
normally
installed within the unit are aclet. Each lenum shall discharge i&na%ngle
tuated to cause itto change defrostoperatim
common xuct section, the duct &.wirnturn
normal heating operation. During thetest,
discharging into the air measuring&-mice (or to
auxiliary resistance heaters shall not be ema suitable dampering device when (SImutair ployed
m
during either the heating nr d
measurement is not employed). E~&~$i.mum
shall have an adjustable restrictm lraatad In portion of the test.
the plane where the lenums enter cikmm- A3.2.1.4 Low temperature test cozrdirinm.
b
e
mon duct sectionfore!t purpose o f q d l j d n g The Low Temperature Test shall
the static pressures in each plenrum. The at a dry-bulb temperature entering the outdoor portion of the unitof 17 F and a w e t a b
length of the plenum is a minimum a f r 325 x
(A x B)?,A = width and B = hex@ih,~Kduct temperature of 15 F. The air enterin the inor outlet. Static pressure readings metdcen door portion of the unit shall havea &-bulb
a t a distance of 2 X (A x B) frormt!hexutiet. temperature of 70 F and a maxlmum wet-bdb
A3.2 Testing conditions for air auu-w &at- temperature of 60 F.
Additional testing conditions. All
zng only units. The equipment underbwthall A3.2.1.5
-
--.
.
X
?
,
tested in such a manner that when operated time (e,,) of 60 minutes. In lieuof conductin
under steady-stateconditions, the cooling coil C and D tests, an assigned value of 0.25 sld?
and condenser coil alr flows meet the reauire- be used for the degradationcoefficient for molments of Sections 5.1.3.4. 5.1.3.5,and 5:1.3.6 ing. C,.
of A R I Standard 210/240-94.
A4.1.1.3 Testingproceduresfor triple-capac.
A4.1.1 Test operating procedures.
ity compressors. (Reserved)
A4.1.1.1 Steady-state wet-coil performance A4.1.1.4 Intermediatecoolingsteady-state
tests (Test A and Test B/.Steady-state wet-coil test for units with
carzable-speed compressors.
performance tests ( A and B) shall be con- For units with variable-speed compressors,an
ducted in accordance with the conditions de- intermediate cooling steady-state test shall be
scribed in sections A3.1.1.1, A3.1.2, A3.1.3,
conducted in whlch the unit shallbe operated
A3.1.4. and A3.1.5 of this appendix and the a t a constant, intermediate compressor speed
test procedures described for cooling tests in tk= i ) in which the dry-bulb and wet-bulb
Section 8 of ASHRAE standard 37-88 and temperatures of the alr entering the indoor
evaluated in accordance with the cooling-re- coil are 80 F,, and 6i F,, and theoutdoor coil
lated requirements of Section 10 of the ASH- are 87 DB and 69 FwR.The tolerances for the
RAE Standard 37-88. The test room recondi- dry-bulb and wet-bulb temperatures of the air
tioning apparatus and the equipment under
entering theindoor and outdoor coils shall &
test shall be operated until equilibrium con- the test operating tolerance and test
condition
ditions are attained.
tolerance specified in A6.1.1. The intermediate compressor speed shall be the minimum
A4.1.1.2 Steadystate and cyclir and dry-coil compressor
speed plus one-third the differperformance tests (Test C and Dl.The steady- ence
between the max~mum and minimum
state and cyclic dry-coil tests (C and D)shall speeds
of the cooling mode. (Inter. speed =
be conducted as described belowin accordance min. speed
13 max. speed - min. s
with the conditions described in sections
of plus five percent or
A3.1.1.2. A3.1.2. A3.1.3. A3.1.4. and A3.1.5 tolerance
higher inverter frequency step frqm that c a l and A3.1.6.2. The results shall be evaluated culated
ls allowed.
in accordance with the cooling related reA4.1.1.5 Testingprocedures forsplit-type
quirements of Section 10.1.5, 10.1.6 and
10.1.7. of ASHRAE Standard 37-88. The test ductless systems.Cyclic tests of ductless units
room reconditioning apparatus and the
equip- will be conducted without dampers The data
ment under test shall be operated until equi- cycle shall be preceded by a minimum of two
cycles in which the indoor fan cycles on and
librium conditions are attained, but notfor
less than one hour before data for test C are off with the compressor. For the datacycle the
recorded. For all equipment test methods in- indoor fan will operate three minutesprior to
cluding the Compressor Calibration Method, compressor cut-on and remain on for three
test C shall be performed with data recorded minutes aftercompressor cut-off. The integraat lominute intervals until four consecutive tion time for capacity andpower shall be from
sets of readings are attained with the toler- compressor cut-on time to indoor fan cut-off
ance prescribed in Section 9.2 of ASHRAE time. The fan power for three minutes aRer
Standard 37-88. When the Air-Enthalpy compressor cut-off shall be added to the inteMethod is used on the outdoor side for testC, grated cooling capacity.
the requirements of this section shall applyto A4.1.2 Testznstrmentation. Thesteadyboth the preliminary test and the regular
state and cyclic performance tests shall have
equpment test; the requirements of Section the
same requirements pertaining to instru8.5 of ASHRAE Standard 37-88 shall also ap- mentation
and data as those
specified in Secply. Immediately after testC is completed the tion 5 and Table
of ASHRAE Standard 37test unit shall be manually cycled off and 88. For the cyclic5dry-coil
performance tests.
on using the time
penods from A3.1.1 of this the dry-bulb temperature of
the air entering
Appendix untd steadily repeating ambient
leaving the cooling coil, or the difference
conditions are again achieved in both the in- and
between these two dry-bulb temperatures,
door and outdoor test chambers, but for not shall
be continuousIyrecorded with instruless than 2 complete offPon cycles.
Without mentation
to within = 0.3 F of india break in the cycling pattern, the unit shall cated valueaccurate
and have a response time of 2.5
be run through an additional offYon cycle seconds or less. Response time is the time reduring which the test data required in A5.1
for the instrumentation to obtain 63
shall be recorded. Durmg this last cycle, quired
percent of the final steady-state temperature
which is referred to as the test cycle, the in- difference
when subjected to a step chan
door and olltdoor test room ambient condi- temperature
difference of 15 F or more.
tlons shall remain wthin the tolerances spec- trical measurement
(watt-hour meified in A4.1.3 dunng thecyclic dry-coil tests, ters) used during all devices
tests shall
be accurate to
all air moving equipment on the condenser within ~ 0 . percent
5
of
indicated
value.
side shall cycle on and O F when the compressor cycles on and off. The indoor air A4.1.3 Testtolerances. All steady-state wetmoving equipment shall also cycle off as and dry-coil performance tests shall be pergoverned by any automatic controlsnormally formed within the applicable operating and
installed with the unit. This last requirement test condition tolerances s cified in Section
applies to units havingan indoor fan timede- 9.2 and Table 4 of A S H d S t a n d a r d 37-88.
lay. Units not suppliedwith an indoorfan
time delay shall have the indoor air moving A4.1.3.1 The indoor andoutdooraverage
equipment cycleon and OWas the com- dry-bulb temperature for the cyclic dry coil
test D shall both be within 1.0 F of the indoor
pressor cycles onand off,
for
Cooling cyclictests for Variable-speed units and outdoor average dry bulb temperature
shall be conducted by cycling the com ressor the steady-state drycoil test C,respectively.
12 minutesonand 48 minutesoff. h e ca- 4.1.33 The testcondition and test operating
pacity shall be measured for the integration tolerances for conducting test D are stated in
time (8).which is the compressor on time of A6.1.1. Variation in the test conditions
12 minutes or the on time as extended by greater than the tolerances prescribed in
fan delay,if so equipped. The electrical energy A6.1.1 shall invalidate the
test. I t is suggested
shall be measured for the total integration
that an electric resistance heater having a
17
Y"-
e-'
type
i
n
%
18
%tan-
,E dry
the tolerances specified in Section A6.2,l. .
Variation greater than those oven shall in(iii) Indoora i r flow rate (SCFM)and extervalidate thetest. The heating capacity results nal resistance to indoor a i r flow (inches of
water W.C.).
by the indoor Air Enthalpy Method shall
agree within 6 percent of the value deter(iv)Air temperatures (F)
mined by any othersimultaneously conducted Outdoor dry bulb
capacity test in orderfor the test tobe valid. Outdoor wet bulb
A 4 3 3 2 Test tolerances for the cyclic test. Indoor dry bulb
The test condition tolerances and test oper- Indoor wet bulb
ating tolerances for the on-period portion of
Where t h e .cooling capacities Q ..' (95.F).
the test cycle are specified in Section A6.2.2. from test
Q.,' (82). from test B. and Q...
Variations exceeding anyspecified test toler- dry, from A,
test C. are calculated using the
ances shall invalidate the test results.
.SHRAE
equation specified in section 7.3.3of4
A42.3.3 Test tolerances for thefrost accu- Standard 37-88. The total cooling done. Q,
mulation test. Test condition and test operat- dry from test D, is calculated using equation
ing tolerances for Frost Accumulation Tests ( 1 )below.
Units which do not have
indoor air circulatare specified in Section A6.2.3. Test operating
tolerances during heating applies when the ing fans furnishedas parr of the model shall
unit is in the heating mode, exceptfor the first have their measured total coolin capacities
5 minutes after the termination of a defrost adjusted by subtracting 1250 Bt& per 1,OOO
cycle. Test operatin tolerance during defrost CFM of measured indoor air flow and adapplies duringa defrost cycle and during the to the total steady-state electrical power input
first 5 minutes after defrost terminationwhen 365 watts per 1,OOO CFM of measured indoor
the unit is operating in the heatmg mode. In air flow.
Energy efficiency ratios from tests A, B, and
determining whether thetest condition tolerances are met, onlythe heatingportion of the C.EER,, EER,, EER,., dry respectively, are
test period shall be used n caicula
the av- each calculatedas the ratio of the totalcooling
erage values. v h a t i o n s e x c e h s e toler- capaaty in Btuh to the total electrical power
ances presented in Section A6.2.3 shall inval- input in watts.
idate the test.
Units which do not have
indoor air circulatA4.2.3.4 Test tolemnces for the low temper- ing fans Furnished as part of the model shall
ature test. During the test period for the Low adjust their total cooling done and energy
used in one complete cyclefor the effect of
Temperature Test, the operating conditions circulating
indoor air equipment power. The
shall be within the tolerances specified in Sec- vaue
to be used for the circulating indoor air
tion A6.2.1.
equipment power shall be 1250 Btuh per
A43 Testing procedures for air source units 1,OOO CFM of circulating indoor air. The enwhich provide both hating and cooling. The ergy usage required in one comlete cycle retesting procedures for units which provide quired for indoor
air circulation is the product
both heating andcooiing shall be the same as of the circulating indoor air equipment power
those specified in Sections A4.1 and A4.2. Also and the durationof time in one cycle that the
during the off-period of the dry-coil cooling circulating indoor air equipment is
on. The
test (test D),the switch-over valve shall re- total cooling done shall thenbe the measured
main in the cooling mode, unless the controls cooling in one complete cycle minus the ennormally supplied with the unit are designed ergy usage required for indoor air circulation
to reverse it, in which case the controls shall in one complete cycle. The total electrical enoperate the valve. During the off-period of the ergy usage shall be the sum of the energy
cyclic test a t 47 F, the switch-over valve shall usage required forindoor air circulation in
remain in the heating mode, unless the con- one complete cycle and theenergy used bythe
trols normally supplied with the unit are de- remaining equipment components (compressigned to reverse it. in which case the controls soT(s). outdoor fan. crankcase heater. transshall operate the valve.
formerb). etc.) in one complete test cycle.
efficiency ratio from tests D. EERA5.0 Calculations for performuncefactors. (,.,. Energy
dry is calculated as the ratio of the total
AS-1 Calcuiations of seasonalenergy effi- cooling done in Btu's to the
total electrical enciency ratios (SEER)in air-source unats. The ergy usage in watt-hours.
testir4 data and resultsrequired to calculate
the seasonal energy efficiency ratio (SEER)in
Btu's per watt-hour shall include the following:
( i ) Cooling capacities (Btuh)from tests.A
and B and, if applicable, the cooling capaaty
(Btuh) from test C and the total cooling done
from test D (Btu's).
19
where
Q..
d r , = T ~ t .canling
l
over a eye10 cornisling of one
compressor "off' p n o d and one mmp.&on"penod (Btll's).
V=lndoor a1r flow nte (cfm) at the dry-bulb
temperature.hllmidityratio.
and prasw
exsung 111 the reglon ofmcIuuemLnt.
C,.=Spec~~heat a t constant resure of airwater
mlxturp
per pounS of dry .L,
I,
SEER-PLF(O.5) X EERB
where
EERs-en
-Tin
efkiency ntio
determined
from
where
whzre .
CLF-coolina l a d factor.
Q-.dry = Total steady-statecoohng capacltv from test C
IBtuhl
r=D~lrsrlonof tImc(hours) for one Wmplcte
cycle consmng of one comprewr ''on'' tuna
and one compressor "otl" tlme.
where
@ \ - I ~ T ,=I Steadv-statecwllngcapac:tyIBtuh~attemper
aturei IT,1 from sectlon A5 1 3
PtF(3.5)=1-0.5XC0
where
Q(Ti)=ntio
bln
"r
15
01
total cooling
tu)
in tempentllre
fmmA6.1.2.
where
E~=ntloofEnergy~e(watt-hr.)intempcrat:trr
bin j to the number of temperaruse bmhol~rs.
PLF.L-'=l-~D-'(l-x~-l).
7',)=Qaak(95 F)
20
A5.13.5
hr. using
Q( Ti)
Similarly, ener
perature T,and
equations:
and
where
E,.~h-L.CT,l
the electncal power lnput requlred by the
unlt to deliver capaclty matchmgthe building load a t temperature q.
where
QSsk-'(T
)-the capaclty deliveredby the unit
ma&&
the buildlng load at temperature
T.
EER,'-'~T,I = t h e steady-state energy efficiency ratlo at
temperature T, and an intermedlatespeed
at whlch the unlt capacity matches the
buildmg load.
@c'(T,)
Where:
Qs.'
where
temperatureatwhlchtheunlt.operat1ngat
t h e m ~ n ~ m ucompressor
m
speed. dellvers
capfcltyequal t o thebulldlngload
16,. 1(TII=BLtT3)).found bv e uatm
the capaclty equatlon l ( Q , , k ' i , 4 ~ l an!
building load equation IBL IT 11 in sectton
A5.1.3 and solvlng for temperiture.
temperature a t whlch the unlt, operating
at
the maxlmum compressor speed. delivers
capacitvequal t o thebulldlngload
I Q . . ' - ~ ~ ? ~ ~ =(T21l.
E L found bv equatlng
the capaclty equatlon I ~ Q , ~ ' = ~and
( T ,the
)I
buiId~ngequat~onlBL~T,~IinsectronA5.1.3
and solvlng for temperature.
EER..' .the steady state energy efficiency ratlo at
the mlnlmum compressor speed a t temperature TI.
EERS,'-'(T2l=the
steady state energy efficiency ratio at
the maxlmum compressor speed at temper.
ature Tz.
-'iT~l=
the electrlcal power Input at the mlnimum
compressor speed at temperature T I . calculated by the equhon ~nsectlon A5.1.3.
*f T ~= the
I electrlcal power Input at the maxlmum
compressor speed at temperature T2. calculated by the equation In sectlon A5.1.3.
T, + C
'I:
CIS_Q(T
N1
1
E(T )
SEER =
C,"l $-
e;
82 - 67
X
F;'(T,)
(82
M,=scopeoftheelectr~calpower~nputcurveforthe
mtermediate compressor speedlk = 1 1
T,)
E $ i 1 ( 8 2F)
X 1 - NE)
E:,- '(67 F) - E:,- Y82 F)
f
82 - 67
x (82 - T , )
Case I1 is when the compressor operates a t
any intermediate ( k= u) speed between the
maximum (k= 2) and minimum (k= 1) speeds
The energy efficiency ratio of the unit,
to satisfy the building cooling load. Evaluate
EERJT,), at the intermediate speed (k= i)
the following equations:
and temperature T, can be calculated by the
B t ; " ( T , ) = BL(T,)
equation:
=
21
Ecye(40.
EDEF@).
tiiil Indoor air flow rate tSCFM1 andexternal resistance toindoor air flow (Inches
of water W.C.)
(iv) Air temperature (F)
Outdoor dry bulb
Outdoor wet bulb or dew point
Indoor dry bulb and
Indoor wet hulh.
( V I Data as specified in Tab& 5 of ASHRAE Standard 37-88
Where the heating capacities Q . , ( 4 7 ) ,
Q,,(62)and Q,,\(17)and theindoor air flow rate
are calculated usingthe equationsspecified in
section 7.3.4 and 7.8.3of A S H W standard
37-88. Thetotalheating
done, Q,,(47) and
Q ( & 3 5 )are calculated using the equations
below.
Units not having an indoor fan as part of
the model tested shall add 1250 Btuh per
1.000 SCFM of indoor air handled to the
measured capacity to obtainthe total heating
capacity,Q,.(17). Q,,(47), or Q,,(62). and add
365 watts per 1,000 SCFM of indoor alr handled tothe measuredpower to obtainthe total
power input, E,>(17), E,,(47),
or E,,(62),to the
unit.
T h e coeffirients of performance (COP)
for the High Temperature Tests cOP,,f62)
or COP..(47), and Low Temperature Test,
COP..(l7), arecalculated as theratio of
the
heatin
capacity Btuh
in
to the
product of 5.413 and the power inptits to
the indoorfanin
wattsandthc
power
inputs to the remainingeqcipment coinponents (inciucliog all controls) in watts.
Units which do not have indoor air ciras pnrt of the
culating
fans
furnished
modelshallhavetheir
total hearing done
(Q,,.i47)) and energy used E,,,(47) in one
complete cycle adjustcd for the effect of
circulatingindoorairequipment
power.
For units tc>ted without
an indoor f3n 1s
part of the model, Q0,(47) shall !)e increased by a quantity of heat equal to the
product
of
1250 Btuh.per
1,000 SCFM,
the length of the on-period of the test cycle
in hours, and the flow rate of indoorair
cmulated in units of 1,000 SCFM. The
total energy usage, K y O ( 4 7 )shall
,
he t:le
sum of thecnelgy usagerequired for n ~ r
circulationduringt5etest
cycle :md the
energy u.cec! I)y the remninlngeqtlipment
components (including all controls) tlurmg
the test cyc!c. Units not hnvinp an indoor
fan as part of the moclcl tested, shall set the
energy reqlliredforindooraircirculation
qua! to the quantitygiven by the product
of 365 watts per 1000 SCFM, the length of
the on-period of t h e t e s t cycle in houls, and
Lhe rate of indoor air circulated in units of
lo00 SCFM.
The cyclic
coefficient
of performance,
coPey,(47) is calcuiated as the ratio of the
total heatingdone (Qcrc(47))in Btus to
the productof 3.413 Btulwatt-hour and the
total energy usage (E.,.(47)? in watt hours.
The net heating capacity,Q uEbi35)Btuh, is
the total net heatingdone over the testpenod
( ~ncluding any
credit for the indoor fan heat)
divided hy the total length of the test period,
hours.
22
- 0 03 , I X
T,,
.I - 90111T
,,,.,- 90 1 t
where:
F,,.,=dernand defrostcredlr lused as a rnultlpllerto
HSPF
where
V5 the average of the alr h
o
u rawcalculated at four
or more time Intervals throughout the heatme
hase of the testusin the equatlon In scctmn
P.8.3 of ASHRAE Stanfard 37.88
C,.=SpecrIicheat
at colnsmlt p m s l l r e Of air-r&tC
rnlxture per pound of dry alr. IBtu/lb-FI.
V . x = m m n c v o w n e 01 alr-water r n l x t w r at thr s m r
ratio. and pm
dry-hudb lemperatttre. htlrnld~~y
slue used rn I.he devrmlnstlon 01 the Indoor l l r
llow rate bftTlb).
H;=&un~diry ratio(lbilbj.
where
n-hm
~ 4 4 7 )8s d&ed
&(Ai)
where
-V= the
flow
above
u definedabove
A5.2.1
HSPF
door cod < F I a i time I I I
T.z(f)=br~-ouiutemperalure 01 a r ieavmg the indoorco~l~flattmelrl
Thenet
heating, QDEF (35) in Btus
done during the test period shall !,e detcrmined using the foilowing equation:
where
RH;T,)=suppkmentary
resistance
heat
turn at
3'
l e m p e r a t w T, reqrured m those eayS where
the
heat
pump
automat!cdlY
f u n s Oc
iT,<T.,q]) or when 11 IS needed to m e t the
balance of the bu1lQng hurrng requIrm1enrJ.
tW81W.
2 =IS the
B tu.
PLF(S) and
RH(T;)
as defined In A5 2.1
s as defined In A5.2 !
n,
where
T,as defined In A5 2
N
are defined'by the following equations:
Q,
E, shall be obtained
In Btuh
where
(xinimum design hcsting requiremeEtj
where
(C)=O.7i is a correction factor a h i c h tcnds to
mmprove the agreement brrreen calcnlstfd
and mensurd buildmploads
(DlfR)=the mlnimtun and msxlmumdesign hratlne
requuur.ent rluch the beat pump is hkely
1
.
0 encounter r h r n tnstalltd In a residzpcr.
rounded 05to the neswt nandsrdlred
DER
In sectton A626 in Btuh
KheR
and
(556p)
for regions I,
~,,(47)
=I
11, 111,
IV, and VI
0,,(47), for region
.2&:(47)
for region V
where
and
.
maximum design heating requirement
Q,,'*-"1471
Too
11, 111,
IV, and VI
2.20,.(47), for region V
where
Q,, (GT) IS thc h e a t pnmp capacity messmed dunng
10;T i I T o m
and
where $..(47) and E..*(47)and QDEF(35)
E,,(47)andQ..t17)andE..(17)arethecapacities (in Btuh) and powers (in watts), measure.! during the High Temperature Test, the
Frost Accumulat~on test, and the Low Temperature Test. respectively.
"For each of the six re '0116specified in section A6.2.5, calculate t f e heating seasonal
performancefactors and seasonal operating
costs corresponding to the standardized maximum and minimumdesignheatinguirements and for all other standardM%gn
heating requirements (see secti0n~A6.2.8)
between the maximum and theminimum.
A532 Calculation of the heating seasonal
performance factor (HSPF)for air
source heat pumps with a two-speed
compressor, two compressors, or cylinder unloading.
Foreach climatic re nlistedin
section
h6.2;4. szd-for design g a t i n g requirements
L.
*he
standardized
minimum
and
--...
. A . G . - . . ~ ~ : ~ . heating
requirementsdehned Mow. calculate the HSPFdefined as:
RHIT,I
c-1.c:
I
d
~
g
n
23
BL(Ts) 1 e 2 ( T i )
17 F<T,<45 F
and low speed or single compressor operation ( k = l ) to satisfy the building heating
load at temperature Ti.
&-*
( Ti)
=
Ti)<BL(T,)<Qc-'( Ti)
For each of the six reQons specified in section A6.2.5.calculate the heating seasonal
performance factors and seasonal operating
costs correspondmg to the standardized
maximum and minimum design heating requirements and for all other standardized design
heating requirements ( s e e section A6.2.6) between the maxirnum and the minimum.
A
S
S Heating sccsonal performance fzctor
for air-source units with tripLecapacity corn
pressors. I R e s e r v e d )
A 5 2 4 Heating seasonal performance fzctor
for units with variable-speedcompressors. For
units with variable-speed compressors, the
heating seasonal performance factor (HSPF!
is defined by the following equation:
HSPF
24
P-YT,) = BL;(T,)
- Ti
- T$
T:
T8i
where:
&'i351
ME
at
47
Iv,,
e-
A5.2.2.
A525 Heating seasonal performance fmtm
The coefficient of performance, COF"-'(T,,), for split-type ductless systems. For split-type
at the intermediate speed ( K = i ) and temper- ductless systems, HSPF shall be defined as
ature T,,can be calculated by the equation:
specified in section A5.2.1of this Appendix.
Separate valuesof HSPF shall be determined
for each correspondingcombination set of indoor cots used in the develo ment of SEER
Similarly, coefficients of performance a t as specified in section A5.1.7. h e calculations
temperature T3 and T,can be calculated by used shall be the same asthose used for unit
with the same type of compressor.
the equations:
A53 Calculations of the Actual Represenbt i w Regional Annual PerformanceFac. tors of Air Source Central A
k
r Codtioners (Heat Pum sl Which Provide
Both Heating and &ling.
A5.3.1
Calculation of actual re 'onalannual
performancefactors (A$F,) for a particular locahon and for each standardized design heatingrequirement.
where:
@-I'(ql
=capacrty
delivered by the unita t any Intermedrate speed between the mrnimum and
manmum compressor speed matchxng the
buildrng load at temperatureT,.
,C"-"IT,)=theelcctrrcal power Input rqulred by the
unit at temperature T ta delmer capacity
marchmr the buildinghad
COP'. "fql= the coefficrent of perfornunce at which the
unrt delivers capanty matehrng the buildIng load a t temperature T,
Q@351=
~k=i~rnthefmnMlmulatioetest
Mq = slope of the capacity curve for the intermediate compressorspeed (& = E l
where
tCL&I
is the actual cooling load hours for the partrcular loutron. detenarned fromthe map in
m t l o n A6.1.3.
IQ,*(95Fll IS defined In A5.1.
IDHRI IS defined rn A5.2.2.
CCI ISdefined in A5.2.2.
f H M A 1 is the actual heaung load hours for the partrcular loeation determrned from the map
rcction A6.2.5.
(SEER1is the
energy efiiciency ratio detcrmrned m ractmn A5.1.
IHSPF) is the beatan seaaonal performance factors
udetcrmrne8in s+ionA5.2~forearhrc+u d i ,&sign heapng rquvrment n b
the partrcular I w t ~ o In region or for the .etual design heatingrequirement if k n o w n .
season+
where the particular location's region is determined from map in section A6.2.5and, the
standardized design heating requirements
within the region are determined in sections
A52 and A6.2.6.
25
A5.3.2
(APFR)=
'
(CLHR)(QSt(95F)1
( H L H R )( D H R )( C )
(CLHR)(&.'(~~F)
SEER
( H L H R )( D H R ) ( C )
+
HSPP
%.'
26
where
ICLHHI
ISthe
.. .. .. .. .. .. ..-.
.
.....
c n v m - m ~ m . +
'0
a+f-wmmm
0 0 0 0 0 0 0 4 CJ
u u u u u u u
n
moLT.oLnoLno
0
a++rnemm-l
- ~ N P . I . P ~ W * W
.4
n c
In
Ln
.0.
.II
PPI
c urla
LC
... u....
.
al. PI..
r d
L.
u .
.d
m
Y
c .
c .
.4
.c.
3 Gu-uj-
doccoal
27
8::::::
I
F?
rl
;::::::
0o 0o 0o 0o 0a 8
919c?9(90,
0100N10rnO
1 1 1 1 1 1 1
28
.
I
m.
.*
t e
n~
I I
0:
..
-2
C Y
1:
1:
S
j
r..
?
I
Nl
9
N
M
4
a.
1
a
W
L
0
0
Y
ii
n~
39
0:
99
-.d
n~
0:
99
--.
c.cI
a.
Y
a
Y
0
0
0
LI
"
? i
a
Y
:
L
0
::
d
29
n
0
. I
1
II tI
0U 1I
9 :
N I
.,
30
0
0
00
31
(Btuh)
Heating
ments DesignStandardA6.2.6
A6.3
5,000
25 ,000
50,000
90,000
10,000
30,000
60,000
100,000
15 ,000
35 ,000
70,000
110,000
20,000
40,000
=R
I
I1
i F R Doc. -38293
32
2400
1250
750
1800
I11
1200
1750
IV
800
2250
4 00
2750
VI
200
2750
Ground Water
Temperature
Filed 12-17-79: 8:Uam]
130,00080,000
A6.4
Map (Reserved)
ARI STANDARD2101240-94
APPENDIX B. REFERENCES
B1 Listed here are all standards, handbooks andother
publications essentialto the formation and implementation of
the standard. All references in this appendix are considered
as part of this standard.
B1.1 ASHRAE Handbook of Heating,Ventilating,
and
Air
Conditioning
Systems
and
Equipment.
American Society of Heating, Refrigerating, and AirConditioning Engineers, Inc., 1791 Tullie Cicle N.E.,
Atlanta, GA 30329, U.S.A.
B1.2 ASHRAE Termimlogy of Hearing, Ventilation,
Air Conditioning & Refrigeration. American Society of
Heatmg, Refrigerating, andAir-conditioning Engineers,
Inc.. 1991, 1791 Tullie Circle N.E., Atlanta, GA 30329,
U.S.A.
B 1 3 ASHRAE Standard 37-1988, Methods of
Testing for Rating Unitary Air-conditioning and Heat
Pump
Equipment,
American Society of Heating,
Refrigerating,and Air-conditioning Engineers. Inc.,
1988,1791 Tullie Circle N.E., Atlanta, GA 30329,
U.S.A.
33
APPENDIX
PRESCRIPTIVE
C.
METHODOLOGY
FOR THE CYCLIC TESTINGOF DUCTED SYSTEMS
REQUIRED BY APPENDIX A, SECTIONS A4.1 and A4.2
C1 For the
purpose
of uniformity
in
the
cyclic
test
requirements of Appendix A, the following test apparatus and
conditions shallbe met:
C1.1 The test apparatus is a physical arrangement of
dampers, damper boxes.mixers, thermopile and ducts all
properly sealed and insulated. See Figures C1 through
C4 for typicaltestapparatus.Notearrangementand
size(s) of the components may be altered to meet the
physical requirementsof the unit tobe tested.
'ZT'
34
I/
1 jlI
'
,I
' +
CL
I
36
I
I
U
v)
I'
VI
a
c
VI
L5
9
W
t
a
W
I'
38
I'
&
D1.l
Purpose.
This appendix
shows
sample
calculationsfordeterminingIntegratedPart
Load Values (IPLV).
D1.l.l
Dl3
D3.1.1
Dara
&
Sample
Assume
equipment
four
has
capacity steps as follows:
Scope
100% (full load)
This appendix
for
isequipment
covered by this standard.
D1.2.1
D3.1.2
D3.13
per 5.2.
Obtain EERateachcapacitystep
D3.1.4 CalculateIPLVusing
equation with:
n=4
PLF, = 1.0
PLF, = 0.9
PLF, = 0.4
PLF, = 0.1
the general
EER, = 8.9
[2.6]
EER, = 7.7 [2.3]
EER, = 7.1[2.1]
EER, = 5.0 [ 1-51
Superscript 1 =
PLV =
Part-LoadFactor
determined
from
Figure I
Total number
capacity steps
+ (0.4
- 0.1)
100% capacity
and
Specific capacityand
EER at part-load steps
per 5.2.
+-)7.7
- 0.9) (-8.9
+ (0.9
of
(1.0
(0.1 x 5.0)
(0.1 x 83)
+
7.1
(03 L 6.0)
5.0
(0.5 x 7.4)
0.5
39
sL!h&
PLV = (1.0
+ (0.9
+ (0.1
- 0.9) (2.6 2+ 23 1
0.4) (2'3
2'1)
+ (0.4
- 0.1)
(2'1
x 5.0)
0245
1.1 + 0.54
1.5
IPLV = 2.0
20
80
40
100
= -0.12773Y 17 x IO -''
= -0.27648713 x 1 0 - 3
= 0.50672449 x
= -0.259 66636 x
= 0.69875354 X
= -0.76859712 x
= 0.28918272 x
IO-'
IO-'
lo-"
lo-"
IO-"'
41
capacity
step
tFull Load
100%
2
3
PLF'
cap.
75%
50%
1.o
0.9
0.4
Mrs. Part
LoadEER
8.9'
7.7
7.1
0.1 25%
5.0
090
F'LF Diff.
Avg. Part
LoadEER
8.3
7.4
6.0
5.0'
Weighted
Avg.
Diff. =
(1.0 - 0.9)d.l
8.3 x 0.1
(0.9 - 0.4)=0.5
7.4 x 0.5
(0.4 - 0.1)=0.3
6.0 x 0.3
--
(0.1 - O.O)=o. 1
5.0' x 0.1
-__-_
0.0
-1
0.83
3.70
1.80
LIZ!
Single number
JPLV
6.83'
*Rounded to6.8
NOTES:
'For the range between
0% capacity and the last capacity step, use EER of the last capacity step forthe average W .
'The 100% capacity andEER are to be determined at the p
a
r
t
o
la
drating conditions;
'Pan-load factor from FigureDl.
Capacity
step
2
3
4
%Fullhad
PLF'
cap.
100%
75%
50%
25%
0%
1 .o
0.9
0.4
0.1
0.0
2.6
PLF Diff.
2.45
2.2
1.8
1.5
2.3
2.1
1.5
_____
Avg.
0.245
(0.9 - 0.4kO.5
2.2 x 0.5
1.1
(0.4 - 0.1)=0.3
1.8 x 0.3
0.54
(0.1 - O.O)=O. 1
1.5' x 0.1
Q,Ll
- 0.9)dl.l
NOTES:
'For the range between0% capacity and the last capacity step. use EER of the last capacity step forthe average EER.
'The 100%capacity and EER arc tobe determined at the part-load mmg condmonr.
'Pan-load factor from FigureDl.
42
Weighted
2.45 x 0.1
( 1 .O
2.0