2CDC241010F0011
Description
MS116-16
Manual motor starters (MMS) are protection devices for the main circuit. They combine motor control and
protection in a single device. MMS are used mainly to switch motors manually ON/OFF and protect them
and the installation fuse less against short-circuit, overload and phase failures. Fuse less protection with
a manual motor starter saves costs, space and ensures a quick reaction under short-circuit condition, by
switching off the motor within milliseconds.
MS116 is a compact and economic range for motor protection up to 7.5 kW (400 V) / 32 A in width of 45mm.
Further features are the build-in disconnect function, temperature compensation, trip-free mechanism and
a rotary handle with a clear switch position indication. The manual motor starter is suitable for three- and
single-phase applications. Auxiliary contacts, signalling contacts, undervoltage releases, shunt trips, threephase bus bars, power in-feed blocks and locking devices for protection against unauthorized changes
are available as accessory.
2CDC241001F0011
Ordering details
2CDC241013F0011
MS116-25
2CDC241012F0011
MS116-0.16-HKF1-11
MS116-32-HKF1-11
Rated
operational
power
400 V
AC-3
kW
0.03
0.06
0.09
0.12
0.25
0.55
0.75
1.5
2.2
4.0
5.5
7.5
9.0
12.5
15.5
0.03
0.06
0.09
0.12
0.25
0.55
0.75
1.5
2.2
4.0
5.5
7.5
9.0
12.5
15.5
Rated
Short-circuit
operational breaking
current
capacity ICS at
400 V AC
A
0.10 ... 0.16
0.16 ... 0.25
0.25 ... 0.40
0.40 ... 0.63
0.63 ... 1.00
1.00 ... 1.60
1.60 ... 2.50
2.50 ... 4.00
4.00 ... 6.30
6.30 ... 10.0
8.00 ... 12.0
10.0 ... 16.0
16.0 ... 20.0
20.0 ... 25.0
25.0 ... 32.0
0.10 ... 0.16
0.16 ... 0.25
0.25 ... 0.40
0.40 ... 0.63
0.63 ... 1.00
1.00 ... 1.60
1.60 ... 2.50
2.50 ... 4.00
4.00 ... 6.30
6.30 ... 10.0
8.00 ... 12.0
10.0 ... 16.0
16.0 ... 20.0
20.0 ... 25.0
25.0 ... 32.0
A
1.56
2.44
3.90
6.14
11.50
18.40
28.75
50.00
78.75
150
180
240
300
375
480
1.56
2.44
3.90
6.14
11.50
18.40
28.75
50.00
78.75
150
180
240
300
375
480
Main dimensions
kA
50
50
50
50
50
50
50
50
50
50
25
16
10
10
10
50
50
50
50
50
50
50
50
50
50
25
16
10
10
10
Type
Order code
Weight
(1 pce)
MS116-0.16
MS116-0.25
MS116-0.4
MS116-0.63
MS116-1.0
MS116-1.6
MS116-2.5
MS116-4.0
MS116-6.3
MS116-10
MS116-12
MS116-16
MS116-20
MS116-25
MS116-32
MS116-0.16-HKF1-11
MS116-0.25-HKF1-11
MS116-0.4-HKF1-11
MS116-0.63-HKF1-11
MS116-1.0-HKF1-11
MS116-1.6-HKF1-11
MS116-2.5-HKF1-11
MS116-4.0-HKF1-11
MS116-6.3-HKF1-11
MS116-10.0-HKF1-11
MS116-12.0-HKF1-11
MS116-16.0-HKF1-11
MS116-20-HKF1-11
MS116-25-HKF1-11
MS116-32-HKF1-11
1SAM250000R1001
1SAM250000R1002
1SAM250000R1003
1SAM250000R1004
1SAM250000R1005
1SAM250000R1006
1SAM250000R1007
1SAM250000R1008
1SAM250000R1009
1SAM250000R1010
1SAM250000R1012
1SAM250000R1011
1SAM250000R1013
1SAM250000R1014
1SAM250000R1015
1SAM250005R1001
1SAM250005R1002
1SAM250005R1003
1SAM250005R1004
1SAM250005R1005
1SAM250005R1006
1SAM250005R1007
1SAM250005R1008
1SAM250005R1009
1SAM250005R1010
1SAM250005R1012
1SAM250005R1011
1SAM250005R1013
1SAM250005R1014
1SAM250005R1015
kg
0.225
0.225
0.225
0.225
0.225
0.265
0.265
0.265
0.265
0.265
0.265
0.265
0.310
0.310
0.310
0.240
0.240
0.240
0.240
0.240
0.280
0.280
0.280
0.280
0.280
0.280
0.280
0.326
0.326
0.326
mm, inches
79,9 / 3,15"
69,8 / 2,75"
80,1 / 3,15"
2CDC242001F0011
14 / 0,55"
45 / 1,77"
45 / 1,77"
57,8 / 2,3"
35 / 1,38"
27,5 / 1,1"
1,7 / 0,07"
45 / 1,77"
97,8 / 3,85"
14 / 0,55"
2CDC131039C0201_1s10
57,8 / 2,3"
35 / 1,38"
14 / 0,55"
45 / 1,77"
2/2 | ABB
43,3 / 1,7"
43,5 / 1,71"
2CDC242002F0010
14 / 0,55"
75 / 2,95"
27,5 / 1,1"
1,7 / 0,07"
90 / 3,54"
5,5 / 0,22"
5,5 / 0,22"
1,5 / 0,06"
70 / 2,76"
75 / 2,95"
1,5 / 0,06"
MS116
IEC/EN 609472, IEC/EN 60947-4-1, IEC/EN 60947-1
690 V AC
50/60 Hz
10A
3
100 %
6 kV
690 V AC
See ordering details
See ordering details
See table "Short-circuit breaking capacity and back-up fuses"
See table "Short-circuit breaking capacity and back-up fuses"
lCU
ICC
Note: Maximum rated current of the back-up fuses if ICC > ICS
Type
MS116-0.16
MS116-0.25
MS116-0.4
MS116-0.63
MS116-1.0
MS116-1.6
MS116-2.5
MS116-4.0
MS116-6.3
MS116-10
MS116-12
MS116-16
MS116-20
MS116-25
MS116-32
230 V AC
ICU
ICS
kA
kA
gG, aM
A
400 V AC
ICS
ICU
kA
kA
gG, aM
A
440 V AC
ICS
ICU
kA
kA
gG, aM
A
500 V AC
ICS
ICU
kA
kA
gG, aM
A
690 V AC
ICS
ICU
kA
kA
gG, aM
A
25
16
10
10
10
25
16
15
15
10
80
80
-
25
16
10
10
10
25
16
15
15
10
80
80
-
10
6
6
6
6
6
3
3
3
10
6
6
6
6
6
6
6
6
25
25
63
63
63
63
-
10
6
6
6
6
4
3
3
3
10
6
6
6
6
4
4
4
4
25
25
63
63
63
63
-
5
2
2
2
2
2
2
2
2
5
2
2
2
2
2
2
2
2
25
25
40
50
50
63
-
2CDC131039C0201_2s10
MS116-10: No need for back-up fuse in networks with a prospective current of up to 50 kA at 400 V.
MS116-16: No need for back-up fuse in networks with a prospective current of up to 16 kA at 400 V.
With an approbiate 80 A type gG fuse the device can be used in a network with a prospective current of up to 100 kA.
MS116-32: No need for back-up fuse in networks with a prospective current of up to 15 kA at 400 V.
ABB | 2/3
Horse power
Type
MS116-0.16
MS116-0.25
MS116-0.4
MS116-0.63
MS116-1.0
MS116-1.6
MS116-2.5
MS116-4.0
MS116-6.3
MS116-10
MS116-12
MS116-16
MS116-20
MS116-25
MS116-32
110-120 V AC
hp
FLA
LRA
220-240 V AC
hp
FLA
LRA
1/2
1
1-1/2
2
3
3
5
0.96
1.5
2.4
3.78
6.0
9.6
15.0
16.0
40
60
80
100
128
128
184
1/2
1
1-1/2
3
3
5
5
7-1/2
10
0.96
1.5
2.4
3.78
6.0
9.6
20
30
40
64
64
92
92
127
162
0.16
0.25
0.4
0.63
1.0
1.6
2.5
4.0
4.4
8.4
12
13.6
19.2
19.2
30.4
0.16
0.25
0.4
0.63
1.0
1.6
2.2
4.2
6.4
9.6
9.6
15.2
15.2
22
28
440-480 V AC
hp
FLA
3/4
1
2
3
5
7-1/2
10
10
15
20
0.16
0.25
0.4
0.63
1.0
1.6
2.1
3.4
4.8
7.6
11
14
14
21
27
LRA
500-600 V AC
hp
FLA
LRA
0.96
1.5
2.4
3.78
6.0
12.5
15
25
32
46
63.5
81
81
116
145
1/2
3/4
1-1/2
3
5
7-1/2
10
10
15
20
25
0.96
1.5
2.4
3.78
8
10
16
25.6
36.8
50.8
64.8
64.8
93
116
146
0.16
0.25
0.4
0.63
0.9
1.3
2.4
3.9
6.1
9
11
11
17
22
27
MS116-0.16
MS116-0.25
MS116-0.4
MS116-0.63
MS116-1.0
MS116-1.6
MS116-2.5
MS116-4.0
MS116-6.3
MS116-10
MS116-12
MS116-16
MS116-20
MS116-25
MS116-32
1)
600 V
kA
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
600 V
kA
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
Suitable as motor disconnect only when provided with padlock SA1 or SA3...
2CDC131039C0201_3s10
Type
Standards
Maximum operational voltage
Manual motor controller ratings
Trip rating
Motor ratings
Horse power
Full load amps (FLA)
Locked rotor amps (LRA)
2/4 | ABB
MS116
3
Yes
Open - compensated without derating
Open
Enclosed (IB132)
Storage
Ambient air temperature compensation
Maximum operating altitude permissible
Resistance to shock acc. to IEC 60068-2-27
Resistance to vibrations acc. to IEC 60068-2-6
Mounting position
Mounting
Group mounting
Minimum distance to other
units same type
Minimum distance to
electrical conductive board
Degree of protection
Horizontal
Vertical
Horizontal, up to 400 V
Horizontal, up to 690 V
Vertical
Enclosure / terminals
Solid
Flexible
Stranded acc. to UL/CSA
Flexible acc. to UL/CSA
Stripping length
Tightening torques
Connection screw
1 or 2 x
1 or 2 x
1 or 2 x
1 or 2 x
MS116 16 A
MS116 20 A
1 ... 4 mm
0.75 ... 2.5 mm
AWG 16-12
AWG 16-12
9 mm
0.8 ... 1.2 Nm / 10 12 Ib.in
M3.5 (Pozidriv 2 / 5.5 mm)
2.5 ... 6 mm
1 ... 6 mm
AWG 12-8
AWG 12-8
10 mm
2.0 Nm / 18 Ib.in
M4 (Pozidriv 2 / 6.5 mm)
2CDC131039C0201_4s10
Connecting characteristics
Main circuit
Type
Connecting capacity
ABB | 2/5