Swirl diffusers
Type FD
recommended room heights from 2.60 . . . 4.00 m

TROX GmbH
Heinrich-Trox-Platz
D-47504 Neukirchen-Vluyn

Telephone +49 / 28 45 / 2 02-0


Telefax
+49 / 28 45 / 2 02-2 65
e-mail trox@trox.de
www.troxtechnik.com

Contents Description
Description
Construction Dimensions
Materials
Installation Assembly

2
3
4
4

FD-Q Construction

FD-R Construction

The diffuser face of the type FD consists of fixed, radially


arranged air control blades. The supply air design has
specially arranged internal air guidance elements which are
not required on the extract version.
Due to the rotary swirling motion of the air discharge,
induction of room air occurs very quickly, resulting in rapid
decay of supply air velocity and temperature differential. Air
change rates of 30 per hour can be achieved with supply air
temperature differentials of +10K to 10K.
To stabilise horizontal discharge, all sizes must be mounted
flush with a ceiling.
The minimum mounting height between floor and diffuser
face is 2.60 m.

Flow Visualisation

Nomenclature
Acoustic Data
Aerodynamic Data
Order Details

5
6
9
13

Construction Dimensions
If a circular diffuser face is ordered, the plenum box with side
entry spigot has a 35 mm extension piece fitted to the plenum.

Construction
Type FD swirl diffusers are available in 5 sizes.
Depending on the architectural requirements, the face plate
can be circular or square. The fixed air control blades on the
diffuser face are arranged radially.
The diffuser face can be attached or removed via a centre
fix screw into the plenum box. The screw head is covered
with a decorative cap. The plenum box can be supplied with
either top or side entry spigots and on request, with spigot
lip seals and volume control damper.

For simple adjustment of the volume flow, on request the


plenum box can be provided with a test connection for
measurement of a reference pressure and a volume control
damper operated by sheathed cables. The characteristic
curve of pressure reading versus volume flow rate for each
size of plenum box is supplied.
Note: If a larger size side entry plenum is fitted to a diffuser
face, this should be considered in relation to performance
(lower noise levels and pressure drop).
AK code, diffuser face 1)
Square
Circular

Size

H2

P

300

280

158

250

298

300

250

290

278

AK001

AK013

400

364

198

350

398

400

295

372

362

AK002

AK014

500

462

198

450

498

500

295

476

460

AK003

AK015

600

559

248

538

598

600

345

567

557

AK004

AK016

625

559

248

538

623

623

345

567

557

AK004

AK016

1) Valid only for FD-...-H!

FD-R-...-V
FD-R-...-H

fixing screw
for diffuser face
FD-Q-...-V
FD-Q-...-H

Plenum Boxes
K

35

H2

D

H2

D

K

P


FD-Q-...-H

FD-R-...-H

FD-...-V

Materials Installation Assembly


Materials

Assembly

The diffuser face is made of galvanised sheet steel. The


surface is pre-treated and powder coated white (RAL 9010)

The plenum box is suspended by wires or slotted strips


using the drilled holes in the plenum return edge or hanging
brackets, when provided. For the side entry plenum box,
a self adhesive seal, supplied loose, must be fitted by the
client. The diffuser face is fitted to the plenum box by means
of centre fix screw locating in cross channel in the plenum
box.

The plenum boxes are galvanised sheet steel, the lip seal of
rubber.

Installation
All sizes are suitable for flush mounting into a ceiling.
If the diffuser is installed below a closed ceiling (i. e. freely
suspended) a stable discharge can be achieved if a peripheral
collar  50 mm is provided available on request.

Measurement of Reference Pressures


For simple adjustment of the volume flow, on request the
plenum box can be provided with a test connection for
measurement of a reference pressure and a volume control
damper operated by sheathed cables. The characteristic
curve of pressure reading versus volume flow rate for each
size of plenum box is supplied.

Installation flush to ceiling

Freely suspended

Installation with cut out in ceiling

Installation
using hangers

Surface mounting on ceiling

Hangers by others

Self adhesive seal,


fitted by others

Fixing of diffuser face


using centre screw

 Test nipple

 Inclined manometer

 Plastic tube

 Code

 White sheathed cable damper open

 Diffuser face

 Green sheathed cable damper closed

Plenum box

Nomenclature

V
in l/s: Volume flow per diffuser
V
in m3/h: Volume flow per diffuser
A, B in m: Spacing between two diffusers
X
in m: Distance between diffuser centre and wall
H1
in m: Distance between ceiling and occupied zone
v- H1 in m/s: Time average air velocity between two
diffusers at distance from ceiling H 1
L
in m: (Horizontal + vertical) distance (X + H 1)
discharge to the wall
v- L
in m/s: Time average air velocity at the wall
 tZ
in K: Temperature difference between supply air and
room air
 tL
in K: Difference between core and room air temperature
at distance L = A/2 + H 1
or L = B/2 + H 1
or L = X + H 1
A eff in m2: Effective outlet area
 p t in Pa: Total pressure drop (supply air)
LWA in dB(A): A-weighted sound power level
LWNC
: NC rating of sound power level
LWNR
: LWNR = LWNC + 2
L pA, L pNC : A-weighting and NC rating respectively of room
sound pressure level L pA  L WA 8 dB
L pNC  L WNC 8 dB

in : Damper angle

Nomenclature

Quick Selection (Supply air)


Vmin

Vmax
l/s

m /h

l/s

m3/h

LWA max
dB(A)

LW NC max
NC

LWA min
dB(A)

LW NC min
NC

Aeff
m2

300

055

200

40

145

40

34

 31

 25

0.00884

400

110

400

50

180

40

34

25

 20

0.0180

500

145

520

60

215

40

34

 20

 20

0.0251

600
625

165

600

80

290

40

34

 20

 20

0.0295

Size

Octave band spectrum on request!

Acoustic Data FD-...-V


Supply Air

Correction to diagram 1: Volume control damper setting


Damper
angle 

45

90

Damper
angle 

p t

x 1.0

x 1.2

x 2.5

L WA

L WNC

45

90

p t

x 1.0

x 1.5

x 4.0

+2

L WA

+3

+7

+2

L WNC

+3

+7

Correction to diagram 2: Volume control damper setting


Damper
angle 

Correction to diagram 4: Volume control damper setting

45

90

Damper
angle 

p t

x 1.0

x 1.1

x 2.1

L WA

+1

L WNC

+1

Sound power level and pressure drop


Size 300

Sound power level and pressure drop


Size 400

45

90

p t

x 1.0

x 1.1

x 2.2

+2

L WA

+1

+4

+2

L WNC

+1

+4

Sound power level and pressure drop


Size 500

Sound power level and pressure drop


Size 600 and 625

Pressure drop  p t in Pa

Pressure drop  p t in Pa

Pressure drop  p t in Pa
Pressure drop  p t in Pa

Correction to diagram 3: Volume control damper setting

Acoustic Data FD-...-H


Supply Air

Correction to diagram 5: Volume control damper setting


Damper
angle 

Correction to diagram 7: Volume control damper setting

45

90

Damper
angle 

p t

x 1.0

x 1.1

x 2.3

L WA

+0

L WNC

+0

45

90

p t

x 1.0

x 1.4

x 4.3

+2

L WA

+1

+8

+2

L WNC

+1

+8

Correction to diagram 6: Volume control damper setting


Damper
angle 

Correction to diagram 8: Volume control damper setting

45

90

Damper
angle 

p t

x 1.0

x 1.3

x 2.7

L WA

+1

L WNC

+1

Sound power level and pressure drop


Size 400

45

90

p t

x 1.0

x 1.4

x 3.5

+3

L WA

+1

+4

+3

L WNC

+1

+4

Sound power level and pressure drop


Size 500

Sound power level and pressure drop


Size 600 and 625

Pressure drop  p t in Pa

Sound power level and pressure drop


Size 300

Pressure drop  p t in Pa

150

45

100

Pressure drop  p t in Pa

50
45

40
35

50

35
in
dB
(A)

20

30

20

WA

25

30

30

40

40

15

25

15

WN

20

10

Pressure drop  p t in Pa

70

7
30

40

m 3/h 150

50
200

70

100
300

l/s 150

400

500

300

200
900

Acoustic Data
Extract Air

Correction to diagram 9 and 10: Volume control damper setting


Size
300

400

500

600/625

Sound power level and pressure drop FD - . . . - V

10

Damper angle

45

90

x 1.0

x 1.1

x 2.0

L WA

+ 3.0

L WNC
 pt

+ 3.0

x 1.0

x 1.0

x 1.9

L WA

+ 4.0

L WNC
 pt

+ 4.0

x 1.0

x 1.1

x 2.5

L WA

+ 7.0

L WNC
 pt

+ 7.0

x 1.0

x 1.1

x 2.2

L WA

+ 1.0

+ 4.0

L WNC

+ 1.0

+ 4.0

Sound power level and pressure drop FD- . . . - H


Size

Pressure drop  p t in Pa

Pressure drop  p t in Pa

Size

 pt

Aerodynamic Data FD 300

Correction!
For an installation below the ceiling line, the values
v-H1, v-L and  t L /  t Z must be multiplied by a factor of 0.71!

Diffuser arrangement: single or more than one row


if B  4.00 m

H 1 = 0,9

1,2

1,6 2 m

A=1

30
0,
25
0,
20

0,04

0,03

80

(1

15

45

v- L in m/s

90

(2

0,

)
3 /h
(m 60)

(3

(2

(14

0,3

0,02

0,
10

5
0,2
0,2

0,8

1,5

0,1

5 6m

5
0,8

1,5

Spacing A

14

1,6 2 m

5 6m

0
0,
5
40
0,
30
0,
0,

15

0,

0,
2

10

0,

25

0,

15

v- H1 in m/s

0,

)
3 /h
(m 60)
(3
0)
l/s
(29
00
=1 0
V
8

25

0,01
5 6m

5)
(21
0)
(18 )
5
(14

40

0,

1,6 2 m

50

20

1,2

60

V = l/s (m
3
80
/
(29 h)
70 0)
(25
0)
60
(21
5)
50
(18
0)
40
(14
5)

0,

Square Array of Diffusers

H 1 = 0,9

30

1,2

Distance L

Diffuser arrangement: more than one row


if B = 3.00 m

H 1 = 0,9

v- H1 in m/s

0,05

l/s 0
10

80

0,4

5)

12

0,08

=
V

0
0,5

(1

(18

0
60

15

0,10

40

0,

3m

0,6

(21

0)

40

0,06

0,8

5)

50

1,5

 tL
 tZ

V = l/s
10 (m 3
0 ( /h)
36
0)
80
(29
0)

60

Temperature Quotient

50

v- H1 in m/s

13

Temperature quotient  t L /  t Z

11

0,8

1,5

Spacing A

5 6m

0,8

1,5

Spacing A or B

Aerodynamic Data FD 400


Example
Data given:
2 off type FD-Q-H-Z/400
Volume flow per diffuser
V = 70 l/s
Supply air temperature difference
 tZ = 8K
Spacing between two diffusers
A = 1.20 m
Distance between diffuser centre and wall
X = 1.50 m
Distance between ceiling and occupied zone
H 1 = 1.20 m

Diagram 17:
L = A/2 + H 1 = 0.6 + 1.20 = 1.80 m
 t L /  t Z = 0.08
 t L = 8 0.08 = 0.64 K
L = X + H 1 = 1.50 + 1.20 = 2.70 m
 t L /  t Z = 0.053
 t L = 8 0.053 = 0.4 K
v- L  0.22 m/s

Temperature Quotient

between two diffusers

at the wall

Diagram 6:
Sound power level and pressure drop
L WA = 26 dB(A) (L WNC = 21 NC)
 p t = 16 Pa
Diffuser arrangement:
single or more than one row

v- H1 = 0.10 m/s

15

Diffuser arrangement: single or more than one row


if B  4.00 m

H 1 = 0,9

1,2

Correction!
For an installation below the ceiling line, the values
v- H1, v- L and  t L /  t Z must be multiplied by a factor of 0.71!

17

1,6 2 m

Temperature Quotient
A=1

1,5

3m

0,20
 tL
 tZ

0,
25
0,
20
0,
15
0,
0,
10

v- L in m/s
4

0,1

5 6m

5
0,8

1,5

18

5 6m

0
0,
5
40
0,
0,

15

0,

0,
2

10

0,

25

0,

30

v- H1 in m/s

0)

0,

0,
0,

5)

(18

)
3 /h
( m 50)
(4
0)
(36 )
0
(29

0
10

(21

l/s 5
2

30

0,02
5 6m

=1
V

25

1,6 2 m

5)
(21 )
0
(18

50

1,2

80

60

20

Square Array of Diffusers

H 1 = 0,9
V = l/s
12 (m 3
5 ( /h)
45
0)
10
0(
36
0)
80
(29
0)

15

Distance L

1,6 2 m

0,

0,04

60
50

v- H1 in m/s

)
3 /h
(m 50)
(4

90

1,2

(2

0,03

Diffuser arrangement: more than one row


if B = 3.00 m

H 1 = 0,9

0,05

5
0,2

Spacing A

16

60

(3

1,5

0,06

)
15 )
80

0,08

(1

0,3

(2

0,2

0,8

10

0
0,5
0,4

0,10

l/s 5
12

,60

80

60
50

v- H1 in m/s

0,12

0,8

=
V

30

V = l/s
12 (m 3
5 ( /h)
45
0)
10
0(
36
0)
80
(29
70 0)
(25
0)
60
(21
5)
50
(18
0)

0,16

0,8

1,5

Spacing A

10

5 6m

0,8

1,5

Spacing A or B

Temperature quotient  t L /  t Z

Diagram 15:

Aerodynamic Data FD 500

Correction!
For an installation below the ceiling line, the values
v- H1, v- L and  t L /  t Z must be multiplied by a factor of 0.71!

Diffuser arrangement: single or more than one row


if B  4.00 m

H 1 = 0,9

1,2

1,6 2 m

0
0

0,06

50

(4

(3

60

0,05

90

(2

0,08

(5

0,4

0
0,5

0,
10

5)

15

0,3

(21

0,04

5
0,2
0,03

0,2

0,8

1,5

0,1

5 6m

5
0,8

1,5

Spacing A

22

1,6 2 m

5 6m

0
0,
0,

15

0,

0,
2

10

0,

25

0,

40

0,
5

15

30

(2

0,

30
25

5)
(21

20

l/s
15 (m 3
0(
54 /h)
0)
12
5
(4
50
)
10
0
(3
60
)
80
(2
90
)
60

15

0,02
5 6m

)
3 /h
(m 40)
(5 0)
l/s
45
(
50
0)
1
(36
V = 125
0)
0
(29
10

0,

1,6 2 m

60

0,

1,2

80

0,

Square Array of Diffusers

H 1 = 0,9
V

v- H1 in m/s

1,2

Distance L

Diffuser arrangement: more than one row


if B = 3.00 m

H 1 = 0,9

v- H1 in m/s

0,10

)
3 /h
( m 40)

0,6

v- L in m/s

30
0,

0,12

0,8

(2

60

20

0,16

l/s 0
15

25

0,20

12

0,

3m

=
V

20

80

0,

1,5

10

15

A=1

 tL
 tZ

V = l/s
15 (m 3
/
0(
54 h)
0)
12
5(
45
0)
10
0(
36
0)
80
(29
0)

0,

Temperature Quotient

60

v- H1 in m/s

21

Temperature quotient  t L /  t Z

19

0,8

1,5

Spacing A

5 6m

0,8

1,5

Spacing A or B

11

Aerodynamic Data FD 600 and FD 625


Example
Data given:
4 off type FD-Q-Z-H/600
Volume flow per diffuser
Spacing between two diffusers
Distance between ceiling
and occupied zone

V = 100 l/s
A = B = 2.00 m
H 1 = 1.60 m

Required: air velocity in occupied zone


Diagram 26:
Square array of diffusers
v- H1 = 0.22 m/s

Correction!
For an installation below the ceiling line, the values
v- H1, v- L and  t L /  t Z must be multiplied by a factor of 0.71!

23

Diffuser arrangement: single or more than one row


if B  4.00 m

H 1 = 0,9

1,2

25

1,6 2 m

Temperature Quotient
A=1

1,5

3m

0,20

V = l/s
20 (m 3/
0(
72 h)
0)

 tL
 tZ

0,16

30
25
0,
20
0,

0)

0,3

0,04

0,
10

0,03

0,8

1,5

0,1

5 6m

5
0,8

1,5

Spacing A

26

5 6m

0
40

0,
5

15

0,

15

0,

0,

10

20

0,

25

0,

0,

(2
90
)

30

20

1,6 2 m

0,

25

0,

1,2

80

0,

l/s
15 (m 3
0(
54 /h)
0)
12
5
(4
50
)
10
0(
36
0)
80

0,

0,02
5 6m

0
10

30

)
3 /h
( m 30)
(6 0)
l/s 5
(54 0)
7
1 0
(45
V = 15
0)
5
(36 )
12
0
(29

Square Array of Diffusers

H 1 = 0,9

1,6 2 m

v- H1 in m/s

1,2

Distance L

Diffuser arrangement: more than one row


if B = 3.00 m

H 1 = 0,9

v- H1 in m/s

0,05

5
0,2
0,2

24

0,06

90

(29

0,4

0,08

(2

15

0)

36

80

0
0,5

80

0(

0,

0,6

0)

0,10

12

45

10

v- L in m/s

0,

0)

5(

)
3 /h
( m 0)
3
(6 0)
4
l/s 5
(5 0)
5
17
(4 0)
0
6
(3
15 5
)

54

12

10

v- H1 in m/s

0,8

=
V

0(

0,8

1,5

Spacing A

12

5 6m

0,8

1,5

Spacing A or B

Temperature quotient  t L /  t Z

0,12
15

Order Details

Order Code

These codes do not need to be completed for standard products


FD - Q - Z - V - M - L

Square
Circular

Q
R

IE
OEP

Supply
Extract

Z
A

IE
OEP

Top entry plenum


Side entry plenum

V
H

IE
OEP

Volume control damper


with single blade

400
300
400
500
600
625
Size

Volume control damper with


MN
cable and measuring nipple

RAL 9016

Not used
State colour

L Spigot with lip seal

P1

IEE
EEE
EO
EEE
EEE
P

TE
EE
EE
EE
EZE
EE
EE
EE
U

0 Standard finished
powder coated
to RAL 9010 (GE 50 %) 1)
P1 Powder coated
to RAL 9006 (GE 30 %) 1)
other colours
to RAL . . . (GE 70 %) 1)

Specification Text
Fixed swirl diffusers in square and circular construction for
swirling, horizontal air discharge with high induction, for air
change rates up to 30 per hour, comprising the diffuser face
with radially arranged air control blades, top or side entry
spigot, on request with spigot lip seal and/or volume control
damper. On request, to measure the reference pressure, the
spigot is fitted with a cable-adjusted volume control damper
and measuring nipple.
The plenum with circular side entry spigot can be fitted to
various TROX diffusers; however, variation in performance must
be taken into account.

Design changes reserved All rights reserved TROX GmbH (8/2008)

1) GE = gloss level

Materials:
Diffuser face is in galvanised sheet steel. The surfaces are
pre-treated and powder coated white (RAL 9010). The plenum
box is also of galvanised sheet steel, the lip seal of black
rubber.

Order Example
Make: TROX
Type: FD - Q - Z - V - M / 400 / P1 / RAL 9016