Sei sulla pagina 1di 143

Scope of work for CMMS and CCMS

CONTENTS
1.0

Purpose

2.0

Scope

2.1

Scope of Work for Computerized Maintenance


Management System (CMMS)

2.2

Scope of Work for Completion Certification


Management System (CCMS

3.0

Codes and Standard

APPENDIX - I

CMMS Asset and Activity Registration Procedure

APPENDIX-I

APPENDIX - II

Selection of Safety Critical Elements (SCE) and


Development of Performance Stds (PS) & PS
Assurance Tasks.

APPENDIX-II

APPENDIX - III

Engineering and Operations Procedure for


Z6 Notification

APPENDIX-III

APPENDIX - IV

Criticality Assessment Procedure

APPENDIX-IV

APPENDIX - V

E-SPIR 2000 Procedure & Project Documents


Requirement

APPENDIX-V

Doc. No: ZAU-84-104810 -VA-6793-20001-0000

PAGE 2 of 5

REVISION: 02
Date: 03.06.2013

Scope of work for CMMS and CCMS

1.0

PURPOSE
The purpose of this document is to provide the clear scope of work for Computerized
Maintenance Management System (CMMS) and Completion Certification Management
System (CCMS) in order to proper loading to PDO SAP system for the Zauliyah Gas Plant
project.

2.0

SCOPE

2.1

Scope of Work for Computerized Maintenance Management System (CMMS)


The scope of work for CMMS consists of basically three activities i.e. SAP PM, CIMS and ESPIR. The detailed scope is given below.
Sl.
Description
No.
01. SAP PM Pack 1 - Asset Resister:
The scope for preparing asset data is collecting, verifying and
formatting the asset data by referring to respective design drawings,
various manuals, other relevant document sources.
- RBI workshop
- RCM workshop
- IPF workshop
- SCE Identification Study ( After conducting RBI/RCM/IPF
and Design HSE case)
The Asset Resister work should be carried out as per PDO document
No. PR-1344 Rev 05 (Dec-2009). For Ref. Appendix I for this
document.
02. SAP PM Pack 2 - SCE Identification:
Identification and Data preparation for Safety Critical Elements
(SCE) for SAP Upload as per EP-2009-9009 & guidelines. SAP PM
template. Ref. Appendix II
- Function locations level 1-5 in SAP PM (using AFC drawings)
- Equipment data
- FLOCs classification
- Equipment classification
- SCE / performance standards
- 25% CMMS review workshop (In presence of Project team +
UEPI 31)
- MCPs in SAP (based on RCM Study)
- Task list in SAP PM (based on RCM Study)
- Maintenance plans/scheduling
- 50% CMMS review workshop (In presence of PDO Operation
+Project +UEPI31+CDFP)

Doc. No: ZAU-84-104810 -VA-6793-20001-0000

PAGE 3 of 5

Remarks

REVISION: 02
Date: 03.06.2013

Scope of work for CMMS and CCMS

Z6 Creation. Refer PDO DOC. No. PR-1528, Rev 03 (Sep,


2009). For details refer Appendix III
- Z6 Review and Approval
- Asset Registration
- 75% CMMS review workshop (In Presence of PDO Operation
+Project +UEPI31)
- 100% CMMS Review.
03. SAP PM Pack 3 -RCM & RBI Study:
PR 1248
Appropriate pro-active maintenance (PM) tasks are selected on the
basis of a criticality assessment as per doc no PR-1248 Version 02
July2000. For detail ref. Appendix IV
04. SAP PM Pack 4 - Asset Maintenance Plan Deliverable:
Further, for every asset maintenance plan, data to be prepared based
on the output of RCM&RBI study.
05. Corrosion inspection Management System (CIMS):
In addition to PDO SAP system registration (i.e. Plant Maintenance
Planning and Inspection scheduling), CIMS master data for all static
& Piping equipment need to be prepared for CORROSION
MONITORING and CORROSION ANLYSIS requirements.
-

Provide CIMS Template


CIMS Data Population (based on RBI Study)
CIMS Data Review and Approval
75% CMMS Review Workshop (In-presence of PDO
Operation + Project + UEOC5 + Purchaser)
- Carry out Baseline Survey
- Log Baseline Actual Result in CIMS
- Switch Gear Operating Procedures
- 100% CMMS review workshop (before PSUA)
06. Electronic Spare Parts List and Interchangeability Record (E-SPIR):
The spares data will be prepared as per SPIR form for ESPIR input.
The data will be collected and prepared from related documents
from EPC / Vendors. Spare parts list will be prepared as per PDO
procedure PR-1443 Rev-2 June-09. For Details ref. Appendix V.
- Spare Parts.
- E-SPIR data population
- E-SPIR data review
- E-SPIR data review / approval
- SAP spares coding
- Progress review - can be combined with 50% CMMS review
- Bill of Materials (BOM) link to equipments. After function
location level 1-5 in SAP PM using AFC Drawings
- Progress review - can be combined with 75% CMMS review
Doc. No: ZAU-84-104810 -VA-6793-20001-0000

PAGE 4 of 5

REVISION: 02
Date: 03.06.2013

Scope of work for CMMS and CCMS

Vender needs to co-ordinate with the individual vendors and the purchaser engineering team
directly to get the required data.
2.2

Scope of Work for Completion Certification Management System (CCMS)


The detailed scope is given below.
Sl.
Description
No.
01. Identification of Area and Sub-area:
Vender has to prepare the Area and Sub-area identification after
discussing with purchaser engineering and commissioning team.
02. Preparation of Database (Xls file):
Vendor need to prepare the database based on the engineering
documents.
03 Uploading the database to PDO system:
The database prepared in PDO format need to be uploaded in the
PDO system.
04. Downloading of check sheets for Construction / Precommissioning / commissioning activity:
Vendor need to download the check sheets form PDO server which
needs to be required for purchasers Construction / Precommissioning / commissioning activity.

3.0

Remarks

CODES AND STANDARDS


Following Codes and standards need to be followed by vendor:
PR-1032
PR-1248
PR-1250
PR-1344
PR-1416
PR-1443
PR-1528
GU-558

Maintenance Plans Approval Procedure


Criticality Assessment Procedure
CIMS Manual
Engineering and Operation - Asset and Activity Registration and Deletion in
SAP.
Procedures for the Use of Pipe-RBI Methodology
E-SPIR 2000 Procedure & Project Documents Requirement
E-SPIR 2000 Procedure & Project Documents Requirement
Selection of Safety Critical Elements (SCE) and Development of Performance
Stds (PS) & PS Assurance Tasks

Doc. No: ZAU-84-104810 -VA-6793-20001-0000

PAGE 5 of 5

REVISION: 02
Date: 03.06.2013

Scope of work for CMMS and CCMS

APPENDIX I
Engineering and Operations- Asset and Activity Registration and Deletion in SAP

Doc. No: ZAU-84-104810 -VA-6793-20001-0000

APPENDIX-I

REVISION: 02
Date: 03.06.2013

UNRESTRICTED
Dec-09

Document ID: PR-1344


Filing Key: Business Control

Petroleum Development Oman L.L.C.

Engineering and Operations


Asset and Activity
Registration and Deletion in
SAP

User Note:
The requirements of this document are mandatory. Non-compliance shall only be authorised by
the Document Owner or his Delegate through STEP-OUT approval.
A controlled copy of the current version of this document is on PDO's EDMS. Before making
reference to this document, it is the user's responsibility to ensure that any hard copy, or
electronic copy, is current. For assistance, contact the Document Custodian or the Document
Controller.
Users are encouraged to participate in the ongoing improvement of this document by providing
constructive feedback.

Please familiarise yourself with the


Document Security Classification Definitions
They apply to this Document!

This document is the property of Petroleum Development Oman, LLC. Neither the whole nor any part of
this document may be disclosed to others or reproduced, stored in a retrieval system, or transmitted in any
form by any means (electronic, mechanical, reprographic recording or otherwise) without prior written
consent of the owner.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

This page was intentionally left blank

Page 2

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Document Authorisation

Authorised For Issue December 2009

Page 3

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC

ii Revision History
The following is a brief summary of the 4 most recent revisions to this document. Details of all
revisions prior to these are held on file by the issuing department.

Revision
No.

Date

Author

Scope / Remarks

5.0

Dec 09

Derek Maguire
Latent
Limited

Procedure reviewed and updated to


improve the understanding to projects and
PDO Staff, of what is required to be
uploaded into SAP for an effective
Maintenance Management System.
Checked format and reviewed Sections 2,
3 and 4 with inputs from UOM32
Procedure reviewed due to improved
process work-flow and validated with extra
related business control documents
including deletion procedure.
Updated to SAP version

Robin Norman UOP6


4.0

Sep 06

UOM/321

3.0

Jul 03

TTO/32

iii Related Business Processes


Code
EP.64

Business Process (EPBM 4.0)


Design, Construct, Modify and Decommission Facilities

EP.65

Execute Operations Readiness & Assurance Activities

EP.72

Maintain & Assure Facilities Integrity

EP.80

Manage Abandonment

iv Related Corporate Management Frame Work (CMF)


Documents
The related CMF Documents can be retrieved from the CMF Business Control Portal.
CP-114

Maintenance and Integrity Management CoP

PR-1032

CMMS (SAP) - Maintenance Plans Creation & Approval Procedure

PR-1528

Z6 Notification

PR-1078

Lifting and Hoisting Procedure Inspection Testing and Certification Inspection

PR-1428

Functional Criticality Assessment Procedure

Page 4

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

TABLE OF CONTENTS
1

Introduction ............................................................................................................................ 9
1.1

Background ...................................................................................................................... 9

1.2

Purpose ............................................................................................................................ 9

1.3

Scope ............................................................................................................................... 9

1.4

Distribution / Target Audience .......................................................................................... 9

1.5

Review and Improvement .............................................................................................. 10

1.6

Step-Out Authorisation ................................................................................................... 10

Asset and Activity Registration Process .............................................................................. 11


2.1

Scope ............................................................................................................................. 11

2.2

Process Description ....................................................................................................... 11

2.3

Maintaining and Auditing of Asset Registration Data Accuracy and Availability ........... 15

Asset Deactivation and Deletion Process ............................................................................ 16


3.1

Abandonment and Redundancy .................................................................................... 16

3.2

Writing-Off an Asset ....................................................................................................... 16

3.3

Scrapping of an Asset .................................................................................................... 16

PM Technical Objects Deletion Process ............................................................................. 17


4.1

Background .................................................................................................................... 17

4.2

Deletion Process ............................................................................................................ 17

Functional Location Hierarchy ............................................................................................. 20


5.1

Functional Location Hierarchy Structure ........................................................................ 20

5.2

Functional Location Hierarchy Structure Description .................................................... 20

5.3

Functional Location Category ........................................................................................ 21

5.4

Description ..................................................................................................................... 21

5.5

ABC Indicator ................................................................................................................. 21

5.6

Superior Functional Location ......................................................................................... 21

5.7

Object Type .................................................................................................................... 22

5.8

Start-up Date .................................................................................................................. 22

5.9

Authorisation Group ....................................................................................................... 22

5.10

Main Work Centre ....................................................................................................... 23

5.11

WBS Elements ............................................................................................................ 23

5.12

Plant Section ............................................................................................................... 23

5.13

Catalogue Profile ........................................................................................................ 23

5.14

Installation Specification, Single Installation ............................................................... 23

5.15

Manufacturer ............................................................................................................... 24

5.16

Manufacturer Country ................................................................................................. 24

5.17

Model Number ............................................................................................................ 24

5.18
Page 5

Class............................................................................................................. 24
PR-1344 - Asset and Activity Registration and Deletion in
SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Functional Location Tag Structuring .................................................................................... 25

6.1

General Equipment TAG Structuring for SAP ................................................................ 25

6.2

Functional Location Hierarchy Level 1 Country and Area Codes .................................. 25

6.3

Functional Location Hierarchy Level 2 Grouped Facility Location Codes ................... 25

6.4

Functional Location Hierarchy Level 3 Grouped Facility System Codes ..................... 25

6.5

Functional Location Hierarchy Level 4 Equipment Codes ............................................. 26

6.6

Equipment Descriptions.................................................................................................. 26

6.7

Functional Location Hierarchy Level 4a ......................................................................... 27

6.8

Functional Location Hierarchy Level 5 ........................................................................... 27

6.9

Functional Location Descriptions Level 5 ....................................................................... 27

Standard Tag Format for Mechanical, Rotating & Static Equipment ................................... 28
7.1

Introduction ..................................................................................................................... 28

7.2

Superior Functional Location Level 4 ............................................................................. 28

7.3

Functional Location Level 5 ............................................................................................ 28

Standard Tag Format for Lifting Equipment ......................................................................... 30


8.1

Introduction\ .................................................................................................................... 30

8.2

Responsibility ................................................................................................................. 31

8.3

Functional Location Level 4 ............................................................................................ 31

8.4

Functional Location Level 5 ............................................................................................ 31

Standard Tag Format for Control and Automation (Instruments) ........................................ 32


9.1

Introduction ..................................................................................................................... 32

9.2

Functional Location Level 4a .......................................................................................... 33

9.3

Functional Location Level 5 ............................................................................................ 33

9.4

Instruments Common to a Parent Tag ........................................................................... 34

9.5

Additional Fields and Class & Characteristic ................................................................. 34

10

Standard Tag Format for Electrical Equipment .............................................................. 36

10.1

Introduction .................................................................................................................. 36

10.2

Electrical Functional Location Level 3 ......................................................................... 36

10.3

Electrical Functional Location Level 4 ......................................................................... 37

10.4

Electrical Functional Location Level 5 ......................................................................... 37

11

Standard Tag Format for Piping ..................................................................................... 39

11.1

Functional Location Hierarchy Level 4 ........................................................................ 39

11.2

Piping Functional Location Level 5 ............................................................................. 39

12

Standard Tag Format for Fire and Safety Systems ........................................................ 40

12.1

Functional Location Hierarchy Level 3 ........................................................................ 40

12.2

Functional Location Hierarchy Level 4 ........................................................................ 40

12.3

Functional Location Hierarchy Level 5 ........................................................................ 40

13

Telecommunications Equipment .................................................................................... 41

Page 6

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

14

Functional Location Non Compliance ............................................................................ 42

15

Equipment Hierarchy and Required Fields .................................................................... 43

15.1

Tech Ident No. ........................................................................................................... 43

15.2

Functional Location ................................................................................................... 43

15.3

Description ................................................................................................................ 43

15.4

Equipment Category ................................................................................................. 43

15.5

Object Type ............................................................................................................... 44

15.6

Weight ....................................................................................................................... 44

15.7

Unit of Weight ............................................................................................................ 44

15.8

Size/Dimension ......................................................................................................... 44

15.9

Acquisition Value ....................................................................................................... 45

15.10

Acquisition Date ........................................................................................................ 45

15.11

Manufacturer ............................................................................................................. 45

15.12

Manufacturer Country ............................................................................................... 45

15.13

Model Number ........................................................................................................... 45

15.14

Construction Year ..................................................................................................... 45

15.15

Construction Month ................................................................................................... 45

15.16

Manufacturer Part Number........................................................................................ 45

15.17

Manufacturer Serial Number ..................................................................................... 46

15.18

Authorization Group .................................................................................................. 46

15.19

Start-up Date ............................................................................................................. 46

15.20

Maintenance Plant..................................................................................................... 46

15.21

Company Code ......................................................................................................... 46

15.22

Asset ......................................................................................................................... 46

15.23

Sub-number............................................................................................................... 47

15.24

Catalogue Profile ....................................................................................................... 47

16

Class_FLOC Required Fields ........................................................................................ 48

16.1

Class Type .................................................................................................................. 48

16.2

TechIdentNo. .............................................................................................................. 48

16.3

Class ........................................................................................................................... 48

16.4

Characteristic .............................................................................................................. 48

16.5

Int.Meas.Unit ............................................................................................................... 48

17

Class_Equi Required Fields ........................................................................................... 49

17.1

Class Type .................................................................................................................. 49

17.2

TechIdentNo. .............................................................................................................. 49

17.3

Class ........................................................................................................................... 49

17.4

Characteristic .............................................................................................................. 49

Appendix 1 Code Identification Tables .................................................................................... 50


Page 7

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Appendix 2 - SAP Master Data Management Team Templates ................................................. 58


Appendix 3 Abbreviations ......................................................................................................... 59
Appendix 4 Responsibilities Flow Chart ................................................................................... 60
Appendix 5 - User Feedback Page ............................................................................................. 61

FIGURES
Figure 1 Simplified Asset Registration ..................................................................................... 12
Figure 2 Examples of the Data Input Templates ...................................................................... 13
Figure 3 Equipment Classes (Characteristics) Template ......................................................... 14
Figure 4 Simplified FL Deletion Process .................................................................................. 17

Page 8

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Introduction

1.1

Background

Revision: 5.0
Effective: Dec-09

The Asset Register shall be created during the Define and Design Phases of the
project (see CP-114 Maintenance and Integrity Management CoP Section 3.2) and
maintained current throughout the life of the asset. The information on the Asset
Register shall be stored in SAP and used to prepare the Maintenance Plans (see PR1032 - Maintenance Plan Creation & Approval Procedure).
In PDO the majority of the Projects are development and modification of existing
facilities / equipment and therefore this procedure has been developed on this basis.
For the large project some variance may be required to accommodate the volume of
data that will be required for registration.
IMPORTANT NOTE: No Commissioning, Project Close-Out or Equipment Handover
shall be allowed until the Asset Registration Process is completed, unless the Asset
Owner agrees and signs the appropriate authorization.

1.2

Purpose
The purpose of the procedure is to ensure that Assets are registered and changes are
managed throughout the life of the asset. It shall also ensure that all changes to SAP
Master Data are in accordance with SAP requirements.

1.3

Scope
This procedure shall cover corrections and additions to SAP Master Data that are
eligible using the Z6 Notification Process (see PR-1528 Z6 Notification Procedure).
The structured approach will ensure maintenance and integrity of facilities is
maintained.

1.4

Distribution / Target Audience


The target audience for this document consists of:

Page 9

SAP Master Data Team;

Corporate Discipline Focal Points (CDFPs);

Asset Holders;

Project Managers;

Project Engineers;

Maintenance Engineers (coast and interior) and Flow line Engineers;

Commissioning Teams;

Maintenance Coordinators & Maintenance Supervisors;

Planning Engineers (coast), Area Planners (interior) and Work Schedulers;

Discipline Supervisors;

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


1.5

Revision: 5.0
Effective: Dec-09

Review and Improvement


This document shall be subject to review by the Document Owner / Document
Custodian every 3 years from the last date of issue.
At any time during this period the document Users may request the contents to be
reviewed and revised. Requests for review and revision shall be made in writing to the
Document Custodian using the User Feedback Page or by sending a Marked Up
copy of the document. The decision to review or revise the document shall rest with the
Functional Maintenance & Integrity Manager (UOM), the Owner.

1.6

Step-Out Authorisation
This Procedure is mandatory and Step-Out shall only permitted if authorised by the
Document Owner and / or the Asset Owner.

Page 10

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Asset and Activity Registration Process

2.1

Scope

Revision: 5.0
Effective: Dec-09

The Asset and Activity Registration process shall cover all PDO assets, sub-surface
and surface. The assets will be presented in a functional hierarchy of technical objects.
The process shall provide a standard method for equipment tagging which shall be
consistent to all disciplines, which will be of assistance when constructing the SAP
Asset Field Location Hierarchy.
Structures in SAP are set up such that they will:

support the Group Asset Management and Group Cost Management Reporting
Philosophies, and;

enable Financial Accounting (FI) (EPCOM) reporting requirements and


integrated activity planning across PDO.

NOTE: SAP fulfils the computerised maintenance management system (CMMS) role for
PDO with regard to relevant sub-surface and surface equipment and systems.

2.2

Process Description
NOTE: Reference should be made to Figure 1 Simplified Asset Registration
throughout this process.
The following process description is high level, data structure and requirements shall
be covered in more detail in Section * of this procedure.
1.

The requirement for Asset Registration can come from Projects and from the
Asset.
Asset registration relating to a project will be the responsibility of the Project
Engineer and the project team to address, whereas registration resulting from
the Asset shall be the responsibility of the Asset Holder and asset team.

2.

The personnel nominated to undertake the collection of data for the Asset
registration process should conduct a meeting with the SAP Master Data
Management Team to discuss the scope of work and deliverable from the
process.
NOTE: This meeting shall not be mandatory but is strongly recommended.

3.

The scope of work will be similar for both Project and Asset, but the volume
shall normally be higher on a Project.
The data required shall be collected and entered on to templates provided by
the SAP Master Data Management Team. Each template shall have
Mandatory and Optional fields highlighted accordingly (see Figure 2). Key
information required shall be:

Function Location details and characteristic

Equipment details and characteristics

Guidelines to identification of these requirements and the data format can be


found within this procedure and in the Appendices.

Page 11

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Figure 1 Simplified Asset Registration


Page 12

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

TechIdentNo. FunctLocation

TechIdentNo. FunctLocation

Description

Description

EquipCategory

EquipCategory

Object type Weight

Object type Weight

Revision: 5.0
Effective: Dec-09

Unit of weight Size/dimensions AcquisValue Acquistn. Dat Manufacturer ManufCountry Model number ConstructYear ConstructMth ManufPartNo. ManufSerialNo. Auth. Group Start-up date MaintPlant Company code Asset

Unit of weight Size/dimensions AcquisValue Acquistn. Dat Manufacturer ManufCountry Model number ConstructYear ConstructMth ManufPartNo. ManufSerialNo. Auth. Group Start-up date MaintPlant Company code Asset

Sub-number Catalog profile Comment

Mandatory fields
Optional fields

Figure 2 Examples of the Data Input Templates


The embedded worksheets in Figure 2 can be
opened in Excel by right clicking on the respective
worksheet and selecting Open as indicated left.
Note on the worksheet that some entries are
Mandatory and some are Optional indicated by
colour.
Use the information in the Appendix or further on in
the procedure to define the data required to be
entered.

3
(contd)
Page 13

Equipment Classes (Characteristic) Templates can be accessed from the


UOM3 Homepage (see Figure 3) at the bottom of the list. Within this folder
PR-1344 - Asset and Activity Registration and Deletion in
SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


.

Revision: 5.0
Effective: Dec-09

are all the current Equipment Classes. It is recommended that consultation


is made with the Master Data Management Team before accessing the
required information.

Figure 3 Equipment Classes (Characteristics) Template


4.

Check if Maintenance Craft Procedures (MCPs) are available for the Asset
being registered. Existing MCP can be used if appropriate or adapted as
necessary. If MCPs are not available these shall require to be developed by
the Project or Function / Asset Maintenance Teams and approved by the
appropriate Discipline Technical Authority (TA1).

5.

Check if Maintenance Plans are available for the Asset being registered.
Existing maintenance plans can be used if appropriate or adapted as
necessary. If maintenance plans are not available these shall require to be
developed by the Project or Function / Asset Maintenance Teams and Work
Schedulers. The plan will be approved by the appropriate Discipline Technical
Authority (TA1).
See PR-1032 Maintenance Plan Creation and Approval Procedure.

6.

Raise a Z6 Notification. See PR-1528 Z6 Notification Procedure.


NOTE: The Z6 Notification may cover a specific phase of the Project or part of
the Asset Registration process in the case of large Greenfield of Brownfield
projects. Clarification and agreement should obtained from the Master Data
Management Team as to how best to carryout this action.

Page 14

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


7.

8.

Revision: 5.0
Effective: Dec-09

The submission of the Z6 Notification shall be accompanied by the delivery of


other required documentation as applicable, such as:

FLOC and Equipment Data Templates (mandatory)

As-Built Drawing information i.e. Process and engineering Flow


Schematics (PEFS) at minimum Approved For Construction (AFC)
issue

Instrumentation Drawing

Electrical Single Line Diagrams (SLDs)

Vendor Data Sheets

Process Mass Flow Balance Sheets

The Z6 Notification and all attachments shall be sent to the Master Data
Management Team for compliance / quality checking and upload to SAP.
Incorrect, incomplete or missing data / information shall be returned or
requested from Projects or Asset as appropriate. Registration shall not be
considered complete until all required data / information has been received
and processed.

IMPORTANT NOTE: No Commissioning, Project Close-Out or Equipment


Handover shall be allowed until the Asset Registration Process is completed,
unless the Asset Owner agrees and signs the appropriate authorization.

2.3

Maintaining and Auditing of Asset Registration Data Accuracy and


Availability
Asset Holders shall be responsible for ensuring that the Asset Register is current and
accurate through out the facility / equipment lifetime. Changes to the asset shall be
managed in accordance with PR-1528 Z6 Notification Procedure. Anomalies or
inconsistencies regarding asset data shall be reported by Asset Holder to the Master
Data Management Team who shall investigate and rectify accordingly.

Page 15

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Asset Deactivation and Deletion Process


Asset data stored in SAP shall be maintained current at all times to enable effective
operation of the business. For the business to be effectively monitored changes to
facilities and equipment require to be actioned promptly. Abandonment and write-off or
incorrect entries of assets that do not exist (due to migration from older legacy systems)
must be captured and actioned so that the Asset Register reflects an accurate picture.
Where an asset is deactivated, activities associated with the asset i.e. maintenance
plans etc, shall require to be modified or suspended. Until the asset is removed and
disposed of it will still be maintained as an asset and accounted for accordingly,
however its functional location and / or equipment data may change, and this requires
to be captured and recorded. Once the asset is finally removed and disposed of then
the asset can be deleted from the register and SAP.

3.1

Abandonment and Redundancy


The Asset Holder, Asset Owner and / or any person with the correct authorisation for
initiating abandonment or redundancy of an asset, has the responsibility to ensure that
a Z6 Notification (See PR-1528 Z6 Notification Procedure) is raised to ensure all
relevant information i.e. maintenance, location, tag information etc, is deactivated or
modified as required.

3.2

Writing-Off an Asset
The Asset Holder, Asset Owner and / or any person with the correct authorisation for
writing-off an asset, has the responsibility to ensure that a Z6 Notification (See PR-1528
Z6 Notification Procedure) is raised to deactivate the asset in SAP PM module with all
relevant data including equipment movement information, where applicable. Additionally
the Asset Holder should oversee the asset write-off in accordance with
PR-1164 - Fixed Asset Abandonment Procedure
PR-1419 Abandonment and Restoration
PR-1576 - Fixed, Movable Assets and Stock Write-Off
When the Write-off Committee approves Write-off, another Z6 request is to be made to
move the entire asset Data to the area Write-off FLOC.
Once the asset is disposed off and financial books cleared, another Z6 should be raised
to request for all relevant FLOC's, Equipment and Maintenance plans to be flagged for
deletion.

3.3

Scrapping of an Asset
An assets that has been identified for scrap shall require Approval from the
Shareholders and completion of the Write-Off Proposal Form (see PR-1576 - Fixed,
Movable Assets and Stock Write-Off) before it can be flagged for deletion from the
Asset Register.
The Asset Holder, Asset Owner and / or any person with the correct authorisation for
the scrapping of the asset shall ensure a Z6 Notification is raised to amend the SAP PM
Module.

Page 16

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

PM Technical Objects Deletion Process

4.1

Background

Revision: 5.0
Effective: Dec-09

The management of Technical Objects in SAP is an ongoing process, requiring at times


deletion from the system. The migration of very large quantities of data from the old
legacy system resulted in data being identified that was incorrect and therefore
requiring deletion. This together with ongoing validation of the data, has led to a
situation where for instance, there are Functional Location (FL) records held in the
system that have been flagged for deletion (DLFL).
This process shall outline how Technical Objects can be deleted from SAP in such a
way that minimal work shall be required by the PDO business community as a whole.
For clarity Functional Location has been considered as the Technical Object, but the
process can be adapted for other Technical Objects i.e. Equipment.

4.2

Deletion Process

Figure 4 Simplified FL Deletion Process


Page 17

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


1.

Revision: 5.0
Effective: Dec-09

The normal Status for a Functional Location (FL) is CRTE (Created). This is
the status for all Live Functional Locations and allows all normal business
transactions to be carried out on or by the FL.
To suspend normal activities for a FL the status INAK (Inactive) should be
activated. This status allows changes to be made to the FL, but will prevent
Work Orders or Notifications to be created against it. Additionally Maintenance
Plans require to be deactivated preventing WO being generated from PM
Plans.

2.

Prior to any FL being flagged as DLFL a number of simple checks need to be


performed in order to ensure that there will be no subsequent problems when
the FL is deleted. These include the following;

If any children or dependant FLs are attached to the FL, ensure they to
are to be flagged as DLFL.
NOTE: If this is the case then ensure all of these checks are carried out on
all such FLs.

Run IL02 to determine if any Equipment records are installed on this FL. If
the change is simply to create a replacement FL for the one being deleted,
then it is essential that the EQ record be assigned to the new FL before
flagging the old FL for deletion. If the FL and the EQ records are to be
deleted then de-install the attached EQ and insure that it is also flagged
for deletion.

Run IL02 (or similar) to identify ANY Work Orders against the FL to be
flagged DLFL. If any Work Orders, irrespective of their Status, are found
then they must be changed to have the correct FL entered against them.
This will at times be straight forward but will sometimes be quite complex
to perform. Ensure any Notifications that are attached to the Work Orders
are also updated. If the Orders have been completed (TECO) or Closed
(CLSD) then care needs to be taken in respect to the dates of the Work
Order when re TECO or re CLSD is carried out..

Run IL02 (or similar) to identify ANY Notifications against the FL to be


Flagged for DLFL. In most cases, carrying out the check b) should
identify all of these Notifications but this check should be carried out
anyway.

Run IL02 (or similar) to identify any Maintenance Plans/Items that use this
FL. If found then either insert the new FL in place of the old one or
remove the old one and mark the Maintenance Plan as Inactive.

Run IL02 (or similar) to identify any Measurement Point that use this FL. If
found then ascertain if there are Measurement Documents for the
Measurement Point, if so then delete them. Once all Measurement
Documents have been deleted then delete the Measure Point.

If there is to be a straight replacement of a new FL for a old FL number


then it may be necessary to transfer the above information to the new FL.
This will have to be a business decision.

Run IL02 (or similar) to identify if there is any BOM related items
associated with the FL. If allocations are found then remove the BOM ref
number from the ConstType field on the FL.

Page 18

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

There are two distinct ways (at least) that a FL can be found on an Object
List. The first is via a Maintenance Item and the second is via a Work
Order. In order to find where there may be a possible use of the FL on
either of these two options, two methods will have to be executed.
o

Run IW38 with the Object List option selected and enter the FL to find
if the FL is used in any Work Order Object Lists.

Run IP18 again with the Object List option selected and enter the FL
to find if the FL is used in any Maintenance Item Object Lists.

In either/both of these cases, the FL will have to be removed from all of the
Work Order Object List or Maintenance Item Object List before the FL can
be deleted.

Run IL02 (or Similar) to identify if there is an Asset record associated with
this FL. If there is then consideration must be given as to what needs to
done with this Asset record as part of the deletion process.

IMPORTANT NOTE: If the deletion of the FL is simply to create a new FL to


replace the old FL number then the Asset record must be referenced on the
new FL. If the FL is being deleted as it no longer exists then this information
needs to be communicated to the Asset team so that the asset record can be
closed.
3.

Set the FL to DLFL and move to OM.000 for archiving prior to deletion.

4.

Carryout final checks if required and set status to DLT.


NOTE: This process shall be carried out on all children / dependant FLs as
well.

5.

Page 19

Delete the FL from the system.

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Functional Location Hierarchy


Refer to Appendix 1 for Code Identification Tables

5.1

5.2

Functional Location Hierarchy Structure


Level

Description

Example

Level 1

Complex (Area)

OM.LEK

Level 2

Grouped Facility (Location)

OM.LEK.00261

Level 3

Facility (System)

OM.LEK.00261.CI

Level 4

Grouped Tag Position (Operational


Package)

OM.LEK.00261.CI.P2605A

Level
4a

Control Systems - all Inst Tags (CS)

OM.LEK.00261.CI.P2605A-CS

Level 5

Equipment Tag Position (Maint Tag)

OM.LPS.P2605A-MT

Level 5

Control Systems Equip Tag (Maint


Tag)

OM.LPS.26-PRC-930-CV

Functional Location Hierarchy Structure Description


A Functional Location is a Technical Object in SAP terms and represents the
hierarchical breakdown of an asset.
The Function Location is the lowest level of this hierarchy, where equipment is
generally installed (where there is a business requirement and settings permit,
equipment can be installed at a higher level of the hierarchy).
The following Functional Location structure is applied from the highest level 1, to the
lowest level 5, the breakdown is as follows:

Level 1 - Representing the Country OM for Oman and the area LEK for
Lekhwair.

Level 2 - Represents the Facility or Station where the equipment is installed.

Level 3 Is the Grouped Process System in which equipment is installed within


the Facility.

Level 4 - The Operational package or Equipment identified as the primary


equipment, although it may itself have equipment attached to it. The Primary
equipment is the Superior equipment to any equipment attached to it. For
example, a pump will be the superior equipment to a lubricating oil filter, which
forms part of the pump lubrication system. It is known as the Superior Function
Location for the maintainable equipment Tags.

Level 4a -This level is applicable to the Instrument Control discipline; it is the


Superior Function Location for all instruments, associated with an operational
package or primary equipment.

Level 5 This is the level that identifies the maintainable equipment Tags, it is
the lowest level and is known as the Function Location of the maintainable
equipment. The Area code and the Facility (station) numeric code is combined
an replaced by a letter code taken from the right hand column in Table 1.

Page 20

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

The Functional Location Structure Hierarchy applies to all disciplines, this guide will
attempt to be specific in identifying the Tag numbering structuring for the following: -

5.3

Mechanical and Lifting Equipment

Electrical Equipment

Instrumentation Equipment

Piping and Valves

Fire & Safety Components

Telecommunication Equipment

Functional Location Category


The following SAP Functional Location Categories will be set up to allow control over
the use of Functional Locations for Surface Assets and Sub-Surface Assets:

Surface Assets

Sub-Surface Assets

The boundary between surface and sub-surface assets is taken at the X-tree - flowline
flanges.

5.4

Description
The field holds the description of the Functional Location. The user shall enter a
meaningful and clear description of the Functional Location. The maximum length
allowed for the description is 40 characters.

5.5

ABC Indicator
The ABC Indicator field will be used to indicate the Functional Location criticality. The
decision has been made to assign the ABC Indicator to a Functional Location, rather
than to the Equipment, as the Functional Location is unlikely to change within a system
or process, while Equipment may be installed at different Functional Locations with
varying criticality (ABC Indicators).
A=

Safety Critical Equipment (SCE)

B=

Production Critical Equipment

C=

Non Critical Equipment

These codes are in accordance with PR-1248 Functional Criticality Assessment


Procedure and EP 2009-9009 Safety Critical Element Management)
NOTE: The ABC indicator can be used to rank Work Orders on their urgency.

5.6

Superior Functional Location


This is a combination of Level 1, 2 & 3. or Level 1,2,3 & 4 (see 5.1)
Example OM.MAR.00281.ED or OM.MAR.00281.ED.SA-SS15A

Page 21

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


5.7

Revision: 5.0
Effective: Dec-09

Object Type
As stated in Section 5 Technical Object Type can cover Functional Locations as well as
Equipment in one single pull down menu, which could be potentially confusing. In PDO,
assignment of Object Types should be to Equipment only as this is seen as to be more
useful i.e. users are more likely to want to search for Equipment of a specific type,
Pump-Centrifugal or Vessel-Separation, etc.
A consolidated list of Object Types for all PDO assets, thus not only ex-EPMARS
(surface facilities), but also estate, telecom, IT, wells, automation & control Equipment
Object Types.
For the facilities ISO 14224 and the Steplib convention could serve as the reference,
using the ISO 14224 Class and Type combination much like NAM did. A centrifugal
pump would then be Object Type PUCE (Class Pump = PU, while Type Centrifugal =
CE), etc.

5.8

Start-up Date
Start-up Date (Commission-Date) of the Functional Location can be entered in this field.
The start-up date is limited to 8 characters in the format dd.mm,yyyy.

5.9

Authorisation Group
The Authorisation Group defines who can create and change Functional Location Data.
NOTE: It is expected that only a small group of people will create and change
Functional Locations. Functional Location data by nature is rather static. In practice
dedicated groups of people will create and maintain Functional Location Records in
their expertise area. It is required to fence off Functional Locations data that are in the
domain of another Authorisation Group.
The current Authorisation Groups are as follows:

Page 22

OM00

Organisational Assets

OM10:

Surface Assets (hydro-carbon producing)

OM20:

Sub-Surface Assets (hydro-carbon producing)

OM30:

Estate Assets

OM40:

Telecom Assets

OM50:

IT Assets

OM60:

Movable Assets

OMIN

Inspection Plans

OMMT

Maintenance Plans

OMSE

Service Entry Plans

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


5.10

Revision: 5.0
Effective: Dec-09

Main Work Centre


The Main Work Centre is a combination of Complex and Discipline e.g. MARELEC
The field can hold the Main Work Centre responsible for the Functional Location.
NOTE: A Work Centre entered here will appear on the Header Data Tab of the PM
Order when an Order is raised against the Functional Location.
A Work Centre Field can be entered on the Location Tab, but no particular requirement
for this has been identified and it will not be used.
The Main Work Centre may be entered in the Functional Location field if in general
there is a unique main Work Centre responsible for the Functional Location.
In case multiple Main Work Centres (mechanical, electrical, etc.) are responsible for a
Functional Location then the field should be left blank, as a default setting into the PM
Order would not be desired.

5.11

WBS Elements
A WBS element can be linked to a Functional Location, whereby a Work Order raised
against the Functional Location will automatically link the costs to the relevant WBS.
The settlement rule applicable for the WBS will assign the costs to the Cost Centre.
This way OPEX related costs would be captured at the right WBS.
NOTE: There will be a development to assign the correct WBS to the Work Order by
checking the Work Order Type against the WBS listed against the Functional Location.
The program will eventually assign the correct WBS to the PM Order.
Currently the combination of Maintenance Activity Type (MAT) and WBS Activity must
be adhered to.

5.12

Plant Section
The Plant Section field will hold the identifier for the Organisational Asset Team
responsible for the Functional Location.

5.13

Catalogue Profile
This field may hold a Catalog Profile, applicable for a Technical Object and can be
populated with an Object Part code. Depending on the Object Part (Pump-Centrifugal,
Pump-Reciprocating, etc.) there will be a different Damage code and Damage Cause
code specific to a certain Object Part.
The Catalog Profile field will be used in the Equipment record to link the Object Part
code. This link will ease completion of PM Notifications raised on Equipment, as the link
to the Object Part code will direct the selection of an appropriate Damage code and
Damage Cause code.

5.14

Installation Specification, Single Installation


This tick box indicates whether multiple Equipment records can be linked / installed at a
single Functional Location. In PDO the system is configured that this box defaults as
ticked, preventing multiple Equipment to be installed at the Functional Location. The
Functional Location creator however can reset this tick box if required.

Page 23

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

NOTE: The rationale behind this was for the old EPMARS system that had a one-toone relationship between Tag Position and Equipment. Therefore when existing
Functional Locations and Equipment are loaded into SAP this one-to-one relationship
will be there already. Furthermore it is a good way to avoid pollution in the system. For
instance it will be possible, with multiple installation enabled, to install the new piece of
Equipment, but forget to dismantle the old one. The single installation configuration will
force users to dismantle old equipment before installing a new one. Just like in a real
situation.
Fill Y for single installation, if more than one leave blank.

5.15

Manufacturer
The Equipment Manufacturer can be entered in this field can be entered. A standard
format will be beneficial to enable search / reporting against a certain Manufacturer.
Manufacture must be selected from SAP Master Database. No free text is allowed
which might result in variations in Manufacturer Descriptions, basically when a List Edit
is performed.
The Maximum length of the Manufacturer is 30 characters.

5.16

Manufacturer Country
The Manufacturer Country can be selected from a pull down menu
Length of the Manufacturer Country is 3 characters.

5.17

Model Number
The Model Number is entered in this field.

5.18

Class
The correct Functional Location Class should be entered in this field, normally for
instrumentation (EP_F_INST) should be used.

Page 24

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Functional Location Tag Structuring


Refer to Appendix 1 for Code Identification Tables

6.1

General Equipment TAG Structuring for SAP


All disciplines shall follow the same Functional Location Hierarchy Structure down to
Level 4. At this point instrument control loops will deviate, by including all Tags under
the suffix CS for control systems.

6.2

Functional Location Hierarchy Level 1 Country and Area Codes


All Level 1 Function Location codes shall contain the Country Code OM for Oman. The
facility code will be the letter code for the area where the facility is located.
The description will be Oman followed by the name of the Area code as shown

6.3

Function Location

Function Location Description

OM.LEK

Oman / Lekhwair

Functional Location Hierarchy Level 2 Grouped Facility Location


Codes
This identifies the Function Location as belonging to or grouped with a specific facility or
location. The Level 2 codes contain the grouped Facility / Station numeric codes with
the descriptions of the facility.

6.4

Function Location

Function Location Description

OM.LEK.00261

Lekhwair Production Station

OM.LEK.00254

Lekhwair B Station and Field Facilities

OM.FAH.00237

Water Well Fahud West

Functional Location Hierarchy Level 3 Grouped Facility System


Codes
This identifies the system within the Facility in which the Function Location
(equipment) is located.
These codes are used as part of the structure for Level 3 Function Location, while the
system description is included in the Function Location Description following the
Facility Description, as per examples below:(Level 3) Function
Location

Function Location Description

OM.LEK.00261.CG

Lekhwair Prod Station Crude Gathering

OM.LEK.00254.OW

Lekhwair B Stn & Fld Facility Oil Wells

OM.FAH.00237.WD

Water Well Fahud West Water Disposal

NOTE: The Function Location Description characters are limited to 39 for the SAP
upload.

Page 25

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


6.5

Revision: 5.0
Effective: Dec-09

Functional Location Hierarchy Level 4 Equipment Codes


This identifies the Function Location code of the primary equipment or packaged units,
installed at a specific location within in the facility / system.
NOTE: The Tag numbering shall be unique within a plant or facility across all
disciplines. Initially issued for use during the Facility Engineering Construction phase or
Improvement Projects, except for Electrical.
The maintainable Tags are identified from these, as being maintainable equipment
items where work needs to be managed, history or cost identified or spares may be
required at this Function Location level, throughout the lifetime of the facility.
The following table provides examples of the Equipment Tag Function codes.
Equipment Type Function Codes

6.6

Code
Code Letter Description
Letter

Code
Code Letter Description
Letter

Packaged Units

Mixers, Stirrers, Mixing Nozzles


etc

Buildings

Pumps (all types)

Columns, Contactors

Quality Measurement devices

Drying Equipment

Pig Receivers

Heat Exchangers

Filters,

Fired Heat Exchangers, Boilers,


etc

Storage Tanks

General Electrical Equipment

Vessels, Pressure Vessels, silos,


hoppers

Compressor

Material Handling Equipment

Pig Launchers

BC

Battery Charger

Equipment Descriptions
Descriptions are important in supporting the identification of the equipment Function
Location. They should start with the Superior Function Location Tag, (Level 4) or the
Parent Tag, followed by a description of the function associated with the equipment,
as per example: A typical example of Level 4 Primary equipment and description is as follows: Superior Function Location

Superior Function Location Description

OM.LEK.00261.CI.P2605A

P2605A CHEMICAL INJ PUMP

This clearly describes the primary equipment as P2605A, then the function of the pump
as being Chemical Injection denoted by the prefix CI.
Control devices associated with the Primary equipment P-2605A, as identified in the
Function
Location
Tag
as
OM.LEK.00261.CI.P2605A,
will
become
OM.LEK.00261.CI.P2605A-CS. The suffix CS denotes a control system
It will follow that all control devices identified in SAP at level 5, will given a Superior
Function Location, similar to Level 4, but followed by the suffix CS.

Page 26

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC


6.7

Functional Location Hierarchy Level 4a


Automated and Control Systems Function Codes and Tag numbering
This is a specific suffix to identify Control and Automation devices, associated with a
Packaged Unit or Primary

6.8

Functional Location Hierarchy Level 5

6.8.1

Grouped Facility Identification Codes


In level 5 the Grouped Facilities code and identification number used in Level 2, are
combined and replaced by an alphabetical code, as shown below.
Examples of Grouped Facility Identification Codes
Level 2 Codes

Facility Location
Description

Level 5 Codes

OM.LEK.00261

Lekhwair
Production Station

LPS

OM.LEK.00254

Lekhwair
B
Station and Field
Facilities

LEB

LEK.00261 becomes LPS and LEK.00254 becomes LEB.


Function Location

Function Location Description

OM.LEK.00261.CI.P2605
A

OM.LPS.CI.P2605A-ME

OM.LEK.00254.CI.P2505
A

OM.LEB.CI.P2505A-ME

ME (Motor Electric) is typical of the suffix to equipment at the Level 5 Function Location

6.9

Functional Location Descriptions Level 5


Descriptions are an important inclusion in supporting the identification of the equipment
Function Location. They should start with the Superior Function Location Tag (Level 4)
or the Parent Tag followed by a description of the function associated with the
Function Location. See below.
Level 5 - Function Location Structure & Description
Superior Function
Location (Level 4)

Superior
Function
Loc
Description
(Level 4)

OM.LEK.00261.CI.P
2605A

P2605A CHEMICAL
INJ PUMP

Function
(Level 5)

Location

OM.LPS.P2605A-ME

Function Location
Description (Level
5)
P2605A
CHEMICAL
INJ
PUMP MOTOR-ME

NOTE: Descriptions are limited to 39 characters for uploading into SAP

Page 27

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC

Standard Tag Format for Mechanical, Rotating & Static


Equipment
Refer to Appendix 1 for Code Identification Tables

7.1

Introduction
From the Process Engineering Flow Schematics (PEFS), equipment identified as being
a maintainable, or where historical data is required to be recorded. The Engineering
Function Location Tag, the Description and the Process System in which the equipment
performs a function is extracted. Equipment to be considered under this requirement
would include, rotating equipment, control equipment, static vessels and tanks, relief
valves etc.

7.2

Superior Functional Location Level 4


The Level 4 Function Location identifies the Superior Function Location Tag, this may
be as a single piece of equipment or as a Skid mounted unit, both will have child Tags
attached.
Example: - In the Lekhwair Production Station Facility, a Chemical Injection pump with
the Engineering Tag format of P-2605A and a Gas Lift Compressor skid with the
Engineering Tag format of A-2750 extracted from the PEFS are both Superior Function
Locations identified as show below.
Superior Function
Location (Level 4)

Superior Function Location Description

OM.LEK.00261.CI.P2605
A

P2605A CHEM INJ PUMP

OM.LEK.00261.GL.A2750

A2750 GAS LIFT COMPRESSOR SKID

Where:OM Is the country location applicable to all PDO Tags


LEK Is the AREA abbreviated code
00261 Is the AREA numerical code
CI & GL Is the Facility System Suffix Code in which the Tag is located
P2605A Is the original Pump Unit Engineering Tag P-2605A (with the - removed)
A2750 Is the Gas Lift Compressor Skid A-2750 (with the - removed)

7.3

Functional Location Level 5


This is the next level down in the hierarchy, where specific equipment associated with
the main equipment (Primary or Superior) is registered in SAP
In the previous example (Section 8.2) the Chemical Injection pump and the Gas Lift
Compressor skid with the Tag formats P-2605A and A-2750 respectively, both have
electric drive motors.
This equipment will be registered in SAP under P2605A and A2750 as the Primary
Equipment; the hierarchy will be the Superior Function Location of the motors, as
shown below.

Page 28

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Function Location

Function Location Description

OM.LPS.P2605A-ME

P2605A CHEM INJ PUMP MOTOR-ME

OM.LPS.A2750-ME

A2750 GAS LIFT COMPRESSOR MOTOR-ME

Where:OM Is the country location applicable to all PDO Tags


LPS A- combination of the level 4 facility identifier codes, LEK & 00261, which is
substituted for a single Level 5, facility identifier code, taken from the RH column of
the Grouped Facility Codes
P2605A Is the original Pump Unit Engineering Tag P-2605A (with the - removed)
A2750 Is the Gas Lift Compressor Skid A-2750 (with the - removed)
ME - The suffix for the electric motor drive
The motor is a child of the primary unit and is identified at the end of the Function
Location by adding the Electrical Equipment Type suffix code of ME.
NOTE: Tables of suffixes shall be obtained from the Master Data Management Team to
ensure currency.

Page 29

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Standard Tag Format for Lifting Equipment


Refer to Appendix 1 for Code Identification Tables

8.1

Introduction\
Lifting equipment will include all types of Cranes (Static and Mobile), Lifting Beams,
Lifting Appliances and Mechanical Handling Equipment (permanent or moveable). All
lifting equipment has to be identified with a unique number and registered.
NOTE: This is a legal requirement under Lifting Operations and Lifting Equipment
Regulations (LOLER)

8.1.1

Permanent Items
Functional Locations
Items such as overhead cranes, runway beams, chain block trolleys etc. that remain
essentially in one location and that require regular inspection should be set up in SAP
as functional locations. The naming convention for these is controlled by a standard that
UOM apply to maintain consistency across PDO.
The Functional location contains a number of fields that contain information about the
item such as object type, manufacturer, serial number etc.
Additional information is held in classification for the functional location e.g. is it an
SCE? Where a functional location has equipment installed the details such as
manufacturer etc will be held in the equipment record.
A workshop is also to be considered as a functional location.
Any removal, additions or changes to existing data in SAP will require a Z6 notification
to be raised by the asset holder.
All items that require inspection / certification must have a maintenance plan to
generate work orders for the preventive maintenance activities. The inspection
frequencies shall be in accordance with PR-1708 - Lifting and Hoisting Procedure
Inspection Testing and Certification Inspection.
Those items that are identified as Safety Critical, will have the additional integrity
solution requirements to be satisfied i.e. results recording in SAP QM module.
Equipment Registered in SAP
Equipments in SAP have a unique number that is system generated in SAP. Where
there is the potential for the item of equipment installed in the functional locations to be
replaced (e.g. lifting appliances such as lever hoists, jacks etc in workshops) then an
equipment record is also created and this would then be installed in the functional
location in SAP. The maintenance of the equipment will be covered by the plan for the
functional location that they are installed in.

8.1.2

Non-Permanent Items
Items such as slings, shackles etc are really considered to be consumable and these
are not added to SAP, the administrative burden of keeping SAP up to date given the
quick turnover of these items is not workable. At local level a Register needs to be
maintained to keep track of these items. This is a legal requirement and therefore
mandatory. The only thing that should be in SAP, is a preventative maintenance plan at
the station level to test / inspect these items at the required interval, and the existing
system of testing and colour coding etc, carries on as it is with the work order as the
trigger for the activity.

Page 30

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC


8.2

Responsibility
It is the responsibility of the Asset Holder to ensure registration and provide the required
information to the Maintenance Function for upload of details into SAP system.
Assistance shall be provided by the Maintenance Strategy & Support Teams.

8.3

Functional Location Level 4


Under the Function Location Code structure for Level 4, all the lifting equipment at a
facility will have a common Superior Function Location. The Grouped Facility System
Code will be Utilities (UT), the Tag identification will be LIFTING as for the following
example.
OM.LEK.00261.UT.LIFTING
FACILITES

with

the

description

LEKHWAIR

LIFTING

UT This is the Utilities Grouped System Facilities Code, all lifting equipment
will be identified under this code, taken from Table 02
LIFTING This identifies the Superior Tag (Primary), for all Lifting equipment in
the facility

8.4

Functional Location Level 5


In SAP the Functional Location Equipment Tag Number for lifting equipment, is a
unique number.
Lifting Equipment Tag identification at Function Location hierarchy Level 5 for a specific
facility, will be structured as follows.
Function Location

Function Location Description

OM.LPS.LB24698-10-LE

RUNWAY BEAM-SULFEROX PLANT

OM.LPS.LC120694-6-LE

CHAIN BLOCK-WTR INJECTION PUMP

Where:OM Is the country location applicable to all PDO Tags


LPS The facilities location
LB/LC An abbreviation specific to the type of lifting equipment
24698-10 / 120694-6 The serial numbers of the lifting equipment provided by the
Manufacturer, and correspond to the serial code number of the issued Test
Certification. This can be any combination of numbers or letters or both.
LE Denotes that the equipment Tag is designated as Lifting Equipment
Lifting Accessories such as slings, small chain blocks, shackles, chains etc, will be
collectively Tagged in SAP. A record of these will be kept in a separate spreadsheet;
and a PM will be raised in SAP to inspect these items collectively every 6 months. With
the registration planned maintenance routines have to be added. For details follow the
requirements of Lifting and Hoisting PR-1708 Inspection, Testing and Certification,
which might have to be supplemented with information from the manufacturer.

Page 31

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC

Standard Tag
(Instruments)

Format

for

Control

and

Automation

Refer to Appendix 1 for Code Identification Tables

9.1

Introduction
To address operation and maintenance requirements, SAP C&A Plant maintenance
data is to be registered at SAP in a structured and consistent way across PDO. The
information in this section has been extracted from a document produced by C&A
Functional department (CDFP C&A), it provides the basic / minimum guidelines to
achieve, good control and consistency on C&A data. This document has not been fully
reviewed or approved and therefore cannot be quoted as a source.
The scope of the coverage includes instrumentation with executive action including:

F&G devices,

Pressure, Flow, Temperature and Vibration measurement, providing alarm or


shutdown, and

control and shutdown valves.

Indicating devices such as TI, FI, PI, PG, controllers, solenoid valves and limit switches
are not to be included in SAP, only the measuring devices, the final elements, reset and
trip switches are to be considered.
These SAP C&A Instrument Maintenance Management directives are to be followed
while modifying and preparing new C&A Instrument Maintenance data.
9.1.1

Instrumented Protective Function Related Groups


Initiators (measuring devices)
Final Elements

9.1.2

Process Related Groups


Control Loops consisting off:

Primary Element - Transmitters

Final Elements - Valves

Open Loops consisting off:

Primary Element - Transmitters

Station Flow meters


Computers
Analysers.
NOTES:
The SOV of an ESD valve is not required to be registered in SAP, if the ESD valve is
registered the associated SOVs are considered as part of the ESD valve.
The Pneumatic Pressure switch of a pneumatic Transmitter is not required to be
registered in the SAP system if the Transmitters are registered. These switches are
considered part of the transmitters.

Page 32

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC

Pressure gauges and in between loop elements like Controllers, Summarizing units,
Function generators, Ratio unit, I/P converters and valve actuators, limit switches, etc
are not required to be registered in the SAP system, as these items have a high MTBF
with no specific PM requirements.

9.2

Functional Location Level 4a


The Instrument tags are grouped / structured under Main or Primary Equipment.
The Superior Tag Function Location for the Instrument Equipment Tags is the Primary
Equipment Tag, followed by the C&A grouped system code CS. All the Instruments
associated with the Primary equipment at Level 5, will be listed under this Superior
Function Location.

9.3

Superior Function Location (4a)

Superior Function Location Description

OM.LEK.00261.CG.V2692-CS

V2692 INSTRUMENT CONTROL TAGS

OM.LEK.00261.WI.P2604D-CS

P2604D INSTRUMENT CONTROL TAGS

Functional Location Level 5


The data input sources for SAP Instrument function location are the PEFS, Trip and
Alarm Drawings and Field Data collection.
Instrumented Protective Function, Process Indication and Control Instruments is
required to be registered in SAP; in order to carry out maintenance schedules and
record equipment history.
Examples of the Level 5 Structure
Superior Function
Location (Level 4a)

Function Location
(Level 5)

Function Location Description


(Level 5)

OM.KEK.00261.WI.P2604E OM.LPS.26-FZA-015-PT 2604E Pressure Switch


From the above the function location format can be determined as follows: OM - The country code location, applicable to all PDO Tags
LPS This is the Facility / Station location code.
26 Facility unit number, this is the first two numbers of the primary equipment V2692
Followed by

FZA - This is the parameter measured & Instrument function taken from the PEFS e.g.
LRCA, FIC, FRC, and FT etc. Where the letter Z is included, it identifies it as being a
safety executive action device for alarm and shutdown.
Followed by

015 This is the instrument serial number taken from the PEFS
Trip Functions - Include the trip function H, HH or L, LL after the serial number on
instruments that are IPF Z Tags only
Followed by

PT - This is the Instrument Type / Object type identified from the PFS, include the
correct suffix from Table 10 i.e. LT, PT, PSW, FT, FSW, CV, etc.

Page 33

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


9.4

Revision: 5.0
Effective: Dec-09

Instruments Common to a Parent Tag


Common Instruments / equipment belonging to 2 or 3 rotating equipment, are to be
listed under first rotating equipment with a word Comn. at end of the description.
Where two or more Tags are in the PEFS with same serial number: Example: -

LRCA-402A, LRCA-402B or 11-LRCA-402C

Should be uploaded into SAP as: OM.LPS.11-LRCA-402A-LT,


OM.LPS.11-LRCA-402B-LT
OM.LPS.11-LRCA-402C-LT
Or
OM.LPS.11-LRCA-402-1-LT,
OM.LPS.11-LRCA-402-2-LT
OM.LPS.11-LRCA-402-3-LT

9.5

Additional Fields and Class & Characteristic


The two additional function location fields and relevant/applicable Class &
Characteristic information below for each C&A Function Location are required to be
collected/uploaded at SAP.

9.5.1

Additional functional location fields


Manufacture
Model

9.5.2

Class & Characteristic


EP_F_INST_UOM
EP_F_INST_Transmitter/Instrument - Range Lower value
EP_F_INST_Transmitter/Instrument -Range High value
EP_F_INST_Trip Low value
EP_F_INST_Trip High value
EP_F_INST_Alarm Low value
EP_F_INST_Alarm High Value
EP_F_INST_Maintenance Group
EP_F_INST_Application
EP_F_INST_SIL Level
EP_F_INST_Parameter of Measurement
EP_F_INST_Technical Object RRM Indicator
EP_F_GENERAL_P.E.F.S Drawing No
EP_F_Valve_Valve Cv Value
EP_F_Valve_Valve Size

Page 34

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC

Application Characteristic values are used to indicate Off Plot & On Plot and IPF &
Process control applications.
Parameter of Measurement Characteristic values are used to indicate the parameter
measured/controlled.
Technical Object RRM Indicator Characteristic values are used to indicate the
maintenance strategy.
Maintenance Group Characteristic values are used to indicate the Preventive
maintenance groups.
Function location ABC indicator field values have to be generated based on
EP_F_INST_Maintenance Group Characteristic values.
NOTE: EP 2009-9009 Safety Critical Element Management) should be consulted in the
implementation of ABC Indicators and subsequent SCE Barriers.
The table below provides sample values to generate Class & Characteristic values
Application

Parameter of Measurement

RRM Indicator

Maintenance Group

Instru.Protect.Funt.
Off Plot

Analyser

IPF-Instrument
Protective Function

ANALYSER

Instru.Protect.Funt.
On Plot

BSW

RCM-Reliability
Centred Maintenance

BS&W Meters

Process Indi.Ctrl
Off Plot

Communicate

OFMOn
Maintenance

ESD VALVES

Process Indi.Ctrl
On Plot

Density

FLOW METERS

ABC Indicator
B
C

Failure

A
C

ESDV-FE

HEATER

FE-Fin.Ele.

IPF SAF GRD

Fire

IPF-FG

Flow

MFM

Flow-FE

MOL METERS

Gas

OFM

Blank

Heat

PROCES CRTL

Level

ROT.EQ.PAKGE

Level-FE

SYSTEMS

No Parameter

WELLHEAD MON

Pressure
Pressure-FE
Smoke
Speed
Temperat-FE
Temperature
Vibration
Vibration-FE

Page 35

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

10

Revision: 5.0
Effective: Dec-09

Standard Tag Format for Electrical Equipment


Refer to Appendix 1 for Code Identification Tables

10.1

Introduction
The Function Location Source information is normally gathered from the project
drawings and other source documents.
For the electrical facilities Function Location / Tagging i.e. TX, GEN, SW, CB, IS etc is
generated from electrical drawings such as, Lighting & Small Power, Distribution Line
drawings etc and will be guided by the Electrical CDFP as required.
The electrical equipment will include hardware such as lighting, both Emergency and
normal, floodlights, main switchboard bus bar sections, switchgear, battery chargers,
Ex junction boxes, distribution boards, electric motors, transformers, control panels,
isolators, cathodic protection, overhead lines, electrical generators, circuit breakers.
From these electrical drawings the equipment is identified by the electrical legend, a
SAP suffix is attributed to the equipment depending upon its function. The area code is
then added, while the function of the equipment is taken from the drawings and
included in the Function Location description.
At this point no serial number is added, the Tag is forwarded to the SAP Master Data
Management Team who will allocate the Tag numbers.

10.2

Electrical Functional Location Level 3


The electrical systems will be grouped under an electrical system suffix code such as
ED for Electrical Distribution, within a facility or station. Depending upon the function
of the equipment, the Grouped Facility System suffix Code will be selected.

Superior Function Location

Superior Function Location Description

OM.LEK.00261.ED.

LEKHWAIR PROD STATION ELECTRICAL


DIST

Where:OM Is the Country Location applicable to all PDO Tags


LEK Is the AREA abbreviated code, taken from the LH column in Table 01.
00261 Is the Facility / Station numerical code
ED From Electrical Grouped Facility System suffix codes

Page 36

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC


10.3

Electrical Functional Location Level 4


The Electrical Equipment will generally be identified by the suffix code of G, the only
exception to this will be the battery charger, and this will be given an equipment suffix of
BC.
Superior Function Location

Superior Function Location Description

OM.LEK.00261.ED.G6411

G6411 33KV POWER SUPPLIES, TEMP.SWGR

OM.LEK.00261.ED.BC2501

BC2501 110V BATTERY CHARGER-A

Where:
ED From Electrical Grouped Facility System suffix codes Table 02
G - Electrical Equipment type Suffix code from Table 03.
6411 = Equipment number allocated by the SAP Team, where 64 is location from
SLD & 11 is power rating as per electrical guidelines given below.
Tag Series for General Electrical Equipment is as follows:

10.4

0-9

Distribution Boards (DB)

24V, 220V

e.g. G2401-DB

10 - 19

CB, TX, SB, etc.

132KV

e.g. G2410-CB

20 - 29

CB, TX, SB, etc.

33KV

e.g. G2422-TX

30 - 39

CB, TX, SB, etc.

11KV

e.g. G2435-SB

40 - 49

CB, TX, SB, etc.

6.6KV

e.g. G2443-CB

50 - 99

CB, TX, SB, etc.

415V

e.g. G2456-SB

Electrical Functional Location Level 5


This is the next level down in the hierarchy, where specific equipment associated with
the main equipment (Primary or Superior) is registered in SAP
In the previous example, both the 33KV G6411 and the Battery Charger BC2501 are
the Superior Power supply to Chemical Injection pump with the Tag format of P-2605A
and the a Gas Lift Compressor skid with the Tag format of A-2750, both have electric
drive motors.
This equipment will be registered in SAP under P2605A & A2750 as the Primary
equipment, the hierarchy will be the Superior Function Location of the motors. Tagging
is done according to Equipment Location (Area) and rating, for HV switch rooms A & B
(A1, A2 / B1, B2) is used for left and right switchgear.
Example:
Function Location

Function Location Description

OM.LPS.G6411-TX

G6411 33/11KV, 8MVA P2616A TRANS-TX

OM.LPS.G6411A1-CB

G6411 33KV OUTDOOR CIRC BREAKER-CB

OM.LPS.G6411A1-IS

G6411 33KV LINE ISOLATOR TO P2616A-IS

Where: TX = Suffix for Electrical Equipment Type for Transformer1


CB = Suffix for Electrical Equipment Type for Circuit Breaker
IS = Suffix for Electrical Equipment Type for Isolator
Page 37

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Page 38

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Revision: 5.0
Effective: Dec-09

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

11

Revision: 5.0
Effective: Dec-09

Standard Tag Format for Piping


Refer to Appendix 1 for Code Identification Tables

11.1

Functional Location Hierarchy Level 4


The Function Location is sourced from the As Built PEFS, Piping Data Sheets or the
RBI Piping database. Piping is identified as On Plot, for piping systems inside the
facility and Off Plot, for pipelines external to the facilities or connecting the facilities.
Example:
Superior Function
Location

Sup Function Loc Description

Function Location

OM.LEK.00261.CG-PO

Crude Oil Gathering On Plot Piping

OM.LPS.26908P

OM.LEK.00261.GC-PO

Gas Conditioning On Plot Piping

OM.LPS.27612P

The superior Function Location for Piping is the Country, Area and Facility Systems
codes followed by On Plot or Off Plot code.
OM Is the country location applicable to all PDO Tags
LEK Is the AREA abbreviated code
00216 Is the AREA numerical code
CG Is the process system suffix in which the Tag is located
PO Piping on plot - Piping within the facility

11.2

Piping Functional Location Level 5


Function Location

Function Location Description

OM.LPS.26908P

0.5 Process Line from P1652 to16302

OM.LPS.27612P

18 Process Line from E2761 to V2762

Where:
OM is the country location applicable to all PDO Tags
LPS is the Level 5 facility code, taken form the LH column in Table 1
26 is the facility or station system suffix code
908 Is the Piping serial Number
P Is the code for the Process Service carried by the line.
Descriptions are an important inclusion in supporting the identification of the piping
Function Location. The description should start with the size of the piping in inches,
followed by a description of the pipe run from to.
IMPORTANT NOTE: There are 2 codes for the On Plot piping in the SAP. Facility
Systems use the code OP and description On Plot Piping, while Static Equipment
use the code PO and description, Piping on Plot. There is not requirement to have
an On Plot piping code within the facility systems as the piping within a facility will fall
into one of the production or utility processes. Therefore the Static Equipment code
shall be used.

Page 39

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

12

Revision: 5.0
Effective: Dec-09

Standard Tag Format for Fire and Safety Systems


Refer to Appendix 1 for Code Identification Tables

12.1

Functional Location Hierarchy Level 3


Fire Fighting and Safety Systems will be under the Grouped Facility System suffix code,
FF.

12.2

Superior Function Location

Sup Function Loc Description

OM.LEK.00261.FF

Lekhwair Fire & Safety Components

Functional Location Hierarchy Level 4


The equipment code will identify the specific type of equipment to be found under
Function Location Level 4.
Example:
Superior Function Location

Sup Function Loc Description

OM.LEK.00261.FF-FE

Lekhwair Pump Stn Fire Extinguishers

OM.LEK.00261.FF-FH

Lekhwair Pump Stn Fire Hydrants

OM.LEK.00261.FF-SS

Lekhwair Pump Stn Safety Showers

Where:
FF-FE = Fire Extinguishers
FF-FH = Fire Hydrants
FF-SS = Safety Showers

12.3

Functional Location Hierarchy Level 5


The Function Location will combine the area codes followed by the Tag number given
to the specific location for the equipment, followed by the suffix code of the equipment.
Example:

Page 40

Function Location

Function Loc Description

OM.LPS.CL-0043-FE

FIRE EXT.CO2 4.55KG TELECOM BLDINGFE

OM.LPS.BATL-004-BA

BA SET TROLLEY FIRE STATION


CLASSROOM-BA

OM.LCP.DL-0133-FE

FIRE EXT.DCP 12KG PROD CHEM LAB-FE

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

13

Revision: 5.0
Effective: Dec-09

Telecommunications Equipment
Telecommunications Equipment will include the Public Announcement system which
can comprise base stations / speakers, radio base stations / portable radios,
telephones and Ex equipment associated with telecommunications hardware.
As there is no Facility System suffix identified for telecommunications equipment, this
section will have to be reviewed and completed at a later date.

Page 41

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

14

Revision: 5.0
Effective: Dec-09

Functional Location Non Compliance


Where the format of the Function Location data entries into SAP deviate from the above
guidelines, for whatever reason, a waiver will be required to be presented to SAP
Master Data Management Team with an approved justification.

Page 42

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC

15

Equipment Hierarchy and Required Fields


Refer to Appendix 1 for Code Identification Tables

15.1

Tech Ident No.


UNO if available. If unavailable leave blank.

15.2

Functional Location
NOTE: Level 5 of functional location to be entered.
Functional Location structure is applied, using the combined EP/COMS and EPMARS
hierarchy levels. Code format for the Functional Location Structure Indicator, governs
levels 1 to 4, while the code for level 5 is governed by the Tag Structure indicator. The
hierarchy between these Functional Location levels is established by means of defining
the relevant superior Functional Location relative to another Functional Location.

15.3

Level

Description

Example

Level 1

Complex (=Area)

OM.MAR

Level 2

Grouped Facility (=Location)

OM.MAR.00281

Level 3

Facility (System)

OM.MAR.00281.ED

Level 4

Grouped Tag
Package)

Level 5

Equipment Tag Position (=Maintenance


Tag)

Position

(=Operational

OM.MAR.00281.ED.SA-SS15A
OM.MPD.SA-SS15-TX3

Description
The field holds the description of the Equipment. Enter a meaningful and clear
description of the Equipment. Maximum length of the description is 40 characters.

15.4

Equipment Category
The following SAP Equipment Categories will be set up to allow control over the use of
Equipment for Surface Assets and Sub-Surface Assets. Furthermore a category for
Production Resource Tools will be made available as well as general Tools. Length of
Equipment Category is 1 character.
The boundary between surface and sub-surface assets is taken at the X-tree - flowline
flanges.

15.4.1 Type A
The Equipment Category A will be tailored to allow control over the use of Equipment
for surface equipment.
15.4.2 Type B
The Equipment Category B will be tailored to allow control over the use of Equipment
for sub-surface equipment.

Page 43

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

15.4.3 Type P
The Equipment Category P will be tailored to allow control over the use of Equipment
as Production Resource Tool (PRT) objects.
NOTE: PRT Equipment permit the existence of a technical object on which
maintenance is performed, but which is also required to serve as a tool for the
maintenance of other technical objects. To distinguish between regular Equipment and
PRTs, a special category has been created: Production Resources Tools.
The legacy systems do not appear to hold any data related to PRTs. The category will
be available for the business if they decide to use it.
15.4.4 Type Q
The Equipment Category Q will be tailored to allow control over the use of Equipment
as Tool objects.

15.5

Object Type
The Object Type can both cover Functional Locations as well as Equipment in one
single pull down menu. This could potentially be confusing. For PDO, assignment of
Object Types to Equipment only has been decided as this is seen as to be more useful.
Users are likely to want to search for Equipment of a Specific Type, like PumpCentrifugal or Vessel-Separation, etc. Maximum length of Object Type is 10
characters.
A consolidated list of Object Types for all PDO assets, thus not only ex-EPMARS
(surface facilities), but also estate, telecom, IT, wells, automation & control Equipment
Object Types.
For the facilities ISO 14224 and the Steplib convention could serve as the reference,
using the ISO 14224 Class and Type combination much like NAM did.
A centrifugal pump would then be Object Type PUCE (Class Pump = PU, while Type
Centrifugal = CE), etc.

15.6

Weight
In this field the Weight can be entered. The weight of that Equipment can be used for
load calculations, lifting and transportation purposes. Maximum length of the Weight is
17 characters.

15.7

Unit of Weight
The Units of weight can be selected using the pull down menu. The following standard
units are available: Gram, Kilogram, US Pound, Milligram, Ounce, Tonnes, US Ton. For
PDO we will use the Standard Units of measure. Maximum length of the Weight Unit is
3 characters. KG : Kilogram.

15.8

Size/Dimension
In this field the Size/Dimension can be entered. The Size/Dimension of that Equipment
can be used for lifting and transportation purposes. There is no firm format for
dimensions available in SAP. But the following formats could be used as a standard.
Maximum length of the Size/dimension is 18 characters.

Page 44

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Example:
L200-W120-H300 for an object with a length of 200cm, width of 120cm and a height
of 300cm.
OR
Or for cylindrical objects: D100-H400 for an object with a diameter of 100cm and a
height of 400cm.

15.9

Acquisition Value
In this field the Acquisition Value of the Equipment can be entered.

15.10 Acquisition Date


In this field the Acquisition Date of the Equipment can be entered.
Length of the Acquisition Date is 17 characters in the format dd.mm.yyyy.

15.11 Manufacturer
In this field the Manufacturer can be entered.
Maximum length of the Manufacturer is 30 characters.

15.12 Manufacturer Country


In this field the Manufacturer Country can be selected from a pull down menu.
Length of the Manufacturer Country is 3 characters.

15.13 Model Number


In this field the Model Number can be entered.
Maximum length of Model Number is 20 characters.

15.14 Construction Year


In this field the Construction Year can be entered. The format is yyyy.
Length of the Construction Year is 4 characters.

15.15 Construction Month


In this field the Construction Month can be entered. The format is mm
Length of the Construction Month is 2 characters.

15.16 Manufacturer Part Number


In this field the Manufacturer Part Number can be entered.
Maximum length of Manufacturer part number is 30 characters.

Page 45

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

15.17 Manufacturer Serial Number


In this field the Manufacturer Serial Number can be entered.
Maximum length of the Manufacturer Serial Number is 30 characters.

15.18 Authorization Group


Defines the Authorization Group to create and change Equipment. It is expected that
only a small group of people will create and change Equipment. Equipment data by
nature is rather static. In practice dedicated groups of people will create and maintain
Equipment Records in their expertise area. It is required to fence off Equipment data
that are in the domain of another Authorization Group. Below the Authorization Groups
are given.
Maximum length of the Authorization Group is 4 Characters.
An example of possible Authorization Groups (needs to be established during Role
Mapping):

OM10: Surface Assets (hydro-carbon producing)

OM20: Sub-Surface Assets (hydro-carbon producing)

OM30: Estate Assets

OM40: Telecom Assets

OM50: IT Assets

15.19 Start-up Date


In this field the Start-up Date (Commission-Date) of the Equipment can be entered.
The format is dd.mm.yyyy
The length of the Start-up Date is 8 characters.

15.20 Maintenance Plant


In this field the Maintenance Plant is entered. For PDO there will be only one Work
Management Maintenance Plant, namely OM01. See PR-1032 Maintenance Plan
Creation and Approval Procedure.

15.21 Company Code


The PDO Company code will be OM01. The Company Code will be defaulted in when
OM01 has been entered in the field Maintenance Plant on the Location Tab.

15.22 Asset
The asset field permits a straight link with the FI Asset Accounting (Asset Register). In
this field the Asset code can be entered to link the FN Asset Register with the PM
Equipment. DSM/FN has decided not to populate this field during data load, but will
enter the relevant codes after go-live. The length of the Asset is 12 characters.

Page 46

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

15.23 Sub-number
The sub-asset field permits a straight link with the FI Asset Accounting (Asset Register).
In this field the Sub-Asset code will be entered to link the FN Asset Register with the
PM Equipment. DSM/FN has decided not to populate this field during data load, but will
enter the relevant codes after go-live. The length of Sub-number is 4 characters.

15.24 Catalogue Profile


This field could hold a Catalog Profile, applicable for a Technical Object. This field can
be populated with a so-called Object Part code. Depending on the Object Part (PumpCentrifugal, Pump-Reciprocating, etc.) there will be a different Damage code and
Damage Cause code specific to a certain Object Part.
The Catalog Profile field will be used in the Equipment record to link the Object Part
code. This link will ease completion of PM Notifications raised on Equipment, as the link
to the Object Part code will direct the selection of an appropriate Damage code and
Damage Cause code.
The length of the Catalog Profile is 9 characters.

Page 47

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC

16

Class_FLOC Required Fields


Refer to Appendix 1 for Code Identification Tables

16.1

Class Type
A class type is a top-level unit of control for classes. Each class must be allocated to
exactly one class type. There is no connection between the individual class types.
Class Type 003 stands for Functional Location.

16.2

TechIdentNo.
Level 5 of Functional Location.
Level 5 Equipment Tag Position (=Maintenance Tag)

16.3

OM.MPD.SA-SS15-TX10

Class
F_GENERAL is used for General Functional Location class.

16.4

Characteristic
An attribute related to a Class. A class may have more than one characteristic.
Following are the characteristics for F_GENERAL:-

16.5

FL001

LAST VERIFICATION DATE

FL002

FLUID HANDLED

FL003

EDCC - ENGINEERING DESIGN CODE

FL004

STREAM 1

FL005

STREAM 2

FL006

STREAM 3

FL007

STREAM 4

FL008

STREAM 5

Int.Meas.Unit
Unit in which a numeric characteristic value is entered.

Page 48

FL006

STREAM 3

FL007

STREAM 4

FL008

STREAM 5

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

17

Revision: 5.0
Effective: Dec-09

Class_Equi Required Fields


Refer to Appendix 1 for Code Identification Tables

17.1

Class Type
Uniquely identifies the class type. A class type is a top-level unit of control for classes.
Each class must be allocated to exactly one class type. There is no connection between
the individual class types. Class Type 002 stands for Equipment class.

17.2

TechIdentNo.
Equipment Number can be entered here. E.g. 30000000157

17.3

Class
Class VASB stands for Valve - PSV conventional with bellows. This is used for Relief
valves without bellows.

17.4

Characteristic
An attribute related to a Class. A class may have more than one characteristic. E.g.
EP249 - Inlet size, EP7108 Set Pressure Positive etc. For complete characteristic
refer to Data Loading Form.
Char. Value
Value of the characteristics.
Int.meas.unit
Unit in which a numeric characteristic value is entered.

Page 49

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC

Appendix 1 Code Identification Tables


The following Code Identification Tables should be used carefully for reference and / or
example. The contents and currency of the information may change and may not be reflected in
these forms. If there is uncertainty then the SAP Master Data Management Team shall be
consulted.
Table 1
Grouped Facility (Station) Codes
Level 2
Codes

Grouped

OM.ALG.00101

Facility

Grouped Facility Location Descriptions

Level 5
Codes

Al Ghubar Prod Station and Field Fac

GPS

OM.ALN.00106

Al Noor Interstation Pipelines

ALP

OM.ALN.00107

Al Noor Prod Station and Field Fac

APS

OM.ALN.99974

Items to be written off in Al Noor

WOF

OM.ANZ.00108

ANZAUZ STATION AND FIELD FACILITY

ZPS

OM.ANZ.00493

INTERFIELD PIPE LINES

ZLP

OM.ANZ.99975

ITEMS TO BE WRITTEN OFF IN ANZAUZ

WOF

OM.EXP.00101

Exploration Al Ghubar

EXP

OM.EXP.99976

Items to be written off in Exploration

WOF

OM.FAH.00217

Fahud SW Field Facilities

FAS

OM.FAH.00218

Fahud Supply

FSU

OM.GAS.00247

Barik Gas Gathering Station

GGB

OM.GAS.00248

Power Plant Saih Rawl (CPP-IPS)

GGE

OM.HWL.00710

Dafaq RMS and Field Facility

DAF

OM.HWL.00711

Ghafeer RMS and Field Facility

GFR

OM.LEK.00201

Dhulaima Field Facilities

DHU

OM.LEK.00202

Malaan Field Facilities

LPS

OM.LEK.99979

Items to be written off in Lekhwair

WOF

OM.MAF.00277

Coastal Workshops

TWS

OM.MAF.00278

Marine / Offshore

TOF

OM.YIB.00523

Yibal C Station and Field Facilities

YBC

OM.YIB.00524

Yibal Camp

YCP

OM.YIB.00525

Yibal Camp Infrastructure

YCI

OM.ZAL.00546

ZAULIYAH STATION AND FIELD FACILITY

ZAS

Page 50

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Facility

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC


Table 2
Grouped Facility System Codes
System Codes System Description

System Codes System Description

AR

Area Roads

IR

In camp Residences

BS

MAF Booster Station

IS

Irrigation System & Facilities

BV

Block Valves Stations

IW

Instrumentation workshop

CA

Control and Safeguarding

LB

Prod & Chem Lab Complex

CB

Commercial Buildings

LC

Local Business Centre

CC

Control Centre

LD

Learning & Development Complex

CD

Crude Dehydration

LG

Gas Lift Wells

CE

Crude Evacuation

MP

Mud Mixing Plant

CF

Commercial Facility

MS

Mosques

CG

Crude Gathering

MW

Mechanical workshop

CH

Camp Horticulture

OB

Office Building

CI

Chemical Injection

OE

Oil Exhibition Centre / Planetarium

CJ

Computer Centre

OP

On Plot Piping

CL

Clinic Building

OR

Off Camp Residences

CM

Camp Maintenance Building

OS

Observation Wells

CN

Catering

OW

Oil Wells

CO

Community Aid Roads

PL

Main Pipeline

CP

Compression Facilities

PW

Production workshop

CR

Camp Roads

PY

PDO Yards

CS

Crude stabilisation

RC

Recreation Buildings

CT

Crude Transportation

RE

Recreational Centre

CW

Campaign Workshop

RO

R.O. Plant

CY

Contractor Yard

RS

RAH RC Swimming Pool

ED

Elec. Distribution

RV

RV Workshops

EG

Elec. Generation

SC

Study Centre

EL

Exploration Laboratory

SE

Sewage Treatment Plant

ES

Estate Services Compound

SF

Surface Facilities

ET

Elec. transmission

SG

Safeguarding

EW

Electrical Workshop

SI

Steam Injection

EX

Exploration Wells

SN

Suspended Wells

F8

Main intake station

ST

Station Tags

FA

Farm

SU

Supply Buildings

*FF

Fire and Safety Compound

SW

SEEB Water Injection Wells

FG

Fuel Gas

TB

Terminal Buildings Area

Page 51

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Grouped Facility System Codes


System Codes System Description

System Codes System Description

FL

Flow Lines

TE

Telecom Buildings

FR

Flare Systems

TF

Tank Farm

*FS

Fire & Safety Systems

TH

Mukheizna Steam Trial Plant

GB

Gas Building

UK

Location unknown North of Oman

GC

Gas Conditioning

UT

Utilities

GE

Gas Evacuation

VW

Vehicle Workshop

GF

Fuel Gas

WC

Combined Workshops

GI

Gas Injection

WD

Water Disposal

GL

Gas Lift Facility

WF

Water Facilities

GP

Gas Processing

WI

Water Injection Wells

GS

Gas Injection Facilities

WJ

Water Injection Facility

GT

Dry Gas Transport

WL

Wells

GW

Gas Wells

WM

Water Monitoring

IA

Instrument Air System

WO

Write Off Items

IB

Industrial Buildings

WS

Water Supply Facilities

IE

Industrial Estates

Table 3
Equipment Type Function Codes
Code Letter

Code Letter Description

Code Letter

Code Letter Description

Packaged Units

Mixers, Stirrers, Mixing Nozzles etc

Buildings

Pumps (all types)

Columns, Contactors

Quality Measurement devices

Drying Equipment

Pig Receivers

Heat Exchangers

Filters,

Fired Heat Exchangers, Boilers, etc

Storage Tanks

General Electrical Equipment

Vessels, Pressure Vessels, silos, hoppers

Compressor

Material Handling Equipment

Pig Launchers

BC

Battery Charger

Page 52

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Table 4
Equipment Suffix List for Mechanical & Rotating Equipment
Equip Type

Description

Equip Type

Description

HA2

Driven Unit

TG2

Power Turbine

KC

Centrifugal comp

TG3

Auxiliary Drive

KC1

Centrifugal Comp 1st Stg

TG4

Lube Oil System

KC2

Centrifugal Comp 2nd Stg

TG5

Air Inlet System

KC3

Centrifugal Comp 3rd Stg

TG6

Exhaust System

KC4

Centrifugal Compressor 4th


Stg

TG8

Starting Means

KC5

KC Seal Oil/Lube Oil System

WB

Weighbridge

KR

Reciprocating compressor

WH

Wellhead

KS

Screw compressor

WH1

PTS line

LH

Launch

AC

Portable Air Compressor Skid

LI

Air Balance Unit (Liner)

AC1

Driver

MG

Manifold

AC2

Driven Unit

MX

Mixer / Macerator / Agitator

BF

Blower/fan

PA

Diaphragm pump

BM

Mooring Buoy

PB

Beam pump

CF

Centrifuge

PF

Centrifugal pump

CI

Chemical Injection Skid

PG

Gearwheel pump

CI3

Pumping unit - air driven

PI

Air Balance Unit (Piston)

CI4

Pumping unit - motor driven

PP

Plunger pump

DW

Drwwks/Der'k/Winch/Hoist/Boom

PR

Rotary pump

ED

Diesel engine

PS

Screw pump

EG

Gas engine

SA

Breathing Air Compressor Skid

EP

Petrol Engine

SA1

SA - Driver

FS

Foam System

SA2

SA - Driven Unit

GB

Gearbox

SK

Sea Skimmer

GM

General Tag (Mechanical)

SL

Screw Lift

HA1

Driver

TE

Turbo expander/Compressor

WH2

Well Hydraulic Control Panel

TG

Gas turbine

WH3

SCSSSV

TG1

Gas Producer

WH4

Panel Operated SSV

HA

Hydraulic Actuator Skid (M/L)

OP

BOP Stack

RO

Containerised Plant

WH5

Flow line Safety Valve

Page 53

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC


Table 5
Equipment Suffix List for Static Equipment
Equip
Type

Description

Equip
Type

Description

AC6

Receiver

IP

Interfield Pipelines

AR

Aerator

OB

Office Buildings

BR

Flare

LA

Loading arm

BV

Block Valve

LE

Lifting equipment

CI1

Storage tank

LS

Scraper launcher

CI2

Day Tank

OT

Oil Treatment Unit

CO

Column / Tower / Contactor

PD

Pulsation damper

DG

Gas scrubber

PO

Piping - On plot

DR

Dryer

RA

Air receiver

FA

Flame Arrestor

RS

Scraper receiver

FL

Filter

RV

Relief valve

FN

Gas/Oil/Water Flow lines

SA3

SA - Accumulator

FU

Furnace/heater

SR

Separator

GS

Steam generator

TK

Tank

HD

Header

TP

Tank Pit

HE

Heat exchanger

VE

Vessel

KO

Knock out vessel

WS

Water softener

IB

Industrial Buildings

Table 6
Cranes
CODE

TYPE DESCRIPTION

CODE

TYPE DESCRIPTION

CPJ

Crane Pedestal Jib

CTL

Crane Truck Loading

CFPJ

Crane Free Standing

CART

Crane Articulating

CPOJ

Crane Portable Jib

CSBP

Crane Side Boom Pipelayers

CPOT

Crane Powered Overhead


Travelling

CPSJ

Crane Pillar Swing

CWSJ

Crane Wall Mounted Swing Jib

CMOT

Crane Manual Overhead Travelling

CCA

Crane Cantilever

CMOTS

Crane Manual Overhead Travelling


Structure

CFG

Crane Fixed Gantry

CTL

Crane Truck Loading

CPG

Crane Portable Gantry

CART

Crane Articulating

CCL

Crane Crawler Mounted Lattice

CSBP

Crane Side Boom Pipe layers

CCT

Crane Crawler Mounted


Telescopic

CPOT

Crane Powered Overhead


Travelling

CCML

Crane Carrier Mounted Lattice

CMOT

Crane Manual Overhead Travelling

Page 54

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC


Cranes
CODE

TYPE DESCRIPTION

CODE

TYPE DESCRIPTION

CCMT

Crane Carrier Mounted


Telescopic

CMOTS

Crane Manual Overhead Travelling


Structure

CRT

Crane Rough Terrain

EOT

Electric Overhead Travelling Crane

Table 7
Lifting Appliances
CODE

TYPE DESCRIPTION

CODE

TYPE DESCRIPTION

CBL

Chain Block

JME

Jack Mechanical

RLB

Ratchet Lever Block

TIR

Tirfor

SBL

Sheave Block

WPO

Winch Powered

SNB

Snatch Block

WMA

Winch Manual

TRO

Trolley

WMR

Winch Man Riding

JHY

Jack Hydraulic

MOR

Monorails

JPN

Jack Pneumatic

RUB

Runway Beams

PTB

Personnel Transfer Basket

PAD

Pad eyes

LFR

Lifting Frame

LBM

Lifting Beam

SPB

Spreader Beam

LEQ
LB

Lifted Equipment (containers


baskets) etc.)
Runway Beam

Table 8
Mechanical Handling Equipment
CODE

TYPE DESCRIPTION

CODE

TYPE DESCRIPTION

ECP

Excavator Crawler Powered

THP

Telescopic Handler Powered

EWP

Excavator Wheeled Powered

FLA

Fork Lift truck Attachment

ESCP

Excavator/loading Shovel
Combined Powered
Loading Shovel Powered

PTM

Pallet Truck Manual

STM

Stacking Truck Manual

TLP

Tail Lift Powered

LSP

SLP

Skip Loader Powered

FLM

Piling Rig Excavator mounted


Powered
Fork Lift truck Counter balanced
Powered
Fork Lift truck Manual

MVLP

FLRP

Fork Lift truck Reach Powered

MEWPP

FLRTP

Fork Lift truck Rough Terrain


Powered
Fork Lift truck Side loading
Powered

MEWP

Motor Vehicle Lifting device


Powered
Mobile Elevated Working Platform
Powered
Mobile Elevated Working Platform

PREP
FLCP

FLSP

Table 9
Lifts
CODE

TYPE DESCRIPTION

CODE

TYPE DESCRIPTION

PAL

Passenger Lifts

GOL

Goods Lifts

Page 55

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC


Table 10
Instrument Equipment Type Suffix
Type

Description

Type

Description

ACT

Actuator

MP

Metering prover

ANP

Analyzer Probe

MV

Multi port selector valve

AP

Accelerometer Probe

OC

Net oil computer

AQ

Analyser

ORI

Orifice

BGU

Break Glass unit

PAN

Panel

ADT

Acoustic Detector

PBT

Push button

BOX

Box

PDM

Positive Displacement Meter

BSW

BSW meter

PLC

PLC

CAB

Cabinet

PP

Proximity Probe

CC

Control Centre

PSF

Process sensor Flow

CCR

Central control room

PSL

Process sensor Level

COMP

Computer

PSP

Process sensor Pressure

CON

Controller

PST

Process sensor Temperature

COR

Corriolis flow meter

PSW

Pressure switch

CS

Control System

PT

Pressure Transmitter

CV

Control valve

PX

Horn/Loud Speaker

DB

Distribution Board

PY

Beacon

DCS

DCS system

QM

Quality Monitor

DT

Density Meter

QMMP

Quality Monitor Meter Prover

FDT

Flame detector

RC

Rod Pump controller

FG

Facility Equip/Fire & Gas

REC

Recorder

FLDT

Flow Detector

RL

Relay

FPC

Field PAC Controller

RT

RTU

FSW

Flow switch

SC

Single Well Safety Cabinet

FT

Flow transmitter

SDT

Smoke Detector

GAN

General Analyzer

SL

Sonic Leak Gas Detector

GBS

Limit Switch

SOV

Solenoid valve

GDT

Gas detector

SQ

SCADA Equipment

GF

Vessel

SPD

Speed related

GI

General Instrument Tag

SRV

Self Regulating valve

HDT

Heat detector

SW

Switch

JB

Junction Box

TR

Transducer

LG

Level Guage

TSW

Temperature switch

LP

Logic Relay Panel

TT

Temperature Transmitter

LSW

Level switch

TUR

Turbine Flow meter

LT

Level Transmitter

UDT

UV detector

MAG

Magnetic flow meter

UT

Ultrasonic Flow Transmitter

MAS

Mass flow meter

VA

Valve

Page 56

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC


Instrument Equipment Type Suffix
Type

Description

Type

Description

MIS

Misc.

VI

Vibration

MON

Monitor

VOR

Vortex flow meter

MOV

Motor Operated valve

VSW

Vibration switch

MR

Metering

XL

Emergency Shutdown Valve (ESD)

OA

Multiphase metering skid

OANA

Oxygen Analyzer

Table 11
SAP Suffix for Electrical Equipment Type
Equip
Type

Description

Equip
Type

Description

Equip
Type

Description

PAN

Panel Teleprotection

ER

Electrical Starting
Reactor

RP

Electrical protection

PQ

Gas/Oil Main Pipelines

ES

Electrical System

RP1

Motor Protector

EX

Certified equipment

GE

Electric generator

SB

Switchboard

BS

Bus section

GL

General Tag (Electrical)

SP

Solar Panel

CB

Circuit breaker

IS

Isolator

SQ

SCADA Equipment

CC

Control panel

IW

Package air conditioner

TC

Cathodic Prot
Transformer

CI5

Pumping unit driver

LU

Lighting Unit

TG7

Electrical System

CT

Current transformer

ME

Electric motor

TX

Transformer

DB

Distribution board

OH

Overhead lines

VT

Capacitor voltage
transformer

EC

ESP Control Panel

PE

Electric Submersible
Pump

YD

Switchyard

EQ

Electrical Equipment

JB

Junction Box

Table 12
Table 12 Fire & Safety Components Suffix Codes
CODE

DESCRIPTION

CODE

DESCRIPTION

FE

Fire Extinguisher

FB

Fire Box

FH

Fire Hydrants

SS

Safety Shower

FM

Fire Monitors

BA

Breathing Apparatus

SP

Sprinkler System

FT

Fire Truck

DL

Deluge

GS

Gaseous Fire Protection

HR

Hose Reels

Page 57

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Appendix 2 - SAP Master Data Management Team Templates


The following Data Loading Templates should be used with the Section 2 of this procedure. If in
doubt then consult the SAP Master Data Management Team for guidance.

Data Loading
Templates

Page 58

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 5.0
Effective: Dec-09

Appendix 3 Abbreviations
AFC

Approved for Construction

BOM

Bill of Materials

C&A

Control and Automation

CDFH

Corporate Discipline Function Head

CDFP

Corporate Discipline Focal Point

CMF

Corporate Management Framework

CMMS

Computer Maintenance Management System

CRTE

Created

DLFL

Deletion Flag

DLT

Deleted

ESD

Emergency Shutdown System

FLOC

Function Location

INAK

Inactive

IPF

Instrumented Protection Function

MAT

Maintenance Activity Type

PEFS

Process and Engineering Flow Schematic

RRM

Risk and Reliability Management

SAP

Systems, Applications and Products

SCE

Safety Critical Elements

SLD

Single Line Diagrams

SOV

Solenoid Operated Valve

TA

Technical Authority

WBS

Work Breakdown Structure

Page 59

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC

Project Design Scope

Initiate Data entry process - Filling in of Master Data


Loading Forms, Provide PEFS, Vendors details etc.

Data
Supp
.
s /A
rea M
nt En
g'rs.
Area
Asse
t Hold
er
END

aster

CDF
P

MM
SAP
P

No Activity Description

Area
P

roj. /
F

lowlin
e

Eng'r

Appendix 4 Responsibilities Flow Chart

Master Data Loading in SAP

Initiation of Standard Text, TaskList and Maintenance Plans.

Loading Standard Text, TaskList and Maintenance Plans.

Plan and Scheduling Maintenance Plans for new


Equipment.

Audit data availability and quality and feedback noncompliance to asset holder.

Maintain accuracy of asset and activity data through out


equip. lifetime. Re-initiate data entry process as required

End of Process

Page 60

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 5.0
Effective: Dec-09

Petroleum Development Oman LLC

Appendix 5 - User Feedback Page


PR-1344 Asset and Activity Registration and Deletion in SAP User
Feedback Page
Any user who identifies an inaccuracy, error or ambiguity is requested to notify
the custodian so that appropriate action can be taken. The user is requested
to return this page fully completed, indicating precisely the amendment(s)
recommended.
Name:
Ref ID

Page Ref:

Date:

Brief Description of Change Required and Reasons

UOM3
Custodian of Document

Page 61

Date:

PR-1344 - Asset and Activity Registration and Deletion in


SAP

Printed 16/12/09

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Scope of work for CMMS and CCMS

APPENDIX II
Selection of Safety Critical Elements (SCE) and Development of Performance Stds (PS) & PS
Assurance Tasks

Doc. No: ZAU-84-104810 -VA-6793-20001-0000

APPENDIX-II

REVISION: 02
Date: 03.06.2013

Scope of work for CMMS and CCMS

APPENDIX III
ENGINEERING AND OPERATIONS PROCEDURE FOR Z6 NOTIFICATION

Doc. No: ZAU-84-104810 -VA-6793-20001-0000

APPENDIX-III

REVISION: 02
Date: 03.06.2013

UNRESTRICTED
Jan-10

Document ID: PR-1528


Filing Key: Business Control

Petroleum Development Oman L.L.C.

Engineering and Operations


Procedure for Z6 Notification

User Note:
The requirements of this document are mandatory. Non-compliance shall only be authorised by
the Document Owner or his Delegate through STEP-OUT approval.
A controlled copy of the current version of this document is on PDO's EDMS. Before making
reference to this document, it is the user's responsibility to ensure that any hard copy, or
electronic copy, is current. For assistance, contact the Document Custodian or the Document
Controller.
Users are encouraged to participate in the ongoing improvement of this document by providing
constructive feedback.

Please familiarise yourself with the


Document Security Classification Definitions
They apply to this Document!

This document is the property of Petroleum Development Oman, LLC. Neither the whole nor any part of
this document may be disclosed to others or reproduced, stored in a retrieval system, or transmitted in any
form by any means (electronic, mechanical, reprographic recording or otherwise) without prior written
consent of the owner.

Petroleum Development Oman LLC

Revision: 3.0
Effective:Jan-10

This page was intentionally left blank

Page 2

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 3.0
Effective:Jan-10

Document Authorisation

Authorised For Issue January 2010

Page 3

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 3.0
Effective:Jan-10

Petroleum Development Oman LLC

ii Revision History
The following is a brief summary of the 4 most recent revisions to this document. Details of all
revisions prior to these are held on file by the issuing department.

Revision
No.

Date

Author

Scope / Remarks

3.0

Sep-09

Robin Norman UOP6

Complete review and update. Process flow


revamped and new screen dumps added.

2.0

Dec.05

UOM/321

Procedure reviewed due to improved


process work-flow and validated with extra
related business control documents.

1.0

Feb.03

TTO/32

Initial

iii Related Business Processes


Code
EP.71.02

Business Process (EPBM 4.0)


Operate Wells and Facilities

iv Related Corporate Management Frame Work (CMF)


Documents
The related CMF Documents can be retrieved from the CMF Business Control Portal.
CP-114

Maintenance and Integrity Management CoP

PR-1001e

Operations Procedure Temporary Variance

PR-1032

CMMS (SAP) - Maintenance Plans Creation & Approval Procedure

PR-1164

Fixed Asset Abandonment Procedure

PR-1344

EMMS Asset and Activity Registration and Deletion Procedure

PR-1419

Abandonment and Restoration Procedure

Page 4

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 3.0
Effective:Jan-10

TABLE OF CONTENTS
1

Introduction ............................................................................................................................ 6
1.1

Background ...................................................................................................................... 6

1.2

Purpose ............................................................................................................................ 6

1.3

Scope ............................................................................................................................... 6

1.4

Distribution / Target Audience .......................................................................................... 6

1.5

Review and Improvement ................................................................................................ 6

1.6

Step-Out and Approval..................................................................................................... 6

Roles and Responsibilities ..................................................................................................... 7

Z6 Notification Processes ...................................................................................................... 8


3.1

Scope ............................................................................................................................... 8

3.2

Overall Process ................................................................................................................ 9

Figure 1 Z6 Notification Process (Simplified) ......................................................................... 9


3.3

Creating New SAP-PM Master Data Record ................................................................. 11

3.4

Updating SAP-PM Master Data Record Equipment Movement ................................. 14

3.5

Updating SAP-PM Master Data Record Redundancy / Write-off of Equipment ......... 15

3.6

Creation of New, or Change to Existing Maintenance Plans ......................................... 15

3.6.1

Creation of a Maintenance Plan for New Equipment .............................................. 16

3.6.2

Rescheduling of Maintenance Plan ......................................................................... 16

3.6.3

Adding or Removing Maintenance Packages when Strategy Changes.................. 17

3.6.4

Suspension of Maintenance Plan ............................................................................ 17

3.6.5

Activating a Suspended Maintenance Plan ............................................................. 17

3.6.6

Additions and / or Deletions from the Task List ....................................................... 17

3.7
4

Cancelling and Deleting a Z6 Notification ...................................................................... 18

Monitoring and Compliance ................................................................................................. 21


4.1

Key Performance Monitoring (KPIs) .............................................................................. 21

4.2

Compliance .................................................................................................................... 21

Appendix 1 SAP-PM Master Data Codes and Work Centres .................................................. 22


Appendix 2 Data Entry Templates ........................................................................................... 24
Appendix 2 Abbreviations ........................................................................................................ 25
Appendix 3 - User Feedback Page ............................................................................................. 26

Tables and Figures


Figure 1 Z6 Notification Process (Simplified) ............................................................................. 9

Page 5

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Introduction

1.1

Background

Revision: 3.0
Effective:Jan-10

The Asset Register Is a complete and detailed overview of all physical (tangible) assets
that are fully or partially owned by PDO and that represent value and/or have related
costs. The Asset Register is held in SAP-PM.
For new builds and modifications the register is compiled and handed over as one of
the key deliverables. Throughout the life of the asset changes are recorded to the
register. With regard to Plant Maintenance the Asset Register shall contain SAP-PM
Master Data on all equipment installed within the asset.
The Z6 Notification is used to record requests made to update SAP-PM Master Data i.e.
creation of new SAP-PM Master Data (e.g. Asset registration for new projects), or
change to existing SAP Master Data (e.g. Equipment Movement from one location to
other, change of Maintenance Plan, etc.), or correction of errors in the Master Data
The Z6 Notification shall also provide the necessary audit trail required to demonstrate
Asset Integrity.

1.2

Purpose
The purpose of the procedure is to ensure that changes to SAP-PM Master Data are
carried out correctly and in accordance with SAP requirements.

1.3

Scope
This procedure shall cover corrections and additions to SAP-PM Master Data that are
eligible using the Z6 Notification process.

1.4

Distribution / Target Audience


The procedure is intended to be referenced and used by Field Operations and
Maintenance Teams, Work Schedulers, Asset Planners, Corporate Discipline Focal
Points and Project Managers. It should also be made available as a source of reference
to Engineering and Maintenance Contractors (EMC), and Offplot Development
Contractors (ODC).

1.5

Review and Improvement


This document shall be subject to review by the Document Owner / Document
Custodian every 3 years from the last date of issue.
At any time during this period the document Users may request the contents to be
reviewed and revised. Requests for review and revision shall be made in writing to the
Document Custodian using the User Feedback Page or by sending a Marked Up
copy of the document. The decision to review or revise the document shall rest with the
Functional Maintenance & Integrity Manager (UOM), the Owner.

1.6

Step-Out and Approval


This Document is Mandatory. Step-Out shall be in accordance with PR-1001e
Operations Procedure Temporary Variance.

Page 6

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 3.0
Effective:Jan-10

Petroleum Development Oman LLC

Roles and Responsibilities


The following table lists the Roles and Responsibilities for the Key Personnel.
Role

Responsibility

Initiator Any PDO /


Contractor personnel
with Access to SAP-PM

Initial Reviewer Tech.


Reliability / Integrity
Engineer, Asset Owner,
Maintenance
Engineers, Support /
Project Engineers /
Flowline Engineers

Approver Corporate
Discipline Focal Point
(refer to Appendix 1
Work Centres Codes
for CDFPs)

Data Input to SAP-PM Head SAP-PM Master


Data Management

Page 7

Raises the Z6 Notification and shall:


-

provide clear long text description of actual Master


Data

change required (with attachments as required)

- assign correct work centre identification

- use correct standard codes to categorise type of


Master Data being changed

Reviews the Z6 Notification in accordance with SAP


Master Data requirements

Provides any additional information as required for the


relevant information

Provide advice on Maintenance Plan data as required


when creating new equipment entries

Provide Maintenance Plan start date and frequency


required

Forwards Z6 Notification to CDFP for approval

Reject (cancel) Z6 Notification if not valid

Review details of the Z6 Notification in accordance with


SAP Master Data requirements

Assess the impact or risk of the proposed data changes

Make recommendation where applicable to standardise or


extend Z6 Notification changes throughout all PDO Assets

Reject the Z6 Notification if not justifies

Approve implementation of the notification

Review the Master data records once implemented in SAPPM

Close out Z6 Notification request

Correct as required Master Data standard codes if


incorrectly categorised by initiator

Apply the approved changes to SAP-PM Master Data

Refer and request any additional or missing information


from CDFP, Reviewers, and / or Initiator as required to
apply changes to SAP-PM Master Data

Request close out from CDFP when all updating has been
completed

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Z6 Notification Processes

3.1

Scope

Revision: 3.0
Effective:Jan-10

The procedure shall address the following Z6 Notification processes:

Creating New SAP-PM Master Data (Assets and Facilities)

Movement of equipment to different or between location

Redundancy / Write-off of equipment (Planned Maintenance routines only)

Creation of New, or Change to existing Maintenance Plans

Cancelling and Deleting a Z6 Notification

The remainder of this page Intentionally Left Blank

Page 8

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


3.2

Revision: 3.0
Effective:Jan-10

Overall Process

Figure 1 Z6 Notification Process (Simplified)


Page 9

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 3.0
Effective:Jan-10

The overall Z6 Notification process is illustrated in Figure 1. Definitions of User Status


can be referenced in Appendix *.
The Z6 Notification is raised in the Work Centre (refer to Appendix ) for the CDFP who
shall be responsible for Approval.
1.

Initiator (any person with SAP-PM access) raises the Z6 Notification in the
respective Work Centre and enters the required data
USER Status INIT

2.

Reviewer changes user status


USER Status INIT NVST

3.

Tech. Reliability / Integrity Engineer, Asset Owner, RV Workshop and


Maintenance Engineer searches SAP-PM for Z6 Notification (in respective
Work Centre) for INIT
Provide additional data as required.
Request more data from Initiator if required. Changes User Status to
INIT.NVST. Initiator shall provide required data
Decision made to Process or Cancel

4.

Tech. Reliability / Integrity Engineer or Asset Owner changes user status


USER Status AWAP

5.

CDFP searches SAP-PM for Z6 Notification (in respective Work Centre)


for AWAP
Decides if data is sufficient.
If insufficient, adds comments and changes User Status to AWAP NVST.
Tech. Reliability / Integrity Engineer or Asset Owner to provide required
data
Decision made to Process or Cancel

6.

CDFP changes user status


USER Status APPR

7.

SAP-PM Master Data Management Team searches SAP-PM for Z6


Notification (in respective Work Centre) for APPR
Decides if data is sufficient.
If insufficient, adds comments and changes User Status to APPR NVST.
Initiator, Reviewer (Tech. Reliability / Integrity Engineer, Asset Owner, RV
Workshop and Maintenance Engineer), or CDFP shall provide required
data OR Cancels the process
If data sufficient SAP-PM Master Data Management Team update SAPPM Master Data
USER Status APPR

8.

SAP-PM Master Data Management Team changes user status


USER Status TBCO

Page 10

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 3.0
Effective:Jan-10

CDFP searches SAP-PM for Z6 Notification (in respective Work Centre)


for TBCO

9.

Decision made on the accuracy / quality of Data


If data is not correct the CDFP will revise notification, add feedback
comments and change User Status to TBCO NVST. SAP-PM Master Data
Management Team to correct data as required
If the data is correct the CDFP shall change User Status to CLSD
Process end. Z6 Notification Closed-Out

10.

USER Status CLSD


IMPORTANT NOTES:
1. The cancellation and deletion of Z6 Notifications shall be addressed in Section 3.*
2. Approving and completion of Z6 Notification must be through put in process using
flags i.e. Green Flag = Approval and Black & White Flag = Closure

3.3

Creating New SAP-PM Master Data Record


NOTE:
New equipment procured on a project would be actioned via the Z6 Notification
process by the Project Team and then handed over to Operations as part of the
Asset Register / SAP-PM Master Data (project deliverable).
New equipment procured as the result of a Field Change Proposal (refer to PR1001a Field Change Proposal) and will be actioned via the Z6 Notification process
by the FCP Team.

Page 11

1.

The Initiator shall raise a new Z6 Notification using Transaction Code IW21

2.

Provide a title for the Notification (Mandatory)


PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 3.0
Effective:Jan-10

3.

Enter Planner group and Main WorkCtr (Mandatory)

4.

Enter Functional Location or a minimum the superior FLOC e.g. OM.FAH

5.

Enter information in Subject Field field (Mandatory)

NOTE: Information here must be as detailed as possible or shall be supplemented by


attachment(s)
6.

Enter the Task Codes (Mandatory)

NOTE: Task Text is optional.

Page 12

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


7.

Revision: 3.0
Effective:Jan-10

Enter Priority and Required End date / time

NOTES:
Amendments to Z6 Notifications should be through transaction codes IW22
(individual) or / and IW28 (Selection of Notifications).
To display the list of notifications use transaction code IW29 and for individual
notification use IW23.
8.

Set User Status to 15 AWAP Awaiting Approval

9.

Notification can be sent to the Tech. Reliability / Integrity Engineer, Asset


Owner, RV Workshop, Maint. Eng., Flowline Eng. that the Z6 requires to be
reviewed and sent for Approval by the CDFP. The action of Master Data entry
shall be carried out by the Master Data Management Team as detailed in
Section 3.2 Overall Process.

Page 13

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


3.4

Revision: 3.0
Effective:Jan-10

Updating SAP-PM Master Data Record Equipment Movement


All Equipment movements shall be accompanied by the creation of a Z6 Notification to
ensure that the change in location data is captured in SAP-PM Master Data.
The creation and processing of the Z6 shall be as detailed in 3.2 .
The key responsibilities shall be for personnel authorising movement of equipment(s)
either to replace an existing item, or as a new installation to ensure that all SAP-PM
Master Data records updated.
The initiator shall provide all information required for SAP-PM Master Data similar to
that shown in the following illustration.
The completed Z6 shall be:

reviewed by the Tech. Reliability / Integrity Engineer, Asset Owner, RV


Workshop, Maint. Eng., Flowline Eng.;

NOTE: RV movement and / or new RV entries to be reviewed by RV personnel.

Page 14

approved by the CDFPMMS

actioned by the SAP-PM Master Data Team; and

closed out by the CDFPMMS

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


3.5

Revision: 3.0
Effective:Jan-10

Updating SAP-PM Master Data Record Redundancy / Write-off of


Equipment
Equipment Abandonment, Redundancy or Write-Off shall be undertaken in accordance
with the following procedures:
PR-1164 - Fixed Asset Abandonment Procedure
PR-1419 Abandonment and Restoration
SAP-PM Master Data changes that result should be managed through Z6 Notification.
Function teams and individuals who have the authority to authorise abandonment /
redundancy or write-off of equipment shall ensure that this requirement is adhered to.
The long text shall clearly state:

The Equipment No. of the item being moved;

The original FLOC, and the destination FLOC to which it will be moved to e.g.
Write-off yards.

Function Location list of all associated equipment being moved (maybe added
as an attachment if large)

Task codes i.e.

If Equipment is redundant and can be re-used and requires to be moved to another


location then Section 3.4 shall be referenced.
Equipment that has been made redundant or is no longer uses (bypassed) shall be
temporarily De-Activated with the system status code INAK allocated by the SAP-PM
Master Data Management Team. Should the equipment be isolated and chemically
preserved (mothballed) the system status code MOTH allocated.
A decision to write-off the equipment shall require a completed Write Off Form signed
and approved. The SAP-PM Master Data Management Team to change the system
status code to INAK. After removing the Asset from PDO the Master Data Management
Team change the status code to INAK DLFL and change the Location Code from
MUSWOF to OM000 (dedicated location in SAP for written off assets).
NOTE: It is the responsibility SAP-PM Data Management Team to inform Asset
Accounting Team on all asset redundancy requests completed via Z6, only after
obtaining approval to remove the Asset from PM data.

3.6

Creation of New, or Change to Existing Maintenance Plans


The creation and processing of the Z6 shall be as detailed in 3.2.
The responsibility for creating, changing and quality checking Maintenance Plans shall
be the Asset Owners, but shall in the most part a collaborative exercise between the
former and the Maintenance Supervisor, Tech. Reliability / Integrity Engineer, Area
Planner, Work Scheduler and CDFPs.

Page 15

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 3.0
Effective:Jan-10

Preventative / Recurring Maintenance Activities i.e. scheduled-dates, task-lists, and


maintenance periodicity, are considered as being SAP Master Data and shall be
processed using the Z6 Notification Process. This includes:

Creating new maintenance plans or change / altering start dates of existing


maintenance plans

Rescheduling of maintenance plans to align with current or intended planning


and execution schedules

Suspending maintenance plans when equipment is removed from service,


abandoned, scrapped or mothballed.

Activating / restarting previously suspended maintenance plans

Adding or removing maintenance plans to match changes in Maintenance


Strategy

Additions and deletions to / from the content of existing Maintenance Plans i.e.
activities, materials, services, standard text etc.

NOTE: Weekly services are scheduled on different plans from monthly and yearly
services, and it may be necessary for changes to be made to two Maintenance Plans
for a single Functional Location (FLOC).
3.6.1

Creation of a Maintenance Plan for New Equipment


The Maintenance Plan and the subsequent Task List shall be developed in accordance
with PR-1032 - CMMS (SAP) - Maintenance Plans Creation & Approval Procedure. The
information from the Maintenance Plan and Task List shall be entered onto Excel
spreadsheets (refer to Appendix 2).
Checking for required information / accuracy and approval will be the responsibility of
the CDFPs with input from the respective Tech. Reliability / Integrity Engineer as
required.
NOTE: Where the required information is available on SAP-PM i.e. like for like or
similar, this can be copied and pasted. Information that is not available on SAP-PM
shall require to be generated. This shall be carried out by the Tech. Reliability / Integrity
Team and CFDHs.
The initiator shall raise a Z6 Notification as detailed in Section 3.2 ensuring that all
required information is entered in the Subject Description. The Task Code will be
N060 - New Recurring Activity Item / Plan. The appropriate Excel Spreadsheets shall
accompany the Z6 Notification and be forwarded to the UOM3 Team for data entry.

3.6.2

Rescheduling of Maintenance Plan


Maintenance plans may require to be rescheduled when they do not align with the
Integrate Maintenance Activity Plans or if a change in maintenance frequency is
required.
The SAP-PM system requires a single date in order to start / execute a Maintenance
plan or to change the due dates for a Maintenance Plan.
The changes to the scheduling of the Maintenance Plan will be reviewed by the Tech.
Reliability / Integrity Engineer and approved by the respective CDFPs. Once approved
the Z6 Notification shall be raised to action the changes.
The initiator shall raise a Z6 Notification as detailed in Section 3.2 ensuring that the
Maintenance Plan number and next due date are entered in the Subject Description.
The Task Code will be C080 Change Recurring Activity Schedule. The Z6 Notification
and be forwarded to the UOM3 Team for action.

Page 16

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 3.0
Effective:Jan-10

Petroleum Development Oman LLC


3.6.3

Adding or Removing Maintenance Packages when Strategy Changes


The Maintenance Package is the time lengths assigned to a Maintenance Strategy.
For example the strategy OM01 PDO-Time-Weekly has got packages of 1, 2, 3, and 8
weeks. The Maintenance Package determines the frequency of maintenance
undertaken.
The changes to the Maintenance Package required when the strategy changes will be
reviewed by the Tech. Reliability / Integrity Engineer and approved by the respective
CDFPs. Once approved the Z6 Notification shall be raised to action the changes.
The initiator shall raise a Z6 Notification as detailed in Section 3.2 ensuring that the
Maintenance Plan number, Task List Group and Group Counter are entered in the
Subject Description. The Task Code will be C070 Change Recurring Activity
Strategy / Package. The Z6 Notification and be forwarded to the UOM3 Team for
action.
NOTE: The Task List shall be revised if a suitable Group or Group Counter are
unavailable in SAP-PM. The Excel spreadsheet detailed in Appendix 3 will be
populated for this requirement and attached to the Z6.

3.6.4

Suspension of Maintenance Plan


A Z6 Notification is required to be raised when equipment is removed from service,
abandoned, scrapped or mothballed. Live Work Orders in the system shall also require
to be removed by the Asset Owner (Maintenance).
The process detailed in Section 3.2 shall be adhered. Data required to be added to the
Z6 will be:

3.6.5

Maintenance plan number to be de-activated.

Equipment number and / or FLOC in the case of redundant, by-passed or


written-off equipment.

Activating a Suspended Maintenance Plan


A Z6 Notification is required to be raised when equipment suspended from service is
reinstated.
The process detailed in Section 3.2 shall be adhered. Data required to be added to the
Z6 will be:

3.6.6

Maintenance Plan number to be re-activated.

The next due date and frequency from where the Maintenance Plan shall be
commenced.

Additions and / or Deletions from the Task List


Changes, additions or deletions, to the Task Lists will only be made after approval has
been obtained from the discipline CDFP using the Z6 Notification process. Task Code
C050.
In most cases the existing Task List can be copied and edited to indicate the required
additions and / or deletions. The amended Task List shall be forwarded with the Z6
Notification to the discipline CDFPs for approval and then the Master Data
Management Team for action.

Page 17

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC


3.7

Revision: 3.0
Effective:Jan-10

Cancelling and Deleting a Z6 Notification


The following procedure shall be followed to cancel and delete a Z6 Notification.
1.

Enter Transaction IW22 to change / amend Z6 Notification

2.
Set CNCL Status by clicking either the status detail button
status click back button)

flag (to cancel

OR
Set status button

Page 18

flag to CANCEL status and click

button.

Status Detail

Set Status Button

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 3.0
Effective:Jan-10

3.
Click on the edit text button
Long text dialogue box.

4.

Page 19

and enter the reason for cancellation in the

From Drop Down Menus under Maintenance Notification select Functions


followed by Deletion Flag, followed by Set

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

5.

Page 20

Revision: 3.0
Effective:Jan-10

This completes the Cancel / Deletion process

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Monitoring and Compliance

4.1

Key Performance Monitoring (KPIs)

Revision: 3.0
Effective:Jan-10

The SAP PM Master Data Management Team is responsible for monitoring the Z6
Process performance through monthly KPIs.
KPIs will be monitored based on Z6 Notifications statuses as detailed (See the table
below). However, special attention will need to be given to the main 4 types of
notifications, in order to ensure proper execution of all Z6 notifications with Dual coded
NVST user-status codes (I.e. APPR NVST, AWAP NVST, INIT NVST, INIT and
APPR).

4.2

Status Code

To be measured against

APPR NVST

CDFPs, Tech. Reliability / Integrity & Maint. Engineers.

AWAP NVST

CDFPs (Working with Tech. Reliability / Integrity & Maint.


Engineers.)

INIT NVST

Tech. Reliability / Integrity & Maint. Engineers (Working with


Initiators)

TBCO NVST

PM Master Data Team (UOM/3s)

INIT

Planning, Project s and Tech. Reliability / Integrity, Flowline &


Maint. Engineers

AWAP

CDFPs

APPR

PM Master Data team (UOM/3s)

TBCO

CDFPs

Compliance
Compliance to the Z6 Process will be ensured by regular Road shows and one-on-one
discussions to identify and address problems within the system. A formal audit process
is not conducted.

Page 21

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 3.0
Effective:Jan-10

Appendix 1 SAP-PM Master Data Codes and Work Centres


SAP-PM Master Data Existing Records
Code

Description

C000

Equipment Movement (Enter Details in Text)

C010

Change Equipment Records

C020

Change Function Location Record

C030

Change Measuring Point

C035

Change Measurement Reading Entry List

C040

Change Work Centre

C050

Change Task list

C060

Change Recurring Activity Item/Plan

C070

Change Recurring Activity Strategy/Package

C080

Change Recurring Activity Schedule

C090

Change Material Record

C100

Change Bill of Materials

C110

Change PRT (Production Resource Tool)

C120

Change Class/Characteristic

C130

Change Maintenance Catalogue Code

C140

Change Standard Text

C150

Change Contract

C160

Other (Please Specify)

C170

Process Waver for approved PR-1005 Form

C180

Change Object Links

New SAP-PM Master Data New Records


Code

Description

N010

New Equipment Records

N020

New Function Location (FLOC) Record

N030

New Measuring Points

N035

New Measurement Reading Entry List

N040

New Work Centre

N050

New Task list

N060

New Recurring Activity Item/Plan

N070

New Recurring Activity Strategy/Package

N080

New Recurring Activity Schedule

N090

New Material Record

N100

New Bill of Materials

Page 22

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Code

Description

N110

New PRT (Production Resource Tool)

N120

New Class/Characteristic

N130

New Maintenance Catalogue Code

N140

New Standard Text

N150

New Contract

N160

Others (Specify in Text)

N170

Create Object Links

Revision: 3.0
Effective:Jan-10

Work Centre Codes


Work
Centre

Short description

CFDP

CDFPCAU

CDFP-Control-and-Automation

UEOA3

CDFPEUT

CDFP-Electrical-and-Utilities

UIE3 (UEE2)

CDFPPPL

CDFP-Pipelines

UIP5 (UEL1

CDFPREQ

CDFP-Rotating-Equipment

UEC4

CDFPSEQ

CDFP-Static-Equipment

UEC15

CDFPMMS

CDFP-Maint Mngt Syst

UOM3

CDFPMAR

CDFP- Marine

UIT4

IMPORTANT NOTE: Reference Indicators are subject to change due to re-organisation,


staff movements etc. Please check if unsure.

Page 23

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 3.0
Effective:Jan-10

Appendix 2 Data Entry Templates


The following Links will take the User to LiveLink and access to the respective Templates.

Maintenance Plan

Task List

Page 24

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Petroleum Development Oman LLC

Revision: 3.0
Effective:Jan-10

Appendix 2 Abbreviations
CFDH

Corporate Function Discipline Head

CDFP

Corporate Discipline Focal Point

CMF

Corporate Management Framework

CMMS

Computer Maintenance Management System

CoPs

Codes of Practices

EMC

Engineering and Maintenance Contractors

FLOC

Function Location

KPIs

Key Performance Indicators

ODC

Offplot Development Contractors

PRs

Procedures

SAP-PM

System Application and Products Plant Maintenance

SAP Abbreviations
APPR

Approved

APPR
NVST

Approved Incomplete Information

AWAP

Awaiting Approval

AWAP
NVST

Awaiting Approval Incomlete Information

CLSD

Closed

INIT

Initiate

INIT NVST

Initiate Incomplete Information

TBCO

To be Closed Out

TBCO
NVST

To Be Closed Out Incomplete Information

Page 25

PR-1528 Z6 Notification

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Revision: 3.0
Effective:Jan-10

Petroleum Development Oman LLC

Appendix 3 - User Feedback Page


PR-1528 Z6 Notification User Feedback Page
Any user who identifies an inaccuracy, error or ambiguity is requested to notify
the custodian so that appropriate action can be taken. The user is requested
to return this page fully completed, indicating precisely the amendment(s)
recommended.
Name:
Ref ID

Page Ref:

Date:

Brief Description of Change Required and Reasons

UOM3
Custodian of Document

Page 26

PR-1528 Z6 Notification

Date:

Printed 11/01/10

The controlled version of this CMF Document resides online in Livelink. Printed copies are UNCONTROLLED.

Scope of work for CMMS and CCMS

APPENDIX IV
Criticality Assessment Procedure

Doc. No: ZAU-84-104810 -VA-6793-20001-0000

APPENDIX-IV

REVISION: 02
Date: 03.06.2013

Petroleum Development Oman L.L.C.

UNRESTRICTED
July 2000

Document ID : PR-1248
Filing key :

Criticality Assessment Procedure

Keywords:
This document is the property of Petroleum Development Oman, LLC. Neither the whole nor any
part of this document may be disclosed to others or reproduced, stored in a retrieval system, or
transmitted in any form by any means (electronic, mechanical, reprographic recording or otherwise)
without prior written consent of the owner.

Assessment Criticality Procedure

Version 1

Authorised For Issue 1/1/2000

Signed : on 12/07/2000
Naaman Naamani UOM
CFDH Maintenance

The following is a brief summary of the most recent revisions to this document. Details of all
revisions prior to these are held on file by the issuing department.

Version No.
Version 2

Date
July 2000

Author
Khamis Al-Busaidi
OTT/51

Checked
Hiren Sarma, UOM/6

Version 1

Apr 2000

Khamis Al-Busaidi
OTT/51

Hiren Sarma, UOM/6

Version 0

Jan 2000

Khamis Al-Busaidi
OTT/51

Hiren Sarma, UOM/6


Cameron Mitchell,
UOM/1

23/04/00

Page i

Scope / Remarks
Incl.Reputation
cost in sec 2.1 and
highlighted that the
HSE matrix in sec.4
is exclusively to be
used for equipment
criticality only.
Modification of
equipment criticality
matrix
Initial Issue

PR-1248

Version 1

Criticality Assessment Procedure

Contents
Authorised For Issue 1/1/2000 ................................................................................................... i
Contents ..................................................................................................................................... ii
1 Introduction ......................................................................................................................... 1
1.1 Background ................................................................................................................ 1
1.2 Purpose ....................................................................................................................... 2
1.3 Distribution/Target Audience ..................................................................................... 2
1.4 Document Improvements ........................................................................................... 2
2 Criticality Assessment Methodology .................................................................................. 4
2.1 Asset and Production Loss ......................................................................................... 5
2.2 Safety .......................................................................................................................... 6
2.3 Environment ............................................................................................................... 7
2.4 Frequency of Demand (Occurrence) .......................................................................... 7
2.5 Functional Criticality Class Calculations ................................................................... 8
3 RCM Implementation ......................................................................................................... 9
4 Equipment Criticality........................................................................................................ 10
4.1 Asset and Production Loss ....................................................................................... 10
4.2 Safety ........................................................................................................................ 10
4.3 Environment ............................................................................................................. 10
4.4 Time Interval Between Failures ............................................................................... 11
Appendix A Example of Station Function Criticality .......................................................... 12
Appendix B Glossary of Definitions, Terms and Abbreviations ......................................... 13
ATTACHMENT User Feedback Sheet ................................................................................. 14

PR-1248

Page ii

23/04/00

Criticality Assessment Procedure

Introduction

1.1

Background

Version 1

Maintenance spending represents a significant percentage of total costs and, more


importantly, of controllable costs across many industries. The benefits of maintenance
excellence go beyond cost control to affect multiple performance dimensions of the
organisation. These benefits are not trade offs and can be concurrent outcomes of
maintenance improvement programs:

Lower direct maintenance cost

Higher capital and labour productivity

Reduced risk of catastrophic failure

Achieving maintenance excellence should be viewed as an evolutionary process where the


End State is the cost-effective elimination of defects through the use of equipment specific
maintenance approaches, e.g. fig.1.1. A continuous maintenance improvement cycle is
obtained by continuously implementing the following steps: 1.

Determine operational business requirement.

2.

Identify possible system designs and maintenance options.

3.

Determine optimum maintenance strategies.

4.

Monitor system performance and maintain strategy effectiveness.

Maintenance Optimization
Identify possible system
designs and maintenance
options

Define Operational
business requirements

Criticality
SET MAINTENANCE
OBJECTIVES

Assessment

RELIABILITY
CENTRED
MAINTENANCE

-INTEGRITY
-PRODUCTION
-COSTS

INPUT RCM BASED


STRATEGIES

UPDATE WITH
OPTIMUM STRATEGIES

ADJUST

SYSTEM
EFFECTIVENESS
MODELLING

PERFORMANCE
MEASUREMENT
IMPLEMENT OPTIMUM
STRATEGIES

Monitor system performance


and maintenance strategy
effectiveness

Determine optimum
maintenance strategies

Figure 1.1: Shell Maintenance Optimization

23/04/00

Page 1

PR-1248

Version 1

Criticality Assessment Procedure

One of the recognised approaches to establish the maintenance requirements for any
equipment is the use of Reliability Centred Maintenance (RCM). It is based on determining
what must be done to ensure that the equipment fulfils its intended functions in its current
operating context. RCM differs from previous maintenance thinking in two main ways; it
focuses on the function of equipment rather than the equipment itself, and it generates
maintenance activities designed to avoid or mitigate the consequence of failure.
Prior to applying RCM, the critical functions of selected assets are filtered in terms of Asset
(Production), Safety and Environment criticality by Criticality Assessment Analysis which is
described in this procedure. Under each critical function, the criticality is further defined in
terms of individual equipment. Reference may be made to the PDO Risk Management Code
of Practice CP-131 and to the DEP 32.80.10.10-PDO titled Classification and
Implementation of Instrumented Protective Function.
1.2

Purpose
Criticality Assessment helps in determining what functions and equipment tags are critical
and those which need to have Reliability Centered Maintenance (RCM) analysis carried out.
It identifies and focuses on those items which are critical, not only in terms of maximising
asset flow (production) but also potential risk to safety, and the environment.
Reliability Centered Maintenance (RCM) and Risk Based Inspection (RBI) are defined as
techniques used to determine the maintenance requirements of any physical asset in its
operating context. RCM and RBI are then applied in detail to these critical functions. The
maintenance strategy/requirements for less and/or non-critical functions are then
recommended using reference data already available for similar equipment. However, the
operating context of these functions must be considered on a case by case basis while
making such recommendations. Figure 1.2 depicts the relationship between criticality
assessment and maintenance strategy development.

1.3

Distribution/Target Audience
The primary target audiences of this criticality assessment procedure are the Reliability
Engineers, Maintenance Engineers, Project Engineers, CDFPs, Discipline Engineers and
Asset Team members involved in the planning, development and operational activities
relevant to the particular asset.

1.4

Document Improvements
The custodian of this document is UOM/7. If you have any concerns or recommended
improvements please contact OTT/51 or UOM/7.

PR-1248

Page 2

23/04/00

Criticality Assessment Procedure

Version 1

Criticality
Assessment

IPF/RCM
Results

Existing Facilities

Existing
or New Facilities

IPF

New Facilities

Compare
Epmars

Identify Cost Benefits &


Agree with Asset teams where
Improvement could be achieved.

Prepare - WSNS
Select MCPS

Update EPMARS

Fig. 1.2: The relationship between RCM and the Criticality Assessment.

23/04/00

Page 3

PR-1248

Version 1

Criticality Assessment Procedure

Criticality Assessment Methodology


The Criticality Assessment is performed by determining the potential impact on the
functions of a group of assets against the following criteria: Production and asset - The effect on production output and asset loss.
Safety The direct or indirect personnel risk or equipment damage.
Environment - The effect on the local environment.
Frequency of occurrence - Failure frequency (reciprocal of Mean Time Between Failure).
The results of the initial assessment should be updated following commissioning of
additional assets on site, further failure occurrences and/or more operational data. These
results should be sorted to understand the importance of each function in terms of its impact
on the Environment, Safety or Production criticality.
The following documents were referred to during the preparation of the criticality
assessment procedure;
1.

Risk Management Code of Practice, CP-131

2. DEP 32.80.10.10-PDO titled Classification


Instrumented Protective Function.

and

Implementation

3. LNG
documents
titled
Maintenance
and
Integrity
Development(LNG-9-0001-090-F1-4 and LNG-F1-SP-1-017).

of

Strategy

4. EP Maintenance Management Guides (SIEP 98-5200/5215).


The functional criticality is done according to the risk matrix shown below. This matrix is the
same as the PDO risk matrix described in the Risk Management Code of Practice CP-131. It
should be noted however that since the magnitude of cost involved in the repair and upkeep of
equipment is far lower than that involved in the original risk matrix (CP-131), the values in
the asset column have been scaled down as per DEP 32.80.10.10-PDO. (see sections 2.1 to
2.4 for description)

PR-1248

Page 4

23/04/00

Criticality Assessment Procedure

Version 1

Frequency of Demand (occurrence)

Consequence
Rating Environment Safety

Assets

1 No/slight effcet No/slight


injury

No/slight
effcet

2 Minor effcet

Minor effcet

Minor
injury

Localised
effect

4 Major effect

Single
fatality

Major effect

Multiple
fatality

Massive effect

2.1

B
C
20 - 100 Year 4 - 20 Year

D
0.5 - 4 Year

E
0 - 0.5 Year

Never heard
of but could
feasible
occur

Does not
occur
during the
lifetime of
the facility

Occurs
once
between
maintenan
ce shutdowns

Occurs
several
times a
year

Normal
demand
when
variables
are
controlled

Low

3 Localised effect Major


injury

5 Massive effect

A
> 100 Year

Medium

High

Extreme

Asset and Production Loss


A more detailed description of the potential production and equipment loss selections is
indicated in the table below. Damage refers to direct hardware replacement and repair cost
and also to consequential losses due to down time.

Cat

Potential impact

No/Slight effect

No disruption to operation, no operational upset or no damage to assets.


(total loss value less than US$ 1,000)

Minor effect

Brief disruption, minor operational upset or minor damage to assets.


(total loss value less than US$ 100,000)

Localised effect

Partial shutdown, moderate operational upset or moderate damage to assets


(total loss value less than US$ 1M)

Major effect

Partial operation loss, major operational upset or major damage to assets (total
loss value less than US$ 10M)

Massive effect

Substantial or total loss of operations, damage causing major loss of


containment or damage to essential assets (total loss value in excess of
US$ 10M)

Description (refer to DEP 32.80.10.10-PDO)

The asset and production loss calculation taking four main elements into account:

Total loss value = Production loss + Reprocessing cost + Reputation Cost (Applicable only for Gas
plants) + Repair cost + Own labour cost.
23/04/00

Page 5

PR-1248

Version 1

Criticality Assessment Procedure

Where:

Production loss is the deferred income (no or downgraded production) plus the product wasted
(e.g. flared, spilled).

Reprocessing cost is the cost (energy, tankage, etc.) required for reprocessing of off-spec. product
or waste.

Reputation cost: For Government Gas Plants viz. Yibal-GGP, LNG Upstream and Barik Gas
station; the reliability of gas production in terms of quality and quantity of gas produced is of very
high importance. The impact of faiure of a particular asset on the quality and quantity of gas
produced shall be quantified under this Reputation Cost.

Repair cost is the cost incurred to have the damage repaired or assets replaced.

Own labour cost is the cost (hours etc.) of the owners personnel involved in the incident
From the calculated total loss value, the (asset and production) loss consequence category
can be established from the above table.

2.2

Safety
A more detailed description of the safety effect is indicated in the table below.

Cat

Potential impact

No/Slight injury

No safety effect or slight injury or health effects (including first aid case and
medical treatment case) - Not affecting work performance or causing disability.

Minor injury

Minor injury or health effects (Lost Time Injury) Affecting work


performance, such as restriction to activities (Restricted Work Case) or
a need to take a few days to fully recover (Lost Workday Case). Limited
health effects, which are reversible, e.g. skin irritation, food poisoning.

Major injury

Major injury or health effects (including Permanent Partial Disability)


Affecting work performance in the longer term, such as a prolonged absence
from work. Irreversible health damages without loss of life, e.g. noise induced
hearing loss, chronic back injuries.

Single fatality

Single fatality From an accident or occupational illness (poisoning, cancer).

Multiple fatality

Multiple fatalities - From an accident or occupational illness (poisoning,


cancer).

PR-1248

Description (refer PDO HSE Risk assessment Matrix)

Page 6

23/04/00

Criticality Assessment Procedure

2.3

Version 1

Environment
A more detailed description of the environment effect is indicated in the table below.

Cat

Potential impact

No/Slight effect

No/Slight effect Very Local environmental damage. Within the fence and
within systems. No change in the environment. Negligible financial
consequences.

Minor effect

Minor effect Contamination. Damage sufficiently large to attack the


environment. Single exceedance of statutory or prescribed criterion.
Single complaint. No permanent effect on the environment.

Localised effect

Localised effect Limited loss of discharges of known toxicity. Repeated


exceedance of statutory or prescribed limit. Affecting neighbourhood.

Major effect

Major effect Severe environmental damage. The company is required to take


extensive measures to restore the contaminated environment to its original state.
Extended exceedance of statutory or prescribed limits.

Massive effect

Massive effect Persistent severe environmental damage or severe


nuisance extending over a large area. In terms of commercial or
recreational use or nature conservancy, a major economic loss for the
company. Constant, high exceedance of statutory or prescribed limits.

2.4

Description (refer PDO HSE Risk assessment Matrix and DEP


32.80.10.10-PDO)

Frequency of Demand (Occurrence)


For a given risk item one frequency or probability needs to be picked though in reality a risk
issue often exists in a certain probability range. At a higher probability of occurrence a risk
may carry a lower exposure while at a lower frequency the risk exposure may be much
higher. This translates into a risk area on the risk matrix rather than a single point.
Judgement should be applied when making the assessment.

Cat

Frequency (*)

Description (refer to PDO HSE Risk assessment


Matrix and DEP 32.80.10.10-PDO)

> 100 Year

Never heard of but could feasible occur (> 100 year)

20 - 100 Year

Does not occur during the lifetime of the facility


(20 100 year)

4 - 20 Year

Normal demand
(4 - 20 years)

0.5 - 4 Year

Occurs once
(0.5 - 4 years)

0 0.5 Year

Occurs several times a year (0 - 0.5 year)

when

between

variables

are

maintenance

controlled

shut-downs

* Note that the life time of some equipment (i.e. some rotating equipment) can be around 20 years.

23/04/00

Page 7

PR-1248

Version 1

2.5

Criticality Assessment Procedure

Functional Criticality Class Calculations


Each station is divided into functions (Operation Packages) by using the PEFS and PFS. A
criticality assessment sheet, with all functions listed within the station, is completed for each
station as shown in appendix A. A desktop exercise is arranged with the relevant discipline
maintenance/operations personnel, to agree to the criticality class for each of the Asset
(Production), Safety and Environment per function; i.e. Low, Medium, High or Extreme.
(see the risk matrix in section 2)
It should be emphasised that one representative at least from each core discipline
(Instrument, Electrical, Mechanical, Production and preferably HSE) shall be part of the
exercise. It is also recommended that one representative from the Engineering design team
is part of the team. In the case of a new facility, this is very important. The team shall be
led by an experienced Reliability Engineer.

PR-1248

Page 8

23/04/00

Criticality Assessment Procedure

Version 1

RCM Implementation
RCM is implemented based on the functional criticality classes obtained as stated in section
2.5. For each function, if the criticality class of Asset, Safety Or Environment is High OR
Extreme (coloured blue or red in the matrix), then RCM will be implemented on that
function. If none of the Asset, Safety Or Environment classes of the function is High OR
Extreme, then RCM will NOT be implemented on that function.

23/04/00

Page 9

PR-1248

Version 1

Criticality Assessment Procedure

Equipment Criticality
If RCM is decided to be applied, then the functional criticality is drilled down further by
determining Equipment Criticality taking into account the redundancy of the equipment.
This is done during the RCM analysis exercise stated in section 2.5. The equipment
criticality is applied in the same way as the functional criticality but on individual items of
equipment and using the risk matrix shown below in which, the frequency of failures has
been scaled down to reflect the failure and life time of equipment in the field.
The criticality matrix shown below shall be exclusively used for determining
equipment criticality only.
Three criticality classes are given for Assets, Safety and Environment. The Safety and
Environment criticality classes will be the same as those classes obtained during the
functional criticality for that particular function which the equipment falls under. The Asset
criticality class may reduce if there is redundancy on the equipment. Depending on the
number of standby units, the production and deferment loss will reduce and so the risk will
decrease.
In case where RCM methodology is not applied for function analysis, individual equipment
criticality can be determined by using the same methods outlined above.

Time Interval between Failures (T)

Consequence
Rating Environment

Safety

Assets

1 No/slight effect

No/slight
injury

No / slight
effect

2 Minor effect

Minor
injury

Minor effect

Major
injury

Localized
effect

Single
fatality

Major effect

Multiple
fatality

Massive effect

3 Localized effect

4 Major effect

5 Massive effect

4.1

A
B
C
T >= 10 Years 5 =< T < 10 2 =< T < 5
Years
Years

D
0.5 < T < 2
Years

Low

Medium

High

Extreme

Asset and Production Loss


Refer to section 2.1.

4.2

Safety
Refer to section 2.2.

4.3

Environment
Refer to section 2.3.

PR-1248

Page 10

23/04/00

E
T <= 0.5
Years

Criticality Assessment Procedure

4.4

Version 1

Time Interval Between Failures


For a given risk item one frequency or probability needs to be picked though in reality a risk
issue often exists in a certain probability range. At a higher probability of occurrence a risk
may carry a lower exposure while at a lower frequency the risk exposure may be much
higher. This translates into a risk area on the risk matrix rather than a single point.
Judgement should be applied when making the assessment.

Cat

Interval (*)

Description

10 years or more

Time interval between failures is 10 years or more

5 =< T < 10 Years

Time interval between failures is 5 years or more

2 =< T < 5 Years

Time interval between failures is 2 years or more

0.5 < T < 2 Years

Time interval between failures is more than 6 months

0.5 year or less

Time interval between failures is 6 months or less

* Note this was scaled down to reflect the failure and life time of field equipment.

23/04/00

Page 11

PR-1248

Version 1

Criticality Assessment Procedure

Appendix A Example of Station Function Criticality

PR-1248

Page 12

23/04/00

Criticality Assessment Procedure

Version 1

Appendix B Glossary of Definitions, Terms and Abbreviations


CP
LNG
EC
EI
EP, E&P
EPMARS
EWMS
FP
HSE
IPF
MCP
MTBF
PC
PD
PDO
PEFS
PFS
PI
RC
RCM
SC
SIEP
SRCM
SI
WSNS

23/04/00

Code of Practice
Liquidify Natural Gas
Environmental Criticality
Environmental Impact
Exploration & Production
Exploration & Production Maintenance Administration and
Reporting System.
Engineering Work Management System
Failure Probability
Health Safety and Environment
Instrumented Protective Function
Maintenance Craft Procedure.
Mean Time Between Failure.
Production Criticality
Production Downtime
Petroleum Development Oman
Process Engineering Flow scheme
Process Flow Scheme.
Production Impact
Repair Cost.
Reliability Centered Maintenance
Safety Criticality
Shell International Exploration & Production Co.
Shell (Proprietary) Reliability Centered Maintenance.
Safety Impact.
Work Specifications Numbers.

Page 13

PR-1248

Version 1

Criticality Assessment Procedure

ATTACHMENT User Feedback Sheet


OPERATIONS PROCEDURES

USER FEEDBACK SHEET

Any user who identifies an error, inaccuracy or ambiguity in these Operations Procedures
documents is requested to advise the custodians in the Systems & Information Section by
returning this page (or copy) with his comments.

Volume:

Part:

User name:

Ref. Ind:

New Operations Standard or Practice required: Yes / No

Date:

(delete as applicable)

New Procedure, Name or Error Location : e.g. PR New Procedure/ Comment / Error / Suggestion
number, page, paragraph.

PR-1248

Page 14

23/04/00

Scope of work for CMMS and CCMS

APPENDIX IV
E-SPIR 2000 Procedure & Project Documents Requirement

Doc. No: ZAU-84-104810 -VA-6793-20001-0000

APPENDIX-V

REVISION: 02
Date: 03.06.2013

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

UNRESTRICTED

DOCUMENT ID: PR-1443

OCTOBER 2003

FILING KEY:

Petroleum Development Oman L.L.C.

E-SPIR 2000 Procedure & Project Documents Requirement


(Electronic Spare Parts list and Interchange ability Record)

Procedures

KEYWORDS: E-SPIR, PR-1443

Authorized for Issue Second Revision: 01/07/2009


Signed:

----------------------------------,
Technical Eng Consultancy Manager - UEC

This document is the property of Petroleum Development Oman, LLC. Neither the whole nor any part of this
document may be disclosed to others or reproduced, stored in a retrieval system or transmitted in any form by
any means (electronic, mechanical, reprographic recording or otherwise) without prior written consent of the
owner.

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

REVISION CONTROL SHEET

REVISION Date

Reason for Revision

Revision By:

Oct.2003 Original Issue

TTO/41

Jan-07

Second Revision

UEC/41

Jun-09

Third Revision

UOM/412

Document author

UOM/412

Document custodian UOM/41

Shidhany Al SYS
Nasser Al Bakry

Approved

UOM/4

Rashid Al Fahdi

Authorised

UEC

Harthy, Salim

Custodianship:
The document custodian of E-SPIR 2000 procedures shall be responsible for its updates and all
queries should be directed to the custodian.

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

Table of Contents
No

1
1.1
1.2
1.3
2
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
3.0
3.1

Description
Title Cover Page
Document Revision Status & Authorization
Table of Contents
Introduction to E-SPIR 2000
Background
Purpose
Distribution & Target Audience
Project Documentation Requirement for E-SPIR
Scope
Principles
Procedure Description
Funding of spare parts
Roles and Responsibilities
E-SPIR Form
References
Request for Stocking Spare parts
Request for stocking spare parts (RFSS)
Motor Name Plate Technical Data
Rechargeable batteries
Appendix A (Definitions)
Appendix B (Abbreviations)
Appendix C (Project Material & SPIR Process Flowchart)
Appendix D (SPIR Documentation Conformity Review Process)
Appendix E ( Procedure Process, Activities & Responsibilities)
Appendix F (Rotating Equipments)
Appendix G (Static Equipments)
Appendix H (Process Instrumentation)
Appendix I (Electrical Equipment)

Page
No
1
2
3
4
4
4
4
5
5
5
5
5
6&7
8
9
9
10
11
12

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

1.

Introduction to E-SPIR 2000

Electronic Spare Parts and Interchangeability Record is a software package for obtaining spare parts
information from equipment suppliers in a standard format. It supports the purchaser in reviewing and
selecting spare parts.
1.1

Background

Project engineering code of practice (CP-117) stipulates the mandatory requirement of Consultants,
Manufacturers, Suppliers and Vendors of equipment or plant supplied to and installed in PDO facilities to
provide spare parts recommendation on E-SPIR forms supported with all relevant documentation.

1.2

Purpose

The purpose of this procedure is to describe the process of spare parts management and the mandatory
requirements by project engineers in the submission E-SPIR forms along with a consistent set of other
supporting relevant documentation (see appendix G, H & I) to Head, Spare Parts Management (UOM/41).

1.3

Distribution/Target Audience

This document is primarily intended for PDO project engineers. It is also made available to PDO operation
engineers, contracting/procurement department personnel and to approved consultants, manufacturers,
suppliers and vendors of equipment and material.

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

Project Documentation requirement for E-SPIR

2.1

Scope

This procedure is to be followed to ensure information that is entered into the E-SPIR forms and the project
documentation (see appendixes F, G, H & I ) as submitted by the consultant/manufacturer/vendors/suppliers
along with the E-SPIR forms meets the obligations as mentioned in PR-1443 & DEP 70.10.90.11-Gen.

2.2

Principles

The basic principle of this procedure is to provide a clear well defined document that lists out the requirement
in filling the standard E-SPIR form correctly and providing other relevant supporting documents. The
documents provided by the manufacturer/supplier/vendor are to be used as a source of spare part data for
clearly identifying the spare parts and interchangeability thus assisting to determine the holding of the
optimum quantity necessary to safeguard cost effective operations of equipment/plant. The decision to stock
or not to stock is made by applying the Decision Rule as described in DEP 70.10.90.11- Gen.
2.3

Procedure Description

The procedures presented as flowchart (appendixes C, D &E) constitutes PR-1443.


2.4

Funding of Spare Parts

Commissioning and initial start up spares including long lead Capitalized Insurance Spares (if any) are to be
ordered along with the main project equipment on project CAPEX budget and shall be available at site prior
to commissioning. Capitalized Insurance spares are stocked in the companys warehouses at zero value. End
users using these spares have to provide a RFA to replenish them.
Operating supply spares listed and recommended to stock under Materials Catalogue Request Form (MCRF)
are authorized by Head Spare Parts Management (UOM/41). They are further approved for procurement and
stocking by Head, Procurement (FPO) against Contracting & Procurement departments Capital Budget
(stock account) and stocked at companys warehouses at MAF, Fahud and Marmul as per MCRF.
The cost of spares are charged to the end users OPEX budget at the time of issue for usage and replenished by
C&P (contracting & procurement department) against stock account for subsequent availability and
requirement of end users.

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

2.5

Roles and Responsibility in the E-SPIR process.

Consultant/Manufacturer/Supplier/Vendor

Provide spare parts data on E-SPIR form on a diskette together with a set of hard copy with relevant
drawings, parts list, technical catalogues, brochures, etc. in accordance with DEP 70.10.90.11Gen.and PR-1443

Capitalized Insurance long lead spare-parts supplied (if any) also to be mentioned in the E-SPIR

E-SPIR and other relevant documentation from project engineers for onward transmittal to Head,
Spare Parts Management UOM/41.

Project Engineer

Provide PEP (project execution plan) showing an overview of project scope, etc. and specify
equipment criticality as per the ABC indicator as listed in SAP.

Decide in consultation with operation engineers from UOM, UIE & UPOA on the requirement of
stocking Capitalized Insurance Spare (SAP code CSDT) for the mechanical, electrical and
instrumentation control/process equipment respectively. Capitalized Insurance Spares has to be
purchased along with the main equipment.

Provide UOM/41 list of all Capitalized Insurance Spares prior to ordering so as to counter check for
duplication against existing spares in stock.

Ensure quality of E-SPIR and relevant documentation package is submitted to UOM/41 at least
three months prior to commissioning date of plant/equipment.

Liaise with UOM/41 for the SAP coding of long lead Capitalized Insurance spares (if any) that has to
be returned to store.

Liaise with UOM/41 for returning to store unused commissioning and initial start-up spares procured
by PDO before project close out.

Provide overall co-ordination between consultant, manufacturer, supplier and vendors in spare parts
matters.

Ensure that receipt of quality E-SPIR forms and relevant documents is linked to the contract
milestones payment schedule in the Project Execution Plan.

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

Spare Parts Analyst (UOM/41X)

Technically review, scrutinize and identify electrical spare parts from vendor SPIR forms submitted
by project engineers. Compare/verify with existing spares database to avoid duplication and over
stocking. Decide and recommend critical new spares for optimum stocking by challenging the
vendors recommended spares and quantity.

Draft technical specification of spare parts, prepare coding list, raise stock proposal for authorization
by Head Spare Parts Management (UOM/41) and submit to Contracting and Procurement department
for procuring and stocking action.

Create, maintain and update Bill of Material (BOM) of spare parts and link it to equipment in SAP
system. This information can be used by end users to view spare parts data of installed equipments in
PDO.

Technical evaluations of spare parts quotations deviating from the standard purchase order text.

Helpdesk and technical support to asset field personnel, operation support engineers and project
engineers on spare parts matters and advise substitutes during emergencies.

Liaison with project engineers on the selection of long lead capitalized insurance spares for ordering
on project CAPEX account.

Technical investigation/liaison with end users and procurement department on spare parts COM
(criticism of material) form

SAP Content Group (FPP/3)


Corporate focal point between PDO and SAP Blue Print Global Catalogue Kuala Lumpur in the
creation/amendment/deletion of SAP material number from the MCRF (Materials Catalogue
Request Form) for HIBE & CSDT material.
Create/Amend/Delete/and maintain plant records

Stock Analyst/Buyers (FPO/2X)

Analyze, procure and stock spare parts as per the authorized MCRF (Materials Catalogue Request
Form).

Analyze and adjust minimum/maximum levels for existing stock as per consumption rate in
consultation with UOM/41X

Spares Categories and responsibilities:


Spares categories
Commissioning Spares
Capital Insurance Spares

2 Yearly / Operational Spares

Responsibility of Purchase
Project Scope
UEC/2 CFDH to Approve with
UOM41 Involvement and
purchased via Project
UOM41

Budget
Capex Account
Capex Account

Corporate Account

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

2.6

E-SPIR FORM

The above form with its explanation and instruction for completion can be downloaded from the below
hyperlink.
Press Ctrl and click the below.
http://www.e-spir.com/

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

References

2.7

2.8

DEP 70.10.90.11-Gen. (Manual SPARE PARTS)


CP-117 (Project Engineering Code of Practice)
ERD-00-18 (Engineering Guidelines Vendor Documentation)

Request for Stocking Spare parts


Spare parts missed out during project execution stages and deemed necessary by field
operation teams to be held in stock and other spare parts required to be kept in stock due to field
change proposal (FCP) can be proposed for stocking by submission of
RFSS form to UOM/41.

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

2.9 Request For Stocking of Spares Form (RFSS)

10

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

To download the above RFSS form, press Ctrl and click the below hyperlink
http://sww.pdo.shell.om/sites/UEOD/UOM/UOM4/Spare%20Parts%20Management/Forms/AllItems.aspx

3.0

Motor Name Plate Technical Data

11

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

To download the above form, press Ctrl and click the below hyperlink
http://sww.pdo.shell.om/sites/UEOD/UOM/UOM4/Spare%20Parts%20Management/Forms/AllItems.aspx

3.1

Rechargeable Batteries Coding Request Spares Form

12

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

To download the above form, press Ctrl and click the below hyperlink

http://sww.pdo.shell.om/sites/UEOD/UOM/UOM4/Spare%20Parts%20Management/Forms/AllItems.aspx

13

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

Appendix A
Definitions

Consumable spare parts are those parts of equipment that are subject to
deterioration due to normal operation and which requires replacement for the
smooth efficient and safe running of plant/machinery.
Insurance spare parts are those parts of equipment, equipment assemblies or
complete items of equipment/plant that are required for replacement of items not
subject to deterioration by normal use, but failure of which is critical for continued
and safe operation of the equipment or plant.
Capital Insurance spare parts are insurance spares having a high value (> US $
10,000) and which would only be used in abnormal circumstances i.e. major
damage or failure.
Commissioning spare parts are parts that would be required initially to enable
uninterrupted installation and start up of the equipment or plant.
Initial spare parts are those spares required to safeguard the operation of
equipment during the running-in start up periods and the first year of operation.
Initial spare parts shall on site prior to start up of equipment or plant.
Operating spare parts are those spares required for normal operation and day to
day maintenance in the two year period following the initial operation period
Major equipment overall spare parts are those spares required during the
planned major overall of equipment or plant (campaign maintenance)

Overview of Commissioning, Initial and Operating spare parts


Project / Contractor

Commissioning

Production Unit

1st Year

Rolling 2 years

Commissioning

Initial

Operating

Spare Parts

Spare Parts

Spare Parts

Start-up

Project Budget

Stock / Maintenance Budget

14

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

Appendix B
Abbreviations
ABC
Indicator

Equipment criticality i.e. A= Extreme B= High C= Medium D=Low

BOM

Bill Of Material

CSDT

Capitalized Insurance Spare

DEP

Design and Engineering Practice

FCP

Field Change Proposal

HIBE

Operating Supplies

MCRF

Materials Catalogue Request Form

OEM

Original Equipment Manufacturer

PEP

Project Execution Plan

PMSS

Project Material Strategy Sheet

RFA

Request For Authorization

RFSS

Request For Stocking Spares

SAP

System Application and Products

E-SPIR

Electronic Spare Parts list and Interchange ability Record

15

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

16

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

17

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

18

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

19

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

20

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

21

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

22

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

23

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

24

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

25

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

26

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

27

PR-1443 (SPIR PROCEDURE AND PROJECT DOCUMENTS REQUIREMENT)

28

Potrebbero piacerti anche