KITCHEN VENTILATION CALCULATIONS

(KEF-01 & KMF-01)

COMPUTATION:
1. Appliance Area (Mobile Hot Cabinet) = 5.75 ft x 2.3 ft
= 13.25 ft
2. Qc = Area (ft) x Thermal Updraft Vel. (fpm)
Mobile Hot Cabinet ;

Qc = 13.25 ft x 50 fpm = 662.5 Cfm

3. QSD = (Total Area of Hood Total Area of Appliances) x 50 fpm


QSD = ( 6 ft x 3.28 ft ) (13.25 ft ) x 50 fpm
= 321.5 Cfm
4. QE = QC + QSD = 662.5 Cfm + 321.5 Cfm = 984 Cfm
5. QCF = QE x Hood Factor
From Table Hood Factor :
Single Island Hood, HF = 1.2

QCF = 984 Cfm x 1.2 = 1180 Cfm, Say use: 1200 Cfm
A. KITCHEN EXHAUST AIR FLOWRATE; (KEF-01)
KEF-01 = 1200 Cfm
B. KITCHEN MAKE-UP FAN AIR FLOWRATE; (KMF-01)
KMF-01 = 1200 Cfm x .80
KMF-01 = 960 Cfm

SAF-110

22

(559)

25

(635)

Inlet
81/4 (210)

(535)

133/8
(340)

91/4
(235)

11/2 (38)

119/16 (294)

(762)

cur
ve

30

211/16

to

th
el
ef

Airflow

f th
is s
y st
em

30

(762)

tt

Damper Size = 14 x 14 (355 x 355)


Roof Opening = 161/2 x 161/2 (419 x 419)
Curb Cap Thickness = 0.052 (1)
^Approximate Unit Weight = 181 lb. (82 kg)

Do

lec
t se
no

cfm

All dimensions in inches (millimeters).


^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number

Fan
CFM
820

1000

1180

1360

1540

1720
SAF-110
1900

2080

2260

2440

2620

RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones
RPM
BHP
Sones

0.125
432
0.05
11.4
476
0.07
10.0
525
0.11
10.5
577
0.15
11.2
632
0.21
12.0
688
0.28
13.1
745
0.37
14.2
802
0.47
15.5
859
0.59
16.9
918
0.72
18.8
977
0.88
21

0.25
549
0.08
11.9
579
0.11
11.7
616
0.14
11.2
660
0.19
11.0
707
0.25
11.7
757
0.33
12.8
809
0.42
14.1
864
0.53
15.7
920
0.66
17.6
976
0.80
19.6
1032
0.97
22

0.375

672
0.14
11.3
701
0.18
11.5
736
0.23
11.4
777
0.30
11.7
822
0.38
12.4
870
0.48
13.7
920
0.59
15.9
971
0.71
18.1
1025
0.87
20
1080
1.04
23

Static Pressure in inches wg


0.5
0.625
0.75
1

755
0.17
10.5
780
0.22
11.2
809
0.28
11.4
844
0.35
11.8
883
0.43
12.8
927
0.53
14.5
974
0.65
16.5
1023
0.78
18.6
1073
0.94
21

1.125

1.25

1.5

MAXIMUM RPM = 1400


TIP SPEED = RPM x 2.91
MAXIMUM MOTOR FRAME SIZE = 145T
AVERAGE OUTLET VELOCITY = CFM/1.07

850
0.26
11.2
878
0.32
11.8
908
0.40
12.7
943
0.48
13.9
982
0.59
15.4
1026
0.71
17.3
1071
0.85
19.4
1120
1.01
22

941
0.37
12.7
969
0.45
13.7
1001
0.54
14.9
1036
0.65
16.4
1075
0.77
18.2
1119
0.92
21

1082
0.55
15.2
1110
0.65
17.9
1140
0.77
18.6
1174
0.90
20
1210
1.05
22

1134
0.60
18.3
1162
0.71
18.9
1189
0.83
19.5
1221
0.97
21

1192
0.66
19.5
1210
0.77
19.9
1238
0.90
20
1266
1.04
21

1307
0.89
22
1328
1.02
23

Performance certified is for installation type B: free inlet, ducted outlet. Power rating (Bhp) does not include transmission losses. Performance ratings include the effects of a filter.
The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m) in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type B:
free inlet hemispherical sone levels.

USGF-140HP - Belt Drive

H-

W.G.

s sys
tem
curv
e

2878
(733)

2934*
19 8 (756)
(492)

26
(660)

no

ts
ele
ct

to
th

e le

ft o

f thi

134
(44)

Do

Roof Opening = 181/2 x 181/2 (470 x 470)


Windband Thickness = 0.051 (1.3)
Motor Cover Thickness = 0.040 (1.0)
Curb Cap Thickness = 0.064 (1.6)
^Approximate Unit Weight = 125 lb. (57 kg)
All dimensions in inches (millimeters).
*May be greater depending on motor.
^Weight shown is largest cataloged Open Drip Proof motor.
Model
Number

Motor
hp

USGF-140HP-4

1/4

Fan
rpm
895

1037

1179

1321

1465
USGF-140HP-3

1/3
1605

USGF-140HP-5

1/2
1725

1845
USGF-140HP-7

3/4
1960

2035

2110

CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones
CFM
BHP
Sones

0.5
331
0.06
6.1
566
0.10
6.7
733
0.13
8.9
878
0.18
12.1
1016
0.24
14.2
1146
0.31
15.2
1256
0.38
16.1
1363
0.46
17.0
1463
0.54
18.1
1528
0.60
18.9
1592
0.67
19.8

0.75

CFM / Static Pressure in inches wg


1.25
1.5
1.75
2

2.25

2.5

2.75

MAXIMUM BHP AT A GIVEN RPM = (RPM/2285)3


MAXIMUM RPM = 2110
TIP SPEED (ft/min.) = RPM x 3.829
MAXIMUM MOTOR FRAME SIZE = 145T
AVERAGE DISCHARGE VELOCITY (FPM) = CFM/1.72

563
0.14
9.2
756
0.19
11.6
920
0.26
13.5
1063
0.33
14.4
1178
0.40
15.4
1292
0.48
16.6
1399
0.57
17.7
1468
0.63
18.5
1536
0.70
19.3

591
0.19
13.6
798
0.26
13.2
965
0.34
14.2
1098
0.42
15.0
1219
0.50
16.2
1330
0.59
17.4
1402
0.66
18.2
1473
0.72
19.1

642
0.26
15.5
846
0.34
14.0
999
0.43
14.9
1137
0.52
16.0
1260
0.61
17.2
1335
0.68
18.0
1409
0.75
19.0

704
0.34
15.2
879
0.43
14.7
1042
0.52
15.9
1176
0.62
17.1
1261
0.69
18.0
1341
0.77
18.9

747
0.42
15.7
924
0.52
15.6
1086
0.63
17.0
1175
0.70
17.8
1262
0.78
18.8

800
0.51
16.1
970
0.62
16.8
1077
0.70
17.7
1178
0.78
18.6

854
0.62
16.9
965
0.69
17.5
1073
0.78
18.5

826
0.67
17.8
965
0.77
18.3

804
0.73
20

Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP) does not include transmission losses. Performance ratings do not include the effects
of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft (1.5 m) in a hemispherical free field calculated per AMCA Standard 301.
Values shown are for installation type A: Free inlet hemispherical sone levels. The AMCA Certified Ratings Seal applies to sone ratings only.

11

Potrebbero piacerti anche