Sei sulla pagina 1di 22

Transformer

Protection
By
Susobhan Patra

5/8/2014

Induction Law
The transformer is based on two principles:
1. An electric current can produce a magnetic field.
2. A changing magnetic field within a coil of wire induces a voltage across the
ends of the coil (electromagnetic induction).

POWER TRANSFORMERS
The term power transformer is used to refer to those transformers used in the
generator and the distribution circuits, and these are usually rated at 500 KVA and
above. Power systems typically consist of a large number of generation locations,
distribution points, and interconnections within the system or with nearby systems,
such as a neighboring utility. The complexity of the system leads to a variety of
transmission and distribution voltages. Power transformers must be used at each of
these points where there is a transition between voltage levels.

CAUSE OF FAULTS IN POWER TRANSFORMER


1. The most common type of fault being the winding to core faults because of
weakening of insulation. Phase faults inside the transformers are rare.
2. Power transformers are generally provided with on-load tap changing (OLTC)
gear. This is another major area of occurrence of fault.
3. All large transformers are oil immersed type. There is a possibility of oil leakage.
4. Transformers experience large inrush currents that are rich in harmonic content
at the time of switching.
5. A transformer may develop inter turn faults giving rise to local hot spots within the
winding.
6. Transformers may suffer from over fluxing due to under frequency operation at
rated voltage. Over fluxing may also be caused when the transformer is
subjected to over voltage at the rated frequency.
7. In case of sustained overload conditions, the transformer should not be allowed
to operate for long duration.

Tap changer

PROTECTION OF POWER TRANSFORMERS


(A) DIFFERENTIAL PROTECTION
This scheme is employed for the protection of transformers against internal
short circuits. It provides the best overall protection for internal faults.
The following factors affect the differential current in transformers and
should be considered while applying differential protection.
1. Magnetizing inrush current The normal magnetizing current drawn is
25% of the rated current. However during Magnetizing inrush the
current can be as high as 830 times the rated current for typically 10
cycles,
2. Overexcitation This is normally of concern in generatortransformer
units. Transformers are typically designed to operate just below the flux
saturation level. Any further increase from the max permissible voltage
level could lead to saturation of the core, in turn leading to substantial
increase in the excitation current drawn by the transformer.
3. CT Saturation External fault currents can lead to CT saturation. This
can cause relay operating current to flow due to distortion of the
saturated CT current.
4. Different primary and secondary voltage levels, that is the primary &
secondary CTs are of different types and ratios

Transformer Differential Relay


To account for the above variables less sensitive Differential Relays with percentage
characteristics in the range of 15 to 60% are applied to transformers. Additionally, in
modern microprocessor and numeric relays harmonic restraints can be applied.
Transformer Differential Relay Connections:

Harmonic Restraint:
The differential scheme tends to mal
operate due to magnetizing inrush.
The inrush current waveform is rich in
harmonics whereas the internal fault
current consists of only the
fundamental component. So to solve
the problem of inrush current, which
is neither an abnormal condition nor
a fault, additional restraint is
developed which comes to picture
only during inrush condition and is
ineffective during internal faults.

(B) RESTRICTED EARTH FAULT PROTECTION :


A differential relay has a certain minimum value of pick up for internal faults. Faults
with current below this value are not detected by the relay.
Winding-to-core faults, which are single phase to ground type, involving high
resistance, fall in this category.
Therefore for such type of faults RESTRICTED EARTH FAULT PROTECTION is
used. The reach of such a protection must be restricted to the winding of the
transformer; otherwise it may operate for any ground fault, anywhere in the system,
beyond the transformer, hence the name of this scheme.

(C) OVER CURRENT PROTECTION :


Over current protection is used for the purpose of providing back up protection for
large transformers. (above 5MVA).Two phase fault and one ground fault relay is
sufficient to provide OC protection to star delta transformer.

HV Bushing & connection

LV Connection to bus

(D) PROTECTION AGAINST OVERFLUXING :


The magnetic flux increases when voltage increases. This results in increased
iron loss and magnetizing current. The core and core bolts gets heated and the
lamination insulation is affected. Protection against overfluxing is required where
overfluxing due to sustained overvoltage can occur. The reduction in frequency
also increases the flux density and thus has the same effect of overfluxing.
The expression for flux in a transformer is given by
= K E/f
Where = flux, f = frequency, E = applied voltage and K is a constant.
To control flux, the ratio E/ f is controlled. When the ratio exceeds a threshold
value, it has to be detected. Electronic circuits with suitable relays are available to
measure this ratio. Overfluxing does not require high speed tripping and hence
instantaneous operation is undesirable when momentary disturbances occur. But
the transformer should be isolated in one or two minutes at the most if overfluxing
persists.

(E) PROTECTION AGAINST OVERHEATING :


The rating of a transformer depends on the temperature rise above an assumed
maximum ambient temperature. Sustained overload is not allowed if the ambient
temperature is equal to the assumed ambient temperature. The maximum safe
overloading is that which does not overheat the winding. The maximum allowed
temperature is about 95C. Thus the protection against overload depends on the
winding temperature.
In thermal image technique, a temperature sensing device like silicon resistor is placed
in the transformer oil near the top of the transformer tank. A CT is employed on the
H.V. side to supply current to a small heater. Both the temperature sensing device and
the heater are placed in a small pocket. The silistor is used as an arm of a resistance
bridge supplied from the stabilized dc source. An indicating instrument is energized
from the out of balance voltage of the bridge. Also the voltage across the silistor is
applied to a static control circuit which controls cooling pumps and fans, gives warning
of overheating and ultimately trips the transformer circuit breakers.

(F) PROTECTION AGAINST INCIPIENT FAULTS:


INCIPIENT FAULTS: Faults which are not serious at the beginning but which slowly
develops into serious faults are known as incipient faults.

BUCHHOLZ RELAY :
It is a gas actuated relay. When a fault develops slowly, it produces heat, thereby
decomposing solid or liquid insulating material in the transformer. The decomposition
of the insulating material produces inflammable gases. In between the transformer tank
and the conservator the Buchholz relay is placed and it is a slow acting device, the
minimum operating time is 0.1 s and the average time is 0.2 s.
When an incipient fault such as a windingto-core fault or an inter-turn fault occurs on
the transformer winding, there is severe
heating of the oil. This causes gases to be
liberated from the oil. There is a build-up of
oil pressure causing oil to rush into the
conservator. A vane is placed in the path of
surge of oil between the transformer and the
conservator. A set of contacts, operated by
this vane, is used as trip contacts of the
Buchholz relay This output of Buchholz
relay may be used to trip the transformer.

BUCHHOLZ RELAY :

GAS ANALYSIS :
The trapped gases in the conservator can give valuable clue to the type of damage
that takes place inside the transformer. This is because the insulation between the
winding turns, the insulation between the stampings of the core and the oil, all
liberate specific gases when they get heated up due to a fault. The presence of
these gases can be used as a signature of a particular type of damage that may
have taken place inside the transformer.

PRESSURE RELIEF VALVE :


An oil pressure relief valve is fitted at the top of the transformer tank. It is a spring
controlled valve placed at the top of the tank. Whenever a surge in the oil is
developed, it bursts , thereby allowing the oil to discharge rapidly. It operates when
the pressure exceeds 10 psi but closes automatically when the pressure falls below
the critical level. This avoids the explosive rupture of the tank and the risk of fire.

(G) PROTECTION AGAINST FIRE :


Power transformers are subject to fires from many sources. They often occur because of
deterioration of insulation in the transformer. This produces arcing which in turn overheats the
insulating oil and causes the tanks to rupture; further arcing then will start a fire. Fires are also
initiated by lightning and occasionally by dirty insulators on the outside of the tanks.
In spite of protection by these measures and expert maintenance, the risk of fire remains quite
high, and a fire protection system is always recommended and often required. In addition,
suppression systems are frequently installed.

Potrebbero piacerti anche