Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
070
Power Analyser
UMG 604
www.janitza.com
Installation and
Putting into Service
Temperature
measurement
input
RS232 RS485
2 digital inputs
2 digital outputs
Power supply voltage
AB
Profibus
(optional)
Ethernet
(optional)
4 x current
measurement
4 x voltage
measurement
UMG 604
Contents
General Information
Protected trademarks
Meaning of the symbols used
Display password
Homepage password
4
4
5
Inspection on receipt
Scope of supply
Available accessories
Notes on Use
7
7
8
Product Description
10
Intended use
UMG604 features
Methods of measurement
Operating concept
GridVis programming software
Three-phase 4-wire systems
Three-phase 3-wire systems
10
11
12
12
13
14
16
Use 18
Key functions
Concealed key (service)
Display mode
Programming mode
18
18
19
20
21
21
Installation 22
Installed position
22
Power supply voltage
23
Current measurement
24
Ammeter 26
Direct measurement
28
Voltage measurement
30
Interfaces 32
RS485 33
RS485 profibus DP V0 slave
36
Digital inputs and outputs
38
Temperature measurement input
42
43
43
43
44
45
45
46
Configuration 48
Current transformer ratio
48
Current measurement connection options 49
Voltage transformer ratio
50
Voltage measurement connection options 51
Interfaces 52
RS232 52
RS485 52
Ethernet (optional)
53
UMG 604
Profibus (optional)
54
Recordings 55
System information
56
Overrange 56
Serial number
57
Date 57
Firmware release
57
Time 57
58
Voltage measurement
Parameter list
69
71
Appendix 76
Measured value displays
Declaration of conformity
Dimensioned drawings
UMG604 connection example
76
77
78
79
80
Technical specifications
62
General information
62
Ambient conditions during operation
62
Transport and storage
62
Power supply voltage
63
Protection class
64
Inputs and outputs
65
Temperature measurement input
66
Interfaces 67
Measurement uncertainty
68
Measuring inputs
69
UMG 604
General Information
Protected trademarks
All trademarks and their resulting rights belong
to the respective holders of these rights.
UMG 604
c
m
Dangerous voltage!
Danger or risk of severe injury.
Disconnect the system and device
Note.
UMG 604
Inspection on receipt
Fault free and safe use of this device requires
appropriate transport, proper storage, erection
and assembly as well as careful operation and
maintenance. If it can be assumed that safe
operation is no longer possible, the device
must be immediately taken out of service and
secured against being accidentally started
up.
The device must be unpacked and packed
with the usual care, without the use of force
and only using suitable tools. The devices
must be visually inspected for perfect
mechanical condition. Please also note and
follow the installation instructions enclosed
with the device.
It can be assumed that safe operation is no
longer possible if the device, e.g.
has visible damage,
no longer works, despite intact mains power
supply,
has been exposed to unfavourable conditions
(e.g. storage outside the permissible climatic
limits without adjustment to the ambient
climate, condensation, or similar) for a lengthy
period or was exposed to unfavourable effects
or loads during transport (e.g. fall from a large
height even if there is no visible external
damage, or similar).
6
UMG 604
Scope of supply
Number Product No.
Name
1
52 16 xxx1)
1
33 03 070
1
51 00 116
1
10 01 807
1
10 01 808
1
10 01 809
1
10 01 810
1
89 10 051
1
08 01 505
UMG604 XX2)
Installation and start-up instructions.
CD with the following content:
- GridVis programming software,
- Functional descriptions, GridVis, UMG604 ..
- GSD file 0B41.GSD for profibus DP V0
Screw-type terminal, plug-in, 2 pin.
Screw-type terminal, plug-in, 3 pin.
Screw-type terminal, plug-in, 5 pin.
Screw-type terminal, plug-in, 6 pin.
Slot-head screwdriver (0.40x2 mm), ESD
Patch cable, 2m, twisted, grey. (UMG604 - PC/switch connection)
Available accessories
Product No.
Name
21 01 058
18 08 094
08 02 427
UMG 604
Notes on Use
Please read these operating instructions and
all other publications which have to be used
to work with this product (in particular for
installation, operation or maintenance).
Note and follow all safety instructions as well
as any warnings. If you do not follow the
instructions, personal injuries and/or damage
to the product could be the result.
Any unauthorised change or use of this device
which extends beyond the given mechanical,
electrical or other operating limits can cause
personal injuries and/or damage to the
product.
Any such unauthorised change is misuse
and/or negligence under the product's
warranty and therefore excludes the warranty
for cover of possible resulting injuries or
damage.
UMG 604
c
m
m
Important!
If the device is not operated according
to the instruction manual, protection
is no longer ensured and the device
can cause hazards.
UMG 604
Product Description
Intended use
The UMG604 is intended to be used for the
measurement and calculation of electrical
variables such as voltage, current, energy,
work, harmonic components, etc. in building
installations, at distribution boards, circuitbreakers and busbar trunking systems.
Measuring-circuit voltages and currents must
originate from the same system.
10
UMG 604
UMG604 features
- Measurement in IT and TN systems,
- 4 voltage measurement inputs
- 4 current measurement inputs,
- Continuous scanning of the voltage and current measurement inputs,
- Energy measurement, measurement uncertainty class 0.5 for ../5A current transformers,
- Energy measurement, measurement uncertainty class 1 for ../1A current transformers,
- Registers more than 800 measured values (readings),
- Fourier analysis 1st to 40th harmonic component for U, I, P (consumption/supply) and Q
(inductive/capacitive),
- Registering and storage of transients (>50 s),
- 2 digital inputs,
- 2 digital outputs,
- Temperature measurement input,
- LC display, backlight (optional),
- 2 keys,
- Profibus DPV0 (optional),
- RS485 (modbus RTU, modbus master),
- RS232,
- Ethernet (web server, EMAIL) (optional),
- Programming own applications in Jasic,
- Operating temperature range -10C .. +55C,
- Mounting on top hat rails 35 mm,
- Suitable for installation in distribution boards,
- Suitable for measurements in networks with frequency inverters.
11
UMG 604
Methods of measurement
Operating concept
m
12
UMG 604
PC
UMG
604
GridVis features
RS232
Interface
converter
RS232
PC
RS485
UMG
604
PC
Ethernet
UMG
604
13
UMG 604
UL-N / UL-L
66 V / 115 V
120 V / 208 V
127 V / 220 V
220 V / 380 V
230 V / 400 V
240 V / 415 V
260 V / 440 V
277 V / 480 V
14
UMG 604
L1
230/400V 50/60Hz
L2
L3
N
PE
L4 L1 L2 L3 N
Earthing the
system
4M
4M
4M
4M
4M
AC/DC
DC
Voltage measurement
Auxiliary power
UMG604
15
UMG 604
UL-L
66 V
115 V
120 V
127 V
200 V
230 V
240 V
260 V
277 V
347 V
280 V
400 V
415 V
440 V
480 V
16
UMG 604
L1
L1
400V 50/60Hz
L2
230/400V 50/60Hz
L2
L3
L3
N
Impedance
Impedance
L4
L1
L2 L3 N
L4
L1
L2 L3
Voltage measurement
Auxiliary power
UMG604
4M
4M
4M
Earthing the
system
4M
DC
AC/DC
4M
4M
4M
4M
4M
Earthing the
system
4M
AC/DC
DC
Voltage measurement
Auxiliary power
UMG604
17
UMG 604
Use
The UMG604 has a display, keys 1 and 2 and
the Service key to make it easier to install and
start up the UMG604 without a PC.
Important parameters such as current
transformers and device address are included
in the parameter list (see Appendix) and can
be directly programmed at the device.
A differentiation is made between operation
with the
display mode and
Programming mode.
Key functions
Press the key briefly:
page forwards
Digit/value +1
Press the key for long time:
page backwards
Digit/value -1
Simultaneously press both keys for around
1second and keep them pressed:
Switch between display mode and
programming mode.
18
Display
Key 1
Key 2
Concealed key
Keys 1 and 2
1
UMG 604
Display mode
After the power supply is resumed the device
is in Display mode.
In Display mode you can use Keys 1 and 2 to
page between the measured value displays.
1
N L1
V
Hz
Important!
The user can use the GridVis/Jasic to
reconfigure the function of the keys
and selection of the values to be
displayed.
UMG 604
Programming mode
The most important settings required for
operation of the UMG604 can be displayed
and changed in programming mode.
The parameter list in the Appendix contains
the addresses for the most important settings.
You can make further settings using the GridVis
software included in the scope of supply.
If you simultaneously press Keys 1 and 2 for
around 1 second, programming mode opens
via a password query. If a display password has
not been programmed, the first programming
menu opens directly.
Programming mode is denoted in the display
by the text PRG. The digits of the address
flash.
If you are in programming mode and have not
pressed a key for approximately 60 seconds or
simultaneously press Keys 1 and 2 for around
1 second, the device returns to display mode.
20
PRG
Address
Content
UMG 604
Display password
You can program a 4-digit display password
to make it difficult to accidentally change the
programming data directly at the device. A
display password is not set in the factory.
PRG
Homepage password
Content
Password mode
The
UMG604
differentiates
between
3 password modes for the homepage
password:
0 = The homepage password is not
queried.
2 = Changes to the configuration and the
display of measured values require the
password to be entered once.
128 = Each change to the configuration
requires renewed input of the
password.
Addr. Content
500
501
502
Display password
0 =the password is not queried.
Homepage, password mode
Homepage password
Forgot password?
After a safe connection between the UMG604
and GridVis please clear the password via
software.
21
UMG 604
Installation
Installed position
The UMG604 can be installed in control
cabinets or in small distribution boards
according to DIN 43880. It is mounted on a
35mm mounting v according to DIN EN60715.
It can be installed in any position.
22
UMG 604
Power supply
voltage Uh
Fuse
Disconnecting device
-
A disconnector or circuit-breaker
must be provided for the power
supply voltage in the building
installation.
- The disconnector must be installed
near the device and must be easy
for the user to reach.
-
The switch must be labelled as
a disconnecting device for this
device.
-
Voltages which are above the
allowable voltage range can destroy
the device.
m
c
Important!
The inputs for the supply voltage are
dangerous to touch!
23
UMG 604
Current measurement
The UMG604 is designed for the connection of
current transformers with secondary currents
of ../1A and ../5A. Only alternating currents,
not direct currents, can be measured.
Each current measurement input can be
permanently loaded with 6A or for 1 second
with 100 A.
L1
S1
L2
L3
N
S2
S1
S2
S1
S2
S1 S2
Verbraucher
Loads
c
m
c
24
Attention!
The current inputs are live.
Important!
The UMG604 is not suitable for the
measurement of direct voltages.
Earthing current transformers
If a connection is provided for earthing
the secondary winding, this must be
connected with earth.
UMG 604
Current
Current
Current
Current
UMG 604
Ammeter
If you not only want to measure the current
with the UMG604 but with an ammeter also,
the ammeter must be connected in series to
the UMG604.
26
UMG 604
Example
The current is measured via two current
transformers. Both current transformers
have a transformation ratio of 1000/5A. The
summation measurement is performed with a
5+5/5A summation current transformer.
The UMG604 must then be set as follows:
Primary current: 1000A + 1000A = 2000A
Secondary current:
5A
27
UMG 604
Direct measurement
Nominal currents up to 5 A can also be measured
directly with the UMG604. In this case it must
be noted that each current measurement input
may be loaded continuously with 6 A or for
1second with max 100 A.
As the UMG604 does not have any integrated
protection for the current measurement, this
protection (e.g. 6A fuse type C) must be
provided for during installation.
28
UMG 604
29
UMG 604
Voltage measurement
The UMG604 is designed for the measurement
of alternating voltages in 300 V systems in
which category III overvoltages can occur.
The UMG604 can only determine measured
values if a measurement-current voltage
greater than 10 Veff is applied to at least one
voltage measurement input.
The following must be noted when selecting
the instrument leads for the voltage
measurement:
The instrument leads required for the
voltage measurement must be suitable
for voltages up to 300 VAC to earth and
520VAC conductor to conductor.
Normal instrument leads must be fused by
an overcurrent protective device and routed
via disconnectors.
Short-circuit proof instrument leads must be
routed via disconnectors only.
Overcurrent
protective
devices
and
disconnectors must be positioned near the
device and must be easy for the user to
reach.
C
30
Disconnector
10A
(UL listed)
N
L3
L2
L1
Fig. 30.1 Connection example: Voltage measurement via short-circuit proof instrument leads.
c
m
Important!
The voltage measurement inputs are
hazardous live!
Important!
The UMG604 can only determine
measured values if a measurementcurrent voltage greater than 10 Veff
is applied to at least one voltage
measurement input.
UMG 604
Voltage
Voltage
Voltage
Fig. 31.1 Connection examples for voltage measurement in three-phase 4-conductor systems.
(Connection option 0, see page 51)
Voltage
Voltage
Fig. 31.2 Connection examples for voltage measurement in three-phase 3-conductor systems.
(Connection option 1, see page 51)
Measuring-circuit
voltages
and
currents must originate from the same
system.
Important!
Voltages above 300 VAC to earth
must be connected via voltage
transformers.
31
UMG 604
Interfaces
RS232
Shielding
PC
Com1
Mini Combicon,
5 pin
UMG 604
RS485
Terminating resistors
RS485 Bus
A
B
Correct
AB
Incorrect
33
UMG 604
Shields
A twisted, shielded cable is foreseen for connections using the RS485 interface.
Ground the shields of all cables leading to
the cabinet at the cabinet entry point.
Connect the shield extensively and with
good conductivity with a low external voltage ground.
Intercept the cable mechanically above
the ground clip in order to avoid damages
caused by cable movements.
Use suitable cable insert guides, such
as PG glands, to guide the cable into the
switch cabinet.
Cable
Strain relief
Cable shielding braid
Grounding clip
Low external voltage ground
Cable type
The cables used must be suitable for an environmental temperature of at least 80C.
Recommended cable types:
Unitronic Li2YCY(TP) 2x2x0.22 (Lapp cable)
Unitronic BUS L2/FIP 1x2x0.64 (Lapp cable)
m
C
34
Important!
Profibus, RS232, RS485 and
temperature measurement input are
not metallically separated from each
other.
UMG 604
Bus-Struktur
In case that the master UMG with terminated bus resistor will be removed, the bus is
not under operation.
In case that slave UMG with terminated bus
resistor will be removed or is not switched
on, the bus can be unstable.
UMGs which have no termination can be
replaced without any interruption of the
bus.
Master
Bus terminator on
T
Slave
Slave
Slave
Repeater
T
Slave
Slave
Slave
Slave
UMG 604
36
UMG 604
D-sub,
9 pin,
socket
D-sub,
9pin,
connector
Other
profibus
stations
Screw-type terminals
UMG 604
m
38
Attention!
The digital outputs are not shortcircuit-proof.
24V
DC
+
UMG 604
24V
AC
~
~
24V
DC
Digital outputs
18
K1
Digital
Output 2
17
16
Digital
Output 1
K2
Digital
Output 1
16
Digital
Output 2
17
18
K1
Digital outputs
UMG604
K2
UMG604
39
UMG 604
Digital inputs
UMG604
24V
DC
- +
S1
S2
+
24V
=
-
40
Digital
Input 2
20
3,9V 4,4k
3,9V 4,4k
21
m
Fig. 40.1 Connection example.
Digital
Input 1
19
Attention!
The polarity of the feeding voltage
must be respected for the digital
inputs.
UMG 604
S0 pulse input
UMG604
24V
DC
- +
S0 pulse generator
1,5k
+
24V
=
-
Digital
Input 2
20
1,5k
3,9V 4k
3,9V 4k
21
UMG 604
KTY83
m
m
42
UMG 604
Frequency measurement
43
UMG 604
Minimum voltage
A measuring-circuit voltage greater than
10Veff must be applied to at least one of the
voltage measurement inputs. If an adequately
high measuring-circuit voltage is not applied
the UMG604 cannot determine the system
frequency and can therefore also not take a
measurement.
44
At least one phase (L) and the neutral conductor (N) must be connected to the voltage measurement input for the measurement.
UMG 604
Phase sequence
Check the direction of the voltage rotating
field in the measured value display of the
UMG604.
A right rotating field usually exists.
45
UMG 604
46
UMG 604
47
UMG 604
Configuration
Current transformer ratio
You can assign each of the 4 current
transformer inputs its own current transformer
ratio. A current transformer ratio of 5 A/5 A
is programmed in the factory for all 4 current
transformer inputs.
You can program current transformers with the
same current transformer ratios in addresses
000 and 001. Program current transformers
with different current transformer ratios in
addresses 010 to 041.
A change in current transformer values in
address 000 or 001 overwrites the contents
of addresses 010 to 041 with the current
transformer values from addresses 000 and
001.
A change in current transformer values in
one of the addresses 010 to 041 deletes the
current transformer values in addresses 000
and 001.
48
Address
000
001
L1 L2 L3 L4 (primary)
L1 L2 L3 L4 (secondary)
010
011
020
021
030
031
040
041
L1 (primary)
L1 (secondary)
L2 (primary)
L2 (secondary)
L3 (primary)
L3 (secondary)
L4 (primary)
L4 (secondary)
UMG 604
Connection option 0
Address
Connection option
110
0=T
hree current transformers.
(Default factory setting)
1=T
wo current transformers
(Aron circuit)
Connection option 1
UMG 604
50
Address
002
003
L1 L2 L3 L4 (primary)
L1 L2 L3 L4 (secondary)
012
013
022
023
032
033
042
043
L1 (primary)
L1 (secondary)
L2 (primary)
L2 (secondary)
L3 (primary)
L3 (secondary)
L4 (primary)
L4 (secondary)
UMG 604
Address
Connection option
111
0=T
hree-phase 4-conductor
systems (default factory
setting)
1 = t hree-phase 3-conductor
systems
Connection option 0
Connection option 1
UMG 604
Interfaces
The UMG604 has 4 serial interfaces:
- RS485
- RS232
- Ethernet (optional)
- Profibus (optional)
All interfaces can be used simultaneously.
RS232
The following data must be programmed for
use of the RS232 interface:
- Baud rate,
- Operating mode.
Refer to the parameter list in the Appendix
for the default factory setting and the setting
ranges.
52
RS485
The following data must be programmed for
use of the RS485 interface:
- Device address,
- Baud rate,
- Operating mode.
Refer to the parameter list in the Appendix
for the default factory setting and the setting
ranges.
Addr.
Content
200
UMG 604
Ethernet (optional)
Fixed IP address
PC
UMG604
BootP
DHCP mode
DHCP enables fully automatic integration of a
UMG604 in an existing network without any
further configuration. On starting the UMG604
automatically imports the IP address, the net
mask and the gateway from the DHCP server.
The UMG604 is set in the factory to DHCP.
Zeroconf
Zeroconf allows fully automatic integration (allocation of IP address) of a UMG604 in an existing network without DHCP servers.
Patch cables
PC
UMG604
Patch
cables
Switch
Patch cables
Switch
Patch cables
UMG 604
Profibus (optional)
The UMG604 can manage 16 profibus profiles. Each profibus profile contains 128 data
bytes maximum.
The first data byte of the output area of the
PLC (programmable logic controller) always
contains the profile number of the profibus
profile required by the UMG604.
To request a profibus profile, write the profile
number in the first byte of the output area of
the PLC.
All system variables and global variables1) can
be individually scaled and converted into one
of the following formats:
- 8, 16, 32 bit integer with and without sign.
- 32 or 64 bit float format.
- Big or little Endian2).
PLC
Output area of the programmable controller
1. Byte = profile number
The variables for the
UMG604 follow from the
2nd byte.
Input area of the programmable controller
1. Byte = profile number
feedback
The requested variables
for the UMG604 follow
from the 2nd byte.
UMG604
Profibus profiles
Addr.
Content
200
54
UMG 604
Recordings
2 recordings are preconfigured in the default
factory setting of the UMG604. Recordings
are adjusted and extended via GridVis.
Recording 1
The following measured values are recorded
with the time base of 15 minutes:
Voltage L1-N
Voltage L2-N
Voltage L3-N
Voltage L4-N
Current L1
Current L2
Current L3
Current L4
Active power demand L1
Active power demand L2
Active power demand L3
Active power demand L4
(The mean value, minimum value and
maximum value are also recorded for each
measured value.)
Recording 2
The following measured values are recorded
with the time base of 1 hour:
Active power demand L1
Active power demand L2
Active power demand L3
Active power demand L4
Reactive power demand L1
Reactive power demand L2
Reactive power demand L3
Reactive power demand L4
55
UMG 604
System information
Overrange
Overranges are displayed as long as they exist
and cannot be acknowledged. An overrange
exists if at least one of the four voltage or
current measurement inputs lies outside their
specified measuring range.
If an overrange exists it is shown in the display
with EEEE.
The symbols L1, L2, L3 and L4 are used to
indicate at which input the overrange has
occurred. The V and A symbols indicate
whether the overrange occurred in the current
or in the voltage path.
m
56
Important!
Voltages and currents that lie outside
the permissible measuring range can
destroy the device.
L1 L2 L3 L4
VA
UMG 604
Serial number
Firmware release
Date
Time
UMG 604
Front film
The front film can be cleaned with a soft cloth
and standard household cleaning agent. Do
not use acids and products containing acid
for cleaning.
Battery
The internal clock is provided with power
from the power supply voltage. If the power
supply voltage fails the clock is supplied by
the battery. The clock supplies date and time
information, e.g. for recordings, minimum and
maximum values and events.
The life expectancy of the battery is at least
5 years, at a storage temperature of +45C.
The typical life expectancy of the battery is 8
to 10 years.
The device must be opened to change the
battery. If the device has been opened a
renewed safety check is necessary for safe
58
Disposal
Firmware update
If a firmware update has to be performed for
your UMG604 you can do this with the GridVis
software included in the scope of supply.
Service
Should questions arise, which are not
described in this manual, please contact the
manufacturer directly.
We will need the following information from
you to answer any questions:
- Device name (see rating plate),
- Serial name (see rating plate),
- Software release (see measured value
display),
- Measuring-circuit voltage and power supply
voltage,
- Precise description of the error.
UMG 604
Trouble shooting
Possible error
Cause
Remedy
No display.
Replace fuse.
Device is defective.
No current display.
Displayed
current
is too large or too
small.
EEEE and A
in the display.
59
UMG 604
Possible error
Cause
Remedy
Displayed
voltage
is too small or too
large.
Displayed voltage is
too small.
Overrange.
The peak voltage value at the measurement input has been exceeded
by harmonic components.
EEEE and V
in the display.
60
Voltage transformer
programmed.
incorrectly
Important!
Ensure
the
measurement inputs are not
overloaded.
UMG 604
Possible error
Cause
Remedy
No connection with
the device.
RS485:
- Device address is incorrect.
- Wrong protocol.
- Termination missing.
Ethernet:
- IP address incorrect
- The concealed key
(service) was used.
Device is defective.
61
UMG 604
Technical specifications
General information
Net weight
Device dimensions
Housing flammability class
Installed position
Fixing/mounting
Battery
Backlight lifetime
: 350g
: approx l=107.5 mm, b=90 mm, h=82 mm
(according to DIN 43871:1992)
: UL94V-0
: any
: 35 mm top hat rail
(according to IEC/EN 60999-1, DIN EN 50022)
: Type Lithium CR2032, 3V
(according to UL 1642)
: 40000h (50% of initial brightness)
UMG 604
63
UMG 604
Protection class
Class II according to IEC 60536 (VDE 0106, Part 1), i.e. a PE terminal is not required!
Protection against ingress of solid foreign
bodies and water
64
UMG 604
: 20 Hz
: 200 ms
: 18V. 28 V DC (typically 4 mA)
: 0 .. 5 V DC, current less than 0.5 mA
: up to 30 m unshielded
: greater than 30m shielded
: 0.08 - 1.5 mm2
:1
mm2, only one conductor may connected per
terminal connection!
65
UMG 604
: approx 200 ms
: PT100, PT1000, KTY83, KTY84
: max 4 kohm
Sensor type
Temperature range
Resistance range
Measurement
uncertainty
KTY83
KTY84
PT100
PT1000
-55 .. +175 C
-40 .. +300 C
-99 .. +500 C
-99 .. +500 C
1.5% rng
1.5% rng
1.5% rng
1.5% rng
66
: up to 30 m unshielded
: greater than 30 m shielded
: 0.08 - 1.5 mm2
:1
mm2, only one conductor may be connected
per terminal connection!
UMG 604
Interfaces
RS232
Protocol
Transfer rate
RS485
Protocol, modbus RTU
Transfer rate
RS485 (optional)
: Connector, SUB D 9 pin
Protocol, profibus (optional)
: Profibus DP/V0 according to EN 50170
Transfer rate
: 9.6 kbaud up to 12 Mbaud
Ethernet 10/100Base-TX (optional)
Connection
: RJ-45
Functions
: Modbus gateway, embedded web server (HTTP)
Protocols
: TCP/IP, EMAIL (SMTP), DHCP-Client (BootP),
Modbus/TCP(Port 502), ICMP (Ping), NTP, TFTP,
Modbus RTU over Ethernet (Port 8000), FTP.
67
UMG 604
Measurement uncertainty
The measurement uncertainty of the UMG604 applies to use of the following measuring ranges.
The measured value must lie within the given limits. Outside these limits the measurement
uncertainty is unspecified.
Measured value
Measurement uncertainties
Voltage
Current L
Current N
Power
Harmonic components U, I
Active energy
Current transformer ../5A
Current transformer ../1A
Reactive energy
Current transformer ../5A
Current transformer ../1A
Frequency
Internal clock
UMG 604
Measuring inputs
Voltage measurement
1)The UMG604 can only detect measurement values if a voltage L-N larger than 10Veff or a volt-
age L-L larger than 18Veff is applied to at least one voltage measurement input.
UMG 604
Current measurement
Nominal current
Rated current
Resolution
Measurement range
Crest-faktor
Measurement category
Specified impulse withstand voltage
Power input
Overload for 1 sec
Scanning frequency
70
:5A
:6A
: 1mA
: 0.001 .. 8.5Arms
: 2 (referring to 6 Arms)
: 300 V CAT III
: 4 kV
: approx 0.2 VA (Ri=5 mohm)
: 100 A (sinusoidal)
: 20 kHz
UMG 604
Parameter list
Add Name
Setting range
000
001
002
003
010
011
012
013
020
021
022
023
030
031
032
033
040
041
042
043
Units
Default
setting
0 .. 1000000
1 .. 5
0 .. 1000000
1 .. 480
A
A
V
V
5
5
400
400
0 .. 1000000
1 .. 5
0 .. 1000000
1 .. 480
0 .. 1000000
1 .. 5
0 .. 1000000
1 .. 480
0 .. 1000000
1 .. 5
0 .. 1000000
1 .. 480
0 .. 1000000
1 .. 5
0 .. 1000000
1 .. 480
A
A
V
V
A
A
V
V
A
A
V
V
A
A
V
V
5
5
400
400
5
5
400
400
5
5
400
400
5
5
400
400
71
UMG 604
Add Name
Setting range
Units
Default
setting
0 .. 9999
0 .. 1
0 .. 1
0 .. 1
112
113
114
0 .. 1
0 .. 1
0 .. 1
-
-
0
0
72
UMG 604
Add Name
Setting range
Units
Default
setting
1 .. 255
0 .. 4
1
4
0 .. 5
0 .. 6
0 .. 6
73
UMG 604
Add Name
Setting range
Units
Default
setting
0, 1, 2, 3 2
300
301
302
303
0 .. 255
0 .. 255
0 .. 255
0 .. 255
000
000
000
000
304
305
306
307
0 .. 255
0 .. 255
0 .. 255
0 .. 255
000
000
000
000
310
311
312
313
0 .. 255
0 .. 255
0 .. 255
0 .. 255
000
000
000
000
74
UMG 604
Add Name
Setting range
Units
Default
setting
400 Day
401 Month
402 Year
403 Hour
404 Minute
405 Second
406 Accept date and time
1 = accept set data
500 Device password
501 Homepage, password mode
502 Homepage, password
510 Activate EMAX option, licence part 1
511 Activate EMAX option, licence part 2
1 .. 31
1 .. 12
1 .. 9999
0 .. 23
0 .. 59
0 .. 59
0, 1
xx
xx
xxxx
xx
xx
xx
0
0 .. 9999
0, 2, 128, 130
0 .. 9999
xxxx
0
xxxx
0 .. 9999
0 .. 9999
xxxx
xxxx
0 .. 9999
0 .. 9999
xxxx
xxxx
600
601
602
603
0 .. 99
0 .. 16
0 .. 8
0 .. 9999
50
10
3
60
LCD, Contrast
LCD, Backlight, max. brightness
LCD, Backlight, min. brightness
LCD, Backlight,
-
-
-
s
75
UMG 604
Voltage
L2-N
Voltage
L3-N
Voltage
L4-N
Voltage
L1-L2
Voltage
L2-L3
Voltage
L3-L1
Current
L1
Current
L2
Current
L3
Current
L4
Active Power
demand L1
Active Power
demand L2
Active Power
demand L3
Active Power
demand L4
Active Power
demand L1..L3
Active Power
demand L1..L4
Reactive
Power L1
Reactive
Power L2
Reactive
Power L3
Reactive
Power L4
Reactive
Power L1..L3
Reactive
Power L1..L4
Active Energy
demand L1..L3
Active Energy
demand L1..L4
cos(phi)
L2
cos(phi)
L3
cos(phi)
L4
cos(phi)
L1..L3
Frequency
Rotating field
Temperature
input
Date
Time
Serial
number
76
Firmware
Release
UMG 604
Declaration of conformity
The UMG604 fulfils the safety requirements of:
Directive 2004/108/EC in conjunction with DIN EN 61326-1 (2006-10) as well as Directive
2006/95/EC in conjunction with EN 61010-1 (2002-08)
Safety requirements
Safety requirements for electrical instrumentation, control and laboratory equipment
: EN 61010-1 08:2002, IEC 61010-1:2001
Protection class
EMC requirements
Emitted interference, residential area : DIN EN61326-1:2006, Class B, IEC61326-2-1:2005
Interference immunity, industrial area : DIN EN 61326-1:2006, Table 2, IEC 61326-2-1:2005
Housing
: Electrostatic discharge, IEC 61000-4-2 (4 kV/8 kV)
: Electromagnetic fields, IEC 61000-4-3:2002 (10 V/m)
: Electromagnetic fields, IEC 61000-4-8:2000 (100A/m)
Power supply voltage
: Voltage dips, IEC 61000-4-11 (0.5 periods)
: Bursts, IEC 61000-4-4 (2 kV)
: Surge voltages, IEC 61000-4-5 (1 kV L to N)
: Conducted HF signals, IEC 61000-4-6 (3 V)
Measurement inputs
: Surge voltages, IEC 61000-4-5 (2 kV)
: Conducted HF signals, IEC 61000-4-6 (3 V)
: Bursts, IEC 61000-4-4 (2 kV)
RS485, RS232, ethernet, digital inputs and outputs, temperature measurement input
: Conducted HF signals, IEC 61000-4-6 (3 V)
: Bursts, IEC 61000-4-4 (1 kV)
RS485, ethernet, digital inputs and outputs, temperature measurement input
: Surge voltages, IEC 61000-4-5 (2 kV)
Electrical measuring transducer for converting alternating current variables into analog or digital
signals.
: DIN EN 60688 April 2002,
: IEC 60688:1992 +A1:1997+ A2:2001
77
UMG 604
Dimensioned drawings
Front view
78
Side view
UMG 604
79
UMG 604
Change address
PRG
Address
Content
PRG
80
Address
Content