LED
RUN
(Power)
Operating Status
ON
Power supply ON
OFF
ON
Option error
Drive connection
error
Normal operation
Communication
connected
Green
ERR
(Option Error)
Red
Flashing
OFF
COMM
(Communication
Status)
ON
Green
OFF
No data exchange
ON
BF
(PROFIBUS-DP
Error)
Red
Flashing
OFF
Waiting for
communication
procedure setting
Communication
setting error
Normal operation
Remarks
Power is supplied to the option, and the option hardware self-diagnostics check
is complete.
The drive has no power supply.
Option and drive are not connected properly and/or no power is supplied to
the option.
An internal, self-diagnostic error occurred in the option.
Self-diagnostic error occurred in the option.
Connection error between option and drive. This includes node address setting
errors to parameter F6-30 on the drive side.
Drive and option are properly connected.
Normal send/receive between the option and the PROFIBUS-DP master.
There is a problem establishing communication between the option and the
PROFIBUS-DP master.
Communication-related parameters are in the process of being set or initialized
by the PROFIBUS-DP master.
Communication parameter error from PROFIBUS-DP master.
LED shuts off when the PROFIBUS-DP master is finished setting
communication-related parameters.
No power
Possible Cause
Solution
Checking
connection with
the drive
Waiting for data
from the master
Problem connecting
to the drive
Incorrect data or
option time out
waiting for data
Sending or
receiving data
{: On / : Flashing / : Off
YASKAWA ELECTRIC SIEP C730600 42B 1000-Series Option SI-P3 Technical Manual