ASHRAE Compliance
Using Modern Air Handlers
I
ntroduction
Heat Removed
Sensible (MBH)
Latent (MBH)
Total (MBH)
Sensible/Total
% of Total Capacity
Required for O/A
Leaving Air
Dewpoint (F)
0%
Cfm
10%
400
20%
800
30%
1200
78.3
29.0
107.3
79.8
29.3
109.1
60.6
50.8
111.4
62.2
51.3
113.5
0.739
0.731
0.544
0.548
0%
27%
50%
69%
57.7
59.3
60.4
61.8
Over the last few years there has been a push to specify and
manufacture air conditioners with high SEER (System Energy
Efficiency Ratio) ratings which improve the energy efficiency of
the systems by increasing their sensible capacity and reducing
the compressors power consumption. This performance shift
in modern air handlers has come, however, at the expense of
the units ability to remove the latent energy component.
Furthermore, the Table shows that the air handler cannot maintain
a leaving air dewpoint below the typical maximum level of 60F.
Again, the occupants will find this objectionable. In addition, a
significant new concern is introduced in that the high moisture
levels provide the final ingredient required for mold, mildew
and viruses to thrive and multiply. (See Figure 1.)
TECHNICAL BULLETIN 14
r
tu
Fo
20%
Cfm 800
30%
1200
40%
1600
Heat Removed
Sensible (MBH)
Latent (MBH)
Total (MBH)
82.1
23.7
105.8
80.4
25.5
105.9
81.0
24.5
105.5
Sensible/Total
0.78
0.76
0.77
Leaving Air
Dewpoint (F)
57.0
56.6
56.3
ra
e
Needs
of
Living
Organism
pe
m
Te
od
Moisture
Figure 1) Required components of a living organism
No Preconditioning
Assumptions
O/A conditioned to 75Fdb /50% RH / 55F dewpoint
R/A conditions 78Fdb / 55% RH
S/A volume: 4000 cfm
100 rh(%) 80
60
160
140
30% O/A
120
20% O/A
0% O/A
100
80
w/ Preconditioning
60
20% O/A
30% O/A
40
Outside Air
20
W(grains/lbm)
What is the solution? How can high SEER rating air handlers
be used to meet ASHRAE 62 ventilation requirements without
causing a new set of problems?
An easy but effective solution is to precondition the outside air
so that it is similar to return air or neutral conditions. Any of
several different technologies can be used to dehumidify the
outside air to a level below the 60F dewpoint. (The target is a
55F dewpoint at design conditions.) In this way, the air handler
can continue to do its job as designed while maintaining high
efficiency and not requiring new energy to reheat the air when
the system overcools the space.
Table 2 shows the impact on the air handler when outside air
has been preconditioned to a 55F dewpoint. The simple addition
of dehumidification allows the air handler to do the job it was
originally installed to do.
40 t (F)
50
60
70
80
90
100
C onclusion
Existing and new air handlers cannot properly maintain internal
space humidity for the vast majority of North American
locations, where design summer moisture values are greater
than 70Fwb. A simple but effective solution is to precondition
the outside air to eliminate the moisture before it reaches the
air handler or the space.
(Please refer to Desert Aire Technical Bulletins 15 and 16 for detailed
sizing and application information for dehumidifiers.)