DESIGN OF ONE-WAY SLABS BY

INCORPORATING THE

STRUCTURAL CODE OF
SELECT ONE-WAY SLAB
TO DESIGN >>>>>

Y SLABS BY THE ACI MOMENT COEFFICIENT METHO

ORATING THE PROVISIONS OF THE NATIONAL

AL CODE OF THE PHILIPPINES VOLUME I - 2010


NUMBER OF SPANS

Created by:
GUILLERMO C. SUEGA, JR.
2014
Powered by: MICROSOFT EXCEL 2010

IENT METHOD

Design of Five-Span One-way Slab By ACI Moment Coefficient Method


STEP 1 - Enter the spans in meter in the yellow cells provided for
the 5-span one-way floor system layout given below:

1 m strip

3.00

3.60

3.00

3.40

4.00

FLOOR SYSTEM LAYOUT


STEP 2 - INPUT DATA
Enter the data or select from drop down list where required in the
yellow colored cells below:
Discontinuous End:

Spandrel

Width of Supports, b =

0.35 m

Rebar Grade =

40

Main Bar dia. =

12

mm

12
21

mm
MPa

0.70

kPa

Temperature Bar dia. =


ength of concrete = f'c =
Dead Loads:
Floor Finish =

fy =
Area Mbar =
Area Tbar =
=

276

MPa

113.10

mm2

113.10
0.85

mm2

Ceiling Loads =
0.40
kPa
Movable partition =
0.60
kPa
Others =
0.13
kPa
Superimposed Dead Loads>>>>>>>
Live Load =

4.80

Total =

1.83

kPa

Check on limitations of ACI Coefficients:


1. Adajcent spans' Long/short ratio <=1.2?
2. Live load to dead load ratio <=3 ?
Limits of ACI Coefficients are satisfied

YES
YES

STEP 3 - Click "VIEW OUTPUT" to see the design results.

NAVIGATION
BACK TO MAIN MENU
VIEW OUTPUT
CALCULATIONS

kPa

DETAILED COMPUTATION AND ANALYSIS

NSCP Vol. I - 2010 Pro

5-SPAN ONE-WAY SLAB


Maximum Spans:
3.65 m
3.25 m

l=
l=

{for end spans}


{for interior spans}

Sec. 409.6.2 page 4-44


Table 409-1 page 4-45

1. Solve for min. slab thickness for end and interior spans

Minimum thickness of no

for end span:

prestressed beams

Req'd h

0.40 + fy

125 mm

/one-way slabs

24
700
for interior span:
l
0.40 + fy
Req'd h
=
95 mm
28
700
min. Slab thickness, hs =
125
mm
WD = DL + weight of slab = DL + h(unit weight of concrete)
=
WD =

1.83
+
3.00
4.83 kPa.
2. Check for limitations of ACI Coefficient Method:
Are all adajcent spans' Long/short ratio <=1.2?
Live load = WL =
4.80 kPa.
WL/WD =
Ratio =
0.99

YES

Sec. 408.4.3 page 4-38

Live load to dead load ratio <=3 ?


Design by ACI Coefficient
3. Determine combined factored loads
Considering 1 meter strip:
WD =
4.83 kN/m
WL = Live load =
4.80 kN/m
WU = factored loads = 1.2WD + 1.6WL
WU =
13.48 kN/m

YES

Sec. 409.3.1 page 4-43

4. Design Moment - Maximum negative moment


Discontinuous End:
Spandrel
and
Slab span/s
>
3 meters
Mu =
WU l 2
1/10
3.35 m
15.12 kN m

l=
Mu =

Sec. 408.4.3 page 4-38

Sec. 408.4.3
page 4-38 to 4-39

{ave. Of adjacent clear spans}

5. Solve for d:
d = h - concrete cover - 0.5db

Sec. 407.8.1 page 4-31

d=
99 mm
6. Required Reinforcement
(For Top Bars)
Solve for :
X=
Mu

NSCP Vol. I - 2010 Pro

bd2 fy
X=
m=

0.00621196
fy
0.85f'c

m=
15.462
Minimum = 0.25f'c/fy =
=
1.4/fy =
Minimum =
req'd = 1- 1-2mX
m
req'd =
0.0065
(4/3) (req'd ) =
Use =
Spacing of Bars:
Req'd S = Ab/d =
=
Smax =
Smax = 3h =
USE Spacing =

0.0042
0.0051
0.0051 governs

0.0087
0.0065

170 mm
450 mm
375 mm

OR

Sec. 410.6.1 to 6.2


page 4-50
Eqn. (410-3),
(410-4) - minimum As

Sec. 410.6.3 page 4-50

or

Sec. 407.7.5 page 4-30

170 mm

7. Required Temperature Bars:


g =
0.002
Req'd S =Ab/gh =

Sec. 407.13.2.1,
page 4-34

Smax =
Smax = 5h =
USE Spacing =

450 mm
450 mm
625 mm

or

Sec. 407.13.2.2,
page 4-35

450 mm

8. Step 4 is repeated to determine negative moments at other supports and positive


moments at mid-spans using corresponding ACI Moment Coefficient then Steps 6
and 7 are also repeated for the required reinforcements, top bars for negative and
bottom bars for positive moments, in each of those locations.
9. Results are tabulated as shown in WORKSHEET Output5

8.00

8.00

8.00

NSCP Vol. I - 2010 Provisions

Sec. 409.6.2 page 4-44


Table 409-1 page 4-45
Minimum thickness of nonprestressed beams
/one-way slabs

Sec. 408.4.3 page 4-38

NAVIGATION
BACK TO TOP
BACK TO MAIN MENU

VIEW OUTPUT

Sec. 408.4.3 page 4-38

Sec. 409.3.1 page 4-43

Sec. 408.4.3
page 4-38 to 4-39

Sec. 407.8.1 page 4-31


NSCP Vol. I - 2010 Provisions

Sec. 410.6.1 to 6.2


page 4-50
Eqn. (410-3),
(410-4) - minimum As

Sec. 410.6.3 page 4-50

Sec. 407.7.5 page 4-30

Sec. 407.13.2.1,
page 4-34

Sec. 407.13.2.2,
page 4-35

NAVIGATION
BACK TO TOP
BACK TO MAIN MENU

VIEW OUTPUT

Design of Four-Span One-way Slab


By ACI Moment Coefficient Method
STEP 1 - Enter the spans in meter in the yellow cells provided for
the 4-span one-way floor system layout given below:

1 m strip

2.40

2.70

3.00

2.80

FLOOR SYSTEM LAYOUT

BACK TO MAIN MENU

DETAILED COMPUTATION AND ANALYSIS


4-SPAN ONE-WAY SLAB
Solution:

2.50 m
{for end spans}
l=
2.70 m
{for interior spans}
l=
1. Solve for slab thickness and total dead load
l
0.40 + fy
Req'd h
=
85 mm
24
700
l
0.40
+
fy
Req'd h
=
80 mm
28
700
min. Slab thickness, hs =
85
mm
WD = DL + weight of slab = DL + h(unit weight of concrete)
=
WD =

3.10
+
2.006
5.11 kPa.
2. Check for limitations of ACI Coefficient Method:
Are all adajcent spans' Long/short ratio <=1.2?
LL/DL
=
0.71
Live load to dead load ratio <=3 ?
YES
Design by ACI Coefficient
3. Determine combined factored loads
Considering 1 meter strip:
WD =
5.11 kN/m
WL = Live load =
3.60 kN/m
WU = factored loads = 1.2WD + 1.6WL
WU =
11.89 kN/m

YES

4. Design Moment - Maximum negative moment


Discontinuous End:
Shear wall
and
Slab span/s
<=
3 meters
Mu =
WU l 2
1/12
2.60 m
6.70 kN m

l=
Mu =

{ave. Of adjacent clear spans}

5. Solve for d:
d = h - concrete cover - 0.5db
d=
60 mm
6. Required Reinforcement
(For Top Bars)
Solve for
X=
Mu

bd2 fy
X=
m=

0.0074884
fy
0.85f'c

m=
15.611
Minimum = 0.25f'c/fy =
=
1.4/fy =

0.0041
0.0051

OR

Minimum =
req'd =

0.0051 governs

1- 1-2mX
m
0.0080

req'd =
(4/3) (req'd ) =
Use =
Spacing of Bars:
Req'd S = Ab/d =
=
Smax =
Smax = 3h =

0.0106
0.0080

160 mm
450 mm
255 mm

USE Spacing =

or
160 mm

7. Required Temperature Bars:


g =
0.002
Req'd S =Ab/gh =
Smax =
Smax = 5h =
USE Spacing =

460 mm
450 mm
425 mm

or
425 mm

8. Step 4 is repeated to determine negative moments at other supports and positive


moments at mid-spans using corresponding ACI Moment Coefficient then Steps 6
and 7 are also repeated for the required reinforcements, top bars for negative and
bottom bars for positive moments, in each of those locations.
9. Results are tabulated as shown in WORKSHEET Output4

w cells provided for

STEP 2 - INPUT DATA


Enter the data or select from drop down list where r
yellow colored cells below:
6.00

6.00

6.00

Discontinuous End:
Width of Supports:
b=

Shear wall
0.30

Rebar Grade =

40

Main Bar dia.

10

Temperature Bar dia. =


f'c =
Floor Finish =
Ceiling Loads =
Movable partition =
Others =
Superimposed Dead Loads:
Live Load =

10
20.8
0.80
0.50
0.80
1.00
>>>>>>>
3.60

Check on limitations of ACI Coefficients:


1. Adajcent spans' Long/short ratio <=1.2?
2. Live load to dead load ratio <=3 ?
Limits of ACI Coefficients are satisfied

STEP 3 - Click "VIEW OUTPUT" to see the design resu

NAVIGATION
BACK TO MAIN MENU

VIEW OUTPUT

CALCULATIONS

NSCP Vol. I - 2010 Provisions

Sec. 409.6.2 page 4-44


Table 409-1 page 4-45
Minimum thickness of nonprestressed beams
/one-way slabs

Sec. 408.4.3 page 4-38


Sec. 408.4.3 page 4-38

Sec. 409.3.1 page 4-43

Sec. 408.4.3
page 4-38 to 4-39

Sec. 407.8.1 page 4-31

Sec. 410.6.1 to 6.2


page 4-50

Eqn. (410-3),
(410-4) - minimum As

Sec. 410.6.3 page 4-50

Sec. 407.7.5 page 4-30

Sec. 407.13.2.1,
page 4-34
Sec. 407.13.2.2,
page 4-35

ts at other supports and positive


oment Coefficient then Steps 6
ments, top bars for negative and

r select from drop down list where required in the

Shear wall
m

mm
mm
MPa
kPa
kPa
kPa
kPa
>>>>>>>

fy =
Area bar =

276

MPa

78.54

mm2
mm2

78.54
0.85

Total =

3.10

kPa

Area Tbar =

kPa

ions of ACI Coefficients:


' Long/short ratio <=1.2?

efficients are satisfied

IEW OUTPUT" to see the design results.

CALCULATIONS

YES
YES

NAVIGATION
BACK TO TOP

BACK TO TOP
BACK TO MAIN MENU

VIEW OUTPUT

NAVIGATION
BACK TO TOP
BACK TO MAIN MENU

VIEW OUTPUT

Design of Three-Span One-way Slab


By ACI Moment Coefficient Method
STEP 1 - Enter the spans in meter in the yellow cells provided for
the 3-span one-way floor system layout given below:

1 m strip

4.00

3.60

3.20

BACK TO MAIN MENU

DETAILED COMPUTATION AND ANALYSIS


3-SPAN ONE-WAY SLAB
Solution:
3.70 m
{for end spans}
l=
3.30 m
{for interior spans}
l=
1. Solve for slab thickness and total dead load
l
0.40 + fy
Req'd h
=
140 mm
Req'd h

24
l

700
0.40 + fy

110 mm

28
700
min. Slab thickness, hs =
140
mm
WD = DL + weight of slab = DL + h(unit weight of concrete)
=
WD =

2.80
+
3.304
6.10 kPa.
2. Check for limitations of ACI Coefficient Method:
Are all adajcent spans' Long/short ratio <=1.2?
LL/DL
=
0.49
Live load to dead load ratio <=3 ?
YES
Design by ACI Coefficient
3. Determine combined factored loads
Considering 1 meter strip:
WD =
6.10 kN/m
WL = Live load =
3.00 kN/m
WU = factored loads = 1.2WD + 1.6WL

YES

WU =

12.12 kN/m
4. Design Moment - Maximum negative moment
Discontinuous End:

Unrestrained

Slab span/s

3 meters

Mu =

>
1/10

WU l 2

3.50 m
14.85 kN m

l=
Mu =

and

{ave. Of adjacent clear spans}

5. Solve for d:
d = h - concrete cover - 0.5db
d=
114 mm
6. Required Reinforcement
(For Top Bars)
Solve for
X=
Mu

bd2 fy
X=
m=

0.0036808
fy
0.85f'c

m=
19.328
Minimum = 0.25f'c/fy =
=
1.4/fy =

0.0033
0.0041

OR

Minimum =

0.0041 governs

req'd =

1- 1-2mX
m
req'd =
0.0038
(4/3) (req'd ) =
Use =
Spacing of Bars:
Req'd S = Ab/d =
=
Smax =
Smax = 3h =

0.0051
0.0041

240 mm
450 mm
420 mm

USE Spacing =

or
240 mm

7. Required Temperature Bars:


g =
0.002
Req'd S =Ab/gh =
Smax =
Smax = 5h =
USE Spacing =

280 mm
450 mm
700 mm

or
280 mm

8. Step 4 is repeated to determine negative moments at other supports and positive


moments at mid-spans using corresponding ACI Moment Coefficient then Steps 6
and 7 are also repeated for the required reinforcements, top bars for negative and
bottom bars for positive moments, in each of those locations.
9. Results are tabulated as shown in WORKSHEET Output3

w cells provided for

8.00

8.00

8.00

STEP 2 - INPUT DATA


Enter the data or select from drop down list where required in
yellow colored cells below:
Discontinuous End:
Unrestrained
Width of Supports:
b=
0.3 m
Rebar Grade =

50

Main Bar dia. =

12

mm

Temperature Bar =
f'c =

10
21

mm
MPa

Floor Finish =
Ceiling Loads =
Movable partition =
Others =
Superimposed Dead Loads:
Live Load =

0.80
0.70
0.80
0.50

kPa
kPa
kPa
kPa
>>>>>>>

3.00

kPa

Check on limitations of ACI Coefficients:


1. Adajcent spans' Long/short ratio <=1.2?
2. Live load to dead load ratio <=3 ?
Limits of ACI Coefficients are satisfied
STEP 3 - Click "VIEW OUTPUT" to see the design results.

NAVIGATION
BACK TO MAIN MENU

VIEW OUTPUT

CALCULATIONS

NSCP Vol. I - 2010 Provisions


Sec. 409.6.2 page 4-44
Table 409-1 page 4-45
Minimum thickness of nonprestressed beams
/one-way slabs

Sec. 408.4.3 page 4-38


Sec. 408.4.3 page 4-38

Sec. 409.3.1 page 4-43

Sec. 408.4.3
page 4-38 to 4-39

Sec. 407.8.1 page 4-31

Sec. 410.6.1 to 6.2


page 4-50

Eqn. (410-3),
(410-4) - minimum As

Sec. 410.6.3 page 4-50

Sec. 407.7.5 page 4-30

Sec. 407.13.2.1,
page 4-34
Sec. 407.13.2.2,
page 4-35

ts at other supports and positive


oment Coefficient then Steps 6
ments, top bars for negative and

om drop down list where required in the

fy =
Area bar =

345

MPa

113.10

mm2
mm2

78.54
0.85

Total =

2.80

kPa

Area Tbar =

YES
YES

UT" to see the design results.

CALCULATIONS

NAVIGATION
BACK TO TOP
BACK TO MAIN MENU
VIEW OUTPUT

Design of Two-Span One-way Slab


By ACI Moment Coefficient Method
STEP 1 - Enter the spans in meter in the yellow cells provided for
the 2-span one-way floor system layout given below:

1 m strip

5.00

4.00

FLOOR SYSTEM LAYOUT

BACK TO MAIN ME

DETAILED COMPUTATION AND ANALYSIS


2-SPAN ONE-WAY SLAB
4.70 m
l=
{based on maximum clear span}
1. Solve for minimum slab thickness and total dead load
l
0.40 + fy
Req'd h
=
175 mm
24
700

USE Thickness of slab, hs =


175 mm
WD = DL + weight of slab = DL + hs(unit weight of concrete)
=
WD =

3.4
+
4.13
7.53 kPa.
2. Check Limitations of ACI Coefficient Method :
Are all adajcent spans' Long/short ratio <=1.2?
LL/DL
=
0.40
Live load to dead load ratio < =3?
YES

NO

3. Determine combined factored loads


Considering 1 meter strip:
WD =
7.53 kN/m
WL = Live load =
3 kN/m
WU = factored loads = 1.2WD + 1.6WL
WU =
13.84 kN/m
4. Design Moment - Maximum negative moment
Discontinuous End:
Spandrel
and
Slab span/s
>
3 meters
Mu =
WU l 2
1/ 9
4.20 m
27.12 kN m

l=
Mu =

{ave. Of adjacent clear spans}

5. Solve for d:
d = h - 20 mm cover - 0.5db
d=
149 mm
6. Required Reinforcement
(For Top Bars)
Solve for
X=
Mu

bd2 fy
m=

X=
fy
0.85f'c

0.003934

m=
19.328
Minimum = 0.25f'c/fy =
=
1.4/fy =
Minimum =
1- (1-2mX)
m
req'd =
0.0041
(4/3) (req'd ) =
Use =
Spacing of Bars:

0.0033
0.0041
0.0041 governs

req'd =

0.0055
0.0041

OR

Req'd S = Ab/d =
=
Smax =
Smax = 3h =

180 mm
450 mm
525 mm

USE Spacing =

or
180 mm

7. Required Temperature Bars:


g =
0.002 for fy =
Req'd S =Ab/gh =
Smax =
Smax = 5h =
USE Spacing =

220 mm
450 mm
875 mm

345 MPa.

or
220 mm

8. Step 4 is repeated to determine negative moments at other supports and positive


moments at mid-spans using corresponding ACI Moment Coefficient then Steps 6
and 7 are also repeated for the required reinforcements, top bars for negative and
bottom bars for positive moments, in each of those locations.
9. Results are tabulated as shown in WORKSHEET Output2

cells provided for

STEP 2 - INPUT DATA


Enter the data or select from drop down list where requir
yellow colored cells below:
Discontinuous End:
Spandrel
Width of Supports:
b=
0.3
m

10.00
Rebar Grade =

50

Main Bar dia. =

12

mm

Temperature bar dia =

10
21

mm
MPa

f'c =

Floor /Finish = 0.40


Ceiling Loads = 1.00
Movable partition = 1.00
Others = 1.00
Superimposed Dead Loads:
10.00

Live Load =

3.00

kPa
kPa
kPa
kPa
>>>>>>>
kPa

Check on limitations of ACI Coefficients:


1. Adajcent spans' Long/short ratio <=1.2?
2. Live load to dead load ratio <=3 ?
Limits of ACI Coefficients are not met, change input value
STEP 3 - Click "VIEW OUTPUT" to see the design results.

NAVIGATION
BACK TO MAIN MENU

VIEW OUTPUT

CALCULATIONS

NSCP Vol. I - 2010 Prov.


Sec. 409.6.2 page 4-44
Table 409-1 page 4-45
Minimum thickness of

non-prestressed beams
/one-way slabs

Sec. 408.4.3 page 4-38


Sec. 408.4.3 page 4-38

Sec. 409.3.1 page 4-43

Sec. 408.4.3
page 4-38 to 4-39

Sec. 407.8.1 page 4-31

Sec. 410.6.1 to 6.2


page 4-50
Eqn. (410-3),
(410-4) - minimum As

Sec. 410.6.3 page 4-50

Sec. 407.7.5 page 4-30

Sec. 407.13.2.1,
page 4-34
Sec. 407.13.2.2,
page 4-35

s at other supports and positive


ment Coefficient then Steps 6
nts, top bars for negative and

from drop down list where required in the

fy =
Area bar =
Area Tbar =
=

Total =

345

MPa

113.10

mm2

78.54
0.850

mm2

3.4

kPa

NO
YES
s are not met, change input values relevant to limitation with NO indicated next to it

TPUT" to see the design results.

CALCULATIONS

NAVIGATION
BACK TO TOP
BACK TO MAIN MENU

VIEW OUTPUT

VIEW OUTPUT

NO indicated next to it

DESIGN RESULTS OF 5-SPAN ONE-WAY SLAB USING ACI MOMENT COEFFICIENTS


DESIGN DATA
f'c =
21 MPa
4.83 kPa
Dead Load
fy =
276 MPa
4.80 kPa
Live Load
12 mm
125 mm
Main bar
thickness =
12 mm
d=
99 mm
Temp. bar
TABULATION OF DESIGN RESULTS

Spcg.(mm)
Use Spcg.

1/24
3.94
0.0016
0.0016
0.0022
520
375

AB
2.65
13.48
1/14
6.76
0.0028
0.0028
0.0038
300
300

Spcg. Temp.
Bars

450

450

Support/Span

Clear Span (m)


Wu (kN/m)

Coeff.
Mu (kN)
X
Req'd
Use

1/10
11.73
0.0048
0.0050
0.0051
220
220

BC
3.25
13.48
1/16
8.90
0.0037
0.0038
0.0050
220
220

1/11
10.66
0.0044
0.0045
0.0051
220
220

CD
2.65
13.48
1/16
5.91
0.0024
0.0025
0.0033
340
340

450

450

450

450

SKETCH OF DESIGN DETAILS


12 mm temp. bars @
450 mm
12 mm @
12 mm @
220 mm
220 mm

12 mm @
375 mm

12 mm @
300 mm
3.00 m

12 mm @
220 mm
3.60 m

12
340

COEFFICIENTS

1/11
9.95
0.0041
0.0042
0.0051
220
220

DE
3.05
13.48
1/16
7.84
0.0032
0.0033
0.0044
250
250

450

450

1/10
15.12
0.0062
0.0065
0.0065
170
170

EF
3.65
13.48
1/14
12.82
0.0053
0.0055
0.0055
200
200

1/24
7.48
0.0031
0.0031
0.0042
270
270

450

450

450

F DESIGN DETAILS

12 mm @
220 mm

12 mm @
170 mm

12 mm @
270 mm

125 mm

mm @
mm
3.00 m

12 mm @
250 mm
3.40 m

12 mm @
200 mm
4.00 m

NAVIGATION
5-SPAN
CALCULATIONS
BACK TO MAIN MENU

DESIGN RESULTS OF 4-SPAN ONE-WAY SLAB USING ACI MOMENT COEFFICIENTS


DESIGN DATA
f'c =
20.8 MPa
5.11 kPa
Dead Load
fy =
276 MPa
3.60 kPa
Live Load
10 mm
85 mm
thickness =
Main Bar
10 mm
d=
60 mm
Temp. Bar
TABULATION

Spcg.(mm)
Use Spcg.

1/12
4.37
0.0049
0.0051
0.0051
250
250

AB
2.10
11.89
1/14
3.74
0.0042
0.0043
0.0051
250
250

Spcg. Temp.
Bars

425

425

Support/Span

Clear Span (m)


Wu (kN/m)

Coeff.
Mu (kN)
X
Req'd
Use

1/12
5.01
0.0056
0.0059
0.0059
220
220

BC
2.40
11.89
1/16
4.28
0.0048
0.0050
0.0051
250
250

425

425

1/12
6.44
0.0072
0.0077
0.0077
170
170

CD
2.70
11.89
1/16
5.42
0.0061
0.0064
0.0064
200
200

1/12
6.70
0.0075
0.0080
0.0080
160
160

425

425

425

SKETCH OF DESIGN DETAILS


10 mm temp. bars @
10 mm @
250 mm

10 mm @
220 mm

10 mm @
170 mm

B
10 mm @
250 mm

0.30

C
10 mm @
250 mm

0.30
2.10 m

425

10 mm @
200 mm

0.30
2.40 m

2.70

NAVIGATION
4-SPAN
CALCULATIONS
BACK TO MAIN MENU
DE
2.50
11.89
1/14
5.31
0.0059
0.0062
0.0062
200
200

1/12
6.19
0.0069
0.0073
0.0073
170
170

425

425

mm
10 mm @
160 mm

10 mm @
170 mm

85
mm

D
10 mm @
200 mm
0.30
m

0.30
2.50

DESIGN RESULTS OF 3-SPAN ONE-WAY SLAB USING ACI MOMENT COEFFICIENTS


DESIGN DATA
f'c =
21 MPa
6.10 kPa
Dead Load
fy =
345 MPa
3.00 kPa
Live Load
12 mm
140 mm
thickness =
Main Bar
10 mm
d=
114 mm
Temp. Bar
TABULATION

Spcg.(mm)
Use Spcg.

0
0.00
0.0000
0.0000
0.0041
240
240

AB
3.70
12.12
1/11
15.09
0.0037
0.0039
0.0041
240
240

Spcg. Temp.
Bars

280

280

Support/Span

Clear Span (m)


Wu (kN/m)

Coeff.
Mu (kN)
X
Req'd
Use

1/10
14.85
0.0037
0.0038
0.0041
240
240

BC
3.30
12.12
1/16
8.25
0.0020
0.0021
0.0028
350
350

280

280

1/10
11.65
0.0029
0.0030
0.0040
250
250

CD
2.90
12.12
1/11
9.27
0.0023
0.0024
0.0031
310
310

0
0.00
0.0000
0.0000
0.0041
240
240

280

280

280

SKETCH OF DESIGN DETAILS


10 mm temp. bars @
12 mm @
240 mm

12 mm @
240 mm

0.3

C
12 mm @
350 mm

0.3
3.70 m

mm

12 mm @
250 mm

B
12 mm @
240 mm

280

12 mm @
310 mm

0.3
3.30 m

2.90

NAVIGATION
3-SPAN
CALCULATIONS
BACK TO MAIN MENU

12 mm @
240 mm

140
mm

0.30

DESIGN RESULTS OF 2-SPAN ONE-WAY SLAB USING ACI MOMENT COEFFICIENTS


DESIGN DATA
f'c =
21 MPa
7.53 kPa
Dead Load
fy =
345 MPa
3.00 kPa
Live Load
12 mm
175 mm
thickness =
Main Bar
10 mm
d=
149 mm
Temp. Bar
TABULATION OF RESULTS:
Support/Sp
an

Spcg.(mm)
Use Spcg.

1/24
12.73
0.0018
0.0019
0.0025
300
300

AB
4.7
13.84
1/14
21.83
0.0032
0.0033
0.0041
180
180

Spcg. Temp.
bars

220

220

Clear span(m)
Wu (kN/m)

M Coeff.
Mu (kN)
X
Req'd
Use

1/ 9
27.12
0.0039
0.0041
0.0041
180
180

BC
3.7
13.84
1/14
13.53
0.0020
0.0020
0.0027
280
280

1/24
7.89
0.0011
0.0012
0.0015
490
450

220

220

220

SKETCH OF DESIGN DETAILS


Temp. Bars :
10 mm @

12 mm @
300 mm

A
0.30

12 mm @
180 mm
4.70

12 mm @
180 mm

B
0.30

12 mm @
280 mm
3.70

220

12 mm @
450 mm
h=
175
mm

C
0.30

NAVIGATION
2-SPAN
CALCULATIONS
BACK TO MAIN MENU