Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Boiler tuning is something of a balancing act. Feedwater enters the boiler through a series of low- and highpressure steam heaters into the drum. The water then journeys through the water walls of the furnace and
absorbs heat until steam is formed in the main steam drum.
This steam then enters the main steam line and passes through a series of superheaters and desuperheaters
until it finally ends up at the turbine governor and/or stop valves. The boiler controls the turbine throttle pressure
by modulating the boiler-firing rate. This means that the amount of fuel and air that is going into the furnace is
increased or decreased depending on whether the turbine requires more or less steam pressure.
There are four usual modes of operation in the world of drum boilers: base mode, boiler-following mode,
turbine-following mode, and coordinated control (Table 1). Each of these operating modes is described in the
following paragraphs.
Table 1.
In general, the boiler master will be either in auto or manual control mode. The turbine is another matter.
Turbine controls generally have a number of stand-alone loops such as megawatt, pressure, valve position,
or speed which are control loops that do not respond to the DCS turbine master. If the turbine controls are
not looking at the front end, then as far as the front end is concerned, the turbine is in manual control. For our
purposes, "auto" under the turbine master heading in Table 1 means the front end is controlling the turbine
governor valves.
Base Mode. In this mode, there is no automatic response to changes in main steam or throttle pressure or
megawatt setpoint by the front-end controllers. An operators steady hand is required to make the final boiler
control adjustments. The turbine might be in one of its own stand-alone loops, but the turbine master has no
control of the plant. Many plants operate in this or a similar mode prior to upgrading their turbine controls to a
DCS.
Boiler-Following Mode. In this mode of operation, the boiler master is in automatic and the turbine is not. This is
an automatic control loop, controlling steam pressure. Depending on the boiler, it can be well controlled.
Generally, this is the loosest of the three typical automatic front-end modes of operation (Figure 1).
1.
Loaded questions. A typical boiler-following response following a setpoint change.Source: Tim Leopold
This is one of those loops that uses the dreaded derivative gain. The proportional gain is normally pretty high,
the integral action slow, and the derivative is absolutely a must. The real keys to tuning the front end are a few
simple concepts. For example, dont add to an upset; that is, dont have any of your gains disproportionately
high. We use the derivative because we are trying to anticipate the steam pressure deviation.
The feedforward signal is an important part of this control loop and is often referred to as target steam flow.
Target steam flow is the measured steam flow multiplied by the ratio of throttle pressure setpoint to throttle
pressure. Typically, there is a function generator designed such that 0% to 100% of the input signal is
proportional to a 0% to 100 % output signal. The nicely dynamic nature of the ratio helps the boiler master
move in the right direction. Additional "kickers" may also be available. One option is a throttle pressure setpoint
kicker that adds a little to the feedforward signal if the setpoint is changed. The derivative action of the
controller also acts as a kicker.
Turbine-Following Mode. In many ways, this is my favorite plant operating mode, because it is the easiest to
tune. It also offers a good strong safety net to operators in times of crisis. In turbine-following mode the boiler
master is in manual and the turbine master is in automatic mode. The turbine master controls throttle pressure
by modulating the turbine governor valves. Megawatts are then produced in the generator and pushed to the
grid as a function of the boiler load.
Compared to the slow and sometimes lumbering response of the boiler, turbine response is usually fast and
agile. Proportional gains are usually moderately large, and the integral action can be quite fast. Although
adaptive tuning is possible, there usually isnt the need for this; many units use only one value for the
proportional and/or the integral gain. Also, the need for a feedforward is minimal. The turbine governor valves
operate as one large pressure control valve that can easily control throttle pressure when the control loops are
well-tuned.
Turbine-following mode is also a favorite among operators. If the plant is in coordinated mode, and the unit
starts to go out of control for almost any reason, operators simply have to put the boiler master into manual.
Immediately, the controls will automatically default to turbine-following mode. The valves open or close, as
necessary to control the main steam pressure. Meanwhile, because the firing rate has steadied, the boiler
controls will soon settle out.
Figure 2 plots the data taken during start-up of a 320-MW power plant. At the lower left corner you can see
where the valve transfer occurred. The valve transfer is a process in which the turbine, upon start-up, transfers
control from the stop valve to the governor valve. There are actually two sets of valves in the main steam line
before the turbine: the main stop valve and the governor valves. The next interesting point on this figure is the
area that I call the "disturbing delta." There was a long period, during this load ramp, when the difference
(delta), between the throttle pressure and the throttle pressure setpoint was virtually constant (the purple and
green lines at the first vertical white dotted line). When we expect the controls to act one way, and they do not,
its time to investigate.
2.
Under control. Taming a control loop that switched out the integral control on a load ramp. Source: Tim
Leopold
During a change in unit load demand, in coordinated control, it is common practice to decrease the integral
action of the boiler master controller to zero until the load ramp is finished. This strategy was used in all of the
turbine and boiler master controller modes. This is a case where more is definitely not better; there was a touch
of feedforward, based on boiler demand, substantial proportional gain, and no integral gain when I looked at
the logic. Tuned as it was, the error signal between throttle pressure and throttle pressure setpoint will never go
away.
I tried to tune out the error without success. Although the error decreased, as shown in Figure 2, we soon
discovered that the tuning was not robust under all operating conditions. We then downloaded the necessary
logic modifications (the second white vertical dotted line), causing the unit to drop out of turbine-following and
into base load mode, and then back again. When the logic modifications were made, from that point on (the
third white vertical dotted line) you can see good control of the throttle pressure. This is how a well-tuned
turbine-following mode should operate.
Next comes the tuning of the controllers. In general, the turbine master is the easier of the two components to
tune, so that is the one to attack first. The gains will be less aggressive than were used for the turbine-following
mode, but it is good practice to have the turbine master control the megawatts as tightly as possible at first. If
that response is too much for the boiler to handle, the tuning can be loosened up later. Note that this will only
be proportional and integral tuning with no derivative action.
The key to tuning the boiler master is balancing the proportional, integral, and derivative action of the controller
so that the pressure is maintained with good control, moves toward the setpoint in a timely manner, and
correctly anticipates the movement of the error signal. In general, the proportional gain will be fairly large, the
integral action slow, and the derivative gain in the controller should be relatively small.
Finally, the controls that make up the coordinated front end may use some feedforward and the various kickers
that are part of it. The feedforward signals to both the turbine and the boiler master controllers, in coordinated
mode, is a function of unit load demand.
the less swing will occur when the load change is finished. Some boilers are well behaved and very responsive,
so this kick is minimal. Some boilers are not well behaved, and their kickers can be pretty substantial. There
can be other kickers, possibly based on the throttle pressure or the throttle pressure setpoint kicker, as
described for the boiler-following mode.
3.
Unresponsive. A load change on this 800-MW unit showed poor response and controls in need of a good
tuning. Source: Tim Leopold
By the third day, the coordinated controls were responding well after I slightly decreased the integral and
proportional gain and increased the derivative action of the controller by about 25%. I also modified the
feedforward signal slightly. Figure 4 illustrates the unit response to a 353-MW load increase test. About halfway
through, the operator was unable to start an induced-draft (ID) fan, so he changed to base mode and then to
boiler-following mode. When the ID fan was finally started, he returned to coordinated control mode. As you can
see in Figure 4, a request was received by the front end to increase load just after the operator decided to raise
his throttle pressure. This well-tuned boiler sailed through each test with rock-solid performance.
4.
New lease on life. The same 800-MW unit as in Figure 3 showed much better response to a load change
after tuning the proportional and integral gain and increasing the derivative action of the controller by
25%. Source: Tim Leopold
Usually, the fuel master will be in auto. The boiler demand is then reduced by the rundown logic from where it
was to some value that allows the error that is driving the rundown to fall below some preset limit. If the error
does not go down, the rundown will continue to reduce boiler load to a set minimum value.
The first runback logic that I ever came into contact with was very severe. On a loss of equipment, the boiler
controls would attempt to stay in coordinated mode. The unit load demand would run down, at some preset,
fast, rate. This would decrease the boiler demand and the demand to the turbine governor valves. That worked
all right for some boilers, but the rate that was necessary for the boiler to get to a safe operating load was very
fast. The difficulty is that the turbine governor valve would close down at the same rate. When these valves
close, the main steam pressure must climb and may eventually lift the boiler pressure safety relief valves. This
is very hard on the drum level and your ears, and often results in a master fuel trip. Granted, it was a trip from a
lower boiler load, rather than if we had otherwise simply tripped the boiler, but it was a trip nonetheless.
As a result, what I like to call a kinder, gentler runback was developed. Some call it the turbine-following
runback, where the boiler switches to manual on the loss of a piece of equipment. If you are in coordinated
mode, the boiler should go to manual control and turbine-following mode for the steam turbine. At this time, the
runback logic reduces the boiler demand to a predetermined level at a preset rate. In the meantime, the turbine
is free to control the main steam pressure. The megawatt load is then gently reduced, and the plant
experiences a soft landing. Turbine-following is the best mode to select in an emergency.
A further goal of a runback is to recover automatically so the operators can figure out what happened to the
equipment and fix it while the unit is still online and avoid a master fuel trip.
The data shown in Figure 5 were collected during an actual runback test on a 95-MW plant that operated with
three pulverizers. The runback occurred when an ID fan was tripped, which had the effect of tripping one of the
FD fans. The runback of the boiler was set to a point that was below the three-mill minimum load for safe and
stable operation. As a result, automatic mill tripping on a runback was developed.
5.
Avoiding unit trips. A runback test is necessary when any changes are made to boiler gas pass, fans, or
mills. In this test of a 95-MW unit, the runback occurred when an ID fan was tripped. Source: Tim Leopold
You can see the boiler demand dropping, and the fuel flow percentage dropping even further as one of the
three mills is shut down by the runback logic. The pulverizer master (coal master demand) picks up
momentarily as the mill is stopped, then ramps back down, eventually getting the fuel percentage down to the
boiler demand. Automatic mill tripping is generally a good idea, especially on larger units with a lot of mill
capacity. Also, notice how the turbine pushes the throttle pressure back to the setpoint. Drum level also
dropped slightly before it recovered. The entire runback occurred in just over two minutes. Figure 6 is a longer
view of the entire episode.
6.
Many moving parts. The same runback test (Figure 5) of a 95-MW unit but with a longer time-span is
illustrated. Here you can see the pulverizer master ramping back and the lowering of the turbine operating
pressure setpoint. Source: Tim Leopold
In this test, as is true for most of the tests I have run over the years, the fan and fuel runbacks are easily
handled by the turbine-following runback logic. However, the boiler feedwater pump runback can be another
matter. The turbine valves are relatively slow to respond and tend to suck steam from the drum. Though some
boilers are able to survive this without tripping on low drum level, many can not.
As a result, new logic was developed. I like to call this special type of runback the separated runback. On the
loss of a boiler feed pump, the boiler master goes to manual, coal mills are tripped, and the boiler demand is
driven to minimum. The turbine master remains in auto to stay in turbine-following mode. At this point, we add a
special high-limit override enabled during this runback that overrides the turbine-following controller and
marches the governor valves to a predetermined position. The rate at which the valves are closed is variable
and depends on the throttle pressure. Higher pressures tend to depress the drum level, which we do not want,
and really high pressures lift safeties, which started us on this runback logic journey in the first place.
If you plan to test your runback logic, its a good idea to elevate the drum level a few inches before your test. At
this same 95-MW plant, we tested the boiler feedwater pump runback using separated runback logic from 75%
load with the drum level rundown initiated when the runback was complete. Figure 7 data illustrate this
successful test from the feedwater perspective. Notice the action of the feedwater control valve. The drum level
dropped about 6.5 inches. The low drum level trip was set at 7.7 inches. That was successful, but a little too
close for comfort.
7.
Different perspective. The same runback test (see Figure 5) of a 95-MW unit but from the perspective of
the feedwater system. Note the drum level response. Source: Tim Leopold