FIRE PROTECTION CONCEPT


1

GENERAL

DESIGN BASES

2.1

Codes and Standards

2.2

Principles of Protection

FIRE PROTECTION MEASURES

3.1
Process-Related Fire Protection Measures
3.1.1
Measures for Mechanical Equipment
3.1.2
I&C System Measures
3.1.3
Measures for Electrical Installation

5
6
6
7
8

3.2
Structural Fire Protection Measures
3.2.1
Structural Components and Materials used for Fire Barriers in Fire Protection Areas
3.2.2
Table of minimum fire-rating values of the elements of the buildings
3.2.3
Fire Areas
3.2.4
Oil Filled Transformers (UBE/UBF)
3.2.5
Escape Routes
3.2.6
Provisions for Smoke Removal

8
9
10
11
14
15
15

3.3
Fire Fighting Measures
3.3.1
Fire Suppression Water Supply
3.3.2
Fire Extinguishing Systems
3.3.3
Fire Detection

16
16
16
17

TABLE OF FIRE ALARM AND FIRE FIGHTING EQUIPMENT

19

ESCAPE ROUTE AND FIRE PROTECTION DRAWINGS

36

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
3 of 36

1 General
This concept generally describes the fire protection measures for the Pengerang cogen
plant.
The structural and process-related fire protection measures serve both to protect the plant
operating personnel and to reduce/minimize the potential of fire loss. For this purpose the
plant is divided by structural means into fire areas. In addition suitable equipment and
materials are provided to minimize the risk of fire.
The fire protection concept described herein takes into account the following combustible
materials in particular:

The fuel fired at the plant: Fuel gas


Diesel as fuel for the black start and emergency power generators and fire fighting
pump
Lubricating oil, hydraulic oil and transformer oil
Seal oil
H2 as coolant for generators
Materials used for electrical equipment: primarily cable sheathing and insulating
materials in switchgear and electronic equipment cabinets
Hydrogen released during battery charging processes
Other flammable gases: e.g. acetylene
Other combustible and flammable fluids: e.g. lubricants, paints

All combustible materials are considered to define suitable measures to:

Prevent fires from starting (fire prevention)


Detect fires at an early stage (fire detection)
Prevent fires from spreading over a wide area (fire confinement)
Actively fight fires (fire suppression).

Measures for fire protection will be described for the buildings and structures listed below.
00
00
00

UAA
UAC
UBA

11/21
11/12/21/22
31/32
11/12/21/22
31/32
11/12/21/22
11/12/21/22/31/32
00
00
00
31/32

UBA
UBA
UBA
UBD
UBD
UBE
UBF
UBH
UBN
UBS
UBX

81/82;
91,94
68
01 - 03
21 - 22
01

01 05

275kV AIS switchyard


275kV Control building
Power control centres (PCC)
Power control centres (PCC)
Power control centres (PCC)
Power control centres (PCC)
LV auxiliary transformer
LV auxiliary transformer
Unit auxiliary power transformers
Generator transformer
Oil separator
Black start & emergency power generation
Cable pulling pit
Generator circuit breaker for steam turbine

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

11/12/21/22
11/12/21/22/31/32
00
00
11/12/21/22
00
00
00
00
00
00
00
00
00
00
00
30
30
00
11/12/21/22
11/12/21/22
11/12/21/22
11/12/21/22
11/12/21/22
10/20
30
11/12/21/22
11/12/21/22
11/12/21/22/30
30
30
00
00
00
11/12/21/22
11/12/21/22
11/12/21/22
00
00
00
00

UBX
UBY
UEH
UEN
UEN
UEY
UGA
UGC
UGC
UGD
UGE
UGF
UGJ
UGU
UGU
UGV
UGX
UGX
UGY
UHA
UHN
UHW
UHX
UHY
ULA
UMA
UMB
UMX
UMY
URA
URD
USG
UST
USV
USX
USY
UTG
UTR
UYC/
UCA
UYG
UYE
UZ
UZD

01 02
01 03
10

01 02
01
02
01 03
04
01

01 02

0/05 / 2015-07-16
4 of 36

Generator circuit breaker for gas turbine


Cable bridge
Structure for unloading station
Gas conditioning skid (open structure)
Gas filter and preheating
Pipe Bridge and sleeperway
Treated water tank
Demineralized water tank
Demineralized water filters
Water treatment plant & condensate building
Neutralization system
Fire water tanks
Cooling tower make-up water treatment
Utilities effluent pit
Accidentally oil contaminated waste water pit
Sewerage pit
Condensate water tank
Polished condensate water tank
Pipe bridge and sleeperway
Heat recovery steam generator
Bypass stack and diverter
Boiler blow down tank
Sampling container
Pipe bridge
Feed water pumps
Steam turbine building
Gas turbine building
Diffuser
Pipe bridge and sleeper ways
Cooling tower structure
Cooling water pumps
Firefighting pump house
Workshop and storage building
Laboratory room
Chemical dosing shelter
Sleeperway
H2 bottle storage and supply rack
Chemical and lube oil storage building
Administration and control room building
Visitor building OPTION
Gate house
Outdoor area
Parking area

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
5 of 36

When defining the fire protection measures for affected areas it was taken into account that
the fuel gas emergency stop valve must be in its close limit position, before fire extinguishing
measures (manually, as well as automatically) may start. Extinguishing a gas fire without first
shutting off the fuel supply creates an additional explosion hazard.

2 Design Bases
2.1 Codes and Standards
The fire protection measures described are defined in accordance with the codes and
standards of the contract relevant edition of National Fire Protection Association (NFPA), and
relevant international regulations and standards. The relevant local statutory requirements of
Malaysia are implemented where necessary.

2.2 Principles of Protection


The fire protection measures are provided to ensure:

Personnel protection
Material protection (damage minimization)
Availability of the power plant
Environmental protection

These safety goals are achieved by means of provisions implemented in the process design
as well as through structural fire protection provisions incorporated into the civil engineering.
The risk of fire is significantly reduced by minimizing the fire loads through use as far as
possible - of non-combustible materials as well as by reducing the quantities of combustible
materials required for operation.

3 Fire Protection Measures


Fire protection measures are subdivided into process-related measures, structural measures
and active fire protection measures.
The following are examples of process-related fire protection measures:

Shut off the oil filled transformers due to transformer self-protection signal
Trip of turbine generator set by the distributed control system (DCS)
Retention of fire suppression water

The following are examples of structural fire protection measures:

Installation remote from other facilities (i.e. physical separation through distance)
Subdivision of buildings
Isolation of main fire loads by establishing fire zones
Enclosure of areas containing oil (spray protection, drip pan for oil tanks, oil pits)

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
6 of 36

Selection of materials (wherever possible use of non-combustible or fire-resistant


materials, e.g. isolation materials, etc.)

The following are examples of active fire protection measures:

Fire alarm systems with automatic fire detectors and manual pushbutton alarms
Fire suppression water supply
Fixed extinguishing systems
Manual firefighting equipment
Mobile fire extinguishers
Fire hydrants

3.1 Process-Related Fire Protection Measures


3.1.1 Measures for Mechanical Equipment
The following principal fire protection measures are provided in the vicinity of the gas turbine,
the steam turbine, the generators, the oil-immersed transformers and other areas where oil is
contained:

The oil stations and oil tanks are equipped with oil troughs or leakage tanks to
prevent the spread of leakages.
The collecting/drainage system for the transformers must at minimum have the
capacity to accommodate the oil and the fire water arising from 10.2l/mmin for the
transformer surface area and from 6.1l/mmin for the non-absorbing floor area of the
greatest transformer (UBF) and 1890l/min for hose lines at an assumed water flow
duration of 10 minutes. (The water flow rates and extinguishing times are according
to NFPA 15)
The oil collecting pit for the lube oil system must at minimum have the capacity to
accommodate the oil and the fire water arising from 12.2l/mmin for the oil system
projected base area and 379l/min for hose lines at an assumed water flow duration of
10 minutes.
The water retention capacity for areas served by more than one extinguishing system
has to be calculated for all systems working parallel (e.g. area beneath turbine
generator set floor and bearing protection).
The oil tanks are equipped with level monitoring equipment for leak detection.
Process-related component monitoring equipment (pressures, temperatures, etc.) for
fault detection.
The emergency and black start power generating set consists of 6 units (2
emergency and 4 black start). Every one of these units is equipped with its own diesel
oil tank 500-1000L located in a separate room of the enclosure. In case of leakage
the oil is collected within a pan inside the tank room. The tanks are delivered by a
common storage tank which is located outside approx. 20,000L.
Oil pipes shall not be routed above hot surfaces.
Sufficient measures have to be provided to avoid the propagation of fire through
pipes or connective openings between structures.

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
7 of 36

3.1.2 I&C System Measures


Gas turbine enclosure incl. fuel gas skid
The gas turbine enclosures incl. fuel gas skid is monitored with flame, heat and optical
smoke detectors. Activation of a single detector initiates an alarm signal.
Activation of a second detector of different detection type initiates the following:

Transfer of a signal to the I&C system for releasing a turbine trip incl. cut-off of fuel
supply outside of the turbine building
Transfer of a signal to the ventilation system of the noise enclosure to shut off and
close vents as soon as the fuel gas emergency stop valve is in its close-limit position;
the vents close with a specified time delay to ensure pressure relief in the area to be
flooded with extinguishing agent,
The lube oil supply shall be switched over to the emergency supply.
Actuation of the gaseous fire extinguishing system after receiving check-back signal
that the fuel gas valve is closed.

Hydraulic oil skid (Gas turbine)


The hydraulic oil skid of the gas turbine is monitored with automatic optical smoke detectors.
Activation of a single detector initiates an alarm signal.
Activation of a second detector of different detection type initiates the following:

Transfer of a signal to the I&C system for releasing a turbine trip incl. cut-off of fuel
supply outside of the turbine building
Shut down of the hydraulic oil system

Lube oil skid without enclosure


The lube oil skid is monitored with automatic heat and optical smoke detectors. Activation of
a single detector initiates an alarm signal.
Activation of a second detector of different detection type initiates the following:

Transfer of a signal to the I&C system for releasing a turbine trip incl. cut-off of fuel
supply outside of the turbine building
The lube oil supply shall be switched over to the emergency supply.

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
8 of 36

Power Control Centers


The power control centres are monitored with automatic optical smoke detectors. Activation
of a single detector initiates an alarm signal.
Activation of a second detector initiates the following:
Transfer of a signal to the I&C system for releasing a turbine trip incl. cut-off of fuel supply
outside of the turbine building
Transfer of a signal to the HVAC system of the PCC to shut off
Actuation of the gaseous fire extinguishing system.

3.1.3 Measures for Electrical Installation


The electrical installation of safety related equipment (e.g. firefighting water pumps, fire
control panel; smoke removal system) will be provided in accordance to the relevant
regulations and standards. Normative requirements to fire protection of electrical installations
will be considered.

3.2 Structural Fire Protection Measures


The power plant facility is divided into various buildings and structures. Separate fire zones
are established by separation of the buildings and the power plant systems contained
therein.
The length of time during which a steel structure needs to maintain its integrity depends on
local circumstances such as type of plant, availability of fire-fighting services, and risk of
escalation. A minimum of 30 minutes protection time against a hydrocarbon fire shall be
provided. It is assumed that after this period structures can be cooled by water or plant
operating staff will have been evacuated. In special cases where this is unlikely, increasing
the fire resistance to a longer duration will be considered (depending of the Risk
assessment). Where effective water cooling is not feasible (e.g. due to the configuration of
the structure), the required duration of the fire resistance depends on the estimated time for
the fire to burn out or be extinguished. The hydrocarbon fire test as defined in UL 1709 is
applicable to all fireproofing systems applied on steel supports and structures. This fire is
more severe than the cellulose type of fire which is usually referred to in building regulations.
During the test a protected steel column is exposed to a particular heat flux that produces a
temperature of 1 093C. The test is terminated (failure point) when the average temperature
of the steel substrate reaches 538C.
Cables in trays, racks or ducts which are critical (e.g. cables feeding emergency shutdown
and emergency depressuring valves) shall be of a fireproof construction in accordance with
IEC 60331-21 (i.e. they shall withstand temperatures of at least 750C for a period of 90
minutes).
Wherever possible in terms of plant design, all buildings and structures are separated from
other buildings and building areas by non-combustible walls which also prevent the spread of
smoke.
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
9 of 36

In principle, non-combustible materials are used. Combustible materials are only used in
cases where material requirements must be met. Noise and thermal insulation, e.g. on steam
turbines or external building walls, consist of non-combustible materials (e.g. mineral wool) to
reduce fire loads and inhibit the spread of fire.
Where possible, openings in walls, which are not subject to any fire ratings, are sealed.
The outermost roofing of the buildings shall be resistant to flying embers and radiated heat.
Under section 3.2.3 Fire Areas detailed information is given where fire areas will be
provided.
In rooms where suspended ceilings or false floors are provided, the spaces above the
suspended ceiling or underneath the false floor are part of the considered room.

3.2.1 Structural Components and Materials used for Fire Barriers in Fire
Protection Areas
In general fire walls are designed to have a fire resistance rating of 120 minutes in
accordance to NFPA 850. The fire wall assemblies e.g. fire doors and fire dampers are
designed for a fire resistant rating of 90 minutes in accordance to NFPA 850.
Openings and penetrations in walls and ceilings subject to specific fire ratings are sealed
with fire stops (for cables and pipes), designed to the specified fire-resistance rating of the
given wall. (Refer to the Petronas specification Section 5 Part 16: Civil & Structural Page
262/263/263 of 274; 4.14.4 Passive Fire Protection/Fire resistant of elements).
Table of Petronas specification:

Minimum period of smoke and fire resistance


Fire rating in hours
Number Building type
1

Offices, bulk store, canteen,


medical centre, fire station,
gate house, training centre,
workshops
Warehouses

Laboratory, computer room

Analyser buildings, substations


1)
2)

External walls
including doors
excluding windows1

Internal walls
including doors
excluding windows2

0.5

1
2
2

1
1
1

Rating shall be applicable for structural integrity, flame tightness and insulation
Rating shall be applicable for flame tightness and insulation in bearing wall (1) shall be applicable

In addition, floors in elevated buildings shall have a minimum period of smoke and fire resistance 1h.
Raised floors (computer floors) shall have a minimum period of smoke and fire resistance of 0,5h. Walls of
heater/ boiler rooms shall have a minimum period of smoke and fire resistance of 1h.

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
10 of 36

As a compensation measure a nozzle of the fire suppression system will be located in front
of the penetration of the bus ducts through the fire wall (between UBE and UBF).
Non-combustible piping is provided with guard pipes at penetration points to allow
expansion. The space between the guard pipe and main pipe is filled with a non-combustible
material and sealed smoke tight. In cases in which movement (i.e. expansion) need not be
allowed for, penetrations are sealed with mortar or finishing concrete. Penetrations are
designed to the fire-resistance rating of the given wall.
Piping penetrations for combustible piping are equipped with sealing systems corresponding
to the fire-resistance rating of the given wall.
Ventilation and air conditioning ducts traversing fire areas or fire zones are designed to the
specified fire-resistance rating of the given wall or are likewise equipped with fire dampers in
compliance with the specified fire-resistance rating of the given wall.

3.2.2 Table of minimum fire-rating values of the elements of the


buildings
As mentioned above the buildings will be classified as follow:

Minimum period of smoke and fire resistance


Fire rating in hours
KKS

Number

UAC

UBE

NA

External walls
including doors
excluding windows1
2
-

Internal walls
including doors
excluding windows2
1

Remarks

Fire wall between UBE/UBF

UBF

NA

Fire wall between UBE/UBF

UHA

NA

Open structure

UHX

NA

ULA

NA

UMA

NA

UMB

NA

URA

NA

USG

UST

USV

USX

UTG

NA

UTR

UYC/
UCA
UYG

0.5

0.5

UYE

0.5

Open structure
Internal walls for rooms with
electrical equipment F60

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
11 of 36

3.2.3 Fire Areas


Buildings / Structures

Measures for Isolation

275kV AIS switchyard (00UAA)

Installed remote from all buildings 9.1 m

Grid system switchgear building


(00UAC)

Power control centres (11UBA 01-

Installed remote from all buildings 9.1 m


Fire resistant areas:

Control room incl. false floors

Battery room incl. false floors

Telecommunication room incl. false floors

AC-DC room incl. false floors

Offices incl. false floors

Corridor incl. false floors

Suspending ceilings
Installed adjacent to 11UMB < 9.1 m (compensation
measure: extinguishing system inside UBA containers
is provided)
Installed remote from all other buildings 9.1 m
Installed adjacent to 12UMB < 9.1 m (compensation
measure: extinguishing system inside UBA containers
is provided)
Installed remote from all other buildings 9.1 m
Installed adjacent to 21UMB < 9.1 m (compensation
measure: extinguishing system inside UBA containers
is provided)
Installed remote from all other buildings 9.1 m
Installed adjacent to 22UMB < 9.1 m (compensation
measure: extinguishing system inside UBA containers
is provided)
Installed remote from all other buildings 9.1 m
Installed adjacent to UBN and 20ULA < 9.1 m
(compensation measure: extinguishing system inside
UBA containers is provided)
Installed remote from all other buildings 9.1 m
Installed adjacent to 30URA and 30URD < 9.1 m
(compensation measure: extinguishing system inside
container is provided)
Installed remote from all buildings 9.1 m

03/68)

Power control centres (12UBA 01-03)

Power control centres (21UBA 01-

03/68)

Power control centres (22UBA 01-03)

Power control centres


(00UBA91/94; 31/32UBA21-22)

Power control centre (00UBA81/82)

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Buildings / Structures

0/05 / 2015-07-16
12 of 36

Measures for Isolation

LV auxiliary transformers
(00/11/12/21/22UBD)
Auxiliary transformer
(11/12/21/22UBE)

Outdoor installation (Dry type transformers)

Generator transformer
(11/12/21/22/31/32UBF)

Generator transformer (31/32UBF)

Oil separator (00UBH 01-05)


Black start and emergency power
generation (00UBN)

Separated from 11/12/21/22UBF by fire wall


Separated from 11/12/21/22UBD by fire wall
Installed remote from all other buildings according to
section 3.2.3 > 7.6m
Separated from 11/12/21/22UBE by fire wall
Installed remote from all other buildings according to
section 3.2.3 > 15m
Separated from 30UMA by fire wall
Installed remote from all other buildings according to
section 3.2.3 >15m
Underground structure
Fire resistant areas:

Electrical equipment room with gas extinguishing


system

Generator room
Installed adjacent to 00UBA94 and 20ULA < 9.1 m
(compensation measure: extinguishing system is
provided)
Installed remote from all other building 9.1 m
Underground installation
Outdoor installation

Outdoor installation

Outdoor installation

Outdoor installation
Outdoor installation

Cable pulling pit (00UBS)


Generator circuit breaker for gas
turbine (11/12/21/22UBX)
Generator circuit breaker for steam
turbine (31/32UBX)
Cable bridge
(11/12/21/22/31/32UBY)
Gas conditioning skid (00UEN)
Gas metering and filter station
(11/12/21/22UEN)
Demineralization water filters
(00UGC10)
Neutralization system (00UGE)

Water treatment plant &


condensate building (00UGD)

Cooling tower make-up water


treatment (10UGJ)

Installed adjacent to 00UGX02 < 9.1 m (no fire load


inside UGC)
Installed adjacent to the electrical room of UGD
< 9.1m
(compensation measure: extinguishing system inside
the E-room of UGD is provided)
Installed adjacent to 00UGE and 00UGX01 < 9.1m
(compensation measure: 30min fire resistant wall
between the structures)
Fire resistant areas:

Electrical equipment room incl. false floors

Chemical Storage room

Vessels and pump area


Installed remote from all buildings 9.1 m
Fire resistant areas:

Electrical equipment room incl. false floor


Installed remote from other buildings 9.1 m

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Buildings / Structures
Heat recovery steam generator
(11/12/21/22UHA)

Measures for Isolation

Sampling container
(11/12/21/22UHX)

Feed water pumps house


(10/20ULA)

Steam turbine building (30UMA)


Gas turbine building (21/22UMB)

Gas turbine building (11/12UMB)

0/05 / 2015-07-16
13 of 36

Cooling tower structure (30URA)

Cooling tower pumps (30URD)

Firefighting pump house (00USG)


Workshop and storage building
(00UST)

11UHA and 10ULA are one fire compartment


12UHA and 20ULA are one fire compartment
11UHA is installed adjacent to 11/12UHX < 9.1 m
(compensation measure: detection system inside the
11/12UHX is provided)
12UHA Installed adjacent to 21/22UHX < 9.1 m
(compensation measure: detection system inside the
21/22UHX is provided)
11UHA and 11/12USX are one fire compartment
21UHA and 21/22USX are one fire compartment
Installed remote from all other buildings 9.1 m
Installed adjacent to 11/21UHA < 9.1 m
(compensation measure: fire detection system for
11/12/21/22UHX is provided)
Installed remote from all other buildings 9.1 m
10ULA and 11UHA are one fire compartment
20ULA and 21UHA are one fire compartment
20ULA installed adjacent to 00UBN and 00UBA91/94
< 9.1 m (compensation measure: fire detection system
for 20ULA is provided)
Installed remote from all other buildings 9.1 m
30UMA, 21UMB and 22UMB are one fire
compartment
30UMA is separated from 31/32UBF by fire wall
21UMB is installed adjacent to 21UBA01/02/03/68
< 9.1 m (compensation measure: extinguishing system
for 21UBA01/02/03/68 is provided)
22UMB is installed adjacent to 22UBA01/02/03
< 9.1 m (extinguishing system for 12UBA01/02/03 is
provided)
21UMB is installed remote from 21UBE 7.6 m
22UMB is installed remote from 22UBE 7.6 m
21UMB is installed remote from 21UBF 15 m
22UMB is installed remote from 22UBF 15 m
Installed remote from all other buildings 9.1 m
11UMB and 12UMB are one fire compartment
11UMB is installed adjacent to 11UBA01/02/03
< 9.1 m (compensation measure: extinguishing system
for 11UBA01/02/03 is provided)
12UMB is installed adjacent to 12UBA01/02/03
< 9.1 m (extinguishing system for 12UBA01/02/03 is
provided)
11UMB is installed remote from 11UBE 7.6 m
12UMB is installed remote from 12UBE 7.6 m
11UMB is installed remote from 11UBF 15 m
12UMB is installed remote from 12UBF 15 m
Installed remote from all other buildings 9.1 m
Outdoor installation
30URA and 30URD are one fire compartment
30URA and 30URD are one fire compartment
Installed remote from all other buildings 9.1
Installed remote from all buildings 9.1 m
Installed remote from 00UTR < 9.1 m to
(compensation fire detection system is provided
further a sprinkler system for UST is installed)

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Buildings / Structures

0/05 / 2015-07-16
14 of 36

Measures for Isolation

Fire resistant areas:


Electrical equipment room incl. false floor
Workshop-, Welding area and machine hall
Warehouse
Offices
FOR DETAILS REFER TO SECTION 3.2.2
Fire resistant separation between office area and
workshop-, welding area and machine hall
Fire resistant separation between workshop-, welding
area and machine hall and warehouse
Installed remote from all buildings 9.1 m
11/12USX and 11UHA are one fire compartment
21/22USX and 21UHA are one fire compartment
Installed remote from all other buildings 9.1 m
Outdoor installation
Installed remote from all buildings 9.1 m
Fire wall to UBA
Fire wall to UBE/UBF
Installed remote from 00UST/USV < 9.1 m to
(compensation fire detection system is provided
further flammable substances inside 00UTR are
covered in F90)
Flammable and non-flammable chemical storage
inside building and storages and warehouse will be
separated with fire wall (F-90)
Installed remote from all buildings 9.1 m
Fire resistant areas:

Communication room incl. false floor

Electrical equipment room incl. false floor

Ventilation facilities

Archive room

Control room incl. false floor

Archive room
FOR DETAILS REFER TO SECTION 3.2.2
Installed remote from all buildings 9.1 m
Fire resistant areas:

Auditorium

Server room

Facility service room

HVAC room

Storage room

Canteen area

Audio / Video control room


Installed remote from all buildings 9.1 m
Installed remote from all buildings 9.1 m

Chemical dosing shelter


(11/12/21/22USX)

Gas bottle storage and supply skid


(11/12/21/22UTG)

Chemical and lube oil storage


building (00UTR)

Administration and control room


building
(00UYC & UCA)

Visitor center
(00UYG)
OPTION

Gate house (00UYE01-02)

3.2.4 Oil Filled Transformers (UBE/UBF)


The transformers (UBE/UBF) must be located away from the adjacent buildings:

Oil capacity 18.925 m3: distance 15 m


Oil capacity 18.925 m3: distance 7.6 m

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
15 of 36

If the distance to the adjacent buildings is 7.6m and 15m respectively fire walls have to
be provided. Between the adjacent transformers UBE / UBF a firewall has to be provided.

3.2.5 Escape Routes


General
There are adequate escape routes in the buildings via stairwells and open stairs. The design
of the escape routes pays particular attention to the provision of separate escape routes to
ensure that protected areas or the outdoors can be reached via several routes. The buildings
and platforms are designed in such a way that the escape routes leading from any location
(work place, staff amenity rooms) to the outdoors or other protected areas do not exceed
45m. Dead end conditions shall not exceed 18m. The maximum travel distance from any
point of a floor in an occupied building to the nearest exit of that floor shall not exceed 25m.
Exit doors open in the direction of exit. Revolving doors and sliding doors are not allowed for
emergency exits. The escape routes are appropriately marked and provided with emergency
lighting. Exit doors provided for emergency exits will be designed in such a way that they
could be opened in any case in the direction of exit.
Escape routes will have at least a width of 1200mm. Ladders in escape routes are not
allowed.
For platforms & floors a continuous and unobstructed escape way will be provided from any
point at elevated equipment, structure and building egress points. Maximum distance of dead
end platforms without secondary means of escape is 6.0m. Maximum length of travel
between primary and secondary escape is 25.0m.

3.2.6 Provisions for Smoke Removal


The gas turbine buildings (UMB), the steam turbine building (UMA) and the chemical and
lube oil storage building (UTR) will be equipped with smoke and heat removal systems.
For details related to the smoke and heat removal systems of the above mentioned buildings
refer to system description of each building:

00UGD:
11/12UMB:
21/22UMB:
30SAM:

UNID 494510870,
UNID 494511310,
UNID 494510856,
UNID 494510863,

PCP-SAG-MEC-DES-SAG-560011
PCP-SAG-MEC-DES-SAM-560008
PCP-SAG-MEC-DES-SAM-560009
PCP-SAG-MEC-DES-SAM-560010

For details related to the smoke and heat removal systems of the Design & Construct
buildings refer to description of the buildings.
Enclosed staircases will be equipped with smoke and heat removal systems with a horizontal
opening area of 5% (not less than 1m) of the staircase floor base.
In all other buildings smoke is removed by means of mobile equipment provided by the local
fire brigade or by opening doors and windows.

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
16 of 36

The spreading of smoke/or gas through the HVAC system shall be prevented. In the HVAC
system a smoke / gas detection is installed. In case of an alarm safety measures will be
started in reference to the specification (e.g. system stopped, light will be activated, dampers
will be closed). The HVAC system design will cater for abnormal (i.e. explosion, fire, toxic
release, etc.) conditions. The required working conditions for the electronic equipment will be
ensured during abnormal conditions. A fire and gas detection system will be installed with
gas-tight, quick-closing, spring-operated dampers in the fresh air intakes and exhausts. An
explosion valve will be installed just before the beginning of the air intake. After the explosion
the valve will be automatically opened. In order to cope with flammable/toxic gases outside
the plant building, one or more of the following features will be considered:

Gas-tight, quick closing, spring-operated dampers in the fresh air intakes and
exhausts;
Explosion-proof dampers in the fresh air intakes and exhausts;
HVAC emergency shutdown switch

3.3 Fire Fighting Measures


3.3.1 Fire Suppression Water Supply

A fire main loop is installed around the power plant.


Branch lines are provided to serve the consumers inside the buildings.
The fire main loop is subdivided by shut-off valves so that, in the event of a section
failing, the supply of fire suppression water to the other sections of the main loop is
ensured.
The fire suppression is stored in the fire suppression water tanks 2x50% (UGF01/02).
A minimum capacity of 1x100% of the fire suppression water demand is reserved
exclusively for firefighting purposes. Fire suppression water supply is provided with
two 100%-capacity firefighting water pumps. One 100% electrically driven and one
100% diesel driven firefighting water pump. The firefighting water network is
maintained at a constant pressure by means of a jockey pump.

3.3.2 Fire Extinguishing Systems


Portable (manual) firefighting equipment
An adequate number in accordance to NFPA10 of portable fire extinguishers will be provided
including:

Dry chemical extinguishers


CO2 extinguishers
Water extinguishers
Foam extinguishers

9 kg
5 kg*
XX l*
XX l*

The given sizes will be adapted to the available local standard sizes.

For the quantity refer to Table chapter 4.

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
17 of 36

Fire hydrants
Fire hydrants are provided to enable effective early firefighting measures.

In order to cover the risk at the outdoor area of the power plant, the fire water ring
main will be provided with yard hydrants. The distance between two yard hydrants
should be preferably not more than 70 meters.
In areas with potential high fire loads, indoor hydrant cabinets (foam/water based) or
hose reels (water based) are provided in accordance to the risk.

Stationary Extinguishing Systems


For areas with potentially high fire loads, stationary fire extinguishing systems are installed:

Sprinkler systems
Pre-action sprinkler systems
Spray deluge systems
CO2 extinguishing systems
Clean agent extinguishing systems

3.3.3 Fire Detection


To ensure that fires are detected at an early stage, several areas/systems are monitored with
automatic fire detectors. The following types of detectors are used:

Smoke detectors (optical smoke detectors, aspirating smoke detectors)


Flame detectors
Heat detectors (control sprinkler, sprinkler, combination of fixed temperature and rate
of rise detectors, linear heat detectors)

In addition to the automatic fire detectors a video system is installed in the 30UMA and
11/12/21/22UMB.
In addition to the automatic fire detectors, non-automatic fire alarms (manual push button
alarms) are installed.
The fire detection system is designed in such a way that:

The location of a fire can be identified immediately.


The detectors for several fire zones can be connected to one loop.
Non-automatic fire alarms can share a loop with automatic fire detectors.
The fire detectors will be combined to one detector group for the activation of
stationary fire extinguishing systems of the respective area.
Each automatic fire detector and manual push button of the fire alarm system is
displayed in such a way that it is possible to identify where any fire detector or
manual push button is installed.
Detectors located in concealed places (e.g. above suspended ceilings) have
activation indicators visible from normal operating areas.

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
18 of 36

A signal initiates an alarm on the relevant local fire control panel and activates the
indication light of the affected detector.
All fire alarm signals will be led to the main fire alarm panel either via a local fire
alarm panel or directly.
Activation of a manual push button or automatic activation of a detector or
extinguishing system causes a fire alarm in the building of origin. In areas with a high
noise level in addition to the acoustic alarm a visible indication is provided. The noise
level of the acoustic alarm must be higher than the noise level of the building/area in
normal operation. The sound level of the alarm will be minimum 20dBA higher above
surrounding noise level.
A main fire alarm panel is installed inside the central control room.
The BOMBA fire alarm panels are located at the gate houses or at a location
approved by BOMBA.
An additional local/repeater panel will be installed in the BOMBA fire department
centre of the industrial area.
Local fire alarm panels will be installed inside the PCC`s 11UBA, 12UBA, 21UBA,
22UBA, 31UBA. Other locations will be implemented during the detail design.

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Siemens

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
19 of 36

4 Table of Fire Alarm and Fire Fighting Equipment


Fire Detection

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

00UAA

275kV AIS switchyard

00UAC

275kV control building

PVC

---

1)

Hydrant
Cabinets/
2)
Hose reels

---

2HR

Fire Suppression Systems

---

Control room

Various

Smoke

False floor of control room

PVC

ASD

Battery room

PVC

Smoke

Telecommunication room

PVC

Smoke

False floor of Telecommunication room

PVC

ASD

AC-DC room

PVC

Smoke

False floor of AC-DC room

PVC

ASD

Corridor

Various

Smoke

---

All other false floors

Various

ASD

---

Suspending ceiling

PVC

ASD

---

False floor

Cable distribution area below container

PVC

Smoke

Various

ASD

PVC

Linear heat

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

CO2

Water

Foam

9kg

5kg

Local size

Local size

---

---

---

---

---

10

---

---

---

---

---

Clean agent system (a/m)


--Clean agent system (a/m)

Clean agent system (a/m)

31UBA21-22; Power control centre for steam turbine


32UBA21-22; Rooms with electrical equipment

3)

Dry
Chemical

--Clean agent system (a/m)


---

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
20 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

00UBA91/94

Power control centre for steam turbine

Rooms with electrical equipment

False floor

Cable distribution area below container

Cable distribution area below container

Power control centres for gas turbine


11UBA 0103/68;
Rooms containing electrical equipment
12UBA 01(incl. False floors)
03;

False floor
21UBA 0103/68;
22UBA 01-03 Cable distribution area below container

1)

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

---

PVC

Smoke

Clean agent system (a/m)

Various

ASD

Clean agent system (a/m)

PVC

Linear heat

---

PVC

Linear heat

---

4x2

PVC

PVC

Linear heat

11/12/21/22
UBE

Auxiliary transformers

oil

11/12/21/22/
31/32UBF

Generator transformers

Transformer
oil

Transformer

Bus duct (between UBE and UBF)

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

CO2

Water

Foam

9kg

5kg

Local size

Local size

---

---

---

---

6x2

---

---

CO2- System (a/m)


ASD

LV auxiliary transformers

Dry
Chemical

Smoke

Various

00/11/12/21/
22/31/32
UBD 01-05

---

3)

---

---

---

Outdoor hydrants

---

---

---

---

Control Sprinkler

---

---

Spray deluge system (a/m)

---

---

---

---

Control Sprinkler

---

---

Spray deluge system (a/m)

---

---

---

---

Control Sprinkler

---

---

Spray deluge system (a/m)

---

---

---

---

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
21 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

00UBH
01 - 05
00UBN

Oil separator

Various

---

Black start & Emergency power


generation

1)

Hydrant
Cabinets/
2)
Hose reels

---

---

---

Fire Suppression Systems

3)

Outdoor hydrants

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

---

---

---

---

---

---

---

---

Generator room

Diesel

Flame

---

Electrical room

PVC

Smoke

Clean agent system (a/m)

Diesel

Heat

---

PVC

---

---

---

Outdoor hydrants

---

---

---

---

Tank outside building

Outdoor hydrants installation of


2 HC with foam

00UBS

Cable pulling pit

31/32UBX

Generator circuit breaker for steam


turbine

Various

---

---

---

Outdoor hydrants

---

---

---

---

11/12/21/22
UBX

Generator circuit breaker

Various

---

---

---

Outdoor hydrants

---

---

---

---

11/12/21/22
/31/32UBY

Cable bridge

Various

---

---

---

Outdoor hydrants

---

---

---

---

00UEN

Gas conditioning skid (open structure)

Fuel gas

---

---

---

---

---

11/12/21/ 22
UEN

Gas filter and preheating

Fuel gas

---

---

---

---

---

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
22 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

1)

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

---

---

---

---

---

---

00UEY

Pipe bridge and sleeperway

00UGD

Water treatment plant & condensate


building
Electrical equipment room

PVC

Smoke

False floor

PVC

ASD

Chemical storage area

Chemicals

Smoke

---

Vessel and pump area

Various

Smoke

---

Various

---

---

---

Outdoor hydrants

---

---

---

---

PVC

---

---

---

---

---

Various

---

---

---

2HR

Outdoor hydrants

Clean agent system (a/m)

00UGE

Neutralization system

10UGJ

Cooling tower make-up water treatment

00UGU 01

Utilities effluent pit

Various

---

---

---

Outdoor hydrants

---

---

---

---

00UGU 02

Accidentally oil contaminated waste


water pit

Various

---

---

---

Outdoor hydrants

---

---

---

---

00UGV

Sewerage pit

Various

---

---

---

Outdoor hydrants

---

---

---

---

00UGY 01

Pipe bridge and sleeperway

Various

---

---

---

Outdoor hydrants

---

---

---

---

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
23 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

11/12/21/22
UHA

11/12/21/22
UHN

Automatic

Hydrant
Cabinets/
2)
Hose reels

4x7

---

Risk

Heat recovery steam generator (open


structure)
Duct firing skid fuel gas

Various

---

Fuel gas

---

Various

Smoke

Elevator

Bypass stack hydraulic unit

Hydraulic oil

Smoke

Fire Suppression Systems

---

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

4x7

4x7

---

---

4x1

4x1

---

---

---

4x1

Bypass stack and diverter

1)

-----

11/12/21/22
UHW

Boiler blow down tank

Various

---

---

---

Outdoor hydrants

---

---

---

---

11/12/21/22
UHX

Sampling containers

Various

Smoke

2x2

---

---

2x2

2x2

---

---

11/12/21/22
UHY

Pipe bridge

Various

---

---

---

Outdoor hydrants

---

---

---

---

2x2

---

2x2

2x2

---

---

10/20ULA

Feed water pumps

Feed water pumps

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Oil

Electrical heat

---

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
24 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

30UMA
21/22UMB

33

Steam turbine building

Lube oil tank and lube oil lines

Hydraulic skid

Accessible steam turbine and steam


turbine generator bearings

1)

Lube oil

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

3)

19HC

Sprinkler

Sprinkler system (a)

Sprinkler/Smoke

Pre-action sprinkler system (a)

Flame/Heat/Smoke

CO2- System (a/m)

Sprinkler/Heat/Smoke

Sprinkler system (a)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

37

37

---

---

20

20

---

---

4x2

4x2

---

---

Hydraulic oil
Oil

Gas turbine building

11/12UMB

11/12/21/22
UMX

Gas turbine enclosure incl. fuel gas skid

Fuel gas

Lube oil skids without enclosure

Lube oil

Seal oil skid

Seal oil

Sprinkler

Sprinkler system (a)

Hydraulic skid

Hydraulic oil

Sprinkler/Smoke

Sprinkler system (a)

Accessible gas turbine generator bearings

Oil

Sprinkler/Smoke

Pre-action sprinkler system (a)

20

Gas turbine building

Gas turbine enclosure incl. fuel gas skid

Fuel gas

Lube oil skids without enclosure

Seal oil skid

Hydraulic skid

Accessible gas turbine generator bearings

Diffuser

8HC

Flame/Heat/Smoke

CO2- System (a/m)

Lube oil

Sprinkler/Heat/Smoke

Sprinkler system (a)

Seal oil

Sprinkler

Sprinkler system (a)

Hydraulic oil

Sprinkler/Smoke

Sprinkler system (a)

Oil

Sprinkler/Smoke

Pre-action sprinkler system (a)

Various

---

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

4x2

---

Outdoor hydrants

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
25 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

1)

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

11/12/21/22/
30UMY

Pipe bridge and sleeper ways

Various

---

---

---

Outdoor hydrants

---

---

---

---

30URA

Cooling tower structure

Various

---

---

Outdoor hydrants

---

---

00USG

Firefighting pump house

Various

Sprinkler

---

Sprinkler system (a)

---

---

00UST

Workshop and storage building

21

8HC

21

21

---

---

01.01 Facility Services

01.02 Electrical Equipment

Various

Smoke

---

PVC

Smoke

---

01.03 Janitor

Various

Smoke

---

01.04 Airlock

Various

Smoke

---

01.05 Balance room

Various

Smoke

---

01.06 Laboratory room

Various

Smoke

---

01.07 Document room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.08 Foreman room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.09 Maintenance Manager room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.10 Oil and paint storage room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.11 Hot room

Various

Smoke

---

01.12 Machine Hall

Various

Sprinkler / Smoke

Sprinkler system (a)

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
26 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

1)

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

01.13 Store keeper room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.14 Storage area

Various

Sprinkler / Smoke

Sprinkler system (a)

01.15 Storage small parts

Various

Sprinkler / Smoke

Sprinkler system (a)

01.16 Welding area

Various

Sprinkler / Heat

Sprinkler system (a)

01.17 Toilet

Various

Smoke

---

01.18 Staircase

Various

Smoke

---

01.19 Office Technicians

Various

Sprinkler / Smoke

Sprinkler system (a)

01.20 Mechanical Supervisor

Various

Sprinkler / Smoke

Sprinkler system (a)

01.21 Mechanical Maintenance

Various

Sprinkler / Smoke

Sprinkler system (a)

01.22 Electrical Maintenance

Various

Sprinkler / Smoke

Sprinkler system (a)

01.23 I&C Maintenance

Various

Sprinkler / Smoke

Sprinkler system (a)

01.24 Cold room

Various

Smoke

---

01.25 Corridor

Various

Smoke

---

01.26 Pantry Common room 1

Various

Heat

---

01.27 Locker room male

Various

Smoke

---

01.28 Anteroom Male

Various

Smoke

---

01.29 Toilet Male

Various

Smoke

---

01.30 Toilet / shower / locker room

Various

---

---

01.31 Anteroom Female

Various

Smoke

---

01.32 Locker Female

Various

Smoke

---

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
27 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

1)

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

01.33 Toilet Female

Various

Smoke

---

02.01 HVAC

Various

Smoke

---

02.02 Airlock

Various

Smoke

---

02.03 Prayer room Male

Various

Smoke

---

02.04 Prayer room Female

Various

Smoke

---

02.05 Training room

Various

Sprinkler / Smoke

Sprinkler system (a)

02.06 Maintenance engineering room

Various

Sprinkler / Smoke

Sprinkler system (a)

02.07 Chargeman room

Various

Sprinkler / Smoke

Sprinkler system (a)

02.12 Void Machine Hall

Various

Sprinkler / Smoke

Sprinkler system (a)

02.14 Void storage area

Various

Sprinkler / Smoke

Sprinkler system (a)

02.15 Storage small parts

Various

Sprinkler / Smoke

Sprinkler system (a)

02.16 Void Welding area

Various

Sprinkler / Heat

Sprinkler system (a)

02.18 Staircase

Various

Smoke

---

02.19 Corridor

Various

Smoke

---

02.20 EHV Supervising Engineer

Various

Sprinkler / Smoke

Sprinkler system (a)

02.21 Document Room

Various

Sprinkler / Smoke

Sprinkler system (a)

02.22 Turn around shut down office

Various

Sprinkler / Smoke

Sprinkler system (a)

02.23 Meeting room

Various

Sprinkler / Smoke

Sprinkler system (a)

02.24 Cleaner`s room

Various

Smoke

---

02.25 Corridor

Various

Smoke

---

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
28 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

1)

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

02.26 Storage

Various

Smoke

---

02.27 Pantry / Common room 2

Various

Heat

---

02.28 Locker / Shower Male

Various

---

---

02.29 Anteroom Male

Various

Smoke

---

02.30 Toilet Male

Various

Smoke

---

02.31 Shower / Locker Female

Various

---

---

02.32 Anteroom Female

Various

Smoke

---

02.33 Toilet Female

Various

Smoke

---

Suspending ceiling

PVC

ASD

---

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

00USV

Laboratory room

Various

Sprinkler / Smoke

2HR

Sprinkler system (a)

---

---

11/12/21/22
USX

Chemical dosing shelter

Various

Electrical heat

2x1

---

---

2x1

2x1

---

---

00USY

Sleeperway

Various

---

---

---

Outdoor hydrants

---

---

---

---

11/12/21/22/
UTG

Gas bottle storage H2 and H2 bottle racks

Various

Heat

4x1

---

Outdoor hydrants

4x2

4x2

---

---

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
29 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

00UTR

Chemical and lube oil storage building

Various

Smoke

00UYC / UCA Administration and control room building

1)

Hydrant
Cabinets/
2)
Hose reels

2HR

16

13HR

Fire Suppression Systems

---

01.01 Staircase

Various

Sprinkler / Smoke

Sprinkler system (a)

01.02 Open plan office

Various

Sprinkler / Smoke

Sprinkler system (a)

01.03 Corridor

Various

Sprinkler / Smoke

Sprinkler system (a)

01.04 Meeting room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.05 Shower room

Various

---

---

01.06 Toilet Female

Various

Smoke

---

01.07 Anteroom

Various

Sprinkler / Smoke

Sprinkler system (a)

01.08 Office room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.09 Storage

Various

Sprinkler / Smoke

Sprinkler system (a)

01.11 Staircase

Various

Sprinkler / Smoke

Sprinkler system (a)

01.12 Corridor

Various

Sprinkler / Smoke

Sprinkler system (a)

01.13 Office room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.14 Eng. Trainer performance room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.15 Office room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.16 Toilet Male

Various

Smoke

---

01.17 Anteroom Toilet Male

Various

Smoke

Sprinkler system (a

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

---

---

20

24

---

---

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
30 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

1)

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

01.18 Shower / Locker Male

Various

---

---

01.19 Tea kitchen

Various

Sprinkler / Heat

Sprinkler system (a)

01.20 Corridor

Various

Sprinkler / Smoke

Sprinkler system (a)

01.21 HVAC room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.22 Airlock

Various

Sprinkler / Smoke

Sprinkler system (a)

01.23 UPS Charger

Various

Smoke

False floor / suspending ceiling of 01.23

Various

ASD

01.24 Electrical AC room

Various

Smoke

False floor / suspending ceiling of 01.24

Various

ASD

01.25 LV Trafo

Various

Sprinkler / Smoke

Sprinkler system (a)

01.26 Facility services

Various

Sprinkler / Smoke

Sprinkler system (a)

01.27 Batteries for CCR DC system

Various

Smoke

False floor / suspending ceiling of 01.27

Various

ASD

01.28 Batteries for Solar system

Various

Smoke

False floor / suspending ceiling of 01.28

Various

ASD

01.29 Electr. equipment for solar system

Various

Smoke

False floor / suspending ceiling of 01.29

Various

ASD

01.30 Instrumentation & Control room

Various

Smoke

False floor / suspending ceiling of 01.30

Various

ASD

01.31 Fire Fighting

Various

Sprinkler / Smoke

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

Clean agent system (a/m)

Clean agent system (a/m)

Clean agent system (a/m)

Clean agent system (a/m)

Clean agent system (a/m)

Clean agent system (a/m)


Sprinkler system (a)

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
31 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

1)

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

01.32 Engineering office

Various

01.33 Shift engineer

Various

01.34 Billing Computer

Various

01.35 Control room

Various

01.36 Engineering office

Various

False floor / suspending ceiling of 01.32;


01.33; 01.34; 01.35; 01.36

Various

ASD

01.37 Discussion room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.38 Document room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.39 Electrical equipment room

Various

Smoke

False floor / suspending ceiling of 01.39

01.40 Simulator Training room

False floor / suspending ceiling of 01.40

01.41 Cleaners room

Various

Sprinkler / Smoke

Sprinkler system (a)

01.42 Toilet disabled

Various

Smoke

---

01.43 Lobby

Various

Sprinkler / Smoke

Sprinkler system (a)

01.44 First Aid

Various

Sprinkler / Smoke

Sprinkler system (a)

01.45 Permit office

Various

Sprinkler / Smoke

Sprinkler system (a)

02.01 Staircase

Various

Sprinkler / Smoke

Sprinkler system (a)

02.02 Conference room

Various

Sprinkler / Smoke

Sprinkler system (a)

Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

CO2

Water

Foam

9kg

5kg

Local size

Local size

Clean agent system (a/m)

Smoke
ASD

Siemens

Dry
Chemical

Smoke

ASD
Various

3)

Clean agent system (a/m)

Clean agent system (a/m)

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
32 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

1)

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

02.03 Corridor

Various

Sprinkler / Smoke

Sprinkler system (a)

02.04 Operation Manager

Various

Sprinkler / Smoke

Sprinkler system (a)

02.05 HSE Manager

Various

Sprinkler / Smoke

Sprinkler system (a)

02.06 Shower / Locker Female

Various

---

---

02.07 Toilet Female

Various

Smoke

---

02.08 Anteroom

Various

Sprinkler / Smoke

Sprinkler system (a)

02.09 Prayer room Female

Various

Sprinkler / Smoke

Sprinkler system (a)

02.10 Storage

Various

Sprinkler / Smoke

Sprinkler system (a)

02.11 Staircase

Various

Sprinkler / Smoke

Sprinkler system (a)

02.12 Corridor

Various

Sprinkler / Smoke

Sprinkler system (a)

02.13 Prayer room Male

Various

Sprinkler / Smoke

Sprinkler system (a)

02.14 Toilet Male

Various

Smoke

---

02.15 Anteroom Toilet Male

Various

Sprinkler / Smoke

Sprinkler system (a)

02.16 Shower / Locker Male

Various

---

---

02.17 Tea kitchen

Various

Sprinkler / Heat

Sprinkler system (a)

02.18 Copy / Printing

Various

Sprinkler / Smoke

Sprinkler system (a)

02.19 Corridor

Various

Sprinkler / Smoke

Sprinkler system (a)

02.20 Facility services

Various

Sprinkler / Smoke

Sprinkler system (a)

02.21 Airlock

Various

Sprinkler / Smoke

Sprinkler system (a)

02.22 Open plan office

Various

Sprinkler / Smoke

Sprinkler system (a)

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
33 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

1)

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

02.23 Training room

Various

Sprinkler / Smoke

Sprinkler system (a)

02.24 Office

Various

Sprinkler / Smoke

Sprinkler system (a)

02.25 Account Manager

Various

Sprinkler / Smoke

Sprinkler system (a)

02.26 Library

Various

Sprinkler / Smoke

Sprinkler system (a)

02.27 HR / Admin

Various

Sprinkler / Smoke

Sprinkler system (a)

02.28 Meeting room

Various

Sprinkler / Smoke

Sprinkler system (a)

02.29 Office / Library

Various

Sprinkler / Smoke

Sprinkler system (a)

02.30 Open roof terrace with Sun


protection

---

---

---

02.31 Flat roof

---

---

---

02.32 Discussion room

Various

Sprinkler / Smoke

Sprinkler system (a)

02.33 Filling room

Various

Sprinkler / Smoke

Sprinkler system (a)

02.34 Plan Manager

Various

Sprinkler / Smoke

Sprinkler system (a)

02.35 Secretary

Various

Sprinkler / Smoke

Sprinkler system (a)

02.36 General Manager

Various

Sprinkler / Smoke

Sprinkler system (a)

02.37 Toilet / shower / Locker

Various

---

---

02.38 Cleaners room

Various

Sprinkler / Smoke

Sprinkler system (a)

All false floors

Various

ASD

---

All suspended ceiling

Various

ASD

---

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
34 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

00UYE
01 - 02

Gate houses

Various

00UYG
OPTION

Visitor Center

Various

Smoke

1)

Hydrant
Cabinets/
2)
Hose reels

2x4

---

4HR

Fire Suppression Systems

---

01.01 Multi Dressing room

Sprinkler / Smoke

Sprinkler system (a)

01.02 Storage room

Sprinkler / Smoke

Sprinkler system (a)

01.03 Audio / Video control room

Smoke

---

01.04 Auditorium

Sprinkler / Smoke

Sprinkler system (a)

01.05 Female Surau

01.06 Toilet Female

Smoke

---

01.07 Anteroom Female

01.08 Toilet disabled

Smoke

---

01.09 Anteroom Man

01.10 Toilet Man

Smoke

---

01.11 Male Surau

01.12 Canteen / Cafeteria

01.13 Lunch counter

Heat

---

01.14 Scullery

01.15 Storage Area

Sprinkler / Smoke

Sprinkler system (a)

01.16 Preparation area

Heat

---

01.17 Airlock Delivery

Smoke

---

01.18 Facility service and connection

Smoke

Clean agent system (a/m)

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

2x2

2x2

---

---

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&BDB070-550401


Index / Date:
Page:
Fire Detection

0/05 / 2015-07-16
35 of 36

Fire Suppression
Portable / Mobile Extinguishers

Building / Area

Risk
Automatic

01.18 False floor service and


connection

01.19 HVAC room

Smoke

01.20 Server room

Smoke

01.20 False floor server room

01.21 Emergency control center

01.22 Lobby / reception

01.23 Airlock

1)

Hydrant
Cabinets/
2)
Hose reels

Fire Suppression Systems

3)

Dry
Chemical

CO2

Water

Foam

9kg

5kg

Local size

Local size

ASD
--Clean agent system (a/m)

ASD
Smoke

---

Sprinkler / Smoke

Sprinkler system (a)

Smoke

---

All other false floors

ASD

---

All suspending ceilings

ASD

---

UZ

Outdoor area

Various

---

---

---

Outdoor hydrants

---

---

---

---

UZD

Parking area

Various

---

---

---

Outdoor hydrants

---

---

---

---

Abbreviations
1)

m = manual push button

2)

HC Hydrant cabinet (cabinet with hose reel and tubes) HR Hose reel

3)

a = automatic release of extinguishing system; m = manual release of extinguishing system

Siemens
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.

Document No.: MY1008-5504-&ADB070-550401


Index / Date:
Page:

0/05 / 2015-07-16
36 of 36

5 Escape Route and Fire Protection Drawings


The fire protection measures described within this concept are shown in the following
overview drawings. Detailed information related to the design or function of the fire protection
systems are described in the respective system description.
Building / Structure
UAC
UBE / UBF / UTG

Drawing No
MY1008-5504-ABS040-550450
MY1008-5504-ABS040-550436
MY1008-5504-ABS040-550437
MY1008-5504-ABS040-550438
MY1008-5504-ABS040-550439
UHA
MY1008-UHA-ABS040-550430
MY1008-UHA-ABS040-550431
MY1008-UHA-ABS040-550432
MY1008-UHA-ABS040-550433
MY1008-UHA-ABS040-550434
UMA
MY1008-UMA-ABS040-550440
MY1008-UMA-ABS040-550441
UMB
MY1008-5504-ABS040-550410_11-12UMB
MY1008-5504-ABS040-550411_11-12UMB
MY1008-5504-ABS040-550412_11-12UMB
MY1008-5504-ABS040-550413_11-12UMB
MY1008-5504-ABS040-550414_21-22UMB
MY1008-5504-ABS040-550415_21-22UMB
MY1008-5504-ABS040-550416_21-22UMB
MY1008-5504-ABS040-550417_21-22UMB
URA
MY1008-00URA-ABS040-550435
UST
MY1008-00UST-ABS040_550442
UYC / UCA
MY1008-5504-ABS040-550451
MY1008-5504-ABS040-550452
UYE
MY1008-5504-ABS040-550450
Other buildings will be added soon as Will be added
available

Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its
contents and communication thereof to others without express authorization are prohibited. Offenders
will be held liable for payment of damages. All rights created by patent grant or registration of a utility
model or design patent are reserved.
Fire Protection Concept_Pengerang_00_04_01withcombinedUCAandvistorcenter.docx