Sei sulla pagina 1di 16

Cont.No.

HAL/FMD/EC-2524/13-14

Page 1 of 16

http://eproc.hal-india.com
HINDUSTAN AERONAUTICS LIMITED
BANGALORE COMPLEX
FACILITIES MANAGEMENT DIVISION
NAME OF THE WORK: " Providing Air-Conditioning Facility to the existing Strutural Assembly Hangar by modifying the Existing Force
draft Ventillation System at LCA - PG Division, HAL (BC)."
Cont.No.HAL/FMD/EC-2524/13-14
PRICE BID
Name of the Contractor :
BILL OF QUANTITIES WITH SPECIFICATIONS

Notes: The tenderers are requested to read the following before quoting
1) The payment terms shall be governed as per terms indicated in special conditions of contract.
2) Rate quoted shall be inclusive of all taxes and duties except Service Tax.However,the tenderers are requested to indicate the applicable
service tax as on date of service and also indicate the anticipated service tax amount separately as indicated.
3) L-1 will be determined without considering the service tax element.
4) The Service Tax will calculated as per Annexure-S Sl.No 2.a (40% of the quoted value will be considered as labour portion)
to Tenderers.

Of Instructions

5) Service Tax will be reimbursed against claims as indicated at clause No-27 of Instructions to Tenderers.
6)The tenderers are requested to abide by the rules of prevailing service tax act.
Sl.
No

Specification of item

PART-A :AIR-CONDITIONING WORK


I)

CHILLERS AND AHUS

Quanti
ty

Unit

Rate in Figs
(excluding
Service Tax)

Rate in words

Amount in Rs
(excluding
Service Tax)

Cont.No.HAL/FMD/EC-2524/13-14

Page 2 of 16

AIR COOLED SCREW CHILLER

Supply, installation, testing, commissioning and handing over of compact Air


cooled water chilling machine consisting of 130TR capacity semi hermetically
sealed screw multi compressors suitable for R-134a refrigerant complete with
suction and discharge valves, relief valve, oil filter, suction filter, dual pressure
switch, oil safety switch, crank case heaters, crank case heater relay, automatic
capacity control etc. and pressure relief valve and 1 No. DX/flooded chiller
complete with insulation, anti freeze thermostats, cooling themostats,
thermostatic expansion valves, liquid line strainer, shut off valve,
interconnecting refrigerant pipes and fittings, suction line insulation, first charge
of refrigerant and oil including multiple air cooled condensers with condensating
coils, fans, fan motors, casing all assembled together on a common MS frame
and mounted on vibration isloating spring mounts as per standards including
necessary internal wiring complete.
The units shall be of suitable
The units shall be controlled
BMS compatible controller for
and casing and expandable
complete in all respects.

Nos

#VALUE!

0.00

Nos

#VALUE!

0.00

for outdoor service and for pedestal installation.


by suitable Microprocessor based programmable
the above units with all necessary internal wiring
with LCD display as per technical specification

CAPACITY ; 130TR-( 2W +1S )


2

PRIMARY CHILLED WATER PUMPS

Supplying, Installing, testing and commissioning of Single stage centrifugal Back


pull out CHILLED WATER PUMPS, factory mounted on a common base with
electric motor for recirculation of water for the central air conditioning system.
All pumps shall be aligned properly as required. The pump motor shall be TEFC
squirrel cage,415+10% volts, 50 cycles, 3 phase power supply. Pumps with
performance characteristics as given below. The noise level shall be limited to 65
dBA at a distance of 1.8 m The quoted price shall also include cost of thermal
insulation, cladding and Spring vibration isolator. The complete unit should be
suitable for outdoor installation in the platform as indicated in the layout
drawing.
No of Pumps (2W +1S )
Water flow rate :306 USGPM
Motor RPM: 1500 RPM ( Maximum )
Total Head = 22 MWC

Cont.No.HAL/FMD/EC-2524/13-14

Page 3 of 16

AIR HANDLING UNITS


Design, Supply, installation on annexe second floor roof, testing &
commissioning of sheet metal cabinet type double skin air handling unit of
0.6mm outer and 0.6mm inner and 45mm thick
thermal break profile
34000CFM with 55 mm static pressure ,6 row deep cooling coils, complete with
coil section cooling coil, filter section with washable synthetic type filters,
damper section with dampers, DIDW centrifugal backword curve inclined blade
fan, squuirrel cage induction fan motor, belt drive, belt guard, SS Drain Tray,
fresh air inlet with pre-filter, fine filter,return air with mixing chamber and filters
etc. including all accessories. As per technical specification complete in all
respects.

Nos

#VALUE!

0.00

Supply installation and testing of Sequence


controling, sequencing the AHU, Chillers, Water
wiring ,termination of control wiring laying in
accesseries and fixing arrangement complete in
Engineer in charge etc.

Set

#VALUE!

0.00

control panel for automatic


Pumps etc including all control
the MS conduit including all
all respect and as directed by

II) CHILLED WATER PIPE & VALVES WORKS


5

CHW-PIPING
Supply, Installation, testing and commissioning of Insulated MS C class chilled
water pipe of following size with 75mm thick Expanded polystyrene TF Quality
insulation with 24G AL cladding with necessary fittings like, elbows, tees etc.
including clamps, brackets, anchors etc. chipping and plastering of affected
areas in walls, roof, ceiling as directed by engineer in charge for supporting the
pipes.MS Supporting arrangement shall be measured seperatly complete in all
repect and as directed by Engineer in charge.

150 mm dia

120

Rmt

#VALUE!

0.00

125 mm dia

200

Rmt

#VALUE!

0.00

100 mm dia

160

Rmt

#VALUE!

0.00

BUTTERFLY VALVES
Supply, Installation, testing and commissioning of following sizes extended stem
type slimseal butterfly valves with companion flanges and hot dip galavanized
bolt & nuts for chilled water piping including insulation complete as per technical
specification.

Cont.No.HAL/FMD/EC-2524/13-14

Page 4 of 16

125 mm dia valves

12

Nos

#VALUE!

0.00

100 mm dia valves

Nos

#VALUE!

0.00

Motorised shut off valve


3

Nos

#VALUE!

0.00

Nos

#VALUE!

0.00

Supply, Installation, testing and commissioning of 125 mm dia 2-way Motorized


ON/OFF valves with actuator complete.
8

NON-RETURN VALVES
Supply, Installation,testing and commissioning of 125 mm dia non return valves
for chilled water piping including insulation complete as per technical
specification.

Y' STRAINERS
Supply and fixing of the following dia 'Y' strainer for chilled water piping
including insulation complete as per technical specification.

125 mm dia valves

Nos

#VALUE!

0.00

100 mm dia valves

Nos

#VALUE!

0.00

10

BALANCING VALVES
Supply Installation Testing and commissioning of the following size manual
balancing valves including insulation complete in all respect.

125 mm dia valves

Nos

#VALUE!

0.00

100 mm dia valves

Nos

#VALUE!

0.00

12

Nos

#VALUE!

0.00

11

BELLOWS
Supply, Installation ,testing and commissioning of 125mm dia flexible
connections of suitable pressure rating to be installed at CHILLERS, & Pumpsets
inlets & outlets and at pipes crossing building expansion joints rubber bellows
complete as per specification.

12

3-Way Mixing Valve for AHU

Cont.No.HAL/FMD/EC-2524/13-14

Supply, Installation, testing and commissioning of 80mm dia 3 way mixing valve
complete as per specification.
13

Nos

#VALUE!

0.00

12

Nos

#VALUE!

0.00

Nos

#VALUE!

0.00

10

Nos

#VALUE!

0.00

60

Rmt

#VALUE!

0.00

No

#VALUE!

0.00

EXPANSION TANK
Supply, installation & commissioning of
Closed expansion tank of 1500L
capacity made of mild steel and has a synthetic rubber membrane. Nitrogen gas
or compressed air is filled in space between the membrane and the wall of the
tank. The tank should be supplied complete with pump of 2 nos (1W+1S),
isolating valve, check valve, strainer, drain valve & pressure gauge. Before
connecting the tank to water system, the gas pressure should be checked
through the charging valve and adjusted according to the requirements. It shall
be suitable for outdoor installation and pump motor IP-55,mounted on existing
duly painted MS frame work for installation the expansion tank.Complete in all
respect and as directed by engineer in charge.

III) AIR DISTRIBUTION


19

18

DRAIN PIPING
Supply, installation, testing & commissioning of 32 mm dia GI Class 'B' Drain
pipes with all screwed joints, including necessary elbows, tees and reducers as
per specifications, etc

18

0.00

AUTO AIR VENTS


Supply and Fixing Automatic Air Vents with valves, complete in all respect.

17

#VALUE!

WATER FLOW SWITCH


Supply and fixing of water flow switches for chilled water and condenser water
lines.

16

Nos

THERMOMETERS
Supply and fixing of Dial type 4" Thermometers of mercury in steel enclosure
with 6" stem and copper thermowell, range suitable for the temperature
services. Complete in all respect.

15

PRESSURE GAUGE
Supply and installation of dial type pressure gauge 4" dia complete with syphon
and cock.

14

Page 5 of 16

DUCT WORKS

Cont.No.HAL/FMD/EC-2524/13-14

Page 6 of 16

Design, supply, installation & testing and commissioning of factory fabricated


GSS ducting with zinc coating of minimum class VIII ie. 120GSM total on both
sides as per IS 277 complete with suspenders of MS rods / wall brackets,
cradles, angle iron supports, bolts and nuts, gaskets, stiffeners, canvas
connections, fixing of anchor grip bolts, zinc chromate painted angle iron
flanges, chipping and plastering of opening made for duct supports, outside air
in takes complete with bird screen, damper, bowl, rough filters etc. complete as
per specifications:
Note: Duct support
shall be measured separately
a

24 G

100

Sq.Mtrs

#VALUE!

0.00

22 G

150

Sq.Mtrs

#VALUE!

0.00

20 G

750

Sq.Mtrs

#VALUE!

0.00

18 G

150

Sq.Mtrs

#VALUE!

0.00

20

FLEXIBLE CONNECTION (FOR AHU CONNECTION)


Supply, fabrication, installation and testing the flexible connections constructed
of fire resistance flexible double canvas sleeve as per required size.Complete

22

#VALUE!

0.00

Sq.Mtrs

#VALUE!

0.00

22

Sq.Mtrs

#VALUE!

0.00

10

Sq.Mtrs

#VALUE!

0.00

DAMPERS
VOLUME CONTROL DAMPERS
Supply and Fixing of G.I. Volume control dampers with factory made 1.6 mm
thick of GSS blades,complete with linkage, nylon gears and MS flanges for
mounting on ducts. Complete and as per standard practice.

Nos

SUPPLY/RETURN GRILL
Supply, installation, testing and balancing of powder coated Extruded Supply/
Return air Aluminium grills

24

FRESH AIR ARRANGEMENT


Supply and fixing of fresh air intake in AHU cabins with wall cowls, bird screen
and dampers

23

#VALUE!

FIRE DAMPERS with Actuator

Cont.No.HAL/FMD/EC-2524/13-14

Supply, Fixing,testing and commissioning of Motorised UL555S rated smoke and


fire dampers complete with spring loaded actuator including stepdown
transformer, controller, output to BMS and factory made 1.6mm thick, 400 mm
long GSS sleeves suitable for 90 minute fire rating and control panel with
required lengths of control wiring as per site requirments.The damper shall be
motorised to close the damper and trip the AHU's in the event of smoke/fire
automatically and open the same in case of power being restored.Complete in
all respect.

Page 7 of 16

10

Sq.Mtrs

#VALUE!

0.00

20

Sq.Mtrs

#VALUE!

0.00

850

Sq.Mtrs

#VALUE!

0.00

Supply, Installation & Testing of Thermal Insulation for supply and return air
ducts with 13mm thick Close cell elastomeric nitrile insulation with self
adhesives and factory laminated reinforced aluminium foil on one side Joints
b.1
shall be overlapped and joints sealed with 75 mm wide aluminium foil self
adhesive tape. A per technical specification, Complete and as per standard
practice.

2300

Sq.Mtrs

#VALUE!

0.00

Supply, Installation & Testing of Thermal Insulation for all exposed supply and
return air ducts with 25mm thick Close cell elastomeric nitrile insulation with
self adhesives and factory laminated reinforced aluminium foil on one side Joints
b.2
shall be overlapped and joints sealed with 75 mm wide aluminium foil self
adhesive tape. Covered with weather proof polyshield coating of approved
colour.As per technical specification, Complete in all respect.

500

Sq.Mtrs

#VALUE!

0.00

COLLAR DAMPERS
Supply and installation of Powder coated GI Collar Dampers for supply air grill
fixed to collar complete in all respect.

25
a

INSULATION
ACOUSTIC INSULATION
Supply & Installation of Acoustic insulation for Supply and return air ducts with
25 mm thick rigid fibre optic glass of 48Kg/Cum density covered with factory
laminated RP tissue and 26 G perforated Aluminum sheet etc. As per technical
specification, Complete in all respect.

THERMAL INSULATION

Cont.No.HAL/FMD/EC-2524/13-14

Supply and Fixing of Underdeck insulation for hangar roof galvanized sheet
(corrugated) at the height of 12 mtr using 50 mm thick fiberglass insulation with
oneside factory laminated aluminium sheet using bituminous paint to fix the
insulation on the sheet with additional support of GI net for entire insulated area
using GI washers and tie wires on perlins including all accesseries and required
hardware as per site requirement and as directed by Engineer in charge.
Scaffloding/mobile crane shall be arranged by contractor. Complete and as per
standard practice.
Note
:Contractor should make sure that there should not be any sag after fixing the
insulation.

PART-B

Out door weather proof kiosk for Panel Board-1

Page 8 of 16

3500

Sq.Mtrs

#VALUE!

0.00

Set

#VALUE!

0.00

ELECTRICAL WORKS

Design, fabrication, supply, installation, testing and commissioning of the


following weatherproof cubicle type Outdoor LT Panel with front lockable door
arrangement, suitable to be mounted on the existing brick pedestal using M.S
channel frame work, with cable entry from bottom with removable gland plates
with required knock-outs, panel fabricated out of CRCA sheet steel folded and
braced as necessary to provide a rigid support for all components, totally
enclosed, dust and vermin proof and degree of protection shall not be less than
IP-55, multi-tier cubicle type formation with front hinged doors lockable doors
for the individual feeders/compartments, preparation of surface and treatment
by seven tank process, powder coated with approved colour for not less than 50
microns, with front lockable door(double leaf), and all doors and covers shall be
fully gasketed using good quality EPDM gasket and/or rubber strips and ensure
good lockable, durable door opening & closing mechanism, suitable meshed
ventilator louvers with suitable cover,

canopy type top cover to avoid rainwater collection/entry, Aluminium bus bars
for three phases and neutral, bus bar insulators, heat shrinkable PVC sleeves
etc., with necessary interconnections as specified in Technical specifications for
electrical & mechanical works, comprising of following switchgear and
accessories complete in all respects and as directed by Engineer-in-charge.

Note :- 1. The operating height of the Panel shall not exceed 2.1 mtr. from FFL.

2. The brick pedestal will be measured separately.

Cont.No.HAL/FMD/EC-2524/13-14

Incoming

a)

01-No., 800A, TPN, 415V gr. 50 KA manually operated drawout type Air Circuit
breaker of approved make suitable for 415V, 3 Phase & Neutral supply with
microprocessor based tripping device comprising of overload, short circuit,
instantaneous and ground fault protection and separate LED indications for
overload, short circuit and ground fault along with release and also micro
switches for service, isolated and locking positions for the breaker, door
interlock, secondary isolating contacts, auxillary contacts as required including
ON/OFF indications, trip push button, front operating handle and other
connected accessories complete in all respects.

b)

1 No- 3ph, 240V(L-N), 5A, CL-1,RS 485 Port Digital multi data meter of L&T
Quasar/
Conzerv
EM6400/Schneider
PM
210
including
necessary
interconnections.

c)

Lot- 1000A, TP (3 bus bars) Aluminium bus bars and 500 A neutral Aluminium
bus bar with busbar insulators, heat shrinkable PVC sleeves etc., complete.

d)

1 Set- RYB indicating lamps of LED module with toggle switches.

e)

1 Set- 2A, 230V gr. SP MCB's for the protection of measuring instruments for all
feeders.

f)

1 Set - 800/5A, Class 1 CT's with suitable VA burden for metering and
protection.
Outgoing

e)

5Nos- 400 A 415V gr. 35KA TPNL MCCB


Note :- All the MCCBs in the above panels shall be with adjustable thermal
settings (80% to 100%) and fixed Magnetic setting, overload and short circuit
releases including door interlocking device and front operating handle ON and
OFF indication using LED module complete in all respects.

Out door weather proof Panel Board-2

Page 9 of 16

Cont.No.HAL/FMD/EC-2524/13-14

Design, fabrication, supply, installation, testing and commissioning of the


following weatherproof cubicle type Outdoor LT Panel with front lockable door
arrangement, mounted on the M.S channel frame work at terrace roof, with
cable entry from bottom with removable gland plates with required knock-outs,
panel fabricated out of CRCA sheet steel folded and braced as necessary to
provide a rigid support for all components, totally enclosed, dust and vermin
proof and degree of protection shall not be less than IP-55, multi-tier cubicle
type formation with front hinged doors lockable doors for the individual
feeders/compartments, preparation of surface and treatment by seven tank
process, powder coated with approved colour for not less than 50 microns, with
front lockable door(double leaf), and all doors and covers shall be fully gasketed
using good quality EPDM gasket and/or rubber strips and ensure good lockable,
durable door opening & closing mechanism, suitable meshed ventilator louvers
with suitable cover,

canopy type top cover to avoid rainwater collection/entry, Aluminium bus bars
for three phases and neutral, bus bar insulators, heat shrinkable PVC sleeves
etc., with necessary interconnections as specified in Technical specifications for
electrical & mechanical works, comprising of following switchgear and
accessories complete in all respects and as directed by Engineer-in-charge.
Note :- 1. The operating height of the Panel shall not exceed 2.1 mtr. from FFL.
i)

Incoming

a)

1 No - 400A, 415V 35KA TP+NL, Moulded Case Circuit Breaker with overload &
short-circuit protection including front operating handle, door interlocking
system etc., complete in all respects.

ii)

Outgoing

b)

5-Nos. 63A,35KA TP+NL 415 V gr MCCB with overload and short circuit releases
including door interlocking device,front oerating handle ON and OFF indication of
LED module etc. complete in all respect.

c)

5 Nos.-32A,TPN MCB 10KA,415V gr. With overload and short circuit releases 'C
curve'.

Page 10 of 16

Set

#VALUE!

0.00

Cont.No.HAL/FMD/EC-2524/13-14

d)

3 Nos- fully automatic panel mounted type Star-Delta starter suitable for 15 HP
chilled water motors rating, AC 3 duty 415V, 50Hz, 3ph motor. The starter shall
be with single phase prevention and electronic timer, with sufficient auxiliary
contacts for remote ON/OFF indication lamps, bi-metallic thermal overload relay
of suitable size current rating,
ON/OFF push buttons suitably wired and
interconnected with 2.5 Sq.mm single stranded PVC copper wires,
etc,
complete in all respects.

e)

3 Nos- fully automatic panel mounted type Star-Delta starter suitable for 35 HP
chilled water motors rating, AC 3 duty 415V, 50Hz, 3ph motor. The starter shall
be with single phase prevention and electronic timer, with sufficient auxiliary
contacts for remote ON/OFF indication lamps, bi-metallic thermal overload relay
of suitable size current rating,
ON/OFF push buttons suitably wired and
interconnected with 2.5 Sq.mm single stranded PVC copper wires,
etc,
complete in all respects.

LT Cables

Page 11 of 16

Supply & laying of following size cables in the cable trench/cable trays/existing
duct/fixing on wall with necessary M.S clamps/ encasing in pipes etc., testing &
commissioning of following size PVC/XLPE insulated Aluminium conductor 1100V
gr. Armoured U.G cables of suitable size as per technical specifications of the
tender document and as detailed below.
a)

3.5 C x 300 Sqmm Al Arm LT Cable

600

Mtrs

#VALUE!

0.00

b)

3.5 C x 120 Sqmm Al Arm LT Cable

300

Mtrs

#VALUE!

0.00

c)

3.5 C x 25 Sqmm Al Arm LT Cable

150

Mtrs

#VALUE!

0.00

d)

4 C x 10 Sqmm Al Arm LT Cable

150

Mtrs

#VALUE!

0.00

Cable End Terminations

Nos

#VALUE!

0.00

Supply and connecting indoor type cable end joints / flame proof joints for the
following size 1.1 KV gr., Aluminum conductor PVC/XLPE insulated armoured LT
UG cables by employing necessary glands/ flame proof double compression
glands , terminals, bolts & nuts etc., complete in all respects and as detailed
below:
a)

3.5 C x 300 Sqmm Ar LT Cable

Cont.No.HAL/FMD/EC-2524/13-14

b)

3.5 C x 120 Sqmm Al Arm LT Cable

c)

Page 12 of 16

16

Nos

#VALUE!

0.00

3.5 C x 25 Sqmm Al Arm LT Cable

Nos

#VALUE!

0.00

d)

4 C x 10 Sqmm Al Arm LT Cable

Nos

#VALUE!

0.00

Supply and laying in already excavated trench 250mm dia size RCC hume pipe
with collars and jointing the same with 1:6 cement mortar and closing ends of
pipe with gunny bags and as directed after encasing the cable complete in all
respects.

25

Mtr

#VALUE!

0.00

Fabrication, supply, fixing/welding to the existing steel truss/wall/steel


columns/roof suitable size duly painted with one cote of primer MS angles/flats
with cross supports, clamps etc. for suspending/ fixing on wall/ roof the drain
pipes / refrigerant pipes/ chiller pipes/cable trays/ Duct/ water tanks etc. as
required at the site as directed by Engineer in charge.

1500

Kgs

#VALUE!

0.00

Supply, fixing & connecting 32x6mm G.I strip on wall / clamping to the existing
wall / fixing on steel structures/ laying 2 ft. below the ground level including
excavation, refilling, consolidation & levelling of soil after laying for
interconnection between the earth pits and the panels/DBs, Looping the
incoming & outgoing cable glands etc as directed by Engineer-in-charge.

150

Mtr

#VALUE!

0.00

Supply, fixing and connecting 8 gauge G.I wire between the DB's /SMC box/
cables, poles, Looping the incoming & outgoing cable glands etc ensuring earth
continuity etc., complete as directed by Engineer in charge.

50

Rmt

#VALUE!

0.00

Supply, fabricating, installing the following size perforated GI cable Trays


including horizontal and vertical bends, reducers, tees, cross members and
other accessories as required and duly suspended from the ceiling/fixing to the
wall/RCC beam/iron structures , using existing M.S. angle supports and
including necessary fixing hardware as required and as per site requirements.
Note : 1. Cable tray support will be measured separately.

300X 50 MM, 2mm thick

150

Rmt

#VALUE!

0.00

150 X 50 MM 2mm thick

200

Rmt

#VALUE!

0.00

Cont.No.HAL/FMD/EC-2524/13-14

10

Dismantling of existing 6 nos. Ventilation AHUs, Existing Duct, Plenum, dampers


including all connected accessories as is basis at terrace roof (approximate 11
mtr height from ground level) complete in all respect , shifting from terrace roof
AHU to the place as shown by the Engineer in charge/Plant maintenance
department of LCA-PG Division (Not more then 3 KM) including loading
transporting unloading etc as instructed by Engineer in charge.

Page 13 of 16

LS

#VALUE!

0.00

Demolition of reinforced Cement Concrete of any description and at any height


including cutting, scaffolding, removing the debris to a distance exc.1500m but
not exc. 5000m and depositing etc., completed all as directed by Engineer - In Charge (EIC).

Cmtr

#VALUE!

0.00

Dismantling / Removing existing Zincalume/


Galvalume Sheets of any
description from roofing / cladding from Supporting members etc., including
cutting, scaffolding, returning the serviceable materials to HAL stores and debris
off the site etc., complete all as directed by EIC.

25

Sqmtrs

#VALUE!

0.00

Dismantling existing Brick Masonry of any description including scaffolding,


removing the debris to a distance exc.1500m but not exc. 5000m and
depositing, scaffolding, etc., complete all as directed by EIC.

Cmtr

#VALUE!

0.00

Dismantling structural steel of any description from door / claddign frame work
etc., including cutting, dewelding, scaffolding, removing the debris off the site
and handing over serviceable materials to stores etc., complete all as directed
by EIC.

Qtl

#VALUE!

0.00

Earth work excavation over areas for foundation in all soils of depth not exc. 1.5
mtrs and getting out including returning filling in sides of foundation in layers of
20 cms thick with excavated earth, watering, consolidation including removing
the surplus earth to a distance exceeding 1500 mtrs but not exceeding 2000
mtrs. and depositing, spreading, levelling where directed etc., complete all as
dircted by EIC.

Cmtr

#VALUE!

0.00

Supplying, mixing and placing cement concrete (1:4:8) using 40mm down
graded granite aggregates of thickness as required including consolidation,
curing, formwork for bed concrete etc., complete all as directed by EIC.

1.5

Cmtr

#VALUE!

0.00

Supplying, mixing & Placing Cement Concrete 1:1.5:3 with 20mm down graded
granite aggregate for foundations including Pedestals etc., aligning and placing
in position Foundation bolts as per drawings, consolidation, curing, form work,
etc., complete all as directed by EIC. (Bolts will be paid seperately)

Cmtr

#VALUE!

0.00

Part -C: Miscellaneous civil works for Airconditioning

Cont.No.HAL/FMD/EC-2524/13-14

Supplying, Fabricating and Fixing Purlins, Runners, Beams, Lug angles,


Supporting Plates made up of MS Structurals of ISMC, ISAS ,MS Plates for ,
including welding, cutting, embedding in concrete, scaffolding etc., complete all
as dircetd by EIC.

Page 14 of 16

1540

Kg

#VALUE!

0.00

1540

Kg

#VALUE!

0.00

18

Smtr

#VALUE!

0.00

11

Providing and fixing Aluminium-glazed Three track Sliding window with Powder
coated (thickness of powder coating not less than 70 Micron) aluminium Frame
work with aluminium section of bottom frame not less than 92 x31.75 mm of
thickness 1.50 mm, weighing not less than 1.06 kg/m with side and top sections
not less than 92x 31.75 of thickness 1.50 mm weighing not less than 1.06 kg/m
to accomdate required shutters of each section 40x18x1.29 mm all round
weighing not less than 0.45 kg /m
including necessary
jointing cleats,
supplying& fixing plain Glass 5.5 mm thick for shutters, rubber gaskets,
powder coated aluminium snap beading, screws, powder coated aluminium
fittings and locking arrangements etc., complete all as dircted by EIC.

Smtr

#VALUE!

0.00

12

Supplying and Fixing in position Pre- painted Galvalume Corrugated steel sheets
0.50mm thick of approved colour & profile having Tensile strength not less than
550 Mpa in Roofs / cladding / doors fixed with self taping screws, neoprene
washers including L-flahings, drip moulds, lapping, wastage, etc., complete all
as per manufacturer's speciifcation and as directed by EIC. [The quotated rate
shall include all lapings, flashing sheets for water proof, measurement shall be
on finished plain surface]

200

Smtr

#VALUE!

0.00

10

Painting the Structural Members with Two Coats of Synthetic Enamel Paint of
approved Colour and Manufacture over a coat of approved red Oxide Zinc
Chrome Primer, including Preparation of Surface, scaffolding, etc., complete all
as dircted by EIC.
Providing and installing aluminium fully glazed partitions in required opening size
with outer frame verticals and horizontal members (of powder coated not less
than 50 micron thk) aluminium extruded rectangular hollow tubes from alloy
conforming to designation 63400 of I.S 737 and temper W.P (H.E.9 W.P) of
'JINDAL', 'INDAL' or other approved equivalent manufacture comprising of the
following:
a) Anodised Aluminium extruded rectangular hollow tubes measuring not less
than (101 X 44 X 2.0)mm for outer frame, intermediate, verticals and
horizontals spaced at 100cms. centres (approximately)
b) Panels fixed with 5.0mm thick sheet glass of approved quality, conforming to
I.S.2835 in panes exceeding 0.50 Smtrs including providing glass louvers
wherever required etc.,
c) Superior quality rubber glazing gaskets and aluminium tapered glazing clips
0.7mm thick and measuring (19 X 17)mm self interlocking screwless, snap on
type for fixing glazing, etc. all complete as directed by Engineer-in-charge.

Cont.No.HAL/FMD/EC-2524/13-14

Page 15 of 16

13

Providing Brick work with table moulded bricks built in cement mortar (1:6) for
superstructure at all levels for
23cms thick
walls including raking out
joints 10mm deep scaffolding, curing etc., all complete as directed by the
Engineer-in-Charge. (Brick conforming to IS 1077: Sub Class A having
compressive strength not less than 35Kgs/ Sq.cms).

Cmtr

#VALUE!

0.00

14

Supplying, spreading 225 mm consolidated thick WBM in Three layers [Each


75mm thk] using 63mm down size hard aggregate including all interstices filled
with good quality sand for each layer, hand rolled, consolidated, watering,
required level , etc., complete all as dirceted by EIC.

25

Smtr

#VALUE!

0.00

15

Supplying and Laying in position 175mm thick Controlled grade CC M20


Concrete using 20mm down graded granite aggregate for Pavement including
consolidation, Power Trowel and top finished by belting, curing, form work in
sides, etc., complete all as directed by EIC.

25

Smtr

#VALUE!

0.00

16

Painting the Interior surfaces of walls and ceilings with two coats of oil bound
washable distemper of approved shade and manufacture conforming to IS 428
on previously painted surface /new surfaces after preparation of surface, a coat
of primer, putty whereever required, scaffolding, etc., all complete as directed
by the EIC.

25

Smtr

#VALUE!

0.00

17

Painting external walls with Two coats of Weather Proof emulsion of high grade
(Apex Ultima or other equivalent) of approved colour & manufacturer including
preparation of surface, one coat of suitable primer, putty where ever required,
scaffolding, washing down the surface etc., complete all as directed by EIC.

25

Smtr

#VALUE!

0.00

18

Plastering with cement mortar (1:4) 10mm thick on concrete / brick surfaces
finished smooth with lime rendering / sand finish including, curing, scaffolding,
etc., all complete as directed by the Engineer-in-Charge.

65

Smtr

#VALUE!

0.00

#VALUE!

0.00

Total (Without Service Tax)

Applicable Service Tax in percentage :

12.36%

100% Service tax @ 12.36% on 40% of the total amount as calculated - Rs.:

0.00

Sl. No
3

Specification of item
PART-A :AIR-CONDITIONING WORK
AIR HANDLING UNITS
Design, Supply, installation on annexe second floor roof,
testing & commissioning of sheet metal cabinet type double
skin air handling unit of 0.6mm outer and 0.6mm inner and
45mm thick thermal break profile 34000CFM with 55 mm
static pressure ,6 row deep cooling coils, complete with coil
section cooling coil, filter section with washable synthetic
type filters, damper section with dampers, DIDW centrifugal
backword curve inclined blade fan, squuirrel cage induction
fan motor, belt drive, belt guard, SS Drain Tray, fresh air inlet
with pre-filter, fine filter,return air with mixing chamber and
filters etc. including all accessories. As per technical
specification complete in all respects.

Quantity

Unit

Nos