Calculation Procedures
Jeffrey D. Spitler, Ph.D., P.E.
Ipseng (Calvin) Iu
Oklahoma State University
Building and Environmental Thermal
Systems Research Group
Introduction
Limitations what limitations?
Simplified Procedures
ASHRAE 942-RP
Examples (Primarily with RTS)
ASHRAE 942-RP
Comparison of ASHRAE and CIBSE load
calculation procedures.
Compared results of procedures for
thousands of different zones.
Sample Results
Heavyweight Zones
Lightweight Zones
500
700
600
2
400
500
400
300
200
300
200
100
100
0
100
200
300
400
500
600
2
700
100
200
300
400
2
500
Example
Two-story (+ basement) office building
located in Chicago. Look at first floor,
Northeast zone.
Heavyweight walls: brick/concrete block
Floor: Lightweight layer on top of 4 concrete
Ceiling: 4 concrete, airspace, acoustic tile
Lightweight partitions: gypsum/studs
20'-0"
20'-0"
15'-0''
Office
Storage
15'-0"
3
Office
Corridor
Toilet
20'-0"
4
Conference
Room
5
Office
7
Lobby
50'-0"
50'-0"
10'-0"
Example
North wall (150 sq. ft. total) has 40 sq. ft. of
double-pane windows
East wall (200 sq. ft. total) has 60 sq. ft. of
double-pane windows.
4 people on office schedule
1 W/sq. ft. equipment on office schedule
1 W/sq. ft. fluorescent lighting
No infiltration.
Overly high design condition: high of 96 F,
19 F range
Base case
Base - Chicago
16000
14000
12000
10000
HBM
8000
RTS
6000
4000
2000
0
1
13
Time (hrs)
17
21
35000
30000
25000
20000
HBM
RTS
15000
10000
5000
0
1
13
-5000
Time (hrs)
17
21
40000
35000
30000
25000
HBM
20000
RTS
15000
10000
5000
0
1
13
-5000
Time (hrs)
17
21
Summary - Chicago
Chicago
35%
Overprediction
30%
25%
20%
DP
15%
SP
10%
5%
0%
Base
Base+50%
Base+100%
Base+200%
35000
30000
25000
20000
HBM
15000
RTS
10000
5000
0
1
13
-5000
-10000
Time (hrs)
17
21
Seattle Summary
Seattle
40%
35%
Overprediction
30%
25%
DP
20%
SP
15%
10%
5%
0%
Base
Base+50%
Base+100%
Base+200%
626-RP Tabulated WF
+29%
16000
14000
12000
HBM
10000
RTS
8000
TFM
6000
4000
2000
0
1
13
Hour
17
21
Conclusions
RTS procedure works well for many
zones.
RTS procedure may over predict for
zones with high amounts of glazing
Exacerbating factors include:
Single pane glass
Low outdoor design temperatures