Introduction
Introduction
1.1
This volume sets out the requirements of the National Water Services
Commission (SPAN), referred to as the Commission in this document
for the design and construction of individual septic tanks within
developments.
Developments of more than 150 PE shall not employ the use of septic
tanks.
An individual septic tank can only serve one premise. The largest capacity
of individual septic tank shall not be more than 30 PE. Where the design
PE is more than 30 for a single unit of building or sub-divided lots, other
system of treatment shall be provided. Furthermore, the use of multiple
individual septic tanks within a single sub-divided lot is not allowed.
The developer shall consult the following MSIG for developments that
falls outside the scope of this volume, namely:
Volume 1
Volume 2
Volume 3
Volume 4
The user of this volume of the MSIG shall also refer to Volume 3 of
the above guidelines on the provision of oil and grease interceptors to
protect sewerage treatment systems from the discharge of these matters
from hotels, restaurants, canteens, garage workshops or any premises
that collects such matters.
This volume does not cover the installation of internal plumbing systems
to buildings. The requirements for internal plumbing systems are managed
by the relevant Local Authorities.
Septic Tanks
Volume 5
Introduction
1.2
The Environment Quality Act (EQA) 1974 specifies two standards for
effluent discharge. These are namely Standard A for effluent discharge
located upstream of raw water intake points and Standard B for effluent
discharge located downstream of the raw water intake points. The
current Third Schedule of the Environmental Quality Act 1974, under the
Environmental Quality (Sewage and Industrial Efluents) Regulations 1979,
regulations 8 (1), 8 (2) and 8 (3) has been revisited and the Department
of Environment (DOE) has proposed 8th Schedule for the Act which
stipulate effluent discharge limits for parameters specific to domestic
wastewater. The effluent discharge limits in 8th Schedule are summarised in
Appendix B.
BOD5
Suspended Solids
: 50 mg/l
: 100 mg/l
1.3
Volume 5
Malaysian Sewerage
Industry Guidelines
Introduction
1.4
This volume does not cover all aspects of design and construction of
septic tanks. Where information is not covered in this volume, the designer
shall follow the requirements given in MS 1228: 1991 Code of Practice
for Design and Installation of Sewerage Systems.
Malaysian Standards
Other Documents
Volume
Volume
Volume
Volume
Septic Tanks
Volume 5
Section 2
General Guidelines
General Guidelines
2.1
Initial Consultation
It is advised that the matters listed in section 2.2 and 2.3, and 2.4 for
homestead developments, are discussed and clarified before making a
formal application to the Commission.
2.2
2.3
Where a public sewer is not available, the developer shall consider the
following before proceeding:
a)
b)
c)
Septic Tanks
Volume 5
General Guidelines
2.4
Homestead Developments
2.4.1
The owner must provide all septic tanks as part of the owners infrastructure
works. Septic tanks must be constructed to standard design.
The owner must provide a 150 mm by-pass pipe from the last manhole
before the septic tank and extended to the outside drain line of the
premises. The pipe end shall be capped for future connection. Please
refer to Section 3.2.8 of this Volume for further details.
2.4.2
2.4.3
For single development over 30 units in total and with an average housing
density of less than 25 persons per hectare, a sewer reticulation and a
treatment plant is preferred.
a)
b)
10
Volume 5
Malaysian Sewerage
Industry Guidelines
General Guidelines
c)
d)
e)
2.4.4
a)
b)
d)
f)
c)
e)
Septic Tanks
Volume 5
11
Section 3
Design Guide
Design Guide
3.1
General
Organic loading from the incoming raw sewage shall be based on 250
mg/ of BOD5 (5 days at 20oC) per population equivalent per day, and
300 mg/ of suspended solids per population equivalent per day.
In Malaysia, there exist two (2) forms of septic tank which have found
wide usage. The first type is a cast in-situ septic tank previously promoted
by the Ministry of Health. The cast in-situ septic tank consists of a septic
tank with a minimum of 24 hours hydraulic retention time followed by
a dual size aggregate down flow filter media. The second type is the
prefabricated septic tank manufactured locally using polyethylene, glass
fiber reinforced plastic or reinforced precast concrete materials. The
filter chamber for prefabricated septic tanks is incorporated inside of the
septic tank on the outlet section (as opposed to the filter chamber located
externally in the cast in-situ septic tanks) to enhance its performance.
One fundamental difference between the cast in-situ and the prefabricated
septic tanks is the size of the filter employed. The cast in-situ employs
the use of stone filter several orders of magnitude larger than the typical
proprietary filter media used in the prefabricated septic tanks. The other
distinction is the direction of flow employed. The stone filters employ
the use of a down-flow scheme while the proprietary filters use an upflow scheme. Both of the fundamental differences have some bearing on
the treatment performance and the site (topography); where each type of
the septic tank may have special niche in its applications.
Septic Tanks
Volume 5
15
Design Guide
a)
3.2
Planning
i)
ii)
iii)
iv)
v)
vi)
vii)
3.2.1
Site Selection
a)
b)
16
Site Selection
Maintenance Vehicle Access
Safety Requirements
Desludging Works
Location of Septic Tank within Premise of Property
Inspection Chamber
Septic Tank Drawings
Malaysian Sewerage
Industry Guidelines
Design Guide
c)
d)
e)
f)
g)
h)
i)
3.2.2
The Water Services Industry Act 2006 has the following clauses relating
to vehicle access for desludging and other maintenance works:
a)
b)
Septic Tanks
Volume 5
17
Design Guide
a)
b)
c)
d)
3.2.3
Safety Requirements
a)
b)
Care must be taken when entering septic tanks. Ensure that the
gases in the septic tanks are thoroughly ventilated before entry.
c)
3.2.4
Desludging Works
3.2.5
a)
18
b)
c)
Open space.
e)
d)
Fully accessible.
Volume 5
Malaysian Sewerage
Industry Guidelines
Design Guide
Septic tanks shall be situated at the rear end of properties to allow for
maintenance vehicle movements and to minimise visual impact. However,
if this is not possible due to inavailability of backlane access, it shall
be located at the front end.
3.2.6
Inspection Chamber
Inspection chambers are required where septic tanks are installed for
maintenance purposes. It is required at the following locations:
a)
b)
At each bend.
c)
d)
3.2.7
a)
Septic Tanks
b)
Volume 5
19
Design Guide
c)
d)
e)
f)
3.2.8
a)
b)
c)
20
A plan of the septic tank and filter to a scale of not greater than
1:50 showing the general arrangement of pipeworks, compartments,
baffles and channels and critical dimensions.
Point of discharge of final treated effluent to the drain, water course
or soakaway system.
See Appendix F and G for the location and typical details of the bypass
line.
Volume 5
Malaysian Sewerage
Industry Guidelines
Design Guide
3.3
Design
3.3.1
Volumetric Capacity
The volumetric sizing of septic tanks shall be based on per capita wastewater
generation rate of 225 litres/day and for a hydraulic retention time of
24 hours. This is the effective working volume which is required for
the biological degradation of the wastewater and excludes the volume of
head room of air above the water level, accumulated sludge volume for
2 years and filter media if placed within the septic tank. This minimum
volumetric capacity of septic tanks shall not be less than 2000 litres or
2 cubic meters.
Working Volume, C
Where,
C
PE
Desludging Period
Hydraulic Retention Time
= 225 x PE
= 0.04 m3/PE.year
Effective Working Volume = Working volume + Accumulated sludge
volume
Septic Tanks
The effective volumes for the varies PE for septic tank are shown in
Table 3.1
Volume 5
21
Design Guide
Minimum Working
Volume
L
1125
1350
1575
1800
2025
2250
2475
2700
2925
3150
3375
3600
3825
4050
4275
4500
4725
4950
5175
5400
5625
5850
6075
6300
6525
6750
m3
1.125
1.350
1.575
1.800
2.025
2.250
2.475
2.700
2.925
3.150
3.375
3.600
3.825
4.050
4.275
4.500
4.725
4.950
5.175
5.400
5.625
5.850
6.075
6.300
6.525
6.750
Accumulated Sludge
Volume in 2 years
L
400
480
560
640
720
800
880
960
1040
1120
1200
1280
1360
1440
1520
1600
1680
1760
1840
1920
2000
2080
2160
2240
2320
2400
m3
0.40
0.48
0.56
0.64
0.72
0.80
0.88
0.96
1.04
1.12
1.20
1.28
1.36
1.44
1.52
1.60
1.68
1.76
1.84
1.92
2.00
2.08
2.16
2.24
2.32
2.40
Required
Effective
Working Volume
L
m3
1525
1.525
1830
1.830
2135
2.135
2440
2.440
2745
2.745
3050
3.050
3355
3.355
3660
3.660
3965
3.965
4270
4.270
4575
4.575
4880
4.880
5185
5.185
5490
5.490
5795
5.795
6100
6.100
6405
6.405
6710
6.710
7015
7.015
7320
7.320
7625
7.625
7930
7.930
8235
8.235
8540
8.540
8845
8.845
9150
9.150
3.3.2
Compartmentalisation
Cast in-situ septic tanks shall be designed with two or more compartments.
The capacity of the first compartment shall not be less than two thirds
of the total volume. The division wall in two compartment tank shall
have openings of at least 100 mm with a total area of at least 150 cm2.
Openings shall be located at mid-liquid depth. The division wall shall
have a ventilation air space at the underside of the roof to allow the
free passage of gases.
22
Volume 5
Malaysian Sewerage
Industry Guidelines
Design Guide
For vertical flow septic tank, baffle wall or scum box shall be provided to
prevent scum and Oil & Grease (O&G) from entering the filter chamber.
Wall of filter chamber could be considered as baffle wall if up-flow filter
chamber is adopted.
3.3.3
The inlet pipes to and outlet pipes from the septic tank shall be a
minimum diameter of 100 mm and by means of dip pipes made of cast
iron, or uPVC with sufficient stiffness and thickness located below the
scum level. The inlet dip pipe shall utilise a T-shape pipe and the outlet
dip pipe shall utilise a 90 elbow pipe.
The difference in level between the invert level of the inlet pipe and
the invert level of the outlet pipe shall be a minimum of 75 mm. The
minimum distance between the inlet pipe and the outlet pipe shall be
1300 mm.
The depth of the submerged end of the inlet dip pipe shall be extended to
a minimum of 300 mm below the water level. In the outlet pipe section,
the depth of the submerged end of the outlet dip pipe shall range from
375 mm to 610 mm below the water level. The non-submerged ends of
both inlet and outlet dip pipes shall be projected of at least 150 mm
above the water level.
Septic Tanks
Volume 5
23
Design Guide
Effluent Discharge
Submersible Pump
a)
b)
c)
Pump Well
a)
b)
c)
d)
e)
3.3.5
Head Room
The space between the top water level and the underside of the tank
shall be a minimum of 250 mm and must be adequately ventilated or
provided with an adequate means of drawing off gases. A minimum
of 50 mm diameter pipe or a minimum of 75 mm diameter ventilation
duct provided in the septic tank to the exterior shall be proofed against
the entry of mosquitoes by a fine mesh screen. The design of all septic
tanks shall prevent mosquito breeding. All covers shall be air tight.
24
Volume 5
Malaysian Sewerage
Industry Guidelines
Design Guide
3.3.6
Covers
The covers of the septic tank and inspection chamber shall be adequately
reinforced to take superimposed loadings. These cover shall be airtight,
and may be of light duty if not subjected to vehicular loading. If these
cover are subjected to higher loading then suitable covers shall be
used based on this higher loading the cover shall come with hinge and
lock.
Where bigger cover is required due to deep sited tanks chequered plate
of mild steel or ductile iron with protective coating may be used. The
chequered plate shall be of reasonable size, having a maximum weight
of 16kg/piece, to facilitate its removal and handling. Secondary air tight
covers shall be provided at the septic tank opening when chequered plates
are provided at ground level. The secondary covers shall be airtight and
manufactured in accordance to the relevant standards.
3.3.7
Construction
Where bricks are used to construct septic tanks, the following additional
conditions shall apply:
a)
b)
Septic Tanks
the depth of a 220 mm thick brick wall tank shall not exceed 1500
mm below ground surface, and
the depth of a 300 mm thick brick wall shall not exceed 2000 mm
below ground surface.
Volume 5
25
Design Guide
Where septic tanks are of precast units, all internal surface shall be
coated with sulphate resisting material or approved product or epoxy
coating materials.
In cases where the septic tank may be subjected to traffic load or other
surcharges, such as those installed in industrial development, the tank shall
be of reinforced concrete design with Engineers approval. In the case of
the proprietary type septic tanks, strict adherence to the manufacturers
specification must be observed.
3.3.8
The principal dimensional requirements for cast in-situ septic tanks are
shown in Table 3.2
Table 3.2 Cast In-situ Septic Tank Dimensions
Requirement
Dimensions
Liquid depth
Minimum width
815 mm
1.5:1
250 mm
100 mm
100 mm
3.3.9
26
Volume 5
Malaysian Sewerage
Industry Guidelines
Design Guide
Dimensions
100 mm
250 mm
50 mm
1.3 m
1.5 : 1
3.4
Non-proprietary Systems
All non-proprietary septic tanks shall comply with cast in-situ septic tanks
details with a minimum of 24 hours hydraulic retention time followed
by a dual size media downflow filter chamber. Typical design drawings
are available for two (2) categories of size; less than 12 PE and 12-30
PE are provided in Appendices H and I, respectively. These drawings
shall show the critical dimensions of the septic tank as well as the stone
filter chamber design.
3.5
Proprietary Systems
Septic Tanks
Volume 5
27
Design Guide
the approved list. All tests required by the Commission shall be done
in accordance with approved standards/methods.
3.5.1
Tank Material
a)
b)
c)
d)
e)
Laminates shall contain not less than 30% chopped glass strands
and be not less than 3 mm thick. All edges of openings and
covers of the tank shall be increased to a minimum thickness
of 6 mm for a minimum distance of 40 mm and shall have
a minimum of 30% glass. No fillers shall be included in the
laminate. The laminate thickness shall be uniform. Pigments
may be allowed on the outer surfaces.
f)
28
Volume 5
Malaysian Sewerage
Industry Guidelines
Design Guide
3.5.2
3.5.3
a)
b)
c)
d)
Inspection chamber shall be provided after the septic tank if the discharge
point is more than 3 m or change direction of flow.
3.5.4
a)
b)
c)
Septic Tanks
Material shall be of cast iron and not other materials which, may
warp over time.
Volume 5
29
Design Guide
d)
e)
f)
g)
All fittings through the walls of the tanks, such as the ventilation,
inlet and outlet pipes, shall be installed with a permanent watertight
seal.
h)
3.5.5
a)
b)
c)
d)
e)
f)
g)
h)
The clearance between the crown of the inlet pipe and the underside
of the roof of the septic tank shall be at a minimum of 50 mm.
The BOD 5 loading of filter chamber shall not exceed 1.2 kg/
m3.day
The SS loading of filter chamber shall not exceed 1.0 kg/m3.day
i)
j)
3.5.6
Marking/Labelling
30
The volumetric loading of filter chamber shall not exceed 2.5 m3/
m3day.
The void percentage of filter chamber shall not be less than 80%.
The void percentage is referred to the interstitial voids for percolation
of the liquor.
Volume 5
Malaysian Sewerage
Industry Guidelines
Design Guide
a)
b)
c)
d)
e)
f)
g)
h)
The marking or label shall be located on top of the tank close to the
access opening and shall be left exposed and visible after installation.
3.5.7
a)
b)
c)
3.5.8
Installation
a)
b)
c)
d)
e)
Septic Tanks
Volume 5
31
Design Guide
3.5.9
a)
c)
All liquid inside the septic tank shall be completely pumped out
and an observation be made. If the tank fails in the buoyancy test
due to upthrust pressure or is distorted due to lateral pressure, the
septic tank shall be rejected. The failed tank shall be removed and
replaced with a new septic tank. The reinstalled septic tank shall
then be retested.
32
b)
The septic tank shall be water proofed and checked against leakage.
Volume 5
Malaysian Sewerage
Industry Guidelines
Section 4
Septic Tanks Located in Sensitive Receiving
Watercourses
4.1
General
4.2
a)
Septic Tanks
35
b)
c)
Proponents and designers who are keen to pursue how, when, and where
to design such a system, may consult a list of references as provided in
Appendix N.
4.3
Disinfection
36
Volume 5
Malaysian Sewerage
Industry Guidelines
Appendix
A to O
Appendix
Appendix
Number of
each similar
use
Building use
Participation in
gathering place
facilities
Estimation formula
n = 0.08 A
n = 16 C
n = 0.065 A
Dwelling house
n = 5 +(A - 100)
30
Estimation unit
n:
A:
n:
Participation in
housing facilities
A:
n = 0.07 A
n=P
a
3
Participation in
lodging facilities
Participation in
medical facilities
Participation in
shops
n = 0.05 A
Apartment - house
Hotel , and
RYOKAN
(Japanese)
(Japanese Hotel)
n = 0.15 A
n = 0.075 A
Motel
n=5R
n=P
Hospital,
sanatorium, and
in-fectious
hospital
For under
300 beds
n=8B
For under
300 beds
For not less
than 300
beds
n=5B
n = 0.19 A
n = 0.075 A
Department store
n = 0.15 A
Eating
house
population (man)
total floor area (m2)
population (man)
However, n is 5 men for not more
than 100 m2 in A and 10 men for
over 220 m2 in A .
A:
n:
A:
n:
population (man)
total floor area (m2)
population (man)
P:
n : population (man)
A:
n:
R:
n:
population (man)
number of guest rooms
population (man)
P:
n : population (man)
number of beds (bed)
A:
n = 7.14 (B -300)
+ 1500
C(1):
n:
A:
n:
n:
population (man)
n = 0.72 A
n = 2.94 A
n = 0.55 A
n:
population (man)
A :
n:
population (man)
total floor area (m2)
A:
n = 0.80 A
Teahouse
Septic Tanks
Volume 5
39
Septic Tanks
Volume 5
27
Appendix
Appendix
Number of
each similar
use
Building use
Participation in
amusement
facilities
Estimation formula
Estimation unit
n = 0.075 A
Pinball house
n = 0.11 A
n = 0.15 A
Discotheque
n = 0.50 A
n = 0.25 S
Bowling alley
n = 2.50 L
n = 0.20 S
Tennis Court
n=3S
n:
population (man)
n:
population (man)
n:
population (man)
number of lanes (lane)
n:
population (man)
number of batting seats (seat)
n:
population (man)
S :
population (man)
n = 16 C
(piece)
n:
C :
j
n = 20 C + 120 U x t
population (man)
number of closet bowls (piece)
t = 1.0 to 2.0
k
Camp site
n = 0.56 P
Golf course
n = 21 H
Service
Area
n:
population (man)
n:
population (man)
number of squares (square)
P :
n = 1.50 P
Stand
Participation in
parking area
population (man)
number of persons to be
admitted (man)
n = 6.15 P
Lavatory
n:
P :
n:
population (man)
number of closet bowls (piece)
C :
b
n = 20 C + 120 U x t
Participation in
school facilities
Gasoline stand
n = 20
n = 0.25 P
n = 0.31 P
Library
n = 0.08 A
n:
n:
population (man)
population (man)
40
Volume 5
Malaysian Sewerage
Industry Guidelines
28
Volume 5
Malaysian Sewerage
Industry Guideline
Appendix
Appendix
Number of
each similar
use
Participation in
office
10
Participation in
workshop
11
Building use
Participation
which do not
belong to users of
1 to 10
Office
Factory,
workshop,
laboratory and
ex-perimental
station
(2)
(3)
n = 0.075 A
Estimation unit
n:
population (man)
n:
population (man)
Market
n = 0.02 A
n = 0.17 A
Public lavatory
n = 16 C
n : population (man)
A : total floor area (m2)
n:
population (man)
Note:
(1)
Estimation formula
Station, and
bus terminal
n = 0.008 P
n = 0.010 P
n = 0.013 P
n:
population (man)
Total number of toilet stools is total sum of the number of closet bowls, the
number of urinals and the number of double use toilet stools
The living room herein, which is the living room specified by the definitions of
Building Standard Law, means a room continuously used for the purpose of
dwelling, execution of one's bussiness, operation, meeting, pleasure or the like.
However, a kitchen and a dining room in apartment house are excepted.
In a lady exclusive use lavatory, about one half of the number of toilet stools are
considered urinals.
Septic Tanks
Volume 5
41
Septic Tanks
Volume 5
29
Appendix
Appendix
The Environmental Quality Act (EQA) 1974 specifies two standards for effluent
Appendix
B: Effluent
Standards
to Malaysian
Inlandand
Waters
discharge.
Standard
A for Discharge
discharge upstream
of any
raw water intake
Standard
B for discharge downstream of any raw water intake.
The Environmental Quality Act (EQA) 1974 specifies two standards for effluent
discharge: Standard A for discharge upstream of any raw water intake and Standard B
Thedischarge
current downstream
Third Schedule
the
Environmental
Quality Act 1974, under the
for
of anyofraw
water
intake.
Design
BOD5
20
SS
50
COD
AMN
Nitrate
Nitrogen
Total
Phosphorus
O&G
Standard B
Standard A
Absolute
Design
Absolute
Design
10
50
20
20
20
100
40
50
120
60
200
100
10
20
20
10
N/A
Standard B
Absolute
Design
10
50
20
20
100
40
120
60
200
100
10
50
20
10
10
N/A
N/A
N/A
10
10
10
Notes:
Notes:
NA = Not Applicable
NAvalues
= Not
applicable
All
in mg/l
unless otherwise stated.
valuesWater
in mg/
unless
otherwise
stated.
*All
Stagnant
Bodies
refer to
enclosed water
bodies such as lakes, ponds and slow moving
watercourses
where dead
zonerefer
occurto enclosed water bodies such as lakes, ponds and
* Stagnant Water
Bodies
42
Volume 5
Malaysian Sewerage
Industry Guidelines
Appendix
Appendix
Front road
Front access
Bungalow/Factory 2
4
2 1
Legends :
Septic tank
Roadside drain
Property boundary (fence)
Rear access
Effluent to roadside drain
Backlane
Rear access
Septic tank
1 2
Gate
Inspection Chamber
1
2
3
4
5
Toilet
Bath
Kitchen sink
Wash room
Shower
4
5
Bungalow/Factory 1
Front access
Front road
Septic Tanks
Volume 5
Septic Tanks
Volume 5
43
31
RA
44
Volume 5
32
Volume 5
FA
FA
Frontal road
ST
ST
RA
RA
Backlane
FA
ST
ST
FA
RA
RA
FA
1, 2, 3, 4
ST
Gate
Inspection chamber
Septic tank
Roadside drain
Property Boundary (fence)
Legends :
Appendix
Appendix
Malaysian Sewerage
Industry Guidelines
Malaysian Sewerage
Industry Guideline
ST
Septic Tanks
Septic Tanks
FA
RA
RA
Volume 5
Volume 5
Frontal road
FA
Backlane
ST
RA
FA
1, 2
ST
Gate
Inspection chamber
Septic tank
Roadside drain
Boundary line
Legends :
Appendix
Appendix
45
33
Appendix
46
Volume 5
Malaysian Sewerage
Industry Guidelines
Appendix
Appendix
600 mm manhole
Brickwork with
cast iron manhole
cover
A
100 mm UPVC
inlet pipe
from WC
100 mm UPVC
pipe from WB/FT
sink
300 x 300 mm
grease trap
600 x 600 mm
outlet manhole
Rubber plug
Plan
Inlet manhole
Building boundary
Ground beam
Top water level
Rubber plug
Section A - A
Septic Tanks
Volume 5
Septic Tanks
Volume 5
47
35
Appendix
48
Volume 5
Malaysian Sewerage
Industry Guidelines
Appendix
Septic Tanks
Volume 5
49
Appendix
Appendix
Appendix J Typical detail of a proprietary septic tank
600mm O / 450x600mm
airtight cover & frame
ground level
200
brickwork extension
300 min.150
removable
filter
media
min. 100mm
outlet pipe
screwed type
filter chamber
cover
sand
backfilling
filter chamber
min.
150mm
working volume
HRT (min. 24 hours)
stainless steel
anchor strape
grade 304
7.5mm
TWL
min. 900mm
max. 2400mm
(liquid depth)
max. 3000mm
min. 100mm
inlet pipe
m in. 1300mm
min. 500mm
max. 2/3 d
250mm
freeboard
50mm ventilation
pipe to roof top
ground level
filter media
rem ovable
filter
m edia
w orking volum e
H R T (m in. 24 hours)
m in. 100m m
outlet pipe
scre w ed type
filter cham ber
cover
sand
backfilling
filter cham ber
min.
150mm
stainless steel
ancho r strape
grade 304
TW L
min. 500mm
max. 2/3 d
max. 3000mm
m in. 100m m
inlet pipe
m in . 13 00m m
min. 900mm
max. 2400mm
(liquid depth)
300 min.150
250mm
freeboard
50m m ventilation
pipe to roof top
ground level
g ro und level
filte r m edia
Volume 5
Volume 5
Malaysian Sewerage
MIndustry
alaysian SGuidelines
ewerage
Industry Guideline
Septic Tanks
Septic Tanks
Volume 5
Volume 5
600 - 1200 mm
900 - 1800mm
900 - 1800mm
Barrier
Material
Distribution Box
150 - 300mm of
20 - 60mm dia. rock
Perforated
Distribution pipe
Appendix
Appendix
51
39
Appendix
Appendix
C ap
S tra w , H a y or Fabric
F ill
A bs orptio n B ed
T o p s oil
1
3
P lo w e d L a y e r of Top Soil
S lo pe
S tra w , H a y or Fabric
C ap
F ill
A bs orptio n B ed
T o p s oil
1
P lo w e d L a y e r of Top Soil
P e rm e a b le Soil
W a te r T a b le o r C r e v iced B edrock
(b ) C r o s s S e c tio n o f a m o u n d S ystem for a P erm eable S oil,
w ith H ig h G r o u d W a te r o r S hallow C reviced B edrock
52
Volume 5
40
Volume 5
Malaysian Sewerage
Industry Guidelines
Malaysian Sewerage
Industry Guideline
Appendix
Appendix
Vent Pipe
A
Distribution box
House Sewer
Septic
Tank with
Filter
Discharge
Inspection
manhole
Plan
age
Marsh Hay or
drainage fabric
Perforated or Open
Joint Distributors
Graded Gravel
20-60mm diameter
Filter Media
Pea
Gravel
Graded
Gravel 6-40mm
SECTION A-A
Septic Tanks
Volume 5
53
Septic Tanks
Volume 5
41
Appendix
Appendix
54
Volume 5
42
Volume 5
Malaysian Sewerage
Industry Guidelines
Malaysian Sewerage
Industry Guideline
Appendix
Appendix
Appendix O : Typical Layout for Homestead Unit with Septic Tank &