Substation
Engineering

ABB Power Technologies


BA PTPS - 2 -

Substations

Content

Introduction

Various Switching Configuration

Interlocking & Protection


philosophy

Basics of layout engineering

Substation design calculation

Equipment & accessories

Interface requirement of control,


protection & SCADA

Statutory requirements & Safety


in substation

ABB Power Technologies


BA PTPS - 3 -

Substations

Introduction

Substations

Introduction

What is Substation ?

ABB Power Technologies


BA PTPS - 4 -

Substation is an Electrical installation


where power is controlled for
transmission & distribution purpose.

Substations can be categorized


as:

Power evacuation substation

Substation part of Transmission system

Substation part of Distribution system

Substations

Introduction : The Electric Utility

Power Evacuation Substation


Transmission Substation
Switching Substation

ABB Power Technologies


BA PTPS - 5 -

Distribution Substation

Substations

Introduction : Power Evacuation substation

ABB Power Technologies


BA PTPS - 6 -

Located adjacent to the Power Plant


Preferred voltage level

420 kV

245 kV

123,145 kV

72.5, 66 kV

Evacuation voltage level depends on

Quantum of power to be evacuated (size of


power plant)

Distance of Transmission

Gird network voltage of surrounding


transmission system

Normally built by

Utilities (e.g. NTPC, NHPC, Captive Power


Plant by industries)

Independent Power Producer (IPP)

Substations

Introduction : Transmission substation

Location is decided based on Transmission


Grid Network

Preferred voltage level

ABB Power Technologies


BA PTPS - 7 -

420kV

245kV

145kV

Transmission voltage depends on

Quantum of power to be received / transmitted

Length of transmission line

Normally built by

Utilities (e.g. Power Grid, State Electricity


Boards)

Substations

Introduction : Distribution substation

Location is near the load

Preferred voltage level

ABB Power Technologies


BA PTPS - 8 -

245kV

145kV

72.5/36 kV

Station voltage level depends on

Demand of power

Utility norms of distribution

Normally built by

Utilities (e.g. State Electricity Broads)

Industries

ABB Power Technologies


BA PTPS - 9 -

Substations

Switching
Configuration

Substations

Switching Configuration

What is Busbar configuration ?

ABB Power Technologies


BA PTPS - 10 -

Busbar configuration or Bus switching scheme


is the circuit adopted for substation based on
following:

System reliability

Operational flexibility

Ease of maintenance

Limitation of fault level

Simplicity of protection system

Ease of extension

Avaibility of land

Cost

Substations

Switching Configuration : Single Bus Scheme

ABB Power Technologies


BA PTPS - 11 -

With Sectionaliser

Substations

Switching Configuration : Single Bus Scheme


With Sectionaliser

ABB Power Technologies


BA PTPS - 12 -

Without Sectionaliser

ABB Power Technologies


BA PTPS - 13 -

Substations

Switching Configuration: Single Bus Scheme

ABB Power Technologies


BA PTPS - 14 -

Substations

Switching Configuration: Single Bus Scheme

ABB Power Technologies


BA PTPS - 15 -

Substations

Switching Configuration : Bus Sectionalizer

Substations

Switching Configuration: Single Bus Scheme

Application

Industrial stations with voltage level


generally up to 145kV

Also used for 245kV station with 2/3 bays

Features

ABB Power Technologies


BA PTPS - 16 -

Simple system

Ease of Operation & maintenance

Single level bus layout

Easily expandable

Very simple Control & Protection philosophy

Large saving in space

No redundancy

ABB Power Technologies


BA PTPS - 17 -

Substations

Switching Configuration: Double Bus Scheme

Double Bus with two


Main & without
Transfer

Double Bus with one Main


& one Transfer

Double Bus with one Main


& one Main cum Transfer

ABB Power Technologies


BA PTPS - 18 -

Substations

Switching Configuration : One Main & Transfer

ABB Power Technologies


BA PTPS - 19 -

Substations

Switching Configuration : One Main & Transfer

ABB Power Technologies


BA PTPS - 20 -

Substations

Switching Configuration : One Main & Transfer

ABB Power Technologies


BA PTPS - 21 -

Substations

Switching Configuration : Main & Main cum transfer

ABB Power Technologies


BA PTPS - 22 -

Substations

Switching Configuration : Main & Main cum transfer

ABB Power Technologies


BA PTPS - 23 -

Substations

Switching Configuration : Main & Main cum transfer

ABB Power Technologies


BA PTPS - 24 -

Substations

Switching Configuration : Double Main

ABB Power Technologies


BA PTPS - 25 -

Substations

Switching Configuration : Double Main

ABB Power Technologies


BA PTPS - 26 -

Substations

Switching Configuration : Double Main with bypass

ABB Power Technologies


BA PTPS - 27 -

Substations

Switching Configuration : Double Main with bypass

Substations

Switching Configuration:Application of Transfer Bus

ABB Power Technologies


BA PTPS - 28 -

Bus Coupler Bay

Substations

Switching Configuration : One Main & Transfer

Application

ABB Power Technologies


BA PTPS - 29 -

Normally this is used for most industrial


stations and some time small power
evacuation system

Features

Simpler system

Better availability as additional bus is


provided

Breaker can be taken out for maintenance


where transfer bus feature is provided

Substations

Switching Configuration: Three Bus Scheme


Transfer
Main-2

ABB Power Technologies


BA PTPS - 30 -

Main-1

Three Bus with Main I & II


and separate Transfer Bus

Substations

Switching Configuration: Three Bus Scheme

Transfer
Main-2

ABB Power Technologies


BA PTPS - 31 -

Main-1

Substations

Switching Configuration : Three Bus

ABB Power Technologies


BA PTPS - 32 -

Main Bus#1

Main Bus#2

Transfer Bus

ABB Power Technologies


BA PTPS - 33 -

Substations

Switching Configuration : Three Bus

ABB Power Technologies


BA PTPS - 34 -

Substations

Switching Configuration : Three Bus (Bus Coupler)

ABB Power Technologies


BA PTPS - 35 -

Substations

Switching Configuration : Three Bus (Bus Transfer)

Substations

Switching Configuration: Three Bus Scheme

ABB Power Technologies


BA PTPS - 36 -

Application

Power evacuation station

Interconnecting substation for transmission lines

Heavy Industrial stations viz. Steel, Aluminium,


Petro-chemicals

Features

Independent two buses sharing the feeder

Better load management

Better reliability

One transfer bay is in-built for redundancy of


one bay

Complex Control & Protection system

ABB Power Technologies


BA PTPS - 37 -

Substations

Switching Configuration: One & Half CB Scheme

Main-1
Main-2

ABB Power Technologies


BA PTPS - 38 -

Substations

Switching Configuration: One & Half CB Scheme

Main-1
Main-2

ABB Power Technologies


BA PTPS - 39 -

Substations

Various Busbar Configuration : One & Half CB Scheme

Substations

Switching Configuration: One & Half CB Scheme

ABB Power Technologies


BA PTPS - 40 -

Application

Mostly this configuration is adopted where high


reliability is required

Power evacuation station for big power plant

Interconnecting transmission substations with


420/245kV level

Features

Very high reliability

Costly because of increase no. of Circuit Breaker

Complex Control & Protection philosophy

Substations

Switching Configuration : Application

Power Generating Stations

Double Bus Scheme

Three Bus scheme

One & Half CB Scheme

Transmission Stations

Double Bus scheme

ABB Power Technologies


BA PTPS - 41 -

Main & Main cum transfer

Three Bus scheme

Two main & one transfer

Two main & one transfer

One & Half CB Scheme

Substations

Switching Configuration : Application

Distribution Stations

Single Bus scheme

Single Bus with sectionalizer

Double Bus scheme

ABB Power Technologies


BA PTPS - 42 -

Main & transfer

Double Main & Transfer (Industrial customer)

ABB Power Technologies


BA PTPS - 43 -

Substations

Engineering
Calculations

Substations

Engineering Calculations

Purpose of doing engineering calculation

To establish & validate design

To Optimize

To give complete error free solution to


customer.

To ensure safety

ABB Power Technologies


BA PTPS - 44 -

Of Persons

Of Animals

Of equipments

To ensure correct Power system operation

Substations

Engineering Calculations

ABB Power Technologies


BA PTPS - 45 -

Reference Used by ABB for doing


Calculations

IEC Standards

IEEE Standards

IS Standards

CBIP

International papers

Substations

ABB Power Technologies


BA PTPS - 46 -

Engineering Calculations

Different types of calculations done in switchyard engineering


1.

Short Circuit Force Calculation for Flexible conductor

2.

Short Circuit force calculations for Rigid conductor

3.

Cantilever strength check for bus support insulators

4.

Wind Pressure calculation

5.

Temperature rise calculation for Flexible conductor

6.

Temperature rise calculation for Rigid conductor

7.

Earthing Calculation

8.

Shielding Calculation

9.

Sag Tension Calculation

10.

Battery sizing calculation

Substations

Engineering Calculations : EDF


ELECTRICAL CONNECTION

ABB Power Technologies


BA PTPS - 47 -

FLEXIBLE

RIGID

TENSILE FORCE ( Ft)

FORCE AT RIGID END


(Fda)

DROP FORCE ( Fs)

FORCE AT FLEXIBLE END


(Fdb)

PINCH FORCE ( Fpi)

Substations

ABB Power Technologies


BA PTPS - 48 -

Inputs for Calculation

Short Circuit Force for Flexible conductor

Substations

Engineering Calculations : EDF

ABB Power Technologies


BA PTPS - 49 -

PURPOSE :

TO FIND OUT THE MAXIMUM SHORT CIRCUIT


FORCE COMING ON THE EQUIPMENT TERMINAL.

TO FIND OUT THE CANTELIVER STRENGTH OF THE


BUS POST INSULATOR.

TO EVALUATE THE FORCES FOR DESIGN OF CIVIL


AND STRUCTURE.

FACTORS/INPUTS ON WHICH EDF DEPENDS:

TYPE OF CONDUCTOR ( FLEXIBLE OR RIGID


CONDUCTOR)

SHORT CIRCUIT CURRENT.

FAULT CLEARANCE TIME.

SPAN LENGTH.

PHASE DISTANCE.

NUMBER OF CONDUCTOR PER PHASE.

STATIC TENSION.

Substations

Engineering Calculations : Earthing

ABB Power Technologies


BA PTPS - 50 -

PURPOSE :

TO FIND OUT THE MAXIMUM STEP AND


TOUCH POTENTIAL COMING IN A
SUBSTATION.

TO ACHIEVE SAFE VALUES OF STEP AND


TOUCH POTENTIAL WRT TO THE
CALCULATED VALUES.

TO ACHIEVE SAFE VALUES OF GPR BY


RESTRICTING THE REDUCING THE VALUE OF
GROUND RESISTANCE.

FACTORS/INPUTS ON WHICH EARTHING


DEPENDS:

SHORT CIRCUIT CURRENT.

FAULT CLEARANCE TIME.

SOIL RESISTIVITY.

Substations

Engineering Calculations : DSLP

PURPOSE :

ABB Power Technologies


BA PTPS - 51 -

TO PROTECT SUBSTATION FROM


LIGHTNING STROKE BY PROBABLISTIC
METHOD.

FACTORS/INPUTS ON WHICH DSLP


DEPENDS:

HEIGHT OF LIGHTNING MAST/SHIELD WIRE.

HEIGHT OF THE EQUIPMENT TO BE


PROTECTED.

Substations

Engineering Calculations : DSLP


Protective Zone
by LM

Typical DSLP Layout

Shield wire
Lightning Mast

ABB Power Technologies


BA PTPS - 52 -

What are the methods for D.S.L.P. design?

As per "High Voltage Engineering" by Razevig with help of LM

As per IS:2309 which is also using LM and spikes

As per electro-geometry method by using combination of LM and shield wire.

Substations

ABB Power Technologies


BA PTPS - 53 -

Inputs for Calculation

Shielding Calculation

Substations

Engineering Calculations : DSLP

ABB Power Technologies


BA PTPS - 54 -

Substation Engineering Calculation

Substations

Engineering Calculations : Sag Tension

ABB Power Technologies


BA PTPS - 55 -

PURPOSE :

TO STRING THE CONDUCTOR AT MAIN BUS LEVEL


AND JACK BUS LEVEL.

TO MAINTAIN NECESSARY ELECTRICAL


CLEARANCES.

FOR PANTOGRAPH ISOLATORS TO ACHIEVE A


PROPER CONTACT AREA BETWEEN THE HANGER
AND THE PANTOGRAPH ARM.

FACTORS/INPUTS ON WHICH SAG TENSION


DEPENDS:

STATIC TENSION

SPAN OF CONDUCTOR, TYPE & NUMBER OF


CONDUCTOR.

MAXIMUM AND MINIMUM TEMPERATURE.

WIND PRESSURE.

WEIGHT OF STRING HARDWARE, INSULATOR


STRING, SPACERS.

Substations

ABB Power Technologies


BA PTPS - 56 -

Inputs for Calculation

Sag Tension Calculation

Substations

Engineering Calculations : Wind Pressure

ABB Power Technologies


BA PTPS - 57 -

PURPOSE :

TO EVALUATE THE WIND PRESSURE AT VARIOUS


LEVELS.

WIND PRESSURE FORMS INPUT FOR STRUCTURE


AND CIVIL DESIGN.

WIND PRESSURE CALCULATION IS ALSO USED


FOR DETERMINING CANTELIVER STRENGTH OF
ALL INSULATORS (ALONG WITH EDF FORCES)

STANDARDS USED ARE IS:802 AND IS:875

FACTORS/INPUTS ON WHICH WIND PRESSURE


CAL DEPENDS:

WIND ZONE IN WHICH A SUBSTATION IS


SITUATED.

TOPOGRAPHY NEAR THE SUBSTATION.

LOCATION OF CLIFF, VALLEY OR MOUNTAIN NEAR


A SUBSTATION.

Substations

Engineering Calculations : Temperature Rise

PURPOSE :

ABB Power Technologies


BA PTPS - 58 -

To determine thermal sizing of conductors


( Flexible Conductor / AL.Tube)

FACTORS/INPUTS ON WHICH TEMPERATURE


RISE CAL DEPENDS:

Continuous current.

Short Circuit Current.

SOLAR HEAT GAIN.

RADIATION LOSS.

CONVECTION HEAT LOSS.

FAULT DURATION TIME.

AMBIENT TEMPERATURE.

Substations

ABB Power Technologies


BA PTPS - 59 -

Inputs for Calculation

Temperature rise calculation for Flexible Conductor

Substations

ABB Power Technologies


BA PTPS - 60 -

Inputs for Calculation

Temperature rise calculation for Rigid Conductor

Substations

Engineering Calculations : Temperature Rise

PERMISSIBLE VALUES OF OPERATING


TEMPERATURE :

ABB Power Technologies


BA PTPS - 61 -

Maximum allowed temperature rise under


normal condition.

ACSR Conductor = 75deg C (As per CBIP


Manual)

Al. Tube

= 85 deg C ( BS:159)

Maximum allowed temperature under short


circuit condition.

ACSR Conductor = 650 deg C ( As per CBIP


paper)

Al tube

= 200 deg C ( As per IEEE:605)

ABB Power Technologies


BA PTPS - 62 -

Substations

Layout
Engineering

Substations

Layout Engineering

What is Substation Layout ?


Substation Layout is the conception which
transforms to reality through engineering,
execution & commissioning.

ABB Power Technologies


BA PTPS - 63 -

Layout Engineering . . . .

is the basic document to be sent to Customer /


Consultants for approval

forms the basis of entire project scope

forms basis for engineering estimates

form input for civil & structure design

basic document for statutory approval

Substations

Layout Engineering : Plan View

TYPICAL SUBSTATION PLAN LAYOUT

ABB Power Technologies


BA PTPS - 64 -

Incoming Line
Bay
Single
Bus Bar
Outgoing
Transformer Bay

Substations

Layout Engineering

ABB Power Technologies


BA PTPS - 66 -

Following details form the input for layout


engineering:

Bay & Busbar configuration

Bay width & depth, Height of busbar, Distance to


fence, Building and total dimensions.

Statutory clearances (Phase to Phase, Phase to


Earth, Sectional clearance)

Lightning Mast, Gantries (Column & Beam), String


Insulators, Busbar, Equipment etc.

Position of various drive box, junction box,


Marshalling box.

Maintenance aspect for Transformer, Reactor,


CB.

Illumination requirement.

Calculations like EDF ( deciding max safe span


length& location of BPI) , DSLP (locating LM).

Substations

Layout Engineering

ABB Power Technologies


BA PTPS - 67 -

Bay Width will depend on .

Phase to Phase & Phase to Earth clearances

Sectional Clearances

Tower width

Swing of conductor

Bird clearances

Cable trench routing

Maintainability of equipment

Tandem Isolator arrangement

Distances in between equipment will depend


on..

Phase to Phase & Phase to Earth clearances

Sectional Clearances

Position of switch cubicle, junction box, drive box


etc.

Maintainability of equipment

ABB Power Technologies


BA PTPS - 68 -

Substations

Layout Engineering

Substations

Layout Engineering

Standard bay width & clearances

ABB Power Technologies


BA PTPS - 69 -

System
Voltage

Phase to Phase Phase to Earth


Distance
Distance

Bay width

Sectional
Clearance

kV
66
132

mm
2000
2700

mm
2000
2500

mm
8000
9400

mm
3000
3500

132
(Standard)

3000

3000

12000

3500

220
(standard)
220
(Industry)

4500

4000

17000

4500

4500

4500

18000

4500

220 (IPP)

5000

4000

18000

4500

400

7000

6500

27000

6000

ABB Power Technologies


BA PTPS - 70 -

Substations

Layout Engineering

ABB Power Technologies


BA PTPS - 71 -

Substations

Equipment &
Accessories

Substations

Equipment & Accessories

Substation

ABB Power Technologies


BA PTPS - 72 -

Main
Equipment

Engineered
items

Civil

Auxiliary
Equipment

Structure

Auxiliary
System

ABB Power Technologies


BA PTPS - 73 -

Substations

Equipment & Accessories


Main Equipment

Circuit Breaker

Instrument Transformer (CT/CVT)

Surge Arrester

Isolator

Transformer & Reactor

Bus Support Insulator

Line Traps

Control & Protection system

Power Line Carrier Communication system

Substations

Equipment & Accessories

420kV, 50kA type ELF SP 6-2

245kV, 40kA type ELF SP 4-1

245 kV, 40 kA type LTB E1

145kV, 40kA type LTBD1

72.5kV, 31.5kA type ED


420 kV ELF SP Breaker

ABB Power Technologies


BA PTPS - 74 -

245 kV ELF SP Breaker

245 kV LTB E1 Breaker


72.5 kV EDI Breaker

72.5 kV EDF Breaker

ABB Power Technologies


BA PTPS - 75 -

Substations

Equipment & Accessories

Single

pole vacuum circuit


breakers and interrupters with
magnetic actuators for 25kV AC
railway traction applications

Outdoor

live tank vacuum & SF6


circuit breakers 3.3kV to 40.5kV
Spring and magnetic actuator
mechanism (12/15kV)

ABB Power Technologies


BA PTPS - 76 -

Substations

Equipment & Accessories

PRODUCT

RANGE

Dead Tank Current Transformers

66-420 kV

Capacitor Voltage Transformers

72.5-420 kV

Coupling Capacitors

72.5-420 kV

Grading Capacitors

Up to 280 kV

Substations

Equipment & Accessories

ABB Power Technologies


BA PTPS - 78 -

Types of Isolator
Center

Break

Double

Break

Vertical

Break-knee type

Voltage

11kV - 800kV

Op. Mech.

Motor / Manual

Current

100-3150A

STC

40kA

Earth Switch

1, 2, Independent

Orientation

Series / Parallel / Tandem

Substations

Equipment & Accessories

ABB Power Technologies


BA PTPS - 79 -

Power transformers / Converter


Transformer/ Traction Transformer

Used of conversion of energy from one


voltage to another voltage level

Costliest equipment in substation

Single phase & three phase installation

For major substations tertiary being


loaded for feeding auxiliary power to
substation

Oil & paper as insulating material prevails

Use of High Temperature


Superconducting (HTS) material

FEM based tools for design analysis

ABB Power Technologies


BA PTPS - 80 -

Substations

Equipment & Accessories

Bus Support Insulators are used for


supporting the busbars

Important selection parameters

Voltage level

Canteliver strength

Creepage distance

Top & Bottom PCD

Compressive strength

Torsional strength

ABB Power Technologies


BA PTPS - 81 -

Substations

Equipment & Accessories

Line traps are used for Power system


communication

It blocks high frequency carrier signals

Important selection parameters

Voltage level

mH rating

Continuous current rating

Short Circuit current rating

Type of mounting

Pedestal

Suspension

ABB Power Technologies


BA PTPS - 82 -

Substations

Equipment & Accessories

Control & Protection System

Used for controlling flow of power

Advent of 61850 based relays

Mounting of panels in outdoor AC


Kiosk

New trend started by PGCIL

First Kiosk drawing conceptualised by


ABB DESIGN

Substations

Substation

ABB Power Technologies


BA PTPS - 83 -

Main
Equipment

Engineered
items

Civil

Auxiliary
Equipment

Structure

Auxiliary
System

Substations

Equipment & Accessories


Engineered Items

ABB Power Technologies


BA PTPS - 84 -

Busbar Materials

Strung bus conductor (ACSR)

Rigid bus conductor (AL Tube)

Clamps & Connectors

String Insulator & Hardware

Earthing Materials

Main earthing materials (Rod or Flat)

Earth Pits

Cables & accessories

LT Power & Control cable

HT Power Cable

Cable terminations, gland, lugs, ties, marker


etc.

Cable supporting materials

Substations

Component & Accessories


Types of Busbar

Rigid bus comprising of AL tube

Strung bus comprising of A C S R / A A A


conductor

ABB Power Technologies


BA PTPS - 85 -

Types of Support

Bus post insulator for rigid bus

String Insulator for strung bus

Substations

Equipment & Accessories

Expansion type terminal Connector

ABB Power Technologies


BA PTPS - 86 -

Tee - Connector

Terminal Connector

Substations

Equipment & Accessories

Bus Support Insulator Clamp

ABB Power Technologies


BA PTPS - 87 -

Tee Connector

PG Clamp

Substations

Equipment & Accessories

Hardware Material

ABB Power Technologies


BA PTPS - 88 -

Double Tension String Hardware

Tension Clamp & Arcing Horn

Substations

Equipment & Accessories

Drop Clamp & Through Clamp

Single Suspension String Hardware

ABB Power Technologies


BA PTPS - 89 -

(Drop type & Through type)

Substations

Substation

ABB Power Technologies


BA PTPS - 90 -

Main
Equipment

Engineered
items

Civil

Auxiliary
Equipment

Structure

Auxiliary
System

ABB Power Technologies


BA PTPS - 91 -

Substations

Equipment & Accessories


Auxiliary Equipment

LTAC Switchgear Panel

DC Distribution Board

Battery & Batter Charger

DC Distribution Board

Auxiliary LT Transformer

Lighting Transformer

Main Lighting distribution transformer

Emergency lighting distribution transformer

Diesel Generator

UPS

Substations

Equipment & Accessories : LT AC Distribution


11KV FROM
S.E.B.
250KVA DG 630KVA AUX.
TRAFO.
SET

415V AC
AUXILIARY
SYSTEM

33KV FORM TERTIARY OF


315MVA TARNSFORMER
1000KVA AUX.
TRAFO.

415V MAIN SWDB-1A

FIRE
FIGHTING
SYSTEM

100KVA
LIGHTING
TRAFO.

415V ACDB-2A
EMERGENCY
LIGHTING DB4A

ABB Power Technologies


BA PTPS - 92 -

VENTILATIO
N DB-5A

220V
BATTERY
CHARGER

50V BATTERY
CHARGER

LIGHTING
DB-3A

Typical AC System SLD

ABB Power Technologies


BA PTPS - 93 -

Substations

Equipment & Accessories : AC & DC Board

Substations

Equipment & Accessories : DC System


DC Auxiliary System

Auxiliary system which provides reliable DC source for


control & protection circuit of substation equipment. DC
system backed up by Battery ensures higher level of
security over AC auxiliary system

ABB Power Technologies


BA PTPS - 94 -

Typical DC Load in substation

Protection & interlocks

Switchgear control

Remote control & Indication

Annunciation system

Control & instrumentation

Power line carrier ( PLCC )

Emergency DC Lighting

Electric clocks

Communication systems

Data acquisition & logging system

ABB Power Technologies


BA PTPS - 95 -

Substations

Equipment & Accessories : DC System

Tubular Battery
Battery is simple construction
Life is 10 years.
Most Economical

Plante Battery
40% better performance
Longer Life (20 years)
Almost 2.5-3 times Costlier than
Tubular battery

Maintenance Free
Does not require any topping up of
water
Less hazardous and no special room
required
Needs control environment at 270C
Cost is 2 times of Tubular battery

Ni-Cd Battery
Longer life span (25 years)
More stable & reliable performance
Less hazardous and corrosion free
Cost is 4 times of tubular battery

Substations

Equipment & Accessories : DC System


Inputs for Battery Sizing

Instantaneous or Momentary Load

Circuit Breaker Trip / Close, Protective Relays

Continuous Load

Annunciation system, DC supervision, Indication


Lamps, Auxiliary Relays, Semaphores

Emergency Loads

ABB Power Technologies


BA PTPS - 96 -

Emergency lighting

Substations

Equipment & Accessories : DC System

No of cells selected =

ABB Power Technologies


BA PTPS - 97 -

Sr. No.

1
2
3
4
5
6
7
8
9
10
11
12
13

200
0-1min.

175

1-179min.

150

179-180min.

110.56

111

Minimum Battery voltage at end of discharge= 111*1.8V=


Maximum Battery voltage = 111*2.28V=
Nominal battery Voltage = 111*2.0V=

Electrolyte temperature =

BATTERY LOADING DIAGRAM

LOAD IN AMPS

BATTERY SIZING
Maximum allowable battery voltage(V) =
254
Minimum allowable battery voltage(V) =
199
Float voltage (minimum)(V) =
2
Float voltage (maximum)(V) =
2.28
Minimum allowable cell voltage(V) =
1.80
No. of cells = min.allowable battery voltage/end of discharge cell voltage = 199/1.8=

199.8
253.08
222

125
100
75
50
25

19 Deg. Celsius

System/Loads

0-1min.

1-179min.

179-180min.

Sub Total for 400kV Swgr. System (sheet 4 of 13)


Sub Total for 33kV swgr system (sheet 6 of 13)
Sub Total for 415V main system (sheet 8 of 13)
Sub total for 415V valve cooling (sheet 11 of 13)
Sub total for 415V DG swgr (sheet 11 of 13)
Sub total for 415V fire fighting system (sheet 11 of 13)
Sub total for 415V water system (sheet 11 of 13)
Sub total for 415V AC/vent. system (sheet 11 of 13)

61.995
6.205
8.102
5.041
1.511
0.155
0.123
2.743

1.995
0.295
1.157
2.586
0.193
0.155
0.123
0.107

1.995
1.205
1.157
2.586
0.193
0.155
0.123
0.107

Em. Lighting Load (sheet 13 of 13)


Sub Total for MACH2 system (sheet 12 of 13)
Sub Total for Key interlock system(sheet 12 of 13)
Sub total for emergency swgr (sheet 9 of 13)
Total (=1+2+3+4+5+6+7+8+9+10+11+12+13) =

18.182
14.545

18.182
14.545

18.182
14.545

1.511
120.114

0.193
39.532

0.193
40.441

0-1min.

TIME
1-179min.

179-180min.

LOAD CYCLE :
PERIOD
LOAD (AMP.)
0-1min.
1-179min.
179-180min.

120.114
39.532
40.441

Substations

Period

Equipment & Accessories : DC System

Load (Amperes)

Change in load (Amperes)

(CA)
Section 1 - First period only - If A2 is greater than A1, go to section 2
1
A1=
120.11
A1-0=
120.11

Duration of Period
(minutes)

Time to End of Section


(minutes)

K
Factor

Required section size

(Curve) Pos. Value Neg. Value


(IF CA>0,
(IF CA<0,
(K)
POS=CA*K) NEG=CA*K)
M1=

T=M1=
SEC 1 Sub-Total =
SEC 1 Total =

1.100

132.125
132.125
132.125

0.000
0.000

0.000
0.000

0.000

492.466
0.000
1.000
493.466
163.080

0.000
-330.385
0.000
-330.385

Section 2 - First two periods only - If A3 is greater than A2, go to section 3


SEC 2 Sub-Total =
SEC 2 Total =

ABB Power Technologies


BA PTPS - 98 -

Section 3 - First three periods only - If A4 is greater than A3, go to section 4


1
A1=
120.11
A1-0=
120.11
2
A2=
39.53
A2-A1=
-80.58
3
A3=
40.44
A3-A2=
0.91

A)
B)
C)
D)
E)

M1=
M2=
M3=

Max. Uncorrected Section size (Maximum of Sec1 Total, Sec2 Total, Sec3 Total)
Temperature Correction Factor :
Adding temperature correction compensation :
Adding 25% ageing compensation (per DCD) :
With 10% design margin
Standard battery rating selected = 300AH

1
178
1

T=M1+M2+M3=
T=M2+M3=
T=M3=
SEC 3 Sub-Total =
SEC 3 Total =
163.08
1.070
174.50
218.12
239.93

180
179
1

AH

4.100
4.100
1.100

ABB Power Technologies


BA PTPS - 99 -

Substations

Equipment & Accessories : DC System

Substations

Substation

ABB Power Technologies


BA PTPS - 100 -

Main
Equipment

Engineered
items

Civil

Auxiliary
Equipment

Structure

Auxiliary
System

Substations

Equipment & Accessories


Auxiliary System

ABB Power Technologies


BA PTPS - 101 -

Illumination system

Indoor (Control Room, FFPH, Kiosk)

Outdoor

Fire fighting system

HVWS system

Nitrogen injection

Air conditioning system

Substations

Equipment & Accessories


Fire Fighting System

ABB Power Technologies


BA PTPS - 102 -

Fire fighting

Fire Water Storage Tank

Fire Water Pumping System

Hydrant System

High Velocity Water Spray System

Portable Fire Extinguishers

CO2 Gas Extinguishers

Fire detection

Thermal Heat Detectors

Ionization Smoke Detectors

Photoelectric Smoke Detectors

Response Indicators

Manual Call Points

Hooters

Fire Alarm Panel

ABB Power Technologies


BA PTPS - 103 -

Substations

Equipment & Accessories : P & I Diagram

ABB Power Technologies


BA PTPS - 104 -

Substations

Equipment & Accessories : Fire Fighting Building

ABB Power Technologies


BA PTPS - 105 -

Substations

Equipment & Accessories : Fire Fighting Building

ABB Power Technologies


BA PTPS - 106 -

Substations

Equipment & Accessories : Hydrant System

ABB Power Technologies


BA PTPS - 107 -

Substations

Equipment & Accessories : HVWS System

ABB Power Technologies


BA PTPS - 108 -

Substations

Equipment & Accessories : HVWS System

ABB Power Technologies


BA PTPS - 109 -

Substations

Equipment & Accessories : N2 Injection

ABB Power Technologies


BA PTPS - 110 -

Substations

Equipment & Accessories: Air Conditioning System

Separate AC System for Control room /


Other areas

Ventilation System Other Areas, Valve


Hall

AC System 100% Standby

AC - Chilled Water System / Split Units

Ventilation with Humidity Control

Substations

Equipment & Accessories : Illumination System

ABB Power Technologies


BA PTPS - 111 -

Lighting system for substation are considered as:

Normal AC to cater lighting requirement


during normal operating condition

Emergency lighting on failure of normal AC


lighting source

DC emergency for illuminating strategic locations

Lighting from DG system for bigger substations

Outdoor Lighting

Building Lighting

Fire fighting building

Control room building

Kiosk Lighting

Street Lighting

Substations

Illumination level required for substation is.

ABB Power Technologies


BA PTPS - 112 -

Equipment & Accessories : Illumination System


Lighting shall provide enough light depending on nature of work
to be carried out. Operational lighting as per IS:3646 part-III.

Substations

Equipment & Accessories : Illumination System

ABB Power Technologies


BA PTPS - 113 -

Outdoor Illumination System

High Pressure Sodium Vapour (HPSV) luminaries


with various combination of rating with high beam
& narrow beam used to achieve desired
illumination

Ratings usually considered

2X400W HPSV, 1X400W HPSV for switchyard and


outdoor equipment

2X250W HPSV, 1X250W HPSV for switchyard and


outdoor equipment

1X150W HPSV for street lighting

High Pressure Mercury Vapour / Halogen


luminaries are also taken if they specifically
required by customer

Substations

Equipment & Accessories : Illumination System

ABB Power Technologies


BA PTPS - 114 -

Indoor Illumination System

Indoor illumination is achieved by various types of


luminaries according to the requirement and utility of
various rooms.

Room with CP/RP, office, conference room with air


conditioning and false ceiling are provided with
recessed mounted 2X36W fluorescent lamp with mirror
optic reflector.

For LT room, DG, Store etc. where no false ceiling or


AC provided, industrial type 2x36W fluorescent lamp is
used.

For cable cellar bulk head or industrial type 2x36W


fluorescent lamp is used as per specification.

Battery room is provided with corrosion proof industrial


type 2X36W fluorescent lamp.

For DC emergency bulk head incandescent lamps are


used.

Substations

ABB Power Technologies


BA PTPS - 115 -

Interlocking &
Protection
Philosophy

Substations

Fundamental Concepts

CIRCUIT BREAKER

Normally kept interlock free

European practice is to prevent opening or


closing of circuit breaker when isolator is in
intermediate position

CB is operated only when isolator is fully open


or close

Isolator

ABB Power Technologies


BA PTPS - 116 -

Isolator is allowed to operate (open offload)


when associate

Circuit breaker is open

Earth switch is closed

Isolator permitted to operate for bus transfer


when voltage on both the sides are same

Substations

Fundamental Concepts

ABB Power Technologies


BA PTPS - 117 -

EARTH SWITCH

Earth switch is allowed to operate when


adjacent isolators are open

Earth switch is used to earth the trap charges

Nowadays, customer ask for same short


circuit rating of main blade & earth blade

ABB Power Technologies


BA PTPS - 118 -

Substations

Interlocking : Single Bus scheme

ABB Power Technologies


BA PTPS - 119 -

Substations

Interlocking : Double Bus scheme

ABB Power Technologies


BA PTPS - 120 -

Substations

Interlocking : Three Bus scheme

ABB Power Technologies


BA PTPS - 121 -

Substations

Interlocking : One & Half Breaker Scheme

ABB Power Technologies


BA PTPS - 122 -

Substations

Protection Philosophy

Introduction to Protection

General protection requirements


applicable to

Transmission/distribution substations

Distribution plants/ MV switchgear

Brief on various type of protection

Application guide

Substations

Protection Philosophy

Electric Power Systems

ABB Power Technologies


BA PTPS - 123 -

Generation

Transmission

Consumption

Generation

Distribution

Transmission

Distribution

Load

ABB Power Technologies


BA PTPS - 124 -

Substations

Protection Philosophy

Substations

Protection Philosophy

The main task for Relay Protection


U

C
E

Protect people and property


around the power system
Protect equipment, lines etc..
in the power system

ABB Power Technologies


BA PTPS - 125 -

Separate the faulty part from


the rest of the power system

Substations

Protection Philosophy

Requirements on Protection System


Speed

Thermal damage

Electro dynamic forces

Sensitivity

ABB Power Technologies


BA PTPS - 126 -

High resistance faults

Reliability

Dependability

Security

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 127 -

Factors influencing reliability


Choice of the protection system

Principle of measuring

Environment

The maintenance

Flexibility under different service conditions and


extension of the network

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 128 -

Single failure criteria


Fault clearance must be executed even in case
of a single fault in the clearance chain

In the fault clearance system no part of the


clearance should have lower reliability

Back-up clearance function must be there

Remote back up

Local back up

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 129 -

Primary and backup protection zones

Remote back-up with time selectivity is most common at


Medium and low voltage functions

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 130 -

Remote back-up protection with time grading

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 131 -

Redundant protection system

Separate measuring cores

Duplicate trip coils

Separate dc distribution/ double battery system

Physical separation of protection system

Separate cable ways

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 132 -

DC supply

The protection system that gives back up for other


protection should not be fed from the same DC supply

For example if line and transformer protections are


from same DC the backup function of the transformer
will not be able to operate for a failure to clear the fault
on the line by the primary protection

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 133 -

Principle of breaker failure protection

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 134 -

Duplication of breaker fail protection


Often 2 out of 2 connection of current and time
is used to obtain high security

For numerical relays this is not necessary

Duplication of breaker fail protection gives high


reliability but lower security.

Considering probability of failures only one


breaker failure relay is used

Substations

Protection Philosophy

Disturbance Registration and Fault Signaling


Alarm system

ABB Power Technologies


BA PTPS - 135 -

Supervision of alarm voltage

Disturbance recorder & Event logger

DC system for alarm independent of distribution

Analysis of print out will help discover inoperative


relays , incorrect settings and badly chosen measuring
principle

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 136 -

General protection requirements applicable


to

Transmission/distribution substations

Distribution plants/ MV switchgear

Substations

Protection Philosophy

General protection requirements


applicable to

Transmission/distribution substations

ABB Power Technologies


BA PTPS - 137 -

This depends on following


1.

Voltage level

2.

Type of feeders

3.

Application specific criticality

Substations

Protection Philosophy
Protection Philosophy normally followed at EHV level

EHV/HV : 800KV ,400KV,220KV,132KV


Common protection
Busbar protection:

ABB Power Technologies


BA PTPS - 139 -

It is mandatory to provide bus bar protection up to


220KV level. Depending on criticality of
installation and philosophy of each industry, it is
optional to provide bus bar protection at 132KV
level

Generally Low impedance type up to 400KV and


high impedance /low impedance type for 220KV
and 132KV

Duplicate protection (without Check zone) for


each of the main buses for 800KV and 400KV
stations

For 220KV/132KV ,one protection for each bus.

Substations

Protection Philosophy
Common protection contd

ABB Power Technologies


BA PTPS - 140 -

Local breaker back up protection.

This protection is primarily provided to isolate


the system in case the circuit breaker fails to
operate.

This protection isolates all the feeders which


can feed the fault.

Mandatory from 220KV substation and above.

ABB Power Technologies


BA PTPS - 141 -

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 142 -

Substations

Protection Philosophy

Substations

Protection Philosophy
Feeder wise Protection

EHV : 800kv ,400kv ,220KV

ABB Power Technologies


BA PTPS - 143 -

Line Protection

Main-1,Main-2 protection connected to


separate CT cores

Both protections should have different


make/operating principle.

Normally up to 400 KV, distance


protection is provided.

For 220KV,distance for main-1 protection


and either distance or directional earth
fault for main -2 protection is provided

Substations

General protection requirements contd

ABB Power Technologies


BA PTPS - 144 -

Transformer Protection

Main-1,Main-2 protection connected to


separate CT cores

Differential protection is provided for main-1

Restricted e/f is provided as main-2

Over fluxing protection

Gas detector relay ( Buchholz)

Over current protection

Pressure relay for tap changer

Oil level monitor

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 145 -

Transformer Protection Contd

Gas detector relay ( Buchholz)

Over load protection

Thermal relays

Temperature monitoring relays

Ground fault protection

Differential protection

Inter turn faults

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 146 -

Capacitor Bank faults

Terminal shunt faults

Capacitor unit failures

Capacitor unit over voltages

Capacitor rack arc-over

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 147 -

Capacitor Bank Protection Contd

Short -circuit protection (3I >>)

Ground-fault protection (I )

Overload protection (3I/U >)

Under current protection (I/U <)

Unbalance protection (IN-N)

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 148 -

Conditions as per IEC 60871-1

Capacitors should be able to withstand 10%


over voltage

The capacitors should tolerate 30% over


current ( r.m.s. value) arising from over voltage
and harmonics. Depending on the capacitance
deviations, which may be not more than 1.15
Cn, the maximum current may be up to 1.15 x
1.3 = 1.5 In

Capacitors may not be reconnected until they


have discharged to 10% of their rated voltage.

Substations

Protection Philosophy
Unbalance relay detects :-

ABB Power Technologies


BA PTPS - 149 -

Detects asymmetry due to

Blown internal fuses

Short circuits across bushings

Short circuits between capacitor units /racks

If capacitor value decrease below 5/6 of


nominal value bank must be taken out of
service

Faulty elements taken out by fuses cause


increase in voltage level

Capacitors can withstand 110% of rated


voltage

Substations

Protection Philosophy

ABB Power Technologies


BA PTPS - 150 -

Unbalance Protection Schemes :

Provide early unbalance alarm signal to


indicate the operation of fuses (internally or
externally fused capacitors) or failure of
capacitor elements (fuse less capacitors)

Trip the bank for unbalances that are large


enough to indicate that continuing operation
may result in damage to remaining good
capacitors or elements from over voltage

Many schemes available for detecting


unbalances

Most installations will require an individual


engineering analysis to determine the most
appropriate detection scheme

ABB Power Technologies


BA PTPS - 151 -

Substations

General Safety
Criteria

Substations

General Safety Requirement

ABB Power Technologies


BA PTPS - 152 -

Rule No. 34 Accessibility of Bare


conductors in buildings

Ensure they are inaccessibile

Provide necessary switches in accessible


position for rendering them dead whenever
required.

Take safety measures as recommended


necessary by inspector.

Substations

General Safety Requirement

ABB Power Technologies


BA PTPS - 153 -

Rule No. 35 Danger Notices

Applicable for Medium, high and extra-high


voltage installations.

Insists on danger sign depicted by skull and


bones as per IS:2551

To be installed on every

Motor, generator, transformer & other electrical


plant and equipment together with apparatus
used for controlling or regulating the same.

All supports of extra high voltage, O/H lines


which can be easily climbed upon w/o aid of
ladder of special appliance

If installation not possible, then Dangerword


should be affixed as near as possible, voltage
printed on equipment.

For enclosed equipment, it should be affixed


to said enclosure

Substations

General Safety Requirement

ABB Power Technologies


BA PTPS - 154 -

Rule No. 36 Handling of electric supply-lines


and apparatus

Before handling any conductor adequate


precaution to be taken to see that conductor is
de-energized.

Accidental induction from adjacent live


conductors to impose no danger to work
person.

Before working on any live electric supply-line


or apparatus, proper authorization from
Inspector to be taken.

Every telecommunication line on high voltage


supports are deemed to be considered as high
voltage lines.

Substations

General Safety Requirement

ABB Power Technologies


BA PTPS - 155 -

Rule No. 41 Distinction of different circuits

Different circuits shall be distinguished by


means of permanent nature.

Applicable for every generating station, substation, junction box or pillar in which there
are any circuits or apparatus (whether
intended for opeartion at different / same
voltage.

Rule No. 41-A Distinction of the installations


having more than one feed

Applicable for every installation including


substation, double-pole structure, four pole
structure of any other structure having more
than one feed.

Indication should be of permanent nature.

Substations

General Safety Requirement

Rule No. 64 (2- e) Provision of Baffle Walls

A substation or switchstation with apparatus


having more than 2000 liters of oil whether
indoor / outdoor

ABB Power Technologies


BA PTPS - 156 -

Baffle walls of 4 hours fire rating shall be


provided

Between Single phase banks

On the consumer premises

Where adequate clearances between units


are not met.

Substations

General Safety Requirement

ABB Power Technologies


BA PTPS - 157 -

Rule No. 64 (2- e) Provision of Soak Pit

Oil soak pit to be provided > 9000 litres of oil

Suitable Oil tank, chamber, receptacle to be


provided.

Special precaution to be taken to prevent


ignition of oil from any cause & provision shall
be made for extinguishing any fire that may
occur.

Spare oil shall not be stored in any such sub


station or switch station.

Dry type transformers to be provided for


basement & residential areas

All transformers & switchgear to be


maintained as per manufacturers instructions
proper record to be maintained

Substations

General Safety Requirement

ABB Power Technologies


BA PTPS - 158 -

Rule No. 64 (3) Over voltage Protection

All EHV apparatus shall be protected against


switching and lightning overvoltages

Proper insulation co-ordination should be


ensured to protect and maintain the stability
of interconnected units of the power system

Substations

General Safety Requirement

ABB Power Technologies


BA PTPS - 159 -

Rule No. 64 A Additional Provision


Interlocks

Isolator should not be operated until adjacent


CBs are in open condition.

Earth switches should not be closed until


Isolators are in Open condition

When two supplies are not intended to be


operated in parallel, CBs shall be interlocked
to prevent inadvertent paralleling

When parallel operation of transformer takes


place, primary CB will trip incase of tripping of
secondary CB

All gates & doors to be interlocked to avoid


any person coming in proximity of live parts

Neutral switching to be adopted for two or


more generators operating in parallel

Substations

General Safety Requirement

ABB Power Technologies


BA PTPS - 160 -

Rule No. 64 A Additional Provision


Protection

Over-current, Earth fault & Earth leakage


protection to be provided where ever required

Gas Pressure type, winding & Oil temperature


protection to give alarm & tripping for all
transformers 1000kVA & above

Differential protection to be provided for


10MVA & above.

All generators 1MVA & above shall be


protected by REF, protection should also be
given for earth fault & leakage

Busbar protection with LBB MUST for all


substations with voltage of 220kV & above

A global leader
in power and automation technologies
that enable utility and industry customers
to improve their performance
while lowering environmental impact