Fire Insulation in E/R


Course 2004

02 September 2009

Fire Insulation - E/R

Purpose of the regulations/rules:


Containment of fire/ prevent spreading of fire.
Avoid excessive temperatures in neighbouring area.
Maintain structural integrity.

02 September 2009
Det Norske Veritas AS. All rights reserved.

Fire Insulation - E/R

Basic Design Principles:


The fire integrity of a division between two spaces will depend
upon the category of the spaces.
The category of a space is defined based upon the function and fire
risk of the space.

02 September 2009
Det Norske Veritas AS. All rights reserved.

Fire Insulation - E/R

Fire Risk Space A


Category Space A
Function Space A

SOLAS Fire
Integrity Matrix

Fire Risk Space B


Category Space B
Function Space B

02 September 2009
Det Norske Veritas AS. All rights reserved.

Fire Integrity Division


Space A & B

Basic requirements;
Table B1 Fire integrity of bulkheads separating adjacent spaces
Spaces

(1)

(2)

(3)

(4)
A-0

Control stations

(1) A-0 5) A-0

A-60

Corridors

(2)

B-0

Accommodation spaces

(3)

Stairways

(4)

Service spaces (low risk)

(5)

Machinery spaces of
category A

(6)

Other machinery spaces

(7)

Cargo spaces

(8)

Service spaces (high risk)

(9)

Open decks

(10)

Ro-ro cargo spaces

(11)

C 1)2)

B-0
A-0 3)
B-0
A-0 3)
B-0
A-0 3)

(10)

(11)

A-15 A-60 A-15 A-60 A-60

*)

A-60

B-0

A-60

A-0

A-0

A-0

*)

A-30

B-0

A-60

A-0

A-0

A-0

*)

A-30

B-0
A-60
A-0 3)

A-0

A-0

A-0

*)

A-30

A-0

A-0

A-0

*)

A-0

A-0 A-0 7) A-60

*)

A-60 6)

A-0

*)

A-0

A-0

*)

A-0

A-0 4)

*)

A-30

A-0

(6)

A-60
*)

(7)

(8)

A-0 4) A-0
*)

(9)

*)8)

See notes under Table B2.


02 September 2009
Det Norske Veritas AS. All rights reserved.

(5)

Basic requirements;
Table B2 Fire integrity of decks separating adjacent spaces
Space below

above

(1)

(2)

(3)

(4)

(5)

(6)

(7)

(8)

(9)

(10)

(11)

Control stations
Corridors

(1)
(2)

A-0
A-0

A-0
*)

A-0
*)

A-0
A-0

A-0
*)

A-60
A-60

A-0
A-0

A-0
A-0

A-0
A-0

*)
*)

A-60
A-30

Accommodation spaces
Stairways

(3)
(4)

A-60
A-0

A-0
A-0

*)
A-0

A-0
*)

*)
A-0

A-60
A-60

A-0
A-0

A-0
A-0

A-0
A-0

*)
*)

A-30
A-30

Service spaces (low risk)


(5)
Machinery spaces of category A (6)

A-15
A-60

A-0
A-60

A-0
A-60

A-0
A-60

*)
A-60

A-60 A-0
A-0
9)
*) A-60
A-30

A-0
A-60

*)
*) 3)

A-0
A-60

Other machinery spaces


Cargo spaces

(7)
(8)

A-15
A-60

A-0
A-0

A-0
A-0

A-0
A-0

A-0
A-0

A-0
A-0

*)
A-0

A-0
*)

A-0
A-0

*)
*)

A-0
A-0

Service spaces (high risk)


Open decks

(9) A-60
(10)
*)

A-0
*)

A-0
*)

A-0
*)

A-0
*)

A-60
*)

A-0
*)

A-0
*)

A-0 4)
*)

*)
-

A-30
*)

Ro-ro cargo spaces

(11) A-60

A-30

A-30

A-30

A-0

A-60

A-0

A-0

A-30

*)

*) 8)

To be applied to both Tables B1 and B2, as appropriate.


1)
2)
3)
4)

9)

No special requirements are imposed upon bulkheads in methods IIC and IIIC fire protection.
In case of method IIIC <<B>> class bulkheads of <<B-0>> rating shall be provided between spaces or groups of spaces of 50m2 and over in area.
For clarification as to which applies, see 200 and 500.
Where spaces are of the same numerical category and superscript 4) appears, a bulkhead or deck of the rating shown in the tables is only required when the
adjacent spaces are for a different purpose, e.g. in category (9). A galley next to a galley does not required a bulkhead but a galley next to a paint room or a
galley next to a provision store requires an <<A-0>> bulkhead.
Bulkheads separating the wheelhouse, chartroom and radio room from each other may be <<B-0>> rating.
<<A-0>> rating may be used if no dangerous goods are intended to be carried or if such goods are showed not less than 3m horizontally from such bulkhead.
Cargo spaces in which dangerous goods are intended to be carried will be specially considered.
Bulkheads and decks separating ro-ro cargo spaces shall be capable of being closed reasonably gastight and such divisions shall have <<A>> class integrity
on so far as is reasonable and practicable.
Fire insulation need not be fitted if the machinery spaces in category (7) has little or no fire risk. (e.g. air conditioning room)

Where an asterisk appears in the tables, the division is required to be of steel or other equivalent material but is not required to be of <<A>> class standard.

5)
6)
7)
8)

02 September 2009
Det Norske Veritas AS. All rights reserved.

Fire Insulation - E/R

Definitions:
A Class Divisions

B Class Divisions

C Class Divisions

02 September 2009
Det Norske Veritas AS. All rights reserved.

Fire Insulation - E/R


A Class Divisions
Are those divisions formed by bulkheads and decks which
comply with the following criteria:
1. They are constructed of steel or other equivalent material.
2. They are suitably stiffened.
3. They prevent the passage of smoke and flame to the end of the 1
hour standard fire test.

02 September 2009
Det Norske Veritas AS. All rights reserved.

Fire Insulation - E/R


A Class Divisions
4. They are insulated with approved
non-combustible material such that
the average temperature of the
unexposed side will not rise more
than 140 above the original
temperature, nor will the maximum
hot spot temperature rise more than
180 above the original temperature
within the following time:

Class A-0

0 Minutes

Class A-15

15 Minutes

Class A-30

30 Minutes

Class A-60

60 Minutes

5. The administration has required a test of a prototype bulkhead or


deck in accordance with the IMO fire test procedures code to
ensure that it meets the requirements for integrity and
temperature rise.
02 September 2009
Det Norske Veritas AS. All rights reserved.

Fire Insulation - E/R


Standard Fire Test - Furnace Temperature:
1000
T (C)

945
900

841
800

738
700

679

600

576

500
0

10

15

20

25

30

02 September 2009
Det Norske Veritas AS. All rights reserved.

10

35

40

45

50

55

60 65
Min.

Fire Insulation - E/R


B Class Divisions
Are those divisions formed by bulkheads, decks, ceilings or
linings which comply with the following criteria:
1. They are constructed of approved non-combustible materials
and all materials used in the construction and erection of B
class divisions are non-combustible. (Combustible veneers may
be permitted.)
2. They prevent the passage of flame to the end of the first half
hour of the standard fire test.

02 September 2009
Det Norske Veritas AS. All rights reserved.

11

Fire Insulation - E/R


B Class Divisions
3. They have an insulation value such
that the average temperature of the
unexposed side will not rise more
than 140C above the original
temperature, nor will the maximum
hot spottemperature rise more
than 225C above the original
temperature, within the following
time:

Class B-0

0 Minutes

Class B-15

15 Minutes

4. The administration has required a test of a prototype division in


accordance with the IMO fire test procedure code to ensure that
it meets the requirements for integrity and temperature rise.
02 September 2009
Det Norske Veritas AS. All rights reserved.

12

Fire Insulation - E/R


C Class Divisions

Are divisions constructed of approved non-combustible materials


(combustible veneers may be permitted).
No requirements to integrity (passage of flame/smoke) or
temperature rise on the unexposed side.

02 September 2009
Det Norske Veritas AS. All rights reserved.

13

Fire Insulation - E/R

A - 60 REQUIRED
IF THE S/G ROOM
CONTAIN EMERGENCY
FIRE PUMP
ACCOMMODATION
STEERING GEAR ROOM

E/R
CLASS
A-0
CLASS A-60

02 September 2009
Det Norske Veritas AS. All rights reserved.

EMERGENCY
ESCAPE TRUNK

14

Fire Insulation - E/R

02 September 2009
Det Norske Veritas AS. All rights reserved.

15

Fire Insulation - E/R


Case Study 13:
Please review the design below and present your comments, if any.

2
A- 0

5
A - 15

02 September 2009
Det Norske Veritas AS. All rights reserved.

16

Fire Insulation - E/R

References:
SOLAS 2000 Amendments Ch.II-2 Reg.3/5/6/8/9
SOLAS 1974 as amended Ch.II-2 Reg.42/43/44/46/47/49/50/56/57/58
DNV Rules for Ships Pt.5 Ch.3 Sec.7

02 September 2009
Det Norske Veritas AS. All rights reserved.

17

Fire Insulation - E/R


Case 14 ;

Please review this design and present your comments, if any.

A - 60 REQUIRED
IF THE S/G ROOM
CONTAIN EMERGENCY
FIRE PUMP

A-60 Deck
ACCOMMODATION

STEERING GEAR ROOM

E/R
CLASS
A-0
CLASS A-60

02 September 2009
Det Norske Veritas AS. All rights reserved.

EMERGENCY
ESCAPE TRUNK