ARUN III HEP (4x225 MW), NEPAL

Chapter of Generator Transformer (Section-4)


Sr.
No.

Clause no.

1.

4.1.2

2.

4.2.4

3.

4.3

4.

4.5.1

5.

4.8.2

6.

4.5.8

7.

4.9.3

SJVNs Comments

SJVN reply on replies


of WAPCOS dated
30.01.2015
Maximum allowable size and Ok
weight limit of package that
can
be
transported
is
mentioned as 14mX5mX4m
and 100 tonne.
Criteria for choosing this limit
may be provided.
The capacity of EOT crane is Agreed
and
the
mentioned as 90T whereas in capacity should be in
DPR the capacity of crane for line with EOT Crane
transformer
cavern
is chapter
mentioned as 100T. This may
be clarified
Short circuit withstand capacity WAPCOSs
reply
mention is 63kA where as it is awaited
40kA in case of Switchyard.
This may be clarified.
Noise level limit 85dB limit has Relevant
pages
of
specified. Relevant NEMA Nema standard may be
standard publication no. TR-1 supplied by WAPCOS.
as
mentioned
may
be
provided.
The criteria for choosing Agreed
magnetizing
characteristics
upto 1.8 p.u. may be given.
As
per
this
clause Agreed
Transformers
shall
be
capable of operating at full
load for 10 minutes after
failure of the oil or water circulating
system
with
the
calculated winding hot-spot
temperature not exceeding
1400C. Whereas in CBIP
Manual this temperature is
mentioned as 1500C. This may
be clarified.
As per this clause The Calculations
for
penalties per KW for the arriving on such a rate

8.

4.10.1

9.

4.13.1.1

10.

11.

4.13.3.5,4.1
3.3.7,
4.13.3.9,
4.13.4
4.15.1

12.

4.30.6

13.

SLD

14.

SLD

excess of no load losses, load


losses and auxiliary losses
over the guaranteed values
will be calculated at the rate of
Rs 3.50 lakhs; Rs 3.20 & Rs
3.50 respectively.
The
calculation
for
capitalisation of losses to be
provided for mentioned rates.
The criteria for choosing
300mm2 XLPE cable for
connecting HV terminals of
Transformers
with
Air
Insulated Switchgear may be
provided.
Cable
sizing
calculations may be provided.
The criteria / supporting
document for choosing tank
strength to withstand without
distortion pressure of 0.35
Kg/cm2 with oil at operating
level may be provided.
The supporting documents /
calculations for various values
/ parameters chosen in the
clauses may be provided.
Calculations for minimum
knee point voltage (Vk) for
NCT may be provided.
In this clause Special tests
have been indicated as
optional. This may be clarified.

Calculations for all CTs used


for GT shall be provided.
Differential protection shown
in neutral side of GT may be
reviewed.

is to be provided.

Calculations
to
be
provided for choosing
cable size.

Agreed

WAPCOSs
awaited

reply

Ok, Table at 4.15.1


may
be
modified
accordingly.
These tests are not
optional and they are
required to be carried
out on one transformer.
Additionally SFRA test
and FDS test are
required to be carried
out as special test and
site test. TS to be
modified accordingly.
WAPCOSs
reply
awaited
ok, SLD to be modified
accordingly.

Replies of clause 4.40( Station and auxiliary transformers) not


submitted by WAPCOS