AHA-Series
State of the art Manufacturing Facilities
101SGR/AH/220313
Technical Specifications
Ampere Frame as per IEC60947-2
630
AHA 08~20
AH-6D
AHA 08~20
AHA 30
AHA 40
AHA 50
3200
4000
5000
3/4
3/4
3/4
3/4
3/4
Nos. of Poles
Type
Rated Ultimate breaking capacity (kA rms) at 415V AC
50kA
65kA
65kA
65kA
85kA
50kA
65kA
65kA
65kA
85kA
50kA
65kA
65kA
65kA
85kA
105kA
143kA
143kA
143kA
187kA
30/40
30/40
30/40
30/40
30/40
Configuration
Manual Fixed
Electrical Fixed
Manual Drawout
Electrical Drawout
* Rated Service breaking capacity (Ics) & rated ultimate breaking capacity (Icu) are same at 415V. For other voltages please contact us.
Higher Breaking Capacity ACBs available on request.
Breaker
Type
AHA-08N/S
AHA-10S
AHA-12S
AHA-16S
AHA-20N/S
AHA-30S
AHA-40S
AHA-50H
1
Front Panel
fitting
2
Types of
mounting
Terminal 2
arrangement
Accessories
for draw-out
type
Types of
spring charging
system
Accessories for
spring charging
system
Under
voltage trip
devices
Operating
button cover
10
Micro Processor
based OCR
Thermomagnetic
based OCR
Position switch
Position
padlock
Vertical
Door interlock
and 3
defeat facility
Draw-out type
Close-open
cycle counter
Key interlock
system
9
Accessories for
overcurrent trip
devices
11
12
Other
trips
Auxiliary and
Trip indication
switches
Main-circuit
safety shutters
ON/OFF 1
Push Button
Indicator
Cover
Horizontal
Lifter
Fixed
Motor Charging
Manual Charging
Compact
UVT coil
without time
delay for
AC/DC
application
AUH-V-***
mIT-100 for
general
feeder circuit
mIT-G for 3
generator
protection
Mal Insertion
Prevention Device
Castle
key lock
Short circuiting
contacts
Draw-out
position indicator
Micro-Pro
3.1/4.1 / 5.1
for multi purpose
OCR checker
(External)
OCR alarm switch
With Non
Adjustable
INST
24V DC,
Power supply
(External)
With Shunt
Trip
CT for neutral
line
4
With thermal
O/L relay
MCR
Horizontal Terminal upto AHA-20S and Vertical Terminal for AHA-30S and above are available as Standard. Additional adaptors for changing to vertical are available as accessories. 3 On request.
Overcurrent Release
Thermal Magentic Trip Device: Type TM
Microprocessor Based Overcurrent Trip Device: Type mIT-100 & mIT-G
Intelligent Release: Type MicroPro 3.1, 4.1 & 5.1
TM
by selecting the positions of the rotary switches / Dip Switches on the front . The new settings become effective as soon as they are changed
n Direct acting electromagnetic instantaneous trip device with fixed factory set release, settings 3 - 50 kA
when the release is powered by the CTs. The microcontroller in the release ensures positive tripping of the MHT coil under any undesired
conditions of overload ,short circuit or earth fault by giving the trip command as per the selected set of characteristics. There are Red LEDs
in the front for each type of fault indication and on occurrence of overload condition, O/L LED flashes once, every second before the tripping
n Provision for remote tripping / electrical reset as optional features with overload relay.
command is issued. If the Overcurrent condition cease to exist before the release trips, LED flashing also stops. A thermal memory is
incorporated in the release and when the Overcurrent condition occurs again, it takes into account the earlier overcurrent effect before giving
mIT is a true RMS sensing overcurrent trip device, requiring no external supply for its basic function. It is available in two types, i.e., mIT100 for
industrial application and mITG for generator protection.
Error free and user friendly setting of current and time delay.
n MicroPro 3.1
n MicroPro 4.1
n MicroPro 5.1
MicroPro 4.1
Protection thresholds and delays are set using the adjustment
dials. The running load is displayed in amperes.
Type of Protection
n Overload protection
IS 9000 - PG4
n Neutral Protection
I>
t>
Ig
IS 9000 - PG3
IEC 255 - 4
tg
-0.05
-0.1
-0.2
-0.3
x lo
I>
I >>
-2.5
-5
-10
-15
O
I
I>
t>
Sec
IG
Other Features
STD
4+
IG
-LTD
ms
-50
-100
-150
-200
t >>
x lo
ms
n Zone Selectivity
INS
50+ % lo
-50
-100
-150
-200
tG
I >>
4+
-1
-1
-5
-5
-10
-15
NORMAL
15%+
-TEST
-LONG
-SHORT
DIP
- ON
FUNCTION
BLOCKING
50+
-1
-1
-2
-2
GFT
RESET
TEST MODE
IEC 801- 3
IEC 801- 2
IEC 801- 4
IEC 801- 5
IEC 255 - 4
2.5+
t >>
ON
NORMAL
0.5+
1 2 3 4
LTD
I >>
-2
-3
I >>
x lo
-STD
-INS
-GFT
n Trip History
Microprocessor
based relay
n Ampere Meter
n Communication: RS 485, Modbus protocol
n LCD display
n LCD display and fault LED retention in case of power failure
Micropro 3.1
C&S introduces a new release Micropro 3.1 in its range of microprocessor based ACB releases. Micropro 3.1 has been specifically designed
with LSIG protective functions in a compact unit offering an economical solution for basic applications areas.
Types of protection functions
n
n
n
Overload Protection
Pick up- 0.4 to 1.1 In and OFF
Delay- 2.5 to 35 Sec
Type of Protection
n Overload protection
n Short Circuit current protection
Short-circuit Protection
Pick up- 1.5 to 9.0 Ir
Delay- 50 to 800 msec
Instantaneous Protection - 3.0 to 10 Ir and OFF
Other Features
n Zone Selectivity
Trip History
Features
Individual Fault indication LEDs
Tripping characteristics
n Ampere Meter
n Communication: RS 485, Modbus protocol
Microprocessor
based relay
MicroPro 5.1
Protection thresholds and delays are set using the keypad. The
selected value are momentarily displayed in amperes.
n LCD display
n LCD display and fault LED retention in case of power failure
Type
3.1
4.1
5.1
Delay
0.4-1.0 In with
OFF in steps of 0.01
2.5 to 25 sec at
6 Ir in steps of 0.5 Sec
Short Circuit
1.5-9.0 Ir in 16 steps:
1.5, 2.0, 2.5, 3.0, 3.5, 4.0, 4.5, 5.0,
5.5, 6.0, 6.5, 7.0, 7.5, 8.0, 8.5, 9.0
0.05-0.8 sec in 16 steps:
0.05, 0.10, 0.15, 0.20, 0.25, 0.30, 0.35, 0.40,
0.45, 0.50,0.55, 0.60, 0.65, 0.70, 0.75, 0.80
Pick up
Delay
1.5-10 Ir in 10 steps:
1.5, 2, 2.5, 3, 4, 5, 6, 8, 9, 10
2.0-12 Ir In with
OFF in steps of 0.5
Instantaneous
3.0 - 10 Ir with OFF in 9 steps:
OFF, 3, 4, 5, 6, 7, 8, 9, 10
Earth Fault
Pick up
0.2-1.0 Ir with
OFF in10 steps of 0.01
Delay
Not Available
30 min
N Protection
Pick up
Cooling time contact
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
NA
Available
Available
Through 7 programmable
relays (optional)
Through 7 programmable
relays (optional)
Trip History
NA
Zone selectivity
NA
Available
Available
Settings Adjustment by
DIP Switches
Knob
Keypad
LCD Display
NA
YES
YES
Load current
NA
Phase, N & E
Phase, N & E
Fault current
NA
To remote
NA
NA
To SCADA system
through MODBUS
To SCADA system
through MODBUS
Measurements
INDICATIONS
Communication
Inputs
: From The CTs with 200mA rated output One for each phase and one for Neutral current measurement.
Output
Red Led
: indications for different types of fault/tripping such as Over load, Short Ckt, Earth Fault, Instantaneous, Neutral.
Green Led
Operation
When connected to MicroPro and Master PC, Communication Module:
Can read the settings of the MicroPro .
Can change the settings of the MicroPro as dictated by Master PC.
Can record following data related to last 16 faults
a) The type of fault
b) In which phase the fault has occurred
c) At, which instant the fault occurred
d) Fault current.
Can record the normal currents IR, IY, IB, IE, and IN
Operates one of the relays whose contacts are available on the terminals as
soon as MicroPro exceeds the threshold of the trip.
Because of the above capabilities all the relevant information related to status of
the relay can be furnished to the Master. The information can also be used for zone
selectivity interlocking by using the contacts of the relevant relay.
Connections
Zi - D19
Di & Do contacts
ZO / COMMON/DO
Zone selectivity
Input supply 230 V AC for communication module. Phase to be connected to L & neutral
at N & earth at E.
The module has relay outputs corresponding to the type of fault occurred in the MicroPro. There are total 7 Relays and contact of each relay is
available for feeding to alarm annunciator or any other control .
ACB simplifies the design of switchboard and standardizes the installation of the products.
This offers flexibility for construction of busbar as product is available with different terminal requirement (Horizontal, vertical or mixed
The module has built in Power supply card and DC supply for the relay can be obtained from this module.If the relay card is not used then the
connection) meeting varied customer requirement for termination. Such facility allows user to optimize the size of switchboards and busbar
module becomes power supply module.The power supply card is common with Communication module
connection.
Operation - PSRM
The PSRM module when connected to Micro pro will get the information of type of fault and in which phase the fault has occurred.
Corresponding to this a particular relays will operate and the output contacts of the relay will change the status. Through 3 DIP switches, one
can block the function. Blocking ensures that the particular output contact corresponding to the function have no effect even if the function in
the relay device is activated. The contacts will remain open if DIP switches are used to block the function. There will be option of providing 4
or 7 relays.
Auxiliary Supply
Relays
Input:
Output:
24V DC 10%
Number of relays:
Contact rating:
Contacts:
4 or 7 nos.
125V AC, 0.6A or 110V DC 0.6A
1 terminal pair from each relay
Extension functions:
Extension provides operation of relays. Signal for such operation are sent by MicroPro on RS485 serial data
communication interface. The relays operate on following faults:
1. Over current [I>]
2. Phase current High set [I>>}
3. Earth Fault [IE>]
4. Neutral Over current [IN>]
5. Circuit Breaker failure [CBF] 6. Pre-trip alarm [W]
7. Spare
Function blocking:
DIP switches are provided for selectively blocking any of the above functions.
7 Position DIP switch works as follows:
Number of busbars
Copper busbars
Dimensions in mm
630A
40 X 5
400
800A
50 X 5
500
1000A
60 X 5
600
1250A
80 X 5
800
1600A
100 X 5
1000
2000A
100 X 5
1500
2500A
100 X 5
2000
3200A
100 X 5
3000
4000A
200 X 5
4000
5000A
200 X 5
5000
Case 1: Number of relays =7: Each position corresponds to one of the above functions and in the same sequence.
When a switch is in OFF position, the corresponding function is blocked. This means that relay will not trip when its
assigned fault occurs.
Case 2: Number of relays =4: The enabled functions are assigned to consecutive relays. Not more than 4
functions can be enabled since there are only 4 relays.
For example, if switches 2, 4 and 7 are OFF, then assignment is:
I>
Relay1
IE>
Relay2
CBF
Relay3
W
Relay4
Total Terminals: 21
Communication Device
Type
RS485 Master
Size:
W x H x D in mm: 119 x 63 x 50
10
11
Panel Cutout
AHA 30S
AHA 40S, AHA 50H
(3P) (4P)
Panel Cutout
C
N
A
Mounting holes
4-12 (AHA-30S)
4-14 (AHA-40S & 50H)
Mounting holes
4-10
D
E
L
a
98
247
295
3P
316
4P
416
3P
215
F
4P
215
3P
215
4P
315
505
120
J
3P
122
K
4P
122
3P
270
L
4P
270
3P
117
4P
117
509
205
P
3P
100
4P
100
3P
4P
3P
4P
3P
4P
3P
4P
80
247
295
368
468
199
199
199
299
480
120
100
100
379
187
100
100
15
15
334
334
154
254
154
154
98
247
295
316
416
215
215
215
315
505
120
122
122
270
270
117
117
509
205
100
100
154
80
247
295
368
468
199
199
199
299
480
120
100
100
379
187
100
100
15
15
334
334
154
254
154
D/O (AHA-30S)
137
308
363
416
546
270
270
270
400
595
138
163
163
270
270
137
137
570
211.5
130
130
137
308
363
498
658
311
311
311
471
595
93
163
163
270
270
166
166
599
149
160
160
Terminal Arrangements
130
25
160
35 35 35
17.5
17.5
(3P)
(4P)
160
160
20
140
t
P
d
Earth Terminal M8
115
160
149
255
4- 15
55
150
211.5
175
80
213
80
175
255
25
m m
25
645
3030
20
25
54 45
100
20
25
15
57
15
100
2-11
3030
20
3-f15
Mounting Holes 3 14
(3P)
(4P)
140
130
j
j
54
130
3-14
iq
Terminal
blocks for
control circuit
36-M4
25
Mounting Holes
4x12
AHA-50H (Drawout)
Mounting holes 3-14
W
630
AHA-40S (Drawout)
AHA-30S (Draw-Out)
AHA-08~20S
630
AHA-08~20N
AHA-08~20N
AHA-08~20S
81
160
25
160
30
200
Earth terminal M8
Earth Terminal M8
D/O (AHA-08N)
46.8
107
20
30
45
FIX (AHA-08N)
60
107
15
30
45
46.8
115
20
35
20
60
D/O (AHA-20N/S)
i
3P
112.5 112.5
-
112.5 112.5
175
50
48
157
65
440
112.5
175
50
48
157
65
440
4P
3P
4P
175
112.5
175
FIX (AHA-20N)
60
115
15
30
20
45
FIX (AHA-20S)
60
115
15
30
20
55
D/O (AHA-30S)
115
157
25
50
20
100
112.5
175
240
175
240
65
48
213
150
553
D/O (AHA-40S)
106
194
25
55
15
140
112.5
175
255
175
255
80
48
200
30
578
D/O (AHA-50H)
106
194
25
55
30
140
112.5
175
255
175
255
80
48
200
30
578
12
Type of ACBs
AHA-08N
AHA-20N
AHA-08S
AHA-20S
AHA-25S
AHA-30S
AHA-40S
AHA-50H
FIXED
530
550
530
550
DRAWOUT
550
570
550
590
680
735
710
765
710
765
Type of ACBs
AHA
13
MCR
MCR
14
15