Motor Acceleration

Motor Acceleration Comparison Case #1


Comparison of ETAP Motor Acceleration with Torque Control Against Hand Calculated Results
Motor Acceleration Comparison Case #2
Comparison of ETAP Motor Acceleration Results Against Transient Stability
Unbalanced Load Flow
Unbalanced Load Flow Comparison Case #1
Comparison of ETAP Unbalanced Load Flow Results against a Published IEEE 13-Bus Feeder
System
Harmonics
Harmonic Analysis Comparison Case #1
Comparison of ETAP Harmonic Analysis Results Against IEEE Example
Transient Stability
Transient Stability Comparison Case #1
Comparison with Field Measurement Data for Generator Start-Up Condition
Transient Stability Comparison Case #2
Comparison with I.E.E. Japan (IEEJ) Electrical Power System Standard Benchmark
Transient Stability Comparison Case #3
Comparison with Field Measurements from a Digital Fault Recorder
Transient Stability Comparison Case #4
Comparison with 9-Bus Multi-Machine System Benchmark
Transient Stability Comparison Case #5
Comparison with PTI PSS/E Simulation Results
Copyright 2005 Operation Technology, Inc. All Rights Reserved. Page 3 of 66
No part of this documentation may be reproduced or transmitted without prior written permission of OTI. For information on obtaining permissions, contact info@etap.com.
The Licensee
may copy portions of this documentation for their exclusive use, as long as all reproductions include the OTI copyright notice. Copies shall not be distributed to other
persons or entities,
including translating into another language. Certain names and/or logos in this document may constitute trademarks, service marks, or trade names of OTI or other
entities.

ETAP Load Flow


The ETAP V&V process for the Load Flow program has over 1500 test case scenarios that are run
before each
ETAP release. The following case samples are from the Load Flow Solutions & Methods category.

Load Flow Comparison Case # 1


Comparison of ETAP Load Flow Results against a Published Textbook Example

Excerpts from Validation Cases and Comparison Results (TCS-LF-006)


Highlights
Comparison between ETAP Load Flow (LF) results against those published in the textbook
Computer
Aided Power System Operation and Analysis by R.N Dhar, page 89.
Comparison of results for the Newton Rhapson Method.
Comparison of results for the Accelerated Gauss Seidel Method.
Comparison of results for the Fast Decoupled Method.
Study includes generation, motor loads, transformers and cables.
Considers line impedance and admittance.
Comparisons are made against generation schedule, bus voltages and power flows in per-unit.
The difference in the results is less than 1% for all bus voltages and power flows.
System Description
This is a six-bus system that is composed of lines, cables, transformers, generators and utility. The
line
impedance and charging effects are considered. The schedule of generation and loading for each bus
were taken
as described in Table 6.2 of the published example.