Project:
Name of Manufacturer
Spec Clause No.
Tech. Information
Loss calculation
Drawing at Detailed engineering stage.
Load and No load loss
Noise level
Type of Grounding
Short circuit withstand level
Flux density
Drin & Filter Valves
Minimum pressure (vacuum)
oil level indicator
MCCB on LV Box
Impedance

14

oil level indicator

15
16
17

Calculation
Tap Position
Secondary Neutral Bushing

18

List of drawing required

19
20

Secondary Cable Termination


General

TECHNICAL RESOLUTION
Construc on of New 110 / 13.8 kV Substa on AL Adel (Makkah)
Equipment
Saudi Federal Transformer
Date
Query / Clarification required
Bidders Response
Vendor to provide all technical information/ support / documents as per SEC requirement
Vendor shall provide Loss calculation for proposed Transformer.
Vendor to confirm that as per SEC requirement all necessary drawing/documents will be provided during detailed engineering stage.
Vendor to confirm that the offered Load and No load loss of transformer is in-line with IEC 60076-1 or IEEE C57.12.00 standard, please confirm
As per my NEMA TR-1 the allowed Noise level max. is 56dBA, please confirm
revise the type of grounding, as per PTS vendor shall provide the resistive for Station Service Transformer.
Please consider Short circuit withstand level as per PTS., Vendor has to specify Isc for both HV & LV.
As per our understanding the max. flux density@100% rated voltage is 1.75 tesla, Please clarify
Please confirm the proposed Drin & Filter Valves are approved by SEC.
Minimum pressure (vacuum) withstand without permanent deformation for 30 minutes is applicable for rigid body tank only, Please clarify.
As per the 51-TMSS-01 (page 09 of 21), the required Scale range of oil level indicator is Min 25 deg C Max., Please clarify
As per 53-TMSS-01, Rev-01, MCCB to be considered on at LV side of transformer, please confirm the same considered in your offer.
The Impedance as per PTS, Please confirm
As per 51-TMSS-01, Rev.01 the indicator shall have a dark face dial with light markings and light colour indicating pointer, please confirm NGSA approval for
the same.
Please provide the necessary calculation As per latest revision of 51TMSS-01 & TES-P-119-35 (i.e. Short circuit calculation etc.)
Vendor has to confirm and specify the highest primary voltage of tap position s
Vendor shall confirm the BIL for lv neutral bushing as Per 01-TMSS-01
Oil level indicator, Over Pressure vent, Gate Valve with sampling , Filter valve, Roller assembly, name plate, caution plate, Danger plate, painting procedure,
HV & LV bushing, HV & LV cable box assembly, HV spade, Foundation details.
Clause 4.5 Vendor shall revise the provide the type of termination
Vendor shall provide Clause by clause compliance of 51-TMSS-01 & 01-TMSS-01/R1.
ITP
Manufacture Responsibility Statement.
List of all accessories/components in tabulated form indicating:
Catalogues (prefer colored) for: a) Transformer b) Accessories c) Main Breaker (MCCB/ACB-as applicable)

21

Drawings:
a) General Arrangement of Transformer outline with dimensions, legend and quantity of accessories.
b) HV Cable box Assembly
c) LV Cable box Assembly with MCCB
d) HV Bushing indicating rated voltage and creepage
e) LV & LVN Bushings indicating rated volatge and creepage
f) Vendor shall specify the dimensions for both HV & LV bushing to bushing (Phase to Phase)

22

Test Reports
Vendor to provide the Type Test Reports as per SEC norms.
a) Type Test Reports
b) Routine (Production) Tests
c) Special Tests
d) Bushings
e) Offer circuit Tap Changer
f) Accessories Tests

23

Data Schedule
51-TMSS-01/Rev.01
54-TMSS-01/Rev.01
54-TMSS-01/Rev.01

Clause 4.5 Vendor shall revise the provide the type of termination
Vendor shall provide datasheet in readable format.
Clause 5.2 Vendor shall confirm in corrosive sulphur as per IEC62535.

Service Transformer
25/06/15
Resolution