Medium-voltage switchgear ECOS-C

eco-friendly (SF6 free)


digital protection without mounted cabinet
easy to use
monopolar insulated
busbar

Germany sales:

Switchgear type
The ECOS-C switchgear is a
type-tested compact single
busbar system with metal
housing.

Digital protection relay


The digital protection relays (3
types) can be integrated directly
into the switchgear. This means
there is no need for an additional
mounted cabinet.

No. of fields
The ECOS-C is available from 2 to
7 panels.

Eco-friendly
The entire switchgear is
SF6 -free

Safe to touch
The busbar systems and selector switches for busbars/earth
electrodes are entirely touch-safe.
They have monopolar oil insulation made from eco-friendly
synthetic MIDEL 7131.

Advantages of synthetic ester


The advantages of this superb
insulation medium in comparison
to petroleum are as follows:
biodegradable
self-extinguishing
minimal flue gas formation
non-toxic
high combustion point
high moisture tolerance
high thermal resistance

SF6 free

Cellpack Power Systems AG Schtzenhausstrasse 2 5612 Villmergen


Phone +41(0)56 619 88 00 Fax +41(0)56 619 88 04
http://powersystems.cellpack.com power.systems@cellpack.com

Medium voltage switchgear ECOS-C

page number 2

Technical data
The ECOS-C switchgear is suitable for rated voltages of up to 24 kV and rated currents of up to 630 A.

Switchgear (EN62271-200)
Rated voltage Ur

The available switching elements,


circuit-breaker and switch-disconnector, are based on vacuum
switching chamber technology
and do not require maintenance.

24 kV

Rated short-duration power-frequency withstand voltage Ud

50 kV

Rated lightning impulse withstand voltage Up

125 kV

Rated frequency fr

50 Hz

Rated short-time withstand current lk

16 kA

Rated short-time tk

1s

Rated peak withstand current Ip

40 kA

Rated normal current lr

630 A

Ambient air temperature*

-25 bis +50 C

Internal arc classification

IAC A FL 20 kA 1s

Loss of service continuity category

LSC 2 PM

Degree of protection for oi-filled switchgear vessel

IP3x

Degree of protection for swithgear enclosure

IP63

For site altitudes above

unlimited

Insulating

Synth. Ester-Oil

* depending on the secondary equipement used

Circuit-breaker (EN 62271-100)

Switch-disconnector (EN 62271-103)

Rated voltage Ur

24 kV

Rated voltage Ur

24 kV

Rated short-time withstand current lk (1s)

16 kA

Rated short-time withstand current lk (1s)

16 kA

Rated peak withstand current Ip

40 kA

Rated peak withstand current Ip

40 kA

Rated short-circuit making current lsc

16 kA

Rated short-cirvuit making current lma

40 kA

Rated normal current lr

630 A

Rated normal current lr

630 A

Rated mainly active load breaking current lload

630 A

Number of operating cycles, mechanical (class.)

10000

Number of operating cycles, electrical (class.)


Rated operating sequence

E1
O-0,3s-CO-3min-CO

Switching technology

Vacuum

Number of operating cycles, mechanical (class.)


Number of operating cycles, electrical (class.)
Switching technology

10000
E1
Vacuum

ECOS-C-PR-EN-23.06.2014

Subject to technical modifications.

The switching elements, circuit-breaker/switch-disconnector (multi-purpose switch-disconnector), can be


combined in any sequence. The medium-voltage cable is connected at the front via user-friendly angled cable
outlets. You can also connect surge arresters if necessary. There is also a cable converter for measuring current
in the cable connection area.

Dimensions
Switchgear height (without low-voltage compartment)

1400 mm

Switchgear depth

1040 mm

Swithgear width

2-panels

650 mm

3-panels

890 mm

4-panels

1130 mm

5-panels

1370 mm

6-panels

1610 mm

7-panels

1850 mm

Low-voltage compartment height

500 mm

Low-voltage compartment depth

398 mm

Cellpack Power Systems AG Schtzenhausstrasse 2 5612 Villmergen


Phone +41(0)56 619 88 00 Fax +41(0)56 619 88 04
http://powersystems.cellpack.com power.systems@cellpack.com

Potrebbero piacerti anche