Show the two-stage cascade refrigeration system, with each stage operating on the ideal
vapor-compression refrigeration cycle, with refrigerant-134a as the working fluid, on
T s
diagram as in Figure (1).
For the two-stage cascade refrigeration system, with each stage operating on the ideal
vapor-compression refrigeration cycle, with refrigerant-134a as the working fluid, the
Ti hi Pi
i th
temperature, specific enthalpy, pressure, and specific entropy at
state are , , ,
si
and
respectively. Also, the saturated liquid state is denoted by the subscript f, the
saturated vapor is denoted by the subscript g, and the properties at latent stage are
denoted by the subscript fg.
(a)
h1
Use saturated refrigerant-134a pressure table, to find
P1
0.14 MPa
.
h1 hg 239.19 kJ kg
s1
and
of refrigerant-134a, at
s1 sg 0.94467 kJ kg K
s1
s2
s2 s@ s 0.9306
h2 h@ s 0.9306 h@ s 0.9628 h@ s 0.9306
s@ s 0.9628 s@ s 0.9306
0.94467 0.9306
256.59+ 265.88 256.59
0.9628 0.9306
260.65 kJ kg
h3
Use saturated refrigerant-134a pressure table, to find the
P3
.
h3 h f 63.92 kJ kg
h3
For the isenthalpic process 3-4, specific enthalpy remains constant. Hence,
equal.
h5
Use saturated refrigerant-134a pressure table, to find
P5
MPa
.
h5 hg 255.61kJ kg
h4
and
are
s5
and
of refrigerant at 0.4
s5 sg 0.92711kJ kg K
s5
s6
s6 s@ s 0.9185
s@ s 0.9481 s@ s 0.9185
0.92711 0.9185
0.9481 0.9185
P7
h7
Use saturated refrigerant-134a pressure table, to find
h7 h f 95.48kJ kg
h7
For the isenthalpic process 7-8, specific enthalpy remains constant. Hence,
equal.
h8
and
are
m&h m&h
e e
i i
m&A h5 h8 m&B h2 h3
E&in
E&out
m&A 255.61kJ kg
h5 95.48 kJ kg
h8
Rearrange and substitute
for
,
for ,
for ,
h2
h3
m&B
260.65 kJ kg
63.92 kJ kg
for , and
for to find
.
h h
m&B m&A 5 8
h2 h3
0.24 kg s
0.24 kg s
255.61 95.48
260.65 63.92
0.195 kg s
0.195kg s
Hence, the mass flow rate of refrigerant through the lower cycle is
(b)
Q&
L
m&B 239.19 kJ kg
h1
h4
63.92 kJ kg
Substitute
for
,
for , and
for .
&
QL 0.195 kg s 239.19 63.92 kJ kg
0.195 kg s
34.18 kW
34.18 kW
Hence, the rate of heat removed by the Cascade cycle is
W&
in
m&A h6 h5 m&B h2 h1
W&compI,in
Here, the work input for the first compressor is
W&compII,in
second compressor is
.
m&B 239.19 kJ kg
h1 260.65 kJ kg
h2 0.24 kg s
Substitute
for
,
for ,
for ,
for
m&A 269.99 kJ kg
h6
h
255.61kJ kg
5
,
for , and
for .
0.195 kg s
W&in
7.63kW
7.63kW
(c)
COPR
Find the COP for the given Cascade refrigeration system
Q&
COPR L
W&
in
7.63 kW
Substitute
W&in
for
, and 34.18 kW for
34.18 kW
COPR
7.63kW
Q&L
4.479
4.479