Produced on 1/31/2011 with Xpress V5.4.7 - database Central 7.6.

0
Project name
Reference
Client name
Revision

SKY GATE
TYP LEVEL 27,29
-

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model

Qty

Description

RXYQ30PA

1 Heat pump VRV III P COMPACT

FXAQ25P

1 A - Wall mounted unit

FXAQ40P

1 A - Wall mounted unit

FXMQ250MA

1 M - Concealed ceiling unit (large)

FXSQ100P

2 S - Concealed ceiling mounted

FXSQ140P

1 S - Concealed ceiling mounted

FXSQ50P

2 S - Concealed ceiling mounted

FXSQ63P

2 S - Concealed ceiling mounted

FXSQ80P

1 S - Concealed ceiling mounted

KHRQ22M20T

2 REFNET branch piping kit

KHRQ22M29T9

2 REFNET branch piping kit

KHRQ22M64T

5 REFNET branch piping kit

KHRQ22M75T
BRC1E51A
BHFQ22P1007

1 REFNET branch piping kit


11 Remote controller
1 Outdoor unit multi connection piping kit for 2 outdoors

Piping 1/4"

5.0m

Piping 3/8"

42.0m

Piping 1/2"

16.0m

Piping 5/8"

31.0m

Piping 3/4"

9.0m

Piping 7/8"

15.0m

Piping 1 1/8"

16.0m

Piping 1 3/8"

8.0m

The Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Program.

Page 1

2. Indoor Unit Details


2.1. Table of Abbreviations
Name

Logical name of the device, possibly preceeded by room name

FCU

Device model name

Tmp C

Indoor conditions in cooling (dry bulb temp. / RH)

Rq TC

Required total cooling capacity

TC

Available total cooling capacity

Rq SC

Required sensible cooling capacity

SC

Available sensible cooling capacity

Tmp H

Indoor temperature in heating

Rq HC

Required heating capacity

HC

Available heating capacity (integrated heating capacity)

Airflow

Supplied airflow at low and high fan speed

Sound

Sound pressure low and high

PS

Power supply (voltage and phases)

MCA

Minimum Circuit Amps

Fuses

Fuses

WxHxD

WidthxHeightxDepth

Wght

Weight of the device

PI-C 50Hz Power input in cooling at 50Hz


PI-C 60Hz Power input in cooling at 60Hz
PI-H 50Hz Power input in heating at 50Hz
PI-H 60Hz Power input in heating at 60Hz

The Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Program.

Page 2

2.2. OU-TYP-07* - RXYQ30PA

RXYQ24PA

Actual capacity data at conditions and combination ratio (128%) as entered


Name

FCU

Tmp C

Rq TC

TC

Rq SC

SC

Tmp H

Rq HC

HC

Airflow

kW

kW

kW

kW

kW

kW

l/s

BALCONY:AC-TYP-03

FXSQ63P

23.3 / 55%

5.5

5.3

5.5*

4.2

22.0

n/a

5.2 267-325

BEDROOM 4:AC-TYP-02

FXSQ50P

23.0 / 55%

4.2

4.3

3.2*

3.4

22.0

n/a

4.2 183-267

FAMILY ROOM:AC-TYP-05

FXSQ80P

22.6 / 55%

7.0

6.8

5.8*

5.4

22.0

n/a

6.7 333-417

BEDROOM 2:AC-TYO-02

FXSQ50P

23.0 / 55%

4.2

4.3

3.2*

3.4

22.0

n/a

4.2 183-267

MASTER BEDROOM 1:AC-TYP-06 FXSQ100P

22.4 / 55%

8.3

8.3

7.3*

6.4

22.0

n/a

8.3 383-533

BEDROOM 3:AC-TYP-03

FXSQ63P

22.7 / 55%

5.4

5.3

4.4*

4.2

22.0

n/a

5.2 267-325

KITCHEN+PANTRY:AC-TYP-08

FXSQ140P

27.8 / 55%

12.8

12.7

7.0*

9.2

22.0

n/a

11.7 533-767

STAFF ROOM 1:AC-TYP-11

FXAQ25P

22.0 / 55%

1.8

2.1

1.7*

1.7

22.0

n/a

2.1 83-133

STAFF ROOM 2:AC-TYP-12

FXAQ40P

22.0 / 55%

3.1

3.3

3.0*

2.6

22.0

n/a

3.3 150-200

DINING:AC-TYP-06

FXSQ100P

23.4 / 55%

8.6

8.7

5.9*

6.6

22.0

n/a

8.3 383-533

LIVING:AC-TYP-10

FXMQ250MA

23.2 / 55%

20.6

21.6

15.1*

16.1

22.0

n/a

20.9 1033-1200

Total

82.6

TOTAL (120%CR On Actual


Capacity)
Name

63.1

80.1

66

Sound

PS

MCA

dBA

Fuses

WxHxD

Wght

PI-C 50Hz

PI-C 60Hz

PI-H 50Hz

mm

kg

kW

kW

kW

PI-H 6

kW

BALCONY:AC-TYP-03

30-37

230V 1ph

1.1 Factory Std

1000x300x700

35

0.142

0.142

0.130

BEDROOM 4:AC-TYP-02

29-37

230V 1ph

1.2 Factory Std

700x300x700

26

0.192

0.192

0.180

FAMILY ROOM:AC-TYP-05

32-38

230V 1ph

1.3 Factory Std

1000x300x700

35

0.163

0.163

0.151

BEDROOM 2:AC-TYO-02

29-37

230V 1ph

1.2 Factory Std

700x300x700

26

0.192

0.192

0.180

MASTER BEDROOM 1:AC-TYP-06 32-38

230V 1ph

1.6 Factory Std

1400x300x700

46

0.247

0.247

0.235

BEDROOM 3:AC-TYP-03

30-37

230V 1ph

1.1 Factory Std

1000x300x700

35

0.142

0.142

0.130

KITCHEN+PANTRY:AC-TYP-08

34-42

230V 1ph

3.1 Factory Std

1400x300x700

47

0.261

0.261

0.249

STAFF ROOM 1:AC-TYP-11

29-36

230V 1ph

0.4 Factory Std

795x290x238

11

0.028

STAFF ROOM 2:AC-TYP-12

34-39

230V 1ph

0.4 Factory Std

1050x290x238

14

0.020

DINING:AC-TYP-06

32-38

230V 1ph

1.6 Factory Std

1400x300x700

46

0.247

LIVING:AC-TYP-10

45-48

230V 1ph

9 Factory Std

1380x470x1100

137

0.034
0.020
0.247

0.235

Diversified capacity data at conditions as entered and 100% combination ratio


Name

TC

SC

HC

kW

kW

kW

BALCONY:AC-TYP-03

5.8

4.4

6.5

BEDROOM 4:AC-TYP-02

4.6

3.5

5.2

FAMILY ROOM:AC-TYP-05

7.2

5.5

8.4

BEDROOM 2:AC-TYO-02

4.6

3.5

5.2

MASTER BEDROOM 1:AC-TYP-06

8.7

6.6

10.4

BEDROOM 3:AC-TYP-03

5.6

4.3

6.5

15.4

10.2

14.6

STAFF ROOM 1:AC-TYP-11

2.1

1.7

2.6

STAFF ROOM 2:AC-TYP-12

3.4

2.7

4.2

DINING:AC-TYP-06

9.6

6.9

10.4

LIVING:AC-TYP-10

23.5

16.9

26.1

KITCHEN+PANTRY:AC-TYP-08

Outdoor unit placed 3.0m below the indoor units.


The minimum connection ratio for this height difference is 50%.
The Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Program.

Page 3

3. Outdoor Unit Details


3.1. Table of Abbreviations
Name

Logical name of the device

Model

Device model name

Comb

Combination percentage

Tmp C

Outdoor temperature in cooling

CC

Cooling capacity

EER

EER at selection and nominal conditions

Tmp H

Outdoor temperature in heating

HC

Heating capacity (integrated heating capacity)

COP

COP at selection and nominal conditions

Piping

Largest distance from indoor unit to outdoor unit

Bse Refr

Standard factory refrigerant charge (5m actual piping length)


excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook

Ex Refr

Extra refrigerant charge

PS

Power supply (voltage and phases)

MCA

Minimum Circuit Amps

MFA

Maximum Fuse Amps

Run Amps

Running Amps

St Curr

Starting current

Fuses

Fuses

WxHxD

WidthxHeightxDepth

Wght

Weight of the device

The Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Program.

Page 4

3.2. Outdoor Details


Name
OU-TYP-07*
Name
OU-TYP-07*

Model
RXYQ30PA
Model
RXYQ30PA

Comb

Tmp C

CC

kW

128
PS

34.0

EER

85.5

Tmp H

HC

kW

3.5 / 3.2

5.0

80.1

MCA

MFA

Run Amps

St Curr

COP
3.2 / 3.8

Piping

Bse Refr

Ex Refr

kg

kg

34.0

Fuses

400V 3Nph

20.3

7.9

WxHxD

Wght

mm

kg

2170x1680x765

* RXYQ18PA

32.5

40

24.2

85

cfr. local legislation

* RXYQ12P

22.7

25

14

75

cfr. local legislation

565

The Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Program.

Page 5

4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

4.1. Piping OU-TYP-07*


OU-TYP-07*
RXYQ30PA
RXYQ18PA

RXYQ12P

5/8"x1 1/8"

1/2"x1 1/8"

BHFQ22P1007
8.0m [3]
3/4"x1 3/8"

8.0m [1]
1/2"x1 1/8"
KHRQ22M75T

11.0m [2]
3/8"x5/8"
KHRQ22M64T
AC-TYP-03
FXSQ63P

1.0m
1/2"x1 1/8"

1.0m
1/4"x1/2"
KHRQ22M64T
AC-TYP-02
FXSQ50P

1.0m
1/2"x1 1/8"

2.0m [1]
3/8"x5/8"
KHRQ22M64T
AC-TYP-05
FXSQ80P

2.0m
3/8"x7/8"

1.0m
1/4"x1/2"
KHRQ22M29T9
AC-TYO-02
FXSQ50P

1.0m
3/8"x3/4"

7.0m [2]
3/8"x5/8"
KHRQ22M20T
AC-TYP-06
FXSQ100P
2.0m [1]
3/8"x5/8"

AC-TYP-03
FXSQ63P
5.0m
5/8"x1 1/8"

9.0m [1]
3/8"x7/8"
KHRQ22M64T

1.0m
3/8"x5/8"
KHRQ22M29T9
AC-TYP-08
FXSQ140P

1.0m
3/8"x5/8"

2.0m [1]
1/4"x1/2"
KHRQ22M20T
AC-TYP-11
FXAQ25P
1.0m [1]
1/4"x1/2"

AC-TYP-12
FXAQ40P
1.0m
1/2"x1 1/8"

2.0m [1]
3/8"x5/8"
KHRQ22M64T
AC-TYP-06
FXSQ100P
4.0m [1]
3/8"x7/8"

AC-TYP-10
FXMQ250MA

The Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Program.

Page 6

5. Wiring Diagrams
P1P2 = 16-2 AWG 2 core non screened stranded wire (non polarity wiring system)
F1F2 = 16-2 AWG 2 core non screened stranded wire (non polarity wiring system)

5.1. Wiring OU-TYP-07*


OU-TYP-07*
RXYQ30PA

AC-TYP-03
FXSQ63P
IN F1,F2

F1,F2

L,N

RXYQ18PA
Q1,Q2

33A 3Nph
RXYQ12P
Q1,Q2

AC-TYP-02
FXSQ50P

L1,L2,L3,N
F1,F2

L1,L2,L3,N
F1,F2

F1,F2
AC-TYP-06
FXSQ100P
F1,F2

F1,F2

F1,F2

F1,F2

F1,F2

F1,F2

F1,F2

BRC1E51A
1.6A 1ph
BRC1E51A
1.1A 1ph
BRC1E51A
3.1A 1ph
BRC1E51A
0.4A 1ph
BRC1E51A
0.4A 1ph

P1,P2
L,N

AC-TYP-10
FXMQ250MA

1.2A 1ph

P1,P2
L,N

AC-TYP-06
FXSQ100P

BRC1E51A

P1,P2
L,N

AC-TYP-12
FXAQ40P

1.3A 1ph

P1,P2
L,N

AC-TYP-11
FXAQ25P

BRC1E51A

P1,P2
L,N

AC-TYP-08
FXSQ140P

1.2A 1ph

P1,P2
L,N

AC-TYP-03
FXSQ63P

BRC1E51A

P1,P2
L,N

BRC1E51A
1.6A 1ph

P1,P2
L,N

22A 1ph

1.1A 1ph

P1,P2
L,N

AC-TYO-02
FXSQ50P

BRC1E51A

P1,P2
L,N

AC-TYP-05
FXSQ80P

23A 3Nph

P1,P2

BRC1E51A
9A 1ph

The Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Program.

Page 7

6. Device Options
6.1. Outdoor Unit Options
Model

Description

BHFQ22P1007 Outdoor unit multi connection piping kit for 2 outdoors

Used by
OU-TYP-07* [RXYQ30PA]

The Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Program.

Page 8