Sei sulla pagina 1di 34

CHAPTER 5

EXHAUST SYSTEMS

501.0 Scope. CLOSED COMBUSTIBLE CONSTRUCTION –


This chapter includes requirements for environ- Combustible building construction, including walls,
mental air ducts, product-conveying systems, and structural framing, roofs, roof ceilings, floors, and
commercial hoods and kitchen ventilation. floor-ceiling assemblies continuously enclosing a
grease duct on four sides where one or more sides
require protection per Section 507.2. [NFPA
Part I – Environmental Air Ducts and Product- 96:3.3.13.1]
Conveying Systems.
COMBUSTIBLE MATERIAL – Material subject to an
increase in combustibility or flame-spread rating
502.0 Definitions. beyond the limits established in the definition of
For the purposes of this chapter, the following defi- Limited-Combustible Material.
nitions apply: COMMERCIAL FOOD HEAT-PROCESSING
ACCESS PANEL – A closure device used to cover EQUIPMENT – Equipment used in a food establish-
an opening into a duct, an enclosure, equipment, or ment for heat-processing food or utensils and that
an appurtenance. [NFPA 96:3.3.1] produces grease vapors, steam, fumes, smoke, or
odors that are required to be removed through a
AIR INTAKES – An opening in a building's envelope
local exhaust ventilation system.
whose purpose is to allow outside air to be drawn
into the structure to replace inside air that is COMPENSATING HOOD – A hood that has an
removed by exhaust systems or to improve the outside-air supply with air delivered below or
quality of the inside air by providing a source of air within the hood. When makeup air is diffused
having a lower concentration of odors, suspended directly into the exhaust within the hood cavity, it
particles, or heating content. [NFPA 96:3.3.2] becomes a short-circuit hood.
AIR POLLUTION CONTROL DEVICES – Equip- CONCEALED SPACES – That portion(s) of a
ment and devices used for the purpose of cleaning building behind walls, over suspended ceilings, in
air passing through them or by them in such a pipe chases, attics, and elsewhere whose size might
manner as to reduce or remove the impurities normally range from 1-3/4 inch (44.45 mm) stud
contained therein. [NFPA 96:3.3.3] spaces to eight (8) foot (2.44 m) interstitial truss
spaces and that might contain combustible materials
APPURTENANCE – An accessory or a subordinate
such as building structural members, thermal
part that enables the primary device to perform or
and/or electrical insulation, and ducting. Such
improve its intended function. [NFPA 96:3.3.5]
spaces have sometimes been used as HVAC plenum
BAFFLE PLATE – An object placed in or near an chambers. [NFPA 96:3.3.45.1]
appliance to change the direction or retard the flow of
CONTINUOUS ENCLOSURE – A recognized archi-
air, air-fuel mixtures, or flue gases. [NFPA 96:3.3.7]
tectural or mechanical component of a building
CERTIFIED PERSON – A person trained and certi- having a fire resistance rating as required for the
fied by the equipment manufacturer, or by a recog- structure and whose purpose is to enclose the vapor
nized organization through a formal certification removal duct for its full length to its termination
program for the system to be serviced or cleaned, point outside the structure without any portion of
that is acceptable to the Authority Having Jurisdic- the enclosure having a fire resistance rating less than
tion. the required value. [NFPA 96:3.3.22.1]
CLASSIFIED – See Listed. CONTINUOUS WELD – A metal-joining method that
CLEAN(ING) – For kitchen exhaust systems and produces a product without visible interruption or
cooking equipment, the act of removing grease, oil variation in quality. For the purpose of the defini-
deposits, and other residue. [NFPA 96:3.3.11] tion, it specifically includes the exhaust compartment
CLEARLY IDENTIFIED – Capable of being recog- of hoods and welded joints of exhaust ducts, yet
nized by a person of normal vision without causing specifically does not include filter support frames or
uncertainty and indecisiveness about the location or appendages inside hoods. [NFPA 96:3.3.14]
operating process of the identified item. [NFPA COOKING APPLIANCE FLUE OUTLET – The
96:3.3.12] opening or openings in a cooking device where

41
502.0 UNIFORM MECHANICAL CODE

vapors, combustion gases, or both leave the cooking accordance with NFPA 251, Standard Methods of Tests
device. There might or might not be ductwork of Fire Endurance of Building Construction and
attached to this opening. Materials.
DAMPER – A valve or plate within a duct or its FUME INCINERATORS – Devices utilizing intense
terminal components for controlling draft or the flow heat or fire to break down and/or oxidize vapors
of gases, including air. [NFPA 96:3.3.15] and odors contained in gases or air being exhausted
DETECTION DEVICES – Electrical, pneumatic, into the atmosphere. [NFPA 96:3.3.27]
thermal, mechanical, or optical sensing instruments, FUSIBLE LINK – A form of fixed-temperature heat-
or subcomponents of such instruments, whose detecting device sometimes employed to restrain the
purpose is to cause an automatic action upon the operation of an electrical or mechanical control until
occurrence of some preselected event. In the context its designed temperature is reached. Such devices are
of this document, the event in question could be to be replaced following each operation.
excessive temperature or flame, and the action could GREASE – Rendered animal fat, vegetable short-
be the operation of a fire-extinguishing system. ening, and other such oily matter used for the
DIPS – Depression or cup like places in horizontal purposes of and resulting from cooking and/or
duct runs in which liquids could accumulate. [NFPA preparing foods. Grease might be liberated and
96:3.3.17] entrained with exhaust air or might be visible as a
DISCHARGE – The final portion of a duct or pipe liquid or solid.
where the product being conveyed is emptied or GREASE DUCTS – A containment system for the
released from confinement; the termination point of transportation of air and grease vapors that is
the pipe or duct. [NFPA 96:3.3.18] designed and installed to reduce the possibility of
the accumulation of combustible condensation and
EASILY ACCESSIBLE – See Accessible, Readily in
the occurrence of damage if a fire occurs within the
Section 203.0, Chapter 2.
system. [NFPA 96:3.3.20.2]
ENVIRONMENTAL AIR DUCT – Ducting used for
GREASE FILTER – A removable component of the
conveying air at temperatures not exceeding 250˚F
grease removal system designed to capture grease
(121˚C) to or from occupied areas of any occupancy
and direct it to a safe collection point before it enters
through other than heating or air-conditioning
a duct system. Filters are expected to minimize the
systems, such as ventilation for human usage,
projection of flames downstream when attacked by
domestic kitchen range exhaust, bathroom exhaust
flame on the upstream side and are expected to
ducts, and domestic-type clothes dryer exhaust ducts.
maintain their strength, shape, and integrity when
FACTORY-BUILT GREASE ENCLOSURES – A exposed to the anticipated rough handling, cleaning,
listed factory-built grease duct enclosure system and service found in the field.
evaluated for reduced clearances to combustibles,
GREASE FILTER, MESH–TYPE – A general-
and as an alternative to a duct with its fire-rated
purpose air filter designed to collect and retain lint
enclosure. [NFPA 96:3.3.22.2.1]
and grease from the air passing through it. This type
FIELD-APPLIED GREASE DUCT ENCLOSURES – of filter is not tested, listed, or acceptable for
A listed system evaluated for reduced clearances to commercial cooking operations due to the increased
combustibles, and as an alternative to a duct with its fire hazard.
fire-rated enclosure. [NFPA 96:3.3.22.2.2] GREASE REMOVAL DEVICES – A system of
FLAMMABLE VAPOR OR FUMES – The concentra- components designed for and intended to process
tion of flammable constituents in air that exceeds vapors, gases, and/or air as it is drawn through such
twenty-five percent (25%) of its Lower Flammability devices by collecting the airborne grease particles
Limit (LFL). and concentrating them for further action at some
FIRE BARRIER WALL – A wall assembly future time, leaving the exiting air with a lower
complying with the requirements of NFPA 221, Stan- amount of combustible matter. [NFPA 96:3.3.30]
dard for Fire Walls and Fire Barrier Walls, having a fire GREASE-TIGHT – Constructed and performing in
resistance rating of four (4) hours. such a manner as not to permit the passage of any
FIRE PARTITION – An interior wall or partition of a grease under normal cooking conditions. [NFPA
building that separates two areas and serves to 96:3.3.31]
restrict the spread of fire but does not qualify as a HIGH BROILER – See Upright Broiler.[NFPA
fire wall. 96:3.3.8.1]
FIRE RESISTANCE RATING – A relative value in HIGH LIMIT CONTROL – An operating device
minutes or hours assigned to materials or assemblies installed in and serving as an integral component of
that have withstood a fire exposure as established in a deep-fat fryer. Its purpose is the secondary limita-

42
EXHAUST SYSTEMS 502.0

tion of temperature allowed by the cooking opera- tions anticipated, will not ignite, burn, support
tion and, if that temperature is exceeded, the auto- combustion, or release flammable vapors when
matic interruption of the thermal energy input. subjected to fire or heat. Materials that are reported
[NFPA 96:3.3.32] as passing ASTM E 136, Standard Test Method for
HOOD – An air-intake device connected to a Behavior of Materials in a Vertical Tube Furnace at
mechanical exhaust system for collecting and 750°C, shall be considered noncombustible materials.
removing grease, vapors, fumes, smoke, steam, heat, [NFPA 220:3.3.4]
or odors from commercial food heat-processing OPEN COMBUSTIBLE CONSTRUCTION –
equipment. Combustible building constructions including wall,
Fixed Baffle – A listed unitary exhaust hood structural framing, roof, roof ceiling, floor, and floor
design where the grease removal device is a ceiling assemblies adjacent to a grease duct on three
nonremovable assembly that contains an inte- or fewer sides where one or more sides require
gral fire-activated water-wash fire-extinguishing protection per Section 507.2. [NFPA 96:3.3.13.2]
system listed for this purpose. [NFPA
96:3.3.33.1] PITCHED – To be fixed or set at a desired angle or
inclination. [NFPA 96:3.3.37]
Type I – is a kitchen hood for collecting and
removing grease and smoke. PRODUCT-CONVEYING DUCT – Ducting used for
conveying solid particulates, such as refuse, dust,
Type II – is a general kitchen hood for collecting
fumes, and smoke; liquid particulate matter, such as
and removing steam, vapor, heat, or odors.
spray residue, mists, and fogs; vapors, such as
INTERCONNECTED – Mutually assembled to vapors from flammable or corrosive liquids; noxious
another component in such a manner that the opera- and toxic gases; and air at temperatures exceeding
tion of one directly affects the other or that the 250ºF (121ºC).
contents of one specific duct system are allowed to
encounter or contact the products being moved by RECIRCULATING SYSTEMS – Systems for control
another duct system. [NFPA 96:3.3.34] of smoke or grease-laden vapors from commercial
cooking equipment that do not exhaust to the
LIMITED-COMBUSTIBLE MATERIAL – A building
construction material that does not comply with the outside. [NFPA 96:3.3.39]
definition of noncombustible material, that, in the REMOVABLE – Capable of being transferred to
form in which it is used, has a potential heat value another location with a limited application of effort
not exceeding 3,500 Btu/lb. (8141 kJ/kg) (see NFPA and tools. [NFPA 96:3.3.40]
259, Standard Test Method for Potential Heat of Building REPLACEMENT AIR – See Air, Makeup in Section
Materials), and that complies with either of the 203.0, Chapter 2.
following (A) or (B). Materials subject to an increase
in combustibility or flame-spread rating beyond the SALAMANDER BROILER – See Upright Broiler.
limits herein established through the effects of age, [NFPA 96:3.3.8.2]
moisture, or other atmospheric conditions shall be SECONDARY FILTRATION – Fume incinerators,
considered combustible. thermal recovery units, air pollution control devices
(A) Materials having a structural base of noncom- or other filtration media installed in ducts or hoods
bustible material, with a surfacing not exceeding located in the path of travel of exhaust products after
a thickness of 1/8 inch (3.2 mm), and with a the initial filtration.
flame-spread rating not greater than fifty (50). SHALL – Indicates a mandatory requirement.
(B) Materials in the form and thickness used, other
SINGLE HAZARD AREA – As considered in the
than as described in (A), having neither a flame-
applicable extinguishing system standard (see
spread rating greater than twenty-five (25) nor
Section 513.2) or as determined by the Authority
evidence of continued progressive combustion
and of such composition that surfaces that Having Jurisdiction.
would be exposed by cutting through the mate- SOLID COOKING FUEL – Any solid, organic,
rial on any plane would have neither a flame- consumable fuel such as briquette, mesquite, hard-
spread rating greater than twenty-five (25) nor wood, or charcoal. [NFPA 96:3.3.43]
evidence of continued progressive combustion. SOLID-FUEL COOKING EQUIPMENT – Cooking
LIQUID-TIGHT – Constructed and performing in equipment that is fired with solid cooking fuel. This
such a manner as not to permit the passage of any equipment includes ovens, tandoori charcoal pots,
liquid at any temperature. [NFPA 96:3.3.35] grills, broilers, rotisseries, barbecue pits, or any other
NONCOMBUSTIBLE MATERIAL – A material that, type of cooking equipment that derives all or part of
in the form in which it is used and under the condi- its heat source from the burning of solid cooking fuel.

43
502.0 – 504.2 UNIFORM MECHANICAL CODE

SOLVENT – A substance (usually liquid) capable of operated remote control installed at an approved
dissolving or dispersing another substance; a chem- location shall be provided to shut off fans or blowers
ical compound designed and used to convert solidi- in flammable vapor or dust systems. Electrical equip-
fied grease into a liquid or semi-liquid state in order ment used in operations that generate explosive or
to facilitate a cleaning operation. [NFPA 96:3.3.44] flammable vapors, fumes, or dusts shall be inter-
SPARK ARRESTER – A device or method that locked with the ventilation system so that the equip-
minimizes the passage of airborne sparks and ment cannot be operated unless the ventilation fans
embers into a plenum, duct, and flue. [NFPA are in operation. Motors for fans used to convey
96:3.3.46] flammable vapors or dusts shall be located outside
the duct or shall be protected with approved shields
TERMINATION – The final or intended end portion
and dustproofing. Motors and fans shall be acces-
of a duct system that is designed and functions to
sible for servicing and maintenance.
fulfill the obligations of the system in a satisfactory
manner. 503.2 Fans. Parts of fans in contact with explosive or
flammable vapors, fumes, or dusts shall be of nonfer-
THERMAL RECOVERY UNIT – A device or series of
rous or nonsparking materials or their casing shall be
devices whose purpose is to reclaim only the heat
lined or constructed of such material. When the size
content of air, vapors, gases, or fluids that are being
and hardness of materials passing through a fan
expelled through the exhaust system and to transfer
could produce a spark, both the fan and the casing
the thermal energy so reclaimed to a location
shall be of nonsparking materials. When fans are
whereby a useful purpose can be served. [NFPA
required to be spark-resistant, their bearings shall
96:3.3.47]
not be within the airstream, and all parts of the fan
TRAP – A cup like or U-shaped configuration shall be grounded. Fans in systems handling mate-
located on the inside of a duct system component rials that are likely to clog the blades, and fans in
where liquids can accumulate. [NFPA 96:3.3.49] buffing or woodworking exhaust systems, shall be of
UPRIGHT BROILER – An appliance used in the the radial-blade or tube-axial type.
preparation of food whereby foods are exposed to Equipment used to exhaust explosive or
intense radiant heat, and perhaps to convective heat, flammable vapors, fumes, or dusts shall bear an
with the food and the radiant source not limited to a identification plate stating the ventilation rate for
horizontal mode. [NFPA 96:3.3.8.3] which the system was designed.
502.1 Product-Conveying Ducts – Classification. Fans located in systems conveying corrosives
Product-conveying ducts shall be classified shall be of materials that are resistant to the corrosive
according to their use, as follows: or shall be coated with corrosion-resistant materials.
Class 1. Ducts conveying nonabrasives, such as 503.3 Air filters shall be listed units. Liquid adhesive
smoke, spray, mists, fogs, noncorrosive coatings used on filters shall have a flash point of
fumes and gases, light fine dusts, or 350˚F (177˚C) or higher, as determined by the Fire
powders. Code standards.
Class 2. Ducts conveying moderately abrasive
particulate in light concentrations, such 504.0 Environmental Air Ducts.
as sawdust and grain dust, and buffing
504.1 Makeup and Exhaust-Air Ducts. Environ-
and polishing dust.
mental air ducts not regulated by other provisions of
Class 3. Ducts conveying Class 2 materials in this code shall comply with this section. Ducts shall
high concentrations and highly abrasive be substantially airtight and shall comply with the
materials in low concentrations, such as provisions of Chapter 6. Exhaust ducts under posi-
manganese, steel chips, and coke. tive pressure shall not extend into or through ducts
Class 4. Ducts conveying highly abrasive mate- or plenums. Exhaust ducts shall terminate outside
rial in high concentrations. the building and shall be equipped with back-draft
Class 5. Ducts conveying corrosives, such as dampers. Environmental air ducts that have an alter-
acid vapors. nate function as a part of an approved smoke-control
system do not require design as Class 1
product-conveying ducts.
503.0 Motors, Fans, and Filters.
504.2 Domestic Range Vents. Ducts used for
503.1 General. Motors and fans shall be sized to domestic kitchen range ventilation shall be of metal
provide the required air movement. Motors in areas and shall have smooth interior surfaces. Ducts for
that contain flammable vapors or dusts shall be of a domestic range hoods shall only serve cooking appli-
type approved for such environments. A manually ances.

44
EXHAUST SYSTEMS 504.2 – 505.1

Exception: Ducts for domestic kitchen down- 504.3.2.2 Length Limitation. Unless other-
draft grill-range ventilation installed under a wise permitted or required by the dryer
concrete slab floor may be of approved Schedule manufacturer’s installation instructions and
40 PVC provided: approved by the Authority Having Jurisdic-
(1) The under-floor trench in which the duct is tion, domestic dryer moisture exhaust ducts
installed shall be completely backfilled with shall not exceed a total combined horizontal
sand or gravel. and vertical length of fourteen (14) feet
(4,263 mm), including two (2) 90 degree
(2) Not more than one (1) inch (25 mm) of six
(1.57 rad) elbows. Two (2) feet (610 mm)
(6) inch diameter (152 mm) PVC coupling
shall be deducted for each 90 degree (1.57
may protrude above the concrete floor
rad) elbow in excess of two.
surface.
504.3.3 Commercial Clothes Dryers. Commer-
(3) PVC pipe joints shall be solvent cemented to cial dryer exhaust ducts shall be installed in
provided an air and grease-tight duct. accordance with their listings. The installation of
(4) The duct shall terminate above grade commercial clothes dryer exhaust ducts shall
outside the building and shall be equipped comply with the appliance manufacturer’s
with a back-draft damper. installation instructions.
504.3 Clothes Dryers. 504.4 Heat (Energy) Recovery Ventilators.
504.3.1 Moisture Exhaust Ducts. Moisture 504.4.1 Heat (energy) recovery ventilators shall
exhaust ducts shall terminate on the outside of be installed in accordance with their listings and
the building and shall be equipped with a back- comply with the appliance manufacturer’s
draft damper. Screens shall not be installed at installation instructions. Heat (energy) recovery
the duct termination. Ducts for exhausting ventilator ducts shall comply with the provi-
clothes dryers shall not be connected or installed sions of Chapter 6.
with sheet metal screws or other fasteners that 504.5 Termination of Environmental Air Ducts.
will obstruct the flow. Clothes dryer moisture Environmental air duct exhaust shall terminate a
exhaust ducts shall not be connected to a gas minimum of three (3) feet (914 mm) from property
vent connector, gas vent, or chimney, and shall line and three (3) feet (914 mm) from openings into
only serve clothes dryers. Clothes dryer mois- the building.
ture exhaust ducts under positive pressure shall
504.6 Gypsum Wallboard Ducts. Bathroom and
not extend into or through ducts or plenums.
laundry room exhaust ducts may be of gypsum wall-
504.3.2 Domestic Clothes Dryers. When a board subject to the limitations of Section 602.1.
compartment or space for a domestic clothes
dryer is provided, a minimum four (4) inch
diameter (102 mm) moisture exhaust duct of 505.0 Design of Product-Conveying Ventilation
approved material shall be installed in accor- Systems.
dance with this section and Section 504.0. 505.1 General. A mechanical ventilation or exhaust
When a closet is designed for the installation system shall be installed to control, capture, and
of a clothes dryer, a minimum opening of 100 remove emissions generated from product use or
square inches (64,516 mm2) for makeup air shall handling when required by the Building Code or
be provided in the door or by other approved Fire Code and when such emissions result in a
means. hazard to life or property. The design of the system
shall be such that the emissions are confined to the
504.3.2.1 Domestic Dryer Vents. Domestic area in which they are generated by air currents,
clothes dryer moisture exhaust ducts shall hoods, or enclosures and shall be exhausted by a
be of metal and shall have smooth interior duct system to a safe location or treated by removing
surfaces. contaminant's. Ducts conveying explosives or
Exception: Listed clothes dryer transi- flammable vapors, fumes, or dusts shall extend
tion ducts not more than six (6) feet directly to the exterior of the building without
(1,829 mm) in length may be used in entering other spaces and shall not extend into or
connection with domestic dryer through ducts and plenums.
exhausts. Exception: Ducts conveying vapor or fumes
Flexible clothes dryer transition having flammable constituents less than 25
ducts shall not be concealed within percent of their Lower Flammability Limit (LFL)
construction. may pass through other spaces.

45
505.1 – Table 5-1 UNIFORM MECHANICAL CODE

505.1.1 Incompatible materials shall not be Systems for removal of vapors, gases, and smoke
conveyed in the same system. shall be designed by the constant velocity or equal
505.1.2 In systems conveying flammable vapors, friction methods. Systems conveying particulate
gases, or mists, the concentration shall not matter shall be designed employing the constant
exceed 25 percent of the lower flammability limit velocity method. Systems conveying explosive or
(LFL). radioactive materials shall be prebalanced through
duct sizing. Other systems may be designed with
Exception: Higher concentrations shall be balancing devices such as dampers. Dampers
permitted if the exhaust system is designed provided to balance airflow shall be provided with
and protected in accordance with the Stan- securely fixed minimum-position blocking devices to
dard on Explosion Prevention Systems in prevent restricting flow below the required volume
Chapter 17, using one or more of the or velocity.
following techniques:
505.3 Makeup Air. Makeup air shall be provided to
(a) Combustible concentration reduction replenish air exhausted by the ventilation system.
(b) Oxidant concentration reduction Makeup-air intakes shall be located so as to avoid
(c) Deflagration suppression recirculation of contaminated air within enclosures.
(d) Deflagration pressure containment 505.4 Hoods and Enclosures. Hoods and enclo-
sures shall be used when contaminant's originate in a
Separate and distinct systems shall be
concentrated area. The design of the hood or enclo-
provided for incompatible materials.
sure shall be such that air currents created by the
Contaminated air shall not be recirculated to exhaust systems will capture the contaminant's and
occupied areas unless contaminant's have been transport them directly to the exhaust duct. The
removed. Air contaminated with explosive or volume of air shall be sufficient to dilute explosive or
flammable vapors, fumes, or dusts; flammable flammable vapors, fumes, or dusts as set forth in
or toxic gases; or radioactive material shall not Section 505.2. Hoods of steel shall have a base metal
be recirculated. thickness not less than 0.027 inch (0.69 mm) (No. 22
505.2 Minimum Velocities and Circulation. The gauge) for Class 1 and Class 5 metal duct systems;
velocity and circulation of air in work areas shall be 0.033 inch (0.84 mm) (No. 20 gauge) for hoods
such that contaminant's are captured by an airstream serving a Class 2 duct system; 0.044 inch (1.12 mm)
at the area where the emissions are generated and (No. 18 gauge) for hoods serving a Class 3 duct
conveyed into a product-conveying duct system. system; and 0.068 inch (1.73 mm) (No. 14 gauge) for
Mixtures within work areas where contaminant's are hoods serving a Class 4 duct system.
generated shall be diluted below twenty-five (25) Approved nonmetallic hoods and duct systems
percent of their lower explosive limit or lower may be used for Class 5 corrosive systems when the
flammability limit with air that does not contain corrosive mixture is nonflammable. Metal hoods
other contaminant's. The velocity of air within the used with Class 5 duct systems shall be protected
duct shall be not less than set forth in Table 5-1. with suitable corrosion-resistant material. Edges of

TABLE 5-1
Minimum Conveying Velocities
Feet per Minute (m/s)
Vapors, gases, smoke, fumes Any
Fine light dusts, such as cotton, lint, and wood flour (100 mesh 2,000 (10.2)
and under)
Dry dusts; powders, such as fine rubber molding power, soap 2,5001 (12.7)1
dust
Industrial dusts
Average dusts, such as sawdust, grinding dust, coal dust 3,500 (17.8)
Heavy dusts, such as metal turnings, lead dusts 4,000 (20.3)
Moist dusts and chips, such as lead dust with chips, sticky buffing
lint, quick-lime dust 4,500 (22.9)
Note:
1
The velocity for aluminum and magnesium powder shall be not less than 4,000 feet per minute (20.3 m/s).

46
EXHAUST SYSTEMS 505.4 – 506.4

hoods shall be rounded. The minimum clearance 506.2 Construction. Ducts used for conveying prod-
between hoods and combustible construction shall ucts shall be of substantial airtight construction and
be the clearance required by the duct system. shall not have openings other than those required for
operation and maintenance of the system. Ducts
constructed of steel shall comply with Table 5-5 or 5-6.
506.0 Product-Conveying Ducts.
Exceptions:
506.1 Materials. Materials used in product-
conveying duct systems shall be suitable for the (1) Class 1 product-conveying ducts that
operate at less than four (4) inches (102 mm)
intended use and shall be of metal.
water column (995.6 Pa) negative pressure
Exceptions: and convey noncorrosive, nonflammable,
(1) Asbestos-cement, concrete, clay, or ceramic and nonexplosive materials at temperatures
materials may be used when it is shown that not exceeding 250˚F (121˚C) may be
these materials will be equivalent to metal constructed in accordance with Tables 6-1,
ducts installed in accordance with this 6-2, 6-3, 6-4, 6-5, 6-7, 6-8, or, with prior
chapter. approval, UMC Standard No. 6-2.
(2) Ducts serving a Class 5 system may be (2) Ducts used in central vacuuming systems
constructed of approved nonmetallic mate- within a dwelling unit shall be constructed
rial when the corrosive characteristics of the of materials in compliance with the appli-
material being conveyed make a metal cable standards referenced in Chapter 17.
system unsuitable and when the mixture Penetrations of fire-resistive walls, or
being conveyed is nonflammable. floor-ceiling or roof-ceiling assemblies shall
comply with the Building Code. Copper or
Approved nonmetallic material shall be
ferrous pipes or conduit extending from
either a listed product having a within the separation between a garage and
flame-spread index of twenty-five (25) or dwelling unit to the central vacuum unit
less and a smoke-developed rating of fifty may be used.
(50) or less on both inside and outside
The use of rectangular ducts conveying particu-
surfaces without evidence of continued
lates shall be subject to approval of the building offi-
progressive combustion, or shall have a
cial. The design of rectangular ducts shall consider
flame-spread index of twenty-five (25) or
the adhesiveness and buildup of products being
less and shall be installed with an automatic conveyed within the duct.
fire-sprinkler protection system inside the
Aluminum construction may be used in Class 1
duct.
duct systems only. The thickness of aluminum ducts
(3) Ducts used in central vacuum cleaning shall be at least two Brown and Sharpe gauges
systems within a dwelling unit shall be thicker than the gauges required for steel ducts set
constructed of materials in compliance with forth in Tables 5-5 and 5-6.
the applicable standards referenced in
506.3 Fittings. Fittings in Class 2, 3, and 4 systems
Chapter 17. Penetrations of fire walls or
shall be not less than two gauges thicker than the
floor-ceiling or roof-ceiling assemblies shall thickness required for straight runs. Flexible metallic
comply with the Building Code. duct may be used for connecting ductwork to
Copper or ferrous pipes or conduits vibrating equipment. Duct systems subject to wide
extending from within the separation temperature fluctuations shall be provided with
between a garage and dwelling unit to the expansion joints.
central vacuuming unit may be used. Branches shall connect to main ducts at the large
Aluminum ducts shall not be used in systems end of transitions at an angle not exceeding forty-
conveying flammable vapors, fumes, or explosive five (45) degrees (0.79 rad).
dusts, nor in Class 2, 3, or 4 systems. Galvanized Except for ducts used to convey noncorrosive
steel and aluminum ducts shall not be used when the vapors with no particulate, accessible cleanouts shall
temperature of the material being conveyed exceeds be provided at ten (10) foot (3,048 mm) intervals and
400˚F (205˚C). at changes in direction. Access openings shall also be
Metal ducts used in Class 5 systems that are not provided for access to sprinklers and other equip-
resistant to the corrosiveness of the product shall be ment within the duct that require servicing.
protected with appropriate corrosion-resistant mate- 506.4 Explosion Venting. Ducts conveying explo-
rial. sive dusts shall have explosion vents, openings

47
506.4 – 506.7 UNIFORM MECHANICAL CODE

protected by antiflashback swing valves, or rupture specific hazard, the clearance shall be
diaphragms. Openings to relieve explosive forces permitted to be reduced to six (6) inches
shall be located outside the building. When relief (152 mm ) from combustible materials and
devices cannot provide sufficient pressure relief, 1/2 inch (13 mm) from combustible
ductwork shall be designed to withstand an internal construction.
pressure of not less than 100 pounds per square inch Exception No. 2: When the combustible
(689 kPa). material and construction is protected by the
If a room or building contains a dust explosion use of materials or products listed for
hazard that is external to protected equipment, as protection purposes or in accordance with
defined in 2.2.3.1 of NFPA 654, such areas shall be Table 5-2.
provided with deflagration venting to a safe outside 506.7.1.1 Spacers and ties for protection
location. materials shall be of noncombustible mate-
506.5 Supports. Spacing of supports for ducts shall rial and shall not be used directly behind the
not exceed twelve (12) feet (3,658 mm) for eight (8) duct.
inch (203 mm) ducts nor twenty (20) feet (6,096 mm) 506.7.1.2 With all clearance reduction
for larger ducts, unless justified by the design. systems using a ventilated airspace, air
506.5.1 Duct supports shall be designed to carry circulation shall be provided as described in
the weight of the duct half filled with material. Table 5-2. There shall be at least one (1) inch
Where sprinkler protection is provided in the (25 mm) between the wall protector and
duct, the hanger’s design shall include the combustible walls and ceilings for clearance,
weight of the duct half filled with water or with reduction systems using a ventilated space.
the material being conveyed, whichever has the 506.7.1.3 Mineral wool batts (blanket or
higher density. Loads shall not be placed on board) shall have a minimum density of
connecting equipment. eight (8) lb./ft. 3 (3.6 kq/m 3 ) and have a
Exception: Where adequate drainage is minimum melting point of 1,500ºF (816ºC).
provided, the weight of the water shall not 506.7.1.4 Insulation board used as a part of
require consideration. a clearance-reduction system shall have a
506.5.2 Hangers and supports exposed to corro- thermal conductivity of 1 Btu in./ft.2 hrºF
sive atmospheres shall be Type 316 SS or equiva- (0.14 W/m2 hrºC) or less. Insulation board
lent. shall be formed of noncombustible material.
506.5.3 To avoid vibration and stress on the 506.7.1.5 There shall be at least one (1) inch
duct, hangers and supports shall be securely (25 mm) between the duct and the wall
fastened to the building or structure. protector. In no case shall the clearance
506.5.4 Hangers and supports shall be designed between the duct and the wall surface be
to allow for expansion and contraction. [NFPA reduced below that shown in Table 5-2.
91:4.5.6] 506.7.2 Duct systems operating at elevated
506.6 Fire Protection. Sprinklers or other temperatures above 140ºF (60ºC) shall have
fire-protection devices shall be installed within ducts clearances from combustible building construc-
having a cross-sectional dimension exceeding ten tion or any combustible material of not less than
(10) inches (254 mm) when the duct conveys eighteen (18) inch (457 mm).
flammable vapors or fumes. Sprinklers shall be 506.7.3 Where clearance is reduced by using an
installed at twelve (12) foot (3,658 mm) intervals in airspace between the combustible wall and the
horizontal ducts and at changes in direction. In wall protector, air circulation shall be provided
vertical runs, sprinklers shall be installed at the top by one of the following methods.
and at alternate floor levels. 506.7.3.1 Air circulation shall be permitted
506.7 Duct Clearances. to be provided by leaving all edges of the
506.7.1 All ductwork and system components wall protector open with at least a one (1)
handling combustible material and operating at inch (25 mm) airgap.
less than 140ºF (60ºC) shall have a clearance of 506.7.3.2 If the wall protector is mounted
not less than eighteen (18) inches (457 mm) from on a single flat wall away from corners, air
combustible construction or any combustible circulation shall be permitted to be provided
material. by one of the following:
Exception No. 1: When the ductwork (A) Leaving top and bottom edges open to
system is equipped with an approved auto- circulation by maintaining the one (1)
matic extinguishing system designed for the inch (25 mm) airgap.

48
EXHAUST SYSTEMS Table 5-2 – 506.9

TABLE 5-2
Reduction of Duct Clearance with Specified Forms of Protection
Clearance reduction applied to and covering all combustible Minimum Allowable Reduction
surfaces with the distance specified as required clearance in Clearance (%)
with no protection in 506.7.2
Form of Protection As Wall Protector As Ceiling Protector
(a) 3-1/2 in. (90 mm) thick masonry wall without ventilated airspace 33 ––
(b) 1/2 in. (13 mm) thick noncombustible insulation board over 1 in. 50 33
(25.4 mm) glass fiber or mineral wool batts without ventilated airspace
(c) 0.024 in. (0.61 mm) (No. 24 gauge) sheet metal over 1 in. (25.4 mm) glass 66 66
fiber or mineral wool batts reinforced with wire, or equivalent, on rear face
with at least a 1 in. (25.4 mm) air gap
(d) 3-1/2 in (90 mm) thick masonry wall with at least a 1 in (25.4 mm) air gap 66 ––
(e) 0.024 in. (0.61 mm) (No. 24 gauge) sheet metal with at least a 1 in. (25.4 mm) 66 50
air gap
(f) 1/2 in. (13 mm) thick noncombustible insulation board with at least a 1 in. 66 50
(25.4 mm) air gap
(g) 0.024 in. (0.61mm) (No. 24 gauge) sheet metal with ventilated airspace over 66 50
0.024 in. (0.61 mm) (No. 24 gauge) sheet metal with at least a 1 in. (25.4 mm)
air gap
(h) 1 in. (25.4 mm) glass fiber or mineral wool batts sandwiched between two 66 50
sheets 0.024 in. (0.61 mm) (No. 24 gauge) sheet metal with at least a 1 in.
(25.4 mm) air gap

Extent of protection required to reduce clearances from ducts.

(B) Leaving top and both side edges open 506.9.1 Ducts conveying explosive or flammable
to circulation by maintaining the (1) vapors, fumes, or dusts: thirty (30) feet (9,144
inch (25 mm) air gap. mm) from property line; ten (10) feet (3,048 mm)
506.7.3.3 Wall protectors that cover two from openings into the building, six (6) feet
walls in a corner shall be permitted to be (1,829 mm) from exterior walls or roofs; thirty
open at the top and bottom edges with at (30) feet (9,144 mm) from combustible walls or
least a one (1) inch (25 mm) air gap. [NFPA openings into the building that are in the direc-
91:4.6.3.3] tion of the exhaust discharge; ten (10) feet (3,048
mm) above adjoining grade.
506.8 Protection from Physical Damage. Ducts
installed in locations where they are subject to phys- 506.9.2 Other product-conveying outlets: ten
ical damage shall be protected by suitable guards. (10) feet (3,048 mm) from property line; three (3)
506.9 Exhaust Outlets. The termination point for feet (914 mm) from exterior wall or roof; ten (10)
exhaust ducts discharging to the atmosphere shall be feet (3,048 mm) from openings into the building;
not less than the following: ten (10) feet (3,048 mm) above adjoining grade.

49
Table 5-3 UNIFORM MECHANICAL CODE

TABLE 5-3
Reduction of Clearances with Specified Forms of Protection
[NFPA 54: Table 10.2.3(b)]
Where the required clearance with no protection from appliance, vent connector, or single-
wall metal pipe is:
36 in. 18 in. 12 in. 9 in. 6 in.
Allowable Clearances with Specified Protection (in.)
Type of protection applied to Use Col. 1 for clearances above appliance or horizontal connector. Use Col. 2 for clearances from
and covering surfaces of appliances, vertical connector, and single-wall metal pipe.
combustible material within
the distance specified as the Sides Sides Sides Sides Sides
required clearance with no and and and and and
protection [See Figures 5-4 Above Rear Above Rear Above Rear Above Rear Above Rear
through 5-6.] Col. 1 Col. 2 Col. 1 Col. 2 Col. 1 Col. 2 Col. 1 Col. 2 Col. 1 Col. 2

(1) 3-1/2 in. thick masonry -- 24 -- 12 -- 9 -- 6 -- 5


wall without ventilated
air space
(2) 1/2 in. insulation board 24 18 12 9 9 6 6 5 4 3
over 1 in. glass fiber or
mineral wool batts
(3) 0.024 sheet metal over 1 18 12 9 6 6 4 5 3 3 3
in. glass fiber or mineral
wool batts reinforced
with wire on rear face
with ventilated air space
(4) 3-1/2 in. thick masonry -- 12 -- 6 -- 6 -- 6 -- 6
wall with ventilated air
space
(5) 0.024 sheet metal with 18 12 9 6 6 4 5 3 3 2
ventilated air space
(6) 1/2 in. thick insulation 18 12 9 6 6 4 5 3 3 3
board with ventilated air
space
(7) 0.024 sheet metal with 18 12 9 6 6 4 5 3 3 3
ventilated air space over
0.024 sheet metal with
ventilated air space
(8) 1 in. glass fiber or 18 12 9 6 6 4 5 3 3 3
mineral wool batts sand-
wiched between two
sheets 0.024 sheet metal
with ventilated air space

Notes:
Reduction of clearances from combustible materials shall not interfere with combustion air, draft hood clearance and relief, and accessibility of
1

servicing.
Clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the appliance, disre-
2

garding any intervening protection applied to the combustible material.


Spacers and ties shall be of noncombustible material. No spacer or tie shall be used directly opposite the appliance or connector.
3

Where clearance reduction systems use a ventilated air space, adequate provision for air circulation shall be provided as described. [See Figure
4

5-5 and Figure 5-6.]


There shall be not less than one (1) in. (25 mm) between clearance reduction systems and combustible walls and ceilings for reduction systems
5

using a ventilated air space.


Where a wall protector is mounted on a single flat wall away from corners, it shall have a minimum one (1) inch (25 mm) air gap. To provide
6

adequate air circulation, the bottom and top edges, or only the side and top edges, or edges shall be left open.
Mineral wool batts (blanket or board) shall have a minimum density of eight (8) lb/ft.3 (128 kg/m3) and a minimum melting point of 1,500ºF
7

(816ºC).
Insulation material used as part of a clearance reduction system shall have a thermal conductivity of 1.0 Btu in./ft2/h-ºF (0.144 W/m-K) or less.
8

There shall be not less than (1) inch (25 mm) between the appliance and the protector. In no case shall the clearance between the appliance and
9

the combustible surface be reduced below that allowed in this table.


Clearances and thicknesses are minimum; larger clearances and thicknesses are acceptable.
10

Listed single-wall connectors shall be installed in accordance with the terms of their listing and the manufacturer’s instructions.
11

1 in. = 25.4 mm

50
EXHAUST SYSTEMS 507.0 – 507.2

Part II – Commercial Hoods and Kitchen 507.1.7 Cooking equipment used in fixed,
Ventilation. mobile, or temporary concessions, such as
trucks, buses, trailers, pavilions, tents, or any
form of roofed enclosure, shall comply with this
507.0 General Requirements.
standard unless all or part of the installation is
507.1 Cooking equipment used in processes exempted by the Authority Having Jurisdiction.
producing smoke or grease-laden vapors shall be 507.2 Clearance.
equipped with an exhaust system that complies with
507.2.1 Where enclosures are not required,
all the equipment and performance requirements of
hoods, grease removal devices, exhaust fans,
this standard, and all such equipment and perfor-
and ducts shall have a clearance of at least eigh-
mance shall be maintained per this standard during teen (18) inches (457 mm) to combustible mate-
all periods of operation of the cooking equipment. rial, three (3) inches (76 mm) to limited-
Specifically, the following equipment shall be kept in combustible material, and zero (0) inches (0 mm)
good working condition: to noncombustible material. [NFPA 96:4.2.1]
(A) Cooking equipment 507.2.2 Where a hood, duct, or grease removal
(B) Hoods device is listed for clearances less than those
(C) Ducts (if applicable) required in 507.2.1, the listing requirements shall
be permitted. [NFPA 96:4.2.2]
(D) Fans
507.2.3 Clearance Reduction.
(E) Fire suppression systems
507.2.3.1 Where a clearance reduction
(F) Special effluent or energy control equipment system consisting of 0.013 in. (0.33 mm) (28
All airflows shall be maintained. Maintenance gauge) sheet metal spaced out one (1) inch
and repairs shall be performed on all components at (25 mm) on noncombustible spacers is
intervals necessary to maintain these conditions. provided, there shall be a minimum of nine
507.1.1 Cooking equipment that has been listed (9) inches (229 mm) clearance to combustible
in accordance with UL 197 or an equivalent stan- material. [NFPA 96:4.2.3.1]
dard for reduced emissions shall not be required 507.2.3.2 Where a clearance reduction
to be provided with an exhaust system. [NFPA system consisting of 0.027 in. (0.69 mm) (22
96:4.1.1.1*] gauge) sheet metal on one (1) inch (25 mm)
507.1.2 The listing evaluation of cooking equip- mineral wool batts or ceramic fiber blanket
ment covered by Section 507.1.1 shall demon- reinforced with wire mesh or equivalent
spaced out one (1) inch (25 mm) on non-
strate that the grease discharge at the exhaust
combustible spacers is provided, there shall
duct of a test hood placed over the appliance
be a minimum of three (3) inches (76 mm)
shall not exceed 5 mg/m3 when operated with a
clearance to combustible material. [NFPA
total airflow of 0.236 cubic meters per second
96:4.2.3.2]
(500 cfm). [NFPA 96:4.1.1.2]
507.2.3.3 Zero clearance to limited-
507.1.3 The responsibility for inspection, main-
combustible materials shall be permitted
tenance, and cleanliness of the ventilation where protected by metal lath and plaster,
control and fire protection of the commercial ceramic tile, quarry tile, other non-
cooking operations shall be the ultimate respon- combustible materials or assembly of
sibility of the owner of the system provided that noncombustible materials, or materials and
this responsibility has not been transferred in products that are listed for the purpose of
written form to a management company or other reducing clearance. [NFPA 96:4.2.3.3]
party. [NFPA 96:4.1.5] 507.2.4 Clearance Integrity.
507.1.4 All solid-fuel cooking equipment shall 507.2.4.1 In the event of damage, the mate-
comply with the requirements of Section 517.0. rial or product shall be repaired and
507.1.5 Multiple-tenancy applications shall restored to meet its intended listing or clear-
require the concerted cooperation of design, ance requirements and shall be acceptable to
installation, operation, and maintenance respon- the authority having jurisdiction. [NFPA
sibilities by tenants and by the building owner. 96:4.2.4.1]
507.1.6 All interior surfaces of the exhaust 507.2.4.2 In the event of a fire within a
system shall be accessible for cleaning and kitchen exhaust system, the duct and its
inspection purposes. enclosure (rated shaft, factory-built grease

51
507.2 – 507.3 UNIFORM MECHANICAL CODE

duct enclosure, or field-applied grease duct 507.2.7.1 Measures shall be taken to prevent
enclosure) shall be inspected by qualified physical damage to any material or product
personnel to determine whether the duct used for the purpose of reducing clearances.
and protection method are structurally Exception: When the duct is protected
sound, capable of maintaining their fire
with a field-applied grease duct enclo-
protection function, and in compliance with
sure or factory-built grease duct enclo-
this standard for continued operation.
[NFPA 96:4.2.4.2] sure.
507.2.4.3 Protection shall be provided on 507.2.7.2 The specifications of material,
the wall from the bottom of the hood to the gauge, and construction of the duct used in
floor, or to the top of the noncombustible the testing and listing of field-applied grease
material extending to the floor, to the same duct enclosures and factory-built grease
level as required in 507.2.1. [NFPA duct enclosures shall be included as
96:4.2.4.3] minimum requirements in their listing and
507.2.4.4 The protection methods for ducts installation documentation. [NFPA 96:4.3.5]
to reduce clearance shall be applied to the 507.2.7.3 The following clearance options
combustible or limited-combustible construc- for which field-applied grease duct enclo-
tion, not to the duct itself. [NFPA 96:4.2.4.4] sures and factory-built grease duct enclo-
507.2.5 Factory-built grease duct enclosures sures have been successfully evaluated shall
shall be protected with a through-penetration be clearly identified in their listing and
firestop system classified in accordance with installation documentation and on their
ASTM E814 having an "F" and "T" rating equal to label: [NFPA 96:4.3.6]
the fire resistance rating of the assembly being (1) Open combustible clearance at manu-
penetrated from the point at which the duct facturer’s requested dimensions. [NFPA
penetrates a ceiling, wall or floor to the outlet 96:4.3.6(1)]
terminal, and the factory-built grease duct
protection system shall be listed in accordance (2) Closed combustible clearance at manu-
with UL 2221, Standard for Tests of Fire Resistive facturer’s requested dimensions, with or
Grease Duct Enclosure Assemblies and installed in without specified ventilation. [NFPA
accordance with the manufacturer's instructions 96:4.3.6(2)]
and the listing requirements. [NFPA 96:4.3.3, (3) Rated shaft clearance at manufacturer’s
4.3.3.1, 4.3.3.2] requested dimensions, with or without
507.2.6 Field-applied grease duct enclosures specified ventilation. [NFPA 96:4.3.6(3)]
shall be protected with a through penetration 507.2.8 A duct shall be permitted to contact
firestop system classified in accordance with noncombustible floors, interior walls, and other
ASTM E814 having an "F" and "T" rating equal to noncombustible structures or supports, but it
the fire resistance rating of the assembly being shall not be in contact for more than fifty (50)
penetrated. The surface of the field fabricated percent of its surface area per each lineal foot of
grease duct shall be continuously covered on all contact length. [NFPA 96:4.4.1]
sides from the point at which the duct enclosure
507.2.8.1 Where duct contact must exceed
penetrates a ceiling, wall or floor to the outlet
the requirements of 507.2.8, the duct shall be
terminal, and listed in accordance with ASTM E
protected from corrosion. [NFPA 96:4.4.2]
2336 Standard Test Methods for Fire resistive Grease
Duct Enclosure Systems, and installed in accor- 507.2.8.2 Where the duct is listed for zero
dance with the manufacturer's instructions and clearance to combustibles or otherwise
the listing requirements. [NFPA 96:4.3.1, 4.3.1.1, protected with a material or product listed
4.3.1.2] for the purpose of reducing clearance to
zero, the duct shall be permitted to exceed
507.2.7 Field-applied grease duct enclosures
the contact limits of 507.2.8 without addi-
and factory-built grease duct enclosures shall
tional corrosion protection. [NFPA 96:4.4.3]
demonstrate that they provide sufficient
mechanical and structural integrity, resiliency, 507.2.9 Clearances between the duct and inte-
and stability when subjected to expected rior surfaces of enclosures shall meet the
building environmental conditions, duct move- requirements of Section 507.2.
ment under general operating conditions, and 507.3 A drawing(s) of the exhaust system installa-
duct movement due to fire conditions. [NFPA tion along with a copy of operating instructions for
96:4.3.4] subassemblies and components used in the exhaust

52
EXHAUST SYSTEMS 507.3 – 508.2

system, including electrical schematics, shall be 508.2 All seams, joints, and penetrations of the hood
available on the premises. enclosure that direct and capture grease-laden
507.4 If required by the Authority Having Jurisdic- vapors and exhaust gases shall have a liquid-tight
tion, notification in writing shall be given of any continuous external weld to the hood’s lower outer-
alteration, replacement, or relocation of any exhaust most perimeter. [NFPA 96:5.1.2]
or extinguishing system or part thereof or cooking 508.2.1 Seams, joints, and penetrations of the
equipment. Satisfaction shall be provided to the hood shall be permitted to be internally welded,
Authority Having Jurisdiction that the complete provided that the weld is formed smooth or
exhaust system as addressed in this standard is ground smooth, so as to not trap grease, and is
installed and operable in accordance with the cleanable. [NFPA 96:5.1.3]
approved design and the manufacturer’s instruc- 508.2.2 Internal hood joints, seams, filter
tions. support frames, and appurtenances attached
inside the hood shall be sealed or otherwise
508.0 Hoods. made grease-tight. [NFPA 96:5.1.4]
508.1 Where Required. Hoods shall be installed at 508.2.3 Penetrations shall be permitted to be
or above all commercial-type deep fat fryers, sealed by devices that are listed for such use and
broilers, fry grills, steam-jacketed kettles, hot-top whose presence does not detract from the hood’s
ranges, ovens, barbecues, rotisseries, dishwashing or duct’s structural integrity. [NFPA 96:5.1.5]
machines, and similar equipment that produces 508.2.4 Listed exhaust hoods with or without
comparable amounts of steam, smoke, grease, or exhaust dampers shall be permitted to be
heat in a food-processing establishment. For the constructed of materials required by the listing.
purpose of this section, a food-processing establish- [NFPA 96:5.1.6]
ment shall include any building or portion thereof 508.2.5 Listed exhaust hoods with or without
used for the processing of food, but shall not include exhaust dampers shall be permitted to be assem-
a dwelling unit. bled in accordance with the listing requirements.
508.1.1 Construction. The hood or that portion [NFPA 96:5.1.7]
of a primary collection means designed for 508.2.6 Eyebrow-type hoods over gas or electric
collecting cooking vapors and residues shall be ovens shall be permitted to have a duct
constructed of and be supported by steel not less constructed as required in Section 510.0 from the
than 0.043 inch (1.09 mm) (No. 18 MSG) in thick- oven flue(s) connected to the hood canopy
ness, stainless steel not less than 0.037 inch (0.94 upstream of the exhaust plenum as shown in
mm) (No. 20 MSG) in thickness, or other Figure 5-1. [NFPA 96:5.1.8.1]
approved material of equivalent strength and 508.2.7 The duct connecting the oven flue(s) to
fire and corrosion resistance. the hood canopy shall be connected with a
Exceptions: continuous weld or have a duct-to-duct connec-
(1) Listed exhaust hoods with or without tion. [See Figure 5-6(a) through Figure 5-6(d)]
exhaust dampers. [NFPA 96:5.1.8.2]
(2) Type II hoods shall be constructed of at 508.2.8 Insulation materials other than electrical
least 0.024 inch (0.61 mm) (No. 24 gauge insulation shall have a flame spread rating of 25
steel. Hoods constructed of copper shall or less when tested in accordance with UL 723.
be of copper sheets weighing at least [NFPA 96:5.1.9]
twenty-four (24) ounces per square foot 508.2.9 Adhesives or cements used in the instal-
(7.32 kg/m2). Joints and seams shall be lation of insulating materials shall comply with
substantially tight. Solder shall not be the requirements of 508.2.8, when tested with
used except for sealing a joint or seam. the specific insulating material. [NFPA 96:5.1.10]
All hoods shall be secured in place by 508.2.10 Penetrations shall be sealed with listed
noncombustible supports. devices in accordance with the requirements of
508.1.2 Wall mounted exhaust hood assemblies 508.2.11. [NFPA 96:5.1.11]
shall be tight fitting against the back wall as to 508.2.11 Devices that require penetration of the
not permit passage of grease vapor behind the hood, such as pipe and conduit penetration
hood, or between the back wall and the hood fittings and fasteners, shall be listed in accor-
assembly. [NFPA 96:5.1.13] dance with UL 1978. [NFPA 96:5.1.12]

53
Figure 5-1 – 508.4 UNIFORM MECHANICAL CODE

D = distance in feet (mm) between the lower


lip of the hood and the cooking surface.
Q = quantity of air, in cubic feet per minute
(L/s).
When cooking equipment is installed
back to back and is covered by a common
island-type hood, the airflow required may
be calculated using the formula for three
sides exposed. Type II hood airflow require-
ments shall be in accordance with the
requirements for low-temperature appliance
hoods.
508.4.1.2 The minimum airflow for solid-
fuel cooking equipment, grease-burning
charbroilers, and undefined equipment shall
be:
Number of Exposed Sides Formula
FIGURE 5-1 Typical Section of Eyebrow-Type 4 (island or central hood) Q = 300A
Hood. [NFPA 96:5.1.8.1] 3 or less Q = 200A
Alternate formula Q = 100PD
508.3 Insulation materials other than electrical insu-
lation shall have a flame-spread rating of twenty-five 508.4.1.3 Type I hoods when the cooking
(25) or less when tested in accordance with UL 723, equipment includes high-temperature appli-
Standard for Test for Surface Burning Characteristics of ances such as deep-fat fryers:
Building Materials. Adhesives or cements used in the Number of Exposed Sides Formula
installation of insulating materials shall comply with 4 (island or central hood) Q = 150A
the preceding requirements when tested with the
3 or less Q = 100A
specific insulating material.
Alternate formula Q = 100PD
508.4 Hood Size. Hoods shall be sized according to
the following calculations and configured to provide 508.4.1.4 Type I hoods where the cooking
for the capture and removal of grease-laden vapors. equipment includes medium-temperature
(See Section 511.2.3) appliances such as rotisseries, grills, and
508.4.1 Canopy Size and Location. For ranges:
canopy-type commercial cooking hoods, the Number of Exposed Sides Formula
inside edge thereof shall overhang or extend a 4 (island or central hood) Q = 100A
horizontal distance of not less than six (6) inches
3 or less Q = 75A
(152 mm) beyond the edge of the cooking
surface on all open sides, and the vertical Alternate formula Q = 50PD
distance between the lip of the hood and the 508.4.1.5 Type I hoods where the cooking
cooking surface shall not exceed four (4) feet equipment includes low-temperature appli-
(1,219 mm). ances such as medium-to-low-temperature
Exception: Listed exhaust hoods are to be ranges, roasters, roasting ovens, pastry
installed in accordance with the terms of ovens, and equipment approved for use
their listings and the manufacturer’s instal- under a Type II hood, such as pizza ovens:
lation instructions.
Number of Exposed Sides Formula
508.4.1.1 Capacity of Hoods. Canopy-type
commercial cooking hoods shall exhaust 4 (island or central hood) Q = 75A
through the hood a minimum quantity of air 3 or less Q = 50A
determined by application of the following Alternate formula Q = 50PD
formulas:
Exception: Listed exhaust hoods are to
WHERE: be installed in accordance with the
A = the horizontal surface area of the hood, terms of their listing and the manufac-
in square feet (m2). turer’s installation instructions.
P = that part of the perimeter of the hood 508.4.2 Capacity for Noncanopy Hoods. In
that is open, in feet (mm). addition to all other requirements for hoods

54
EXHAUST SYSTEMS 508.4 – 509.2

specified in this section, the volume of air 508.8 Listed Ultra-Violet Hoods. Listed ultra-violet
exhausting through a noncanopy-type hood to hoods shall be installed and maintained in accor-
the duct system shall be not less than 300 cubic dance with the terms of their listing and the manu-
feet per minute per lineal foot (465 L/s per m) of facturer’s instructions. [NFPA 96:5.5]
cooking equipment. Listed noncanopy exhaust 508.9 Exhaust Outlets. An exhaust outlet within an
hoods and filters shall be sized and installed in unlisted hood shall be located so as to optimize the
accordance with the terms of their listing and the capture of particulate matter. Each outlet shall serve
manufacturer’s installation instructions. not more than a twelve (12) foot (3,658 mm) section
Exception: Listed hood assemblies designed of an unlisted hood.
and installed specifically for the intended
use.
509.0 Grease Removal Devices in Hoods.
508.5 Exhaust Hood Assemblies with Integrated
509.1 Grease Removal Devices. Listed grease
Supply-Air Plenums.
filters, baffles, or other approved grease removal
508.5.1 The construction and size of exhaust devices for use with commercial cooking equipment
hood assemblies with integrated supply air shall be provided. Listed grease filters shall be tested
plenums shall comply with the requirements of in accordance with UL 1046, Grease Filters for
Sections 508.1 and 508.4. [NFPA 96:5.3.1] Exhaust Ducts. Mesh filters shall not be used.
508.5.2 The construction of the outer shell or the 509.2 Installation.
inner exhaust shell shall comply with Section
509.2.1 The distance between the grease
508.1. [NFPA 96:5.3.2]
removal device and the cooking surface shall be
508.5.3 Where the outer shell is welded, the as great as possible but not less than eighteen
inner shell shall be of grease-tight construction. (18) inches (457 mm). [NFPA 96:6.2.1.1]
[NFPA 96:5.3.3]
509.2.2 Where grease removal devices are used
508.5.4 Fire Dampers. in conjunction with charcoal or charcoal-type
508.5.4.1 A fire-actuated damper shall be broilers, including gas or electrically heated
installed in the supply air plenum at each charbroilers, a minimum vertical distance of four
point where a supply air duct inlet or a (4) feet (1,219 mm) shall be maintained between
supply air outlet penetrates the continu- the lower edge of the grease removal device and
ously welded shell of the assembly. [NFPA the cooking surface. [NFPA 96:6.2.1.2]
96:5.3.4.1] Exception No. 1: Grease removal devices
508.5.4.2 The fire damper shall be listed for supplied as part of listed hood assemblies
such use or be part of a listed exhaust hood shall be installed in accordance with the
with or without exhaust damper. [NFPA terms of the listing and the manufacturer’s
96:5.3.4.2] instructions. [NFPA 96:6.2.1.5]
508.5.4.3 The actuation device shall have a Exception No. 2: For cooking equipment
maximum temperature rating of 141°C without exposed flame and where flue gases
(286°F). [NFPA 96:5.3.4.3] bypass grease removal devices, the
508.5.5 Supply air plenums that discharge air minimum vertical distance shall be
from the face rather than from the bottom or into permitted to be reduced to not less than six
the exhaust hood and that are isolated from the (6) inches (152 mm). [NFPA 96:6.2.1.3]
exhaust hood by the continuously welded shell Exception No. 3: Where a grease removal
extending to the lower outermost perimeter of device is listed for separation distances less
the entire hood assembly shall not require a fire- than those required in 509.2.1 and 509.2.2,
actuated damper. [NFPA 96:5.3.4.4] the listing requirements shall be permitted.
508.6 Listed Hood Assemblies. Listed hood assem- [NFPA 96:6.2.1.4]
blies shall be installed in accordance with the terms 509.2.3 Grease Removal Device Protection.
of their listing and the manufacturer’s instructions. Grease removal devices shall be protected from
[NFPA 96:5.4.1] Listed hood assemblies shall be combustion gas outlets and from direct flame
tested in accordance with UL 710 or equivalent. impingement occurring during normal opera-
[NFPA 96:5.4.2] tion of cooking appliances producing high flue
508.7 Solid-Fuel Hood Assemblies. Where solid- gas temperatures, such as deep-fat fryers or
fuel cooking equipment is to be used, the solid-fuel upright or high broilers (salamander broilers),
hood assembly shall comply with Section 517.0. where the distance between the grease removal

55
509.2 – 510.3 UNIFORM MECHANICAL CODE

device and the appliance flue outlet (heat 510.1.2 All ducts shall lead as directly as is prac-
source) is less than eighteen (18) inches (457 ticable to the exterior of the building, so as not to
mm). [NFPA 96:6.2.2.1] unduly increase any fire hazard.
509.2.3.1 This protection shall be permitted 510.1.3 Duct systems shall not be interconnected
to be accomplished by the installation of a with any other building ventilation or exhaust
steel or stainless steel baffle plate between system.
the heat source and the grease removal 510.1.4 All ducts shall be installed without
device. [NFPA 96:6.2.2.2] forming dips or traps that might collect residues.
509.2.3.2 The baffle plate shall be sized and In manifold (common duct) systems, the lowest
located so that flames or combustion gases end of the main duct shall be connected flush on
shall travel a distance not less than eighteen the bottom with the branch duct. Duct systems
(18) inches (457 mm) from the heat source to serving a Type I hood shall be so constructed
the grease removal device. [NFPA 96:6.2.2.3] and installed that grease cannot become pock-
509.2.3.3 The baffle shall be located not less eted in any portion thereof, and the system shall
than six (6) inches (152 mm) from the grease slope not less than 1/4 inch per lineal foot (21
removal devices. [NFPA 96:6.2.2.4] mm/m) toward the hood or toward an
approved grease reservoir. Where horizontal
509.2.4 Grease Filters. Grease filters shall be
ducts exceed seventy-five (75) feet (22,860 mm)
listed and constructed of steel or listed equiva-
in length, the slope shall be not less than one (1)
lent material and shall be of rigid construction
inch per lineal foot (83 mm/m).
that will not distort or crush under normal oper-
ation, handling, and cleaning conditions. [NFPA 510.1.5 Openings required for accessibility shall
96:6.2.3.1 and 6.2.3.2] comply with Section 510.3.
509.2.4.1 Filters shall be tight fitting and 510.1.6 A sign shall be placed on all access
firmly held in place and grease filters shall panels stating the following:
be arranged so that all exhaust air passes ACCESS PANEL––DO NOT OBSTRUCT
through the grease filters. [NFPA 96:6.2.3.3] 510.1.7 Duct bracing and supports shall be of
509.2.4.2 Filters shall be easily accessible and noncombustible material, securely attached to
removable for cleaning. [NFPA 96:6.2.3.4] the structure and designed to carry gravity and
509.2.4.3 Filters shall be installed at an lateral loads within the stress limitations of the
angle not less than forty-five (45) degrees Building Code. Bolts, screws, rivets, and other
from the horizontal. [NFPA 96:6.2.3.5] mechanical fasteners shall not penetrate duct
509.2.5 Grease Drip Trays. Filters shall be walls.
equipped with a drip tray beneath their lower 510.1.8 Ducts, Non-Grease. Ducts and
edges. [NFPA 96:6.2.4.1] plenums serving Type II hoods shall be
509.2.5.1 The tray shall be kept to the constructed of rigid metallic materials as set
minimum size needed to collect grease and forth in Chapter 6. Duct bracing and supports
shall comply with Chapter 6. Ducts subject to
shall be pitched to drain into an enclosed
positive pressure shall be adequately sealed.
metal container having a capacity not
exceeding one (1) gallon (3.785 L) [NFPA 510.2 Clearance.
96:6.2.4.2, and 6.2.4.3]. 510.2.1 Clearance between ducts and
509.2.6 Grease Filter Orientation. Grease filters combustible materials shall be provided in accor-
that require a specific orientation to drain grease dance with the requirements of Section 507.2.
shall be clearly so designated, or the hood shall 510.2.2 Listed grease ducts shall be installed in
be constructed so that filters cannot be installed accordance with the terms of their listings and
in the wrong orientation. [NFPA 96:6.2.5] manufacturers’ instructions.
509.3 Solid-Fuel Grease Removal Devices. 510.3 Openings.
Where solid-fuel cooking equipment is provided
510.3.1 Openings shall be provided at the sides
with grease removal devices, these devices shall
or at the top of the duct, whichever is more
comply with Section 517.0.
accessible, and at changes of direction. Openings
shall be protected by approved access panels
510.0 Exhaust Duct Systems. that comply with Section 510.3.4.5.
510.1 General. Exception: Openings shall not be required
510.1.1 Ducts shall not pass through fire walls in portions of the duct that are accessible
or fire partitions. from the duct entry or discharge.

56
EXHAUST SYSTEMS 510.3 – 510.5

510.3.2 For hoods with dampers in the exhaust 510.3.4.4 Access Panels. Access panels
or supply collar, an access panel for cleaning and shall be of the same material and thickness
inspection shall be provided in the duct or the as the duct (Section 510.5.1). Access panels
hood collar. This access panel shall be as close to shall have a gasket or sealant that is rated
the hood as possible but shall not exceed eigh- for 1,500°F (815.6°C) and shall be grease-
teen (18) inches (457 mm). tight. Fasteners, such as bolts, weld studs,
Exception: Dampers that are accessible from latches, or wing nuts, used to secure the
under the hood. access panels shall be carbon steel or stain-
less steel and shall not penetrate duct walls.
510.3.3 Exhaust fans with ductwork connected
to both sides shall have access for cleaning and Exception: Listed grease duct access
inspection within three (3) feet (914 mm) of each door assemblies (access panels) shall be
side of the fan. [NFPA 96:7.3.7] installed in accordance with their terms
510.3.4 Openings in Ducts. Openings shall of the listings and the manufacturer's
conform with Sections 510.3.4.1 through instructions.
510.3.4.5. [NFPA 96:7.4] 510.3.4.5 Openings for installation,
510.3.4.1 Horizontal Ducts. On horizontal servicing, and inspection of listed fire
ducts, at least one 20 inch by 20 inch (508 protection system devices and for duct
mm x 508 mm) opening shall be provided cleaning shall be provided in ducts and
for personnel entry. [NFPA 96:7.4.1.1] enclosures and shall conform to the require-
ments of 510.3. Enclosure openings required
510.3.4.1.1 Horizontal ducting shall be
to reach access panels in the ductwork shall
secured sufficiently to allow for the
be large enough for the removal of the
weight of personnel entry into the duct.
access panel.
Where an opening of this size is not
possible, openings large enough to 510.4 Listed Grease Ducts. Listed grease ducts
permit thorough cleaning shall be shall be installed in accordance with the terms of the
provided at twelve (12) feet (3,658 mm) listing and the manufacturer’s instructions.
intervals. [NFPA 96:7.4.1.2] 510.5 Other Grease Ducts. Other grease ducts shall
510.3.4.1.2 Openings on horizontal comply with the requirements of this section.
grease duct systems shall be provided 510.5.1 Materials. Ducts shall be constructed of
with safe access and a work platform and supported by carbon steel not less than
when not easily accessible from a 10 feet 0.054 inch (1.37 mm) (No. 16 MSG) in thickness
(3 m) stepladder. [NFPA 96:7.4.1.3] or stainless steel not less than 0.043 inch (1.09
mm) (No. 18 MSG) in thickness.
510.3.4.1.3 Support systems for hori-
zontal grease duct systems twenty-four 510.5.2 Installation.
(24) inches (609 mm) and larger in any 510.5.2.1 All seams, joints, penetrations, and
cross-sectional dimension shall be duct-to-hood collar connections shall have a
designed for the weight of the ductwork liquid-tight continuous external weld.
plus 363 kg (800 lb) at any point in the Exception No. 1: Duct-to-hood collar
duct systems. [NFPA 96:7.4.1.4] connections as shown in Figure 5-2 shall
510.3.4.2 On nonlisted ductwork, the edge be permitted.
of the opening shall be not less than 1-1/2 Exception No. 2: Penetrations shall be
inch (38.1 mm) from all outside edges of the permitted to be sealed by other listed
duct or welded seams. [NFPA 96:7.4.1.5] devices that are tested to be grease-tight
510.3.4.3 Vertical Ducts. On vertical duct- and are evaluated under the same
work where personnel entry is possible, conditions of fire severity as the hood or
access shall be provided at the top of the enclosure of listed grease extractors and
vertical riser to accommodate descent. whose presence does not detract from
[NFPA 96:7.4.2.1] the hood's or duct's structural integrity.
510.3.4.3.1 Where personnel entry is Exception No. 3: Internal welding shall
not possible, adequate access for be permitted, provided the joint is
cleaning shall be provided on each formed or ground smooth and is readily
floor. [NFPA 96:7.4.2.2] accessible for inspection.

57
Figure 5-2 – 510.7 UNIFORM MECHANICAL CODE

FIGURE 5-2 Permitted Duct-to-Hood Collar


Connection. [NFPA 96:7.5.2.2]
510.5.2.2 Overlapping duct connections of
either the telescoping or the bell type shall be
used for welded field joints, not butt-weld
connections. The inside duct section shall
always be uphill of the outside duct section.
The difference between inside dimensions of
overlapping sections shall not exceed 1/4
inch (6.4 mm). The overlap shall not exceed
two (2) inches (50.8 mm). (See Figure 5-3.)
510.6 Exterior Installations. FIGURE 5-3 Telescoping and Bell-Type Duct
510.6.1 The exterior portion of the ductwork Connections. [NFPA 96:7.5.5.1(a)(b)]
shall be vertical wherever possible and shall
be installed and adequately supported on the required by the applicable Building Code provi-
exterior of a building. Bolts, screws, rivets, sions. The enclosure shall be sealed around the
and other mechanical fasteners shall not duct at the point of penetration of the lowest fire-
penetrate duct walls. Clearance of any ducts rated ceiling or floor above the hood in order to
shall comply with Section 507.2. maintain the fire resistance rating of the enclosure
and shall be vented to the exterior of the building
510.6.2 All ducts shall be protected on the
through weather-protected openings.
exterior by paint or other suitable weather-
Exception: The continuous enclosure provi-
protective coating or shall be constructed of sions shall not be required where a field-
noncorrosive stainless steel. Ductwork applied grease duct enclosure or a factory-
subject to corrosion shall have minimal built grease duct enclosure (see Section
contact with the building surface. 507.2.3) is protected with a listed duct-
510.7 Interior Installations. through-penetration protection system
510.7.1 In all buildings more than one story in equivalent to the fire resistance rating of the
height, and in one-story buildings where the roof- assembly being penetrated, and the materials
ceiling assembly is required to have a fire resis- are installed in accordance with the condi-
tance rating, the ducts shall be enclosed in a tions of their listings and the manufacturers’
continuous enclosure extending from the lowest instructions and are acceptable to the
fire-rated ceiling or floor above the hood, through Authority Having Jurisdiction.
any concealed spaces, to or through the roof so as 510.7.2 The enclosure required in Section 510.7.1
to maintain the integrity of the fire separations shall conform to Sections 510.7.2.1 through 510.7.2.3.

58
EXHAUST SYSTEMS 510.7 – 510.8

510.7.2.1 If the building is less than four 510.7.3.3 In the event of a fire within a
stories in height, the enclosure wall shall kitchen exhaust system, the duct, the enclo-
have a fire resistance rating of not less than sure, or the covering directly applied to the
one (1) hour. duct shall be inspected by qualified
personnel to determine whether the duct,
510.7.2.2 If the building is four stories or
the enclosure, and the covering directly
more in height, the enclosure wall shall have
applied to the duct are structurally sound,
a fire resistance rating of not less than two
capable of maintaining their fire protection
(2) hours.
functions, suitable for continued operation,
510.7.2.3 Clearance from the duct or the and acceptable to the Authority Having
exhaust fan to the interior surface of enclo- Jurisdiction.
sures of combustible construction shall be not 510.7.4 For listed grease ducts, see Section 510.4.
less than eighteen (18) inches (457 mm), and
510.7.5 If openings in the enclosure walls are
clearance from the duct to the interior surface
provided, they shall be protected by approved
of enclosures of noncombustible or limited-
self-closing fire doors of proper rating. Fire
combustible construction shall be not less doors shall be installed in accordance with
than six (6) inches (152 mm). Provisions for NFPA 80, Standard for Fire Doors and Fire
reducing clearances as described in Section Windows. Openings on other listed materials or
507.2 are not applicable to enclosures. products shall be clearly identified and labeled
Exception: Clearance from the outer according to the terms of the listing and the
surfaces of field-applied grease duct manufacturer's instructions and shall be accept-
enclosures and factory-built grease duct able to the Authority Having Jurisdiction. The
enclosures to the interior surfaces of panels shall be readily accessible.
construction installed around them shall 510.7.6 Each duct system shall constitute an
be permitted to be reduced where the individual system serving only exhaust hoods in
field-applied grease duct enclosure one fire zone on one floor. Multiple ducts shall
materials and the factory-built grease not be permitted in a single enclosure unless
duct enclosures are installed in accor- acceptable to the Authority Having Jurisdiction.
dance with the conditions of their list- 510.8 Termination of Exhaust System.
ings and the manufacturers’ instruc- 510.8.1 The exhaust system shall terminate as
tions and are acceptable to the follows:
Authority Having Jurisdiction.
(A) Outside the building with a fan or duct.
510.7.3 For field-applied grease duct enclosures (B) Through the roof, or to the roof from
and factory-built grease duct enclosures, the outside, as in Section 510.8.2, or through a
materials and products shall conform to Sections wall, as in Section 510.8.3.
510.7.3.1 through 510.7.3.3.
510.8.2 Rooftop Terminations.
510.7.3.1 Field-applied grease duct enclo-
510.8.2.1 Rooftop terminations shall be
sures and factory-built grease duct enclo-
arranged with or provided with the
sures shall demonstrate that they provide following:
sufficient mechanical and structural
(A) A minimum of ten (10) feet (3,048 mm)
integrity, resiliency, and stability when
of clearance from the outlet to adjacent
subjected to expected building environ-
buildings, property lines, and air
mental conditions, duct movement under
intakes. Where space limitations abso-
general operating conditions, and duct
lutely prevent a ten (10) foot (3,048 mm)
movement due to interior and exterior fire horizontal separation from an air intake,
conditions. a vertical separation shall be permitted,
510.7.3.2 Measures shall be taken to prevent with the exhaust outlet being a
physical damage to any covering or enclo- minimum of three (3) feet (914 mm)
sure material. Any damage to the covering above any air intake located within ten
or enclosure shall be repaired and the (10) feet (3,048 mm) horizontally.
covering or enclosure restored to meet its (B) The exhaust flow directed up and away
intended listing and fire-resistive rating and from the surface of the roof and a
to be acceptable to the Authority Having minimum of forty (40) inches (1,016
Jurisdiction. mm) above the roof surface.

59
510.8 – 511.1 UNIFORM MECHANICAL CODE

(C) The ability to drain grease out of any feet (0.076m) for each one (1) degree
traps or low points formed in the fan or from horizontal, the angle of degree
duct near the termination of the system being measured from the center of the
into a collection container that is exhaust termination to the center of the
noncombustible, closed, rainproof, struc- air intake or operable door or window.
turally sound for the service to which it (See Figure 5-4.)
is applied, and will not sustain combus- Exception: A wall termination in a
tion. A grease collection device that is secured area can be at a lower
applied to exhaust systems shall not height above grade if acceptable to
inhibit the performance of any fan. the Authority Having Jurisdiction.
Exception: Grease containers that (B) The exhaust flow directed perpendicu-
are evaluated for equivalency with larly outward from the wall face or
the preceding requirements and upward.
listed as such. (C) All the ductwork pitched to drain the
(D) A listed grease duct complying with grease back into the hood(s), or with a
Section 510.4, or with ductwork drain provided to bring the grease back
complying with Section 510.5. into a container within the building or
(E) A hinged upblast fan supplied with flex- into a remote grease trap.
ible weatherproof electrical cable and (D) A listed grease duct complying with
service hold-open retainer to permit Section 510.4, or other ducts complying
proper inspection and cleaning that is with Section 510.5.
listed for commercial cooking equip- (E) An approved fan, provided it meets the
ment, provided the ductwork extends a requirements of Sections 510.8.3.1(C)
minimum of eighteen (18) inches (457 and 511.1.1 or 511.1.3.
mm) above the roof surface and the fan
discharges a minimum of forty (40) 510.9 Solid-Fuel Duct Systems. Where solid-fuel
inches (1,016 mm) above the roof surface. cooking equipment is to be vented, the duct system
(See Section 511.1.1.) shall comply with Section 517.0.
(F) Other approved fan, provided (1) it
meets the requirements of Sections 511.0 Air Movement.
510.8.2(C) and 511.1.3, and (2) its 511.1 Exhaust Fans for Commercial Cooking
discharge or its extended duct discharge Equipment.
meets the requirements of Section Where solid-fuel cooking equipment is to be vented,
510.8.2(B). the duct system shall comply with Section 517.0.
510.8.2.2 Listed flexible connectors may be 511.1.1 Approved upblast fans with motors
used on exterior roof locations when required surrounded by the airstream shall be hinged,
for proper equipment vibration isolation. supplied with flexible weatherproof electrical
510.8.2.3 Fans shall be provided with safe cable and service hold-open retainers, and listed
access and a work surface for inspection and for this use. (See Figure 5-5.) Installation shall
cleaning. [NFPA 96:7.8.2.2] conform to the requirements of Section 510.8.
510.8.3 Wall Terminations. 511.1.2 In-Line Exhaust Fans.
510.8.3.1 Wall terminations shall be 511.1.2.1 In-line fans shall be of the type
arranged with or provided with the with the motor located outside the airstream
following properties:
and with belts and pulleys protected from
(A) Through a noncombustible wall with a the airstream by a grease-tight housing. They
minimum of ten (10) feet (3,048 mm) of shall be connected to the exhaust duct by
clearance from the outlet to adjacent flanges securely bolted as shown in Figures
buildings, property lines, grade level, 5-6(a) – 5-6(d), or by a system specifically
combustible construction, or electrical
listed for such use. Flexible connectors shall
equipment or lines, and the closest point
not be used. [NFPA 96:8.1.2.1 – 8.1.2.3]
of any air intake or operable door or
window at or below the plane of the 511.1.2.2 If the design or positioning of the
exhaust termination. The closest point fan allows grease to be trapped, a drain
of any air intake or operable door or directed to a readily accessible and visible
window above the plane of the exhaust grease receptacle, not exceeding one (1) gallon
termination shall be a minimum of ten (3.8 L), shall be provided. In-line exhaust fans
(10) feet (3,048 mm) distant, plus 0.25 shall be located in an easily accessible area of

60
EXHAUST SYSTEMS Figure 5-4 – 511.2

511.1.3 Utility set exhaust fans, if installed at the


rooftop termination point, shall meet the require-
ments of Sections 510.8.2.1(A) and Section
510.8.2.3. If the fan is installed within the
building, it shall be located in an easily accessible
area of adequate size to allow for service or
removal. If the duct system connected to the fan is
in an enclosure, the space or room in which the
exhaust fan is located shall have the same fire
resistance rating as the enclosure. The fan shall be
connected to the exhaust duct by flanges securely
bolted as shown in Figures 5-6(a) through 5-6(d)
or by a system specifically listed for such use.
Flexible connectors shall not be used. Exhaust
fans shall have a drain directed to a readily acces-
sible and visible grease receptacle not to exceed
one (1) gallon (3.8 L). [NFPA 96:8.1.3.1 - 8.1.3.6]
511.1.4 Exhaust fan housings shall be constructed
of carbon steel not less than 0.054 inch (1.37 mm)
(No. 16 MSG) in thickness or stainless steel not
less than 0.043 inch (1.09 mm) (No. 18 MSG) in
thickness or, if listed, constructed in accordance
with the terms of the listing. [NFPA 96:8.1.4]
511.1.5 Openings for cleaning, servicing, and
inspection shall conform to the requirements of
Section 510.3.3. Clearances shall conform to the
requirements of Sections 507.2, or 510.7.2.3 if
installed within an enclosure.
FIGURE 5-4 Exhaust Termination Distance from 511.1.6 All wiring and electrical equipment shall
Fresh Air Intake (FAI) or Operable Door or Window. comply with NFPA 70, National Electrical Code.
[NFPA 96:7.8.3]
511.2 Airflow.
511.2.1 The air velocity through any duct shall
be not less than 500 feet per minute (152.4 meters
per minute). [NFPA 96:8.2.1.1]
Exception: Transition duct sections shall be
permitted to be connected to hoods and
exhaust fans that do not meet this velocity,
provided that they do not exceed three (3)
feet (914 mm) in length and do not contain
traps for grease.
511.2.2 Transition duct sections that do not
exceed three (3) feet (914 mm) in length and do
not contain grease traps shall be permitted to be
connected to hoods and exhaust fans that do not
FIGURE 5-5 Upblast Fan Clearances. [NFPA meet this velocity. [NFPA 96:8.2.1.2]
96:7.8.2.1]
511.2.3 Exhaust-air volumes for hoods shall be
of sufficient level to provide for capture and
adequate size to allow for service or removal.
removal of grease-laden cooking vapors. Test
If the duct system connected to the fan is in an
data, performance acceptable to the Authority
enclosure, the space or room in which the
Having Jurisdiction, or both, shall be provided,
exhaust fan is located shall have the same fire
displayed, or both, upon request. [NFPA
resistance rating as the enclosure. [NFPA
96:8.2.2.1, 8.2.2.2]
96:8.1.2.4 – 8.1.2.6]

61
Figure 5-6(a) – 511.4 UNIFORM MECHANICAL CODE

FIGURE 5-6(d) Typical Section of Duct-to-Fan


Connection–Direct to Fan Inlet Cone Method.
FIGURE 5-6(a) Typical Section of Duct-to-Fan [NFPA 96:8.1.2.2(d)]
Connection–Butt Joint Method. [NFPA
96:8.1.2.2(a)] Exception: Lower exhaust-air volumes shall
be permitted during no-load cooking condi-
tions, provided they are sufficient to capture
and remove flue gases and residual vapors
from cooking equipment.
511.2.4 A hood exhaust fan(s) shall continue to
operate after the extinguishing system has been
activated, unless fan shutdown is required by a
listed component of the ventilation system or by
the design of the extinguishing system. It shall
not be required to restart the hood exhaust fan
when the extinguishing system is activated if the
exhaust fan and all cooking equipment served
by the fan had previously been shut down. The
hood exhaust fan shall not be required to start
upon activation of the extinguishing system if
the exhaust fan and all cooking equipment
FIGURE 5-6(b) Typical Section of Duct-to-Fan served by the fan have previously been shut
Connection–Overlapping Method. [NFPA 96: down. [NFPA 96:8.2.3.1 - 8.2.3.2]
8.1.2.2(b)] 511.3 Replacement Air. Replacement air quantity
shall be adequate to prevent negative pressures in
the commercial cooking area(s) from exceeding 0.02
inch water column (4.98 kPa). When its fire-extin-
guishing system discharges, makeup air supplied
internally to a hood shall be shut off. [NFPA 96:8.3.1
- 8.3.2]
Exception: Compensating hoods shall meet the
airflow requirements specified in Sections
508.4.1.3 through 508.4.1.5. Compensating hoods
shall extract at least 20 percent of their required
exhaust airflow from the kitchen area.
511.4 Common Duct (Manifold) Systems.
511.4.1 Master kitchen exhaust ducts that serve
FIGURE 5-6(c) Typical Section of Duct-to-Fan multiple tenants shall include provision to bleed
Connection–Sealant Method. [NFPA 96: air from outdoors or from adjacent spaces into
8.1.2.2(c)] the master exhaust duct where required to main-

62
EXHAUST SYSTEMS 511.4 – 513.1

tain the necessary minimum air velocity in the 512.2.5 Listed lighting units specifically listed
master exhaust duct. [NFPA 96:8.4.1] for such use and installed in accordance with the
511.4.2 The bleed-air ducts shall connect to the terms of the listing shall be permitted to be
top or side of the master exhaust duct. [NFPA installed in concealed spaces. [NFPA 96:9.2.3.4]
96:8.4.2] 512.2.6 All electrical equipment shall be
511.4.3 The bleed-air duct shall have a fire installed in accordance with NFPA 70, National
damper at least twelve (12) inches (305 mm) from Electrical Code, with due regard to the effects of
the exhaust duct connection. [NFPA 96:8.4.3] heat, vapor, and grease on the equipment.
511.4.4 The bleed-air duct shall have the same 512.3 Other Equipment.
construction and clearance requirements as the 512.3.1 Fume incinerators, thermal recovery
main exhaust duct from the connection to the units, air pollution control devices, or other
exhaust duct to at least twelve (12) inches (305 devices shall be permitted to be installed in
mm) on both sides of the fire damper. [NFPA ducts or hoods or located in the path of travel of
96:8.4.4]
exhaust products where specifically approved
511.4.5 Each bleed air duct shall have a means for such use. Downgrading other parts of the
of adjusting (e.g., using volume dampers) the exhaust system due to the installation of these
bleed-air quantity. [NFPA 96:8.4.5] approved devices, whether listed or not, shall
511.4.6 Such means to adjust the bleed air quality not be allowed. [NFPA 96:9.3.1 - 9.3.2]
shall be installed in between the fire damper and 512.3.2 Any equipment, listed or otherwise, that
the source of bleed air. [NFPA 96:8.4.6] provides secondary filtration or air pollution
511.4.7 A bleed air duct shall not be used for the control and that is installed in the path of travel
exhaust of grease-laden vapors and shall be so of exhaust products shall be provided with an
labeled. [NFPA 96:8.4.7] approved automatic fire-extinguishing system
511.4.8 Unused tenant exhaust connections to for the protection of the component sections of
the master exhaust duct that are not used as the equipment and shall include protection of
bleed air connections shall be disconnected and the ductwork downstream of the equipment,
sealed at the main duct. [NFPA 96:8.4.8] whether or not the equipment is provided with a
511.5 Solid-Fuel Air Movement Requirements. damper. Filter media used in secondary filtra-
Where solid-fuel cooking equipment is used, exhaust tion or air pollution control units and not
and replacement air also shall comply with Section complying with Section 509.2.4 shall have fire
517.0. protection that is adequate for the filter media
being used in accordance with the fire-extin-
512.0 Auxiliary Equipment. guishing system manufacturer’s instructions. If
512.1 Dampers. Dampers shall not be installed in the equipment can be a source of ignition, it shall
exhaust ducts or exhaust duct systems. [NFPA be provided with appropriate detection to
96:9.1.1] operate the fire-extinguishing system. [NFPA
96:9.3.3, 9.3.3.1, 9.3.4]
512.1.1 Where specifically listed for such use or
where required as part of a listed device or 512.3.3 Where a cooking exhaust system
system, dampers in exhaust ducts or exhaust employs an air pollution control device that
duct systems shall be permitted. [NFPA 96:9.1.2] recirculates air into the building, the provisions
of Section 516.0 shall apply. [NFPA 96:9.3.5]
512.2 Electrical Equipment.
512.4 Solid-Fuel Auxiliary Equipment. Where solid
512.2.1 Wiring systems of any type shall not be
fuel cooking comprises any part of a cooking opera-
installed in ducts. [NFPA 96:9.2.1]
tion, additional provisions and equipment as
512.2.2 Only where specifically listed for such described in Section 517.0 shall be used where
use shall motors, lights, and other electrical required.
devices be permitted to be installed in ducts or
hoods or located in the path of travel of exhaust
products. [NFPA 96:9.2.2] 513.0 Fire-Extinguishing Equipment.
512.2.3 Lighting units on hoods shall not be 513.1 General Requirements.
located in concealed spaces. 513.1.1 Fire-extinguishing equipment for the
512.2.4 Lighting units shall be permitted in protection of grease removal devices, hood
concealed spaces where such units are part of a exhaust plenums, and exhaust duct systems
listed exhaust hood. [NFPA 96:9.2.3.3] shall be provided. [NFPA 96:10.1.1]

63
513.1 – 513.2 UNIFORM MECHANICAL CODE

513.1.2 Cooking equipment that produces 513.2.4.2 Penetrations and holes resulting
grease-laden vapors (such as, but not limited to, from the removal of conduit or piping shall
deep-fat fryers, ranges, griddles, broilers, woks, be sealed with listed or equivalent liquid
tilting skillets, and braising pans) shall be tight sealing devices. [NFPA 96:10.2.7.2]
protected by fire-extinguishing equipment. 513.2.4.3 The addition of obstructions to
[NFPA 96:10.1.2] spray patterns from the cooking appliance
513.2 Types of Equipment. nozzle(s) such as baffle plates, shelves, or
513.2.1 Fire-extinguishing equipment shall any modification shall not be permitted.
include both automatic fire-extinguishing [NFPA 96:10.2.7.3]
systems as primary protection and portable fire 513.2.4.4 Changes or modifications to the
extinguishers as secondary backup. [NFPA hazard after installation of the fire extin-
96:10.2.1] guishing systems shall result in reevaluation
513.2.1.1 A placard identifying the use of of the system design by a properly trained,
the extinguisher as secondary backup means qualified, and certified person(s). [NFPA
to the automatic fire suppression system 96:10.2.7.4]
shall be conspicuously placed near each 513.2.5 Fixed Baffle Hoods with Water Wash.
portable fire extinguisher in the cooking Grease removal devices, hood exhaust plenums,
area. [NFPA 96:10.2.2] and exhaust ducts requiring protection in accor-
513.2.2 Automatic fire-extinguishing systems dance with Section 513.1.1 shall be permitted to
shall comply with standard UL 300, Fire Testing be protected by a listed fixed baffle hood
of Fire Extinguishing Systems for Protection of containing a constant or fire-actuated water
Restaurant Cooking Areas, or other equivalent wash system that is listed and in compliance
standards and shall be installed in accordance with UL 300 or other equivalent standards and
with their listings. [NFPA 96:10.2.3] shall be installed in accordance with the require-
ments of their listing. [NFPA 96:10.2.8.1]
Exception: Automatic fire-extinguishing
equipment provided as part of listed recir- 513.2.5.1 The water for listed, fixed baffle
culating systems complying with standard hood assemblies shall be permitted to be
UL 710B, Outline of Investigation for Recircu- supplied from the domestic water supply
lating Exhaust System. when the minimum water pressure and
flow are provided in accordance with the
513.2.2.1 Automatic fire-extinguishing
terms of the listing. [NFPA 96:10.2.8.3]
systems shall be installed in accordance with
the terms of their listing, the manufacturer’s 513.2.5.2 The water supply shall be
instructions, and the following standards controlled by a supervised water supply
where applicable. [NFPA 96:10.2.6] control valve. [NFPA 96:10.2.8.4]
(1) NFPA 12, Standard on Carbon Dioxide 513.2.5.3 The water wash in the fixed baffle
Extinguishing Systems hood shall be activated by the cooking
equipment extinguishing system. [NFPA
(2) NFPA 13, Standard for the Installation of
96:10.2.8.5]
Sprinkler Systems
513.2.5.4 A water-wash system approved to
(3) NFPA 17, Standard for Dry Chemical
be used for protection of the grease removal
Extinguishing Systems
device(s), hood exhaust plenum(s), exhaust
(4) NFPA 17A, Standard for Wet Chemical duct(s), or combination thereof shall include
Extinguishing Systems instruction and appropriate electrical inter-
513.2.3 In existing systems, when changes in the face for simultaneous activation of the
cooking media, positioning, or replacement of water-wash system from an automatic fire-
cooking equipment occur, the fire-extinguishing extinguishing system, where the automatic
system shall be made to comply with 513.2.2. fire-extinguishing system is used for
[NFPA 96:10.2.3.1] cooking equipment protection only. [NFPA
513.2.4 Modification of Existing Hood 96:10.2.8.6]
Systems. 513.2.5.5 Where the fire-extinguishing
513.2.4.1 Any abandoned pipe or conduit system provides protection for the cooking
from a previous installation shall be equipment, hood, and duct, activation of the
removed from within the hood, plenum, water wash shall not be required. [NFPA
and exhaust duct. [NFPA 96:10.2.7.1] 96:10.2.8.7]

64
EXHAUST SYSTEMS 513.2 – 513.7

513.2.5.6 The water required for listed auto- 513.4.4 Shutoff devices shall require manual
matic fire-extinguishing systems shall be reset. [NFPA 96:10.4.4]
permitted to be supplied from the domestic 513.5 Manual Activation.
water supply where the minimum water 513.5.1 A readily accessible means for manual
pressure and flow are provided in accor- activation shall be located between forty-two
dance with the terms of the listing. The (42) inches and forty-eight (48) inches (1,067 mm
water supply shall be controlled by a super- and 1,219 mm) above the floor, located in a path
vised water supply control valve. [NFPA of exit or egress, and clearly identify the hazard
96:10.2.9] protected. A manual actuation device shall be
513.2.6 Water Valve Supervision. Valves located a minimum of ten (10) feet (3 m) when
controlling the water supply to listed fixed baffle possible and a maximum of twenty (20) feet (6
hood assemblies, automatic fire-extinguishing m) from the protected kitchen appliance(s)
systems, or both shall be listed indicating type of within the path of egress. Manual actuation
valve and shall be supervised open by one of the using a cable-operated pull station shall not
following methods: require more than forty (40) pounds (178 N) of
force, with a pull movement not to exceed four-
(1) Central station, proprietary, or remote teen (14) inches (356 mm) to actuate the fire
station alarm service suppression system. The automatic and manual
(2) Local alarm service that will cause the means of system activation external to the
sounding of an audible signal at a constantly control head or releasing device shall be separate
attended point and independent of each other so that failure of
(3) Locking valves open one will not impair the operation of the other.
[NFPA 96:10.5.1 – 10.5.2]
(4) Sealing of valves and approved weekly
513.5.2 The manual means of system activation
recorded inspection. [NFPA 96:10.2.10]
shall be permitted to be common with the auto-
513.3 Simultaneous Operation. Fixed-pipe extin- matic means if the manual activation device is
guishing systems in a single hazard area shall be located between the control head or releasing
arranged for simultaneous automatic operation upon device and the first fusible link. [NFPA 96:10.5.3]
actuation of anyone of the systems. [NFPA 96:10.3.1]
513.5.3 An automatic sprinkler system shall not
513.3.1 Simultaneous operation shall not be require a manual means of system activation.
required where the fixed pipe extinguishing [NFPA 96:10.5.4]
system is an automatic sprinkler system. [NFPA 513.5.4 The means for manual actuator(s) shall
96:10.3.2] be mechanical or rely on electrical power for
513.3.2 Simultaneous operation shall not be actuation. [NFPA 96:10.5.5]
required where dry or wet chemical system shall 513.5.5 Electrical power shall be permitted to be
be permitted to be used to protect common used for manual activation if a standby power
exhaust ductwork by one of the methods speci- supply is provided or if supervision is provided
fied in NFPA 17 or NFPA 17A. [NFPA 96:10.3.3] in accordance with Section 513.7. [NFPA
513.4 Fuel Shutoff. 96:10.5.6]
513.4.1 Upon activation of any fire-extin- 513.6 System Annunciation.
guishing system for a cooking operation, all 513.6.1 Upon activation of an automatic fire
sources of fuel and electric power that produce extinguishing system, an audible alarm or visual
heat to all equipment requiring protection by indicator shall be provided to show that the
that system shall automatically shut off. [NFPA system has activated. [NFPA 96:10.6.1]
96:10.4.1] 513.6.2 Where a fire alarm signaling system is
serving the occupancy where the extinguishing
Exception: Solid-fuel cooking operations.
system is located, the activation of the automatic
513.4.2 Steam supplied from an external source fire-extinguishing system shall activate the fire
shall not be required to automatically shut off. alarm signaling system. [NFPA 96:10.6.2]
[NFPA 96:10.4.2] 513.7 System Supervision.
513.4.3 Any gas appliance not requiring protec- 513.7.1 Where electrical power is required to
tion, but located under the same ventilating operate the automatic fire-extinguishing system,
equipment, shall also automatically shut off it shall be monitored by a supervisory alarm,
upon activation of any extinguishing system. with a standby power supply provided. [NFPA
[NFPA 96:10.4.3] 96:10.7.1]

65
513.7 – 514.1 UNIFORM MECHANICAL CODE

513.7.2 System supervision shall not be required sodium bicarbonate and potassium bicarbonate
where an automatic fire-extinguishing system(s) dry chemical and potassium carbonate solutions.
includes automatic mechanical detection and Class B gas-type portables such as CO 2 and
actuation as a backup detection system. halon shall not be permitted in kitchen cooking
[NFPA 96:10.7.2] areas. Manufacturer's recommendations shall be
513.7.3 System supervision shall not be required followed. [NFPA 96:10.10.1 – 10.10.4]
where a fire-extinguishing system(s) is intercon- 513.11.1.1 Portable fire extinguishers listed
nected or interlocked with the cooking equip- specifically for use in the kitchen cooking
ment power source(s) so that if the fire extin- areas shall also be permitted.
guishing system becomes inoperable due to
power failure, all sources of fuel or electric 513.11.2 Other fire extinguishers in the kitchen
power that produce heat to all cooking equip- area shall be installed in accordance with NFPA
ment serviced by that hood shall automatically 10, Standard for Portable Fire Extinguishers. [NFPA
shut off. [NFPA 96:10.7.3] 96:10.10.5]
513.7.4 System supervision shall not be required 513.12 Solid-Fuel Fire-Extinguishing Equipment.
where an automatic fire-extinguishing system, Where solid-fuel cooking equipment is served by fire
including automatic mechanical detection and extinguishing equipment, the provisions of Section
actuation, is electrically connected to a listed fire- 517.0 shall apply.
actuated water-wash system for simultaneous
operation of both systems. [NFPA 96:10.7.4]
514.0 Procedures for the Use and Maintenance of
513.8 Special Design and Application. Equipment.
513.8.1 Hoods containing automatic fire extin- 514.1 Operating Procedures.
guishing systems are protected areas; therefore,
514.1.1 Exhaust systems shall be operated
these hoods are not considered obstructions to
overhead sprinkler systems and shall not require whenever cooking equipment is turned on.
floor coverage underneath. [NFPA 96:10.8.1] [NFPA 96:11.1.1]
513.8.2 A single listed detection device, listed 514.1.2 Filter-equipped exhaust systems shall not
with the extinguishing system, shall be be operated with filters removed. [NFPA 96:11.1.2]
permitted for more than one (1) appliance when 514.1.3 Openings provided for replacing air
installed in accordance with the terms of the exhausted through ventilating equipment shall
listing. [NFPA 96:10.8.2] not be restricted by covers, dampers, or any
513.9 Review and Certification. other means that would reduce the operating
efficiency of the exhaust system. [NFPA
513.9.1 Where required, complete drawings of
96:11.1.3]
the system installation, including the hood(s),
exhaust duct(s), and appliances, along with the 514.1.4 Instructions for manually operating the
interface of the fire-extinguishing system detec- fire-extinguishing system shall be posted
tors, piping, nozzles, fuel shutoff devices, agent conspicuously in the kitchen and shall be
storage container(s), and manual actuation reviewed periodically with employees by the
device(s), shall be submitted to the Authority management. [NFPA 96:11.1.4]
Having Jurisdiction. [NFPA 96:10.9.1] 514.1.5 Listed exhaust hoods shall be operated
513.10 Installation Requirements. in accordance with the terms of their listings and
513.10.1 Installation of systems shall be the manufacturer's instructions. [NFPA
performed only by persons properly trained and 96:11.1.5]
qualified to install the specific system being 514.1.6 Cooking equipment shall not be oper-
provided. The installer shall provide certification ated while its fire-extinguishing system or
that the installation is in agreement with the exhaust system is nonoperational or otherwise
terms of the listing and the manufacturer's impaired. [NFPA 96:11.1.6]
instructions and/or approved design. [NFPA 514.1.7 Secondary filtration and pollution
96:10.9.2] control equipment shall be operated in accor-
513.11 Portable Fire Extinguishers. dance with the terms of its listing and the manu-
513.11.1 Portable fire extinguishers shall be facturer's recommendations. [NFPA 96:11.1.7]
installed in kitchen cooking areas in accordance 514.1.8 Inspection and maintenance of equip-
with NFPA 10, Standard for Portable Fire extin- ment allowed in Section 512.3.1 shall be
guishers. Such extinguishers shall use agents that conducted by properly trained and qualified
specify upon contact with hot grease, such as persons at a frequency determined by the manu-

66
EXHAUST SYSTEMS 514.1 – 514.4

facturer's instructions or equipment listing.


TABLE 5-4
[NFPA 96:11.1.8]
Exhaust System Inspection Schedule
514.2 Inspection. Maintenance of the fire-extin- [NFPA 96: Table 11.4]
guishing systems and listed exhaust hoods
containing a constant or fire-activated water system Type or Volume of Cooking Frequency
that is listed to extinguish a fire in the grease Frequency
removal devices, hood exhaust plenums, and Systems serving solid-fuel cooking Monthly
exhaust ducts shall be made by properly trained, operations
qualified, and certified person(s) or company accept- Systems serving high-volume cooking Quarterly
able to the Authority Having Jurisdiction at least operations such as 24-hour cooking,
charbroiling, or wok cooking
every six (6) months. [NFPA 96:11.2.1]
Systems serving moderate-volume Semi-
514.2.1 All actuation components, including cooking operations annually
remote manual pull stations, mechanical or elec- Systems serving low-volume cooking Annually
trical devices, detectors, actuators, and fire-actu- operations, such as churches, day
ated dampers, shall be checked for proper opera- camps, seasonal businesses, or senior
tion during the inspection in accordance with centers.
the manufacturer's listed procedures. In addition
grease-laden vapors, the contaminated portions
to these requirements, the specific inspection
of the exhaust system shall be cleaned by a prop-
requirements of the applicable NFPA standard
erly trained, qualified, and certified company or
shall also be followed. [NFPA 96-04:11.2.2 -
person(s) acceptable to the Authority Having
11.2.3]
Jurisdiction. [NFPA 96:11.6.1]
514.2.2 Fusible links (including fusible links on
514.4.2 Hoods, grease removal devices, fans,
fire damper assemblies) and automatic sprinkler
ducts, and other appurtenances shall be cleaned
heads shall be replaced at least semiannually, or
to remove combustible contaminant's prior to
more frequently if necessary where required by
surfaces becoming heavily contaminated with
the manufacturer. [NFPA 96-04:11.2.4]
grease or oily sludge. [NFPA 96:11.6.2]
514.2.3 The year of manufacture and the date of
514.4.3 At the start of the cleaning process, elec-
installation of the fusible links shall be marked trical switches that could be activated acciden-
on the system inspection tag. The tag shall be tally shall be locked out. [NFPA 96:11.6.3]
signed or initialed by the installer. [NFPA
96:11.2.5] 514.4.4 Components of the fire suppression
system shall not be rendered inoperable during
Other detection devices not including the cleaning process. [NFPA 96:11.6.4]
fusible links and automatic sprinklers shall be
514.4.5 Fire-extinguishing systems shall be
serviced or replaced in accordance with the
permitted to be rendered inoperable during the
manufacturer’s recommendations. [NFPA 96- cleaning process where serviced by properly
04:11.2.6] trained and qualified persons. [NFPA 96:11.6.5]
514.2.4 Where automatic bulb-type sprinklers or 514.4.6 Flammable solvents or other flammable
spray nozzles are used and annual examination cleaning aids shall not be used. [NFPA 96:11.6.6]
shows no buildup of grease or other material on
514.4.7 Cleaning chemicals shall not be applied
the sprinkler or spray nozzles, annual replace-
on fusible links or other detection devices of the
ment shall not be required. [NFPA 96:11.2.7] automatic extinguishing system. [NFPA 96:11.6.7]
514.2.5 If required, certificates of inspection and
514.4.8 After the exhaust system is cleaned, it
maintenance shall be forwarded to the Authority
shall not be coated with powder or other
Having Jurisdiction. [NFPA 96:11.2.8]
substance. [NFPA 96:11.6.8]
514.3 Inspection for Grease Buildup.
514.4.9 When cleaning procedures are
514.3.1 The entire exhaust system shall be completed, all access panels (doors) and cover
inspected for grease buildup by a properly plates shall be restored to their normal opera-
trained, qualified, and certified company or tional condition. [NFPA 96:11.6.9]
person(s) acceptable to the Authority Having
514.4.10 When an access panel is removed, a
Jurisdiction in accordance with Table 5-4.
service company label or tag preprinted with the
514.4 Cleaning of Exhaust Systems. name of the company and giving the date of
514.4.1 Upon inspection, if the exhaust system is inspection or cleaning shall be affixed near the
found to be contaminated with deposits from affected access panels. [NFPA 96:11.6.10]

67
514.4 – 516.1 UNIFORM MECHANICAL CODE

514.4.11 Dampers and diffusers shall be posi- reconnected in accordance with the
tioned for proper airflow. [NFPA 96:11.6.11] manufacturer’s listed design manual.
514.4.12 When cleaning procedures are [NFPA 96:12.1.2.3]
completed, all electrical switches and system 515.1.2.4 All deep-fat fryers shall be
components shall be returned to an operable installed with at least a sixteen (16) inch (406
state. [NFPA 96:11.6.12] mm) space between the fryer and surface
514.4.13 When an exhaust cleaning service is flames from adjacent cooking equipment.
used, a certificate showing the name of the [NFPA 96:12.1.2.4]
servicing company, the name of the person 515.1.2.5 Where a steel or tempered glass
performing the work, and the date of inspection baffle plate is installed at a minimum eight
or cleaning shall be maintained on the premises. (8) inches (203 mm) in height between the
[NFPA 96:11.6.13] fryer and surface flames of the adjacent
appliance, the requirement for a sixteen (16)
514.4.14 After cleaning or inspection is
inch (406 mm) space shall not apply. [NFPA
completed, the exhaust cleaning company and
96:12.1.2.5]
the person performing the work at the location
shall provide the owner of the system with a 515.1.2.6 If the fryer and the surface flames
written report that also specifies areas that were are at different horizontal planes, the
minimum height of eight (8) inches (203
inaccessible or not cleaned. [NFPA 96:11.6.14]
mm) shall be measured from the higher of
514.4.15 Where required, certificates of inspec- the two. [NFPA 96:12.1.2.5.1]
tion and cleaning and reports of areas not
515.2 Operating Controls. Deep-fat fryers shall be
cleaned shall be submitted to the Authority equipped with a separate high-limit control in addi-
Having Jurisdiction. [NFPA 96:11.6.15] tion to the adjustable operating control (thermostat)
to shut off fuel or energy when the fat temperature
515.0 Minimum Safety Requirements for Cooking reaches 475°F (246°C) at one (1) inch (25 mm) below
Equipment. the surface. [NFPA 96:12.2]
515.1 Cooking Equipment. 515.3 Cooking Equipment Maintenance.
515.1.1 Cooking equipment shall be approved 515.3.1 An inspection and servicing of the
based on one of the following criteria: cooking equipment shall be made at least annu-
ally by properly trained and qualified persons.
(A) Listings by a testing laboratory.
[NFPA 96:11.5.1]
(B) Test data acceptable to the Authority
515.3.2 Cooking equipment that collects grease
Having Jurisdiction. [NFPA 96:12.1.1]
below the surface, behind the equipment, or in
515.1.2 Installation. cooking equipment flue gas exhaust, such as
515.1.2.1 All listed appliances shall be griddles or charbroilers, shall be inspected and,
installed in accordance with the terms of if found with grease accumulation, cleaned by a
their listings and the manufacturer's instruc- properly trained, qualified, and certified person
tions. [NFPA 96:12.1.2.1] acceptable to the authority having jurisdiction.
515.1.2.2 Cooking appliances requiring [NFPA 96:11.5.2]
protection shall not be moved, modified, or
rearranged without prior reevaluation of the 516.0 Recirculating Systems.
fire-extinguishing system by the system 516.1 General Requirements. Recirculating
installer or servicing agent, unless otherwise systems containing or for use with appliances used
allowed by the design of the fire-extin- in processes producing smoke or grease-laden
guishing system. [NFPA 96:12.1.2.2] vapors shall be equipped with components
515.1.2.3 The fire-extinguishing system complying with the following:
shall not require re-evaluation where (A) The clearance requirements of Section 507.2.
the cooking appliances are moved to
(B) A hood complying with the requirements of
perform maintenance and cleaning
Section 508.0.
provided the appliances are returned to
approved design location prior to (C) Grease removal devices complying with Section
cooking operations, and any discon- 509.0.
nected fire-extinguishing system (D) The air movement requirements of Sections
nozzles attached to the appliances are 511.2.1 and 511.2.2.

68
EXHAUST SYSTEMS 516.1 – 516.3

(E) Auxiliary equipment (such as particulate and 516.2.8 The power supply of any electrostatic
odor removal devices) complying with Section precipitator (ESP) shall be of the "cold spark,"
512.0. ferro-resonant type in that the voltage falls off as
(F) Fire-extinguishing equipment complying with the current draw of a short increases. [NFPA
the requirements of Section 513.0. 96:13.2.11]
Exception: References to ducts in Sections 516.2.9 Listing evaluation shall include the
513.1.1 and 513.5.1. following:
(G) The use and maintenance requirements of 514.0. (A) Capture and containment of vapors at
(H) The minimum safety requirements of Section published and labeled airflows.
515.0. (B) Grease discharge at the exhaust outlet of the
(I) All the requirements of this chapter. [NFPA system not to exceed an average of 5 mg/m3
96:13.1] of exhausted air sampled from that equip-
516.2 Design Restrictions. All recirculating systems ment at maximum amount of product that is
shall comply with Section 516.2. [NFPA 96:13.2] capable of being processed over a contin-
uous eight (8) hour test per EPA Test
516.2.1 Only gas- or electrically fueled cooking
Method 202, Determination of Condensable
appliances shall be used. Gas-fueled appliances
Particulate Emissions for Stationary Sources,
shall not have the combustion flue outlet(s)
directly connected to the recirculating system. with the system operating at its minimum
Gas-fueled appliances shall have a minimum listed airflow.
eighteen (18) inch (457 mm) clearance from the (C) Listing and labeling of clearance to
flue outlet to the filter inlet in accordance with combustibles from all sides, top, and bottom.
Section 509.2.3 and shall meet the installation (D) Electrical connection in the field in accor-
requirements of NFPA 54, National Fuel Gas Code, dance with NFPA 70, National Electrical Code.
or NFPA 58, Liquefied Petroleum Gas Code. [NFPA
96:13.2.1 – 13.2.3] (E) Interlocks on all removable components that
lie in the path of airflow within the unit to
516.2.2 Recirculating systems shall be listed ensure that they are in place during opera-
with a testing laboratory. The recirculating tion of the cooking appliance. [NFPA
system listing shall include integral fire protec-
96:13.2.12]
tion for recirculating hoods, including canopy
type [NFPA 96:13.2.4.1] 516.3 Interlocks. The recirculating system shall be
provided with interlocks of all critical components
516.2.3 Cooking appliances that require protec-
and operations as indicated in Sections 516.3.1
tion and that are under a recirculating hood shall
be protected by either the integral fire protection through 516.3.4 such that, if any of these interlocks
system for the hood or a system in accordance are interrupted, the cooking appliance shall not be
with Section 513.0. [NFPA 96:13.2.4.2] able to operate. [NFPA 96:13.3.1]
516.2.4 A recirculating system shall not use 516.3.1 All closure panels encompassing airflow
cooking equipment that exceeds that recircu- sections shall have interlocks to ensure the
lating system's labeled maximum limits for that panels are in place and fully sealed.[NFPA
type of equipment, stated in maximum energy 96:13.3.2]
input, maximum cooking temperature, and 516.3.2 Each filter component (grease and odor)
maximum square area of cooking surface or shall have an interlock to prove the component
cubic volume of cooking cavity. [NFPA
is in place. [NFPA 96:13.3.3]
96:13.2.6]
516.3.3 ESP Interlocks.
516.2.5 The listing label shall show the type(s)
of cooking equipment tested and the maximum 516.3.3.1 Each ESP shall have a sensor to
limits specified in 516.2.4. [NFPA 96:13.2.7] prove its performance is as designed, with
516.2.6 A fire-actuated damper shall be installed no interruption of the power to exceed two
at the exhaust outlet of the system. The actua- (2) minutes. [NFPA 96:13.3.4.1]
tion device shall have a maximum temperature 516.3.3.2 The sensor shall be a manual reset
rating of 375°F (190°C). [NFPA 96:13.2.8, 13.2.10] device or circuit. [NFPA 96:13.3.4.2]
516.2.7 No electrical wiring shall be installed in 516.3.4 An airflow switch or transducer shall be
the interior sections of the hood plenum that provided after the last filter component to
might become exposed to grease. ensure that a minimum airflow is maintained.
Exception: As permitted by NFPA 70, This device opens the interlock circuit when the
National Electrical Code. airflow falls twenty-five (25) percent below the

69
516.3 – 517.3 UNIFORM MECHANICAL CODE

system's normal operating flow or ten (10) 517.0 Solid-Fuel Cooking Operations.
percent below its listed minimum rating, 517.1 Venting Application. Venting requirements of
whichever is lower. This switch or transducer solid-fuel cooking operations shall be determined in
shall be a manual reset device or circuit. [NFPA accordance with Sections 517.1.1 through 517.1.6.
96:13.3.5]
517.1.1 Where solid-fuel cooking equipment is
516.4 Location and Application Restrictions. The required by the manufacturer to have a natural
location of recirculating systems shall be approved draft, the vent shall comply with Section 517.4.
by the Authority Having Jurisdiction. Items to be
reviewed in the fire risk assessment shall include, 517.1.2 Where the solid-fuel cooking equipment
but not be limited to, life safety, combustibility of has a self-contained top, is the only appliance to
surroundings, proximity to air vents, and total fuel be vented in an isolated space (except for a single
load. [NFPA 96:13.4] water heater with its own separate vent), has a
separate makeup-air system, and is provided
516.5 Additional Fire Safety Requirements.
with supply and return air (not supplied or
516.5.1 In addition to the appliance nozzle(s), a returned from other spaces), the system shall
recirculating system shall be listed with the comply with Sections 517.4 and 517.6.
appropriate fire protection for grease filters,
517.1.3 Where the solid-fuel cooking equipment
grease filtration, odor filtration units, and duct-
is located in a space with other vented equip-
work where applicable. [NFPA 96:13.5.1]
ment, all vented equipment shall have an
516.5.2 In addition to any other fire-extin- exhaust system interlocked with a makeup-air
guishing system actuation device, there shall be system for the space as per Section 517.6.
a fire-extinguishing system actuation device
installed downstream of any ESP.[NFPA 517.1.4 Natural draft ventilation systems and
96:13.5.2] power-exhausted ventilation systems shall
comply with Sections 517.3, 517.4, and 517.6.
516.5.3 The requirements of Section 513.6 shall
also apply to recirculating system locations. 517.1.5 Where a solid-fuel cooking appliance
[NFPA 96:13.5.3] allows effluent to escape from the appliance
opening, this opening shall be covered by a hood
516.6 Use and Maintenance.
and an exhaust system that meets the require-
516.6.1 Automatic or manual covers on cooking ments of Sections 517.3, 517.4, and 517.6.
appliances, especially fryers, shall not interfere
517.1.6 Solid-fuel cooking operations shall have
with the application of the fire suppression
spark arresters to minimize the passage of
system.[NFPA 96:13.6.1]
airborne sparks and embers into plenums and
516.6.2 All filters shall be cleaned or replaced in ducts. Where the solid-fuel cooking operation is
accordance with the manufacturer's instructions. not located under a hood, a spark arrester shall
[NFPA 96:13.6.2] be provided to minimize the passage of sparks
516.6.3 All ESPs shall be cleaned a minimum of and embers into flues and chimneys.
once per week following manufacturer's 517.2 Location of Appliances.
cleaning instructions. [NFPA 96:13.6.3]
517.2.1 Every appliance shall be located with
516.6.4 The entire hood plenum and the blower respect to building construction and other equip-
section shall be cleaned a minimum of once ment so as to permit access to the appliance.
every three (3) months. [NFPA 96:13.6.4]
517.2.2 Solid-fuel cooking appliances shall not
516.6.5 Inspection and testing of the total opera- be installed in confined spaces.
tion and all safety interlocks in accordance with
Exception: Solid-fuel cooking appliances listed
the manufacturer's instructions shall be
for installation in confined spaces shall be
performed by qualified service personnel a
installed in accordance with the terms of the
minimum of once every six (6) months, or more
listing and the manufacturer's instructions.
frequently if required. [NFPA 96:13.6.5]
517.2.3 Solid-fuel cooking appliances shall not
516.6.6 Fire-extinguishing equipment shall be
be installed in any location where gasoline or
inspected in accordance with Section 514.2.
any other flammable vapors or gases are likely
[NFPA 96:13.6.6]
to be present.
516.6.7 A signed and dated log of maintenance
as performed in accordance with Sections 516.6.4 517.3 Hoods for Solid-Fuel Cooking.
and 516.6.5 shall be available on the premises for 517.3.1 Hoods shall be sized and located in a
use by the Authority Having Jurisdiction. manner capable of capturing and containing all
[NFPA 96:13.6.7] of the effluent discharging from the appliances.

70
EXHAUST SYSTEMS 517.3 – 517.7

The hood and its exhaust system shall comply exhaust-air system and powered, if necessary, to
with the provisions of the code. prevent the space from attaining a negative pres-
517.3.2 All solid-fuel cooking equipment served sure while the solid-fuel appliance is in opera-
by hood and duct systems shall be separate from tion.
all other exhaust systems. 517.7 Fire-Extinguishing Equipment for Solid-
Exception: Cooking equipment not Fuel Cooking.
requiring automatic fire-extinguishing 517.7.1 Approved fire-extinguishing equipment
equipment (as per the provisions of Section shall be provided to protect all solid-fuel-
510.0) shall be permitted to be installed burning cooking appliances that might be a
under a common hood with solid-fuel source of ignition of grease in the hood, grease
cooking equipment that is served by a duct removal device, or duct.
system separate from all other exhaust Exception: If acceptable to the Authority
systems. Having Jurisdiction, solid-fuel-burning
cooking appliances constructed of solid
517.4 Exhaust Systems for Solid-Fuel Cooking.
masonry or reinforced portland or refractory
Where a hood is not required, in buildings where the
cement concrete and vented in accordance
duct system is three (3) stories or less in height, a
with NFPA 211, Standard for Chimneys, Fire-
duct complying with Section 510.0 shall be provided.
places, Vents, and Solid Fuel–Burning
517.4.1 If a hood is used, the duct system shall Appliances, Chapters 3 and 4, shall not require
conform with the Section 510.0. fixed automatic fire-extinguishing equipment.
517.4.2 A listed or approved grease duct system 517.7.2 Approved fire-extinguishing equipment
shall be provided for solid-fuel cooking exhaust shall be provided for the protection of grease
systems that are four (4) stories in height or removal devices, hoods, and duct systems.
greater. Exception: If acceptable to the Authority
517.4.3 Where a hood is used, the duct system Having Jurisdiction, solid-fuel-burning
shall conform with the requirements of Section cooking appliances constructed of solid
510.0. masonry or reinforced portland or refractory
517.4.4 Wall terminations of solid-fuel exhaust cement concrete and vented in accordance
with NFPA 211, Standard for Chimneys, Fire-
systems shall be prohibited.
places, Vents, and Solid Fuel–Burning Appli-
517.5 Grease Removal Devices for Solid-Fuel ances, Chapters 3 and 4, shall not require
Cooking. Grease removal devices shall be automatic fire-extinguishing equipment.
constructed of steel or stainless steel or be approved
517.7.3 Approved fire-extinguishing equipment
for solid-fuel cooking.
for solid-fuel-burning cooking appliances, where
517.5.1 If airborne sparks and embers can be required, shall comply with NFPA 211 and shall
generated by the solid-fuel cooking operation, be comprised of water-based agents.
spark arrester devices shall be used prior to the
517.7.4 Fire-extinguishing equipment shall be
grease removal device to minimize the entrance
rated and designed to extinguish solid-fuel
of these sparks and embers into the grease
cooking fires, in accordance with the manufac-
removal device and into the hood and duct turer's recommendations. The fire-extinguishing
system. equipment shall be of sufficient size to totally
517.5.2 Filters shall be a minimum of four (4) extinguish fire in the entire hazard area and
feet (1.2 m) above the appliance cooking surface. prevent reignition of the fuel.
517.6 Air Movement for Solid-Fuel Cooking. 517.7.5 All solid-fuel appliances (whether or not
Exhaust system requirements shall comply with the under a hood) with fireboxes of five (5) ft.3 (0.14
provisions of the code for hooded operation or shall m3) volume or less shall at least have a listed 2-A
be installed in accordance with the manufacturer's rated water-type fire extinguisher or a 1.6 gal (6
recommendation for unhooded applications. L) wet chemical fire extinguisher listed for Class
517.6.1 A replacement or makeup-air system K fires in accordance with NFPA 10, in the
shall be provided to ensure a positive supply of immediate vicinity of the appliance. [NFPA
replacement air at all times during cooking oper- 96:14.7.8]
ations. 517.7.6 Solid-fuel appliances with fireboxes
517.6.2 Makeup-air systems serving solid-fuel exceeding five (5) ft.3 (0.14 m3) shall be provided
cooking operations shall be interlocked with the with a fixed-water-pipe system with a hose in

71
517.7 – 517.8 UNIFORM MECHANICAL CODE

the immediate vicinity of the appliance. The


hose shall be equipped with an adjustable nozzle
capable of producing a fine to medium spray or
mist. The nozzle shall be of the type that cannot
produce a straight stream. The system shall have
a minimum operating pressure of forty (40) psi
(275.8 kPa) and shall provide a minimum of five
(5) gpm. [NFPA 96:14.7.9.1 – 14.7.9.2]
517.7.7 Fire suppression for fuel storage areas
shall comply with Section 517.9.
517.7.8 In addition to the requirements of
Sections 517.7.5 or 517.7.6, where any solid-fuel
cooking appliance is also provided with auxil-
iary electric, gas, oil, or other fuel for ignition or
supplemental heat and the appliance is also
served by any portion of a fire-extinguishing
system complying with Section 513.0, such auxil-
iary fuel shall be shut off upon actuation of the
fire-extinguishing system.
517.8 Other Safety Requirements.
517.8.1 Metal-fabricated solid-fuel cooking
appliances shall be listed for the application
where produced in practical quantities or shall be
approved by the Authority Having Jurisdiction.
When listed, they shall be installed in accordance
with the terms of their listings and with the
applicable requirements of this standard.
517.8.2 Site-built solid-fuel cooking appliances
shall be submitted for approval to the Authority
Having Jurisdiction before being considered for
installation. All units shall be installed, operated,
and maintained in accordance with the
approved terms of the manufacturer's instruc-
tions and any additional requirements set forth
by the Authority Having Jurisdiction.
517.8.3 Except for the spark arrester required in
Section 517.1.6, there shall be no additional
devices of any type in any portion of the appli-
ance, flue pipe, and chimney of a natural draft
solid-fuel operation.
517.8.4 No solid-fuel cooking device of any type
shall be permitted for deep-fat frying involving
more than one (1) quart of liquid shortening, nor
shall any solid-fuel cooking device be permitted
within three (3) feet (0.92 m) of any deep-fat
frying unit.

72
EXHAUST SYSTEMS Table 5-5

TABLE 5-5
Minimum Sheet Metal Thickness for Round Ducts for Product-Conveying System Ducts
Reinf. Class 1
Negative Spacing
Pressure (Inches) Up to 7" 8" to 11" 12" to 15" 16" to 19" 20" to 23" 24" to 35" 36" to 47" 48" to 59" 60"

To 7" 0 .021 (24 ga.) .021 (24 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .127 (10 ga.)
96 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.)
48 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.)
24 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.)

8" to 11" 0 .021 (24 ga.) .027 (22 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.)
96 .021 (24 ga.) .027 (22 ga.) .027 (22 ga.) .044 (18 ga.) .044 (18 ga.) .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
48 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.)
24 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .027 (22 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.)

12" to 15" 0 .021 (24 ga.) .033 (20 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
96 .021 (24 ga.) .027 (22 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .097 (12 ga.) .112 (11 ga.) .112 (11 ga.)
48 .021 (24 ga.) .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.)
24 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .027 (22 ga.) .027 (22 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

16" to 20" 0 .021 (24 ga.) .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.)
96 .021 (24 ga.) .033 (20 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.)
48 .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.)
24 .021 (24 ga.) .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.)
Class 2
To 7" 0 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .127 (10 ga.)
96 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.)
48 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)
24 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

8" to 11" 0 .027 (22 ga.) .027 (22 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.)
96 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
48 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.)
24 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

12" to 15" 0 .027 (22 ga.) .033 (20 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
96 .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .097 (12 ga.) .112 (11 ga.) .112 (11 ga.)
48 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.)
24 .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

16" to 20" 0 .027 (22 ga.) .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.)
96 .027 (22 ga.) .033 (20 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.)
48 .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.)
24 .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

Class 3

To 7" 0 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .127 (10 ga.)
96 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
48 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
24 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)

8" to 11" 0 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.)
96 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
48 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
24 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)

73
Table 5-5 continued – Table 5-6 UNIFORM MECHANICAL CODE

TABLE 5-5 (continued)


Minimum Sheet Metal Thickness for Round Ducts for Product-Conveying System Ducts
Reinf. Class 3
Negative Spacing
Pressure (Inches) Up to 7" 8" to 11" 12" to 15" 16" to 19" 20" to 23" 24" to 35" 36" to 47" 48" to 59" 60"
12" to 15" 0 .033 (20 ga.) .033 (20 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
96 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .097 (12 ga.) .112 (11 ga.) .112 (11 ga.)
48 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
24 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)

16" to 20" 0 .033 (20 ga.) .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.)
96 .033 (20 ga.) .033 (20 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.)
48 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.)
24 .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
Class 4
To 7" 0 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .127 (10 ga.)
96 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
48 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
24 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

8" to 11" 0 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.)
96 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
48 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
24 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

12" to 15" 0 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
96 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.) .112 (11 ga.)
48 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
24 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

16" to 20" 0 .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .112 (11 ga.)
96 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.)
48 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
24 .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
Note: 1 in. = 25.4 mm

TABLE 5-6
Minimum Sheet Metal Thickness for Rectangular Ducts
Longest Side of Duct
Class 1 Class 2
Negative Reinf.
Pressure Spacing Up to 12" 13" to 24" 25" to 36" 37" to 48" 49" to 60" Up to 12" 13" to 24" 25" to 36" 37" to 48" 49" to 60"

To 7" 48 .021 (24 ga.) .033 (20 ga.) .055 (16 ga.) .068 (14 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .068 (14 ga.)
To 7" 24 .021 (24 ga.) .027 (22 ga.) .033 (20 ga.) .033 (20 ga.) .033 (20 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)
To 7" 12 .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .021 (24 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

8" to 11" 48 .027 (22 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .033 (20 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
8" to 11" 24 .027 (22 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .033 (20 ga.) .055 (16 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.)
8" to 11" 12 .021 (24 ga.) .027 (22 ga.) .027 (22 ga.) .027 (22 ga.) .027 (22 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

12" to 15" 48 .044 (18 ga.) .097 (12 ga.) .044 (18 ga.) .044 (18 ga.)
12" to 15" 24 .044 (18 ga.) .055 (16 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.) .044 (18 ga.) .044 (18 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
12" to 15" 12 .027 (22 ga.) .044 (18 ga.) .044 (18 ga.) .044 (18 ga.) .044 (18 ga.) .033 (20 ga.) .044 (18 ga.) .055 (16 ga.) .055 (16 ga.) .055 (16 ga.)

16" to 20" 48 .068 (14 ga.) .112 (11 ga.) .068 (14 ga.) .112 (11 ga.)
16" to 20" 24 .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.) .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.)
16" to 20" 12 .033 (20 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .033 (20 ga.) .044 (18 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.)
Class 3 Class 4
To 7" 48 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
To 7" 24 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
To 7" 12 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

8" to 11" 48 .044 (18 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.)
8" to 11" 24 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
8" to 11" 12 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

12" to 15" 48 .044 (18 ga.) .097 (12 ga.) .055 (16 ga.) .097 (12 ga.)
12" to 15" 24 .044 (18 ga.) .055 (16 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
12" to 15" 12 .044 (18 ga.) .055 (16 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)

16" to 20" 48 .068 (14 ga.) .112 (11 ga.) .055 (16 ga.) .112 (11 ga.)
16" to 20" 24 .068 (14 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.) .055 (16 ga.) .068 (14 ga.) .112 (11 ga.) .112 (11 ga.) .112 (11 ga.)
16" to 20" 12 .044 (18 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .068 (14 ga.) .055 (16 ga.) .068 (14 ga.) .097 (12 ga.) .097 (12 ga.) .097 (12 ga.)
Note: 1 in. = 25.4 mm

74

Potrebbero piacerti anche