Indoor unit

(R410A)
0CVP0-01A

Indoor unit
(R410A)
0CVP0-01A

(R410A)
Indoor unit
Introduction
General Information
Indoor Units
Dip Switch & Group Control Setting

Introduction
1. Preface
R410A Model
is the most favored choice when there is a need for precise air conditioning of relatively big projects extending from Multi-Room structure to big commercial places. We have a big line up, that offers wider
flexibility of model selection.
Equipped with inverter technology and long piping installation, the product matches well if one talk about optimum power consumption in high rise buildings. Add on capacity feature makes it easy to upgrade the existing
capacity at any time.
With the growing concern about environment preservation,
comes with R410A refrigerant which
is environment friendly and thus our
system is a high technology and environment friendly product.

Unique refrigerant flow and electronic circuit control gives this system an unique capability to work in
extreme/abnormal working conditions making our customer feel great about their decision of selecting
LG
as their first choice.
This publication provides a detailed and in depth information about the design and installation of
.
We hope that with this information you would become an expert of your

system.

Air-Conditioning Company

2. Step by Step
(1)

(2)

System Selection Process

Calculate or obtain the maximum heat load for the area(s) to be air conditioned

Decide the indoor unit specifications


Decide the outdoor unit specifications
Capacity coefficient factor
Decide the air velocity and temperature distributions

(3)

(4)

Selection of refrigerant pipe joints and headers

Selection of the control system


Control wiring method
Description of devices

(5)

Electrical wiring
Electric characteristics
Field wiring

Caution

1. Air conditioners should not be installed in areas where corrosive gas such as acid gas
or alkaline gas is produced.
2. If the outdoor unit is installed close to the sea shore, direct exposure to the sea breeze
should be avoided and choose an outdoor unit with anti-corrosion treatment.

Indoor unit
General Information
1. Model Names
2. External Appearance
3. Nomenclature
4. Indoor Unit Capacity Index

1. Model Names
Chassis
5k
Name (1.6)

Category

9k
(2.8)

12k
(3.6)

15k
(4.5)

ARNU18G ARNU24G
S5*2
S5*2

S5
ARNU07G ARNU09G ARNU12G ARNU15G
SE*2
SE*2
SE*2
SE*2

SE
Mirror
ART COOL

ARNU18G ARNU24G
S8*2
S8*2

S8

Gallery

ARNU07G ARNU09G ARNU12G


SF*2
SF*2
SF*2
ARNU07G ARNU09G ARNU12G
GTU*2
GTU*2
GTU*2

SF
TU

1 Way

ARNU18G ARNU24G
TT*2
TT*2
ARNU18G ARNU24G
TL*2
TL*2

TT
2 Way
Ceiling

TL
TR

Cassette

ARNU05 ARNU07G ARNU09G ARNU12G


GTR*2
TR*2
TR*2
TR*2
ARNU15 ARNU18G
GTQ*2
TQ*2

TQ
4 Way

Capacity(Btu/h(kW))
18k 24k
28k
36k
42k
48k
76k
96k
(5.6) (7.1) (8.2) (10.6) (12.3) (14.1) (22.4) (28.0)

ARNU07G ARNU09G ARNU12G ARNU15G


SE*2
SE*2
SE*2
SE*2

SE

Wall Mounted
(General)

7k
(2.2)

ARNU24G ARNU28G
TP*2
TP*2

TP

ARNU36G
TN*2

TN

ARNU42G ARNU48G
TM*2
TM*2

TM
BH
High
Static
Ceiling
Concealed
Duct

ARNU07G ARNU09G ARNU12G ARNU15G ARNU18G ARNU24G


BHA2
BHA2
BHA2
BHA2
BHA2
BHA2
ARNU28G ARNU36G ARNU42G
BGA2
BGA2
BGA2

BG

ARNU48G
BRA2

BR

URNU76G URNU96G
B8A2
B8A2

B8
B1
Low Static

ARNU07
GB1G2

ARNU09
GB1G2

ARNU12
GB1G2

ARNU15
GB1G2
ARNU18
GB2G2

B2
B3
Built In

ARNU07G ARNU09G ARNU12G ARNU15G


B3G2
B3G2
B3G2
B3G2
ARNU18G ARNU24G
B4G2
B4G2

B4
Ceiling & Floor

VE

Ceiling Suspended

VJ
CE

With Case

ARNU09G ARNU12G
VEA2
VEA2
ARNU18G ARNU24G
VJA2
VJA2
ARNU07G ARNU09G ARNU12G ARNU15G
CEA2
CEA2
CEA2
CEA2
ARNU18G ARNU24G
CFA2
CFA2

CF

Floor
Standing

Without
Case
Console

CE

ARNU07G ARNU09G ARNU12G ARNU15G


CEU2
CEU2
CEU2
CEU2
ARNU18G ARNU24G
CFU2
CFU2

CF
QA
BR

Fresh Air Intake Unit

ARNU24
GB2G2

ARNU07G ARNU09G ARNU12G ARNU15G


QAA2
QAA2
QAA2
QAA2
ARNU48G
BRZ2

B8

*ART COOL- SE/S8( * R:Mirror, V:Silver, B : Blue), SF(* E:Red, V:Silver, G:Gold , 1: Kiss (Photo changeable))
*Wall Mounted- A: Basic, L:Plasma, *Ceiling Cassette- A: Basic, C:Plasma

1 _ General Information

URNU76 URNU96
GB8Z2
GB8Z2

2. External Appearance
Ceiling Cassette- 1Way

Ceiling Concealed Duct - High Static

ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2

ARNU07GBHA2
ARNU09GBHA2
ARNU12GBHA2
ARNU15GBHA2
ARNU18GBHA2
ARNU24GBHA2
ARNU28GBGA2

ARNU18GTT*2
ARNU24GTT*2

* A:Basic, C:Plasma

ARNU36GBGA2
ARNU42GBGA2
ARNU48GBRA2
URNU76GB8A2
URNU96GB8A2

Ceiling Cassette- 4Way

Wall Mounted

ARNU05GTR*2
ARNU07GTR*2
ARNU09GTR*2
ARNU12GTR*2
ARNU15GTQ*2
ARNU18GTQ*2

ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2

ARNU24GTP*2
ARNU28GTP*2
ARNU36GTN*2
ARNU42GTM*2
ARNU48GTM*2
* A:Basic, C:Plasma

Ceiling Concealed Duct - Low Static


ARNU07GB1G2 ARNU15GB1G2
ARNU09GB1G2 ARNU18GB2G2
ARNU12GB1G2 ARNU24GB2G2

Ceiling Concealed Duct Built-in


ARNU07GB3G2
ARNU09GB3G2
ARNU12GB3G2

ARNU15GB3G2
ARNU18GB4G2
ARNU24GB4G2

ARNU15GSE*2
ARNU18GS5*2
ARNU24GS5*2
* A:Basic, L:Plasma

ART COOL Gallery


ARNU07GSF*2
ARNU09GSF*2
ARNU12GSF*2
* E:Red V:Silver
G:Gold 1: Kiss (Photo changeable)

Floor Standing
With case
ARNU07GCEA2
ARNU09GCEA2
ARNU12GCEA2

ARNU15GCEA2
ARNU18GCFA2
ARNU24GCFA2

ART COOL Mirror

Without case

ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2

ARNU07GCEU2
ARNU09GCEU2
ARNU12GCEU2

ARNU15GSE*2
ARNU18GS8*2
ARNU24GS8*2
* R:Mirror, V:Silver, B:Blue

ARNU15GCEU2
ARNU18GCFU2
ARNU24GCFU2

Ceiling & Floor


Console

ARNU09GVEA2
ARNU12GVEA2

Ceiling Suspended
ARNU18GVJA2
ARNU24GVJA2

Ceiling Cassette -2Way


ARNU18GTL*2
ARNU24GTL*2

ARNU07GQAA2
ARNU09GQAA2
ARNU12GQAA2
ARNU15GQAA2

Fresh Air Intake Unit


ARNU48GBRZ2
URNU76GB8Z2
URNU96GB8Z2

* A:Basic, C:Plasma

General Information _ 2

3. Nomenclature
ARN

07

TU

2
Serial Number
Combinations of functions
A:Basic function
L:Neo Plasma(Wall Mounted)
C:Plasma(Ceiling Cassette)
G: Low Static
U : Floor Standing without Case
ART COOL Type Panel Color
SE/S8 - R:Mirror V:Silver B:Blue
SF - E:Red V:Silver G:Gold 1: Kiss (Photo changeable)
Q : Console
Z : Fresh Air Intake Unit
Chassis Name
Electrical Ratings
2:1, 220V, 60Hz
6:1, 220 - 240V, 50Hz
G:1, 220 - 240V, 50Hz / 1, 220V, 60Hz
Total Cooling Capacity in Btu/h
EX) 5,000 Btu/h Class '05'
18,000 Btu/h Class '18'
Combination of Inverter Type and
Cooling Only or Heat Pump
N: AC Inverter and H/P V: AC Inverter and C/O
U: DC Inverter and H/P and C/O
System with
Indoor Unit using R410A
LGETA:U Ex) URN

3 _ General Information

4. Indoor Unit Capacity Index


INDOOR UNIT CAPACITY INDEX
Unit Capacity
(Btu/h)

5k

7k

9k

12k

15k

18k

24k

28k

36k

42k

48k

76k

96k

Capacity
Index

1.6

2.2

2.8

3.6

4.5

5.6

7.1

8.2

10.6

12.3

14.1

22.4

28.0

Capacity Index is same as the capacity(kW).

General Information _ 4

5 _ General Information

Indoor unit
Ceiling Cassette 1-Way
Ceiling Cassette 2-Way
Ceiling Cassette 4-way
Ceiling Concealed Duct(High Static)
Ceiling Concealed Duct(Low Static)
Ceiling Concealed Duct(Built in)
Wall Mounted
ART COOL Mirror
ART COOL Gallery
Ceiling & Floor/Ceiling Suspended
Floor Standing
Console
Fresh Air Intake Unit
Dip Switch & Group Control Setting

Indoor unit
Ceiling Cassette 1-Way
1. List of functions
2. Specifications
3. Dimensions
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. Air Velocity and Temperature Distribution
8. Electric Characteristics
9. Sound Levels
10. Installation
11. Accessories

1. List of functions
Category

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Air supply outlet


Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU07GTU*2, ARNU09GTU*2, ARNU12GTU*2


ARNU18GTT*2, ARNU24GTT*2
1
Auto
O
4/5/4
X
O
O
X
Option
O
O
O
X
O
O
O
O
O(Heat recovery)
X
O(Heat pump or Cooling only)
O
O
O
O
O
O
O
O
Accessory
Accessory
Accessory
Accessory
X
Accessory
-

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.
* Some functions can be limited by remote controller.

Ceiling Cassette 1-Way _ 1

Indoor Units

Air flow

Function

2. Specifications

Indoor Units

* Model Name
A:Basic, C:Plasma
Type
Model
Cooling Capacity

Heating Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Casing
Body
Dimensions (WxDxH)
Front Panel
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

mm
inch
mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
Body
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Panel Color
Panel Name(Accessory)

, V, Hz

1Way Ceiling Cassette


ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2
2.2
2.8
3.6
1,900
2,400
3,100
7,500
9,600
12,300
2.5
3.2
4.0
2,200
2,800
3,400
8,500
10,900
13,600
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
860 x 450 x 132
860 x 450 x 132
860 x 450 x 132
33.8 x 17.7 x 5.2
33.8 x 17.7 x 5.2
33.8 x 17.7 x 5.2
1100 x 500 x 34
1100 x 500 x 34
1100 x 500 x 34
43.3 x 19.7 x 1.3
43.3 x 19.7 x 1.3
43.3 x 19.7 x 1.3
2 x 12 x 18
2 x 12 x 18
2 x 12 x 18
0.16
0.16
0.16
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
30
30
30
0.18
0.18
0.18
8.2 / 7.3 / 6.4
9.2 / 8.6 / 8.2
10 / 9.2 / 8.2
289.5 / 257.7 / 225.9
324.7 / 303.6 / 289.5
353 / 324.8 / 289.5
Direct
Direct
Direct
BLDC
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Foamed polystrene
Fuse
Fuse
Fuse
6.35(1/4)
6.35(1/4)
6.35(1/4)
12.7(1/2)
12.7(1/2)
12.7(1/2)
25(1)
25(1)
25(1)
14.7(32.4)
14.7(32.4)
14.7(32.4)
32 / 29 / 25
35 / 34 / 32
38 / 35 / 32
1, 220-240, 50
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
1, 220, 60
EEV
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
White
White
White
PT-UUC(Grill), PT-UUD(Panel)

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are Net Capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Cassette 1-Way

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specifications
* Model Name
A:Basic, C:Plasma

Cooling Capacity

Heating Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Casing
Body
Dimensions (WxDxH)
Front Panel
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

mm
inch
mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
Body
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Panel Color
Panel Name(Accessory)

, V, Hz

1Way Ceiling Cassette


ARNU18GTT*2
ARNU24GTT*2
5.6
7.1
4,800
6,100
19,100
24,200
6.3
7.1
5,400
6,100
21,500
24,200
Galvanized Steel Plate
Galvanized Steel Plate
1180 x 450 x 132
1180 x 450 x 132
13.3 x 17.7 x 5.2
46.5 x 17.7 x 5.2
1420 x 500 x 34
1420 x 500 x 34
55.9 x 19.7 x 1.3
55.9 x 19.7 x 1.3
2 x 12 x 18
2 x 12 x 18
0.24
0.24
Cross Flow Fan
Cross Flow Fan
30
30
0.30
0.30
13.3 / 12.1 / 10.9
14.6 / 13.3 / 11.5
515.4 / 427.1 / 384.8
575.4 / 469.5 / 406
Direct
Direct
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Fuse
Fuse
6.35(1/4)
9.52(3/8)
12.7(1/2)
15.88(5/8)
25(1)
25(1)
18.7(41.23)
18.7(41.23)
40 / 37 / 35
43 / 40 / 36
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
White
White
PT-UTC(Grill), PT-UTD(Panel)

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are Net Capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Ceiling Cassette 1-Way _ 3

Indoor Units

Type
Model

109.5

1100

88

106.8
206.6
275.8
57.4
96.5
168.3

4 _ Ceiling Cassette 1-Way


1012

861

109.5

44
34

500

46.5

27

Air suction grill


Air discharge grill

3
4

(unit : mm)

Unit size(7k, 9k, 12k):12.7

Unit size(7k, 9k, 12k):6.35

Descripition

CHASSIS CODE: TU

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Gas pipe connection

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

(Panel Name: PT-UUC)

320.5

453

Liquid pipe connection

Name

Number

ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2

Ceiling Cassette 1-way

Indoor Units

3. Dimensions

Ceiling Cassette 1-Way _ 5

500

109.5

1012

1100

88

106.8
206.3
275.8
96.5
168.3
57.4

453
354.3

46.5

861

109.5

453
320.5

34

Air discharge grill

Unit size(7k, 9k, 12k):12.7

Unit size(7k, 9k, 12k):6.35

Descripition

(unit : mm)

CHASSIS CODE: TU

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Air suction grill

Gas pipe connection

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

(Panel Name: PT-UUD)

27

Liquid pipe connection

Name

Number

ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2

Indoor Units

117

Ceiling Cassette 1-way

3. Dimensions

46.5

247.5
180.6
65.3

453.8

173.8
96.1
91
20.6 57.4
31.7

500

6 _ Ceiling Cassette 1-Way

34

109.5

1332

1176.4

1420

65.1

109.5

453.8

44

CHASSIS CODE: TT

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Air suction grill


Air discharge grill

Unit size(18k):12.7, (24k):15.88

Gas pipe connection

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

(Panel Name: PT-UTC)

(unit : mm)
Descripition

Liquid pipe connection Unit size(18k):6.35, (24k):9.52

Name

Number

ARNU18GTT*2
ARNU24GTT*2

Ceiling Cassette 1-way

Indoor Units

3. Dimensions

Ceiling Cassette 1-Way _ 7

65.3

453.8
247.5
180.6

173.8
97.1
91

500

57.4
31.7
20.6

46.5

34

109.5

1332

1420

14

65.1

15.2

1176.4

22.3

57
132
109.5

335

453.8

Air discharge grill

CHASSIS CODE: TT

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Air suction grill

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

(Panel Name: PT-UTD)

96.5

Gas pipe connection

Unit size(18k):12.7, (24k):15.88

Liquid pipe connection Unit size(18k):6.35, (24k):9.52

Descripition

Name

(unit : mm)
1

Number

ARNU18GTT*2
ARNU24GTT*2

Indoor Units

44

Ceiling Cassette 1-way

3. Dimensions

4. Piping Diagrams

Indoor Units

Heat Exchanger

EEV

Filter

:Cooling
:Heating

Th2

Th3
C.F.F.

Filter
Th1

lndoor unit

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

Model

Gas

Liquid

12.7(1/2)

6.35(1/4)

15.88(5/8)

9.52(3/8)

ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2
ARNU18GTT*2
ARNU24GTT*2

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

8 _ Ceiling Cassette 1-Way

5. Wiring Diagrams
TU, TT Chassis
Indoor Units

CONNECTOR NUMBER
CN-MOTOR1
CN-D/PUMP
CN-485
CN-DISP
CN-EEV
CN-VANE2
CN-FLOAT
CN-PIPE/IN
CN-PIPE/OUT
CN-ROOM
CN-REMO
CN-CC
CN-OPTION
CN-COM
CN-VANE1

LOCATION POINT
Fan motor output
Drain pump output
Communication
Display
EEV Output
Step motor
Float switch input
Suction pipe sensor
Discharge pipe sensor
Room sensor
Remote controller
Dry contact
Option pwb.
Communication
Step motor

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION
Motor output of BLDC
AC output for drain pump
Connection between indoor and outdoor
Display of indoor status
EEV Control output
Step motor output
Float switch sensing
Pipe in thermistor
Pipe out thermistor
Room air thermistor
Remote control line
Dry contact line
Communication between main and option
Communication between indoor and outdoor
Step motor output

Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

Ceiling Cassette 1-Way _ 9

6. Capacity Tables

Indoor Units

6.1 Cooling Capacity

Capacity
Index

2.2

2.8

3.6

Outdoor
air temp.
(DB, C)
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

Cooling capacity

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

Notes:
TC: Total Capacity(kW)

10 _ Ceiling Cassette 1-Way

1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

SHC: Sensible Heat Capacity(kW)

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

30
22
TC SHC
kW
kW
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

32
24
TC SHC
kW kW
2.9
2.9
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8

1.7
1.6
1.6
1.6
1.6
1.6
1.5
1.5
1.5
1.5
1.5
1.4
1.4
1.4
1.4
1.4
2.1
2.1
2.1
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.9
1.8
1.8
1.8
1.8
1.7
2.7
2.7
2.7
2.6
2.6
2.5
2.5
2.5
2.5
2.4
2.4
2.4
2.3
2.3
2.3
2.2

6. Capacity Tables

5.6

7.1

Outdoor
air temp.
(DB, C)
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

Notes:
TC: Total Capacity(kW)

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7

5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9

5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1

3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6

4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1

30
22
TC SHC
kW
kW
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3

32
24
TC SHC
kW kW
7.4
7.3
7.2
7.1
7.0
6.9
6.8
6.7
6.6
6.6
6.5
6.4
6.3
6.2
6.1
6.0
9.3
9.2
9.1
9.0
8.8
8.7
8.7
8.5
8.4
8.3
8.2
8.1
7.9
7.8
7.7
7.6

4.2
4.1
4.1
4.0
4.0
3.9
3.9
3.8
3.8
3.7
3.7
3.6
3.6
3.5
3.5
3.4
5.3
5.2
5.2
5.1
5.0
5.0
4.9
4.9
4.8
4.7
4.7
4.6
4.5
4.4
4.4
4.3

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 1-Way _ 11

Indoor Units

Capacity
Index

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

6. Capacity Tables

Indoor Units

6.2 Heating Capacity


Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

2.2

2.8

3.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

Heating capacity
Indoor air temp. (DB, C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.8
2.8
2.9
2.9
2.9
2.9
2.9
2.1
2.2
2.3
2.5
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.6
3.6
3.7
3.7
3.7
3.7
3.7
2.7
2.8
2.9
3.1
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.4
4.5
4.6
4.6
4.6
4.6
4.6

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
2.7
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.3
4.3
4.3
4.3
4.3
4.3
4.3

1.7
1.7
1.8
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.5
2.5
2.5
2.5
2.1
2.2
2.3
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2
2.7
2.8
2.9
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
2.6
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

1.7
1.7
1.8
1.9
2.0
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.1
2.2
2.3
2.4
2.6
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Notes:
TC: Total Capacity(kW)

12 _ Ceiling Cassette 1-Way

6. Capacity Tables
Heating capacity

5.6

7.1

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

4.2
4.3
4.6
4.9
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
7.0
7.1
7.2
7.2
7.2
7.2
7.2
4.8
4.9
5.2
5.5
5.8
6.0
6.1
6.2
6.5
6.7
7.0
7.5
7.9
8.0
8.2
8.2
8.2
8.2
8.2

4.2
4.3
4.6
4.8
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
6.7
6.7
6.7
6.7
6.7
6.7
6.7
4.8
4.9
5.2
5.4
5.8
6.0
6.1
6.2
6.5
6.7
7.0
7.5
7.6
7.6
7.6
7.6
7.6
7.6
7.6

4.2
4.3
4.6
4.3
4.5
4.8
4.9
5.0
5.1
5.4
5.5
5.8
6.2
6.3
6.3
6.3
6.3
6.3
6.3
4.8
4.9
5.2
4.9
5.1
5.4
5.5
5.6
5.8
6.0
6.2
6.6
6.9
7.1
7.1
7.1
7.1
7.1
7.1

4.2
4.3
4.6
4.8
5.0
5.4
5.4
5.5
5.6
5.8
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
4.7
4.9
5.2
5.4
5.7
6.0
6.1
6.2
6.3
6.6
6.8
6.9
6.9
6.9
6.9
6.9
6.9
6.9
6.9

4.2
4.3
4.6
4.8
5.0
5.3
5.4
5.5
5.6
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
4.7
4.8
5.2
5.4
5.7
6.0
6.1
6.2
6.3
6.6
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7

4.2
4.3
4.5
4.8
5.0
5.3
5.4
5.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
4.7
4.8
5.1
5.4
5.7
6.0
6.0
6.1
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2

Notes:
TC: Total Capacity(kW)

Ceiling Cassette 1-Way _ 13

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU07GTU*2
Cooling

Heating
Discharge angle: 60C
Air velocity [m/s]

0.1

2m

2.0

2m

0.5

2.
5

0.1

0.5

22

.5

0.
1

0.1

0.1

0.5

0.5

1.5

1.0
3.5.
43
.0
5

Air velocity [m/s]


0.5

1.0

0.1

1.0

05

0.
5

0.5

1m

1.0

0.5

1m

0.1
1.0

1.5

0.5

0.5

0.5

0.5

1.5

1.5

5
0.

1
0.

0.1

0.5

0.5
1

4m

0.5

3m

0.1

2m

1m

5m

Temperature [C]

4m

0.5

0.5

0.5

0.5

3m

01

2m

1m

Temperature [C]

32

32
14

30

30

16
20

31

32

33

34

2m

31

36

3
37 8

32

34
31

35

24

22

2m

36

31

28

28

35

34

30

28

26

24

4327

32

30

41 3
396

5m

26

32

1m

35

37
36

24

1m
34

28

26

30

33

28

30

28

24

32

36

26

4m

3m

28

26

28

30

5m

2m

31

0
5m

1m

35

4m

36

35

34

3m

2m

1m

ARNU09GTU*2
Cooling

Heating

Discharge angle: 50C

Discharge angle: 60C

Air velocity [m/s]

Air velocity [m/s]


2.5
0.5

3.0

2.
0
0.5

1.0
1.5

0.5

1.0

1.0

0.5

0.5

0.5

5
0.

1m

1.5

1m

0.5

01

0.5

1.5

0.5

0.5

2m

0.1

1.0

1.5

2m

0.1

0.1

5
0.
0.5

0.1

1.5 1.5

2.
5 3
.5
5
1.

0.5

0.1

0.1

0.5

1
0.5

4m

0.5

3m

2m

1m

5m

Temperature [C]

4m

1.0
0.5

01

3m

2m

1m

Temperature [C]

32

31 32

2284
20

32

38

18

30

32

35

30

22

32

43
38326354
9

5m

36

33
37
36
33

30

32

22

2m
36

26 28

26

31

2m

28

24

1m

36

33

34
35
37

34

3231

24

30

28

1m

4m

28

3m

26

26
30 28

2m

1m

32

0
0

33

32

26

30

5m

36

31

24

34

35

28

28

Indoor Units

Discharge angle: 50C

5m

4m

36

35

34

3m

2m

0
1m

Note:
The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m

14 _ Ceiling Cassette 1-Way

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU12GTU*2
Cooling

Heating

Discharge angle: 50C

Discharge angle: 60C

1.0

0.1

2.
5

0.5

1.0

1. 0.
05

2m
1.5

1m

0.5

0.1

0.1

0.
5

0.1

0.1

0.5

1.5

0.5

5
0.

1.50.5

1.5

0.5

0.
5

5
1.
0.5

2.
0

0.5

1
0.

2m

05

0.1

11.5
.0 2.
420.5
.0

2 11
.5

Air velocity [m/s]


1.5

1m

1.0

3m

2m

1.0

1m

01

5m

4m

3m

2m

1m

Temperature [C]

32

32

32

32

28

31

32

37
41

30

3
4064

Temperature [C]

0.5

4m

05

0.5

5
0.

5m

0.5

1.0

1.0

1.5

0.5

0.5

0.5

30

26

33

2m

2m

33

37
32

4m

36

35

34
36

31

24

26

34

24

28

3m

36

33

5m

26

30

1m

37

28

28

38

24

28

22

32

30

28

3635

28

31

26

28

30

1m

26

34

39

31

26

2m

5m

1m

37

35

34

32

4m

3536

3m

2m

1m

ARNU18GTT*2
Cooling

Heating

Discharge angle: 50C

Discharge angle: 60C

Air velocity [m/s]

Air velocity [m/s]


1

0.53

.5

01.5
43.5

2
1.5

2.
5

2m

2m

0.5

0.5
0.5

1.5

1.5

0.5

1.5
2

0.5

0.5

5
0.

0.5
0.5

1 0.5

5
0.

2.
5

0.5

.5
1 4

1.5

1m

1.5

1m

0.5

0.5

0.5

0.5

1
.5

0.5

0.5

4m

3m

0
2m

1m

0
5m

4m

3m

2m

1m

Temperature [C]

Temperature [C]
32

32

32

32

3364

30

30
39
40

30

32

26

22

2m
33

31

34

35

24

34

30

28
33

4m

3m

36

33

26

34

24

2826

5m

1m

36

28

36

37

1m

36

32

24

24

31

2628

28

2m

35 33

30

32

32 1
4

38

22

18
28

35

202

31

34

5m

31

0
2m

1m

5m

4m

3m

2m

1m

Note:
The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m

Ceiling Cassette 1-Way _ 15

Indoor Units

Air velocity [m/s]

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU24GTT*2
Cooling

Heating
Discharge angle: 60C

Air velocity [m/s]

Air velocity [m/s]


2.
5

1.5

2m

2
1.5

0.5

1.5

0.5

1m

05

0.5

1
1.5

0 .5

1.5 0.5

0.5

0.5

0.
1.55

1
5
0.

2m

0.
5

0.5

32

.5
4.5

5
0.

1 1.
52

0.5

3.5

0.5

1m

0.5

1.5

1.5

0.5
1

0.5

5m

4m

0.5

3m

2m

1m

0
5m

4m

3m

2m

1m

Temperature [C]

Temperature [C]
32

32

32
161

36

32

31

30

26
22

2m

2m
38

22

31

28

28

39

32333

20

28

32

40

30 24

35

30

30

36

36
37

36

33

1m

24

35

34

30

33

28

31

36

32

1m

34

26

35

37

24

33

24

28

34

28

28

31

30

26

Indoor Units

Discharge angle: 50C

28

5m

4m

3m

0
2m

1m

5m

4m

3m

2m

1m

Note:
The standard setup height is 2.7m. Shown here is the measurement distribution at the ceiling height of 2.7m

16 _ Ceiling Cassette 1-Way

8. Electric Characteristics
Units

Power Supply

Input(W)

kW

FLA

1.23

15

0.03

0.18

40

40

1.23

15

0.03

0.18

40

40

1.23

15

0.03

0.18

40

40

1.38

15

0.03

0.30

70

70

TT

1.38

15

0.03

0.30

70

70

ARNU07GTU*2

TU

1.23

15

0.03

0.18

40

40

ARNU09GTU*2

TU

1.23

15

0.03

0.18

40

40

ARNU12GTU*2

TU

1.23

15

0.03

0.18

40

40

ARNU18GTT*2

TT

1.38

15

0.03

0.30

70

70

ARNU24GTT*2

TT

1.38

15

0.03

0.30

70

70

Type

ARNU07GTU*2

TU

ARNU09GTU*2

TU

ARNU12GTU*2

TU

ARNU18GTT*2

TT

ARNU24GTT*2

Hz

50

Volts

220-240

60

220

Max:264
Min:198

Max:242
Min:198

Cooling Heating

Symbols:
MCA : Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the larger value on the MCA.
5. Instead of fuse, use Circuit Breaker.

Ceiling Cassette 1-Way _ 17

Indoor Units

MFA

Model

Voltage Range MCA

IFM

9. Sound Levels

Indoor Units

Overall
Notes:
- Sound measured at 1.5m away from the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operating condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

1.5m
Microphone

Sound Levels dB(A)


H
M
L

Model
ARNU07GTU*2
ARNU09GTU*2
ARNU12GTU*2
ARNU18GTT*2
ARNU24GTT*2

32
35
38
40
43

29
34
35
37
40

25
32
32
35
36

Sound Pressure Level


ARNU09GTU*2

ARNU12GTU*2
XP

WP

WP

WP

nc MVU

VP
nc MVP
nc MUU

UP

nc MUP
nc MTU

TP

nc MTP
nc MSU

SP

nc MSP

RP

nc MRU

a
h@
t

ncMVP
ncMUU

UP
ncMUP
ncMTU

TP
ncMTP

nc MQU

QRU

RUP

UPP

QPPP

RPPP

TPPP

XPPP

o@b@c@f@HhI

18 _ Ceiling Cassette 1-Way

ncMSU

SP

ncMSP

ncMRU

RP

nc MRP

QP
VS

ncMVU

VP

QP

a
h
t
VS

o@b@s@p@l@Hb@@RPp@I

XP

o@b@s@p@l@Hb@@RPp@I

o@b@s@p@l@Hb@@RPp@I

ARNU07GTU*2
XP

NC-65

VP
NC-60
NC-55

UP
NC-50
NC-45

TP
NC-40

NC-30

QRU

RUP

UPP

QPPP

RPPP

TPPP

o@b@c@f@HhI

XPPP

NC-25

RP

ncMRP
ncMQU

NC-35

SP

QP

Approximate
Hearing
Threshold
VS

NC-20
NC-15

QRU

RUP

UPP

QPPP

RPPP

TPPP

o@b@c@f@HhI

XPPP

9. Sound Levels
ARNU24GTT*2
80

70

70

NC-65
60
NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

NC-25

20
Approximate
Hearing
Threshold

NC-65
60
NC-60

10
125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

20

NC-20
NC-15

63

o@b@s@p@l@Hb@@RPp@I

80

Indoor Units

o@b@s@p@l@Hb@@RPp@I

ARNU18GTT*2

10

NC-25
Approximate
Hearing
Threshold
63

NC-20

125

250

500

1000

2000

4000

NC-15
8000

Octave Band Center Frequency (Hz)

Ceiling Cassette 1-Way _ 19

10. Installation

Indoor Units

Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Outlet

TEM
P

Remote
Controlle
r

Inlet

Required Parts
Connecting cable
Pipes: Gas side
Liquid side
Hanging Bolt
(W 3/8 or M10 length 650mm)
Insulated drain hose
Additional Drain hose

Wired remote
controller

Required Tools
Level
Screw driver
Electric drill
Hole core drill
Flaring Tool set
Torque Wrenches
Hexagonal Wrench
Gas-leak detector
Thermometer

20 _ Ceiling Cassette 1-Way

Ceiling board

500 or
more

300 or less

500 or
more

Above 2500
3300 or less

Ceiling
Ceiling board

1000
or more

There should not be any heat source or steam near the


unit.
There should not be any obstacles to the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall,
ceiling, or other obstacles.
The indoor unit must have the maintenance space.

200 or more

10.1 Selection of the best location

Unit:mm
Floor

10. Installation
10.2 Ceiling opening dimensions and hanging bolt location
1,385
1,285

50

50

354
466

1,180

448

306

400

40

600

40

Ceiling
250

TT Chassis

Level gauge

1,065
600

965

50

250

448

860

354
466

This air-conditioner uses a drain pump.


Install the unit horizontally using a level gauge.
During the installation, care should be taken not to
damage electric wires.

40

400

CAUTION

306

40

50

TU Chassis

Select and mark the position for fixing bolts and piping hole.
Decide the position for fixing bolts slightly tilted to
the drain direction after considering the direction of
drain hose.
Drill the hole for anchor bolt on the wall.

(unit: mm)

Ceiling board

NOTE:
Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
Make sure that ventilation fan is enough to cover all noxious gases from this place.
Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.
Air conditioner

Take enough
distance
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table

2. Avoid installing air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.

Ceiling Cassette 1-Way _ 21

Indoor Units

The dimensions of the paper model for installation


are the same as those of the ceiling opening dimensions.

10. Installation
Ceiling

Indoor Units

Nut
(W3/8 or M10)

70mm

Keep the length of the bolt


from the bracket to 40mm

Hanging bolt
(W3/8 or M10)

Flat washer for M10


(accessory) Ceiling board

Spring washer
(M10)

Flat washer for M10


(accessory)
Nut
(W3/8 or M10)

Air conditioner body

Set screw of
paper model (4 pieces)

Paper model
for installation

Open the ceiling board


along the outer edge of the
paper model

Adjust the same height

The following parts are local purchasing.


Hanging bolt - W 3/8 or M10
Nut
- W 3/8 or M10
Spring washer - M10
Plate washer - M10

Ceiling board

CAUTION
Tighten the nut and bolt to prevent the unit
from falling.

10.3 Wiring Connection


Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit
respectively.
Terminal block of outdoor unit
Terminal block of indoor unit
1(L)

2(N)

Outdoor unit Indoor unit

SODU SODU IDU IDU INTERNET DRY1 DRY2 GND 12V

Indoor power input

WARNING
Make sure that the screws of the terminal are not loose.

22 _ Ceiling Cassette 1-Way

Central controller

10. Installation
10.4 Installation of Decoration Panel (Panel Type)

1. Open the air outlet vane, and extract side covers.


2. Remove the air inlet panel from the decoration panel.
3. Hook decoration panel to indoor unit, using hooks attached at the backside of both side of decoration
panel.
4. Arrange wires not to get caught between decoration panel and indoor unit.
5. Screw 7 fixing screws. (7,9,12kBtu : 6 screws)
6. Connect the vane motor connector ,display connector and air inlet panel connector.
7. Install the air inlet panel (including the air filter) and side covers.
Air conditioner unit

Mesh
Control box cover

Side cover
Robot kit
Decorative panel
fixing screws
(hexagon M6 screws)
(tightening about 20mm)

Air inlet panel

Decorative panel
Air outlet vane

CAUTION

Install certainly the


decoration panel.
Cool air leakage causes sweating.
Waterdrops fall.

Good example

Bad example
Air conditioner
unit
Cool air leakage
(no good)
Ceiling
board
Decorative panel

Air conditioner
unit
Ceiling
board
Decorative panel

Fit the insulator (this part) and


be careful for cool air leakage

Ceiling Cassette 1-Way _ 23

Indoor Units

Before installing the decoration panel,


always remove the paper template.

The decoration panel has its installation


direction.

10. Installation

Indoor Units

10.5 Installation of Decoration Panel(Grille Type)


Before installing the decoration panel,
always remove the paper template.

The decoration panel has its installation


direction.
1. Open the air outlet vane, and extract side covers.
2. Remove the air inlet grille from the decoration panel.

3. Hook decoration panel to indoor unit, using hooks attached at the backside of both side of decoration
panel.
4. Arrange wires not to get caught between decoration panel and indoor unit.
5. Screw 7 fixing screws. (7,9,12kBtu : 6 screws)
6. Connect the vane motor connector and display connector. (Plasma connector for plasma model)
7. Install the air inlet grille (including the air filter) and side covers.

Air conditioner unit

Mesh
Control box cover

Side cover
Plasma filter
(applied only to plasma model)
Decorative panel
fixing screws
(hexagon M6 screws)
(tightening about 20mm)
Air inlet grille

Decorative panel
Air inlet grille

CAUTION

Install certainly the


decoration panel.
Cool air leakage causes sweating.
Waterdrops fall.

Good example

Bad example
Air conditioner
unit
Cool air leakage
(no good)
Ceiling
board
Decorative panel

Fit the insulator (this part) and


be careful for cool air leakage

24 _ Ceiling Cassette 1-Way

Air conditioner
unit
Ceiling
board
Decorative panel

10. Installation
10.6 Indoor Unit Drain Piping

Piping material: Polyvinyl chloride pipe 25mm


and pipe fittings

Upward
routing
not allowed

Pipe clamp

Indoor Units

Drain piping must have down-slope (1/50 to 1/100): be sure


not to provide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra
force on the drain port on the indoor unit.
The outside diameter of the drain connection on the indoor
unit is 32mm.

Indoor unit

Maintenance
drain port

Be sure to install heat insulation on the drain piping.


1/50~1/100

Heat insulation material: Polyethylene foam with


thickness more than 8 mm.

Max 700mm

Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose


(accessory)
Main
drain pipe

Drain pump

Drain
port

Glue the joint

Drain hose connection


Use the clip (accessory)

Connect the main drain pipe to the exterior


and leave it provisionally until the test comes
to an end.
Feed water to the flexible drain hose and
check the piping for leakage.
Be sure to check the drain pump for normal
operating and noise when electrical wiring is
complete.
When the test is complete, connect the flexible drain hose to the drain port on the indoor
unit.

Drain pan

CAUTION
Max 300mm
Metal
clamp
Flexible drain hose

Hanger bracket
1/50~1/100 slope
Max 700mm

The supplied flexible drain hose should not be curved,


neither screwed. The curved or screwed hose may
cause a leakage of water.

Hanger
distance
1~15m

Insulation

Ceiling Cassette 1-Way _ 25

10. Installation

Indoor Units

CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit
diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to
which the unit is subjected during the course of transportation. Check them and make sure that they are all
tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Confirm the Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name
plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of
a overload protection device.
Proper starting power is not given to the compressor.

WIRED REMOTE CONTROLLER INSTALLATION


Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away
from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's,
the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Remote Controller

5feet
(1.5meters)

TEMP

Controller
Remote

no

no

Fig.1 Typical locations for remote controller

26 _ Ceiling Cassette 1-Way

11. Accessories
Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for
hanging bracket
8 EA

Plastic band

Insulation for
fitting

4 EA

1 SET

Shape

for gas pipe

for liquid pipe

Name

Paper pattern for installation

Installation and Owner's manual

Quantity

1EA

1EA

Shape

CAUTION
Use only those accessories (Standard or optional) which have designated specifications.

Ceiling Cassette 1-Way _ 27

Indoor Units

Name

Indoor unit
Ceiling Cassette 2-Way
1. List of functions
2. Specifications
3. Dimensions
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. Air Velocity and Temperature Distribution
8. Electric Characteristics
9. Sound Levels
10. Installation
11. Accessories

1. List of functions
Category

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Air supply outlet


Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU18GTL*2, ARNU24GTL*2
2
Auto
O
4/5/4
X
O
O
X
Option
O
O
O
X
O
O
O
O
O(Heat recovery)
X
O(Heat pump or Cooling only)
O
O
O
O
O
O
O
O
Accessory
Accessory
Accessory
Accessory
X
Accessory
-

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

Ceiling Cassette 2-way _ 1

Indoor Units

Air flow

Function

2. Specifications

Indoor Units

* Model Name
A:Basic, C:Plasma
Type
Model
Cooling Capacity

Heating Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Casing
Body
Dimensions (WxDxH)
Front Panel
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

mm
inch
mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
Body
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Panel Color
Panel Name(Accessory)

, V, Hz

2Way Ceiling Cassette


ARNU18GTL*2
5.6
4,800
19,100
6.3
5,400
21,500
Galvanized Steel Plate
830 x 550 x 225
32.6 x 21.6 x 8.9
1,050 x 640 x 28.5
41.3 x 25.2 x 1.1
2 x 11 x 20
0.13
Cross Flow Fan
20 x 2
0.18 x 2
13 / 12 / 10
459 / 424 / 353
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Fuse
6.35(1/4)
12.7(1/2)
25(1)
22(48.5)
40 / 36 / 32
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C
Morning fog
PT-HL*

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are Net Capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Cassette 2-way

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specifications
* Model Name
A:Basic, C:Plasma

Cooling Capacity

Heating Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Casing
Body
Dimensions (WxDxH)
Front Panel
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

mm
inch
mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
Body
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Panel Color
Panel Name(Accessory)

, V, Hz

2Way Ceiling Cassette


ARNU24GTL*2
7.1
6,100
24,200
8.0
6,900
27,300
Galvanized Steel Plate
830 x 550 x 225
32.6 x 21.6 x 8.9
1,050 x 640 x 28.5
41.3 x 25.2 x 1.1
2 x 11 x 20
0.13
Cross Flow Fan
20 x 2
0.18 x 2
17 / 15 / 13
601 / 530 / 459
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Fuse
9.52(3/8)
15.88(5/8)
25(1)
22(48.5)
42 / 38 / 34
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C
Morning fog
PT-HL*

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are Net Capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Ceiling Cassette 2-way _ 3

Indoor Units

Type
Model

35.6

144.2

893

931.2
830
34
1

482
550

2
205.5
69.2

4 _ Ceiling Cassette 2-way


177.1
225

6.5

92

206.5
69.2

162.4

Air discharge grill

Unit size(24k):15.88

Unit size(18k):12.7

Unit size(24k):9.52

Unit size(18k):6.35

Descripition

(unit : mm)

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

CHASSIS CODE: TL

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Air suction grill

Gas pipe connection

2
3

Liquid pipe connection

Name

Number

ARNU18GTL*2
ARNU24GTL*2

Ceiling Cassette 2-way

Indoor Units

3. Dimensions

4. Piping Diagrams

EEV

Filter

:Cooling
:Heating

Th2

Th3
C.F.F.

Filter
Th1

lndoor unit

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

Model

Gas

Liquid

ARNU18GTL*2

12.7(1/2)

6.35(1/4)

ARNU24GTL*2

15.88(5/8)

9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Cassette 2-way _ 5

Indoor Units

Heat Exchanger

5. Wiring Diagrams

Indoor Units

TL Chassis

CONNECTOR NUMBER
CN-POWER
CN-MOTOR1
CN-MOTOR2
CN-D/PUMP
CN-485
CN-DISP
CN-EEV
CN-VANE2
CN-FLOAT
CN-PIPE/IN
CN-PIPE/OUT
CN-ROOM
CN-REMO

SPEC
AC Power supply
Fan motor output
Fan motor output
Drain pump output
Communication
Display
EEV Output
Step motor
Float switch input
Suction pipe sensor
Discharge pipe sensor
Room sensor
Remote controller

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

DESCRIPTION
AC Power line input for indoor controller
Motor output of BLDC
Motor output of BLDC
AC output for drain pump
Connection between indoor and outdoor
Display of indoor status
EEV Control output
Step motor output
Float switch sensing
Pipe in thermistor
Pipe out thermistor
Room air thermistor
Remote control line
Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

6 _ Ceiling Cassette 2-way

6. Capacity Tables
6.1 Cooling Capacity

5.6

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

10

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.4

4.2

12

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.3

4.1

14

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.2

4.1

16

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.1

4.0

18

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

7.0

4.0

20

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.9

3.9

21

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.8

3.9

23

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.7

4.2

6.7

3.8

25

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.6

4.2

6.6

3.8

27

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.4

4.1

6.6

3.7

29

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.4

4.0

6.5

3.7

31

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.3

3.9

6.4

3.6

33

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.2

3.9

6.3

3.6

35

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

6.0

4.0

6.0

3.8

6.2

3.5

37

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

5.8

3.9

5.9

3.7

6.1

3.5

39

3.8

3.2

4.5

3.6

5.2

3.9

5.6

3.9

5.7

3.9

5.8

3.7

6.0

3.4

Outdoor
air temp.
(DB, C)

Notes:
TC: Total Capacity(kW)

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 2-way _ 7

Indoor Units

Capacity
Index

Cooling capacity

6. Capacity Tables

Indoor Units

Cooling capacity

Capacity
Index

7.1

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

10

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.3

5.3

12

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.2

5.2

14

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.1

5.2

16

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

9.0

5.1

18

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.8

5.0

20

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.7

5.0

21

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.7

4.9

23

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.5

5.3

8.5

4.9

25

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.4

5.3

8.4

4.8

27

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.2

5.1

8.3

4.7

29

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.1

5.1

8.2

4.7

31

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

8.0

5.0

8.1

4.6

33

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

7.8

4.9

7.9

4.5

35

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.6

5.1

7.7

4.8

7.8

4.4

37

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.4

5.0

7.5

4.7

7.7

4.4

39

4.8

4.1

5.7

4.5

6.6

4.9

7.1

5.0

7.2

4.9

7.4

4.6

7.6

4.3

Outdoor
air temp.
(DB, C)

Notes:
TC: Total Capacity(kW)

8 _ Ceiling Cassette 2-way

SHC: Sensible Heat Capacity(kW)

6. Capacity Tables
6.2 Heating Capacity

5.6

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

-19.8 -20.0

kW
4.2

kW
4.2

kW
4.2

kW
4.2

kW
4.2

kW
4.2

-18.8 -19.0

4.3

4.3

4.3

4.3

4.3

4.3

-16.7 -17.0

4.6

4.6

4.6

4.6

4.6

4.5

-14.7 -15.0

4.9

4.8

4.3

4.8

4.8

4.8

-12.6 -13.0

5.1

5.1

4.5

5.0

5.0

5.0

-10.5 -11.0

5.4

5.4

4.8

5.4

5.3

5.3

-9.5 -10.0

5.4

5.4

4.9

5.4

5.4

5.4

-8.5

-9.1

5.5

5.5

5.0

5.5

5.5

5.4

-7.0

-7.6

5.7

5.7

5.1

5.6

5.6

5.5

-5.0

-5.6

6.0

6.0

5.4

5.8

5.8

5.5

-3.0

-3.7

6.2

6.2

5.5

6.1

5.9

5.5

0.0

-0.7

6.6

6.6

5.8

6.1

5.9

5.5

3.0

2.2

7.0

6.7

6.2

6.1

5.9

5.5

5.0

4.1

7.1

6.7

6.3

6.1

5.9

5.5

7.0

6.0

7.2

6.7

6.3

6.1

5.9

5.5

9.0

7.9

7.2

6.7

6.3

6.1

5.9

5.5

11.0

9.8

7.2

6.7

6.3

6.1

5.9

5.5

13.0 11.8

7.2

6.7

6.3

6.1

5.9

5.5

15.0 13.7

7.2

6.7

6.3

6.1

5.9

5.5

Notes:
TC: Total Capacity(kW)

Ceiling Cassette 2-way _ 9

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Heating capacity

6. Capacity Tables

Indoor Units

Heating capacity
Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

7.1

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

-19.8 -20.0

kW
5.4

kW
5.4

kW
5.4

kW
5.3

kW
5.3

kW
5.3

-18.8 -19.0

5.5

5.5

5.5

5.5

5.4

5.4

-16.7 -17.0

5.8

5.8

5.8

5.8

5.8

5.8

-14.7 -15.0

6.2

6.1

5.5

6.1

6.1

6.1

-12.6 -13.0

6.5

6.5

5.8

6.4

6.4

6.4

-10.5 -11.0

6.8

6.8

6.0

6.8

6.7

6.7

-9.5 -10.0

6.9

6.9

6.2

6.9

6.9

6.8

-8.5

-9.1

7.0

7.0

6.3

7.0

7.0

6.8

-7.0

-7.6

7.3

7.3

6.5

7.1

7.1

7.0

-5.0

-5.6

7.6

7.6

6.8

7.4

7.4

7.0

-3.0

-3.7

7.9

7.9

7.0

7.7

7.5

7.0

0.0

-0.7

8.4

8.4

7.4

7.8

7.5

7.0

3.0

2.2

8.9

8.6

7.8

7.8

7.5

7.0

5.0

4.1

9.0

8.6

8.0

7.8

7.5

7.0

7.0

6.0

9.2

8.6

8.0

7.8

7.5

7.0

9.0

7.9

9.2

8.6

8.0

7.8

7.5

7.0

11.0

9.8

9.2

8.6

8.0

7.8

7.5

7.0

13.0 11.8

9.2

8.6

8.0

7.8

7.5

7.0

15.0 13.7

9.2

8.6

8.0

7.8

7.5

7.0

Notes:
TC: Total Capacity(kW)

10 _ Ceiling Cassette 2-way

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU24GTL*2
Cooling

Heating
Discharge angle: 60

Air velocity [m/s]

Air velocity [m/s]


2.7m

2.0

2.5

3.0

3.0

2.5

2m

2.0

1.5

1.5

1.0

1.0

0.5

4m

2.7m
2.5
2.0
1.5

1m

2m

1m

0m

1m

2m

0m
4m

3m

Temperature [C]

21

20

20

0.5

4m

3m

2m

22

0m

32
31

2m

23

1m

2m

0m
4m

3m

24

1m

28
26

1m

0m

1m

2m

3m

0m
4m

4m

27

3m

2m

1m

29

2.7m

32
31

30

24

2m

0.5

1m

2.7m
21

23

3m

1m

1.0

Temperature [C]

22

4m

2m

1.5

1.0

0.5

3m

2.5
2.0

2m

30
27

28

29
28

0m

1m

28
27

1m

26

2m

3m

0m
4m

Ceiling Cassette 2-way _ 11

Indoor Units

Discharge angle: 40

8. Electric Characteristics

Indoor Units

Units
Model

Type

ARNU18GTL*2

TL

ARNU24GTL*2

TL

ARNU18GTL*2

TL

ARNU24GTL*2

TL

Power Supply
Hz

Volts

50

220-240

60

220

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

Max:264

0.52

15

0.04

0.41

70

70

Min:198

0.52

15

0.04

0.41

70

70

Max:242

0.52

15

0.04

0.41

70

70

Min:198

0.52

15

0.04

0.41

70

70

Symbols:
MCA : Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the larger value on the MCA.
5. Instead of fuse, use Circuit Breaker.

12 _ Ceiling Cassette 2-way

9. Sound Levels
Overall

1.5m
Microphone

Sound Levels dB(A)

Model

ARNU18GTL*2

40

36

32

ARNU24GTL*2

42

38

34

Sound Pressure Level


ARNU24GTL*2

80

80

70

70

NC-65
60
NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

20

10

NC-25
Approximate
Hearing
Threshold
63

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU18GTL*2

NC-65
60
NC-60

NC-50

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

NC-45

40

NC-40
NC-35

30

NC-30

20

NC-20
NC-15

NC-55

50

10

NC-25
Approximate
Hearing
Threshold
63

NC-20
NC-15
125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

Ceiling Cassette 2-way _ 13

Indoor Units

Notes:
- Sound measured at 1.5m away from the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operating condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

10. Installation

Indoor Units

Please read the instruction sheets completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Anti-bacteria filter
TEMP

Remote Controller

Air Intake
Air Outlet

Required Parts
Connecting cable
Pipes: Gas side
Liquid side
Hanging Bolt
(W 3/8 or M10 length 650mm)
Insulated drain hose
Additional Drain hose

Required Tools
Level
Screw driver
Electric drill
Hole core drill
Flaring Tool set
Torque Wrenches
Hexagonal Wrench
Gas-leak detector
Thermometer

14 _ Ceiling Cassette 2-way

Ceiling Board

50 or
more

30 or less

50 or
more

Above 200
300 or less

Ceiling
Ceiling Board

100
or more

There should not be any heat source or steam near the


unit.
There should not be any obstacles to the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall,
ceiling, or other obstacles.
The indoor unit must have sufficient maintenance
space.

20 or more

10.1 Selection of the best location

Unit:cm
Floor

10. Installation
10.2 Ceiling opening dimensions and hanging bolt location

Ceiling board

Ceiling
Level gauge

CAUTION
This air-conditioner uses a drain pump.
Install the unit horizontally using a level gauge.
During the installation, care should be taken not to
damage electric wires.

Select and mark the position for fixing bolts and


piping hole.
Decide the position for fixing bolts slightly tilted
to the drain direction after considering the direction of drain hose.
Drill the hole for anchor bolt on the wall.

NOTE:
Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
Make sure that ventilation fan is enough to cover all noxious gases from this place.
Ensure enough distance from the cooking room to install the air conditioner in such a place where it may
not suck oily steam.

Air conditioner

Take enough
distance
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.

Ceiling Cassette 2-way _ 15

Indoor Units

The dimensions of the paper pattern for installation


are the same as those of the ceiling opening
dimensions.

10. Installation

Nut
(W3/8 or M10)

90mm

Indoor Units

Ceiling
Keep the length of the bolt
from the bracket to 40mm

Hanging bolt
(W3/8 or M10)

Flat washer for M10


False
(accessory)
ceiling board

Flat washer for M10


(accessory)
Nut
(W3/8 or M10)

Air Conditioner body

Set screw of
paper pattern (4 pieces)

Paper pattern
for installation

Open the ceiling board


along the outer edge of the
paper pattern

Adjust the same height

The following parts are locally purchased.


Hanging Bolt - W 3/8 or M10
Nut
- W 3/8 or M10
Spring Washer - M10
Plate Washer - M10

False ceiling board

CAUTION
Tighten the nut and bolt to prevent the unit
from falling.

10.3 Wiring Connection


Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit
respectively.

Terminal Block Indoor


1(L)

2(N)

SODU

INDOOR POWER INPUT

WARNING
Make sure that the screws of the terminal are not loose.

16 _ Ceiling Cassette 2-way

INTERNET DRY1 DRY2 GND 12V

IDU
-

Outdoor
Unit

10. Installation
10.4 Installation of Decoration Panel

1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by amount 10mm in
length.)
The fixing screws (hexagon M5 screw) are included in the indoor unit box.
2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.)
3. Hook the decoration panel key hole (
) on the screws fixed in step above, and slide the panel so that the screws
reach the key hole edge.
4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5. Connect the louver motor connector and display connector.
6. After tightening these screws, install the air inlet grille
(including the air filter).
Air conditioner unit
Decorative panel
fixing screws
(hexagon M6 screws)
Temporary fitting
at 2 poles
(Tightening about 10mm)

Piping side

Control box cover


Cover

Plasma filter

Louver motor

Key holes

Decorative panel
fixing screws
(Hexagon M6 screw)

Decorative panel
Push

Ratch
pull

Inlet Grille

CAUTION
Install the decoration panel
otherwise cool air leakage
causes condensation.
Water drops fall.

Correct method

Wrong method
Air conditioner
unit
Cool air leakage
(no good)
Ceiling
board
Decoration panel

Air conditioner
unit
Ceiling
board
Decoration panel

Fit the insulator (this part) and


be careful for cool air leakage

Ceiling Cassette 2-way _ 17

Indoor Units

Before installing the decoration panel,


always remove the paper template.

The decoration panel has its installation


direction.

10. Installation
Drain piping must have down-slope (1/50 to 1/100): Make sure
not to provide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra
force on the drain port on the indoor unit.
The outside diameter of the drain connection on the indoor
unit is 32mm.

Upward
routing
not allowed

Pipe clamp
Indoor unit

Maintenance
drain port

Piping material: Polyvinyl chloride pipe inner


diameter 25mm and pipe fittings
1/50~1/100

Make sure to install heat insulation on the drain piping.

MAX 700mm

Heat insulation material: Polyethylene foam with


thickness more than 8 mm.

Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose


(accessory)
Main
drain pipe

Drain Pump

Drain
port

Glue the joint

Drain hose connection


Use the clip (accessory)

Connect the main drain pipe to the exterior and leave it


provisionally until the test comes to an end.
Feed water to the flexible drain hose and check the piping for leakage.
Make sure to check the drain pump for normal operating
and noise when electrical wiring is complete.
When the test is complete, connect the flexible drain
hose to the drain port on the indoor unit.

Drain pan

CAUTION
The supplied flexible drain hose should not be strained.
A strained hose may cause leakage of water.

Max 300mm

Hanger
distance
1~15m

Metal
clamp
Flexible drain hose
Insulation

18 _ Ceiling Cassette 2-way

Hanger Bracket
1/50~1/100 slope
Max 700mm

Indoor Units

10.5 Indoor Unit Drain Piping

10. Installation
CAUTION

HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual.
(air filter cleaning, temperature control, etc.)

WIRED REMOTE CONTROLLER INSTALLATION


Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away
from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller
LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller
Remote

TEMP

Remote Controller

5feet
(1.5meters)

no

no

Fig.1 Typical locations for remote controller

Ceiling Cassette 2-way _ 19

Indoor Units

After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram
pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the
unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are
loose, it could give rise to burn-out of the wires.)
4) Confirm the specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
Proper starting power is not given to the compressor.

11. Accessories

Indoor Units

Standard Accessories
Name

Clamp metal

Drain hose

Insulation for
fitting

Quantity

2 EA

1 EA

1 set

Washer for
hanging bracket
8 EA

Clamp
(Tie Wrap)
4 EA

Bolt

(Other)

4 EA
Paper pattern for
installation
Owner's manual
Installation manual

Shape

for gas pipe

for liquid pipe


Screws for fixing panels are attached to decoration panel.

CAUTION
Use only those accessories (Standard or optional) which have designated specifications.

20 _ Ceiling Cassette 2-way

Indoor unit
Ceiling Cassette 4-way
1. List of functions
2. Specifications
3. Dimensions
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. Air Velocity and Temperature Distribution
8. Electric Characteristics
9. Sound Levels
10. Installation
11. Accessories

1. List of functions

Indoor Units

Category

Air flow

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Function
Air supply outlet
Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Elevation Grill
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU05GTR*2, ARNU07GTR*2, ARNU09GTR*2, ARNU12GTR*2


ARNU15GTQ*2, ARNU18GTQ*2, ARNU24GTP*2, ARNU28GTP*2
ARNU36GTN*2, ARNU42GTM*2, ARNU48GTM*2
4
Auto
O
4/5/4
X
O
O
O
X
Option
O
O
X
X
O
O
O
O
O(Heat recovery)
X
O(Heat pump or Cooling only)
O
O
O
O
O
O
O
O
Accessory (TM,TN,TP only)
Accessory
Accessory
Accessory
Accessory
X
Accessory
-

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.
* Plasma kit and Elevation Grille are not applicable at the same time

1 _ Ceiling Cassette 4-way

2. Specifications
* Model Name
A:Basic, C:Plasma

Cooling Capacity

Heating Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Casing
Body
Dimensions(WxDxH)
Front Panel
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

mm
inch
mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control

Sound Absorbing Thermal Insulation Material


Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
Body
kg(lbs)
Packaged
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Panel Color
Panel Name(Accessory)

, V, Hz
mm2
mm2

ARNU05GTR*2
1.6
1,400
5,500
1.8
1,500
6,100
Galvanized Steel Plate
570 x 570 x 214
22.4 x 22.4 x 8.4
700 x 700 x 30
27.5 x 27.5 x 1.2
1 x 8 x 18
0.21
Turbo Fan
43 x 1
0.2
7.5 / 7.0 / 6.6
265 / 247 / 212
Direct
BLDC
Microprocessor,
Thermostat for cooling
and heating
Foamed polystrene
Fuse
6.35(1/4)
12.7(1/2)
25(1)
13.1(28.9)
15.4(33.9)
29 / 27 / 26
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C
Morning fog

4 Way Ceiling Cassette


ARNU07GTR*2
ARNU09GTR*2
2.2
2.8
1,900
2,400
7,500
9,600
2.5
3.2
2,200
2,800
8,500
10,900
Galvanized Steel Plate Galvanized Steel Plate
570 x 570 x 214
570 x 570 x 214
22.4 x 22.4 x 8.4
22.4 x 22.4 x 8.4
700 x 700 x 30
700 x 700 x 30
27.5 x 27.5 x 1.2
27.5 x 27.5 x 1.2
1 x 8 x 18
2 x 8 x 18
0.21
0.21
Turbo Fan
Turbo Fan
43 x 1
43 x 1
0.2
0.2
7.5 / 7.0 / 6.6
8.0 / 7.5 / 7.1
265 / 247 / 212
283 / 265 / 251
Direct
Direct
BLDC
BLDC
Microprocessor,
Microprocessor,
Thermostat for cooling Thermostat for cooling
and heating
and heating
Foamed polystrene
Foamed polystrene
Fuse
Fuse
6.35(1/4)
6.35(1/4)
12.7(1/2)
12.7(1/2)
25(1)
25(1)
13.1(28.9)
14.2(31.3)
15.4(33.9)
16.5(36.3)
29 / 27 / 26
30 / 29 / 27
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Morning fog
Morning fog
PT-UQC

Notes:1. Capacities are based on the following conditions:


Cooling
Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating
Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Ceiling Cassette 4-way _ 2

Indoor Units

Type
Model

2. Specifications
* Model Name
A:Basic, C:Plasma

Indoor Units

Type
Model
Cooling Capacity

Heating Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Casing
Body
Dimensions(WxDxH)
Front Panel
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

mm
inch
mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control

Sound Absorbing Thermal Insulation Material


Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
Body
kg(lbs)
Packaged
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Panel Color
Panel Name(Accessory)

, V, Hz
mm2
mm2

ARNU12GTR*2
3.6
3,100
12,300
4.0
3,400
13,600
Galvanized Steel Plate
570 x 570 x 214
22.4 x 22.4 x 8.4
700 x 700 x 30
27.5 x 27.5 x 1.2
2 x 8 x 18
0.21
Turbo Fan
43 x 1
0.2
8.7 / 8.0 / 7.0
307 / 283 / 247
Direct
BLDC
Microprocessor,
Thermostat for cooling
and heating
Foamed polystrene
Fuse
6.35(1/4)
12.7(1/2)
25(1)
14.2(31.3)
16.5(36.3)
32 / 30 / 27
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C
Morning fog

4 Way Ceiling Cassette


ARNU15GTQ*2
ARNU18GTQ*2
4.5
5.6
3,900
4,800
15,400
19,100
5.0
6.3
4,300
5,400
17,100
21,500
Galvanized Steel Plate Galvanized Steel Plate
570 x 570 x 256
570 x 570 x 256
22.4 x 22.4 x 10.1
22.4 x 22.4 x 10.1
700 x 700 x 30
700 x 700 x 30
27.5 x 27.5 x 1.2
27.5 x 27.5 x 1.2
2 x 10 x 18
2 x 10 x 18
0.27
0.27
Turbo Fan
Turbo Fan
43 x 1
43 x 1
0.2
0.2
11.0 / 10.0 / 9.3
11.2 / 11.0 / 10.0
388 / 353 / 328
396 / 388 / 353
Direct
Direct
BLDC
BLDC
Microprocessor,
Microprocessor,
Thermostat for cooling Thermostat for cooling
and heating
and heating
Foamed polystrene
Foamed polystrene
Fuse
Fuse
6.35(1/4)
6.35(1/4)
12.7(1/2)
12.7(1/2)
25(1)
25(1)
15.5(34.2)
15.5(34.2)
18.0(39.7)
18.0(39.7)
36 / 34 / 32
37 / 35 / 34
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Morning fog
Morning fog
PT-UQC

Notes:1. Capacities are based on the following conditions:


Cooling
Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating
Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

3 _ Ceiling Cassette 4-way

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specifications
* Model Name
A:Basic, C:Plasma
4 Way Ceiling Cassette
ARNU24GTP*2
ARNU28GTP*2
ARNU36GTN*2
Cooling Capacity
7.1
8.2
10.6
6,100
7,100
9,100
24,200
28,000
36,200
Heating Capacity
8.0
9.2
11.9
6,900
8,000
10,200
27,300
31,500
40,600
Casing
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
Dimensions
Body
mm
840 x 840 x 204
840 x 840 x 204
840 x 840 x 246
(WxDxH)
inch
33.0 x 33.0 x 8.0
33.0 x 33.0 x 8.0
33.0 x 33.0 x 9.7
Front Panel
mm
950 x 950 x 25
950 x 950 x 25
950 x 950 x 25
inch
37.4 x 37.4 x 1
37.4 x 37.4 x 1
37.4 x 37.4 x 1
Coil
Rows x Columns x FPI
2 x 8 x 19
2 x 8 x 19
2x10x19
Face Area
m3
0.40
0.40
0.57
Fan
Type
Turbo Fan
Turbo Fan
Turbo Fan
Motor Outputx Number
W
30
30
135
Running Current
A
0.15
0.15
0.56
Air Flow Rate(H / M / L)
CMM
17 / 15 / 13
19 / 16 / 14
25 / 21 / 19
cfm
600 / 529 / 459
671 / 565 / 494
883 / 742 / 671
Drive
Direct
Direct
Direct
Motor type
BLDC
BLDC
BLDC
Temperature Control
Microprocessor, Thermostat for cooling and heating
Sound Absorbing Thermal Insulation Material
Foamed polystrene
Foamed polystrene
Foamed polystrene
Safety Device
Fuse
Fuse
Fuse
Pipe
Liquid Side
mm(inch)
9.52(3/8)
9.52(3/8)
9.52(3/8)
Connections
Gas Side
mm(inch)
15.88(5/8)
15.88(5/8)
15.88(5/8)
Drain Pipe(Internal Dia.) mm(inch)
25(1)
25(1)
25(1)
Net Weight
Body
kg(lbs)
20.8(45.8)
20.8(45.8)
23.5(51.8)
Noise Level (Sound Press, 1.5m, H / M / L) dB(A)
36 / 34 / 31
39 / 35 / 33
43 / 40 / 37
Power Supply
1, 220-240, 50
1, 220-240, 50
1, 220-240, 50
, V, Hz
1, 220, 60
1, 220, 60
1, 220, 60
Refrigerant Control
EEV
EEV
EEV
Power cord
CV2.0 X 3C
CV2.0 X 3C
CV2.0 X 3C
Transmission cable
CVV-SB 1.25 X 2C
CVV-SB 1.25 X 2C
CVV-SB 1.25 X 2C
Panel Color
Morning fog
Morning fog
Morning fog
Panel Name(Accessory)
PT-UMC
Elevation Grill(Accessory)
PTEGM0
Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Notes:1. Capacities are based on the following conditions:


Cooling
Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating
Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Ceiling Cassette 4-way _ 4

Indoor Units

Type
Model

2. Specifications

Indoor Units

* Model Name
A:Basic, C:Plasma
Type
Model
Cooling Capacity

Heating Capacity

Casing
Dimensions
(WxDxH)

Body
Front Panel

Coil
Fan

Rows x Columns x FPI


Face Area
Type
Motor Outputx Number
Running Current
Air Flow Rate(H / M / L)

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h
mm
inch
mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Pipe
Liquid Side
mm(inch)
Connections
Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
Body
kg(lbs)
Noise Level (Sound Press, 1.5m, H / M / L) dB(A)
Power Supply
, V, Hz
Refrigerant Control
Power cord
Transmission cable
Panel Color
Panel Name(Accessory)
Elevation Grill(Accessory)

4 Way Ceiling Cassette


ARNU42GTM*2
ARNU48GTM*2
12.3
14.1
10,600
12,100
42,000
48,100
13.8
15.9
11,000
13,200
43,800
51,200
Galvanized Steel Plate
Galvanized Steel Plate
840 x 840 x 288
840 x 840 x 288
33.0 x 33.0 x 11.3
33.0 x 33.0 x 11.3
950 x 950 x 25
950 x 950 x 25
37.4 x 37.4 x 1
37.4 x 37.4 x 1
2 x 12 x 19
2 x 12 x 19
0.57
0.57
Turbo Fan
Turbo Fan
135
135
0.56
0.56
30 / 27 / 24
31 / 29 / 27
1,059 / 954 / 848
1,059 / 1,024 / 954
Direct
Direct
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Fuse
Fuse
9.52(3/8)
9.52(3/8)
15.88(5/8)
15.88(5/8)
25(1)
25(1)
25.6(56.4)
25.6(56.4)
44 / 41 / 38
46 / 43 / 41
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
EEV
EEV
CV2.0 X 3C
CV2.0 X 3C
CVV-SB 1.25 X 2C
CVV-SB 1.25 X 2C
Morning fog
Morning fog
PT-UMC
PTEGM0

Notes:1. Capacities are based on the following conditions:


Cooling
Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating
Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

5 _ Ceiling Cassette 4-way

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Ceiling Cassette 4-way _ 6

55

380(Air outlet hole)


473
700

0
4-R
2
378.6
380(Air outlet hole)
700
22.5

378.6
4

523
59.5
84.5

172

30 19
142.5

2 1

79
53
48

128
570

165

461
570

517

Gas pipe connection


Drain pipe connection
Power supply connection
Air discharge grill
Air suction grill

3
4
5
6

(unit : mm)

Unit size(5k, 7k, 9k, 12k):12.7

Unit size(5k, 7k, 9k, 12k):6.35

Descripition

CHASSIS CODE: TR

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Liquid pipe connection

Name

Number

ARNU05GTR*2
ARNU07GTR*2
ARNU09GTR*2
ARNU12GTR*2

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

Branch Duct Connection

63

69

517
214
34.5

R3

Indoor Units

570

Ceiling Cassette 4-way

3. Dimensions

55

380(Air outlet hole)


473
700

0
4-R
2
378.6
380(Air outlet hole)
700
22.5

378.6
4

523
59.5
125
95.5

172

30 19
142.5

2 1

79
48
570

165

461
570

517

174

R3

570

Gas pipe connection


Drain pipe connection
Power supply connection
Air discharge grill
Air suction grill

3
4
5
6

(unit : mm)

Unit size(15k, 18k):12.7

Unit size(15k, 18k):6.35

Descripition

CHASSIS CODE: TQ

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Liquid pipe connection

Name

Number

ARNU15GTQ*2
ARNU18GTQ*2

Ceiling Cassette 4-way

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

Branch Duct Connection

63

68

517
76
94

7 _ Ceiling Cassette 4-way


256

Indoor Units

3. Dimensions

54

500(Air outlet hole)


734
950

4-

0
R2

500(Air outlet hole)


618
950

25

292

671

108 60

204
154

65 40

618

79
41.5

350

840

165

840

787

787

53.5

62

Air discharge grill


Air suction grill

5
6

(unit : mm)

Unit size(24k, 28k):15.88

Unit size(24k, 28k):9.52

Descripition

CHASSIS CODE: TP

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Power supply connection

Gas pipe connection


Drain pipe connection

2
3

Liquid pipe connection

Name

Number

ARNU24GTP*2
ARNU28GTP*2

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

Branch Duct Connection

80

684
840

A direction View

204

804

R35

Ceiling Cassette 4-way _ 8

Indoor Units

126

60
82
99

Ceiling Cassette 4-way

3. Dimensions

9 _ Ceiling Cassette 4-way


5

246
195
40
110

60
840

165

350

80

246

62

Gas pipe connection


Drain pipe connection
Power supply connection
Air discharge grill
Air suction grill

3
4
5
6

Unit size(36k):15.88

Unit size(36k):9.52

Descripition

(unit : mm)

CHASSIS CODE: TN

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Liquid pipe connection

Name

Number

ARNU36GTN*2

Ceiling Cassette 4-way

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

Branch Duct Connection

53.5

126

78

A direction View

107

R35

100
52

840

103
141

25

Indoor Units

3. Dimensions

1
165

840

350

53.5

126

25

Power supply connection


Air discharge grill
Air suction grill

3
4
5
6

(unit : mm)

Unit size(42k, 48k):15.88

Unit size(42k, 48k):9.52

Descripition

CHASSIS CODE: TM

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Gas pipe connection


Drain pipe connection

Liquid pipe connection

Name

Number

ARNU42GTM*2
ARNU48GTM*2

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

Branch Duct Connection

109

R35

Ceiling Cassette 4-way _ 10

Indoor Units

A direction View

100
84

288

237

Ceiling Cassette 4-way

3. Dimensions

4. Piping Diagrams

Indoor Units

Heat Exchanger

:Cooling
:Heating

EEV
Filter

Th3

Th2
Turbo Fan

Filter

lndoor unit

Th1

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

Model

Gas

Liquid

ARNU05GTR*2

12.7(1/2)

6.35(1/4)

ARNU07GTR*2

12.7(1/2)

6.35(1/4)

ARNU09GTR*2

12.7(1/2)

6.35(1/4)

ARNU12GTR*2

12.7(1/2)

6.35(1/4)

ARNU15GTQ*2

12.7(1/2)

6.35(1/4)

ARNU18GTQ*2

12.7(1/2)

6.35(1/4)

ARNU24GTP*2

15.88(5/8)

9.52(3/8)

ARNU28GTP*2

15.88(5/8)

9.52(3/8)

ARNU36GTN*2

15.88(5/8)

9.52(3/8)

ARNU42GTM*2

15.88(5/8)

9.52(3/8)

ARNU48GTM*2

15.88(5/8)

9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

11 _ Ceiling Cassette 4-way

5. Wiring Diagrams
TR/TQ Chassis
Indoor Units

CONNECTOR NUMBER
CN-POWER
CN-MOTOR1
CN-D/PUMP
CN-485
CN-DISP
CN-EEV
CN-VANE2
CN-FLOAT
CN-PIPE/IN
CN-PIPE/OUT
CN-ROOM
CN-REMO
CN-CC
CN-AIRC

LOCATION POINT
AC Power supply
Fan motor output
Drain pump output
Communication
Display
EEV Output
Step motor
Float switch input
Suction pipe sensor
Discharge pipe sensor
Room sensor
Remote controller
Dry contact
Air clean

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION
AC Power line input for indoor controller
Motor output of BLDC
AC output for drain pump
Connection between indoor and outdoor
Display of indoor status
EEV Control output
Step motor output
Float switch sensing
Pipe in thermistor
Pipe out thermistor
Room air thermistor
Remote control line
Dry contact line
Air cleaner control
Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

Ceiling Cassette 4-way _ 12

5. Wiring Diagrams

Indoor Units

TM/TN/TP Chassis

CONNECTOR NUMBER
CN-POWER
CN-MOTOR1
CN-D/PUMP
CN-485
CN-DISP
CN-EEV
CN-VANE1 / VANE2
CN-FLOAT
CN-PIPE/IN
CN-PIPE/OUT
CN-ROOM
CN-REMO
CN-CC
CN-AIRC

LOCATION POINT
AC Power supply
Fan motor output
Drain pump output
Communication
Display
EEV Output
Step motor
Float switch input
Suction pipe sensor
Discharge pipe sensor
Room sensor
Remote controller
Dry contact
Air clean

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION
AC Power line input for indoor controller
Motor output of BLDC
AC output for drain pump
Connection between indoor and outdoor
Display of indoor status
EEV Control output
Step motor output
Float switch sensing
Pipe in thermistor
Pipe out thermistor
Room air thermistor
Remote control line
Dry contact line
Air cleaner control
Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

13 _ Ceiling Cassette 4-way

6. Capacity Tables
6.1 Cooling Capacity

1.6

2.2

2.8

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

Notes:
TC: Total Capacity(kW)

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9

1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7

1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

32
24
TC SHC
kW kW
2.1
2.1
2.1
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.8
1.8
1.8
1.8
1.7
1.7
2.9
2.9
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0

1.3
1.3
1.3
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.1
1.1
1.1
1.1
1.1
1.1
1.8
1.7
1.7
1.7
1.7
1.6
1.6
1.6
1.6
1.6
1.5
1.5
1.5
1.5
1.5
1.4
2.1
2.1
2.1
2.1
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.9
1.8
1.8
1.8
1.7

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 4-way _ 14

Indoor Units

Capacity
Index

Outdoor
air temp.
(DB, C)

Cooling capacity

6. Capacity Tables

Indoor Units

Cooling capacity

Capacity
Index

3.6

4.5

5.6

Outdoor
air temp.
(DB, C)
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2

Notes:
TC: Total Capacity(kW)

15 _ Ceiling Cassette 4-way

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6

2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

SHC: Sensible Heat Capacity(kW)

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0

2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2

32
24
TC SHC
kW kW
4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8
5.9
5.8
5.8
5.7
5.6
5.5
5.5
5.4
5.3
5.3
5.2
5.1
5.0
5.0
4.9
4.8
7.4
7.3
7.2
7.1
7.0
6.9
6.8
6.7
6.6
6.6
6.5
6.4
6.3
6.2
6.1
6.0

2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.5
2.4
2.4
2.4
2.3
2.3
2.2
2.2
2.2
3.5
3.5
3.4
3.4
3.3
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9
2.9
2.8
4.2
4.1
4.1
4.0
4.0
3.9
3.9
3.8
3.8
3.7
3.7
3.6
3.6
3.5
3.5
3.4

6. Capacity Tables
Cooling capacity

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

Capacity
Index

7.1

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2

5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7

4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6

6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1

5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1

7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.4
7.2

5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.1
5.0

8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.4
8.2
8.1
8.0
7.8
7.7
7.5
7.4

5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.4
5.3
5.2
5.1
5.1
5.0
4.9
4.8

9.3
9.2
9.1
9.0
8.8
8.7
8.7
8.5
8.4
8.3
8.2
8.1
7.9
7.8
7.7
7.6

5.4
5.4
5.3
5.2
5.2
5.1
5.1
5.0
4.9
4.9
4.8
4.7
4.6
4.6
4.5
4.4

8.2

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9
4.9

6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4

7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7

5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8
5.8

8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2

5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9

8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.5
8.4

6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
5.9
5.8

9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.7
9.4
9.3
9.2
9.0
8.9
8.7
8.5

6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.3
6.1
6.1
5.9
5.8
5.7
5.6
5.5

10.8
10.6
10.5
10.4
10.2
10.1
10.0
9.9
9.7
9.6
9.5
9.3
9.2
9.0
8.9
8.8

6.3
6.2
6.1
6.1
6.0
5.9
5.8
5.8
5.7
5.6
5.5
5.4
5.4
5.3
5.2
5.1

10.6

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2

6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3

8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5

6.9
6.9
6.9
6.9
6.9
6.9
6.9
6.9
6.9
6.9
6.9
6.9
6.9
6.9
6.9
6.9

9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9

7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6

7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6

11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.0
10.8

7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.9
7.7
7.5

12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.5
12.2
12.1
11.9
11.7
11.4
11.2
11.0

8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.1
7.9
7.8
7.7
7.6
7.4
7.3
7.1

13.9
13.7
13.6
13.4
13.2
13.0
12.9
12.8
12.6
12.4
12.2
12.0
11.8
11.7
11.5
11.3

8.1
8.0
7.9
7.8
7.7
7.6
7.6
7.5
7.3
7.3
7.1
7.0
6.9
6.8
6.7
6.6

Notes:
TC: Total Capacity(kW)

32
24
TC SHC
kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling Cassette 4-way _ 16

Indoor Units

20
14
TC SHC
kW kW

Outdoor
air temp.
(DB, C)

6. Capacity Tables

Indoor Units

Cooling capacity

Capacity
Index

12.3

14.1

Outdoor
air temp.
(DB, C)
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5

9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3

11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2

7.3
7.3
7.3
7.3
7.3
7.3
7.3
7.3
7.3
7.3
7.3
7.3
7.3
7.3
7.3
7.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3

Notes:
TC: Total Capacity(kW)

17 _ Ceiling Cassette 4-way

8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
9.2
9.2
9.2
9.2
9.2
9.2
9.2
9.2
9.2
9.2
9.2
9.2
9.2
9.2
9.2
9.2

8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0
10.0

12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1

8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
10.2
10.2
10.2
10.2
10.2
10.2
10.2
10.2
10.2
10.2
10.2
10.2
10.2
10.2
10.2
10.2

SHC: Sensible Heat Capacity(kW)

13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
12.8
12.5
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
14.7
14.4

9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
8.9
8.7
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.5
10.2
10.0

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

14.7
14.7
14.7
14.7
14.7
14.7
14.7
14.7
14.5
14.1
14.0
13.8
13.5
13.3
13.0
12.8
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.6
16.2
16.1
15.8
15.5
15.2
14.9
14.7

16.2
15.9
15.8
15.6
15.3
15.1
15.0
14.8
14.6
14.4
14.2
14.0
13.7
13.5
13.4
13.1
18.5
18.3
18.1
17.8
17.6
17.3
17.2
17.0
16.7
16.5
16.3
16.0
15.8
15.5
15.3
15.1

9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.4
9.2
9.1
8.9
8.8
8.6
8.4
8.3
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.8
10.5
10.4
10.2
10.0
9.9
9.7
9.5

9.4
9.3
9.2
9.1
9.0
8.8
8.8
8.6
8.5
8.4
8.3
8.2
8.0
7.9
7.8
7.7
10.8
10.7
10.6
10.4
10.3
10.1
10.1
9.9
9.8
9.6
9.5
9.4
9.2
9.1
8.9
8.8

6. Capacity Tables
6.2 Heating Capacity

1.6

2.2

2.8

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

1.2
1.2
1.3
1.4
1.5
1.5
1.5
1.6
1.6
1.7
1.8
1.9
2.0
2.0
2.1
2.1
2.1
2.1
2.1
1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.8
2.8
2.9
2.9
2.9
2.9
2.9
2.1
2.2
2.3
2.5
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.6
3.6
3.7
3.7
3.7
3.7
3.7

1.2
1.2
1.3
1.4
1.5
1.5
1.5
1.6
1.6
1.7
1.8
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

1.2
1.2
1.3
1.2
1.3
1.4
1.4
1.4
1.5
1.5
1.6
1.7
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.7
1.7
1.8
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.5
2.5
2.5
2.5
2.1
2.2
2.3
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2

1.2
1.2
1.3
1.4
1.4
1.5
1.5
1.6
1.6
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1

1.2
1.2
1.3
1.4
1.4
1.5
1.5
1.6
1.6
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

1.2
1.2
1.3
1.4
1.4
1.5
1.5
1.5
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.7
1.7
1.8
1.9
2.0
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.1
2.2
2.3
2.4
2.6
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

Notes:
TC: Total Capacity(kW)

Ceiling Cassette 4-way _ 18

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Heating capacity

6. Capacity Tables

Indoor Units

Heating capacity
Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

3.6

4.5

5.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.7
2.8
2.9
3.1
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.4
4.5
4.6
4.6
4.6
4.6
4.6
3.4
3.5
3.7
3.9
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.6
5.6
5.8
5.8
5.8
5.8
5.8
4.2
4.3
4.6
4.9
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
7.0
7.1
7.2
7.2
7.2
7.2
7.2

2.7
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.3
4.3
4.3
4.3
4.3
4.3
4.3
3.4
3.5
3.7
3.8
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.4
5.4
5.4
5.4
5.4
5.4
5.4
4.2
4.3
4.6
4.8
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
6.7
6.7
6.7
6.7
6.7
6.7
6.7

2.7
2.8
2.9
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0
3.4
3.5
3.7
3.4
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.6
4.9
5.0
5.0
5.0
5.0
5.0
5.0
4.2
4.3
4.6
4.3
4.5
4.8
4.9
5.0
5.1
5.4
5.5
5.8
6.2
6.3
6.3
6.3
6.3
6.3
6.3

2.6
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.3
3.5
3.7
3.8
4.0
4.3
4.3
4.4
4.4
4.6
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.2
4.3
4.6
4.8
5.0
5.4
5.4
5.5
5.6
5.8
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.3
3.4
3.7
3.8
4.0
4.2
4.3
4.4
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.2
4.3
4.6
4.8
5.0
5.3
5.4
5.5
5.6
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.3
3.4
3.6
3.8
4.0
4.2
4.3
4.3
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.2
4.3
4.5
4.8
5.0
5.3
5.4
5.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

Notes:
TC: Total Capacity(kW)

19 _ Ceiling Cassette 4-way

6. Capacity Tables
Heating capacity

7.1

8.2

10.6

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

5.4
5.5
5.8
6.2
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.9
9.0
9.2
9.2
9.2
9.2
9.2
6.2
6.3
6.7
7.1
7.5
7.8
7.9
8.1
8.4
8.7
9.1
9.7
10.2
10.4
10.6
10.6
10.6
10.6
10.6

5.4
5.5
5.8
6.1
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.6
8.6
8.6
8.6
8.6
8.6
8.6
6.2
6.3
6.7
7.0
7.5
7.8
7.9
8.1
8.4
8.7
9.1
9.7
9.8
9.8
9.8
9.8
9.8
9.8
9.8

5.4
5.5
5.8
5.5
5.8
6.0
6.2
6.3
6.5
6.8
7.0
7.4
7.8
8.0
8.0
8.0
8.0
8.0
8.0
6.2
6.3
6.7
6.3
6.6
7.0
7.1
7.3
7.5
7.8
8.1
8.5
9.0
9.2
9.2
9.2
9.2
9.2
9.2

5.3
5.5
5.8
6.1
6.4
6.8
6.9
7.0
7.1
7.4
7.7
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
6.1
6.3
6.7
7.0
7.4
7.8
7.9
8.1
8.2
8.5
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9

5.3
5.4
5.8
6.1
6.4
6.7
6.9
7.0
7.1
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
6.1
6.3
6.7
7.0
7.4
7.7
7.9
8.1
8.2
8.5
8.6
8.6
8.6
8.6
8.6
8.6
8.6
8.6
8.6

5.3
5.4
5.8
6.1
6.4
6.7
6.8
6.8
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
6.1
6.3
6.6
7.0
7.4
7.7
7.8
7.9
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

8.0
8.2
8.7
9.2
9.6
10.1
10.2
10.5
10.8
11.3
11.8
12.5
13.2
13.4
13.7
13.7
13.7
13.7
13.7

8.0
8.2
8.7
9.0
9.6
10.1
10.2
10.5
10.8
11.3
11.8
12.5
12.7
12.7
12.7
12.7
12.7
12.7
12.7

8.0
8.2
8.7
8.2
8.6
9.0
9.2
9.4
9.7
10.1
10.4
11.0
11.6
11.9
11.9
11.9
11.9
11.9
11.9

7.9
8.2
8.7
9.0
9.5
10.1
10.2
10.5
10.6
11.0
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5

7.9
8.1
8.7
9.0
9.5
10.0
10.2
10.5
10.6
11.0
11.2
11.2
11.2
11.2
11.2
11.2
11.2
11.2
11.2

7.9
8.1
8.6
9.1
9.5
10.0
10.1
10.2
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4

Notes:
TC: Total Capacity(kW)

Ceiling Cassette 4-way _ 20

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

6. Capacity Tables

Indoor Units

Heating capacity
Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

12.3

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

9.2
9.5
10.1
10.6
11.2
11.7
11.9
12.1
12.6
13.1
13.7
14.5
15.3
15.5
15.9
15.9
15.9
15.9
15.9

9.2
9.5
10.1
10.5
11.2
11.7
11.9
12.1
12.6
13.1
13.7
14.5
14.8
14.8
14.8
14.8
14.8
14.8
14.8

9.2
9.5
10.1
9.5
10.0
10.4
10.7
10.9
11.3
11.7
12.1
12.8
13.5
13.8
13.8
13.8
13.8
13.8
13.8

9.1
9.5
10.1
10.5
11.0
11.7
11.9
12.1
12.2
12.8
13.3
13.4
13.4
13.4
13.4
13.4
13.4
13.4
13.4

9.1
9.4
10.1
10.5
11.0
11.6
11.9
12.1
12.2
12.8
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0

9.1
9.4
9.9
10.5
11.0
11.6
11.7
11.8
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1

14.1

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

10.7
11.0
11.6
12.2
12.9
13.5
13.7
14.0
14.5
15.1
15.7
16.7
17.7
17.9
18.3
18.3
18.3
18.3
18.3

10.7
11.0
11.6
12.1
12.9
13.5
13.7
14.0
14.5
15.1
15.7
16.7
17.0
17.0
17.0
17.0
17.0
17.0
17.0

10.7
11.0
11.6
10.9
11.5
12.0
12.3
12.6
13.0
13.5
13.9
14.7
15.5
15.9
15.9
15.9
15.9
15.9
15.9

10.5
11.0
11.6
12.1
12.7
13.5
13.7
14.0
14.1
14.7
15.3
15.4
15.4
15.4
15.4
15.4
15.4
15.4
15.4

10.5
10.8
11.6
12.1
12.7
13.4
13.7
14.0
14.1
14.7
14.9
14.9
14.9
14.9
14.9
14.9
14.9
14.9
14.9

10.5
10.8
11.4
12.1
12.7
13.4
13.5
13.6
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9

Notes:
TC: Total Capacity(kW)

21 _ Ceiling Cassette 4-way

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU05GTR*2, ARNU07GTR*2, ARNU09GTR*2
Cooling

Heating

Air velocity [m/s]

Air velocity [m/s]


2.7m

2.7m
2.0

2.0

2.0

1.5
1.0

1.5
1.0

2m

2.0
1.5

1.5
1.0

2.5m

1.5m

0m

1.5m

0m
2.5m

1.0
0.5

0.5

1m

0.5

0.5

2.5m

2m

1.5m

1m

0m

1.5m

0m
2.5m

Temperature [C]

Temperature [C]

2.7m

2.7m
33

2m

18

18
20

20

22

21

21 2m
27

18

24

27

18
24

24

1m

22

33

1m

24

2.5m

1.5m

0m

1.5m

0m
2.5m

2.5m

1.5m

0m

1.5m

0m
2.5m

ARNU12GTR*2
Cooling

Heating

Discharge angle: 40

Discharge angle: 50
Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m
2.0

2.0
1.5

2.0

2m
1.5

2.0
1.5

1.0
1.0

1.0

0.5

2.5m

2m

1.5
1.0

0.5

1m

1m

0.5

0.5

1.5m

0m

1.5m

0m
2.5m

2.5m

1.5m

0m

0m
2.5m

1.5m

Temperature [C]

Temperature [C]

2.7m

2.7m
18

33

18

20

2m

20

22

33

30
24

22

2m

30

27

27

24

21

21

1m

1m
24

2.5m

1.5m

24

0m

1.5m

0m
2.5m

2.5m

1.5m

0m

1.5m

0m
2.5m

Ceiling Cassette 4-way _ 22

Indoor Units

Discharge angle: 40

Discharge angle: 50

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU15GTQ*2
Cooling

Heating
Discharge angle: 50

Air velocity [m/s]

Air velocity [m/s]

Indoor Units

Discharge angle: 40

2.7m

2.7m
2.0

2.0

2.0
1.5

1.0

1m

1m

0m

1m

2m

0.5

0.5

3m

4m

0m

4m

3m

1m

1.0

1.0

0.5

2m

1.5

1.5

0.5
3m

2m

2m
1.5

1.0

4m

2.0

2m

1m

0m

1m

2m

3m

4m

Temperature [C]

Temperature [C]

2.7m

2.7m
18

18
20

20

33

33

2m

2m
22

22

21

24

24

1m

27

24

24

3m

21

1m
27

4m

0m

2m

1m

0m

1m

2m

3m

4m

0m

4m

3m

2m

1m

0m

1m

2m

3m

4m

0m

ARNU18GTQ*2
Cooling

Heating

Discharge angle: 40

Discharge angle: 50

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m
2.0

2.0

2.0

1.5

2m

1.0

4m

3m

2m

1.5

1.5
1m

1.0

0.5
0m

1m

3m

4m

0m

4m

3m

2m

1m

1.0

0.5

2m

2m

1.5

1.0

0.5
1m

2.0

0.5

1m

0m

1m

2m

3m

4m

Temperature [C]

Temperature [C]

2.7m

2.7m
18
20

18

22

33

20

2m

2m

2m

30

21

22

24

3m

33

30

1m

4m

0m

21
24

27

27

1m

24

24

1m

0m

1m

2m

23 _ Ceiling Cassette 4-way

3m

4m

0m

4m

3m

2m

1m

0m

1m

2m

3m

4m

0m

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU24GTP*2
Cooling

Heating
Discharge angle: 50

Air velocity [m/s]

Air velocity [m/s]

2.7m

2.7m
2.0

2.0

2m

2m
2.0

1.5

3m

1.0

1.0

1.0
4m

1m

1.5

2m

1m

0m

1m

3m

4m

0m

4m

2m

0.5

1m

0m

1m

2m

3m

4m

0m

Temperature [C]

18
20
22

2.7m

2.7m

18
20
22

2m

23

24

2m

1m

0m

1m

2m

3m

4m

0m

4m

30

2m
22

22

3m

1m

24

24

27

23

24

33

33
30

1m

3m

3m

1m

1.0

0.5

2m

Temperature [C]

4m

2.0

2m

1m

27

0m

1m

2m

3m

4m

0m

ARNU28GTP*2
Cooling

Heating

Discharge angle: 40

Discharge angle: 50

Air velocity [m/s]

Air velocity [m/s]

2.7m
2.0

2m

2.0

1.0

1.0

1.0

2m

2m
1.5

1m

1.5

1.0
3m

2.7m

3.0
2.0

1.5

1m

1.5

4m

3.0
2.0

2.5

2.5

1m

0m

1m

2m

3m

4m

0m

0.5

4m

3m

2m

0.5

1m

0m

1m

2m

3m

4m

Temperature [C]

Temperature [C]

2.7m

2.7m
18

33

18

33

2m

2m
21
22

22
23

4m

3m

2m

0m

23

1m

0m

1m

2m

3m

4m

0m

30

24

1m

30

1m

27

4m

3m

2m

21

24

1m

0m

27
1m

2m

3m

4m

0m

Ceiling Cassette 4-way _ 24

Indoor Units

Discharge angle: 40

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU36GTN*2
Indoor Units

Cooling

Heating

Discharge angle: 40

Discharge angle: 50

Air velocity [m/s]

Air velocity [m/s]

3.0
2.5
2.0

2.7m

3.0
2.5
2.0

2m
1.5

1.5
1.0
5m

4m

3m

1m

2m

1m

0m

1m

2m

3m

4m

1.0

3m

2m

1m

2.7m

0m

1m

2m

3m

4m

0m
5m

22

23

1m

0m

2m

1m

2m

3m

4m

0m
5m

30

24
22

1m
23

2m

33

2m

20

22

2.7m

33

18

20

3m

4m

1m

Temperature [C]

18

4m

5m

2m

2.0

1.0

0m
5m

2.7m

3.5
3.0
2.5

2.0

1.0

Temperature [C]

5m

3.5
3.0
2.5

30

27

5m

4m

3m

2m

1m

24
22

1m

4m

0m
5m

27

0m

1m

2m

3m

ARNU42GTM*2
Cooling

Heating

Discharge angle: 40

Discharge angle: 50

Air velocity [m/s]

Air velocity [m/s]

3.2m

3.2m
4.0

4.0

4.0
3.0

3.0

3.0

2m

3.0

4.0

2m

1m

5m

4m

3m

1m
2.0

2.0
1.0

2.0
1.0
2m

1m

0m

1m

2m

2.0

1.0

3m

4m

0m
5m

5m

4m

3m

2m

1.0

1m

0m

1m

2m

3m

4m

Temperature [C]

Temperature [C]
3.2m

3.2m

2m

20

33

33

18

18

24

20

22

22

4m

3m

2m

1m

0m

1m

2m

25 _ Ceiling Cassette 4-way

3m

22
27

24

24

30

22

1m

4m

0m
5m

5m

4m

2m

24
30

5m

0m
5m

3m

2m

1m

1m

27

0m

1m

2m

3m

4m

0m
5m

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU48GTM*2
Cooling

Heating
Discharge angle: 50

Air velocity [m/s]

Air velocity [m/s]

3.2m
4.0

1.0
4m

3m

2m

1m

0m

1m

2m

2m

3.0

3.0

1m

2.0
1.0

2.0

4.0

2m

3.0

3.0

5m

3.2m
4.0

4.0

1m
2.0

2.0

1.0

3m

4m

0m
5m

4m

5m

3m

2m

1m

1.0

0m

1m

2m

3m

4m

0m
5m

Temperature [C]

Temperature [C]
3.2m

3.2m
33

18

18

2m

20

20

33

2m
22

24

22

24

1m
22
24

5m

4m

24

3m

2m

1m

1m

0m

1m

2m

3m

30

30
27

22

4m

0m
5m

5m

4m

3m

2m

1m

27

0m

1m

2m

3m

4m

0m
5m

Ceiling Cassette 4-way _ 26

Indoor Units

Discharge angle: 40

8. Electric Characteristicss
Units

Indoor Units

Model

Type

Power Supply
Hz

Volts

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

ARNU05GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU07GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU09GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU12GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU15GTQ*2

TQ

0.25

15

0.043

0.2

30

30

ARNU18GTQ*2

TQ

0.25

15

0.043

0.2

30

30

0.22

15

0.03

0.17

33

33

50

220-240

MAX : 264
MIN:198

ARNU24GTP*2

TP

ARNU28GTP*2

TP

0.22

15

0.03

0.17

33

33

ARNU36GTN*2

TN

0.81

15

0.135

0.64

144

144

ARNU42GTM*2

TM

0.81

15

0.135

0.64

144

144

ARNU48GTM*2

TM

0.81

15

0.135

0.64

144

144

ARNU05GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU07GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU09GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU12GTR*2

TR

0.25

15

0.043

0.2

30

30

ARNU15GTQ*2

TQ

0.25

15

0.043

0.2

30

30

ARNU18GTQ*2

TQ

0.25

15

0.043

0.2

30

30

ARNU24GTP*2

TP

0.22

15

0.03

0.17

33

33

ARNU28GTP*2

TP

0.22

15

0.03

0.17

33

33

ARNU36GTN*2

TN

0.81

15

0.135

0.64

144

144

ARNU42GTM*2

TM

0.81

15

0.135

0.64

144

144

ARNU48GTM*2

TM

0.81

15

0.135

0.64

144

144

60

220

MAX : 242
MIN:198

Symbols:
MCA : Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the larger value on the MCA.
5. Instead of fuse, use Circuit Breaker.

27 _ Ceiling Cassette 4-way

9. Sound Levels
Overall

Ceiling
1.5m

Model
ARNU05GTR*2
ARNU07GTR*2
ARNU09GTR*2
ARNU12GTR*2
ARNU15GTQ*2
ARNU18GTQ*2

H
29
29
30
32
36
37

Sound Level dB(A)


L
M
26
27
26
27
27
29
27
30
32
34
34
35

Model
H
36
39
43
44
46

ARNU24GTP*2
ARNU28GTP*2
ARNU36GTN*2
ARNU42GTM*2
ARNU48GTM*2

Indoor Units

Notes:
- Sound measured at 1.5m below the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operating condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

Sound Level dB(A)


L
M
34
31
35
33
40
37
41
38
43
41

Sound Pressure Level


ARNU07GTR*2

ARNU09GTR*2
80

70

70

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

10

Approximate
Hearing
Threshold
63

NC-60

125
250
500 1000 2000 4000
Octave Band Center Frequency (Hz)

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

NC-20
NC-15
8000

NC-65

60

10

NC-25
Approximate
Hearing
Threshold
63

Octave Band Sound Pressure Level (dB re 20Pa )

80

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU05GTR*2
80

NC-60

125
250
500 1000 2000 4000
Octave Band Center Frequency (Hz)

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

NC-20
NC-15
8000

NC-65

60

10

NC-25
Approximate
Hearing
Threshold
63

NC-20

125
250
500 1000 2000 4000
Octave Band Center Frequency (Hz)

NC-15
8000

Ceiling Cassette 4-way _ 28

9. Sound Levels
ARNU12GTR*2

80

ARNU15GTQ*2

NC-65
NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

Approximate
Hearing
Threshold

10

63

NC-60
50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

NC-20
NC-15
125
250
500
1000 2000 4000
Octave Band Center Frequency (Hz)

NC-55

20

NC-25

20

NC-65

60

10

NC-25
Approximate
Hearing
Threshold
63

8000

125

ARNU24GTP*2

NC-60
NC-55
NC-50
NC-45
NC-40
NC-35

30

NC-30
20

10

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

NC-65

40

63

250

500

NC-15
1000 2000 4000 8000

4000

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25
Approximate
Hearing
Threshold
63

NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
Approximate
Hearing
Threshold
63

Octave Band Sound Pressure Level (dB re 20Pa )

NC-60

20

250

500

63

125

250

500

NC-15
1000 2000 4000 8000

NC-60

NC-15
1000 2000 4000 8000

Octave Band Center Frequency (Hz)

29 _ Ceiling Cassette 4-way

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

10

NC-25
Approximate
Hearing
Threshold
63

125

NC-20

250

500

NC-15
1000 2000 4000 8000

Octave Band Center Frequency (Hz)

125

250

500

1000

2000

4000

NC-15
8000

NC-65
NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

10

NC-25
Approximate
Hearing
Threshold
63

125

NC-20

250

500

NC-15
1000 2000 4000 8000

Octave Band Center Frequency (Hz)

NC-65

60

NC-20

60

NC-20

70

NC-20

125

10

NC-25
Approximate
Hearing
Threshold

ARNU36GTN*2

ARNU48GTM*2

NC-65

30

NC-30

Octave Band Center Frequency (Hz)

Octave Band Center Frequency (Hz)

70

40

NC-35

30

20

NC-15
8000

80

50

NC-40

70

ARNU42GTM*2
Octave Band Sound Pressure Level (dB re 20Pa )

2000

NC-45

40

70

10

80

60

NC-50

80

Octave Band Center Frequency (Hz)

10

1000

NC-55

50

80

NC-20

125

500

20

NC-25
Approximate
Hearing
Threshold

NC-60

ARNU28GTP*2

70

50

250

NC-65

60

Octave Band Center Frequency (Hz)

80

60

70

NC-20

Octave Band Sound Pressure Level (dB re 20Pa )

60

Octave Band Sound Pressure Level (dB re 20Pa )

80

70

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

70

Indoor Units

ARNU18GTQ*2

80

10. Installation
Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Indoor Units

Anti-bacteria filter

Air
Intake

TEM
P

Remote
Controll

er

Air Outlet
Wired Remote Controller(Optional)

Required Parts

Required Tools

Connecting cable
Pipes: Gas side
Liquid side
Hanging Bolt
(W 3/8 or M10 length 650mm)
Insulated drain hose
Additional Drain hose

Level
Screw driver
Electric drill
Hole core drill
Flaring Tool set
Torque Wrenches
Hexagonal Wrench
Gas-leak detector
Thermometer

Ceiling Board

50 or
more

30 or less

50 or
more

Above 250
360 or less

Ceiling
Ceiling Board

100
or more

There should not be any heat source or steam near the


unit.
There should not be any obstacles to the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall,
ceiling, or other obstacles.
The indoor unit must have sufficient maintenance
space.

30 or more

10.1 Selection of the best location

Unit:cm
Floor

Ceiling Cassette 4-way _ 30

10. Installation
10.2 Ceiling opening dimensions and hanging bolt location
Indoor Units

The dimensions of the paper pattern for installation are the same as those of the ceiling opening dimensions.

Ceiling
Ceiling board

Level gauge

TQ/TR Chassis

TM/TN/TP Chassis

585~660(Ceiling opening)

875(Ceiling opening)

517

461

Unit:mm

CAUTION
This air-conditioner uses a drain pump.
Install the unit horizontally using a level gauge.
During the installation, care should be taken not to
damage electric wires.

875(Ceiling opening)

684(Hanging bolt)

840 Unit size


840 Unit size

671

517

570

585~660(Ceiling opening)

319

523

570

787(Hanging bolt)

Unit:mm

Select and mark the position for fixing bolts and piping hole.
Decide the position for fixing bolts slightly tilted to
the drain direction after considering the direction of
drain hose.
Drill the hole for anchor bolt on the wall.

NOTE:
Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
Make sure that ventilation fan is enough to cover all noxious gases from this place.
Ensure enough distance from the cooking room to install the air conditioner in such a place where it may not suck oily steam.
Air conditioner

Take enough
distance
Use the ventilation fan
for smoke-collecting
hood with sufficient
capacity.
Cooking table

2. Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3. Avoid places where inflammable gas is generated.
4. Avoid place where noxious gas is generated.
5. Avoid places near high frequency generators.

31 _ Ceiling Cassette 4-way

10. Installation
Ceiling

Flat washer for M10


(accessory)
Ceiling board

Air Conditioner body

Ceiling board
Keep the length of 15~18mm
between the air conditioner bottom
surface and the ceiling surface

Flat washer for M10


(accessory)
Nut
(W3/8 or M10)

Set screw of
paper model (4 pieces)
Paper model
for installation

The following parts are locally purchased.


Hanging Bolt - W 3/8 or M10
Nut
- W 3/8 or M10
Spring Washer - M10
Plate Washer - M10

Open the ceiling board


along the outer edge of the
paper model

CAUTION
Tighten the nut and bolt to prevent the unit
from falling.

10.3 Wiring Connection


Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit
respectively.

Indoor cord
Remote
control cord
power cord

TR/TQ Chassis
Terminal Block Indoor
1(L)

2(N)

SODU

INTERNET DRY1 DRY2 GND 12V

IDU

Outdoor
Unit

INDOOR POWER INPUT

TM/TN/TP Chassis
Terminal Block Indoor

Terminal Block Indoor

SODU

1(L) 2(N) 3(L) 4(N)

5(A) 5(B) RD

POWER
INPUT

YL BK

IDU
B

INTERNET DRY1 DRY2 GND 12V


A

Outdoor
Unit

TO AIR
FRESH KIT

WARNING
Make sure that the screws of the terminal are not loose.

Ceiling Cassette 4-way _ 32

Indoor Units

Nut
(W3/8 or M10)

150mm

Keep the length of the bolt


from the bracket to 40mm

Hanging bolt
(W3/8 or M10)

10. Installation

Indoor Units

10.4 Installation of Decoration Panel


Before installing the decoration panel,
always remove the paper template.

The decoration panel has its installation


direction.

1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body. (Tighten by
amount 10mm in length.)
The fixing screws (hexagon M5 screw) are included in the indoor unit box.
2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.)
3. Hook the decoration panel key hole (
) on the screws fixed in step above, and slide the panel so
that the screws reach the key hole edge.
4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5. Connect the louver motor connector and display connector.
6. After tightening these screws, install the air inlet grille (including the air filter).
Piping side
Air conditioner unit

Control box cover


Decoration panel fixing screws
(hexagon M5 screws)
Temporally fitting at 2 places
(Tightening about 10mm)

Louver motor

Decoration panel

Display
Lead wire for
louver motor and
display

Decoration panel fixing screws


(Hexagon M5 screw)

CAUTION
Install certainly the decoration
panel.
Cool air leakage causes
sweating.

Inlet Grille

Good example

Water drops fall.

Bad example
Air conditioner
unit

Ceiling
board
Decoration panel
Fit the insulator (this part) and
be careful for cool air leakage

33 _ Ceiling Cassette 4-way

Air conditioner unit


Air

Cool air leakage


(no good)
Ceiling
board
Decoration
panel

10. Installation
10.5 Indoor Unit Drain Piping

Piping material: Polyvinyl chloride pipe inner


diometes 25mm and pipe fittings

Upward
routing
not allowed

Pipe clamp
Indoor unit

Indoor Units

Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra force on the
drain port on the indoor unit.
The outside diameter of the drain connection on the indoor unit is 32mm.

Maintenance
drain port

Be sure to install heat insulation on the drain piping.

1/50~1/100

Heat insulation material: Polyethylene foam with


thickness more than 8 mm.

MAX 700mm

Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Feed water

Flexible drain hose


(accessory)
Main
drain pipe

Drain Pump

Drain
port

Glue the joint

Drain hose connection


Use the clip (accessory)

Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
Feed water to the flexible drain hose and check the piping
for leakage.
Be sure to check the drain pump for normal operating and
noise when electrical wiring is complete.
When the test is complete, connect the flexible drain hose to
the drain port on the indoor unit.

Drain pan

The supplied flexible drain hose should not be strained.


A strained hose may cause leakage of water.

Max 300mm

Hanger
distance
1~15m

Metal
clamp
Flexible drain hose

Hanger Bracket
1/50~1/100 slope

Max 700mm

CAUTION

Insulation

CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of
control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during
the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the
wires.)
4) Confirm the specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
Proper starting power is not given to the compressor.

HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).

Ceiling Cassette 4-way _ 34

10. Installation

Indoor Units

WIRED REMOTE CONTROLLER INSTALLATION


Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place
away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller LED's,
the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Remote Controller

5feet
(1.5meters)

TEMP

Controller
Remote

no

no

Fig.1 Typical locations for remote controller

35 _ Ceiling Cassette 4-way

11. Accessories
Standard Accessories
Drain hose

Clamp metal

Quantity

1 EA

2 EA

Shape

Washer for
hanging backet
8 EA

Clamp
(Tie Wrap)

Insulation for
fitting

4 EA

1 SET

for gas pipe

Bolt

(Other)

4 EA
Paper pattern for
installation
Owner's manual
Installation manual

for liquid pipe

CAUTION
Use only those accessories (Standard or optional) which have designated specifications.

Ceiling Cassette 4-way _ 36

Indoor Units

Name

Indoor unit
Ceiling Concealed Duct (High Static)
1. List of functions
2. Specifications
3. Dimensions & Gravity point
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. External Static Pressure(E.S.P) & Air Flow
8. Electric Characteristics
9. Sound Levels
10. Installation
11. Accessories

1. List of functions
Category

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Air supply outlet


Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2, ARNU15GBHA2,


ARNU18GBHA2, ARNU24GBHA2, ARNU28GBGA2 , ARNU36GBGA2,
ARNU42GBGA2, ARNU48GBRA2, URNU76GB8A2, URNU96GB8A2
1
3/3/3
X
X
O
O
O
X
O
O
O
O(Heat recovery)
X
O(Heat pump or Cooling only)
O
O
O
O
O
O
O
Accessory
Accessory
Accessory
Accessory
X
Accessory
Accessory
-

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

Ceiling Concealed Duct(High Static) _ 1

Indoor Units

Air flow

Function

2. Specifications

Indoor Units

Type
Model
Cooling Capacity

Heating Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Casing
Dimensions(WxDxH) Body

mm
inch

Rows x Columns x FPI


Face Area
m3
Type
Motor Output x Number
W
Running Current
A
Air Flow Rate(H / M / L)
CMM
(High Mode-factory set)
cfm
Fan
External Static Pressure mmAq(Pa)
Air Flow Rate(H / M / L)
CMM
(Standard Mode)
cfm
External Static Pressure mmAq(Pa)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Coil

Power Supply
Refrigerant Control
Power cable
Transmission cable

, V, Hz
mm2
mm2

ARNU07GBHA2
2.2
1,900
7,500
2.5
2,200
8,500
Galvanized Steel Plate
882 x 450 x 260
34.7 x 17.7 x 10.2
2 x 10 x 21
0.15
Sirocco Fan
118
0.92
8.5 / 7.5 / 6.0
300 / 265 / 212
8(78)
8.5 / 8.0 / 7.5
300 / 282 / 265
6(59)
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Fuse
6.35(1/4)
12.7(1/2)
25(1)
26(57.4)
34 / 33 / 32
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C

Ceiling Concealed Duct -High Static


ARNU09GBHA2 ARNU12GBHA2
2.8
3.6
2,400
3,100
9,600
12,300
3.2
4.0
2,800
3,400
10,900
13,600
Galvanized Steel Plate Galvanized Steel Plate
882 x 450 x 260 882 x 450 x 260
34.7 x 17.7 x 10.2 34.7 x 17.7 x 10.2
2 x 10 x 21
2 x 10 x 21
0.15
0.15
Sirocco Fan
Sirocco Fan
118
118
0.92
0.92
10.0 / 8.5 / 7.5
12.0 / 10.0 / 8.5
353 / 300 / 265
424 / 353 / 300
8(78)
8(78)
8.5 / 8.0 / 7.5
11.0 / 8.5 / 7.5
300 / 282 / 265
388 / 300 / 265
6(59)
6(59)
Direct
Direct
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene Foamed polystrene
Fuse
Fuse
6.35(1/4)
6.35(1/4)
12.7(1/2)
12.7(1/2)
25(1)
25(1)
26(57.4)
26(57.4)
35 / 34 / 33
37 / 35 / 34
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Noise Level is Standard Mode
(for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))
7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Concealed Duct(High Static)

ARNU15GBHA2
4.5
3,900
15,400
5.0
4,300
17,100
Galvanized Steel Plate
882 x 450 x 260
34.7 x 17.7 x 10.2
2 x 10 x 21
0.15
Sirocco Fan
118
0.92
13.5 / 12.0 / 8.5
477 / 424 / 300
8(78)
13.5 / 12.0 / 11.0
477 / 424 / 388
6(59)
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Fuse
6.35(1/4)
12.7(1/2)
25(1)
26(57.4)
39 / 38 / 37
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specifications
Type
Model

Heating Capacity
Casing
Dimensions(WxDxH) Body

mm
inch

Rows x Columns x FPI


Face Area
m3
Type
Motor Output x Number
W
Running Current
A
Air Flow Rate(H / M / L)
CMM
(High Mode-factory set)
cfm
Fan
External Static Pressure mmAq(Pa)
Air Flow Rate(H / M / L)
CMM
(Standard Mode)
cfm
External Static Pressure mmAq(Pa)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Coil

Power Supply
Refrigerant Control
Power cable
Transmission cable

, V, Hz
mm2
mm2

Ceiling Concealed Duct(High Static)


ARNU18GBHA2
ARNU24GBHA2
ARNU28GBGA2
5.6
7.1
8.2
4,800
6,100
7,100
19,100
24,200
28,000
6.3
8.0
9.2
5,400
6,900
8,000
21,500
27,300
31,500
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
882 x 450 x 260
882 x 450 x 260
1,182 x 450 x 298
34.7 x 17.7 x 10.2
34.7 x 17.7 x 10.2
46.5 x 17.7 x 11.7
3 x 10 x 21
3 x 10 x 21
3 x 12 x 21
0.15
0.15
0.26
Sirocco Fan
Sirocco Fan
Sirocco Fan
118
118
390
0.92
0.92
2.30
15.5 / 13.5 / 12.4
18.3 / 16.9 / 15.5
25.9 / 24.1 / 21.8
547 / 477 / 438
646 / 597 / 547
915 / 851 / 770
8(78)
8(78)
10(98)
15.3 / 13.6 / 10.3
19.0 / 16.4 / 14.5
25.3 / 21.8 / 17.6
540 / 480 / 364
671 / 579 / 512
893 / 770 / 622
6(59)
6(59)
8(78)
Direct
Direct
Direct
BLDC
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Foamed polystrene
Fuse
Fuse
Fuse
6.35(1/4)
9.52(3/8)
9.52(3/8)
12.7(1/2)
15.88(5/8)
15.88(5/8)
25(1)
25(1)
25(1)
26.5(58.4)
26.5(58.4)
38.0(83.8)
42.5 / 41 / 37
45 / 43 / 41
44 / 42 / 40
1, 220-240, 50
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
1, 220, 60
EEV
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Noise Level is Standard Mode
(for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))
7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Ceiling Concealed Duct(High Static) _ 3

Indoor Units

Cooling Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

2. Specifications

Indoor Units

Type
Model
Cooling Capacity

Heating Capacity

Ceiling Concealed Duct(High Static)


Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Casing
Dimensions(WxDxH) Body

mm
inch

Rows x Columns x FPI


Face Area
m3
Type
Motor Output x Number
W
Running Current
A
Air Flow Rate(H / M / L)
CMM
(High Mode-factory set)
cfm
Fan
External Static Pressure mmAq(Pa)
Air Flow Rate(H / M / L)
CMM
(Standard Mode)
cfm
External Static Pressure mmAq(Pa)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Coil

Power Supply
Refrigerant Control
Power cable
Transmission cable

, V, Hz
mm2
mm2

ARNU36GBGA2
ARNU42GBGA2
ARNU48GBRA2
10.6
12.3
14.1
9,100
10,600
12,100
36,200
42,000
48,100
11.9
13.8
15.9
10,200
11,000
13,200
40,600
43,800
51,200
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
1,182 x 450 x 298
1,182 x 450 x 298
1,230 x 590 x 380
46.5 x 17.7 x 11.7
46.5 x 17.7 x 11.7
48.4 x 23.2 x 15
3 x 12 x 21
3 x 12 x 21
3 x 13 x 19
0.26
0.26
0.38
Sirocco Fan
Sirocco Fan
Sirocco Fan
390
390
390
2.30
2.30
2.40
32.3 / 29.0 / 25.3
34.5 / 32.3 / 30.7
44.8 / 40.6 / 33.3
1,141 / 1,024 / 894
1,218 / 1,141 / 1,084
1,582 / 1,434 / 1,176
10(98)
10(98)
14(137)
28.4 / 25.3 / 21.8
32.0 / 28.4 / 27.2
44.4 / 39.5 / 33.5
1,003 / 894 / 770
1,130 / 1,003 / 961
1,568 / 1,395 / 1,183
8(78)
8(78)
10(98)
Direct
Direct
Direct
BLDC
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Foamed polystrene
Fuse
Fuse
Fuse
9.52(3/8)
9.52(3/8)
9.52(3/8)
15.88(5/8)
15.88(5/8)
15.88(5/8)
25(1)
25(1)
25(1)
38(83.8)
38(83.8)
53(117)
46 / 44 / 42
48 / 46 / 45
45 / 43 / 41
1, 220-240, 50
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
1, 220, 60
EEV
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Noise Level is Standard Mode
(for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))
7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

4 _ Ceiling Concealed Duct(High Static)

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specifications
Type
Model

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Noise Level is Standard Mode
(for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))
7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Ceiling Concealed Duct(High Static) _ 5

Indoor Units

Ceiling Concealed Duct(High Static)


URNU76GB8A2
URNU96GB8A2
22.4
28
Cooling Capacity
19,300
24,100
76,400
95,900
25.2
31.5
Heating Capacity
21,700
27,100
86,000
107,500
Casing
Galvanized Steel Plate
Galvanized Steel Plate
mm
1,562 x 688 x 460
1,562 x 688 x 460
Dimensions(WxDxH) Body
inch
61.5 x 27.1 x 18.1
61.5 x 27.1 x 18.1
Rows
x
Columns
x
FPI
3
x
21
x
19
3 x 21 x 19
Coil
Face Area
m3
0.59
0.59
Type
Sirocco Fan
Sirocco Fan
Motor Output x Number
W
375 x 2
375 x 2
Running Current
A
4.50
4.50
Air Flow Rate(H / M / L)
CMM
60.0 / 50.0 / 50.0
72.0 / 64.0 / 64.0
(High Mode-factory set)
cfm
2,119 / 1,766 / 1,766
2542 / 2,260 / 2,260
Fan
External Static Pressure mmAq(Pa)
22(216)
22(216)
Air Flow Rate(H / M / L)
CMM
64.0 / 50.0 / 50.0
76.0 / 64.0 / 64.0
(Standard Mode)
cfm
2,260 / 1,766 / 1,766
2,684 / 2,260 / 2,260
External Static Pressure mmAq(Pa)
15(147)
15(147)
Drive
Direct
Direct
Motor type
BLDC
BLDC
Temperature Control
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Sound Absorbing Thermal Insulation Material
Foamed polystrene
Foamed polystrene
Air Filter
Safety Device
Fuse
Fuse
Liquid Side
mm(inch)
9.52(3/8)
9.52(3/8)
Pipe Connections Gas Side
mm(inch)
19.05(3/4)
22.2(7/8)
Drain Pipe(Internal Dia.) mm(inch)
25(1)
25(1)
Net Weight
kg(lbs)
87(192)
87(192)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
50 / 48 / 48
52 / 50 / 50
1,
220-240,
50
1,
220-240, 50
Power Supply
, V, Hz
1, 220, 60
1, 220, 60
Refrigerant Control
EEV
EEV
Power cable
mm2
CV1.5 x 3C
CV1.5 x 3C
Transmission cable
mm2
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

R3

7.

60

114

450

260

47

355

158

20

175

75

21

49

64

24

243

428

882

212

882

87
750

932

745

243

119

65

108

30

115

450
47

133
127
106

6 _ Ceiling Concealed Duct(High Static)

450

219
119

355

224

1
2

100

50

70

260

29

51

123 140

48
52 165

31

Air suction

Unit size(7k,9k,12k,18k):6.35
Unit size(24k):9.52
Unit size(7k,9k,12k,18k):12.7
Unit size(24k):15.88

Descripition

(unit : mm)

Gravity point

CHASSIS CODE: BH

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Air discharge

Drain pipe connection


Power supply connection

3
4

Gas pipe connection

Liquid pipe connection

Name

Number

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

101

ARNU07GBHA2
ARNU09GBHA2
ARNU12GBHA2
ARNU15GBHA2
ARNU18GBHA2
ARNU24GBHA2

Ceiling Concealed Duct (High Static)

Indoor Units

3. Dimensions & Gravity point

Ceiling Concealed Duct(High Static) _ 7

1
0

60

152

224

20

298

220

23

186

450

232

49

565

243

1,182

232

1,182

87
830

1,230

1,043

243

232

115

108

29

75

87

355
450
158
113

219
136

100

50

2
261

165

122 140

47
53

32

Note

(unit : mm)

Unit size(28k,36k,42k):15.88

Unit size(28k,36k,42k):9.52

Descripition

Gravity point

CHASSIS CODE: BG

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Air suction

Air discharge

5
6

Power supply connection

Drain pipe connection

Gas pipe connection

2
3

Liquid pipe connection

Name

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

102
51

Number

ARNU28GBGA2
ARNU36GBGA2
ARNU42GBGA2

Ceiling Concealed Duct (High Static)

Indoor Units

3. Dimensions & Gravity point

R6

60

198

312

380

50

215

621

279

1,230

241

118
1,004

1,284
1,230

279
215

120

114

1
2
135
190
260

115

101
83

Name

Air discharge
Air suction

4
5
6

Unit size(48k):15.88

Unit size(48k):9.52

Descripition

(unit : mm)

Gravity point

CHASSIS CODE: BR

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Power supply connection

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

Gas pipe connection


Drain pipe connection

Liquid pipe connection

Number
26

ARNU48GBRA2

Ceiling Concealed Duct (High Static)

72
123
221
122
144

1,092

477
590
56
168

25

303

32

140

590

8 _ Ceiling Concealed Duct(High Static)


185
174

90
302

Indoor Units

3. Dimensions & Gravity point

Ceiling Concealed Duct(High Static) _ 9

460

460

688

20

440

318

293

329

819

1,562

320

1,220

1,562

1,622

1,396

329

115

688
30

222

560
64

290
161

397

358

68

18

109

58

122 60 70 64

Gas pipe connection


Drain pipe connection
Power supply connection
Air discharge
Air suction

2
3
4
5
6

(unit : mm)

Unit size(76k):19.05
Unit size(96k):22.2

Unit size(76k,96k):9.52

Descripition

Gravity point

CHASSIS CODE: B8

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Liquid pipe connection

Name

Number

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

40
99 1

70
120

URNU76GB8A2
URNU96GB8A2

Ceiling Concealed Duct (High Static)

Indoor Units

3. Dimensions & Gravity point

4. Piping Diagrams

Indoor Units

Heat Exchanger

:Cooling
:Heating

EEV
Filter

Th3

Th2
Sirocco Fan

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GBHA2

12.7(1/2)

6.35(1/4)

ARNU09GBHA2

12.7(1/2)

6.35(1/4)

ARNU12GBHA2

12.7(1/2)

6.35(1/4)

ARNU15GBHA2

12.7(1/2)

6.35(1/4)

ARNU18GBHA2

12.7(1/2)

6.35(1/4)

ARNU24GBHA2

15.88(5/8)

9.52(3/8)

ARNU28GBGA2

15.88(5/8)

9.52(3/8)

ARNU36GBGA2

15.88(5/8)

9.52(3/8)

ARNU42GBGA2

15.88(5/8)

9.52(3/8)

ARNU48GBRA2

15.88(5/8)

9.52(3/8)

URNU76GB8A2

19.05(3/4)

9.52(3/8)

URNU96GB8A2

22.2(7/8)

9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

10 _ Ceiling Concealed Duct(High Static)

5. Wiring Diagrams
BH Chassis
Indoor Units

CONNECTOR NUMBER
CN-POWER
CN-MOTOR1
CN-D/PUMP
CN-COM
CN-EEV
CN-FLOAT
CN-PIPE/IN
CN-PIPE/OUT
CN-ROOM
CN-REMO
CN-ZON
CN-DISPLAY
CN-CC

LOCATION POINT
AC Power supply
Fan motor output
Drain pump output
Communication
EEV Output
Float switch input
Suction pipe sensor
Discharge pipe sensor
Room sensor
Remote controller
Zontroller
RF Remote controller
Dry contact

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION
AC Power line input for indoor controller
Motor output of BLDC
AC output for drain pump
Connection between indoor and outdoor
EEV Control output
Float switch sensing
Pipe in thermistor
Pipe out thermistor
Room air thermistor
Remote control line
Zone control line
RF Remote control line
Dry contact line
Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

Ceiling Concealed Duct(High Static) _ 11

5. Wiring Diagrams

Indoor Units

BG Chassis

CONNECTOR NUMBER
CN-POWER
CN-MOTOR1
CN-MOTOR2
CN-D/PUMP
CN-COM
CN-EEV
CN-FLOAT
CN-PIPE/IN
CN-PIPE/OUT
CN-ROOM
CN-REMO
CN-ZON
CN-DISPLAY
CN-CC

LOCATION POINT
AC Power supply
Fan motor output
Fan motor output
Drain pump output
Communication
EEV Output
Float switch input
Suction pipe sensor
Discharge pipe sensor
Room sensor
Remote controller
Zontroller
RF Remote controller
Dry contact

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION
AC Power line input for indoor controller
Motor output of BLDC
Motor output of BLDC
AC output for drain pump
Connection between indoor and outdoor
EEV Control output
Float switch sensing
Pipe in thermistor
Pipe out thermistor
Room air thermistor
Remote control line
Zone control line
RF Remote control line
Dry contact line
Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

12 _ Ceiling Concealed Duct(High Static)

5. Wiring Diagrams
BR Chassis
Indoor Units

CONNECTOR NUMBER
CN-POWER
CN-MOTOR1
CN-MOTOR2
CN-D/PUMP
CN-COM
CN-EEV
CN-FLOAT
CN-PIPE/IN
CN-PIPE/OUT
CN-ROOM
CN-REMO
CN-ZON
CN-DISPLAY
CN-CC

LOCATION POINT
AC Power supply
Fan motor output
Fan motor output
Drain pump output
Communication
EEV Output
Float switch input
Suction pipe sensor
Discharge pipe sensor
Room sensor
Remote controller
Zontroller
RF Remote controller
Dry contact

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION
AC Power line input for indoor controller
Motor output of BLDC
Motor output of BLDC
AC output for drain pump
Connection between indoor and outdoor
EEV Control output
Float switch sensing
Pipe in thermistor
Pipe out thermistor
Room air thermistor
Remote control line
Zone control line
RF Remote control line
Dry contact line
Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

Ceiling Concealed Duct(High Static) _ 13

5. Wiring Diagrams

Indoor Units

B8 Chassis

CONNECTOR NUMBER
CN-POWER
CN-MOTOR1, CN-MOTOR2
CN-D/PUMP
CN-COM
CN-EEV
CN-FLOAT
CN-PIPE/IN
CN-PIPE/OUT
CN-ROOM
CN-REMO
CN-CC
CN-DISPLAY
CN-OPTION
CN-ZONE

LOCATION POINT
AC Power supply
Fan motor output
Drain pump output
Communication
EEV Output
Float switch input
Suction pipe sensor
Discharge pipe sensor
Room sensor
Remote controller
Dry contact
RF Remocon
Option PCB
Zone controller

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION
AC Power line input for indoor controller
Motor output of BLDC
AC Output for drain pump
Connection between indoor and outdoor
EEV Control output
Float switch sensing
Pipe in thermistor
Pipe out thermistor
Room thermistor
Remote control line
Dry contact line
RF Remocon receiver
Option PCB connector
Zone controller line
Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

14 _ Ceiling Concealed Duct(High Static)

6. Capacity Tables
6.1 Cooling Capacity

Cooling capacity

23
16
TC SHC
kW kW

2.2

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

2.9
2.9
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3

1.8
1.8
1.8
1.7
1.7
1.7
1.7
1.7
1.6
1.6
1.6
1.6
1.5
1.5
1.5
1.5

2.8

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3

3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0

2.3
2.3
2.2
2.2
2.2
2.1
2.1
2.1
2.1
2.0
2.0
2.0
2.0
1.9
1.9
1.9

3.6

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3

2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8

3.0
2.9
2.9
2.8
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.4
2.4

Capacity
Index

Outdoor
air temp.
(DB, C)

Notes:
TC: Total Capacity(kW)

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct(High Static) _ 15

Indoor Units

20
14
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

6. Capacity Tables

Indoor Units

Cooling capacity

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

Capacity
Index

Outdoor
air temp.
(DB, C)

4.5

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4

3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7

5.9
5.8
5.8
5.7
5.6
5.5
5.5
5.4
5.3
5.3
5.2
5.1
5.0
5.0
4.9
4.8

3.7
3.6
3.6
3.6
3.5
3.5
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.1
3.0

5.6

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7

5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2

4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0

5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6

4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
5.8
5.7

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.1
4.0

6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.6
6.4
6.4
6.3
6.2
6.0
5.9
5.8

4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8

7.4
7.3
7.2
7.1
7.0
6.9
6.8
6.7
6.6
6.6
6.5
6.4
6.3
6.2
6.1
6.0

4.4
4.3
4.3
4.2
4.1
4.1
4.1
4.0
3.9
3.9
3.8
3.8
3.7
3.6
3.6
3.5

7.1

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3

5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7

4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7

6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1

7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1

5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2

7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.4
7.2

5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.2
5.1

8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.4
8.2
8.1
8.0
7.8
7.7
7.5
7.4

5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.5
5.4
5.3
5.2
5.1
5.0
4.9
4.8

9.3
9.2
9.1
9.0
8.8
8.7
8.7
8.5
8.4
8.3
8.2
8.1
7.9
7.8
7.7
7.6

5.5
5.5
5.4
5.3
5.2
5.2
5.1
5.1
5.0
4.9
4.8
4.8
4.7
4.6
4.6
4.5

Notes:
TC: Total Capacity(kW)

SHC: Sensible Heat Capacity(kW)

16 _ Ceiling Concealed Duct(High Static)

32
24
TC SHC
kW kW

6. Capacity Tables
Cooling capacity

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

Capacity
Index

8.2

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0

8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2

6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1

8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.5
8.4

6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.2
6.1
6.0

9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.7
9.4
9.3
9.2
9.0
8.9
8.7
8.5

6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.5
6.4
6.3
6.2
6.1
6.0
5.9
5.8
5.7

10.8
10.6
10.5
10.4
10.2
10.1
10.0
9.9
9.7
9.6
9.5
9.3
9.2
9.0
8.9
8.8

6.5
6.4
6.3
6.2
6.1
6.0
6.0
5.9
5.8
5.8
5.7
5.6
5.5
5.4
5.3
5.3

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
7.2
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3

6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
6.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9

7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3
8.3

9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
9.9
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5

7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
7.7
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0
9.0

10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3
12.3

7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1
9.1

11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.0
10.8
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
13.1
12.8
12.5

8.1
8.1
8.1
8.1
8.1
8.1
8.1
8.1
8.1
8.1
8.1
8.1
8.1
8.1
7.9
7.7
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.4
9.2
9.0

12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.7
12.5
12.2
12.1
11.9
11.7
11.4
11.2
11.0
14.7
14.7
14.7
14.7
14.7
14.7
14.7
14.7
14.5
14.1
14.0
13.8
13.5
13.3
13.0
12.8

8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.3
8.1
8.0
7.9
7.8
7.6
7.5
7.3
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.8
9.7
9.4
9.3
9.2
9.0
8.8
8.7
8.5

13.9
13.7
13.6
13.4
13.2
13.0
12.9
12.8
12.6
12.4
12.2
12.0
11.8
11.7
11.5
11.3
16.2
15.9
15.8
15.6
15.3
15.1
15.0
14.8
14.6
14.4
14.2
14.0
13.7
13.5
13.4
13.1

8.4
8.2
8.2
8.0
7.9
7.8
7.8
7.7
7.5
7.5
7.3
7.2
7.1
7.0
6.9
6.8
9.7
9.6
9.5
9.3
9.2
9.1
9.0
8.9
8.8
8.6
8.5
8.4
8.3
8.1
8.0
7.9

10.6

12.3

Notes:
TC: Total Capacity(kW)

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct(High Static) _ 17

Indoor Units

20
14
TC SHC
kW kW

Outdoor
air temp.
(DB, C)

6. Capacity Tables

Indoor Units

Cooling capacity

Capacity
Index

14.1

22.4

28.0

Outdoor
air temp.
(DB, C)
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

Notes:
TC: Total Capacity(kW)

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
15.1
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9
18.9

11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
18.0
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5

13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
13.2
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
21.0
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2
26.2

8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
8.7
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
12.9
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1

9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
9.6
14.3
14.3
14.3
14.3
14.3
14.3
14.3
14.3
14.3
14.3
14.3
14.3
14.3
14.3
14.3
14.3
17.8
17.8
17.8
17.8
17.8
17.8
17.8
17.8
17.8
17.8
17.8
17.8
17.8
17.8
17.8
17.8

10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
15.5
15.5
15.5
15.5
15.5
15.5
15.5
15.5
15.5
15.5
15.5
15.5
15.5
15.5
15.5
15.5
19.3
19.3
19.3
19.3
19.3
19.3
19.3
19.3
19.3
19.3
19.3
19.3
19.3
19.3
19.3
19.3

14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
14.1
22.4
22.4
22.4
22.4
22.4
22.4
22.4
22.4
22.4
22.4
22.4
22.4
22.4
22.4
22.4
22.4
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0
28.0

10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
10.6
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
15.7
19.6
19.6
19.6
19.6
19.6
19.6
19.6
19.6
19.6
19.6
19.6
19.6
19.6
19.6
19.6
19.6

SHC: Sensible Heat Capacity(kW)

18 _ Ceiling Concealed Duct(High Static)

15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
14.7
14.4
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
23.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8
29.8

10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.9
10.6
10.4
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
16.1
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2
20.2

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.6
16.2
16.1
15.8
15.5
15.2
14.9
14.7
26.8
26.8
26.8
26.8
26.8
26.8
26.8
26.8
26.8
26.8
26.8
26.8
26.8
26.8
26.8
26.8
33.5
33.5
33.5
33.5
33.5
33.5
33.5
33.5
33.5
33.5
33.5
33.5
33.5
33.5
33.5
33.5

18.5
18.3
18.1
17.8
17.6
17.3
17.2
17.0
16.7
16.5
16.3
16.0
15.8
15.5
15.3
15.1
29.4
29.0
28.7
28.3
27.9
27.5
27.4
27.0
26.6
26.2
25.8
25.4
25.0
24.6
24.3
23.9
36.8
36.3
35.9
35.4
34.9
34.4
34.2
33.7
33.2
32.8
32.3
31.8
31.3
30.8
30.4
29.9

11.4
11.4
11.4
11.4
11.4
11.4
11.4
11.4
11.2
10.9
10.8
10.7
10.5
10.3
10.1
9.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
16.9
21.1
21.1
21.1
21.1
21.1
21.1
21.1
21.1
21.1
21.1
21.1
21.1
21.1
21.1
21.1
21.1

11.3
11.1
11.0
10.8
10.7
10.5
10.5
10.3
10.2
10.0
9.9
9.7
9.6
9.4
9.3
9.2
16.7
16.5
16.3
16.1
15.9
15.6
15.5
15.3
15.1
14.9
14.7
14.4
14.2
14.0
13.8
13.6
20.9
20.6
20.4
20.1
19.8
19.5
19.4
19.1
18.9
18.6
18.3
18.1
17.8
17.5
17.3
17.0

6. Capacity Tables
6.2 Heating Capacity
Indoor air temp. (DB, C)
16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.2

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.8
2.8
2.9
2.9
2.9
2.9
2.9

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
2.7
2.7
2.7
2.7
2.7
2.7

1.7
1.7
1.8
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.5
2.5
2.5
2.5

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

2.8

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.1
2.2
2.3
2.5
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.6
3.6
3.7
3.7
3.7
3.7
3.7

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.1
2.2
2.3
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.1
2.2
2.3
2.4
2.6
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

3.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.7
2.8
2.9
3.1
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.4
4.5
4.6
4.6
4.6
4.6
4.6

2.7
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.3
4.3
4.3
4.3
4.3
4.3
4.3

2.7
2.8
2.9
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0

2.6
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Notes:
TC: Total Capacity(kW)

Ceiling Concealed Duct(High Static) _ 19

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Heating capacity

6. Capacity Tables

Indoor Units

Heating capacity

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

4.5

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

3.4
3.5
3.7
3.9
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.6
5.6
5.8
5.8
5.8
5.8
5.8

3.4
3.5
3.7
3.8
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.4
5.4
5.4
5.4
5.4
5.4
5.4

3.4
3.5
3.7
3.4
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.6
4.9
5.0
5.0
5.0
5.0
5.0
5.0

3.3
3.5
3.7
3.8
4.0
4.3
4.3
4.4
4.4
4.6
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.3
3.4
3.7
3.8
4.0
4.2
4.3
4.4
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7

3.3
3.4
3.6
3.8
4.0
4.2
4.3
4.3
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4

5.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

4.2
4.3
4.6
4.9
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
7.0
7.1
7.2
7.2
7.2
7.2
7.2

4.2
4.3
4.6
4.8
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
6.7
6.7
6.7
6.7
6.7
6.7
6.7

4.2
4.3
4.6
4.3
4.5
4.8
4.9
5.0
5.1
5.4
5.5
5.8
6.2
6.3
6.3
6.3
6.3
6.3
6.3

4.2
4.3
4.6
4.8
5.0
5.4
5.4
5.5
5.6
5.8
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1

4.2
4.3
4.6
4.8
5.0
5.3
5.4
5.5
5.6
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9

4.2
4.3
4.5
4.8
5.0
5.3
5.4
5.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

7.1

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

5.4
5.5
5.8
6.2
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.9
9.0
9.2
9.2
9.2
9.2
9.2

5.4
5.5
5.8
6.1
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.6
8.6
8.6
8.6
8.6
8.6
8.6

5.4
5.5
5.8
5.5
5.8
6.0
6.2
6.3
6.5
6.8
7.0
7.4
7.8
8.0
8.0
8.0
8.0
8.0
8.0

5.3
5.5
5.8
6.1
6.4
6.8
6.9
7.0
7.1
7.4
7.7
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8

5.3
5.4
5.8
6.1
6.4
6.7
6.9
7.0
7.1
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

5.3
5.4
5.8
6.1
6.4
6.7
6.8
6.8
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Notes:
TC: Total Capacity(kW)

20 _ Ceiling Concealed Duct(High Static)

6. Capacity Tables
Heating capacity

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

8.2

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

6.2
6.3
6.7
7.1
7.5
7.8
7.9
8.1
8.4
8.7
9.1
9.7
10.2
10.4
10.6
10.6
10.6
10.6
10.6

6.2
6.3
6.7
7.0
7.5
7.8
7.9
8.1
8.4
8.7
9.1
9.7
9.8
9.8
9.8
9.8
9.8
9.8
9.8

6.2
6.3
6.7
6.3
6.6
7.0
7.1
7.3
7.5
7.8
8.1
8.5
9.0
9.2
9.2
9.2
9.2
9.2
9.2

6.1
6.3
6.7
7.0
7.4
7.8
7.9
8.1
8.2
8.5
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9
8.9

6.1
6.3
6.7
7.0
7.4
7.7
7.9
8.1
8.2
8.5
8.6
8.6
8.6
8.6
8.6
8.6
8.6
8.6
8.6

6.1
6.3
6.6
7.0
7.4
7.7
7.8
7.9
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0
8.0

10.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

8.0
8.2
8.7
9.2
9.6
10.1
10.2
10.5
10.8
11.3
11.8
12.5
13.2
13.4
13.7
13.7
13.7
13.7
13.7

8.0
8.2
8.7
9.0
9.6
10.1
10.2
10.5
10.8
11.3
11.8
12.5
12.7
12.7
12.7
12.7
12.7
12.7
12.7

8.0
8.2
8.7
8.2
8.6
9.0
9.2
9.4
9.7
10.1
10.4
11.0
11.6
11.9
11.9
11.9
11.9
11.9
11.9

7.9
8.2
8.7
9.0
9.5
10.1
10.2
10.5
10.6
11.0
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5
11.5

7.9
8.1
8.7
9.0
9.5
10.0
10.2
10.5
10.6
11.0
11.2
11.2
11.2
11.2
11.2
11.2
11.2
11.2
11.2

7.9
8.1
8.6
9.1
9.5
10.0
10.1
10.2
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4
10.4

12.3

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

9.2
9.5
10.1
10.6
11.2
11.7
11.9
12.1
12.6
13.1
13.7
14.5
15.3
15.5
15.9
15.9
15.9
15.9
15.9

9.2
9.5
10.1
10.5
11.2
11.7
11.9
12.1
12.6
13.1
13.7
14.5
14.8
14.8
14.8
14.8
14.8
14.8
14.8

9.2
9.5
10.1
9.5
10.0
10.4
10.7
10.9
11.3
11.7
12.1
12.8
13.5
13.8
13.8
13.8
13.8
13.8
13.8

9.1
9.5
10.1
10.5
11.0
11.7
11.9
12.1
12.2
12.8
13.3
13.4
13.4
13.4
13.4
13.4
13.4
13.4
13.4

9.1
9.4
10.1
10.5
11.0
11.6
11.9
12.1
12.2
12.8
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0

9.1
9.4
9.9
10.5
11.0
11.6
11.7
11.8
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1
12.1

Notes:
TC: Total Capacity(kW)

Ceiling Concealed Duct(High Static) _ 21

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

6. Capacity Tables

Indoor Units

Heating capacity

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

14.1

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

10.7
11.0
11.6
12.2
12.9
13.5
13.7
14.0
14.5
15.1
15.7
16.7
17.7
17.9
18.3
18.3
18.3
18.3
18.3

10.7
11.0
11.6
12.1
12.9
13.5
13.7
14.0
14.5
15.1
15.7
16.7
17.0
17.0
17.0
17.0
17.0
17.0
17.0

10.7
11.0
11.6
10.9
11.5
12.0
12.3
12.6
13.0
13.5
13.9
14.7
15.5
15.9
15.9
15.9
15.9
15.9
15.9

10.5
11.0
11.6
12.1
12.7
13.5
13.7
14.0
14.1
14.7
15.3
15.4
15.4
15.4
15.4
15.4
15.4
15.4
15.4

10.5
10.8
11.6
12.1
12.7
13.4
13.7
14.0
14.1
14.7
14.9
14.9
14.9
14.9
14.9
14.9
14.9
14.9
14.9

10.5
10.8
11.4
12.1
12.7
13.4
13.5
13.6
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9
13.9

22.4

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

16.9
17.4
18.4
19.4
20.4
21.4
21.7
22.2
22.9
23.9
25.0
26.5
28.0
28.4
29.0
29.0
29.0
29.0
29.0

16.9
17.4
18.4
19.2
20.4
21.4
21.7
22.2
22.9
23.9
25.0
26.5
27.0
27.0
27.0
27.0
27.0
27.0
27.0

16.9
17.4
18.4
17.3
18.2
19.1
19.5
19.9
20.6
21.5
22.1
23.4
24.6
25.2
25.2
25.2
25.2
25.2
25.2

16.6
17.4
18.4
19.2
20.2
21.4
21.7
22.2
22.4
23.3
24.3
24.4
24.4
24.4
24.4
24.4
24.4
24.4
24.4

16.6
17.1
18.4
19.2
20.2
21.2
21.7
22.2
22.4
23.3
23.7
23.7
23.7
23.7
23.7
23.7
23.7
23.7
23.7

16.6
17.1
18.1
19.2
20.2
21.2
21.4
21.6
22.0
22.0
22.0
22.0
22.0
22.0
22.0
22.0
22.0
22.0
22.0

28.0

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

21.1
21.7
23.0
24.3
25.5
26.8
27.1
27.7
28.7
29.9
31.2
33.1
35.0
35.4
36.2
36.2
36.2
36.2
36.2

21.1
21.7
23.0
23.9
25.5
26.8
27.1
27.7
28.7
29.9
31.2
33.1
33.7
33.7
33.7
33.7
33.7
33.7
33.7

21.1
21.7
23.0
21.6
22.7
23.8
24.4
24.9
25.7
26.8
27.6
29.2
30.8
31.5
31.5
31.5
31.5
31.5
31.5

20.8
21.7
23.0
23.9
25.2
26.8
27.1
27.7
28.0
29.1
30.3
30.5
30.5
30.5
30.5
30.5
30.5
30.5
30.5

20.8
21.4
23.0
23.9
25.2
26.5
27.1
27.7
28.0
29.1
29.6
29.6
29.6
29.6
29.6
29.6
29.6
29.6
29.6

20.8
21.4
22.7
24.0
25.2
26.5
26.8
27.0
27.6
27.6
27.6
27.6
27.6
27.6
27.6
27.6
27.6
27.6
27.6

Notes:
TC: Total Capacity(kW)

22 _ Ceiling Concealed Duct(High Static)

7. External Static Pressure (E.S.P) & Air Flow


ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2
ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2

70
80
90
100
110
120
130
140
145
150

Static Pressure(mmAq(Pa))
3(29)

4(39)

5(49)

6(59)

7(69)

8(78)

9(88)

10(98)

12(118)

4.1
7.6
10.7
13.4
15.9
18.6
19.8
22.3
23.2
24.3

8.1
11.2
13.2
16.2
18.8
21.1
22.2
23.1

6.3
9.6
12.6
15.2
18.0
20.3
21.4
22.3

4.9
7.5
10.3
12.8
15.3
17.7
19.1
21.1

4.0
7.7
11.1
14.2
17.1
18.4
19.8

5.5
9.1
12.4
15.5
16.9
18.3

6.7
10.4
13.7
15.3
16.8

5.3
8.8
12.6
13.8
15.2

5.7
9.7
11.8
13.0

ARNU28GBGA2, ARNU36GBGA2, ARNU42GBGA2


Setting Value
70
80
90
100
110
120
130
140
143
150
160

(Unit: CMM)

Static Pressure(mmAq(Pa))
5(49)

6(59)

7(69)

8(78)

9(88)

10(98)

12(118)

14(137)

16(157)

4.0
12.1
17.0
21.4
25.8
30.0
36.0
37.5
41.0
42.4

6.9
15.5
19.6
24.0
28.5
32.1
33.9
38.0
41.6

4.13
11.01
17.53
21.8
26.93
30.41
32.1
36.0
38.2

6.2
14.0
19.8
25.3
29.0
30.7
34.5
36.1

4.2
11.6
17.9
23.4
27.4
28.8
32.1
35

6.6
14.6
21.8
25.9
27.2
30.1
34.6

12.1
18.1
21.6
23.0
26.3
31.1

14.6
17.8
20.1
22.4
26.8

11.3
14.5
16.8
18.2
23.3

ARNU48GBRA2
Setting Value
91
96
101
106
111
116
121
126

(Unit: CMM)
Static Pressure(mmAq(Pa))
5(49)

6(59)

8(78)

46.5
49.9
52.1
51.4
53.6
62.3
67.0
68.2

43.7
46.1
50.2
51.2
53.7
61.0
64.8
67.5

38.2
43.0
47.9
50.4
52.9
60.3
64.1
66.2

10(98) 12(118) 14(137) 15(147) 16(157) 17(168) 18(176) 20(196)


31.3
33.5
39.5
44.4
49.9
55.7
58.2
65.1

23.2
31.1
37.4
43.1
48.3
50.8
52.2
64.3

14.0
18.4
27.3
33.3
40.6
44.8
50.8
57.4

9.0
13.7
25.2
32.1
40.2
42.6
50.3
54.4

3.7
9.0
17.8
28.9
32.8
40.1
45.7
51.2

2.6
8.9
21.0
31.5
37.6
44.6
50.4

6.1
17.9
27.2
32.5
38.8
46.0

8.3
17.5
27.6
32.2
43.5

Note: 1. The above table shows the correlation between the air rates and E.S.P.

Ceiling Concealed Duct(High Static) _ 23

Indoor Units

Setting Value

(Unit: CMM)

7. External Static Pressure (E.S.P) & Air Flow


URNU76GB8A2, URNU96GB8A2
Indoor Units

(Unit: CMM)
Setting Value

Static Pressure(mmAq(Pa))
6(59)

9(88)

12(118)

15(147)

18(177)

20(196)

22(216)

23(226)

25(245)

60

40.5

65

52.7

70

63.7

47.1

75

71.1

56.9

44.7

80

76.3

69.7

55.2

85

83.3

78.6

67.4

55.9

91

89.7

87.1

78.9

67.6

54.2

95

93.4

91.4

86.1

77.0

66.4

50.6

30.0

100

93.4

91.4

88.3

84.9

75.9

69.5

60.8

43.1

105

93.2

91.3

88.3

84.9

81.1

77.4

69.2

67.9

51.3

Note: 1. The above table shows the correlation between the air rates and E.S.P.

24 _ Ceiling Concealed Duct(High Static)

7. External Static Pressure (E.S.P) & Air Flow


ARNU07GBHA2, ARNU09GBHA2, ARNU12GBHA2
ARNU15GBHA2, ARNU18GBHA2, ARNU24GBHA2
High
(factory set)
7k
Standard
High
(factory set)
9k
Standard
High
(factory set)
12k
Standard
High
(factory set)
15k
Standard
High
(factory set)
18k
Standard

24k

Standard
Set value ESP(mmAq(Pa))

Mode

High
(factory set)
Standard

Hl
Mid
Low
Hl
Mid
Low
Hl
Mid
Low
Hl
Mid
Low
Hl
Mid
Low
Hl
Mid
Low
Hl
Mid
Low
Hl
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low

120
117
115
110
107
105
125
120
117
110
107
105
130
125
120
115
110
105
135
130
120
123
120
115
140
135
130
130
125
110
150
145
140
145
135
128

8(78)
6(59)
8(78)
6(59)
8(78)
6(59)
8(78)
6(59)
8(78)
6(59)
8(78)
6(59)

CMM
8.5
7.5
6
8.5
8
7.5
10
8.5
7.5
8.5
8
7.5
12
10
8.5
11
8.5
7.5
13.5
12
8.5
13.5
12
11
15.5
13.5
12.4
15.3
13.6
10.3
18.3
16.9
15.5
19
16.4
14.5

Lower Limit of External


Static Pressure(mmAq(Pa))

Upper Limit of External


Static Pressure(mmAq(Pa))

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

6(59)

12(118)

4(39)

8(78)

ARNU28GBGA2, ARNU36GBGA2, ARNU42GBGA2


Capacity

28k

High
(factory set)
Standard

36k

Standard
Set value ESP(mmAq(Pa))

Mode

High
(factory set)
Standard
High
(factory set)

42k
Standard

HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low

140
136
130
130
124
116
151
145
139
138
130
124
157
154
151
145
138
134

10(98)
8(78)
10(98)
8(78)
10(98)
8(78)

CMM
25.9
24.1
21.8
25.3
21.8
17.6
32.3
29
25.3
28.4
25.3
21.8
34.5
32.3
30.7
32
28.4
27.2

Lower Limit of External


Static Pressure(mmAq(Pa))

Upper Limit of External


Static Pressure(mmAq(Pa))

8(78)

16(157)

6(59)

10(98)

8(78)

14(137)

6(59)

10(98)

8(78)

12(118)

6(59)

10(98)

Ceiling Concealed Duct(High Static) _ 25

Indoor Units

Capacity

7. External Static Pressure (E.S.P) & Air Flow


ARNU48GBRA2
Indoor Units

Capacity

Standard
Set value ESP(mmAq(Pa))

Mode
High
(factory set)

48k
Standard

HI
Mid
Low
HI
Mid
Low

116
111
106
106
101
96

14(137)
10(98)

CMM
44.8
40.6
33.3
44.4
39.5
33.5

Lower Limit of External


Static Pressure(mmAq(Pa))

Upper Limit of External


Static Pressure(mmAq(Pa))

10(98)

20(196)

7(67)

14(137)

URNU76GB8A2, URNU96GB8A2
Capacity

76k

High
(factory set)
Standard

96k

Standard
Set value ESP(mmAq(Pa))

Mode

High
(factory set)
Standard

HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low

102
98
98
86
83
83
105
102
102
94
89
89

22(216)
15(147)
22(216)
15(147)

26 _ Ceiling Concealed Duct(High Static)

CMM
60
50
50
64
50
50
72
64
64
76
64
64

Lower Limit of External


Static Pressure(mmAq(Pa))

Upper Limit of External


Static Pressure(mmAq(Pa))

12(118)

25(245)

12(118)

25(245)

12(118)

25(245)

12(118)

25(245)

8. Electric Characteristics
Units

Power Supply

Input(W)

kW

FLA

1.32

15

0.118

1.06

150

150

BH

1.32

15

0.118

1.06

150

150

ARNU12GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU15GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU18GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU24GBHA2

BH

Max:264

1.32

15

0.118

1.06

150

150

ARNU28GBGA2

BG

Min:198

3.31

15

0.39

2.65

450

450

ARNU36GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU42GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU48GBRA2

BR

3.45

15

0.39

2.76

450

450

URNU76GB8A2

B8

6.47

15

0.75

5.18

800

800

URNU96GB8A2

B8

6.47

15

0.75

5.18

800

800

ARNU07GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU09GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU12GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU15GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU18GBHA2

BH

1.32

15

0.118

1.06

150

150

ARNU24GBHA2

BH

Max:242

1.32

15

0.118

1.06

150

150

ARNU28GBGA2

BG

Min:198

3.31

15

0.39

2.65

450

450

ARNU36GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU42GBGA2

BG

3.31

15

0.39

2.65

450

450

ARNU48GBRA2

BR

3.45

15

0.39

2.76

450

450

URNU76GB8A2

B8

6.47

15

0.75

5.18

800

800

URNU96GB8A2

B8

6.47

15

0.75

5.18

800

800

Type

ARNU07GBHA2

BH

ARNU09GBHA2

Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFM : Indoor Fan Motor

Hz

50

60

Volts

220-240

220

Cooling Heating

Note :
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits,
2. Maximum allowable voltage unbalance between phases is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.

Ceiling Concealed Duct(High Static) _ 27

Indoor Units

MFA

Model

Voltage Range MCA

IFM

9. Sound Levels

Indoor Units

Overall

DISCHARGE

SUCTION

DUCT

DUCT
1.5m

2m

Model

1m
1m

Sound Level dB(A)

Notes:
- Sound measured at 1.5m away from the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operating condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

Sound Level dB(A)

Model

ARNU07GBHA2

H
34

M
33

L
32

ARNU28GBGA2

H
44

M
42

L
40

ARNU09GBHA2

35

34

33

ARNU36GBGA2

46

44

42

ARNU12GBHA2

37

35

34

ARNU42GBGA2

48

46

45

ARNU15GBHA2

39

38

37

ARNU48GBRA2

45

43

41

ARNU18GBHA2

42.5

41

37

URNU76GB8A2

50

48

48

ARNU24GBHA2

45

43

41

URNU96GB8A2

52

50

50

Sound Pressure Level


ARNU09GBHA2

ARNU12GBHA2
80

70

70

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

10

Approximate
Hearing
Threshold
63

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

NC-20

NC-15
125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

NC-65

60

10

NC-25
Approximate
Hearing
Threshold
63

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20

NC-15
125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

28 _ Ceiling Concealed Duct(High Static)

Octave Band Sound Pressure Level (dB re 20Pa )

80

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU07GBHA2
80

10

Approximate
Hearing
Threshold
63

NC-20

NC-15
125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

9. Sound Levels
ARNU15GBHA2

ARNU18GBHA2

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

20

NC-25
Approximate
Hearing
Threshold
63

70

NC-60

250

500

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20

125

NC-65

60

NC-15
1000 2000 4000 8000

10

Approximate
Hearing
Threshold
63

ARNU28GBGA2

NC-50

NC-40

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25
Approximate
Hearing
Threshold
63

NC-30

250

500

NC-15
1000 2000 4000 8000

10

63

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

10

NC-55
NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold
63

125

250

500

NC-15
1000 2000 4000 8000

Octave Band Center Frequency (Hz)

250

500

NC-15
1000 2000 4000 8000

NC-65

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25
Approximate
Hearing
Threshold
63

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

NC-25
Approximate
Hearing
Threshold
63

125

250

500

Octave Band Center Frequency (Hz)

250

500

NC-15
1000 2000 4000 8000

Octave Band Center Frequency (Hz)

URNU96GB8A2

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

NC-20
NC-15
1000 2000 4000 8000

NC-20

125

80

NC-65

60

10

NC-15
1000 2000 4000 8000

NC-60

10

URNU76GB8A2

70

NC-20

500

60

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20Pa )

NC-60

250

70

NC-20

125

80

NC-65

125

20

NC-25
Approximate
Hearing
Threshold
63

ARNU48GBRA2
70

NC-20

ARNU42GBGA2

NC-65

60

80

50

Approximate
Hearing
Threshold

80

Octave Band Center Frequency (Hz)

60

NC-25

20

Octave Band Center Frequency (Hz)

70

NC-20

125

NC-35

30

Octave Band Sound Pressure Level (dB re 20Pa )

NC-55

50

NC-45

40

Octave Band Sound Pressure Level (dB re 20Pa )

NC-60

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

500

NC-55

50

ARNU36GBGA2

NC-65

60

20

Octave Band Sound Pressure Level (dB re 20Pa )

NC-60

80

70

10

250

NC-15
1000 2000 4000 8000

NC-65

60

Octave Band Center Frequency (Hz)

80

10

70

NC-20

125

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20Pa )

NC-60

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

NC-65

60

80

10

NC-25
Approximate
Hearing
Threshold
63

NC-20

125

250

500

NC-15
1000 2000 4000 8000

Octave Band Center Frequency (Hz)

Ceiling Concealed Duct(High Static) _ 29

Indoor Units

70

10

ARNU24GBHA2

80

80

10. Installation

Indoor Units

Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Air outlet vents

Air filters

Air intake vents


TEMP

Wired LCD Remote Control

Remote Controller

Required Parts

Required Tools

Connecting cable
Pipes: Gas side
Liquid side
Hanging Bolt
(W 3/8 or M10 length 650mm)
Insulated drain hose
Additional Drain hose

Level
Screw driver
Electric drill
Hole core drill
Flaring Tool set
Torque Wrenches
Hexagonal Wrench
Gas-leak detector
Thermometer

10.1 Selection of the best location


Install the air conditioner in the location that satisfies the
following conditions.
The place shall easily bear a load exceeding four times
the indoor units weight.
The place shall be able to inspect the unit as the figure.
The place where the unit shall be leveled.
The place shall allow easy water drainage.(Suitable
dimension H is necessary to get a slope to drain as figure.)
The place shall easily connect with the outdoor unit.
The place where the unit is not affected by an electrical
noise.
The place where air circulation in the room will be good .
There should not be any heat source or steam near the
unit.
The servicing inspection hole in the ceiling should be as
large as the product
The selection of the servicing hole should be approved
by the customer

30 _ Ceiling Concealed Duct(High Static)

[Inspection Hole Standard]


Number of
Inspection hole

Distance between
False ceiling & Actual ceiling

More than 100cm

20cm to 100cm

Hole size should be


more than the size of IDU.

Less than 20cm

Remarks
Sufficient space in the
ceiling for servicing.
Insufficient space.
Difficult for servicing
Minimum height for
motor replacement.

10. Installation
10.2 Ceiling dimension and hanging
bolt location

BH/BG/BR Chassis

C
E

CASE 1

POSITION OF SUSPENSION BOLT

(G)

Apply a joint-canvas between the unit and duct to absorb


unnecessary vibration.
Apply a filter Accessory at air return hole.
Refer to the Dimensions.
(Unit:mm)
Dimension

(G)

932

882

355

47

450

30

87

750

158

BG

1232

1182

355

47

450

30

87

830

186

BR

1282 1230

477

56

590

30

Chassis

BH

Drainage hole

B8 Chassis

120 1006 294

(Unit:mm)
Dimension

Chassis

B8

1680 1565 1160 330 460 580 700 1400 1635 390 445 15

Install the unit leaning to a drainage hole side as a figure


for easy water drainage.

CASE 2
POSITION OF CONSOLE BOLT
A place where the unit will be leveled and that can support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.

M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

Ceiling Concealed Duct(High Static) _ 31

Indoor Units

Installation of Unit
Install the unit above the ceiling correctly.

A
B

10. Installation

Indoor Units

NOTE:
Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat
exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.
Select and mark the position for fixing bolts.
Insert the set anchor and washer onto the suspen Drill the hole for set anchor on the face of ceiling.
sion bolts for locking the suspension bolts on the
ceiling.
Mount the suspension bolts to the set anchor firmly.
Secure the installation plates onto the suspension
bolts (adjust level roughly) using nuts, washers and
spring washers.

Old building

New building

1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
CAUTION

5 Suspension
bolts

Tighten the nut and bolt to prevent unit falling.

10.3 Connecting Cables between Indoor Unit and Outdoor Unit


Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively
Terminal Block Indoor
1(L)

2(N)

SODU

INTERNET DRY1 DRY2 GND 12V

IDU
-

Outdoor
Unit

INDOOR POWER INPUT

WARNING
Make sure that the screws of the terminal are not loose.

Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the
0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.

32 _ Ceiling Concealed Duct(High Static)

10. Installation
THERMAL INSULATION

All thermal insulation must comply with local requirement.

INDOORUNIT

Union for liquid pipe

Thermal insulator for refrigerant pipe


(Local supply) Thermal insulator for
piping(Local supply)

Refrigerant pipe and thermal


insulator(Local supply)
Hose clamp for thermal insulator
(Local supply)

B8

Thermal insulator for refrigerant pipe


(Local supply)
Union for gas pipe

Overlap with thermal


insulator for piping.
Hose clamp for thermal insulator(Local supply)
Make sure that there is no clearance here.

Union for gas pipe


Thermal insulator for refrigerant pipe
(Local supply)
Hose crip for thermal insulator
(Local supply)
Refrigerant pipe and therma
insulator(Local supply)

Union for liquid pipe

10.4 Checking the Drainage


1) Checking the Drainage

BH/BG/BR Chassis

1. Remove the Air Filter.

B8

2. Check the drainage.


Spray one or two glasses of water on the evaporator.
Ensure that water flows through drain hose of
indoor unit without any leakage.

Ceiling Concealed Duct(High Static) _ 33

Indoor Units

BH/BG/BR Chassis

10. Installation
Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra force on the
drain port on the indoor unit.
The outside diameter of the drain connection on the indoor unit is 32mm.

Upward
routing
not allowed

Pipe clamp
Indoor unit

Maintenance
drain port

Piping material: Polyvinyl chloride pipe inner


diometes 25mm and pipe fittings
Be sure to install heat insulation on the drain piping.

1/50~1/100
MAX 700mm

Heat insulation material: Polyethylene foam with


thickness more than 8 mm.

Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Feed water

Drain Pump

Flexible drain hose


(accessory)

Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
Main
drain pipe
Feed water to the flexible drain hose and check the piping
for leakage.
Drain

Be sure to check the drain pump for normal operation and


port
Glue the joint
noise when electrical wiring is complete.
Drain hose connection
Use the clip (accessory) When the test is complete, connect the flexible drain hose to
the drain port on the indoor unit.

Drain pan

CAUTION
The supplied flexible drain hose should not be strained.
A strained hose may cause leakage of water.

Max 300mm

Hanger
distance
1~15m

Hanger Bracket
1/50~1/100 slope

Metal
clamp
Flexible drain hose

Max 700mm

Indoor Units

10.5 Indoor Unit Drain Piping

Insulation

Flexible drain hose


Flexible drain hose
Flexible drain hose

34 _ Ceiling Concealed Duct(High Static)

10. Installation
10.6 Ground drain piping
a) It is standard work practice to make connections to the main pipe from above. The pipe down from the
combination should be as large as possible.

Indoor Units

Face the vent pipe opening facing downward to


keep foreign matter from penetrating the system
Face piping
downward
Vent pipe

b) The pipe work should be kept as short as possible and the number of indoor units per group kept to a
minimum.

10.7 Use of an auxiliary drain hose(flexible)


a) To connect drain pipe to the drain socket on the indoor unit, an auxiliary flexible drain hose should be
used. auxiliary flexible drain hose allows that the drain pipe can be connected to the socket without breaking by excessive strain.
Auxiliary drain hose

Thermal insulation (drain pipe area)

Metal clamp

Metal clamp
Thermal insulation(bend area)
Drain pan

Important points
- The drain pipe should be at least equal in size to that of the indoor unit.
- The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe.
- The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has
been connected some water should be added to the drain pan and the drain pump to check and see if it is
functioning correctly.
- All connections should be secure. (Special care is needed with PVC pipe)
- Insulate auxiliary drain hose with thermal insulation band.

Ceiling Concealed Duct(High Static) _ 35

10. Installation

Indoor Units

WIRED REMOTE CONTROLLER INSTALLATION


Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place
away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller
LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller
Remote

TEMP

Remote Controller

5feet
(1.5meters)

no

no

Fig.1 Typical locations for remote controller

36 _ Ceiling Concealed Duct(High Static)

11. Accessories
Standard Accessories
Drain hose

Clamp metal

Quantity

1 EA

1 EA

Washer for
hanging backet
8 EA

Clamp
(Tie Wrap)

Insulation for
fitting

4 EA

1 SET

(Other)

Owner's manual
Installation manual
Shape

for gas pipe

for liquid pipe

CAUTION
Use only those accessories (Standard or optional) which have designated specifications.

Ceiling Concealed Duct(High Static) _ 37

Indoor Units

Name

Indoor unit
Ceiling Concealed Duct(Low Static)
1. List of functions
2. Specifications
3. Dimensions & Gravity point
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. External Static Pressure (E.S.P) & Air Flow
8. Electric Characteristics
9. Sound Levels
10. Installation
11. Accessories

1. List of functions
Category

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Air supply outlet


Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2,


ARNU15GB1G2, ARNU18GB2G2, ARNU24GB2G2
1
3/3/3
X
X
O
O
O
X
O
O
O
O(Heat recovery)
X
O(Heat pump or Cooling only)
O
O
O
O
O
O
O
Accessory
Accessory
Accessory
Accessory
X
Accessory
Accessory
-

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

Ceiling Concealed Duct(Low Static) _ 1

Indoor Units

Air flow

Function

2. Specifications

Indoor Units

Type
Model
Cooling Capacity

Heating Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Casing
Dimensions(WxDxH) Body

mm
inch

Rows x Columns x FPI


Face Area
m3
Type
Motor Output x Number
W
Running Current
A
Air Flow Rate(H / M / L)
CMM
(High Mode-factory set)
cfm
Fan
External Static Pressure mmAq(Pa)
Air Flow Rate(H / M / L)
CMM
(Standard Mode)
cfm
External Static Pressure mmAq(Pa)
Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Coil

Power Supply
Refrigerant Control
Power cable
Transmission cable

, V, Hz
mm2
mm2

Ceiling Concealed Duct (Low Static)


ARNU07GB1G2
ARNU09GB1G2
ARNU12GB1G2
2.2
2.8
3.6
1,900
2,400
3,100
7,500
9,600
12,300
2.5
3.2
4.0
2,200
2,800
3,400
8,500
10,900
13,600
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
820 x 575 x 190
820 x 575 x 190
820 x 575 x 190
32.3 x 21.7 x 7.5
32.3 x 21.7 x 7.5
32.3 x 21.7 x 7.5
2 x 11 x 21
2 x 11 x 21
2 x 11 x 21
0.16
0.16
0.16
Sirocco Fan
Sirocco Fan
Sirocco Fan
28
28
28
0.15
0.15
0.15
8.5 / 7.5 / 6.5
9.5 / 8.5 / 7.5
10.5 / 9.5 / 8.5
300 / 265 / 229
335 / 300 / 265
371 / 335 / 300
2(20)
2(20)
2(20)
8.5 / 7.5 / 6.5
9.5 / 8.5 / 7.5
10.5 / 9.5 / 8.5
300 / 265 / 229
335 / 300 / 265
371 / 335 / 300
0(0)
0(0)
0(0)
Direct
Direct
Direct
BLDC
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Foamed polystrene
Fuse
Fuse
Fuser
6.35(1/4)
6.35(1/4)
6.35(1/4)
12.7(1/2)
12.7(1/2)
12.7(1/2)
25.4(1)
25.4(1)
25.4(1)
21(46.3)
21(46.3)
21(46.3)
33 / 32 / 29
34 / 33 / 32
35 / 34 / 33
1, 220-240, 50
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
1, 220, 60
EEV
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Noise Level is Standard Mode
(for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))
7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling Concealed Duct(Low Static)

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specifications
Type
Model

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Noise Level is Standard Mode
(for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dB(A))
7. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Ceiling Concealed Duct(Low Static) _ 3

Indoor Units

Ceiling Concealed Duct (Low Static)


ARNU15GB1G2
ARNU18GB2G2
ARNU24GB2G2
4.5
5.6
7.1
Cooling Capacity
3,900
4,800
6,100
15,400
19,100
24,200
5.0
6.3
8.0
Heating Capacity
4,300
5,400
6,900
17,100
21,500
27,300
Casing
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
mm
820 x 575 x 190
1,100 x 575 x 190
1,100 x 575 x 190
Dimensions(WxDxH) Body
inch
32.3 x 21.7 x 7.5
43.3 x 21.7 x 7.5
43.3 x 21.7 x 7.5
Rows
x
Columns
x
FPI
2
x
11
x
21
3
x
10
x
18
3 x 10 x 18
Coil
Face Area
m3
0.16
0.23
0.23
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output x Number
W
28
76
76
Running Current
A
0.15
0.38
0.38
Air Flow Rate(H / M / L)
CMM
11.5 / 10.5 / 9.5
16.0 / 14.0 / 12.0
19.0 / 17.0 / 15.0
(High Mode-factory set)
cfm
406 / 371 / 335
565 / 494 / 424
671 / 600 / 530
Fan
External Static Pressure mmAq(Pa)
2(20)
2(20)
2(20)
Air Flow Rate(H / M / L)
CMM
11.5 / 10.5 / 9.5
16.0 / 14.0 / 12.0
19.0 / 17.0 / 15.0
(Standard Mode)
cfm
406 / 371 / 335
565 / 494 / 424
671 / 600 / 530
External Static Pressure mmAq(Pa)
0(0)
0(0)
0(0)
Drive
Direct
Direct
Direct
Motor type
BLDC
BLDC
BLDC
Temperature Control
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Sound Absorbing Thermal Insulation Material
Foamed polystrene
Foamed polystrene
Foamed polystrene
Air Filter
Safety Device
Fuse
Fuse
Fuse
Liquid Side
mm(inch)
6.35(1/4)
6.35(1/4)
9.52(3/8)
Pipe Connections Gas Side
mm(inch)
12.7(1/2)
12.7(1/2)
15.88(5/8)
Drain Pipe(Internal Dia.) mm(inch)
25.4(1)
25.4(1)
25.4(1)
Net Weight
kg(lbs)
21(46.3)
26(57.3)
26(57.3)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
38 / 37 / 36
40 / 37 / 34
43 / 40 / 37
1,
220-240,
50
1,
220-240,
50
1,
220-240, 50
Power Supply
, V, Hz
1, 220, 60
1, 220, 60
1, 220, 60
Refrigerant Control
EEV
EEV
EEV
Power cable
mm2
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
Transmission cable
mm2
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

575

18

154

383

18

B1 : 448
B2 : 573

B
A

5
13

161
14
B1 : 186
B2 : 175
B1 : 73
B2 : 81

4 _ Ceiling Concealed Duct(Low Static)


4

216
24

277

190

65
60

190

Gas pipe connection


Drain pipe connection
Power supply connection
Air discharge
Air suction

2
3
4
5
6

1072

794

Descripition

(unit : mm)

1131

856

Unit size(7k,9k,12k,18k):6.35
Unit size(24k):9.52
Unit size(7k,9k,12k,18k):12.7
Unit size(24k):15.88

1008

728

(unit: mm)

Gravity point

CHASSIS CODE: B1/B2

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Liquid pipe connection

Name

1100

820

Number

ARNU18GB2G2
ARNU24GB2G2

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

ARNU07GB1G2
ARNU09GB1G2
ARNU12GB1G2
ARNU15GB1G2

ARNU07GB1G2
ARNU09GB1G2
ARNU12GB1G2
ARNU15GB1G2
ARNU18GB2G2
ARNU24GB2G2

Ceiling Concealed Duct (Low Static)

Indoor Units

3. Dimensions & Gravity point

4. Piping Diagrams

EEV
Filter

Th3

:Cooling
:Heating

Th2
Sirocco Fan

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GB1G2

12.7(1/2)

6.35(1/4)

ARNU09GB1G2

12.7(1/2)

6.35(1/4)

ARNU12GB1G2

12.7(1/2)

6.35(1/4)

ARNU15GB1G2

12.7(1/2)

6.35(1/4)

ARNU18GB2G2

12.7(1/2)

6.35(1/4)

ARNU24GB2G2

15.88(5/8)

9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Ceiling Concealed Duct(Low Static) _ 5

Indoor Units

Heat Exchanger

5. Wiring Diagrams

Indoor Units

B1/B2 Chassis

CONNECTOR NUMBER
CN-MOTOR1
CN-MOTOR2
CN-PIPE/OUT
CN-PIPE/IN
CN-ROOM
CN-REMO
CN-FLOAT
CN-EEV
CN-D/PUMP
CN-OPTION
CN-COM
CN-D/PUMP
CN-POWER
CN-ZONE
CN-DISPLAY
CN-CC

SPEC.
Fan motor output
Fan motor output
Discharge pipe sensor
Suction pipe sensor
Room sensor
Remote controller
Float switch input
EEV output
Drain pump output
Option PWB.
Communication
Drain pump output
AC power supply
Zone Controller
RF Remote controller
Dry contact

DESCRIPTION
Motor output of BLDC
Motor output of BLDC
Pipe out thermistor
Pipe in thermistor
Room thermistor
Remote control line
Float switch sensing
EEV control output
AC output for drain pump
Communication between main and option
Communication between indoor and outdoor
AC output for drain pump
AC power line input for indoor controller
Zone control line
RF remote control line
Dry contact line

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

6 _ Ceiling Concealed Duct(Low Static)

6. Capacity Tables
6.1 Cooling Capacity

2.2

2.8

3.6

Outdoor
air temp.
(DB, C)
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

Notes:
TC: Total Capacity(kW)

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.2
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.9
2.9
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.7
3.7

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.6
1.6
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.0
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.6
2.6

30
22
TC SHC
kW
kW
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
2.3
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
4.0
3.9
3.8
3.7

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.6
1.6
1.6
1.6
1.5
1.5
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.1
2.1
2.1
2.0
2.0
1.9
1.9
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.7
2.7
2.6
2.6
2.6
2.5
2.5

32
24
TC SHC
kW kW
2.9
2.9
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8

1.7
1.7
1.7
1.6
1.6
1.6
1.6
1.6
1.5
1.5
1.5
1.5
1.5
1.4
1.4
1.4
2.2
2.1
2.1
2.1
2.1
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.9
1.8
1.8
1.8
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
2.3
2.3

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct(Low Static) _ 7

Indoor Units

Capacity
Index

Cooling capacity

6. Capacity Tables

Indoor Units

Cooling capacity

Capacity
Index

4.5

5.6

7.1

Outdoor
air temp.
(DB, C)
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

Notes:
TC: Total Capacity(kW)

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6

3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1

3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

SHC: Sensible Heat Capacity(kW)

8 _ Ceiling Concealed Duct(Low Static)

4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
5.8
5.7
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.4
7.2

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.0
3.9
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.1
5.0

30
22
TC SHC
kW
kW
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.6
6.4
6.4
6.3
6.2
6.0
5.9
5.8
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.4
8.2
8.1
8.0
7.8
7.7
7.5
7.4

3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
3.9
3.9
3.8
3.7
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.2
5.2
5.1
5.0
4.9
4.8
4.7

32
24
TC SHC
kW kW
5.9
5.8
5.8
5.7
5.6
5.5
5.5
5.4
5.3
5.3
5.2
5.1
5.0
5.0
4.9
4.8
7.4
7.3
7.2
7.1
7.0
6.9
6.8
6.7
6.6
6.6
6.5
6.4
6.3
6.2
6.1
6.0
9.3
9.2
9.1
9.0
8.8
8.7
8.7
8.5
8.4
8.3
8.2
8.1
7.9
7.8
7.7
7.6

3.5
3.5
3.4
3.4
3.3
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9
2.9
2.8
4.2
4.2
4.1
4.1
4.0
4.0
3.9
3.9
3.8
3.8
3.7
3.7
3.6
3.5
3.5
3.4
5.4
5.3
5.2
5.2
5.1
5.0
5.0
4.9
4.8
4.8
4.7
4.6
4.6
4.5
4.4
4.4

6. Capacity Tables
6.2 Heating Capacity
Indoor air temp. (DB, C)
16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.2

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.8
2.8
2.9
2.9
2.9
2.9
2.9

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
2.7
2.7
2.7
2.7
2.7
2.7

1.7
1.7
1.8
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.5
2.5
2.5
2.5

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

2.8

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.1
2.2
2.3
2.5
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.6
3.6
3.7
3.7
3.7
3.7
3.7

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.1
2.2
2.3
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.1
2.2
2.3
2.4
2.6
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

3.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.7
2.8
2.9
3.1
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.4
4.5
4.6
4.6
4.6
4.6
4.6

2.7
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.3
4.3
4.3
4.3
4.3
4.3
4.3

2.7
2.8
2.9
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0

2.6
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Notes:
TC: Total Capacity(kW)

Ceiling Concealed Duct(Low Static) _ 9

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Heating capacity

6. Capacity Tables

Indoor Units

Heating capacity
Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

4.5

5.6

7.1

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

3.4
3.5
3.7
3.9
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.6
5.6
5.8
5.8
5.8
5.8
5.8
4.2
4.3
4.6
4.9
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
7.0
7.1
7.2
7.2
7.2
7.2
7.2

3.4
3.5
3.7
3.8
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.4
5.4
5.4
5.4
5.4
5.4
5.4
4.2
4.3
4.6
4.8
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
6.7
6.7
6.7
6.7
6.7
6.7
6.7

3.4
3.5
3.7
3.4
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.6
4.9
5.0
5.0
5.0
5.0
5.0
5.0
4.2
4.3
4.6
4.3
4.5
4.8
4.9
5.0
5.1
5.4
5.5
5.8
6.2
6.3
6.3
6.3
6.3
6.3
6.3

3.3
3.5
3.7
3.8
4.0
4.3
4.3
4.4
4.4
4.6
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.2
4.3
4.6
4.8
5.0
5.4
5.4
5.5
5.6
5.8
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1

3.3
3.4
3.7
3.8
4.0
4.2
4.3
4.4
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.2
4.3
4.6
4.8
5.0
5.3
5.4
5.5
5.6
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9

3.3
3.4
3.6
3.8
4.0
4.2
4.3
4.3
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.2
4.3
4.5
4.8
5.0
5.3
5.4
5.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

5.4
5.5
5.8
6.2
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.9
9.0
9.2
9.2
9.2
9.2
9.2

5.4
5.5
5.8
6.1
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.6
8.6
8.6
8.6
8.6
8.6
8.6

5.4
5.5
5.8
5.5
5.8
6.0
6.2
6.3
6.5
6.8
7.0
7.4
7.8
8.0
8.0
8.0
8.0
8.0
8.0

5.3
5.5
5.8
6.1
6.4
6.8
6.9
7.0
7.1
7.4
7.7
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8

5.3
5.4
5.8
6.1
6.4
6.7
6.9
7.0
7.1
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

5.3
5.4
5.8
6.1
6.4
6.7
6.8
6.8
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Notes:
TC: Total Capacity(kW)

10 _ Ceiling Concealed Duct(Low Static)

7. External Static Pressure (E.S.P) & Air Flow


ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2

60
65
70
75
80
85
90
95
100
105
110
115

Static Pressure(mmAq(Pa))
0(0)
6.02
6.95
7.69
8.46
9.5
10.35
10.81
11.57
12.58
13.31
14.2
14.82

1(10)
2.25
3.32
5.16
6.93
7.37
8.72
9.66
10.31
11.22
12.27
13.24
13.92

2(20)

3(29)

4(39)

0.61
0.73
1.19
2.42
3.4
5.33
6.75
8.56
9.75
10.89
12.15
12.64

0.54
0.65
0.77
0.87
1.35
3.15
4.73
7.46
8.64
10.49
11.16

0.48
0.56
0.63
0.72
0.88
0.98
1.03
2.31
5.01
7.7
9.48

ARNU18GB2G2, ARNU24GB2G2
Setting Value
65
70
75
80
85
90
95
100
105
110
115
120
125
130

(Unit: CMM)
Static Pressure(mmAq(Pa))

0(0)

1(10)

2(20)

3(29)

4(39)

10.07
11.39
12.01
13.21
14.24
15.04
16.02
17.11
17.99
19.04
19.77
20.94
21.97
22.83

6.9
8.49
9.79
11.03
12.36
13.34
14.63
15.56
16.53
17.71
18.62
19.92
20.56
21.98

0.82
2.2
4.2
5.92
9.41
10.8
12.5
13.66
15.17
16.22
17.1
18.56
19.25
20.75

0.92
2.1
5.29
7.59
11.53
12.35
14.23
15.23
16.98
17.68
19.32

1.01
1.34
5.35
7.67
10.45
13.25
14.66
16.06
17.73

Note :
1. The above table shows the correlation between the air rates and E.S.P.

Ceiling Concealed Duct(Low Static) _ 11

Indoor Units

Setting Value

(Unit: CMM)

7. External Static Pressure (E.S.P) & Air Flow


ARNU07GB1G2, ARNU09GB1G2, ARNU12GB1G2, ARNU15GB1G2
Indoor Units

Capacity

7k

High
(factory set)
Standard

9k

Standard
Set value ESP(mmAq(Pa))

Mode

High
(factory set)
Standard
High
(factory set)

12k
Standard
High
(factory set)
15k
Standard

HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low

94
92
86
75
69
62
99
94
92
82
75
69
103
99
94
89
80
75
107
105
99
95
89
82

2(20)
0(0)
2(20)
0(0)
2(20)
0(0)
2(20)
0(0)

CMM
8.5
7.5
6.5
8.5
7.5
6.5
9.5
8.5
7.5
9.5
8.5
7.5
10.5
9.5
8.5
10.5
9.5
8.5
11.5
10.5
9.5
11.5
10.5
9.5

Lower Limit of External


Static Pressure(mmAq(Pa))

Upper Limit of External


Static Pressure(mmAq(Pa))

4(39)

4(39)

4(39)

4(39)

4(39)

4(39)

4(39)

4(39)

ARNU18GB2G2, ARNU24GB2G2
Capacity

18k

High
(factory set)
Standard

24k

Standard
Set value ESP(mmAq(Pa))

Mode

High
(factory set)
Standard

HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low

110
101
93
95
84
75
125
115
105
110
100
90

2(20)
0(0)
2(20)
0(0)

12 _ Ceiling Concealed Duct(Low Static)

CMM
16
14
12
16
14
12
19
17
15
19
17
15

Lower Limit of External


Static Pressure(mmAq(Pa))

Upper Limit of External


Static Pressure(mmAq(Pa))

4(39)

4(39)

4(39)

4(39)

8. Electric Characteristics
Units
Model

Type

Power Supply
Hz

Volts

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

B1

0.22

15

0.028

0.17

30

30

ARNU09GB1G2

B1

0.22

15

0.028

0.17

30

30

ARNU12GB1G2

B1

Max:264

0.22

15

0.028

0.17

30

30

ARNU15GB1G2

B1

Min:198

0.22

15

0.028

0.17

30

30

ARNU18GB2G2

B2

0.55

15

0.076

0.44

80

80

ARNU24GB2G2

B2

0.55

15

0.076

0.44

80

80

ARNU07GB1G2

B1

0.22

15

0.028

0.17

30

30

ARNU09GB1G2

B1

0.22

15

0.028

0.17

30

30

ARNU12GB1G2

B1

Max:242

0.22

15

0.028

0.17

30

30

ARNU15GB1G2

B1

Min:198

0.22

15

0.028

0.17

30

30

ARNU18GB2G2

B2

0.55

15

0.076

0.44

80

80

ARNU24GB2G2

B2

0.55

15

0.076

0.44

80

80

50

60

220-240

220

Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFM : Indoor Fan Motor
Note :
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above
the listed range limits,
2. Maximum allowable voltage unbalance between phases is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.

Ceiling Concealed Duct(Low Static) _ 13

Indoor Units

ARNU07GB1G2

9. Sound Levels

Indoor Units

Overall
Notes:
- Sound measured at 1.5m away from the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operating condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

1.5m

Ceiling
2.0m
Microphone

Sound Levels dB(A)


Model Name

H
33
34
35
38
40
43

ARNU07GB1G2
ARNU09GB1G2
ARNU12GB1G2
ARNU15GB1G2
ARNU18GB2G2
ARNU24GB2G2

M
32
33
34
37
37
40

L
29
32
33
36
34
37

Sound Pressure Level


ARNU09GB1G2

70

70

70

NC-65

60
NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

63

NC-55

50
NC-50
NC-45

40
NC-40

30

NC-30

NC-15

250

500

10

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

ARNU15GB1G2

250

500

NC-55
NC-50
NC-45
NC-40
NC-35

30

NC-30

20

NC-25

Approximate
Hearing
Threshold
63

Octave Band Sound Pressure Level (dB re 20Pa )

NC-60

40

NC-15

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

NC-40
NC-35

30

NC-30

NC-25
NC-20
NC-15

10
63

1000 2000 4000 8000

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

ARNU24GB2G2
80

70

NC-65

60
NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

NC-25

20
Approximate
Hearing
Threshold

NC-20

125

NC-45

40

ARNU18GB2G2

NC-65

50

NC-50

Approximate
Hearing
Threshold

80

70

10

125

NC-55

50

Octave Band Center Frequency (Hz)

80

60

NC-60

NC-20
NC-15

63

NC-65

60

20

NC-25

Approximate
Hearing
Threshold

NC-20

125

NC-35

70

NC-65

60
NC-60

NC-15

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

14 _ Ceiling Concealed Duct(Low Static)

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

NC-25

20
Approximate
Hearing
Threshold

NC-20

10
63

Octave Band Sound Pressure Level (dB re 20Pa )

10

NC-60

20

NC-25

Approximate
Hearing
Threshold

NC-65

60

Octave Band Sound Pressure Level (dB re 20Pa )

80

20

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU12GB1G2

80

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU07GB1G2
80

NC-20
NC-15

10
63

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

10. Installation
Please read the instruction sheets completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Indoor Units

Required Parts

Required Tools

Connecting cable
Pipes: Gas side
Liquid side
Hanging Bolt
(W 3/8 or M10 length 650mm)
Insulated drain hose
Additional Drain hose

Level
Screw driver
Electric drill
Hole core drill
Flaring Tool set
Torque Wrenches
Hexagonal Wrench
Gas-leak detector
Thermometer

10.1 Selection of the best location


Install the air conditioner in the location that satisfies
the
following conditions.
The place shall easily bear a load exceeding four
times the indoor units weight.
The place shall be able to inspect the unit as given in
the
figure.
The place where the unit shall be leveled.
The place shall allow easy water drainage.(Suitable
dimension H is necessary to get a slope to drain as
figure.)
The place shall easily connect with the outdoor unit.
The place where the unit is not affected by an electrical noise.
The place where air circulation in the room will be
good .
There should not be any heat source or steam near
the unit.
The servicing inspection hole in the ceiling should be
as large as the product.
The selection of the servicing hole should be
approved by the customer.

[Inspection Hole Standard]


Number of
Inspection hole

Distance between
False ceiling & Actual ceiling

More than 100cm

20cm to 100cm

Hole size should be


more than the size of IDU.

Less than 20cm

Remarks
Sufficient space in the
ceiling for servicing.
Insufficient space.
Difficult for servicing
Minimum height for
motor replacement.

Inspection hole
(600X600)
Control box

Top view
(unit: mm)

600

600

Front view

Ceiling Concealed Duct(Low Static) _ 15

10. Installation

Indoor Units

10.2 Ceiling dimension and hanging bolt


location
Installation of Unit
Install the unit above the ceiling correctly.

CASE 1
M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

POSITION OF SUSPENSION BOLT


Apply a joint-canvas between the unit and duct to absorb
unnecessary vibration.

Install the unit leaning to a drainage hole side as a figure


for easy water drainage.

CASE 2
POSITION OF CONSOLE BOLT
A place where the unit will be leveled and that can support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.

NOTE:
Throughly study the following installation locations:
1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat
exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily
steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.

16 _ Ceiling Concealed Duct(Low Static)

10. Installation
10.3 Checking the Drainage

10.4 Indoor Unit Drain Piping


Upward
routing
not allowed

Drain piping must have down-slope (1/50 to 1/100): be sure not to pro- Pipe clamp
vide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra force on the
Indoor unit
drain port on the indoor unit.
The outside diameter of the drain connection on the indoor unit is 32mm.
Maintenance
drain port

Piping material: Polyvinyl chloride pipe inner


diometes 25mm and pipe fittings
Be sure to install heat insulation on the drain piping.

1/50~1/100

Heat insulation material: Polyethylene foam with


thickness more than 8 mm.

MAX 700mm

Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Feed water

Flexible drain hose


(accessory)
Main
drain pipe

Drain Pump

Drain
port

Glue the joint

Drain hose connection


Use the clip (accessory)

Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
Feed water to the flexible drain hose and check the piping
for leakage.
Be sure to check the drain pump for normal operating and
noise when electrical wiring is complete.
When the test is complete, connect the flexible drain hose to
the drain port on the indoor unit.

Drain pan

CAUTION
The supplied flexible drain hose should not be strained.
A strained hose may cause leakage of water.

Hanger
distance
1~15m

Hanger Bracket
1/50~1/100 slope

Metal
clamp
Flexible drain hose

Max 700mm

Max 300mm

Insulation

Flexible drain hose

Ceiling Concealed
Duct(Low
Static)
Flexible
drain hose _ 17
Flexible drain hose

Indoor Units

Spray one or two glasses of water on the evaporator.


Ensure that water flows drain hose of indoor unit without any leakage.

10. Installation

Indoor Units

10.5 Ground drain piping


a) It is standard work practice to make connections to the main pipe from above. The pipe down from the
combination should be as large as possible.

Face the vent pipe mouth downward to keep


foreign matter from penetrating the system
Face piping
downward
Vent pipe

b) The pipe work should be kept as short as possible and the number of indoor units per group kept to a
minimum.

10.6 Use of an auxiliary drain hose(flexible)


a) To connect drain pipe to the drain socket on the indoor unit, an auxiliary flexible drain hose should be
used. auxiliary flexible drain hose allows that the drain pipe can be connected to the socket without breaking by excessive strain.
Auxiliary drain hose

Thermal insulation (drain pipe area)

Metal clamp

Metal clamp
Thermal insulation(bend area)
Drain pan

Important points
- The drain pipe should be at least equal in size to that of the indoor unit.
- The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe.
- The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has
been connected some water should be added to the drain pan and the drain pump to check and see if it
is functioning correctly.
- All connections should be secure. (Special care is needed with PVC pipe)
- Insulate auxiliary drain hose with thermal insulation band.

18 _ Ceiling Concealed Duct(Low Static)

10. Installation
WIRED REMOTE CONTROLLER INSTALLATION

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller
LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller
Remote

TEMP

Remote Controller

5feet
(1.5meters)

no

no

Fig.1 Typical locations for remote controller

Ceiling Concealed Duct(Low Static) _ 19

Indoor Units

Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place
away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

11. Accessories

Indoor Units

Standard Accessories
Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for
hanging backet
8 EA

Clamp
(Tie Wrap)
4 EA

Insulation for
fitting

(Other)

1 SET

Owner's manual
Installation manual
Shape

for gas pipe

for liquid pipe

CAUTION
Use only those accessories (Standard or optional) which have designated specifications.

20 _ Ceiling Concealed Duct(Low Static)

Indoor unit
Ceiling Concealed Duct_Built in
1. List of functions
2. Specifications
3. Dimensions
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. External Static Pressure (E.S.P) & Air Flow
8. Electric Characteristics
9. Sound Levels
10. Installation
11. Accessories

1. List of Functions

Indoor Units

Category

Air flow

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Function

Air supply outlet


Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
1
3/3/3
X
X
O
O
O
X
O
O
O
O(Heat recovery)
X
O(Heat pump or Cooling only)
O
O
O
O
O
O
O
Accessory
Accessory
Accessory
Accessory
X
Accessory
Accessory
-

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

1 _ Ceiling Concealed Duct_Built in

2. Specification

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. EEV: Electronic Expansion Valve
5. To be added for more available Models
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Ceiling Concealed Duct_Built in _ 2

Indoor Units

Ceiling Concealed Duct (Built-in)


PBSGB30/PBSC30
PBSGB30/PBSC30
PBSGB30/PBSC30
Unit
ARNU07GB3G2
ARNU09GB3G2
ARNU12GB3G2
kW
2.2
2.8
3.6
Cooling Capacity
kcal/h
1,900
2,400
3,100
Btu/h
7,500
9,600
12,300
kW
2.5
3.2
4.0
Heating Capacity
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
Casing
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
mm
820 x 575 x 190
820 x 575 x 190
820 x 575 x 190
Dimensions(WxDxH) Body
inch
32.3 x 22.6 x 7.5
32.3 x 22.6 x 7.5
32.3 x 22.6 x 7.5
Rows x Columns x FPI
2 x 11 x 21
2 x 11 x 21
2 x 11 x 21
Coil
Face Area
m3
0.16
0.16
0.16
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output x Number
W
30
30
30
Running Current
A
0.15
0.15
0.15
Air Flow Rate(H / M / L)
CMM
8.0 / 6.5 / 5.5
9.0 / 7.0 / 6.0
10.0 / 8.0 / 6.5
(High Mode-factor set)
cfm
283 / 229 / 194
318 / 247 / 212
353 / 283 / 229
Fan
External Static Pressure mmAq(Pa)
2(20)
2(20)
2(20)
Air Flow Rate(H / M / L)
CMM
8.0 / 6.5 / 5.5
9.0 / 7.0 / 6.0
10.0 / 8.0 / 6.5
(Standard Mode)
cfm
283 / 229 / 194
318 / 247 / 212
353 / 283 / 229
External Static Pressure mmAq(Pa)
0(0)
0(0)
0(0)
Drive
Direct
Direct
Direct
Motor type
BLDC
BLDC
BLDC
Temperature Control
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Sound Absorbing Thermal Insulation Material
Foamed polystrene
Foamed polystrene
Foamed polystrene
Air Filter
Safety Device
Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor
Liquid Side
mm(inch)
6.35(1/4)
6.35(1/4)
6.35(1/4)
Pipe Connections Gas Side
mm(inch)
12.7(1/2)
12.7(1/2)
12.7(1/2)
Drain Pipe(Internal Dia.) mm(inch)
25.4(1)
25.4(1)
25.4(1)
Net Weight
kg(lbs)
21(46.3)
21(46.3)
21(46.3)
Noise Level(Sound Press, 1m, H / M / L)
dB(A)
33 / 32 / 29
34 / 33 / 32
35 / 34 / 33
1,
220-240,
50
1,
220-240,
50
1,
220-240, 50
Power Supply
, V, Hz
1, 220, 60
1, 220, 60
1, 220, 60
Refrigerant Control
EEV
EEV
EEV
Power cable
mm2
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
Transmission cable
mm2
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Type
Accessory
Model

Indoor Units

2. Specification
Ceiling Concealed Duct (Built-in)
PBSGB30/PBSC30
PBSGB40/PBSC40
PBSGB40/PBSC40
Unit
ARNU15GB3G2
ARNU18GB4G2
ARNU24GB4G2
kW
4.5
5.6
7.1
Cooling Capacity
kcal/h
3,900
4,800
6,100
Btu/h
15,400
19,100
24,200
kW
5.0
6.3
8.0
Heating Capacity
kcal/h
4,300
5,400
6,900
Btu/h
17,100
21,500
27,300
Casing
Galvanized Steel Plate Galvanized Steel Plate Galvanized Steel Plate
mm
820 x 575 x 190
1,100 x 575 x 190
1,100 x 575 x 190
Dimensions(WxDxH) Body
inch
32.3 x 22.6 x 7.5
32.3 x 22.6 x 7.5
32.3 x 22.6 x 7.5
Rows
x
Columns
x
FPI
2
x
11
x
21
3
x
10
x
18
3 x 10 x 18
Coil
Face Area
m3
0.16
0.23
0.23
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output x Number
W
30
80
80
Running Current
A
0.15
0.38
0.38
Air Flow Rate(H / M / L)
CMM
11.0 / 10.0 / 8.0
14.0 / 12.0 / 10.0
17.0 / 15.0 / 10.0
(High Mode-factor set)
cfm
388 / 353 / 283
494 / 424 / 353
600 / 530 / 353
Fan
External Static Pressure mmAq(Pa)
2(20)
2(20)
2(20)
Air Flow Rate(H / M / L)
CMM
11.0 / 10.0 / 8.0
14.0 / 12.0 / 10.0
17.0 / 15.0 / 10.0
(Standard Mode)
cfm
388 / 353 / 283
494 / 424 / 353
600 / 530 / 353
External Static Pressure mmAq(Pa)
0(0)
0(0)
0(0)
Drive
Direct
Direct
Direct
Motor type
BLDC
BLDC
BLDC
Temperature Control
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Sound Absorbing Thermal Insulation Material
Foamed polystrene
Foamed polystrene
Foamed polystrene
Air Filter
Safety Device
Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor Fuse, Thermal Fuse for Fan Motor
Liquid Side
mm(inch)
6.35(1/4)
6.35(1/4)
9.52(3/8)
Pipe Connections Gas Side
mm(inch)
12.7(1/2)
12.7(1/2)
15.88(5/8)
Drain Pipe(Internal Dia.) mm(inch)
25.4(1)
25.4(1)
25.4(1)
Net Weight
kg(lbs)
21(46.3)
26(57.3)
26(57.3)
Noise Level(Sound Press, 1m, H / M / L)
dB(A)
41 / 40 / 37
43 / 40 / 37
46 / 43 / 37
1,
220-240,
50
1,
220-240,
50
1,
220-240, 50
Power Supply
, V, Hz
1, 220, 60
1, 220, 60
1, 220, 60
Refrigerant Control
EEV
EEV
EEV
Power cable
mm2
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
Transmission cable
mm2
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Type
Accessory
Model

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without notification
4. EEV: Electronic Expansion Valve
5. To be added for more available Models
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

3 _ Ceiling Concealed Duct_Built in

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Ceiling Concealed Duct_Built in _ 4

575

With Suction Grille & Suction Canvas

250

388

PBSC30
PBSC40

PBSGB30
PBSGB40

E
821
1100

B
910
1188

Btu/h
A
7,9,12,15k 820
18,24k
1100
D
56
56
F
G
274 42~250
274 42~250

C
359
359

With Suction Grille

Name

Air suction
Air discharge

(unit : mm)
Unit size(7k,9k,12k,15k,18k):6.35
Unit size(24k):9.52
Unit size(7k,9k,12k,15k,18k):12.7
Unit size(24k):15.88

Descripition

CHASSIS CODE: B3/B4

Drain pipe connection


Power supply connection

Gas pipe connection

Liquid pipe connection

60

190

3
4

Number

65

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

500(Max)

277

With Suction Grille


& Suction Canvas

190

216
24

With Suction Grille

388
190

B3/B4

Indoor Units

618

Ceiling Concealed Duct (Built in)

3. Dimensions

Indoor Units

4. Piping Diagrams

Heat Exchanger

EEV
Filter

:Cooling
:Heating

Th2

Th3
Sirocco Fan

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

12.7(1/2)

6.35(1/4)

ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

12.7(1/2)

6.35(1/4)

ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

12.7(1/2)

6.35(1/4)

ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

12.7(1/2)

6.35(1/4)

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

12.7(1/2)

6.35(1/4)

ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

15.88(5/8)

9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

5 _ Ceiling Concealed Duct_Built in

5. Wiring Diagrams
B3/B4 Chassis
Indoor Units

CONNECTOR NUMBER
CN-MOTOR1
CN-MOTOR2
CN-PIPE/OUT
CN-PIPE/IN
CN-ROOM
CN-REMO
CN-FLOAT
CN-EEV
CN-D/PUMP
CN-OPTION
CN-COM
CN-D/PUMP
CN-POWER
CN-ZONE
CN-DISPLAY
CN-CC

SPEC.

DESCRIPTION

Fan motor output


Fan motor output
Discharge pipe sensor
Suction pipe sensor
Room sensor
Remote controller
Float switch input
EEV output
Drain pump output
Option PWB.
Communication
Drain pump output
AC power supply
Zone Controller
RF Remote controller
Dry contact

Motor output of BLDC


Motor output of BLDC
Pipe out thermistor
Pipe in thermistor
Room thermistor
Remote control line
Float switch sensing
EEV control output
AC output for drain pump
Communication between main and option
Communication between indoor and outdoor
AC output for drain pump
AC power line input for indoor controller
Zone control line
RF remote control line
Dry contact line

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

Ceiling Concealed Duct_Built in _ 6

6. Capacity Tables

Indoor Units

6.1 Cooling Capacity

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.2

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.6
1.6

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
2.3

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.6
1.6
1.6
1.6
1.5
1.5

2.9
2.9
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3

1.7
1.7
1.7
1.6
1.6
1.6
1.6
1.6
1.5
1.5
1.5
1.5
1.5
1.4
1.4
1.4

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.9
2.9
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.7
3.7

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.0
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.6
2.6

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
4.0
3.9
3.8
3.7

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.1
2.1
2.1
2.0
2.0
1.9
1.9
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.7
2.7
2.6
2.6
2.6
2.5
2.5

3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8

2.2
2.1
2.1
2.1
2.1
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.9
1.8
1.8
1.8
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
2.3
2.3

Capacity
Index

Outdoor
air temp.
(DB, C)

2.2

2.8

3.6

Cooling capacity

Notes:
TC: Total Capacity(kW)

7 _ Ceiling Concealed Duct_Built in

SHC: Sensible Heat Capacity(kW)

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

6. Capacity Tables
Cooling capacity

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

Capacity
Index

4.5

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2

3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3

4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4

3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

5.9
5.8
5.8
5.7
5.6
5.5
5.5
5.4
5.3
5.3
5.2
5.1
5.0
5.0
4.9
4.8

3.5
3.5
3.4
3.4
3.3
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9
2.9
2.8

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6

5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1

4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
5.8
5.7
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.4
7.2

4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.0
3.9
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.1
5.0

6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.6
6.4
6.4
6.3
6.2
6.0
5.9
5.8
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.4
8.2
8.1
8.0
7.8
7.7
7.5
7.4

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
3.9
3.9
3.8
3.7
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.2
5.2
5.1
5.0
4.9
4.8
4.7

7.4
7.3
7.2
7.1
7.0
6.9
6.8
6.7
6.6
6.6
6.5
6.4
6.3
6.2
6.1
6.0
9.3
9.2
9.1
9.0
8.8
8.7
8.7
8.5
8.4
8.3
8.2
8.1
7.9
7.8
7.7
7.6

4.2
4.2
4.1
4.1
4.0
4.0
3.9
3.9
3.8
3.8
3.7
3.7
3.6
3.5
3.5
3.4
5.4
5.3
5.2
5.2
5.1
5.0
5.0
4.9
4.8
4.8
4.7
4.6
4.6
4.5
4.4
4.4

5.6

7.1

Notes:
TC: Total Capacity(kW)

32
24
TC SHC
kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling Concealed Duct_Built in _ 8

Indoor Units

20
14
TC SHC
kW kW

Outdoor
air temp.
(DB, C)

6. Capacity Tables

Indoor Units

6.2 Heating Capacity


Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Heating capacity
Indoor air temp. (DB, C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.2

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.8
2.8
2.9
2.9
2.9
2.9
2.9

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
2.7
2.7
2.7
2.7
2.7
2.7

1.7
1.7
1.8
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.5
2.5
2.5
2.5

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

2.8

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.1
2.2
2.3
2.5
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.6
3.6
3.7
3.7
3.7
3.7
3.7

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.1
2.2
2.3
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.1
2.2
2.3
2.4
2.6
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

3.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.7
2.8
2.9
3.1
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.4
4.5
4.6
4.6
4.6
4.6
4.6

2.7
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.3
4.3
4.3
4.3
4.3
4.3
4.3

2.7
2.8
2.9
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0

2.6
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Notes:
TC: Total Capacity(kW)

9 _ Ceiling Concealed Duct_Built in

6. Capacity Tables
Heating capacity

4.5

5.6

7.1

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

3.4
3.5
3.7
3.9
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.6
5.6
5.8
5.8
5.8
5.8
5.8
4.2
4.3
4.6
4.9
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
7.0
7.1
7.2
7.2
7.2
7.2
7.2

3.4
3.5
3.7
3.8
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.4
5.4
5.4
5.4
5.4
5.4
5.4
4.2
4.3
4.6
4.8
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
6.7
6.7
6.7
6.7
6.7
6.7
6.7

3.4
3.5
3.7
3.4
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.6
4.9
5.0
5.0
5.0
5.0
5.0
5.0
4.2
4.3
4.6
4.3
4.5
4.8
4.9
5.0
5.1
5.4
5.5
5.8
6.2
6.3
6.3
6.3
6.3
6.3
6.3

3.3
3.5
3.7
3.8
4.0
4.3
4.3
4.4
4.4
4.6
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.2
4.3
4.6
4.8
5.0
5.4
5.4
5.5
5.6
5.8
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1

3.3
3.4
3.7
3.8
4.0
4.2
4.3
4.4
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.2
4.3
4.6
4.8
5.0
5.3
5.4
5.5
5.6
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9

3.3
3.4
3.6
3.8
4.0
4.2
4.3
4.3
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.2
4.3
4.5
4.8
5.0
5.3
5.4
5.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

5.4
5.5
5.8
6.2
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.9
9.0
9.2
9.2
9.2
9.2
9.2

5.4
5.5
5.8
6.1
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.6
8.6
8.6
8.6
8.6
8.6
8.6

5.4
5.5
5.8
5.5
5.8
6.0
6.2
6.3
6.5
6.8
7.0
7.4
7.8
8.0
8.0
8.0
8.0
8.0
8.0

5.3
5.5
5.8
6.1
6.4
6.8
6.9
7.0
7.1
7.4
7.7
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8

5.3
5.4
5.8
6.1
6.4
6.7
6.9
7.0
7.1
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

5.3
5.4
5.8
6.1
6.4
6.7
6.8
6.8
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Notes:
TC: Total Capacity(kW)

Ceiling Concealed Duct_Built in _ 10

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Indoor Units

7. External Static Pressure (E.S.P) & Air Flow


ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
Setting Value

(Unit: CMM)

Static Pressure(mmAq(Pa))
0(0)

1(10)

2(20)

3(29)

4(39)

60

6.29

3.03

0.93

65

6.61

4.84

1.52

70

7.69

5.64

2.18

0.79

75

8.19

6.28

2.81

0.85

80

8.91

7.43

4.96

1.58

85

9.51

8.14

5.91

2.75

0.95

90

10.21

8.76

6.79

3.41

1.36

95

10.83

9.62

8.11

5.48

2.61

100

11.31

10.55

9.02

6.12

3.31

105

11.84

11.19

9.99

8.28

5.32

110

12.68

11.88

10.38

9.16

6.92

115

13.19

12.22

11.55

10.21

8.23

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
Setting Value

(Unit: CMM)

Static Pressure(mmAq(Pa))
0(0)

1(10)

2(20)

3(29)

4(39)

75

10.32

7.68

3.55

80

11.06

8.77

4.71

1.38

85

11.84

10.02

6.95

2.16

90

12.73

10.74

8.26

4.73

1.25

95

13.47

12.13

9.93

6.74

2.73

100

14.16

13.25

10.51

8.41

3.65

105

15.29

14.11

12.31

9.83

6.21

110

16.09

14.77

13.49

10.39

8.32

115

16.91

15.88

14.48

12.77

9.92

120

17.81

16.88

15.15

13.98

10.85

125

18.55

17.84

16.12

15.13

12.97

130

19.01

18.55

17.33

16.28

14.59

Note :
1. The above table shows the correlation between the air rates and E.S.P.
2. E.S.P. is given after subtracting coil losses motor step factory installed
3. E.S.P. can be higher than the maximum given in the table, but the unit faces the problem of freezing the coil.

11 _ Ceiling Concealed Duct_Built in

7. External Static Pressure (E.S.P) & Air Flow

Capacity

7k

High
(factory set)
Standard

9k

Standard
Set value ESP(mmAq(Pa))

Mode

High
(factory set)
Standard
High
(factory set)

12k
Standard
High
(factory set)
15k
Standard

HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low

94
88
83
74
62
56
99
89
85
82
66
58
105
94
88
90
74
62
110
105
94
96
90
74

2(20)
0(0)
2(20)
0(0)
2(20)
0(0)
2(20)
0(0)

CMM
8
6.5
5.5
8
6.5
5.5
9
7
6
9
7
6
10
8
6.5
10
8
6.5
11
10
8
11
10
8

Lower Limit of External


Static Pressure(mmAq(Pa))

Upper Limit of External


Static Pressure(mmAq(Pa))

4(39)

4(39)

4(39)

4(39)

4(39)

4(39)

4(39)

4(39))

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
Capacity

18k

High
(factory set)
Standard

24k

Standard
Set value ESP(mmAq(Pa))

Mode

High
(factory set)
Standard

HI
Mid
Low
HI
Mid
Low
HI
Mid
Low
HI
Mid
Low

115
103
93
100
86
74
128
118
93
116
104
74

2(20)
0(0)
2(20)
0(0)

CMM
14
12
10
14
12
10
17
15
10
17
15
10

Lower Limit of External


Static Pressure(mmAq(Pa))

Upper Limit of External


Static Pressure(mmAq(Pa))

4(39)

4(39)

4(39)

4(39)

Ceiling Concealed Duct_Built in _ 12

Indoor Units

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

8. Electric Characteristics

Indoor Units

Units

Power Supply

Input(W)

MFA

kW

FLA

0.22

15

0.028

0.17

30

30

0.22

15

0.028

0.17

30

30

Max:264

0.22

15

0.028

0.17

30

30

Min:198

0.22

15

0.028

0.17

30

30

B4

0.55

15

0.076

0.44

80

80

ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

B4

0.55

15

0.076

0.44

80

80

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

0.22

15

0.028

0.17

30

30

ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

0.22

15

0.028

0.17

30

30

ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

Max:242

0.22

15

0.028

0.17

30

30

ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

Min:198

0.22

15

0.028

0.17

30

30

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

B4

0.55

15

0.076

0.44

80

80

ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

B4

0.55

15

0.076

0.44

80

80

Model

Type

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)

B3

ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

Hz

50

60

Volts Voltage Range MCA

IFM

220-240

220

Cooling Heating

Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFA : Indoor Fan Motor
Note :
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above
listed range limits,
2. Maximum allowable voltage unbalance between phases is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.

13 _ Ceiling Concealed Duct_Built in

9. Sound Levels
Overall

1.5m

Ceiling
2.0m

Indoor Units

Notes:
- Sound measured at 1.5m away from the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

Microphone

Sound Levels dB(A)


Model Name

H
33
34
35
41
43
46

ARNU07GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU09GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU12GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU15GB3G2+PBSGB30(Acc'y), PBSC30(Acc'y)
ARNU18GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)
ARNU24GB4G2+PBSGB40(Acc'y), PBSC40(Acc'y)

M
32
33
34
40
40
43

L
29
32
33
37
37
37

Sound Pressure Level


ARNU09GB3G2+
PBSGB30(Acc'y), PBSC30(Acc'y)
80

70

70

70

NC-65
60
NC-60
NC-55
NC-50
NC-45

40

NC-40
NC-35

30

NC-30

NC-50

NC-40

125

250

500

1000

2000

4000

NC-35

30

NC-30
NC-25
Approximate
Hearing
Threshold

NC-15

63

NC-45

40

NC-20

10

NC-55

50

20

NC-25
Approximate
Hearing
Threshold

NC-60

NC-15
63

8000

70

70

NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35

30

NC-30
20

10

NC-25
Approximate
Hearing
Threshold
63

Octave Band Sound Pressure Level (dB re 20Pa )

80

40

250

500

NC-15
1000 2000 4000 8000

Octave Band Center Frequency (Hz)

250

500

1000

2000

4000

8000

NC-45
NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold

NC-20
NC-15

10
63

125

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

ARNU24GB4G2+
PBSGB40(Acc'y), PBSC40(Acc'y)
80

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

NC-65
60
NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

NC-25

NC-25

20

NC-20

125

NC-50

40

ARNU18GB4G2+
PBSGB40(Acc'y), PBSC40(Acc'y)

80

50

125

NC-55

50

Octave Band Center Frequency (Hz)

ARNU15GB3G2+
PBSGB30(Acc'y), PBSC30(Acc'y)

60

NC-60

NC-20

10

Octave Band Center Frequency (Hz)

NC-65
60

Octave Band Sound Pressure Level (dB re 20Pa )

50

NC-65
60

Octave Band Sound Pressure Level (dB re 20Pa )

80

20

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU12GB3G2+
PBSGB30(Acc'y), PBSC30(Acc'y)

80

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU07GB3G2+
PBSGB30(Acc'y), PBSC30(Acc'y)

10

Approximate
Hearing
Threshold
63

Approximate
Hearing
Threshold

NC-20

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

NC-15
8000

NC-20
NC-15

10
63

125

250

500

1000 2000

4000

8000

Octave Band Center Frequency (Hz)

Ceiling Concealed Duct_Built in _ 14

10. Installation

Indoor Units

Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Suction Grille
TEMP

Remote Controller

Suction Grille +
Suction Canvas

TEMP

Remote Controller

Required Parts

Required Tools

Connecting cable
Pipes: Gas side
Liquid side
Hanging Bolt
(W 3/8 or M10 length 650mm)
Insulated drain hose
Additional Drain hose
(Inner Dia ....................................25mm)

Level
Screw driver
Electric drill
Hole core drill (70mm)
Flaring Tools set
Torque Wrenches
Hexagonal Wrench (4mm, 5mm)
Gas-leak detector
Owners Manual
Thermometer

15 _ Ceiling Concealed Duct_Built in

10. Installation
10.1 Selection of the best location

Top view
(unit:mm)
Airflow

The place shall easily bear a load exceeding four times


the indoor units weight.

Indoor Units

Install the air conditioner in the location that satisfies the


following conditions.

Inspection hole
(600 x 600)

The place shall be able to inspect the unit as the figure.

Control box

The place where the unit shall be leveled.


The place shall easily connect with the outdoor unit.
600

The place where the unit is not affected by an electrical


noise.

600

There should not be any heat source or steam near the


unit
Confirm the positional relationship between the unit and
suspension bolts.

270 or more

The place where air circulation in the room will be good .

(Unit : mm)
Chassis

B3

600

900

B4

600

1100

520 or more

Installation the ceiling opening to clean the filter or service under the product.

Refer to Suction grille and Suction canvas installation


manual for detail installation of Built-in duct type

A(Min)

B3/B4 Series : Built-in Duct type

B(Min)

Ceiling
Service Space

Ceiling Concealed Duct_Built in _ 16

10. Installation
10.2 Ceiling dimension and hanging bolt location
B
A
J

Install the unit above the ceiling correctly.

CASE 1

C
D

POSITION OF SUSPENSION BOLT

Apply a joint-canvas between the unit and duct to absorb


unnecessary vibration.
Apply a filter Accessory at air return hole.

(Unit:mm)
Dimension

I
F

Indoor Units

Installation of Unit

850 900 383 575


1130 1180 383 575

93
93

190
190

Chassis

B3
B4

H
21 795 163 820
21 1065 163 1100

Drainage hole

Drain Pump use

M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

CASE 2
Install the unit leaning to a drainage hole side as a figure
for easy water drainage.

POSITION OF CONSOLE BOLT


A place where the unit will be leveled and that can support
the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.

17 _ Ceiling Concealed Duct_Built in

10. Installation
Select and mark the position for fixing bolts.
Drill the hole for set anchor on the face of ceiling.

Old building

New building

1 Set anchor
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts

CAUTION
Tighten the nut and bolt to prevent unit falling.

10.3 Connecting Cables


Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively
Terminal Block Indoor
1(L)

2(N)

SODU

INTERNET DRY1 DRY2 GND 12V

IDU
-

Outdoor
Unit

INDOOR POWER INPUT

WARNING
Make sure that the screws of the terminal are not from loose.

Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the
0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control
panel.

Ceiling Concealed Duct_Built in _ 18

Indoor Units

Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the
ceiling.
Mount the suspension bolts to the set anchor firmly.
Secure the installation plates onto the suspension
bolts (adjust level roughly) using nuts, washers and
spring washers.

10. Installation
10.4 Part name and functions
Air outlet

Indoor Units

Air outlet

Suction Grille
Suction Grille
Suction Canvas

Buit-in duct type with Suction Grille

Buit-in duct type with Suction Grille and Suction


Canvas

B3/B4 Series : Built-in Duct type Control Box service

19 _ Ceiling Concealed Duct_Built in

10. Installation
INSULATION, OTHERS

All thermal insulation must comply with local requirement.

INDOORUNIT
Union for gas pipe

Refrigerant pipe and thermal


insulator(Local supply)

Thermal insulator for refrigerant pipe


(Local supply) Thermal insulator for
piping(Local supply)

Hose clip for thermal insulator


(Local supply)
Overlap with thermal
insulator for piping.
Hose clip for thermal insulator(Local supply)
Make sure that there is no clearance here.

Thermal insulator for refrigerant pipe


(Local supply)
Union for liquid pipe

Felt

Cabinet

Rubber

Insulation
No clearance

TEST AND CHECK

After all workings are finished, check the working and operation.
Air distribution ............... Is the air circulation good?
Drain ............................. Is the drainage smoothly and no sweating?
Gas leakage ................. Is the piping connection correctly?
Wiring ........................... Is the wiring connection correctly?
Lock-bolt ....................... Is the lock-bolt of compressor loosened?
Insulation
Is the unit fully insulated?
Ground
Is the unit safely grounded?

10.5 Checking the Drainage


1. Remove the Air Filter.

2. Check the drainage.


Spray one or two glasses of water upon the
evaporator.
Ensure that water flows drain hose of indoor unit
without any leakage.

Ceiling Concealed Duct_Built in _ 20

Indoor Units

THERMAL INSULATION

Insulate the joint and tubes completely.

10. Installation

Indoor Units

CAUTION
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 19mm.

Front of view
The unit must be horizontal or declined to the drain hose connected when finished
installation.

Ceiling
Drainage hole

Drain Pump use

10.6 Drain Piping


Drain piping must have down-slope (1/50 to 1/100): be sure not to
provide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra force
on the drain port on the indoor unit.
The outside diameter of the drain connection on the indoor unit is
32mm.

Pipe clamp
Indoor unit

Piping material: Polyvinyl chloride pipe VP-25 and


pipe fittings

Upward
routing
not allowed

Maintenance
drain port

Be sure to install heat insulation on the drain piping.


Heat insulation material: Polyethylene foam with thickness more than 8 mm.

1/50~1/100
MAX 700mm

Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:

Feed water

Flexible drain hose


Main
drain pipe

Drain Pump

Drain
port

Glue the joint

Drain hose connection


Use the clip

Drain pan

21 _ Ceiling Concealed Duct_Built in

Connect the main drain pipe to the exterior and


leave it provisionally until the test comes to an
end.
Feed water to the flexible drain hose and check
the piping for leakage.
Be sure to check the drain pump for normal operating and noise when electrical wiring is complete.
When the test is complete, connect the flexible
drain hose to the drain port on the indoor unit.

10. Installation
Hanger
distance
1~15m

Metal
clamp
Flexible drain hose

Hanger Bracket
1/50~1/100 slope
Max 700mm

Max 300mm

Insulation

CAUTION:
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose
from vibrations to which the unit is subjected during the course of transportation. Check them
and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out
Flexible drain hose
of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the normal function of an overload protection device.
Proper starting power is not given to the compressor.

HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual.
(air filter cleaning, temperature control, etc.)

Ceiling Concealed Duct_Built in _ 22

Indoor Units

CAUTION : The supplied flexible drain


hose should not be curved, neither
screwed. The curved or screwed hose
may cause a leakage of water.

10. Installation

Indoor Units

WIRED REMOTE CONTROLLER INSTALLATION


Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place
away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller
LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Remote Controller

5feet
(1.5meters)

TEMP

Controller
Remote

no

no

Fig.1 Typical locations for remote controller

23 _ Ceiling Concealed Duct_Built in

11. Accessories
Standard Accessories
Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for
hanging backet
8 EA

Clamp
(Tie Wrap)

Insulation for
fitting

4 EA

1 SET

(Other)

Owner's manual
Installation manual
Shape

for gas pipe

for liquid pipe

CAUTION
Use only those accessories (Standard or optional) which have designated specilications.

Ceiling Concealed Duct_Built in _ 24

Indoor Units

Name

Indoor unit
Wall Mounted
1. List of functions
2. Specifications
3. Dimensions
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. Air Velocity and Temperature Distribution
8. Electric Characteristics
9. Sound Levels
10. Installation
11. Accessories

1. List of functions
Category

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Air supply outlet


Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU07GSE*2, ARNU09GSE*2, ARNU12GSE*2


ARNU15GSE*2, ARNU18GS5*2, ARNU24GS5*2
1
SE Manual / S5 Auto
Auto
SE Manual / S5 Auto
X
3/4/3
O
O
O
X
Option
O
O
O
O
O(Heat recovery)
O
O(Heat pump or Cooling only)
O
O
O
O
O
O
O
O
Accessory
Accessory
Accessory
Accessory
Accessory
Accessory
-

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

Wall Mounted _ 1

Indoor Units

Air flow

Function

2. Specifications

Indoor Units

* Model Name
A:Basic L:Plasma
Type
Model
Cooling Capacity

Heating Capacity
Dimensions(WxDxH) Body
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h
mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
kg(lbs)
Noise Level(Sound Press, 1m, H / M / L) dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Color

, V, Hz
mm2
mm2

Wall Mounted
ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2
2.2
2.8
3.6
1,900
2,400
3,100
7,500
9,600
12,300
2.5
3.2
4.0
2,200
2,800
3,400
8,500
10,900
13,600
895 x 165 x 282
895 x 165 x 282
895 x 165 x 282
35.2 x 6.5 x 11.1
35.2 x 6.5 x 11.1
35.2 x 6.5 x 11.1
2 x 15 x 18
2 x 15 x 18
2 x 15 x 18
0.21
0.21
0.21
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
20
20
20
0.2
0.2
0.2
5.6 / 5.0 / 4.6
7.0 / 6.5 / 6.0
9.5 / 9.0 / 8.5
198.0 / 177.0 / 162.5
247.0 / 230.0 / 212.0
336.0 / 318.0 / 300.0
Direct
Direct
Direct
BLDC
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Foamed polystrene
Resin Net(washable)
Resin Net(washable)
Resin Net(washable)
Fuse
Fuse
Fuse
6.35(1/4)
6.35(1/4)
6.35(1/4)
12.7(1/2)
12.7(1/2)
12.7(1/2)
16(5/8)
16(5/8)
16(5/8)
9(19.8)
9(19.8)
9(19.8)
37 / 33 / 23
39 / 35 / 25
41 / 36 / 27
1, 220-240, 50
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
1, 220, 60
EEV
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Morning fog
Morning fog
Morning fog

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Wall Mounted

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specifications
* Model Name
A:Basic L:Plasma

Cooling Capacity

Heating Capacity
Dimensions(WxDxH) Body
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h
mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
kg(lbs)
Noise Level(Sound Press, 1m, H / M / L) dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Color

, V, Hz
mm2
mm2

Wall Mounted
ARNU15GSE*2
ARNU18GS5*2
ARNU24GS5*2
4.5
5.6
7.1
3,900
4,800
6,100
15,400
19,100
24,200
5.0
6.3
8.0
4,300
5,400
6,900
17,100
21,500
27,300
895 x 165 x 282
1,090 x 178 x 300
1,090 x 178 x 300
35.2 x 6.5 x 11.1
42.9 x 7 x 11.8
42.9 x 7 x 11.8
2 x 15 x 18
2 x 15 x 20
2 x 15 x 20
0.21
0.26
0.26
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
20
20
20
0.2
0.2
0.2
10.5 / 9.0 / 8.5
12.0 / 10.5 / 9.0
14.0 / 13.0 / 10.0
371.0 / 318.0 / 300.0
424.0 / 371.0 / 318.0
494.0 / 459.0 / 353.0
Direct
Direct
Direct
BLDC
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Foamed polystrene
Resin Net(washable)
Resin Net(washable)
Resin Net(washable)
Fuse
Fuse
Fuse
6.35(1/4)
6.35(1/4)
9.52(3/8)
12.7(1/2)
12.7(1/2)
15.88(5/8)
16(5/8)
16(5/8)
16(5/8)
9(19.8)
12(26.5)
12(26.5)
42 / 36 / 27
44 / 40 / 36
46 / 41 / 38
1, 220-240, 50
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
1, 220, 60
EEV
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Morning fog
Morning fog
Morning fog

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Wall Mounted _ 3

Indoor Units

Type
Model

4 _ Wall Mounted
567

895

Wall Mounted

Air discharge grill


Air suction grill

1
2

282

Descripition

(unit : mm)

165

(unit : mm)

CHASSIS CODE: SE

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Name

895

ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2
ARNU15GSE*2

Number

Model

ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2
ARNU15GSE*2

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

282
265

165

Indoor Units

3. Dimensions

Wall Mounted _ 5

804

1,090

300

Air discharge grill


Air suction grill

1
2

300

Descripition

(unit : mm)

178

(unit : mm)

CHASSIS CODE: S5

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Name

1090

ARNU18GS5*2
ARNU24GS5*2

Number

Model

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

178

ARNU18GS5*2
ARNU24GS5*2

Indoor Units

281

Wall Mounted

3. Dimensions

4. Piping Diagrams

Indoor Units

Heat Exchanger

EEV
Filter

Th3

:Cooling
:Heating

Th2

C.F.F

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GSE*2

12.7(1/2)

6.35(1/4)

ARNU09GSE*2

12.7(1/2)

6.35(1/4)

ARNU12GSE*2

12.7(1/2)

6.35(1/4)

ARNU15GSE*2

12.7(1/2)

6.35(1/4)

ARNU18GS5*2

12.7(1/2)

6.35(1/4)

ARNU24GS5*2

15.88(5/8)

9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

6 _ Wall Mounted

5. Wiring Diagrams
SE Chassis
Indoor Units

S5 Chassis

CONNECTOR NUMBER
CN-POWER
CN-MOTOR1
CN-COM
CN-DISP1
CN-DISP2
CN-EEV
CN-U/D, CN-L/R
CN-TH1
CN-REMO
CN-CC
CN-HVB

LOCATION POINT
AC Power supply
Fan motor output
Communication
Display
Display
EEV output
Step motor
Room/pipe sensor
Remote controller
Dry contact
Air clean

FUNCTION
AC Power line input for indoor controller
Motor output of BLDC
Connection between indoor and outdoor
Display of indoor status
Display of indoor status
EEV control output
Step motor output
Room and pipe thermistor
Remote control line
Dry contact line
Air clean control

Wall Mounted _ 7

6. Capacity Tables

Indoor Units

6.1 Cooling Capacity

Cooling Capacity

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

Capacity
Index

Outdoor
air temp.
(DB, C)

2.2

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.2

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.5

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
2.3

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.6
1.6
1.6
1.5
1.5
1.5
1.5

2.9
2.9
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3

1.7
1.6
1.6
1.6
1.6
1.6
1.5
1.5
1.5
1.5
1.5
1.4
1.4
1.4
1.4
1.4

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.9
2.9
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.7
3.7

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.6
2.6

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
4.0
3.9
3.8
3.7

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.0
2.0
2.0
1.9
1.9
1.9
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.7
2.7
2.6
2.6
2.5
2.5
2.4

3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8

2.1
2.1
2.1
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.9
1.8
1.8
1.8
1.8
1.7
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.4
2.3
2.3
2.2

2.8

3.6

Notes:
TC: Total Capacity(kW)

8 _ Wall Mounted

SHC: Sensible Heat Capacity(kW)

32
24
TC SHC
kW kW

6. Capacity Tables
Cooling Capacity

23
16
TC SHC
kW kW

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2

3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2

4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3

5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4

3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

5.9
5.8
5.8
5.7
5.6
5.5
5.5
5.4
5.3
5.3
5.2
5.1
5.0
5.0
4.9
4.8

3.5
3.4
3.4
3.3
3.3
3.2
3.2
3.2
3.1
3.1
3.0
3.0
2.9
2.9
2.9
2.8

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7

3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6

5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1

4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
5.8
5.7
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.4
7.2

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.1
4.0
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.1
5.0

6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.6
6.4
6.4
6.3
6.2
6.0
5.9
5.8
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.4
8.2
8.1
8.0
7.8
7.7
7.5
7.4

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
3.9
3.8
3.8
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.4
5.3
5.2
5.1
5.1
5.0
4.9
4.8

7.4
7.3
7.2
7.1
7.0
6.9
6.8
6.7
6.6
6.6
6.5
6.4
6.3
6.2
6.1
6.0
9.3
9.2
9.1
9.0
8.8
8.7
8.7
8.5
8.4
8.3
8.2
8.1
7.9
7.8
7.7
7.6

4.3
4.2
4.2
4.1
4.1
4.0
4.0
3.9
3.9
3.8
3.8
3.7
3.7
3.6
3.6
3.5
5.4
5.4
5.3
5.2
5.2
5.1
5.1
5.0
4.9
4.9
4.8
4.7
4.6
4.6
4.5
4.4

Capacity
Index

Outdoor
air temp.
(DB, C)

4.5

5.6

7.1

Notes:
TC: Total Capacity(kW)

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

SHC: Sensible Heat Capacity(kW)

Wall Mounted _ 9

Indoor Units

20
14
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

6. Capacity Tables

Indoor Units

6.2 Heating Capacity


Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Heating Capacity
Indoor air temp. (DB, C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.2

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.8
2.8
2.9
2.9
2.9
2.9
2.9

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
2.7
2.7
2.7
2.7
2.7
2.7

1.7
1.7
1.8
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.5
2.5
2.5
2.5

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

2.8

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.1
2.2
2.3
2.5
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.6
3.6
3.7
3.7
3.7
3.7
3.7

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.1
2.2
2.3
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.1
2.2
2.3
2.4
2.6
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

3.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.7
2.8
2.9
3.1
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.4
4.5
4.6
4.6
4.6
4.6
4.6

2.7
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.3
4.3
4.3
4.3
4.3
4.3
4.3

2.7
2.8
2.9
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0

2.6
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Notes: TC: Total Capacity(kW)

10 _ Wall Mounted

6. Capacity Tables
Heating Capacity
Indoor air temp. (DB, C)
16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

4.5

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

3.4
3.5
3.7
3.9
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.6
5.6
5.8
5.8
5.8
5.8
5.8

3.4
3.5
3.7
3.8
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.4
5.4
5.4
5.4
5.4
5.4
5.4

3.4
3.5
3.7
3.4
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.6
4.9
5.0
5.0
5.0
5.0
5.0
5.0

3.3
3.5
3.7
3.8
4.0
4.3
4.3
4.4
4.4
4.6
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.3
3.4
3.7
3.8
4.0
4.2
4.3
4.4
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7

3.3
3.4
3.6
3.8
4.0
4.2
4.3
4.3
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4

5.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

4.2
4.3
4.6
4.9
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
7.0
7.1
7.2
7.2
7.2
7.2
7.2

4.2
4.3
4.6
4.8
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
6.7
6.7
6.7
6.7
6.7
6.7
6.7

4.2
4.3
4.6
4.3
4.5
4.8
4.9
5.0
5.1
5.4
5.5
5.8
6.2
6.3
6.3
6.3
6.3
6.3
6.3

4.2
4.3
4.6
4.8
5.0
5.4
5.4
5.5
5.6
5.8
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1

4.2
4.3
4.6
4.8
5.0
5.3
5.4
5.5
5.6
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9

4.2
4.3
4.5
4.8
5.0
5.3
5.4
5.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

7.1

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

5.4
5.5
5.8
6.2
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.9
9.0
9.2
9.2
9.2
9.2
9.2

5.4
5.5
5.8
6.1
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.6
8.6
8.6
8.6
8.6
8.6
8.6

5.4
5.5
5.8
5.5
5.8
6.0
6.2
6.3
6.5
6.8
7.0
7.4
7.8
8.0
8.0
8.0
8.0
8.0
8.0

5.3
5.5
5.8
6.1
6.4
6.8
6.9
7.0
7.1
7.4
7.7
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8

5.3
5.4
5.8
6.1
6.4
6.7
6.9
7.0
7.1
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

5.3
5.4
5.8
6.1
6.4
6.7
6.8
6.8
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Notes: TC: Total Capacity(kW)

Wall Mounted _ 11

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU07GSE*2
Cooling

Heating
Discharge angle:50

Indoor Units

Discharge angle:45
Air velocity [m/s]

Air velocity [m/s]


2.7m

2.7m

2m

2m
2.0
1.5

0.5

1.5

1.0

1m

1m

1.0
0.5

5m

4m

3m

2m

0m
0m

1m

Temperature [C]

5m

4m

3m

2m

0m
0m

1m

Temperature [C]
2.7m

2.7m

2m

2m
21

24

18
20

33
30

1m

1m

27
22

24

5m

4m

3m

2m

0m
0m

1m

5m

4m

3m

2m

0m
0m

1m

ARNU09GSE*2
Cooling

Heating
Discharge angle:50

Discharge angle:45

Air velocity [m/s]

Air velocity [m/s]


2.7m

2.7m

2m

2m
2.0
1.5

1.5

1m

1m

1.0
0.5

1.0
0.5

5m

4m

3m

2m

0m
0m

1m

Temperature [C]

5m

4m

3m

2m

0m
0m

1m

Temperature [C]
2.7m

2.7m

2m

2m
33

18
21
20

24

30

1m

1m

27
22

24

5m

4m

3m

12 _ Wall Mounted

2m

1m

0m
0m

5m

4m

3m

2m

1m

0m
0m

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU12GSE*2
Cooling

Heating
Discharge angle:50

Discharge angle:45

2.7m

2.7m

2m

2m

2.0

2.0

1m

1m
1.5
0.5

5m

4m

3m

2m

1.0

1.0

0.5

0m
0m

1m

5m

4m

1.5

3m

2m

0m
0m

1m

Temperature [C]

Temperature [C]

2.7m

2.7m

2m

2m
33

18

21
30

1m

20

1m

27
24

5m

4m

24

22

3m

2m

0m
0m

1m

5m

4m

3m

2m

0m
0m

1m

ARNU18GS5*2
Cooling

Heating
Discharge angle:50

Discharge angle:45

Air velocity [m/s]

Air velocity [m/s]

2.5
0.5

8m

7m

6m

5m

4m

3m

2.7m

2.7m

2m

2m

1m

1.5

1.0

2m

1.0

0.5

0m
0m

1m

1m

2.0

8m

7m

6m

5m

4m

3m

2m

1.5

0m
0m

1m

Temperature [C]

Temperature [C]

2.7m

2.7m

2m

2m
33

18
20

7m

6m

5m

4m

30

21

3m

2m

1m

0m
0m

8m

7m

6m

5m

4m

3m

1m

27

24

22

24

8m

1m

2m

1m

0m
0m

Wall Mounted _ 13

Indoor Units

Air velocity [m/s]

Air velocity [m/s]

8. Electric Characteristics

Indoor Units

Units

Power Supply

Input(W)

MFA

kW

FLA

0.29

15

0.02

0.23

40

40

0.29

15

0.02

0.23

40

40

Max:264

0.29

15

0.02

0.23

40

40

Min:198

0.29

15

0.02

0.23

40

40

S5

0.29

15

0.02

0.23

40

40

ARNU24GS5*2

S5

0.29

15

0.02

0.23

40

40

ARNU07GSE*2

SE

0.29

15

0.02

0.23

40

40

ARNU09GSE*2

SE

0.29

15

0.02

0.23

40

40

ARNU12GSE*2

SE

Max:242

0.29

15

0.02

0.23

40

40

ARNU15GSE*2

SE

Min:198

0.29

15

0.02

0.23

40

40

ARNU18GS5*2

S5

0.29

15

0.02

0.23

40

40

ARNU24GS5*2

S5

0.29

15

0.02

0.23

40

40

Model

Type

ARNU07GSE*2

SE

ARNU09GSE*2

SE

ARNU12GSE*2

SE

ARNU15GSE*2

SE

ARNU18GS5*2

Hz

50

60

Volts

220 - 240

220

Voltage Range MCA

IFM

Cooling Heating

Symbols:
MCA :Min, Circuit Amps(A)
MFA:Max. Fuse Amps(see note 5)
kW:Fan Motor Rated Output(kW)
FLA:Full Load Amps(A)
IFM:Indoor Fan Motor
Note :
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above
the listed range limits.
2. Maximum allowable voltage unbalance between phases is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.

14 _ Wall Mounted

9. Sound Levels
Overall

1m
1m
Microphone
Sound Levels dB(A)

Model

H
37
39
41
42
44
46

ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2
ARNU15GSE*2
ARNU18GS5*2
ARNU24GS5*2

M
33
35
36
36
40
41

L
23
25
27
27
36
38

Sound Pressure Level

70

70

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

10

Approximate
Hearing
Threshold
63

NC-60

250

500

1000

2000

4000

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20

125

NC-65

60

NC-15
8000

10

Approximate
Hearing
Threshold
63

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20Pa )

80

20

125
250
500 1000 2000 4000
Octave Band Center Frequency (Hz)

NC-15
8000

NC-60

NC-50

NC-40

NC-30
20

10

ARNU18GS5*2

NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25

10

Approximate
Hearing
Threshold
63

NC-65
60
NC-60
50

NC-50

125
250
500 1000 2000 4000
Octave Band Center Frequency (Hz)

NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold

NC-20
NC-15
8000

NC-55

10
63

125
250
500 1000 2000 4000
Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20Pa )

NC-60

Octave Band Sound Pressure Level (dB re 20Pa )

70

NC-65

NC-20

125
250
500 1000 2000 4000
Octave Band Center Frequency (Hz)

NC-15
8000

ARNU24GS5*2

70

20

NC-25
Approximate
Hearing
Threshold
63

70

30

NC-35

30

80

40

NC-45

40

80

50

NC-55

50

80

60

NC-65

60

NC-20

ARNU15GSE*2

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU12GSE*2

ARNU09GSE*2
80

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU07GSE*2
80

NC-65
60
NC-60

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20
Approximate
Hearing
Threshold

NC-20
NC-15
8000

NC-55

50

NC-20
NC-15

10
63

125
250
500 1000 2000 4000
Octave Band Center Frequency (Hz)

8000

Wall Mounted _ 15

Indoor Units

Notes:
- Data is valid at nominal operating condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

10. Installation

Indoor Units

Please read the instruction sheetss completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Installation Parts Provided

1. Type "A" screw

2. Installation Plate

Required Parts

Required Tools

Installation plate
Four type "A" screws
Connecting cable

Level gauge
Screw driver
Electric drill
Hole core drill

Pipes: Gas side


Liquid side
Insulation materials
Additional drain pipe

Flaring tool set


Specified torque wrenches
Spanner......................................................Half union
A glass of water
Screw driver
Thermometer

16 _ Wall Mounted

10. Installation
10.1 Selection of the best location

Front

There

should not be any heat source or


steam near the unit.

Rear left
Down right
Right

Rear right

More than
100mm

More than 200mm

More than
100mm
More than 2300mm

The mounting wall should be strong and solid enough to


protect it from vibration.

S5 chassis

1.Mount the installation plate on the wall with


four Type "A" screws.
(If mounting the unit on the concrete wall, consider using
anchor bolts.)
Always mount the Installation plate horizontally by
aligning the marking-off line by means of thread and a
level.

Installation Plate
Chassis
Hook

Type A

SE chassis
Installation Plate

Chassis
Hook

Type A

Wall Mounted _ 17

Indoor Units

There should not be any obstacles to prevent air circulation.


A place where air circulation in the room will be
good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall,
ceiling, fence, or other obstacles.

Left

10. Installation

Indoor Units

Preparing work for installation


Preparing the indoor unit's piping and drain hose for
installation through the wall.
Remove the plastic tubing retainer(see illustration
below) and pull the tubing and drain hose away from
chassis.
Replace the plastic tubing holder in the original position.

3. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating
at the upper side can cause drain pan to overflow inside the unit.

Loop
Tubing holder
To remove the holder,
press the bottom of
chassis near the holder
upward and pull the tab
out of its hole.

Connecting
cable
Drain hose

Gas side
piping
Liquid side
piping

2 Pull
1 Press

CAUTION
While installing, make sure that the
remaining parts must be removed
clearly so as not to damage the piping
and drain hose, especially power cord
and connecting cable.

For left rear piping


1. Route the indoor tubing and the drain hose in
the direction of rear left.

NOTE: If the drain hose is routed inside the room, insulate


the hose with an insulation material* so that dripping from
"sweating"(condensation) will not damage furniture or
floors.
*Foamed polyethylene or equivalent is recommended.
4. Indoor unit installation
Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the
installation plate.) Ensure that the hooks are properly
seated on the installation plate by moving it left and
right.

Connecting
cable

Drain hose

Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).
Drain hose

2. Insert the connecting cable into the indoor


unit from the outdoor unit through the piping
hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy connection
later.

5. Connecting the pipings to the indoor unit and


drain hose to drain pipe.
Align the center of the pipings and sufficiently tighten
the flare nut by hand.

Indoor unit tubing

18 _ Wall Mounted

Flare nut

Pipings

10. Installation
Tighten the flare nut with a wrench.
Spanner (fixed)

Torque
wrench

Indoor
unit pipe
Wrap with vinyl tape

Connection
pipe
Vinyl tape
(wide)

Connecting cable

Indoor
unit tubing

Pipe

When extending the drain hose at the indoor unit,


install the drain pipe.

Drain pipe

Vinyl tape(narrow)

Bundle the piping and drain hose together by


wrapping them with vinyl tape over the range within which they fit into the rear piping housing section.
Wrap with vinyl tape

Indoor unit
drain hose
Vinyl tape(narrow)

Pipe

Adhesive

Vinyl tape(wide)
Drain hose

6. Wrap the insulation material around the connecting portion.


Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.

Plastic bands

For right rear piping


1. Route the indoor tubing and the drain hose to
the required piping hole position.

Insulation material

2. Insert the piping, drain hose and the connecting cable into the piping hole.
Connecting
cable

Drain pipe

Wall Mounted _ 19

Indoor Units

Flare nut
Connection
pipe

Wrap the area which accommodates the rear piping housing section with vinyl tape.

Indoor Units

10. Installation
3. Insert the connecting cable into the indoor unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.

When extending the drain hose at the indoor unit,


install the drain pipe.

Drain hose

4. Tape the drain hose and the connecting cable.


Connecting cable

Indoor unit drain hose


Vinyl tape(narrow)
Adhesive

7. Wrap the insulation material around the connecting portion.


Overlap the connecting pipe heat insulation and the
indoor unit pipe heat insulation material. Bind them
together with vinyl tape so that there is no gap.
5. Indoor unit installation
Hang the indoor unit from the hooks at the top of
the installation plate.
Insert the spacer etc. between the indoor unit and
the installation plate and separate the bottom of the
indoor unit from the wall.
Indoor unit
Spacer

6. Connecting the pipings to the indoor unit and


the drain hose to drain pipe.
Align the center of the pipings and sufficiently tighten the flare nut by hand.

Flare nut

Pipings

Tighten the flare nut with a wrench.

Spanner (fixed)

Indoor
unit tubing

20 _ Wall Mounted

Wrap the area which accommodates the rear piping


housing section with vinyl tape.

Vinyl tape
(wide)

80mm
(2-3/16 inch)

Torque
wrench

Insulation material

Connection
pipe

Installation plate

Indoor unit tubing

Plastic bands

Flare nut
Connection
pipe

Indoor
unit piping
Wrap with vinyl tape
Pipe

Connecting
cable

Vinyl tape
(narrow)

10. Installation
Bundle the piping and drain hose together by wrapping them with cloth tape over the range within
which they fit into the rear piping housing section.
Pipe
Drain hose

Vinyl tape
(narrow)

Connecting

Wrap with
vinyl tape(wide)

8. Reroute the pipings and the drain hose across


the back of the chassis.

Drain hose

Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).

Piping for
passage through
piping hole

9. Set the pipings and the drain hose to the back


of the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis
and push the bottom of tubing holder to be
engaged at the bottom of chassis.

Tubing holder
1 Hook

2 Push

Wall Mounted _ 21

Indoor Units

10. Indoor unit installation


Remove the spacer.
Ensure that the hooks are properly seated on the
installation plate by moving it left and right.

10. Installation

Indoor Units

10.2 Connection of Pipings


1. To remove the front panel from the indoor unit,
remove the front panel from the indoor unit
cabinet.
Set the air direction louvers up-and-down to the
position(horizontally) by hand.
Remove the securing screws that retain the front
panel. Pull the lower left and right sides of the grille
toward you and lift it off.
(2.1/7, 2.6/9, 3.5/12 kW/Btu models: 2EA,
3.5/18 kW/Btu models: 3EA)

2. To check the drainage.


Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the
drain exit.

Pull the right and


the left side.

Screw

10.3 Connect the cable to the


indoor unit
1. Connect the wires to the terminals on the
control board individually according to the
outdoor unit connection.
Ensure that the color of the wires of outdoor
unit and the terminal No. are the same as those
of indoor unit respectively.

Remote control
co
cord

Connecting cable

22 _ Wall Mounted

10. Installation
Terminal Block Indoor
1(L)

2(N)

SODU

INTERNET DRY1 DRY2 GND 12V

IDU
-

Outdoor
Unit

Indoor Units

INDOOR POWER INPUT

2. Attach the Grille onto the cabinet.


Grasp lower the left and right side of the Grille
and engage four tabs on the top inside edge of
the chassis.
Press the Grille toward the chassis until it is
back in place.

CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) As for the method of wiring, follow the circuit diagram posted on the inside of
control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to
come loose from vibrations to which the unit is subjected during the course of
transportation. Check them and make sure that they are all tightly fastened. (If
they are loose, it could cause burn-out of the wires.)
3) Confirm the specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the
rated voltage marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between the cable length and thickness.)
7) In a wet or moist area, always install an earth leakage circuit breaker.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking,
disturbance of the normal function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the
fixed wiring and have an air gap contact separation of at least 3mm in each
active(phase) conductor.

Wall Mounted _ 23

10. Installation

Indoor Units

WIRED REMOTE CONTROLLER INSTALLATION


Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away
from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller
LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller
Remote

TEMP

Remote Controller

5feet
(1.5meters)

no

no

Fig.1 Typical locations for remote controller

24 _ Wall Mounted

11. Accessories
Standard Accessories
Installation panel

Type "A" screw

Quantity

1 set

SE: 6 EA
S5: 8 EA

(Other)
Owner's manual
Installation manual

SE

Shape
S5

CAUTION
Use only those accessories (Standard or optional) which have designated specifications.

Wall Mounted _ 25

Indoor Units

Name

Indoor unit
ART COOL Mirror
1. List of functions
2. Specifications
3. Dimensions
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. Air Velocity and Temperature Distribution
8. Electric Characteristics
9. Sound Levels
10. Installation
11. Accessories

1. List of functions
Category

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Air supply outlet


Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU07GSE*2, ARNU09GSE*2, ARNU12GSE*2


ARNU15GSE*2, ARNU18GS8*2, ARNU24GS8*2
1
Auto
Auto
Auto
X
3/4/3
O
O
O
X
Option
O
O
O
O
O(Heat recovery)
O
O(Heat pump or Cooling only)
O
O
O
O
O
O
O
O
Accessory
Accessory
Accessory
Accessory
Accessory
-

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

ART COOL Mirror _ 1

Indoor Units

Air flow

Function

2. Specifications

Indoor Units

Type
Model

ART COOL Mirror


ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2
2.2
2.8
3.6
Cooling Capacity
1,900
2,400
3,100
7,500
9,600
12,300
2.5
3.2
4.0
Heating Capacity
2,200
2,800
3,400
8,500
10,900
13,600
915
x
169
x
282
915
x
169
x
282
915
x
169 x 282
Dimensions(WxDxH) Body
36.0 x 6.5 x 11.1
36.0 x 6.5 x 11.1
36.0 x 6.5 x 11.1
Rows x Columns x FPI
2 x 15 x 18
2 x 15 x 18
2 x 15 x 18
Coil
Face Area
m3
0.21
0.21
0.21
Type
Cross Flow Fan
Cross Flow Fan
Cross Flow Fan
Motor Output x Number
W
20
20
20
Running Current
A
0.2
0.2
0.2
Fan
Air Flow Rate(H / M / L)
CMM
7.0 / 6.0 / 4.0
8.0 / 7.0 / 5.0
10.0 / 8.0 / 6.0
cfm
247 / 212 / 141
282 / 247 / 177
353 / 283 / 212
Drive
Direct
Direct
Direct
Motor type
BLDC
BLDC
BLDC
Temperature Control
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Sound Absorbing Thermal Insulation Material
Foamed polystrene
Foamed polystrene
Foamed polystrene
Air Filter
Resin Net(washable)
Resin Net(washable)
Resin Net(washable)
Safety Device
Fuse
Fuse
Fuse
Liquid Side
mm(inch)
6.35(1/4)
6.35(1/4)
6.35(1/4)
Pipe Connections Gas Side
mm(inch)
12.7(1/2)
12.7(1/2)
12.7(1/2)
Drain Pipe(Internal Dia.) mm(inch)
16(5/8)
16(5/8)
16(5/8)
Net Weight
kg(lbs)
11.2(24.7)
11.2(24.7)
11.2(24.7)
Noise Level(Sound Press, 1m, H / M / L)
dB(A)
37 / 33 / 23
39 / 35 / 25
41 / 36 / 27
1,
220-240,
50
1,
220-240,
50
1,
220-240, 50
Power Supply
, V, Hz
1, 220, 60
1, 220, 60
1, 220, 60
Refrigerant Control
EEV
EEV
EEV
Power cable
mm2
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
Transmission cable
mm2
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Front Panel('*' Position)
R:Mirror V:Silver B:Blue
Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h
mm
inch

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ ART COOL Mirror

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specifications
ART COOL Mirror
ARNU15GSE*2
ARNU18GS8*2
4.5
5.6
Cooling Capacity
3,900
4,800
15,400
19,100
5.0
6.3
Heating Capacity
4,300
5,400
17,100
21,500
915
x
169
x
282
1,107
x 200 x 299
Dimensions(WxDxH) Body
36.0 x 6.5 x 11.1
43.9 x 7.9 x 11.8
Rows x Columns x FPI
2 x 15 x 18
2 x 15 x 20
Coil
Face Area
m3
0.21
0.26
Type
Cross Flow Fan
Cross Flow Fan
Motor Output x Number
W
20
20
Running Current
A
0.2
0.2
Fan
Air Flow Rate(H / M / L)
CMM
10.5 / 8.0 / 6.0
14.4 / 13.0 / 11.0
cfm
371 / 283 / 212
508 / 459 / 388
Drive
Direct
Direct
Motor type
BLDC
BLDC
Temperature Control
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Sound Absorbing Thermal Insulation Material
Foamed polystrene
Foamed polystrene
Air Filter
Resin Net(washable)
Resin Net(washable)
Safety Device
Fuse
Fuse
Liquid Side
mm(inch)
6.35(1/4)
6.35(1/4)
Pipe Connections Gas Side
mm(inch)
12.7(1/2)
12.7(1/2)
Drain Pipe(Internal Dia.) mm(inch)
16(5/8)
16(5/8)
Net Weight
kg(lbs)
11.2(24.7)
15(33.1)
Noise Level(Sound Press, 1m, H / M / L)
dB(A)
42 / 36 / 27
37 / 34 / 31
1,
220-240,
50
1,
220-240, 50
Power Supply
, V, Hz
1, 220, 60
1, 220, 60
Refrigerant Control
EEV
EEV
Power cable
mm2
CV1.5 x 3C
CV1.5 x 3C
Transmission cable
mm2
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Front Panel('*' Position)
R:Mirror V:Silver B:Blue
Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h
mm
inch

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

ARNU24GS8*2
7.1
6,100
24,200
8.0
6,900
27,300
1,107 x 200 x 299
43.9 x 7.9 x 11.8
2 x 15 x 20
0.26
Cross Flow Fan
20
0.2
17.9 / 14.4 / 12.0
632 / 508 / 424
Direct
BLDC
Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Resin Net(washable)
Fuse
9.52(3/8)
15.88(5/8)
16(5/8)
15(33.1)
43 / 37 / 32
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

ART COOL Mirror _ 3

Indoor Units

Type
Model

165

282

169

51

Air suction grill

282

Descripition

(unit : mm)

169

(unit : mm)

CHASSIS CODE: SE

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Name
Air discharge grill

915

Number

ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2
ARNU15GSE*2

Model

ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2
ARNU15GSE*2

ART COOL Mirror

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

53

4 _ ART COOL Mirror


567

915

282
265

Indoor Units

3. Dimensions

ART COOL Mirror _ 5

804

1107

72
58 122

281

93

299

200

53

Knockout hole
Installation plate

(unit : mm)
Remark

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

CHASSIS CODE: S8

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Air suction grille

Display & signal receiver

Front panel

Part Name

No.

ARNU18GS8*2
ARNU24GS8*2

Indoor Units

10
63

48

ART COOL Mirror

3. Dimensions

4. Piping Diagrams

Indoor Units

Heat Exchanger

:Cooling
:Heating

EEV
Filter
Th2

Th3

C.F.F

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU07GSE*2

12.7(1/2)

6.35(1/4)

ARNU09GSE*2

12.7(1/2)

6.35(1/4)

ARNU12GSE*2

12.7(1/2)

6.35(1/4)

ARNU15GSE*2

12.7(1/2)

6.35(1/4)

ARNU18GS8*2

12.7(1/2)

6.35(1/4)

ARNU24GS8*2

15.88(5/8)

9.52(3/8)

*Panel Color (SE/S8 chassis) : R(Mirror),V(Silver), B(Blue)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

6 _ ART COOL Mirror

PCB Connector
CN-TH1
CN-TH2

5. Wiring Diagrams
SE/S8 Chassis
Indoor Units

CONNECTOR NUMBER

LOCATION POINT

FUNCTION

CN-MOTOR1

Fan motor output

Motor output of BLDC

CN-COM

Communication

Communication between indoor and outdoor

CN-EEV

EEV output

EEV control output

CN-L/R

Step motor

Step motor output for left/right

CN-U/D

Step motor

Step motor output

CN-TH1

Room/pipe sensor

Room & pipe thermistor

CN-TH2

Discharge pipe sensor

Discharge pipe thermistor

CN-SUC

Step motor(front)

Front panel step motor

CN-HVB

Air purifier

Air purifier output

CN-VFD

Display

Display of indoor status

CN-12V

Safety connection

Safety of indoor status

CN-REMO

Remote controller

Remote control line

CN-CC

Dry contact

Dry contact line

CN-HVB

Air clean

Air clean control

ART COOL Mirror _ 7

6. Capacity Tables

Indoor Units

6.1 Cooling Capacity

Cooling Capacity

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

2.2

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.2

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.5

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
2.3

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.6
1.6
1.6
1.5
1.5
1.5
1.5

2.9
2.9
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3

1.7
1.6
1.6
1.6
1.6
1.6
1.5
1.5
1.5
1.5
1.5
1.4
1.4
1.4
1.4
1.4

2.8

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.9
2.9

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.0
2.0
2.0
1.9
1.9
1.9

3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0

2.1
2.1
2.1
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.9
1.8
1.8
1.8
1.8
1.7

3.6

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.7
3.7

2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.6
2.6

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
4.0
3.9
3.8
3.7

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.7
2.7
2.6
2.6
2.5
2.5
2.4

4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8

2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.4
2.3
2.3
2.2

Capacity
Index

Outdoor
air temp.
(DB, C)

Notes:
TC: Total Capacity(kW)

8 _ ART COOL Mirror

SHC: Sensible Heat Capacity(kW)

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

6. Capacity Tables
Cooling Capacity

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

Capacity
Index

4.5

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2

3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2

4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3

5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4

3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

5.9
5.8
5.8
5.7
5.6
5.5
5.5
5.4
5.3
5.3
5.2
5.1
5.0
5.0
4.9
4.8

3.5
3.4
3.4
3.3
3.3
3.2
3.2
3.2
3.1
3.1
3.0
3.0
2.9
2.9
2.9
2.8

5.6

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7

5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2

4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0

5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6

4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
5.8
5.7

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.1
4.0

6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.6
6.4
6.4
6.3
6.2
6.0
5.9
5.8

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
3.9
3.8
3.8

7.4
7.3
7.2
7.1
7.0
6.9
6.8
6.7
6.6
6.6
6.5
6.4
6.3
6.2
6.1
6.0

4.3
4.2
4.2
4.1
4.1
4.0
4.0
3.9
3.9
3.8
3.8
3.7
3.7
3.6
3.6
3.5

7.1

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3

5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7

4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7

6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1

7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1

5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2

7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.4
7.2

5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.2
5.1

8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.4
8.2
8.1
8.0
7.8
7.7
7.5
7.4

5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.5
5.4
5.3
5.2
5.1
5.0
4.9
4.8

9.3
9.2
9.1
9.0
8.8
8.7
8.7
8.5
8.4
8.3
8.2
8.1
7.9
7.8
7.7
7.6

5.5
5.5
5.4
5.3
5.2
5.2
5.1
5.1
5.0
4.9
4.8
4.8
4.7
4.6
4.6
4.5

Notes:
TC: Total Capacity(kW)

32
24
TC SHC
kW kW

SHC: Sensible Heat Capacity(kW)

ART COOL Mirror _ 9

Indoor Units

20
14
TC SHC
kW kW

Outdoor
air temp.
(DB, C)

6. Capacity Tables

Indoor Units

6.2 Heating Capacity


Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Heating Capacity
Indoor air temp. (DB, C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.2

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.8
2.8
2.9
2.9
2.9
2.9
2.9

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
2.7
2.7
2.7
2.7
2.7
2.7

1.7
1.7
1.8
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.5
2.5
2.5
2.5

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

2.8

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.1
2.2
2.3
2.5
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.6
3.6
3.7
3.7
3.7
3.7
3.7

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.1
2.2
2.3
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.1
2.2
2.3
2.4
2.6
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

3.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.7
2.8
2.9
3.1
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.4
4.5
4.6
4.6
4.6
4.6
4.6

2.7
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.3
4.3
4.3
4.3
4.3
4.3
4.3

2.7
2.8
2.9
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0

2.6
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Notes: TC: Total Capacity(kW)

10 _ ART COOL Mirror

6. Capacity Tables
Heating Capacity
Indoor air temp. (DB, C)
16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

4.5

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

3.4
3.5
3.7
3.9
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.6
5.6
5.8
5.8
5.8
5.8
5.8

3.4
3.5
3.7
3.8
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.4
5.4
5.4
5.4
5.4
5.4
5.4

3.4
3.5
3.7
3.4
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.6
4.9
5.0
5.0
5.0
5.0
5.0
5.0

3.3
3.5
3.7
3.8
4.0
4.3
4.3
4.4
4.4
4.6
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.3
3.4
3.7
3.8
4.0
4.2
4.3
4.4
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7

3.3
3.4
3.6
3.8
4.0
4.2
4.3
4.3
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4

5.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

4.2
4.3
4.6
4.9
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
7.0
7.1
7.2
7.2
7.2
7.2
7.2

4.2
4.3
4.6
4.8
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
6.7
6.7
6.7
6.7
6.7
6.7
6.7

4.2
4.3
4.6
4.3
4.5
4.8
4.9
5.0
5.1
5.4
5.5
5.8
6.2
6.3
6.3
6.3
6.3
6.3
6.3

4.2
4.3
4.6
4.8
5.0
5.4
5.4
5.5
5.6
5.8
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1

4.2
4.3
4.6
4.8
5.0
5.3
5.4
5.5
5.6
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9

4.2
4.3
4.5
4.8
5.0
5.3
5.4
5.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

7.1

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

5.4
5.5
5.8
6.2
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.9
9.0
9.2
9.2
9.2
9.2
9.2

5.4
5.5
5.8
6.1
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.6
8.6
8.6
8.6
8.6
8.6
8.6

5.4
5.5
5.8
5.5
5.8
6.0
6.2
6.3
6.5
6.8
7.0
7.4
7.8
8.0
8.0
8.0
8.0
8.0
8.0

5.3
5.5
5.8
6.1
6.4
6.8
6.9
7.0
7.1
7.4
7.7
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8

5.3
5.4
5.8
6.1
6.4
6.7
6.9
7.0
7.1
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

5.3
5.4
5.8
6.1
6.4
6.7
6.8
6.8
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Notes: TC: Total Capacity(kW)

ART COOL Mirror _ 11

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

7. Air Velocity and Temperature Distribution


ARNU07GSE*2
Indoor Units

Cooling

Heating

Discharge angle:45

Discharge angle:60
Air velocity [m/s]

Air velocity [m/s]


2.7m

2.7m

2m

2m

2.0

2.0

1.5

1m

1m
1.5
1.0

0.5

0.5

5m

4m

3m

2m

0m
0m

1m

5m

4m

1.0

3m

2m

0m
0m

1m

Temperature [C]

Temperature [C]

2.7m

2.7m

2m

2m
33

18
30
20

1m

1m
24

22

21

24

5m

4m

3m

2m

1m

0m
0m

5m

4m

27

3m

2m

0m
0m

1m

ARNU12GSE*2
Cooling

Heating

Discharge angle:45

Discharge angle:60
Air velocity [m/s]

Air velocity [m/s]


2.7m

2.7m

2m

2m
2.0

2.0
1.5

1m

1.5

0.5
0.5

5m

4m

3m

1m

1.0

1.0

2m

1m

0m
0m

5m

4m

3m

2m

0m
0m

1m

Temperature [C]

Temperature [C]
2.7m

2.7m

2m

2m
33

18

30

1m

21

1m
20
24

5m

4m

3m

24

27

22

2m

12 _ ART COOL Mirror

1m

0m
0m

5m

4m

3m

2m

1m

0m
0m

8. Electric Characteristics
Units
Model

Type

Power Supply
Hz

Volts

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

SE

0.29

15

0.02

0.23

40

40

ARNU09GSE*2

SE

0.29

15

0.02

0.23

40

40

ARNU12GSE*2

SE

Max:264

0.29

15

0.02

0.23

40

40

ARNU15GSE*2

SE

Min:198

0.29

15

0.02

0.23

40

40

ARNU18GS8*2

S8

0.29

15

0.02

0.23

35

35

ARNU24GS8*2

S8

0.29

15

0.02

0.23

35

35

ARNU07GSE*2

SE

0.29

15

0.02

0.23

40

40

ARNU09GSE*2

SE

ARNU12GSE*2

SE

ARNU15GSE*2

SE

ARNU18GS8*2
ARNU24GS8*2

50

220 - 240

0.29

15

0.02

0.23

40

40

Max:242

0.29

15

0.02

0.23

40

40

Min:198

0.29

15

0.02

0.23

40

40

S8

0.29

15

0.02

0.23

35

35

S8

0.29

15

0.02

0.23

35

35

60

220

Symbols:
MCA : Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the MCA.

ART COOL Mirror _ 13

Indoor Units

ARNU07GSE*2

9. Sound Levels
Overall

Indoor Units

Notes:
- Data is valid at nominal operating condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

1m
1m
Microphone

Sound Levels dB(A)

Model

H
37
39
41
42
37
43

ARNU07GSE*2
ARNU09GSE*2
ARNU12GSE*2
ARNU15GSE*2
ARNU18GS8*2
ARNU24GS8*2

M
33
35
36
36
34
37

L
23
25
27
27
31
32

Sound Pressure Level


ARNU07GSE*2

80

NC-55
NC-50
NC-45

40

NC-40
NC-35

30

NC-30

63

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-25
Approximate
Hearing
Threshold

70

NC-20

NC-15
125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

10

Octave Band Sound Pressure Level (dB re 20Pa )

NC-60
50

Octave Band Sound Pressure Level (dB re 20Pa )

Approximate
Hearing
Threshold
63

NC-60

NC-50

NC-40

NC-30

10

ARNU24GS8*2
70

NC-60
NC-55
NC-50
NC-45
NC-40
NC-35

Octave Band Sound Pressure Level (dB re 20Pa )

70

NC-65

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

10

NC-25
Approximate
Hearing
Threshold
63

NC-20

NC-15
125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

14 _ ART COOL Mirror

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

NC-30
NC-25

20

10

Approximate
Hearing
Threshold
63

NC-20

NC-15
125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

ARNU18GS8*2

70

20

NC-25
Approximate
Hearing
Threshold
63

80

30

NC-35

30

80

40

NC-45

40

20

NC-15
125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

ARNU15GSE*2

50

NC-55

50

80

60

NC-65

60

NC-20

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

NC-65

60

20

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU12GSE*2
80

70

70

10

ARNU09GSE*2

80

NC-20

NC-15
125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

NC-25

20

10

Approximate
Hearing
Threshold
63

NC-20

NC-15
125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

10. Installation

Installation Parts Provided

1. Type "A" screw

2. Installation Plate

Required Parts

Required Tools

Installation plate
Four type "A" screws
Connecting cable

Level gauge
Screw driver
Electric drill
Hole core drill

Pipes: Gas side


Liquid side
Insulation materials
Additional drain pipe

Flaring tool set


Specified torque wrenches
Spanner......................................................Half union
A glass of water
Screw driver
Thermometer

ART COOL Mirror _ 15

Indoor Units

Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

10. Installation
10.1 Selection of the best location

More than 100mm

unit.
There should not be any obstacles to prevent the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.

More than 200mm

More than 100mm


More than 2300mm

S8 chassis
Installation Plate

Chassis
Hook

The mounting wall should be strong and solid enough to


protect it from the vibration.
Mount the installation plate on the wall with four Type
"A" screws.
(If mounting the unit on the concrete wall, consider using
anchor bolts.)
Always mount the Installation plate horizontally by
aligning the marking-off line by means of the thread
and a level.

Type A

SE chassis
Installation Plate

Chassis
Hook

Type A

The lower left and the right side of Installation Plate


S8 chassis

70mm

70mm

Installation plate
133mm

100mm

Installation plate

70mm

70mm

85mm

Left rear piping

Right rear piping

110mm

SE chassis

110mm

Indoor Units

There should not be any heat source or steam near the

Left rear piping

65mm

Right rear piping

CAUTION : In case that the unit is installed near the sea, the installation parts
may be corroded by salt. The installation parts (and the unit) should be taken
appropriate anti-corrosion measures.

16 _ ART COOL Mirror

10. Installation
Preparing work for installation
3. Tape the tubing, drain hose and the connecting cable. Be sure that the drain hose is located at the lowest side of the bundle. Locating
at the upper side can cause drain pan to overflow inside the unit.

Tape
Connecting
pipe
Drain hose

Connecting cable
NOTICE : If the drain hose is routed inside the room,
insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.

For right rear piping

*Foamed polyethylene or equivalent is recommended.

1. Route the indoor tubing and the drain hose in


the direction of rear left.

Drain hose

4. Indoor unit installation


Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the
installation plate.) Ensure that the hooks are properly
seated on the installation plate by moving it left and
right.

Connecting

Drain hose

2. Insert the connecting cable into the indoor


unit from the outdoor unit through the piping
hole.
Do not connect the cable to the indoor unit.
Make a small loop with the cable for easy connection
later.

Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).

ART COOL Mirror _ 17

Indoor Units

Preparing the indoor unit's piping and drain hose for


installation through the wall.
Remove the plastic tubing retainer(see illustration
below) and pull the tubing and drain hose away from
chassis.
Replace the plastic tubing holder in the original position.

Indoor Units

10. Installation
5. Connecting the pipings to the indoor unit and
drain hose to drain pipe.
Align the center of the pipings and sufficiently tighten
the flare nut by hand.

Wrap the area which accommodates the rear piping housing section with vinyl tape.
Indoor
unit pipe
Wrap with vinyl tape

Connection
pipe
Vinyl tape
(wide)

Connecting cable

Indoor unit tubing

Flare nut

Pipings

Pipe
Vinyl tape(narrow)

Tighten the flare nut with a wrench.


Spanner (fixed)
Flare nut
Connection
pipe

Torque
wrench

Bundle the piping and drain hose together by


wrapping them with vinyl tape over the range within which they fit into the rear piping housing section.
Wrap with vinyl tape

Pipe

Indoor
unit tubing

Mount the clamp on the boss with a type "B"


screw.(optional)

Type "B" screw

Drain hose

Clamp

Vinyl tape(wide)
Drain hose

For left rear piping

Boss

1. Route the indoor tubing and the drain hose to


the required piping hole position.
When extending the drain hose at the indoor
unit, install the drain pipe.

Drain pipe

Indoor unit
drain hose
Vinyl tape(narrow)
Adhesive

6. Wrap the insulation material around the connecting portion.


Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.
Plastic bands

18 _ ART COOL Mirror

Insulation material

2. Insert the piping, drain hose and the connecting cable into the piping hole.

Connecting cable
Drain pipe

10. Installation
When extending the drain hose at the indoor unit,
install the drain pipe.

Drain hose

4. Tape the drain hose and the connecting cable.


Connecting cable

Indoor unit drain hose


Vinyl tape(narrow)
Adhesive

7. Wrap the insulation material around the connecting portion.


Overlap the connection pipe heat insulation and
the indoor unit pipe heat insulation material. Bind
them together with vinyl tape so that there is no
gap.
5. Indoor unit installation
Hang the indoor unit from the hooks at the top of
the installation plate.
Insert the spacer etc. between the indoor unit and
the installation plate and separate the bottom of
the indoor unit from the wall.

Plastic bands

Insulation material

Wrap the area which accommodates the rear piping housing section with vinyl tape.

Indoor unit
Spacer
Installation plate

Connection
pipe
Vinyl tape
(wide)

80mm

Indoor
unit piping
Wrap with vinyl tape
Pipe

6. Connecting the pipings to the indoor unit and


the drain hose to drain pipe.
Align the center of the pipings and sufficiently
tighten the flare nut by hand.

Indoor unit tubing

Flare nut

Connecting
cable

Vinyl tape
(narrow)

Pipings

Tighten the flare nut with a wrench.


Spanner (fixed)

Torque
wrench

Flare nut
Connection
pipe

Indoor
unit tubing

ART COOL Mirror _ 19

Indoor Units

3. Insert the connecting cable into the indoor


unit.
Don't connect the cable to the indoor unit.
Make a small loop with the cable for easy connection later.

Indoor Units

10. Installation
Bundle the piping and drain hose together by
wrapping them with cloth tape over the range
within which they fit into the rear piping housing
section.

9. Set the pipings and the drain hose to the back


of the chassis with the tubing holder.
Hook the edge of tubing holder to tap on chassis
and push the bottom of tubing holder to be
engaged at the bottom of chassis.

Pipe
Drain hose

Vinyl tape
(narrow)

Wrap with
vinyl tape(wide)

8. Reroute the pipings and the drain hose across


the back of the chassis.

Tubing holder

10. Indoor unit installation


Remove the spacer.
Ensure that the hooks are properly seated on the
installation plate by moving it left and right.

Connecting

Piping for
passage through
piping hole

Drain hose

Press the lower left and right sides of the unit


against the installation plate until the hooks engage
into their slots(clicking sound).

20 _ ART COOL Mirror

10. Installation
10.2 Connection of Pipings
2. To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the indoor
unit without any leakage and goes out the drain exit.
Connecting area
drain hose

Leakage
checking
Drain pan

Drain
hose
Leakage
checking

Front panel

The drain hose should point downward for easy drain flow.
Downward slope

Do not make drain piping.


Accumulated
drain water
Air

Do not raise

Water
leakage

Water
leakage

Waving

Tip of drain hose


dipped in water
Water
leakage

Less than
50mm gap

Ditch

10.3 Connect the cable to the


indoor unit
1. Connect the wires to the terminals on the
control board individually according to the
outdoor unit connection.
Ensure that the color of the wires of outdoor
unit and the terminal No. are the same as
those of indoor unit respectively.

Remote control
co
cord

Connecting cable

ART COOL Mirror _ 21

Indoor Units

1. To remove the front panel from the indoor unit,


remove the front panel from the indoor unit
cabinet.
Set the air direction louvers up-and-down to the
position(horizontally) by hand.
Remove the securing screws that retain the front
panel. Pull the lower left and right sides of the grille
toward you and lift it off.

10. Installation
SODU

Terminal Block Indoor

Indoor Units

1(L1) 2(L2)

IDU
-

INTERNET DRY1 DRY2 GND 12V Outdoor unit


B
A
-

INDOOR POWER INPUT

2. Attach the Grille onto the cabinet.


Grasp lower the left and right side of the Grille
and engage four tabs on the top inside edge of
the chassis.
Press the Grille toward the chassis until it is
back into its original place.

CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1) As for the method of wiring, follow the circuit diagram posted on the inside of
control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to
come loose from vibrations to which the unit is subjected during the course of
transportation. Check them and make sure that they are all tightly fastened. (If
they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the
rated voltage marked on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.)
7) Always install an earth leakage circuit breaker in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking,
disturbance of the normal function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the
fixed wiring and have an air gap contact separation of at least 3mm in each
active(phase) conductor.

22 _ ART COOL Mirror

10. Installation
WIRED REMOTE CONTROLLER INSTALLATION

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller
LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller
Remote

TEMP

Remote Controller

5feet
(1.5meters)

no

no

Fig.1 Typical locations for remote controller

ART COOL Mirror _ 23

Indoor Units

Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place away
from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

11. Accessories

Indoor Units

Standard Accessories
Name

Installation panel

Type "A" screws and


plastic anchors

Quantity

1 set

4 set

(Other)

SE

Owner's manual
Installation manual
Shape

S8

CAUTION
Use only those accessories (Standard or optional) which have designated specifications.

24 _ ART COOL Mirror

Indoor unit
ART COOL Gallery
1. List of functions
2. Specifications
3. Dimensions
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. Electric Characteristics
8. Sound Levels
9. Installation
10. Accessories

1. List of functions

Indoor Units

Category

Air flow

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Function
Air supply outlet
Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU07GSF*2, ARNU09GSF*2, ARNU12GSF*2


3
X
Auto
X
O
3/4/3
X
O
O
X
Option
O
O
O
O
O(Heat recovery)
O
O(Heat pump or Cooling only)
O
O
O
O
O
O
O
O
Accessory
Accessory
Accessory
Accessory
Accessory
Accessory
-

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

1 _ ART COOL Gallery

2. Specifications
Type
Model

Heating Capacity
Dimensions(WxDxH) Body
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
kg(lbs)
Noise Level(Sound Press, 1m, H / M / L)
dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Front Panel('*' Position)

, V, Hz
mm2
mm2

ART COOL Gallery


ARNU07GSF*2
ARNU09GSF*2
ARNU12GSF*2
2.2
2.8
3.6
1,900
2,400
3,100
7,500
9,600
12,300
2.5
3.2
4.0
2,200
2,800
3,400
8,500
10,900
13,600
600x146x600
600x146x600
600x146x600
23.6x5.7x23.6
23.6x5.7x23.6
23.6x5.7x23.6
2x20x21
2x20x21
2x20x21
0.18
0.18
0.18
Turbo Fan
Turbo Fan
Turbo Fan
30
30
30
0.16
0.16
0.16
8.1 / 6.3 / 4.2
8.1 / 6.3 / 4.2
9.3 / 7.7 / 6.0
286 / 222 / 148
286 / 222 / 148
328 / 272 / 212
Direct
Direct
Direct
BLDC
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Foamed polystrene
Resin Net(washable)
Resin Net(washable)
Resin Net(washable)
Fuse
Fuse
Fuse
6.35(1/4)
6.35(1/4)
6.35(1/4)
12.7(1/2)
12.7(1/2)
12.7(1/2)
12.2(15/32)
12.2(15/32)
12.2(15/32)
15(33.1)
15(33.1)
15(33.1)
38 / 32 / 27
38 / 32 / 27
44 / 38 / 32
1, 220-240, 50
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
1, 220, 60
EEV
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
E:Red, V:Silver, G:Gold, 1: Kiss (Photo changeable)

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Panel color: E(Red), V(Silver), G(Gold) Panel type


1: Kiss (Photo changeable) Gallery type

ART COOL Gallery _ 2

Indoor Units

Cooling Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h
mm
inch

525

3 _ ART COOL Gallery

Fix Hole

500

Pipe Hole

Hanger Hole

Air discharge grill


Air suction grill

1
2

600

Descripition

(unit : mm)

146

(unit : mm)

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

CHASSIS CODE: SF

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Name

600

Number

ARNU07GSF*2
ARNU09GSF*2
ARNU12GSF*2

Model

ARNU07GSF*2
ARNU09GSF*2
ARNU12GSF*2

ART COOL Gallery

Indoor Units

3. Dimensions

4. Piping Diagrams

Th3

EEV

Filter

:Cooling
:Heating

Th2

Turbo Fan

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

Model

Gas

Liquid

ARNU07GSF*2

12.7(1/2)

6.35(1/4)

ARNU09GSF*2

12.7(1/2)

6.35(1/4)

ARNU12GSF*2

12.7(1/2)

6.35(1/4)

*Panel color :E(Red), V(Silver), G(Gold), 1(Kiss (Photo changeable))


LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

PCB Connector
CN-TH1
CN-TH1

ART COOL Gallery _ 4

Indoor Units

Heat Exchanger

5. Wiring Diagrams

Indoor Units

SF Chassis

CONNECTOR NUMBER
CN-MOTOR1
CN-COM

LOCATION POINT
Fan motor output
Communication

FUNCTION
Motor output of BLDC
Communication between indoor and outdoor

CN-EEV
CN-D1
CN-LR1
CN-LR2
CN-UD
CN-TH1
CN-TH2
CN-REMO
CN-CC
CN-HVB

EEV output
Display
Step motor
Step motor
Step motor
Room/pipe sensor
Discharge pipe sensor
Remote controller
Dry contact
Air clean

EEV control output


Display of indoor status
Step motor output for left/right
Step motor output for left/right
Step motor output
Room and pipe thermistor
Discharge pipe thermistor
Remote control line
Dry contact line
Air clean control

5 _ ART COOL Gallery

6. Capacity Tables
6.1 Cooling Capacity

Cooling Capacity

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

Capacity
Index

2.2

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.2

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.5

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
2.3

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.6
1.6
1.6
1.5
1.5
1.5
1.5

2.9
2.9
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3

1.7
1.6
1.6
1.6
1.6
1.6
1.5
1.5
1.5
1.5
1.5
1.4
1.4
1.4
1.4
1.4

2.8

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.9
2.9

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.0
2.0
2.0
1.9
1.9
1.9

3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0

2.1
2.1
2.1
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.9
1.8
1.8
1.8
1.8
1.7

3.6

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.7
3.7

2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.6
2.6

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
4.0
3.9
3.8
3.7

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.7
2.7
2.6
2.6
2.5
2.5
2.4

4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8

2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.4
2.3
2.3
2.2

Notes:
TC: Total Capacity(kW)

32
24
TC SHC
kW kW

SHC: Sensible Heat Capacity(kW)

ART COOL Gallery _ 6

Indoor Units

20
14
TC SHC
kW kW

Outdoor
air temp.
(DB, C)

6. Capacity Tables

Indoor Units

6.2 Heating Capacity


Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Heating Capacity

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.2

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.8
2.8
2.9
2.9
2.9
2.9
2.9

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
2.7
2.7
2.7
2.7
2.7
2.7

1.7
1.7
1.8
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.5
2.5
2.5
2.5

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

2.8

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.1
2.2
2.3
2.5
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.6
3.6
3.7
3.7
3.7
3.7
3.7

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.1
2.2
2.3
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.1
2.2
2.3
2.4
2.6
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

3.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.7
2.8
2.9
3.1
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.4
4.5
4.6
4.6
4.6
4.6
4.6

2.7
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.3
4.3
4.3
4.3
4.3
4.3
4.3

2.7
2.8
2.9
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0

2.6
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Notes:
TC: Total Capacity(kW)

7 _ ART COOL Gallery

7. Electric Characteristics
Units
Type

ARNU07GSF*2

SF

ARNU09GSF*2

SF

ARNU12GSF*2

SF

ARNU07GSF*2

SF

ARNU09GSF*2

SF

ARNU12GSF*2

SF

Hz
50

Volts
220 - 240

60

220

Voltage Range MCA


Max:264
Min:198

Max:242
Min:198

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

0.23

15

0.024

0.18

35

35

0.23

15

0.024

0.18

35

35

0.23

15

0.024

0.18

35

35

0.23

15

0.024

0.18

35

35

0.23

15

0.024

0.18

35

35

0.23

15

0.024

0.18

35

35

Symbols:
MCA: Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the MCA.
5. Instead of fuse, use Circuit Breaker.

ART COOL Gallery _ 8

Indoor Units

Model

Power Supply

8. Sound Levels

Indoor Units

Overall

Notes:
- Data is valid at nominal operating condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

1m
0.8m
Microphone
Model

Sound Levels dB(A)


M
L

ARNU07GSF*2

38

32

27

ARNU09GSF*2

38

32

27

ARNU12GSF*2

44

38

32

Sound Pressure Level


ARNU07GSF*2
ARNU09GSF*2

ARNU12GSF*2
80

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

80

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

NC-25

20

NC-20

Approximate
Hearing
Threshold

NC-15

10
63

NC-25

20

Approximate
Hearing
Threshold
125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

9 _ ART COOL Gallery

NC-20
NC-15

10
63

125

250

500

1000 2000 4000 8000

Octave Band Center Frequency (Hz)

9. Installation
Please read the instruction sheets completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Indoor Units

Installation Parts Provided

1. Installation guide map

2. Type "A" screw and plastic anchors

Required Parts

Required Tools

Four type "A" screws


Connecting cable
Pipes: Gas side
Liquid side

Level gauge
Screw driver
Electric drill
Hole core drill
Flaring tool set
Specified torque wrenches
Spanner......................................................Half union
A glass of water
Screw driver
Thermometer

Insulation materials
Additional drain pipe

9.1 Selection of the best location


Do not have any heat or steam near the unit.
Select a place where there are no obstacles in front of the unit.
Make sure that condensation drainage can be conveniently
routed away.
Do not install near a doorway.
Ensure that the space around the left and right of the unit is
more than 500mm. The unit should be installed as high on the
wall as possible, allowing a minimum of 200mm from ceiling.
Use a stud finder to locate studs to prevent unnecessary damage to the wall.

More than
200mm
More than
500mm

More than
500mm
More than 1500mm

ART COOL Gallery _ 10

9. Installation
9.2 Preparing Work for Installation
Indoor Units

Open panel front


1. Pull the upper part of the front panel.
2. Lift up the panel.
3. To detach the front panel, remove the two screws at the lower part.
4. Detach the front panel from the body.
5. To detach the panel, disconnect the connector at the upper part.

Panel Front
Connector

Cover pipe and cover side remove


1. Please remove the screw of the center tuning cover.
2. Pull up the side cover of desired connecting direction, then
cover side is separated.
3. Pick the pipe hole of the side cover.

CAUTION: After removing the pipe hole,


cut the burr for safety.

Pipe hole
Side cover

NOTICE

When making pipe path through rear


wall, you dont need to pick the pipe hole.

Drain hose junction


1. Remove the rubber stopple in the desired drain
direction.
2. Insert drain hose into the handle of drain pan, and
join drain hose and connecting hose according to
the figure by.
Adhesive

Onlythe
the
Only
desired
desireddirection
direction

Connecting
part
Drain
hose

11 _ ART COOL Gallery

rubber cap

9. Installation
9.3 Fixing Indoor Unit
1. Attach an Installation guide map on the
desired surface.

Horizontality

3. Make a hole with a diameter of 6mm and


depth of 30-35mm by piercing a screw
point.
IN
ST
AII
AT
IO
N

IN
ST
AL
LA
TIO
N

GU
ID
EM
AP

4. Drill the pierted part as a diameter of 50mm


for connecting piping. (In case of piercing
rear surface)

GU
ID
EM
AP

5. Drive the fore plastic anchors into drilled


points.
IN
ST
AL
LA
TIO
N

GU
ID
EM
AP

6. First, Drive the two points of the upper


parts by screws. (Leave 10mm for hanging
the product)
10

Plastic anchors

7. Hang the hole of product at the upper


screws, and remove the map. (Falling
attention)
INS
TAL
LAT
ION
GUID
EM
AP

mm

IN
ST
AL
LA
TIO
N

GU

8. Drive the lower parts after facing the hole


of product with plastic anchors, and fix
completely the upper screws.
Plastic anchors

Hanger hole
(Rear side of
the product)

9. Check the fixed product with light power.

10. In case of nothing wrong, connect the


pipe and the wire. (Refer to installation
manual)

ART COOL Gallery _ 12

Indoor Units

INSTALLATION GUIDE MAP

2. Look at suited horizon by horizontal


meter on the horizontal setting line, and
fix lightly the map by adhesive tape.

9. Installation
9.4 Connecting the Piping

Indoor Units

Preparing the indoor unit's piping and drain hose for


installation through the wall.
1. Route the indoor tubing and the drain hose in
the direction of rear left or right

3. Connecting the pipings to the in door unit and


drain hose to drain pipe
Align the center of the pipings and sufficiently
tighten the flare nut by hand.

Indoor unit tubing

Flare nut

Pipings

Tighten the flare nut with a wrench.

Drain hose

Spanner (fixed)
Flare nut

2. Tape the tubing, drain hose and the connecting


cable. Be sure that the drain hose is located at
the lowest side of the bundle. Locating at the
upper side can cause drain pan to overflow
inside the unit.

Torque wrench

Connection pipe

Indoor unit tubing

When extending the drain hose at the indoor


unit, install the drain pipe.

Drain pipe

Loop

Connecting
cable

Gas side piping


Liquid side piping

Drain hose

CAUTION: If the drain hose is routed


inside the room, insulate the hose with
an insulation material* so that dripping
from "sweating"(condensation) will not
damage furniture or floors.
*Foamed polyethylene or equivalent is
recommended.

13 _ ART COOL Gallery

Indoor unit drain hose


Adhesive

Vinyl tape(narrow)

4. Wrap the insulation material around the connecting portion.


Overlap the connecting pipe insulation material
and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.

Plastic bands Insulation material

9. Installation
CAUTION: Installation Information
For right piping. Follow the instruction below.
Good case
Indoor Units

Press on the upper side of clamp and unfold the tubing to downward slowly.

Bad case
Following bending type from left to right may cause damage to the turbing.

9.5 Drain Piping


1) To check the drainage.
Pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of
the indoor unit without any leakage and goes out
the drain exit.

2) Drain piping
The drain hose should point downward for easy
drain flow.
Downward slope

Do not make drain piping.


Do not raise

Tip of drain hose


dipped in water

Accumulated
drain water

Less than
50mm gap

Air

Water
leakage

Water
leakage

Waving

Water
leakage

Ditch

ART COOL Gallery _ 14

9. Installation

Indoor Units

9.6 Panel Front Assembly


1. First, Check the side cover assembly
exactly, and fix the power cord in the
bottom groove of cover side left.

2. Assemble connecting lead wire with


controller, fix the upper part of panel
front, and match the lower part of panel
front.
Panel Front
Connector

3. Screw up panel front, and suspend the


hook of panel front in the groove.

15 _ ART COOL Gallery

9. Installation
9.7 Connect the cable to the Indoor unit.

Terminal Block Indoor


1(L)

2(N)

SODU

INTERNET DRY1 DRY2 GND 12V

IDU
-

Outdoor
Unit

INDOOR POWER INPUT

CAUTION
When installing, refer to the circuit diagram on the
Control Box of Indoor Unit.
When installing, refer to the wiring diagram on the
Control Cover Inside Outdoor Unit.

CAUTION
The above circuit diagram is subject to change without notice.
Be sure to connect wires according to the wiring diagram.
Connect the wires firmly, so that not to be pulled out
easily.
Connect the wires according to color codes by referring the wiring diagram.

After the confirmation of the above conditions,


prepare the wiring as follows:
1) Never fail to have separate power circuit specifically for the air conditioner. As for the method
of wiring, follow the circuit
diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing
of electrical fittings are liable to come loose
from vibrations to which the unit is subjected
during the course of transportation. Check
them and make sure that they are all tightly
fastened. (If they are loose, it could cause
burn-out of the wires.)
3) Confirm the specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at
more than 90 percent of the rated voltage
marked on the name plate.
6) Confirm that the cable thickness is as specified
in the power source specification.
(Particularly note the relation between cable
length and thickness.
7) Always install an earth leakage circuit breaker
in a wet or moist area.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage
the contact point, fuse breaking, disturbance of
the normal function of the overload.
9) The means for disconnection from a power
supply shall be incorporated in the fixed wiring
and have an air gap contact separation of at
least 3mm in each active(phase) conductor.

ART COOL Gallery _ 16

Indoor Units

Connect the cable to the indoor unit by connecting the wires to the terminals on the control board individually according to the outdoor unit connection. (Ensure that the color of the wires of the outdoor unit
and the terminal No. are the same as those of the indoor unit.)
The earth wire should be longer than the common wires.

9. Installation

Indoor Units

WIRED REMOTE CONTROLLER INSTALLATION


Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place
away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller
LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller
Remote

TEMP

Remote Controller

5feet
(1.5meters)

no

no

Fig.1 Typical locations for remote controller

17 _ ART COOL Gallery

10. Accessories
Standard Accessories
Installation guide map

Quantity

1 EA

Type "A" screws and


plastic anchors

(Other)

4 SET
Owner's manual
Installation manual

Shape

CAUTION
Use only those accessories (Standard or optional) which have designated specifications.

ART COOL Gallery _ 18

Indoor Units

Name

Indoor unit
Ceiling & Floor / Ceiling Suspended
1. List of functions
2. Specifications
3. Dimensions
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. Electric Characteristics
8. Sound Levels
9. Installation
10. Accessories

1. List of functions
Category

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Air supply outlet


Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU09GVEA2, ARNU12GVEA2
ARNU18GVJA2, ARNU24GVJA2
1
Manual
Auto
X
O
3/4/3
X
O
O
X
X
O
X
X
X
O
O
O
O
O(Heat recovery)
X
O(Heat pump or Cooling only)
O
O
O
O
O
O
O
O
Accessory
Accessory
Accessory
Accessory
X
Accessory
-

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

Ceiling & Floor / Ceiling Suspended _ 1

Indoor Units

Air flow

Function

2. Specifications

Indoor Units

Type
Model
Cooling Capacity

Heating Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Casing
Dimensions(WxDxH) Body
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
kg(lbs)
Noise Level(Sound Press, 1m, H / M / L)
dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Color

, V, Hz
mm2
mm2

Ceiling & Floor


ARNU09GVEA2
ARNU12GVEA2
2.8
3.6
2,400
3,100
9,600
12,300
3.2
4.0
2,800
3,400
10,900
13,600
900 x 200 x 490
900 x 200 x 490
35.4 x 7.9 x 19.3
35.4 x 7.9 x 19.3
2 x 12 x 20
2 x 12 x 20
0.10
0.10
Cross Flow Fan
Cross Flow Fan
27
27
0.15
0.15
7.6 / 6.9 / 6.2
9.2 / 7.6 / 6.9
268 / 243 / 219
325 / 268 / 244
Direct
Direct
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Fuse
Fuse
6.35(1/4)
6.35(1/4)
12.7(1/2)
12.7(1/2)
16(5/8)
16(5/8)
13.7(30.2)
13.7(30.2)
36 / 32 / 28
38 / 36 / 30
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Morning fog
Morning fog

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Ceiling & Floor / Ceiling Suspended

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specifications
Type
Model

Heating Capacity
Casing
Dimensions(WxDxH) Body
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control
Sound Absorbing Thermal Insulation Material
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
kg(lbs)
Noise Level(Sound Press, 1m, H / M / L)
dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable
Color

, V, Hz
mm2
mm2

Ceiling Suspended
ARNU18GVJA2
ARNU24GVJA2
5.6
7.1
4,800
6,100
19,100
24,200
6.3
8.0
5,400
6,900
21,500
27,300
Galvanized Steel Plate+Painting
Galvanized Steel Plate+Painting
950 x 220 x 650
950 x 220 x 650
37.4 x 8.7 x 25.6
37.4 x 8.7 x 25.6
3 x 14 x 19
3 x 14 x 19
0.23
0.23
Sirocco Fan
Sirocco Fan
60
60
0.30
0.30
16.0 / 14.0 /12.0
18.0 / 16.0 / 14.0
565 / 495 / 424
636 / 565 / 495
Direct
Direct
BLDC
BLDC
Microprocessor, Thermostat for cooling and heating Microprocessor, Thermostat for cooling and heating
Foamed polystrene
Foamed polystrene
Fuse
Fuse
6.35(1/4)
9.52(3/8)
12.7(1/2)
15.88(5/8)
16(5/8)
16(5/8)
24.6(54.2)
24.6(54.2)
42 / 40 / 37
43 / 41 / 39
1, 220-240, 50
1, 220-240, 50
1, 220, 60
1, 220, 60
EEV
EEV
CV1.5 x 3C
CV1.5 x 3C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Morning fog
Morning fog

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Ceiling & Floor / Ceiling Suspended _ 3

Indoor Units

Cooling Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

4 _ Ceiling & Floor / Ceiling Suspended


Air suction grill

587

<Ceiling Installation>

Air discharge grill

900
1

Air discharge grill


Air suction grill

1
2

490

Descripition

(unit : mm)

200

(unit : mm)

CHASSIS CODE: VE

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Name

900

ARNU09GVEA2
ARNU12GVEA2

Number

Model

ARNU09GVEA2
ARNU12GVEA2

Ceiling & Floor

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

<Floor Installation>

200

Signal receiver & Operation indicator

24
490

879

273

Indoor Units

3. Dimensions

Ceiling & Floor / Ceiling Suspended _ 5

950

800

41

Note

650

Descripition

(unit : mm)

220

(unit : mm)

CHASSIS CODE: VJ

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Air suction grill

Air discharge grill

1
2

Name

Number

950

ARNU18GVJA2
ARNU24GVJA2

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

(Ceiling Suspended type)

220

Model

ARNU18GVJA2
ARNU24GVJA2

Indoor Units

650

Ceiling Suspended

3. Dimensions

4. Piping Diagrams
VE Chassis
Indoor Units

Heat Exchanger
Th3

EEV

:Cooling
:Heating

Filter

Th2
C.F.F.

Th1

Filter

lndoor unit

VJ Chassis
Heat Exchanger

EEV

:Cooling
:Heating

Filter

Th2

Th3
Sirocco Fan

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

Model

Gas

Liquid

ARNU09GVEA2

12.7(1/2)

6.35(1/4)

ARNU12GVEA2

12.7(1/2)

6.35(1/4)

ARNU18GVJA2

12.7(1/2)

6.35(1/4)

ARNU24GVJA2

15.88(5/8)

9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

6 _ Ceiling & Floor / Ceiling Suspended

5. Wiring Diagrams
VE Chassis
Indoor Units

CONNECTOR
NUMBER
CN-POWER
CN-MOTOR1
CN-MOTOR2
CN-PIPE/OUT
CN-PIPE/IN
CN-ROOM
CN-REMO
CN-FLOAT
CN-EEV
CN-OPTION
CN-COM
CN-D/PUMP
CN-POWER
CN-DISPLAY
CN-DOOR
CN-CC

SPEC.

DESCRIPTION

AC power supply
Fan motor output
Fan motor output
Discharge pipe sensor
Suction pipe sensor
Room sensor
Remote controller
Float switch input
EEV output
Option pwb.
Communication
Drain pump output
AC power supply
Display wire
Door lock switch
Dry contact

AC power line input for indoor controller


Motor output of BLDC
Motor output of BLDC
Pipe out thermistor
Pipe in thermistor
Room thermistor
Remote control line
Float switch sensing
EEV Control output
Communication between main and option
Communication between indoor and outdoor
AC Output for drain pump
AC Power line input for indoor controller
Display wire line
Door lock switch line
Dry contact line

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

Ceiling & Floor / Ceiling Suspended _ 7

5. Wiring Diagrams

Indoor Units

VJ Chassis

CONNECTOR
NUMBER
CN-POWER
CN-MOTOR1
CN-MOTOR2
CN-PIPE/OUT
CN-PIPE/IN
CN-ROOM
CN-REMO
CN-FLOAT
CN-EEV
CN-OPTION
CN-COM
CN-D/PUMP
CN-POWER
CN-DISPLAY
CN-DOOR
CN-CC

SPEC.

DESCRIPTION

AC power supply
Fan motor output
Fan motor output
Discharge pipe sensor
Suction pipe sensor
Room sensor
Remote controller
Float switch input
EEV output
Option pwb.
Communication
Drain pump output
AC power supply
Display wire
Door lock switch
Dry contact

AC power line input for indoor controller


Motor output of BLDC
Motor output of BLDC
Pipe out thermistor
Pipe in thermistor
Room thermistor
Remote control line
Float switch sensing
EEV Control output
Communication between main and option
Communication between indoor and outdoor
AC Output for drain pump
AC Power line input for indoor controller
Display wire line
Door lock switch line
Dry contact line

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

8 _ Ceiling & Floor / Ceiling Suspended

6. Capacity Tables
6.1 Cooling Capacity

Cooling capacity

23
16
TC SHC
kW kW

2.8

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.9
2.9

2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.0
2.0
2.0
1.9
1.9
1.9

3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0

2.1
2.1
2.1
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.9
1.8
1.8
1.8
1.8
1.7

3.6

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1

2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.7
3.7

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.5

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
4.0
3.9
3.8
3.7

2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.7
2.6
2.6
2.6
2.5
2.5
2.4
2.4

4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8

2.7
2.7
2.7
2.6
2.6
2.5
2.5
2.5
2.5
2.4
2.4
2.4
2.3
2.3
2.3
2.2

5.6

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7

5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2

4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0

5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6

4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
5.8
5.7

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.1
4.0

6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.6
6.4
6.4
6.3
6.2
6.0
5.9
5.8

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
3.9
3.8
3.8

7.4
7.3
7.2
7.1
7.0
6.9
6.8
6.7
6.6
6.6
6.5
6.4
6.3
6.2
6.1
6.0

4.3
4.2
4.2
4.1
4.1
4.0
4.0
3.9
3.9
3.8
3.8
3.7
3.7
3.6
3.6
3.5

Capacity
Index

Outdoor
air temp.
(DB, C)

Notes:
TC: Total Capacity(kW)

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

SHC: Sensible Heat Capacity(kW)

Ceiling & Floor / Ceiling Suspended _ 9

Indoor Units

20
14
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

6. Capacity Tables

Indoor Units

Cooling capacity

Capacity
Index

Outdoor
air temp.
(DB, C)

7.1

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

Notes:
TC: Total Capacity(kW)

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7

6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.4
8.2
8.1
8.0
7.8
7.7
7.5
7.4

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2

4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6

5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1

5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1
5.1

SHC: Sensible Heat Capacity(kW)

10 _ Ceiling & Floor / Ceiling Suspended

7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.4
7.2

5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.3
5.1
5.0

5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.4
5.3
5.2
5.1
5.1
5.0
4.9
4.8

32
24
TC SHC
kW kW
9.3
9.2
9.1
9.0
8.8
8.7
8.7
8.5
8.4
8.3
8.2
8.1
7.9
7.8
7.7
7.6

5.4
5.4
5.3
5.2
5.2
5.1
5.1
5.0
4.9
4.9
4.8
4.7
4.6
4.6
4.5
4.4

6. Capacity Tables
6.2 Heating Capacity
Indoor air temp. (DB, C)
16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.8

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.1
2.2
2.3
2.5
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.6
3.6
3.7
3.7
3.7
3.7
3.7

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.1
2.2
2.3
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.1
2.2
2.3
2.4
2.6
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

3.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.7
2.8
2.9
3.1
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.4
4.5
4.6
4.6
4.6
4.6
4.6

2.7
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.3
4.3
4.3
4.3
4.3
4.3
4.3

2.7
2.8
2.9
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0

2.6
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

5.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

4.2
4.3
4.6
4.9
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
7.0
7.1
7.2
7.2
7.2
7.2
7.2

4.2
4.3
4.6
4.8
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
6.7
6.7
6.7
6.7
6.7
6.7
6.7

4.2
4.3
4.6
4.3
4.5
4.8
4.9
5.0
5.1
5.4
5.5
5.8
6.2
6.3
6.3
6.3
6.3
6.3
6.3

4.2
4.3
4.6
4.8
5.0
5.4
5.4
5.5
5.6
5.8
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1

4.2
4.3
4.6
4.8
5.0
5.3
5.4
5.5
5.6
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9

4.2
4.3
4.5
4.8
5.0
5.3
5.4
5.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5

Notes:
TC: Total Capacity(kW)

Ceiling & Floor / Ceiling Suspended _ 11

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Heating capacity

6. Capacity Tables

Indoor Units

Heating capacity

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

7.1

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

5.4
5.5
5.8
6.2
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.9
9.0
9.2
9.2
9.2
9.2
9.2

5.4
5.5
5.8
6.1
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.6
8.6
8.6
8.6
8.6
8.6
8.6

5.4
5.5
5.8
5.5
5.8
6.0
6.2
6.3
6.5
6.8
7.0
7.4
7.8
8.0
8.0
8.0
8.0
8.0
8.0

5.3
5.5
5.8
6.1
6.4
6.8
6.9
7.0
7.1
7.4
7.7
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8

5.3
5.4
5.8
6.1
6.4
6.7
6.9
7.0
7.1
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

5.3
5.4
5.8
6.1
6.4
6.7
6.8
6.8
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Notes:
TC: Total Capacity(kW)

12 _ Ceiling & Floor / Ceiling Suspended

7. Electric Characteristics
Units
Model

Type
VE
VE
VJ
VJ

ARNU09GVEA2
ARNU12GVEA2
ARNU18GVJA2
ARNU24GVJA2

VE
VE
VJ
VJ

Hz

50

Volts

220 - 240

60

220

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

Max:264
Min:198

0.22
0.22
0.43
0.43

15
15
15
15

0.027
0.027
0.060
0.060

0.17
0.17
0.35
0.35

30
30
63
63

30
30
63
63

Max:242
Min:198

0.22
0.22
0.43
0.43

15
15
15
15

0.027
0.027
0.060
0.060

0.17
0.17
0.35
0.35

30
30
63
63

30
30
63
63

Symbols:
MCA: Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the MCA.
5. Instead of fuse, use Circuit Breaker.

Ceiling & Floor / Ceiling Suspended _ 13

Indoor Units

ARNU09GVEA2
ARNU12GVEA2
ARNU18GVJA2
ARNU24GVJA2

Power Supply

8. Sound Levels
Overall
Notes:
- Data is valid at nominal operating condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

1m

Indoor Units

1m
Microphone

Sound Levels dB(A)

Model

Sound Levels dB(A)

Model

ARNU09GVEA2

36

32

28

ARNU18GVJA2

42

40

37

ARNU12GVEA2

38

36

30

ARNU24GVJA2

43

41

39

Sound Pressure Level


ARNU18GVJA2

ARNU12GVEA2
80

70

70

70

NC-65
60
NC-60
NC-55

50

NC-50
NC-45
40
NC-40
NC-35

30

NC-30

NC-25

20
Approximate
Hearing
Threshold

NC-60

NC-50
NC-45
40
NC-40

250

500

1000

2000

4000

8000

Octave Band Center Frequency (Hz)

NC-35

30

NC-30

NC-25

20
Approximate
Hearing
Threshold

NC-15
125

NC-55

50

NC-20

10
63

NC-65
60

NC-15
125

250

ARNU24GVJA2

Octave Band Sound Pressure Level (dB re 20Pa )

70

NC-65
60
NC-60
NC-55
NC-50
NC-45

40

NC-40
NC-35

30

NC-30

NC-25

20

10

Approximate
Hearing
Threshold
63

NC-20
NC-15
125

250

500

1000

2000

4000

500

1000

2000

4000

Octave Band Center Frequency (Hz)

80

50

NC-65
60
NC-60

8000

Octave Band Center Frequency (Hz)

14 _ Ceiling & Floor / Ceiling Suspended

8000

NC-55

50

NC-50
NC-45
40
NC-40
NC-35

30

NC-30

NC-25

20
Approximate
Hearing
Threshold

NC-20

10
63

Octave Band Sound Pressure Level (dB re 20Pa )

80

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU09GVEA2
80

NC-20
NC-15

10
63

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

8000

9. Installation
Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Indoor Units

9.1 Features
9.1.1 VE Chassis

Vertical louver

Horizontal louver
Air outlet vent

Air filters
(behind front panel)
Air inlet vent

Ceiling & Floor / Ceiling Suspended _ 15

9. Installation
9.1.2 VJ Chassis

Indoor Units

Air Discharge

Right Side Cover

Signal Receptor

Air Filter

Left Side Cover

Inlet Grill

Drain hose

16 _ Ceiling & Floor / Ceiling Suspended

9. Installation
VE Chassis

NOTICE

Indoor Units

9.2 Installation Map


Installation parts you should purchase.

There should be no gap between


the ceiling and the unit.

Ceiling Mounting

Sleeve
Bushing-Sleeve
Putty(Gum Type Sealer)
More than
200mm
(Left and right
are identical)

More than 50mm

Bend the pipe as closely


on the wall as possible,
but be careful that it
doesn't break.

Wall Mounting

More than
200mm
(Left and right
are identical)

Vinyl tape (Wide)


To carry out the drainage
test, remove the air filters
and pour water into the heat
exchanger.
Apply after carrying out a
drainage test.

More than 50mm

Saddle

Ceiling & Floor / Ceiling Suspended _ 17

9. Installation
9.3 Select the best Location
Indoor Units

Indoor unit

More than 200mm

1. Do not have any heat or steam near the unit.


2. Select a place where there are no obstacles in front
of the unit.

More than 200mm

3. Make sure that condensation drainage can be conveniently routed away.


More than 50mm

4. Do not install near a doorway.


5. Ensure that the interval between a wall and the left
(or right) of the unit is more than 200mm. The unit
should be installed as low as possible on the wall,
allowing a minimum of 500mm from floor.

More than 200mm

6. Use a stud finder to locate studs to prevent unnecessary damage to the wall.
More than 50mm

More than 200mm

9.4 Preparing Work for Installation


Open panel front
1. Remove the five screws.
2. Release the claws in the 3 places indicated.
3. Pull up the Front Panel.

2 Claw

Cover pipe and cover side remove


1. Pull up the side cover of desired connecting direction,
then cover side is separated.
2. Pick the pipe hole of the side cover.

CAUTION: After removing the pipe


hole, cut the burr for safety.
NOTICE When

making pipe path through rear


wall, you dont need to pick the pipe hole.

Drain hose junction


1. Remove the rubber stopple in the desired drain direction.
2. Insert drain hose into the handle of drain pan, and
join drain hose and connecting hose according to the
figure as shown on the right.

18 _ Ceiling & Floor / Ceiling Suspended

9. Installation
9.5 Mounting the installation plate(Wall Mounting)
The wall you select should be strong and solid
enough to prevent vibration

2. Measure the wall and mark the centerline. It is also


important to use caution concerning the location of
the installation plate-routing of the wiring to power
outlets is through the walls typically. Drilling the
hole through the wall for piping connections must
be done safely.

Indoor Units

1. Mount the installation plate on the wall with


type "A" screws. While mounting the unit on a concrete wall, use anchor bolts.
Mount the installation plate horizontally by aligning
the centerline using a level.

Installation Plate

Type "A" screw

70

70
Installation plate

70mm

120

70mm

more than 2000


Left rear piping

Right rear piping


Floor

Ceiling & Floor / Ceiling Suspended _ 19

9. Installation
9.6 Mounting the anchor Nut & Bolt(Ceiling Mounting)
Indoor Units

Prepare 4 suspension bolts. (Each bolts length


should be same.)
Measure and mark the position for the Suspension
bolts and the piping hole.
Drill the hole for anchor nut on the ceiling.

Anchor nut
Ceiling
Nut

Washer

Suspension
bolts

Insert the nuts and washer onto the suspension bolts


for locking the suspension bolts on the ceiling.

40

235
820

Suspension bolt

50
100

Mount the suspension bolts to the anchor-nuts firmly.


Secure the hangers onto the Suspension bolts
(adjust level roughly.) using nuts, washers and
spring washers.

Reference
of piping
hole (45)

piping hole
(45)

Adjust a level with a level gauge on the direction of


left-right, back-forth by adjusting suspension bolts.
Suspension
bolts

Adjust a level on the direction of top-bottom by


adjusting supension bolts. Then the unit will be
inclined to the bottomside so as to drain well.

: Tighten the nut and bolt to prevent unit falling.

Spring
washer
Hangen
Max.
12mm

Nut

Washer

Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)

Flat washer for M10


(accessory)

Flat washer for M10


(accessory)
Nut
(W3/8 or M10)

20 _ Ceiling & Floor / Ceiling Suspended

9. Installation
: Installation Information For right piping. Follow the instruction below.

Bad case

For left piping. Follow the instruction below.

1. Following bending type from right to


left could cause problem of pipe damage.

1. Press on the upper side of clamp. ()


2. Unfold the tubing downward slowly. ()
3. Bend the tubing to the left side of chassis.

Ceiling & Floor / Ceiling Suspended _ 21

Indoor Units

Good case

9. Installation

Indoor Units

9.7 Checking the Drainage


1. Set the air direction louvers up-and-down to the position(horizontally) by hand.

To check the drainage.


1. Pour a glass of water on the evaporator using a kettle.
2. Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the
drain exit.
Checking the Drainage
1. Remove the Air Filter.

To remove air filter, take hold of tab and pull slightly


upwards.
2. Check the drainage.

Spray one or two glasses of water upon the evaporator.


Ensure that water flows drain hose of indoor unit
without any leakage.

Downward slope

Drain piping
1. The drain hose should point downward for easy drain
flow.
2. Do not make drain piping like the following.

Accumulated
drain water
Air

Do not raise

Water
leakage

Water
leakage

Waving

Less than
50mm gap

Tip of drain hose


dipped in water

Water
leakage

Ditch

9.8 Panel Front Assembly


1. Suspend the hook of panel front in the groove.
2. Press the panel front.

3. Screw up panel front.


3
2

22 _ Ceiling & Floor / Ceiling Suspended

9. Installation
VJ Chassis
9.9 Select the best Location
More than
700mm

2. Select a place where there are no obstacles in


front of the unit.
3. Make sure that condensation drainage can be
conveniently routed away.
4. Do not install near a doorway.
5. Ensure that the interval between a wall and the
left (or right) of the unit is more than 700mm.
6. Use a stud finder to locate studs to prevent
unnecessary damage to the wall.

More than
700mm

More than
300mm

: In case that the unit is installed near the sea, the installation parts may be cor-

roded by salt. The installation parts (and the unit) should be treated with appropriate anti-corrosion measures.

Ceiling & Floor / Ceiling Suspended _ 23

Indoor Units

Indoor unit
1. Do not have any heat or steam near the unit.

9. Installation

Indoor Units

9.10 Preparing Work for Installation


Open side cover
1. Remove two screws from side-cover as shown
in fig.
2. Unlock side-cover from side panel by slightly
pulling the edge of side cover.
3. Tap the side-cover with your palm on the backside.(Inlet grill side.)
4. Hold the side-cover with other hand while tapping to prevent it to fall down.
5. Remove the rubber stopple in the desired drain
direction.
6. Knock out the pipe hole from the left side-cover
with the help or nipper/plier.
7. Knock hole on right side-cover only if right side
is selected for water drain.

24 _ Ceiling & Floor / Ceiling Suspended

2
Edge part

9. Installation
(Unit: mm)

MOUNTING THE ANCHOR NUT AND


BOLT

DIM.

Prepare 4 suspension bolts. (Each bolts length


should be same.)

VJ

855

320

Measure and mark the position for the


Suspension bolts and the piping hole.
Drill the hole for anchor nut on the ceiling.
Insert the nuts and washer onto the suspension
bolts for locking the suspension bolts on the ceiling.
Mount the suspension bolts to the anchor-nuts
firmly.

Anchor nut

Ceiling

Suspension bolt
Nut

Washer

Suspension
bolts

Secure the hangers onto the Suspension bolts


(adjust level roughly.) using nuts, washers and
spring washers.
Adjust a level with a level gauge on the direction
of left-right, back-forth by adjusting suspension
bolts.

Suspension
bolts

Adjust a level on the direction of top-bottom by


adjusting supension bolts. Then the unit will be
inclined to the bottomside so as to drain well.

: Tighten the nut and bolt to prevent unit falling.

Spring
washer
Hangen

Nut

Max.
12mm

Washer

Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)

Flat washer for M10


(accessory)

Flat washer for M10


(accessory)
Nut
(W3/8 or M10)

DRILL A HOLE IN THE WALL.

WALL
Outdoor

(3/16"~5/16")

Indoor

5-7mm

Drill the piping hole with a 70mm hole core drill.


Drill the piping hole at either the right or the left
with the hole slightly slanted to the outdoor side.

Ceiling & Floor / Ceiling Suspended _ 25

Indoor Units

MODEL

9. Installation

Indoor Units

9.11 Indoor unit installation


Hang the Indoor unit on suspension bolt as per following guidelines:
1. Lift the indoor unit to sufficient height.
2. Insert the suspended part of four suspension bolt in the four hangers provided on the side of main body one by one.
3. Lower the indoor unit till the hangers rest on their respective flat washer.
4. Adjust the level in the top down direction by adjusting the suspension bolts.
Inclined the indoor unit as per direction provided in the fig

: Installation Information For Declination

1. Inclination of the indoor unit is very important for drain purposes in the convertible
type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 10mm.
3. If the Installation Plates are fixed to horizontal line, the indoor unit after installing will be
declined to the bottomside.

Front of view
The unit must be horizontal or inclined at angle.
The inclination should be less than or equal to 1 or in between 10 to 20mm inclined in drain direction as
shown in fig.
Ceiling
10~20mm

Side of view
The unit must be inclined to the bottomside of the unit when finished installation.
Ceiling

26 _ Ceiling & Floor / Ceiling Suspended

9. Installation
9.12 Checking the Drainage
Indoor Units

1. Set the air direction louvers up-and-down to the position(horizontally) by hand.

To check the drainage.


1. Pour a glass of water on the evaporator using a kettle.
2. Ensure the water flows through the drain hose of the
indoor unit without any leakage and goes out the
drain exit.

Drain piping
Downward slope

1. The drain hose should point downward for easy drain


flow.

2. Do not make drain piping like the following.


Accumulated
drain water
Air

Do not raise

Water
leakage

Water
leakage

Waving

Tip of drain hose


dipped in water

Water
leakage

Less than
50mm gap

Ditch

Ceiling & Floor / Ceiling Suspended _ 27

9. Installation

Indoor Units

9.13 Wiring Connection


Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of
indoor unit respectively.
Terminal Block Indoor
1(L)

2(N)

SODU

INTERNET DRY1 DRY2 GND 12V

IDU
-

Outdoor
Unit

INDOOR POWER INPUT

WARNING : Make sure that the screws of the terminal are free from looseness.

28 _ Ceiling & Floor / Ceiling Suspended

9. Installation
CAUTION:
After the confirmation of the above conditions, prepare the wiring as follows:

2) Provide a circuit breaker switch between power source and the unit.
3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose
from vibrations to which the unit is subjected during the course of transportation. Check them
and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of
the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly
note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the normal
function of an overload protection device.
Proper starting power is not given to the compressor.

Ceiling & Floor / Ceiling Suspended _ 29

Indoor Units

1) Never fail to have a separate power circuit specially for the air conditioner. As for the method of
wiring, follow the circuit diagram posted on the inside of control box cover.

9. Installation

Indoor Units

WIRED REMOTE CONTROLLER INSTALLATION


Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place
away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller
LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller
Remote

TEMP

Remote Controller

5feet
(1.5meters)

no

no

Fig.1 Typical locations for remote controller

30 _ Ceiling & Floor / Ceiling Suspended

10. Accessories
Standard Accessories
Installation plate

Type "A" screw and


plastic anchor

Quantity

1EA

4EA

(Other)

Owner's manual
Installation manual
Shape

CAUTION
Use only those accessories (Standard or optional) which have designated specifications.

Ceiling & Floor / Ceiling Suspended _ 31

Indoor Units

Name

Indoor unit
Floor Standing
1. List of functions
2. Specifications
3. Dimensions
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. Air Velocity and Temperature Distribution
8. Electric Characteristics
9. Sound Levels
10. Installation
11. Accessories

1. List of functions
Category

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Air supply outlet


Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

Floor Standing _ 1

Indoor Units

Air flow

Function

ARNU07GCEA2, ARNU09GCEA2, ARNU12GCEA2


ARNU15GCEA2, ARNU18GCFA2, ARNU24GCFA2
ARNU07GCEU2, ARNU09GCEU2, ARNU12GCEU2
ARNU15GCEU2, ARNU18GCFU2, ARNU24GCFU2
1
3/3/3
X
X
O
X
O
X
O
O
O
O(Heat recovery)
X
O(Heat pump or Cooling only)
O
O
O
X
O
O
O
Accessory
Accessory
Accessory
Accessory
X
Accessory
-

2. Specification

Indoor Units

Type
Model
Cooling Capacity

Heating Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Casing
Dimensions(WxDxH) Body
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control

Sound Absorbing Thermal Insulation Material


Air Filter
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable

, V, Hz
mm2
mm2

ARNU07GCEA2
2.2
1,900
7,500
2.5
2,200
8,500
Galvanized
Steel Plate
1,067 x 203 x 635
42.2 x 8.0 x 25.0
2 x 12 x 19
0.16
Sirocco Fan
28
0.15
8.5 / 7.5 / 6.5
300 / 265 / 229
Direct
BLDC
Microprocessor,
Thermostat for
cooling and heating
Foamed polystrene
Resin Net(washable)
Fuse
6.35(1/4)
12.7(1/2)
12(15/32)
27(59.5)
35 / 33 / 31
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C

Floor Standing
ARNU09GCEA2
2.8
2,400
9,600
3.2
2,800
10,900
Galvanized
Steel Plate
1,067 x 203 x 635
42.2 x 8.0 x 25.0
2 x 12 x 19
0.16
Sirocco Fan
28
0.15
9.5 / 8.5 / 7.5
335 / 300 / 265
Direct
BLDC
Microprocessor,
Thermostat for
cooling and heating
Foamed polystrene
Resin Net(washable)
Fuse
6.35(1/4)
12.7(1/2)
12(15/32)
27(59.5)
36 / 34 / 32
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Floor Standing

ARNU12GCEA2
3.6
3,100
12,300
4.0
3,400
13,600
Galvanized
Steel Plate
1,067 x 203 x 635
42.2 x 8.0 x 25.0
2 x 12 x 19
0.16
Sirocco Fan
28
0.15
10.5 / 9.5 / 8.5
371 / 335 / 300
Direct
BLDC
Microprocessor,
Thermostat for
cooling and heating
Foamed polystrene
Resin Net(washable)
Fuse
6.35(1/4)
12.7(1/2)
12(15/32)
27(59.5)
37 / 35 / 33
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specification
Type
Model

Heating Capacity
Casing
Dimensions(WxDxH) Body
Coil

Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H / M / L)

mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control

Sound Absorbing Thermal Insulation Material


Air Filter
Safety Device
Liquid Side
mm(inch)
Pipe Connections Gas Side
mm(inch)
Drain Pipe(Internal Dia.) mm(inch)
Net Weight
kg(lbs)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
Power Supply
Refrigerant Control
Power cable
Transmission cable

, V, Hz
mm2
mm2

ARNU07GCEU2
2.2
1,900
7,500
2.5
2,200
8,500
Galvanized
Steel Plate
978 x 190 x 639
38.5 x 7.5 x 25.2
2 x 12 x 19
0.16
Sirocco Fan
28
0.15
8.5 / 7.5 / 6.5
300 / 265 / 229
Direct
BLDC
Microprocessor,
Thermostat for
cooling and heating
Foamed polystrene
Resin Net(washable)
Fuse
6.35(1/4)
12.7(1/2)
12(15/32)
20(44.1)
35 / 33 / 31
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C

Floor Standing
ARNU09GCEU2
2.8
2,400
9,600
3.2
2,800
10,900
Galvanized
Steel Plate
978 x 190 x 639
38.5 x 7.5 x 25.2
2 x 12 x 19
0.16
Sirocco Fan
28
0.15
9.5 / 8.5 / 7.5
335 / 300 / 265
Direct
BLDC
Microprocessor,
Thermostat for
cooling and heating
Foamed polystrene
Resin Net(washable)
Fuse
6.35(1/4)
12.7(1/2)
12(15/32)
20(44.1)
36 / 34 / 32
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

ARNU12GCEU2
3.6
3,100
12,300
4.0
3,400
13,600
Galvanized
Steel Plate
978 x 190 x 639
38.5 x 7.5 x 25.2
2 x 12 x 19
0.16
Sirocco Fan
28
0.15
10.5 / 9.5 / 8.5
371 / 335 / 300
Direct
BLDC
Microprocessor,
Thermostat for
cooling and heating
Foamed polystrene
Resin Net(washable)
Fuse
6.35(1/4)
12.7(1/2)
12(15/32)
20(44.1)
37 / 35 / 33
1, 220-240, 50
1, 220, 60
EEV
CV1.5 x 3C
CVV-SB 1.25 x 2C

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Floor Standing _ 3

Indoor Units

Cooling Capacity

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

2. Specification

Indoor Units

Type
Model

Floor Standing
ARNU15GCEA2
ARNU18GCFA2
ARNU24GCFA2
4.5
5.6
7.1
Cooling Capacity
3,900
4,800
6,100
15,400
19,100
24,200
5.0
6.3
8.0
Heating Capacity
4,300
5,400
6,900
17,100
21,500
27,300
Casing
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
mm
1,067 x 203 x 635
1,345 x 203 x 635
1,345 x 203 x 635
Dimensions(WxDxH) Body
inch
42.2 x 8.0 x 25.0
52.9 x 8.0 x 25.0
52.9 x 8.0 x 25.0
Rows
x
Columns
x
FPI
2
x
12
x
19
3
x
11
x
19
3 x 11 x 19
Coil
Face Area
m3
0.16
0.23
0.23
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output x Number
W
28
76
76
Running Current
A
0.15
0.38
0.38
Fan
Air Flow Rate(H / M / L)
CMM
11.5 / 10.0 / 9.5
16.0 / 14.0 / 12.0
18.0 / 16.0 / 14.0
cfm
406 / 353 / 335
565 / 494 / 424
635 / 565 / 494
Drive
Direct
Direct
Direct
Motor type
BLDC
BLDC
BLDC
Temperature Control
Microprocessor, Thermostat Microprocessor, Thermostat Microprocessor, Thermostat
for cooling and heating
for cooling and heating
for cooling and heating
Sound Absorbing Thermal Insulation Material
Foamed polystrene
Foamed polystrene
Foamed polystrene
Air Filter
Resin Net(washable)
Resin Net(washable)
Resin Net(washable)
Safety Device
Fuse
Fuse
Fuse
Liquid Side
mm(inch)
6.35(1/4)
6.35(1/4)
9.52(3/8)
Pipe Connections Gas Side
mm(inch)
12.7(1/2)
12.7(1/2)
15.88(5/8)
Drain Pipe(Internal Dia.) mm(inch)
12(15/32)
12(15/32)
12(15/32)
Net Weight
kg(lbs)
27(59.5)
34(75.0)
34(75.0)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
38 / 37 / 35
40 / 37 / 34
43 / 40 / 37
1, 220-240, 50
1, 220-240, 50
1, 220-240, 50
Power Supply
, V, Hz
1, 220, 60
1, 220, 60
1, 220, 60
Refrigerant Control
EEV
EEV
EEV
Power cable
mm2
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
Transmission cable
mm2
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

4 _ Floor Standing

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specification
Type
Model

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Floor Standing _ 5

Indoor Units

Floor Standing
ARNU15GCEU2
ARNU18GCFU2
ARNU24GCFU2
4.5
5.6
7.1
Cooling Capacity
3,900
4,800
6,100
15,400
19,100
24,200
5.0
6.3
8.0
Heating Capacity
4,300
5,400
6,900
17,100
21,500
27,300
Casing
Galvanized Steel Plate
Galvanized Steel Plate
Galvanized Steel Plate
mm
978 x 190 x 639
1,256 x 190 x 639
1,256 x 190 x 639
Dimensions(WxDxH) Body
inch
38.5 x 7.5 x 25.2
49.5 x 7.5 x 25.2
49.5 x 7.5 x 25.2
Rows
x
Columns
x
FPI
2
x
12
x
19
3
x
11
x
19
3 x 11 x 19
Coil
Face Area
m3
0.16
0.23
0.23
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output x Number
W
28
76
76
Running Current
A
0.15
0.38
0.38
Fan
Air Flow Rate(H / M / L)
CMM
11.5 / 10.0 / 9.5
16.0 / 14.0 / 12.0
18.0 / 16.0 / 14.0
cfm
406 / 353 / 335
565 / 494 / 424
635 / 565 / 494
Drive
Direct
Direct
Direct
Motor type
BLDC
BLDC
BLDC
Temperature Control
Microprocessor, Thermostat Microprocessor, Thermostat Microprocessor, Thermostat
for cooling and heating
for cooling and heating
for cooling and heating
Sound Absorbing Thermal Insulation Material
Foamed polystrene
Foamed polystrene
Foamed polystrene
Air Filter
Resin Net(washable)
Resin Net(washable)
Resin Net(washable)
Safety Device
Fuse
Fuse
Fuse
Liquid Side
mm(inch)
6.35(1/4)
6.35(1/4)
9.52(3/8)
Pipe Connections Gas Side
mm(inch)
12.7(1/2)
12.7(1/2)
15.88(5/8)
Drain Pipe(Internal Dia.) mm(inch)
12(15/32)
12(15/32)
12(15/32)
Net Weight
kg(lbs)
20(44.1)
27(59.5)
27(59.5)
Noise Level(Sound Press, 1.5m, H / M / L)
dB(A)
38 / 37 / 35
40 / 37 / 34
43 / 40 / 37
1,
220-240,
50
1,
220-240,
50
1,
220-240, 50
Power Supply
, V, Hz
1, 220, 60
1, 220, 60
1, 220, 60
Refrigerant Control
EEV
EEV
EEV
Power cable
mm2
CV1.5 x 3C
CV1.5 x 3C
CV1.5 x 3C
Transmission cable
mm2
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
CVV-SB 1.25 x 2C
Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

148.3

<Without Case>

978
794

<With Case> 2

1067

1067

13

148.3

635
70
20.4

6 _ Floor Standing
62.8

49

639

190
161

203

14

Air discharge grill


Air suction grill

1
2

639

635

Descripition

(unit : mm)

190

203

(unit : mm)

ARNU07GCEU2
ARNU09GCEU2
ARNU12GCEU2
ARNU15GCEU2

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

CHASSIS CODE: CE

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Name

978

ARNU07GCEU2
ARNU09GCEU2
ARNU12GCEU2
ARNU15GCEU2

Number

1067

ARNU07GCEA2
ARNU09GCEA2
ARNU12GCEA2
ARNU15GCEA2

Model

ARNU07GCEA2
ARNU09GCEA2
ARNU12GCEA2
ARNU15GCEA2

Floor Standing

Indoor Units

3. Dimensions

Floor Standing _ 7

148.3

70

21.4

639

<Without Case>

1256
1098
1072

<With Case>

1048.4

203
635
109.8
30

148.3

70
81.4

1345

190
161

203

14

Air discharge grill


Air suction grill

1
2

639

635

Descripition

(unit : mm)

190

203

(unit : mm)

ARNU18GCFU2
ARNU24GCFU2

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

CHASSIS CODE: CF

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Name

Number

1256

1345

ARNU18GCFA2
ARNU24GCFA2
ARNU18GCFU2
ARNU24GCFU2

Model

ARNU18GCFA2
ARNU24GCFA2

Indoor Units

145

49.4

Floor Standing

3. Dimensions

Indoor Units

4. Piping Diagrams

Heat Exchanger

EEV

Filter

:Cooling
:Heating

Th2

Th3
Sirroco Fan

Th1

Filter

lndoor unit

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

Model
ARNU07GCEA2
ARNU07GCEU2
ARNU09GCEA2
ARNU09GCEU2
ARNU12GCEA2
ARNU12GCEU2
ARNU15GCEA2
ARNU15GCEU2
ARNU18GCFA2
ARNU18GCFU2
ARNU24GCFA2
ARNU24GCFU2

8 _ Floor Standing

Gas

Liquid

12.7(1/2)

6.35(1/4)

12.7(1/2)

6.35(1/4)

12.7(1/2)

6.35(1/4)

12.7(1/2)

6.35(1/4)

12.7(1/2)

6.35(1/4)

15.88(5/8)

9.52(3/8)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

5. Wiring Diagrams
CE/CF Chassis
Indoor Units

CONNECTOR
NUMBER

CN-POWER
CN-MOTOR1
CN-MOTOR2
CN-COMM
CN-EEV
CN-PIPE/IN
CN-PIPE/OUT
CN-ROOM
CN-REMO
CN-OPTION
CN-ZONE
CN-DISPLAY
CN-CC

LOCATION POINT

FUNCTION

AC power supply
Fan motor output
Fan motor output
Communication
Float switch input
Suction pipe sensor
Discharge pipe sensor
Room sensor
Remote controller
Option PCB
Zone controller
RF Remote controller
Dry contact

AC Power line input for indoor controller


Motor output of BLDC
Motor output of BLDC
Communication between indoor and outdoor
EEV Control output
Pipe in thermistor
Pipe out thermistor
Room thermistor
Remote control line
Communication between main and option
Zone control line
RF Remote control line
Dry contact line

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

Floor Standing _ 9

6. Capacity Tables

Indoor Units

6.1 Cooling Capacity

Capacity
Index

2.2

2.8

3.6

Outdoor
air temp.
(DB, C)
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

Notes:
TC: Total Capacity(kW)

10 _ Floor Standing

Cooling capacity

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9

2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
2.3
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
4.0
3.9
3.8
3.7

1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.4
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
1.9
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6

2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7

SHC: Sensible Heat Capacity(kW)

2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.2
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.9
2.9
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.7
3.7

1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.5
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.0
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.6

1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.7
1.6
1.6
1.6
1.5
1.5
1.5
1.5
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.1
2.1
2.1
2.0
2.0
1.9
1.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.8
2.8
2.7
2.7
2.6
2.6
2.5
2.5

32
24
TC SHC
kW kW
2.9
2.9
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
3.7
3.6
3.6
3.5
3.5
3.4
3.4
3.4
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
4.7
4.7
4.6
4.6
4.5
4.4
4.4
4.3
4.3
4.2
4.2
4.1
4.0
4.0
3.9
3.8

1.7
1.6
1.6
1.6
1.6
1.6
1.5
1.5
1.5
1.5
1.5
1.4
1.4
1.4
1.4
1.4
2.2
2.1
2.1
2.1
2.1
2.0
2.0
2.0
2.0
1.9
1.9
1.9
1.9
1.8
1.8
1.8
2.8
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
2.5
2.4
2.4
2.3
2.3

6. Capacity Tables
Cooling capacity

4.5

5.6

7.1

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

30
22
TC SHC
kW
kW

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7
2.7

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2

3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5

3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3

4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4

3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6

5.9
5.8
5.8
5.7
5.6
5.5
5.5
5.4
5.3
5.3
5.2
5.1
5.0
5.0
4.9
4.8

3.6
3.5
3.5
3.4
3.4
3.3
3.3
3.3
3.2
3.2
3.1
3.1
3.0
3.0
2.9
2.9

10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39
10
12
14
16
18
20
21
23
25
27
29
31
33
35
37
39

3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
3.3
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1

4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.5
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7
5.7

3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.6

5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6
6.6

4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1
7.1

4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0

6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
5.8
5.7
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.6
7.4
7.2

4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.2
4.1
4.0
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.2
5.1
5.0

6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.7
6.6
6.4
6.4
6.3
6.2
6.0
5.9
5.8
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.4
8.2
8.1
8.0
7.8
7.7
7.5
7.4

4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.3
4.2
4.1
4.1
4.0
3.9
3.8
3.8
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.4
5.2
5.2
5.1
5.0
4.9
4.8
4.7

7.4
7.3
7.2
7.1
7.0
6.9
6.8
6.7
6.6
6.6
6.5
6.4
6.3
6.2
6.1
6.0
9.3
9.2
9.1
9.0
8.8
8.7
8.7
8.5
8.4
8.3
8.2
8.1
7.9
7.8
7.7
7.6

4.3
4.2
4.2
4.1
4.1
4.0
4.0
3.9
3.9
3.8
3.8
3.7
3.7
3.6
3.6
3.5
5.4
5.3
5.2
5.2
5.1
5.0
5.0
4.9
4.8
4.8
4.7
4.6
4.6
4.5
4.4
4.4

Notes:
TC: Total Capacity(kW)

32
24
TC SHC
kW kW

SHC: Sensible Heat Capacity(kW)

Floor Standing _ 11

Indoor Units

Capacity
Index

20
14
TC SHC
kW kW

Outdoor
air temp.
(DB, C)

6. Capacity Tables

Indoor Units

6.2 Heating Capacity


Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Heating capacity
Indoor air temp. (DB, C)

16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

2.2

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.8
2.8
2.9
2.9
2.9
2.9
2.9

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.3
2.4
2.5
2.6
2.7
2.7
2.7
2.7
2.7
2.7
2.7

1.7
1.7
1.8
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.5
2.5
2.5
2.5

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.2
2.2
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4

1.7
1.7
1.8
1.9
2.0
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2

2.8

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.1
2.2
2.3
2.5
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.6
3.6
3.7
3.7
3.7
3.7
3.7

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.9
3.0
3.2
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.4

2.1
2.2
2.3
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1
3.1

2.1
2.2
2.3
2.4
2.6
2.7
2.8
2.8
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0

2.1
2.2
2.3
2.4
2.6
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8

3.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

2.7
2.8
2.9
3.1
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.4
4.5
4.6
4.6
4.6
4.6
4.6

2.7
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.8
4.0
4.2
4.3
4.3
4.3
4.3
4.3
4.3
4.3

2.7
2.8
2.9
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0

2.6
2.8
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9
3.9

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.5
3.6
3.7
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8
3.8

2.6
2.7
2.9
3.0
3.2
3.4
3.4
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Notes:
TC: Total Capacity
Capacity(kW)

12 _ Floor Standing

6. Capacity Tables
Heating capacity

4.5

5.6

7.1

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

3.4
3.5
3.7
3.9
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.6
5.6
5.8
5.8
5.8
5.8
5.8
4.2
4.3
4.6
4.9
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
7.0
7.1
7.2
7.2
7.2
7.2
7.2
5.4
5.5
5.8
6.2
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.9
9.0
9.2
9.2
9.2
9.2
9.2

3.4
3.5
3.7
3.8
4.1
4.3
4.3
4.4
4.6
4.8
5.0
5.3
5.4
5.4
5.4
5.4
5.4
5.4
5.4
4.2
4.3
4.6
4.8
5.1
5.4
5.4
5.5
5.7
6.0
6.2
6.6
6.7
6.7
6.7
6.7
6.7
6.7
6.7
5.4
5.5
5.8
6.1
6.5
6.8
6.9
7.0
7.3
7.6
7.9
8.4
8.6
8.6
8.6
8.6
8.6
8.6
8.6

3.4
3.5
3.7
3.4
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.6
4.9
5.0
5.0
5.0
5.0
5.0
5.0
4.2
4.3
4.6
4.3
4.5
4.8
4.9
5.0
5.1
5.4
5.5
5.8
6.2
6.3
6.3
6.3
6.3
6.3
6.3
5.4
5.5
5.8
5.5
5.8
6.0
6.2
6.3
6.5
6.8
7.0
7.4
7.8
8.0
8.0
8.0
8.0
8.0
8.0

3.3
3.5
3.7
3.8
4.0
4.3
4.3
4.4
4.4
4.6
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.8
4.2
4.3
4.6
4.8
5.0
5.4
5.4
5.5
5.6
5.8
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
5.3
5.5
5.8
6.1
6.4
6.8
6.9
7.0
7.1
7.4
7.7
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8

3.3
3.4
3.7
3.8
4.0
4.2
4.3
4.4
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.7
4.2
4.3
4.6
4.8
5.0
5.3
5.4
5.5
5.6
5.8
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.9
5.3
5.4
5.8
6.1
6.4
6.7
6.9
7.0
7.1
7.4
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5

3.3
3.4
3.6
3.8
4.0
4.2
4.3
4.3
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.2
4.3
4.5
4.8
5.0
5.3
5.4
5.4
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.3
5.4
5.8
6.1
6.4
6.7
6.8
6.8
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0
7.0

Notes:
TC: Total Capacity(kW)

Floor Standing _ 13

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

7. Air velocity and Temperature Distribution(Reference Data)


ARNU07GCEA2 /ARNU07GCEU2
Cooling

Heating
Discharge angle:60
Air velocity [m/s]
2.7m

22

23

21 22

21

23

24

24
3028

26

2.7m

3 0 32

26
32

20

21

34

Air velocity [m/s]

2248

23
20

22

2m

2m

30

36
38

Indoor Units

Discharge angle:45

26

19
19
36
34

22

18

1m

1m

18

28

23

1156

21

26

22

8m

7m

6m

24

23

23

5m

4m

3m

2m

1m

8m

24

7m

6m

5m

4m

28

26

24

3m

2m

Temperature [C]

Temperature [C]

2.7m

0.5

2.7m

0.5
0.5

2m

1.5

2m
1

5
0.

5
0 .2
1.5
1

5
0.

1
0.5

1m

0.5
2

8m

7m

1m

6m

5m

4m

3m

2m

1m

0
0

141.5

8m

7m

6m

5m

4m

3m

2m

1m

1m

ARNU09GCEA2 /ARNU09GCEU2
Cooling

Heating

Discharge angle:45

Discharge angle:60

Air velocity [m/s]

Air velocity [m/s]


2.7m

19

2826

2826

30

30
34

2.7m

32

22
21
20

22
21

32

21
36

38

30

2m

26

2m
20

18

22

42 4
3
36

20

6m

5m

4m

3m

2m

1m

8m

Temperature [C]

28

26

0
7m

30

28

22

8m

7m

6m

1m

26

8
22 1

1m

17
19 21
16

28

40

22

21

26

5m

4m

3m

0
2m

1m

Temperature [C]
0.5

2.7m

0.5

2.7m

0.5
1

0.5

2m

5
1.

0.5

1.5

2m
1

1m

2.5

1m

7m

6m

5m

14 _ Floor Standing

4m

3m

2m

1m

1.5

3.5

8m

0.5

0.5

0
8m

7m

6m

5m

4m

3m

2m

1m

0
0

7. Air velocity and Temperature Distribution(Reference Data)


ARNU12GCEA2 /ARNU12GCEU2
Cooling

Heating
Discharge angle:60

Air velocity [m/s]

22

38

34

28

36

2m

30

32
34

20

18

21

26

30 28

32

26
26

21

2.7m

19 22

20

28

Air velocity [m/s]


21

22

2.7m
2m

30

21
30
20 5
22 1
21 16

1m

22

22

6m

5m

4m

3m

2m

1m

28

26

0
8m

Temperature [C]

7m

6m

5m

4m

3m

2m

1m

Temperature [C]

0.5

2.7m

0.5

0.5

2.7m

0.5

7m

28

26

0
8m

1m

36
42
32

19

40

17

0.5
1.
5

2m

2m
2
1 .5
0

1m

0.
5

1m

2.5
1.5

0.5

2.5
1.5 .5
1

5
0.

1.5

0
8m

7m

6m

5m

4m

3m

2m

1m

8m

7m

6m

5m

4m

3m

2m

1m

ARNU15GCEA2 /ARNU15GCEU2
Cooling

Heating

Discharge angle:45

Discharge angle:60

Air velocity [m/s]

Air velocity [m/s]


2.7m

21
20

3230

28
30

30

1m
34

28

28

0
5m

4m

3m

2m

1m

32

16

21

6m

2m

34

40

8 15
21 1

18
20

21

7m

2.7m

19

17

38

2m

21

8m

32

3436

20

19

30
28

21

1m

28

8m

Temperature [C]

7m

6m

5m

4m

3m

2m

1m

Temperature [C]
1

2.7m

0.5

2.7m

0.5

0.5
1.0

0.5

2m

1.
5

0.5

0.5
5
0.

2m

1.0

1
2

1.
5

3.
5

1m

2.0

1m

2.

7m

6m

5m

4m

3m

2m

1m

0
0

1.0

11.5
2

8m

0.5

0
8m

7m

6m

5m

4m

3m

2m

1m

Floor Standing _ 15

Indoor Units

Discharge angle:45

7. Air velocity and Temperature Distribution(Reference Data)


ARNU18GCFA2 /ARNU18GCFU2
Heating

Discharge angle:45

Discharge angle:60

Air velocity [m/s]

Air velocity [m/s]


20

2m

22

20

30

32
34
32

30

32

2.7m

34

36

20

2.7m

22

18

30

22

20

2m

38

36

20

38 4 2

22

40

32

16

1m

1m
30

18

30

30

22

22

0
8m

7m

6m

5m

4m

3m

2m

1m

8m

Temperature [C]

7m

6m

5m

4m

3m

2m

1m

Temperature [C]
2.7m

1.0

2.7m

0.5

1.0

0.5

1.0
0.
5

2.0

2m

2m
0
2.
0.5

1.0

1.0

1m

1m
1.0

3.
0

2.

8m

7m

6m

5m

4m

3m

2m

1m

0
8m

7m

6m

5m

4m

3m

2m

1m

ARNU24GCFA2/ARNU24GCFU2
Cooling

Heating

Discharge angle:45

Discharge angle:60

Air velocity [m/s]

Air velocity [m/s]


20

20

30

34

32

30

32

38

2.7m

36

2.7m
18

2m

34

30

2m

36

20

32

32

34

40

20
20

18

32

30

1m
20

7m

6m

5m

4m

3m

2m

1m

1m

30

30

0
8m

0
8m

Temperature [C]

7m

6m

5m

4m

3m

2m

1m

Temperature [C]
2.7m

1.0

0.5

1.0

2.7m

0.5

1.0

0.5
2.
0

2m

2m

0
3.

1m

1.0

1m

2.
0

2.0

3.0

1.0

5
0.

0
1.

1.0

0
2.

0.

2.0

Indoor Units

Cooling

0
8m

7m

6m

5m

16 _ Floor Standing

4m

3m

2m

1m

8m

7m

6m

5m

4m

3m

2m

1m

40

8. Electric Characteristics
Units
Model

Hz

Volts Voltage Range MCA

CE
CE
CE

MAX.264
50

220-240

60

220

MIN.198

CE
CF
CF
CE
CE
CE

MAX.242
MIN.198

CE
CF
CF

0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.55
0.55
0.55
0.55
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.55
0.55
0.55
0.55

IFM

Input(W)

MFA

kW

FLA

15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15

0.028
0.028
0.028
0.028
0.028
0.028
0.028
0.028
0.076
0.076
0.076
0.076
0.028
0.028
0.028
0.028
0.028
0.028
0.028
0.028
0.076
0.076
0.076
0.076

0.17
0.17
0.17
0.17
0.17
0.17
0.17
0.17
0.44
0.44
0.44
0.44
0.17
0.17
0.17
0.17
0.17
0.17
0.17
0.17
0.44
0.44
0.44
0.44

Cooling Heating
30
30
30
30
30
30
30
30
80
80
80
80
30
30
30
30
30
30
30
30
80
80
80
80

30
30
30
30
30
30
30
30
80
80
80
80
30
30
30
30
30
30
30
30
80
80
80
80

Symbols:
MCA: Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the MCA.
5. Instead of fuse, use Circuit Breaker.

Floor Standing _ 17

Indoor Units

ARNU07GCEA2
ARNU07GCEU2
ARNU09GCEA2
ARNU09GCEU2
ARNU12GCEA2
ARNU12GCEU2
ARNU15GCEA2
ARNU15GCEU2
ARNU18GCFA2
ARNU18GCFU2
ARNU24GCFA2
ARNU24GCFU2
ARNU07GCEA2
ARNU07GCEU2
ARNU09GCEA2
ARNU09GCEU2
ARNU12GCEA2
ARNU12GCEU2
ARNU15GCEA2
ARNU15GCEU2
ARNU18GCFA2
ARNU18GCFU2
ARNU24GCFA2
ARNU24GCFU2

Type

Power Supply

9. Sound Levels
Overall
Notes:
- Sound measured at 1.5m away from
the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operating condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

Microphone

Indoor Units

With Case

1.5m

Du

1.5m
Model
ARNU07GCEA2
ARNU09GCEA2
ARNU12GCEA2
ARNU15GCEA2
ARNU18GCFA2
ARNU24GCFA2

ARNU07GCEU2
ARNU09GCEU2
ARNU12GCEU2
ARNU15GCEU2
ARNU18GCFU2
ARNU24GCFU2

(Fie

Sound Levels dB(A)


H
L
M
35
33
31
36
34
32
37
35
33
38
37
35
40
37
34
43
40
37

Sound Pressure Level


ARNU07GCEA2
ARNU07GCEU2

ARNU09GCEA2
ARNU09GCEU2
70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

20

10

NC-25
Approximate
Hearing
Threshold
63

250

500

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

NC-20

125

NC-15
1000 2000 4000 8000

10

63

NC-60

250

500

NC-50

NC-40

NC-30

NC-15
1000 2000 4000 8000

10

NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30

10

NC-25

63

NC-60

125

250

500

Octave Band Center Frequency (Hz)

18 _ Floor Standing

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

NC-20
NC-15
1000 2000 4000 8000

NC-65

60

10

NC-25
Approximate
Hearing
Threshold
63

Octave Band Sound Pressure Level (dB re 20Pa )

70

Octave Band Sound Pressure Level (dB re 20Pa )

70

Approximate
Hearing
Threshold

125

250

500

1000

2000

4000

500

1000 2000

NC-15
4000 8000

NC-15
8000

Octave Band Center Frequency (Hz)

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

NC-20

125

250

ARNU24GCFA2
ARNU24GCFU2

ARNU18GCFA2
ARNU18GCFU2

70

20

NC-20

Octave Band Center Frequency (Hz)

80

30

NC-25
Approximate
Hearing
Threshold
63

80

40

NC-35

30

80

50

NC-45

40

Octave Band Center Frequency (Hz)

ARNU15GCEA2
ARNU15GCEU2

60

NC-55

50

NC-20

125

NC-65

60

20

NC-25
Approximate
Hearing
Threshold

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20Pa )

80

Octave Band Sound Pressure Level (dB re 20Pa )

70

Octave Band Sound Pressure Level (dB re 20Pa )

80

Octave Band Sound Pressure Level (dB re 20Pa )

80

ARNU12GCEA2
ARNU12GCEU2

10

NC-25
Approximate
Hearing
Threshold
63

NC-20

125

250

500

1000

2000

4000

NC-15
8000

Octave Band Center Frequency (Hz)

10. Installation
Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

Indoor Units

10.1 Features

[CEA/CFA Type]

Control panel

Air Outlet
Remote Controller
Control panel
TEMP

Remote Controller

Air Filter
Air Inlet

[CEU/CFU Type]

Air Inlet
Air filter
(At Air Inlet)

Floor Standing _ 19

10. Installation
10.2 Selection of the best location
Install the air conditioner in the location that satisfies the following conditions.
The place shall easily bear a load exceeding four times the
indoor units weight.
Sufficient space should be available to inspect the unit as in
the figure shown on the right.

Window

The place where the unit is installed shall be leveled.


The place shall be suitable for easy connection of the indoor
unit with the outdoor unit.
The place where the unit is installed should not be affected
by electrical noise.
The place where air circulation in the room will be good .
There should not be any heat source or steam near the unit

Service space
Select an installation site where the following conditions are
satisfied and that meets your customer's approval.
Where the floor is strong enough to bear the indoor unit
weight.
Where the floor is not significantly inclined.
Where nothing blocks the air passage.

20 or
more

Air flow
direction
Front side

100 or
more

175 or
more

100 or
more

1000 or
more

Air inlet
direction

Where condensate can be properly drained.


Base

Where sufficient clearance for installation and maintenance


can be ensured.
Where there is no possibility of flammable gas leakage.
Where optimum air distribution can be ensured.
Where piping between indoor and outdoor units is possible
within the allowable limit (Refer to the installation manual of
the outdoor unit.)
80 or more

Keep the indoor and outdoor unit, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static.(Depending on the type and source
of the electrical waves, static may be heard even when more
than 1 m away.)

Window

654

Indoor Units

Indoor unit

Ma

Ao

(Unit: mm)
Type

CEU Type

788

1080

CFU Type

1066

1358

20 _ Floor Standing

inte

[IMPORTANT]
Leave sufficient clearance
for air inlet and maintenance.

nan

ce

are

rm
ore
Bo
rm
ore

10. Installation
Bolt pitch
A

Indoor Units

Positioning of holes for fastening to the wall

CEA, CEU
CFA, CFU

858
1136

1. Use the,QVWDOODWLRQPRXQW for installation. Check


whether the wall is strong enough to bear the
weight of the unit or not. if there is a risk, reinforce
the wall before installing the unit.
2. The unit requires a minimum 100 mm clearance
below the unit for air intake. Also, ensure the unit is
leveled when installed so that drainage flows
smoothly. If inclined, water can leak.
3. Depending upon the shape and nature of the wall
surface, operating sound may become bigger.

270

Type

198

(Unit:mm)

How to open/close front panel

(1)

How to open/close the front panel

(2)

(1) Open the lid of control panel(Both left and right)


(2) Remove screws(Both left and right)
(3) Lift the front panel of the unit
To close, perform the procedure in opposite
order.

(3)

(2)

(1)

Floor Standing _ 21

10. Installation

Indoor Units

10.3 Drain piping work


Drain piping must have downward slope(1/50 to 1/100): be sure not to provide up-and-down slope to prevent
reverse flow.
During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.
The outside diameter of the drain connection to the indoor unit is 21mm.
Piping material: Polyvinyl chloride pipe 25mm and
pipe fittings
Be sure to install heat insulation on the drain piping
Heat insulation material: Polyethylene foam with
thickness more than 10 mm.
If converging multiple drain pipes, install according to the procedure shown below.

Slope downwards at a gradient


of at least 1/100
After piping work is finished, check for drainage.
Be sure to insulate all indoor units.

10.4 How to connect wirings


Remove the electric parts Box cover and connect the wiring

Fasten with clamp

Fasten with
accessory clamp

Power Supply wiring


ground wiring
(Field wiring)

22 _ Floor Standing

Power supply wiring


ground wiring
Transmission wiring
(Field wiring)

Transmission wiring

10. Installation
10.5 Wiring Connection

Terminal Block Indoor


1(L)

2(N)

SODU

INTERNET DRY1 DRY2 GND 12V

IDU
-

Outdoor
Unit

INDOOR POWER INPUT

WARNING : Make sure that the screws of the terminal are free from looseness.
CAUTION:
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have a separate power circuit specifically for the air conditioner. As for the method of
wiring, follow the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked on
the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.)
7) In a wet or moist area, always install an earth leakage circuit breaker.
8) The following would be caused by voltage drop.
Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the normal function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and
have an air gap contact separation of at least 3mm in each active(phase) conductor.

Floor Standing _ 23

Indoor Units

Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

10. Installations

Indoor Units

WIRED REMOTE CONTROLLER INSTALLATION


Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place
away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller
LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller
Remote

TEMP

Remote Controller

5feet
(1.5meters)

no

no

Fig.1 Typical locations for remote controller

24 _ Floor Standing

11. Accessories
Standard Accessories
Dran
hose

Level adjustment
screw

Insulation for
fitting

Clamp
(Tie Wrap)

Quantity

1 EA

1 each.

8 pcs.

(1) For gas pipe


Shape

[Other]

Operation
manual
Installation
manual

(2) For liquid pipe

CAUTION
Use only those accessories (Standard or optional) which have designated specifications.

Floor Standing _ 25

Indoor Units

Name

Indoor unit
Console
1. List of functions
2. Specifications
3. Dimensions
4. Piping Diagrams
5. Wiring Diagrams
6. Capacity Tables
7. Air Velocity and Temperature Distribution
8. Electric Characteristics
9. Sound Levels
10. Installation
11. Accessories

1. List of functions
Category

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Air supply outlet


Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Ion Generator
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Wide wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU07GQAA2, ARNU09GQAA2, ARNU12GQAA2


ARNU15GQAA2

Indoor Units

Air flow

Function

2
Manual
Auto
X
O
4/5/4
X
O
O
X
X
O
O
X
X
X
X
O
O
O
O
X
O
O
O
O
O
O
O
O
O
Accessory
X
X
X
X
Accessory
X
X
X

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

Console _ 1

2. Specification
Type
Model

Indoor Units

Cooling Capacity

Heating Capacity

Casing
Dimensions
(W x D x H)

Body
Front Panel

Coil
Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H/M/L)

Console
Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h
mm
inch
mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control

Sound Absorbing Thermal Insulation Material


Safety Device
Pipe
Liquid Side
mm(inch)
Connections
Gas Side
mm(inch)
Drain(OD/ID)
mm
Net Weight
Body
kg(lbs)
Noise Level(Sound Press, 1.5m, H/M/L)
dB(A)
Power Supply
, V, Hz
Refrigerant Control
Power cable
mm2(CV)
Transmission Cable
mm2(VCTF-SB)

ARNU07GQAA2
2.2
1,900
7,500
2.5
2,200
8,500
Galvanized Steel Plate
600 x 700 x 210
23.62 x 27.56 x 8.27
19 x 2 x 19
Turbo fan
48 x 1
0.3
6.7 / 5.9 / 4.8
236 / 209 / 170
Direct
BLDC
Microprocessor,
Thermostat for
cooling and heating
Foamed polystrene
Fuse
6.35(1/4)
12.7(1/2)
17/12.2
14.0(30.9)
37 / 34 / 28
1, 220 - 240, 50
EEV
1.5 x 3C
1.0 ~ 1.5 x 2C

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

2 _ Console

ARNU09GQAA2
2.8
2,400
9,600
3.2
2,800
10,900
Galvanized Steel Plate
600 x 700 x 210
23.62 x 27.56 x 8.27
19 x 2 x 19
Turbo fan
48 x 1
0.3
6.7 / 5.9 / 4.8
236 / 209 / 170
Direct
BLDC
Microprocessor,
Thermostat for
cooling and heating
Foamed polystrene
Fuse
6.35(1/4)
12.7(1/2)
17/12.2
14.0(30.9)
37 / 34 / 28
1, 220 - 240, 50
EEV
1.5 x 3C
1.0 ~ 1.5 x 2C
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

2. Specification
Type
Model
Cooling Capacity

Casing
Dimensions
(W x D x H)

Body
Front Panel

Coil
Fan

Rows x Columns x FPI


Face Area
Type
Motor Output x Number
Running Current
Air Flow Rate(H/M/L)

mm
inch
mm
inch
m3
W
A
CMM
cfm

Drive
Motor type
Temperature Control

Sound Absorbing Thermal Insulation Material


Safety Device
Pipe
Liquid Side
mm(inch)
Connections
Gas Side
mm(inch)
Drain(OD/ID)
mm
Net Weight
Body
kg(lbs)
Noise Level(Sound Press, 1.5m, H/M/L)
dB(A)
Power Supply
, V, Hz
Refrigerant Control
Power cable
mm2(CV)
Transmission Cable
mm2(VCTF-SB)

ARNU12GQAA2
3.6
3,100
12,300
4.0
3,400
13,600
Galvanized Steel Plate
600 x 700 x 210
23.62 x 27.56 x 8.27
19 x 2 x 19
Turbo fan
48 x 1
0.3
7.5 / 5.9 / 4.8
265 / 209 / 170
Direct
BLDC
Microprocessor,
Thermostat for
cooling and heating
Foamed polystrene
Fuse
6.35(1/4)
12.7(1/2)
17/12.2
14.0(30.9)
39 / 34 / 28
1, 220 - 240, 50
EEV
1.5 x 3C
1.0 ~ 1.5 x 2C

Notes:1. Capacities are based on the following conditions:


Cooling Indoor temp. 27C[80.6F]DB/ 19C[66.2F]WB
Outdoor temp. 35C[95F]DB/ 24C[75.2F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating Indoor temp. 20C[68F]DB/ 15C[59F]WB
Outdoor temp. 7C[44.6F]DB/ 6C[42.8F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. EEV : Electronic Expansion Valve
6. Anechoic chamber conversion value is measured at 1.5 m downward from unit centre.
The values depends on the ambient conditions and values are normally higher in actual operation.

ARNU15GQAA2
4.5
3,900
15,400
5.0
4,300
17,100
Galvanized Steel Plate
600 x 700 x 210
23.62 x 27.56 x 8.37
19 x 2 x 19
Turbo fan
48 x 1
0.3
8.7 / 6.7 / 5.9
307 / 236 / 209
Direct
BLDC
Microprocessor,
Thermostat for
cooling and heating
Foamed polystrene
Fuse
6.35(1/4)
12.7(1/2)
17/12.2
14.0(30.9)
42 / 37 / 31
1, 220 - 240, 50
EEV
1.5 x 3C
1.0 ~ 1.5 x 2C
Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Console _ 3

Indoor Units

Heating Capacity

Console
Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

82.5

18

95

160

4 _ Console
600
80
37
100

639

700

666

68.5
37

150

140
120

45

210

80

90

125

584

No.
1
2
3
4
5
6
Gas pipe connection
Drain pipe connection
Display & signal receiver
Air discharge grill
Air suction grill

Part Name
Liquid pipe connection

CHASSIS CODE: QA

Remark
6.35
12.7

ARNU07GQAA2
ARNU09GQAA2
ARNU12GQAA2
ARNU15GQAA2

Console

Indoor Units

3. Dimensions

4. Piping Diagrams
:Cooling
:Heating

EEV
Filter

Th3

Th2
Turbo Fan

Filter

lndoor unit

Th1

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

Model

Gas

Liquid

ARNU07GQAA2

12.7(1/2)

6.35(1/4)

ARNU09GQAA2

12.7(1/2)

6.35(1/4)

ARNU12GQAA2

12.7(1/2)

6.35(1/4)

ARNU15GQAA2

12.7(1/2)

6.35(1/4)

LOC.

Description

Th1

Room thermistor

Th2

Pipe in thermistor

Th3

Pipe out thermistor

Console _ 5

Indoor Units

Heat Exchanger

5. Wiring Diagrams

Indoor Units

QA Chassis

CONNECTOR NUMBER
CN-POWER
CN-MOTOR1
CN-D/PUMP
CN-485
CN-DISP
CN-EEV
CN-VANE2
CN-FLOAT
CN-PIPE/IN
CN-PIPE/OUT
CN-ROOM
CN-REMO
CN-CC
CN-AIRC

LOCATION POINT
AC Power supply
Fan motor output
Drain pump output
Communication
Display
EEV Output
Step motor
Float switch input
Suction pipe sensor
Discharge pipe sensor
Room sensor
Remote controller
Dry contact
Air clean

Dip Switch Setting


SW3
GROUP

Off
Master

On
Slave

SW4

DRY CONTACT

Variable

Auto

SW5

EXTRA 1

Off

On

FUNCTION
AC Power line input for indoor controller
Motor output of BLDC
AC output for drain pump
Connection between indoor and outdoor
Display of indoor status
EEV Control output
Step motor output
Float switch sensing
Pipe in thermistor
Pipe out thermistor
Room air thermistor
Remote control line
Dry contact line
Air cleaner control
Remarks
Group Control setting using Wired Remote Controller
Old Dry Contact Mode Setting
1. Variable : Auto/Manual Mode can be chosen by Wide wired
remote controller or Wireless remote controller
(When shipped from Factory Manual Mode)
2. Auto : For Dry Contact, it is always Auto mode.
1. Duct model
-. OFF : Default(not operate continuosly )
-. ON : Fan operate continuosly
2. Cassette Model : No Function
3. Ceiling Suspended Model
-. OFF : Ceiling(default)
-. ON : Floor

CAUTION
For Multi V Model, Dip Switch 1,2,6,7,8 must be set OFF
That dip switch is used for the other model.

6 _ Console

6. Capacity Tables
6.1 Cooling Capacity

2.2

2.8

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

10

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.8

1.6

12

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.8

1.6

14

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.8

1.6

16

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.7

1.6

18

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.7

1.6

20

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.7

1.6

21

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.6

1.5

2.7

1.6

23

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.5

1.5

2.6

1.5

25

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.5

1.5

2.6

1.5

27

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.5

1.5

2.6

1.5

29

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.5

1.4

2.5

1.5

31

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.4

2.5

1.4

33

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.4

2.4

1.4

35

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.3

1.6

2.4

1.4

2.4

1.4

37

1.5

1.3

1.8

1.4

2.1

1.6

2.2

1.6

2.2

1.6

2.3

1.4

2.4

1.4

39

1.5

1.3

1.8

1.4

2.1

1.6

2.1

1.5

2.2

1.5

2.3

1.3

2.3

1.4

42

1.5

1.3

1.8

1.4

2.1

1.6

2.1

1.5

2.2

1.5

2.2

1.3

2.3

1.3

44

1.5

1.3

1.8

1.4

2.0

1.5

2.1

1.5

2.1

1.5

2.2

1.3

2.2

1.3

46

1.5

1.3

1.8

1.4

1.9

1.5

2.0

1.4

2.0

1.4

2.0

1.2

2.0

1.2

10

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.6

2.1

12

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.6

2.0

14

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.5

2.0

16

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.5

2.0

18

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.5

2.0

20

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.4

2.0

21

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.3

1.9

3.4

2.0

23

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.2

1.9

3.3

1.9

25

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.2

1.8

3.3

1.9

27

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.2

1.8

3.3

1.9

29

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

3.0

2.0

3.1

1.8

3.2

1.8

31

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

2.9

2.0

3.1

1.8

3.2

1.8

33

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

2.9

2.0

3.0

1.8

3.1

1.8

35

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

2.9

2.0

3.0

1.7

3.1

1.8

37

1.9

1.6

2.3

1.8

2.6

2.0

2.8

2.0

2.8

2.0

2.9

1.7

3.0

1.7

39

1.9

1.6

2.3

1.8

2.6

2.0

2.7

1.9

2.8

1.9

2.9

1.7

3.0

1.7

42

1.9

1.6

2.3

1.8

2.6

2.0

2.7

1.9

2.8

1.9

2.8

1.6

2.9

1.7

44

1.9

1.6

2.3

1.8

2.6

1.9

2.7

1.9

2.7

1.9

2.8

1.6

2.9

1.6

46

1.9

1.6

2.3

1.8

2.5

1.8

2.5

1.8

2.5

1.7

2.6

1.5

2.6

1.5

Outdoor
air temp.
(DB, C)

Notes:
TC: Total Capacity(kW)

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

SHC: Sensible Heat Capacity(kW)

Console _ 7

Indoor Units

Capacity
Index

Cooling capacity

6. Capacity Tables

Indoor Units

Cooling capacity

Capacity
Index

3.6

4.5

20
14
TC SHC
kW kW

23
16
TC SHC
kW kW

Indoor air temp. (DB/WB, C)


26
27
28
18
19
20
TC SHC TC SHC TC SHC
kW
kW
kW kW
kW kW

10

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.3

2.5

4.6

2.7

12

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.3

2.5

4.6

2.7

14

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.3

2.5

4.5

2.6

16

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.3

2.5

4.5

2.6

18

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.3

2.5

4.4

2.6

20

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.2

2.5

4.4

2.6

21

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.2

2.4

4.4

2.5

23

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.1

2.4

4.3

2.5

25

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.1

2.4

4.2

2.5

27

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.1

2.4

4.2

2.4

29

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.7

4.0

2.3

4.1

2.4

31

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.8

2.6

4.0

2.3

4.1

2.4

33

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.7

2.6

3.9

2.3

4.0

2.3

35

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.7

2.6

3.9

2.2

3.9

2.3

37

2.4

2.1

2.9

2.4

3.4

2.6

3.6

2.6

3.7

2.5

3.8

2.2

3.9

2.3

39

2.4

2.1

2.9

2.4

3.4

2.6

3.5

2.5

3.6

2.5

3.7

2.2

3.8

2.2

42

2.4

2.1

2.9

2.4

3.4

2.5

3.5

2.5

3.5

2.5

3.6

2.1

3.7

2.2

44

2.4

2.1

2.9

2.4

3.3

2.5

3.4

2.5

3.5

2.4

3.6

2.1

3.7

2.1

46

2.4

2.1

2.9

2.4

3.2

2.4

3.2

2.3

3.3

2.3

3.3

1.9

3.3

1.9

10

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.4

3.1

5.8

3.4

12

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.4

3.1

5.7

3.3

14

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.4

3.1

5.7

3.3

16

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.4

3.1

5.6

3.3

18

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.3

3.1

5.6

3.2

20

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.3

3.1

5.5

3.2

21

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.2

3.1

5.5

3.2

23

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.2

3.0

5.4

3.1

25

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.1

3.0

5.3

3.1

27

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.1

3.0

5.2

3.1

29

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.8

3.3

5.0

2.9

5.2

3.0

31

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.7

3.3

5.0

2.9

5.1

3.0

33

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.7

3.3

4.9

2.9

5.0

2.9

35

3.0

2.7

3.6

2.9

4.2

3.2

4.5

3.2

4.6

3.2

4.8

2.8

4.9

2.9

37

3.0

2.7

3.6

2.9

4.2

3.2

4.4

3.2

4.6

3.2

4.7

2.8

4.8

2.8

39

3.0

2.7

3.6

2.9

4.2

3.2

4.4

3.2

4.5

3.1

4.7

2.7

4.8

2.8

42

3.0

2.7

3.6

2.9

4.2

3.2

4.3

3.1

4.4

3.1

4.5

2.7

4.7

2.7

44

3.0

2.7

3.6

2.9

4.1

3.1

4.3

3.1

4.4

3.0

4.5

2.6

4.6

2.7

46

3.0

2.7

3.6

2.9

4.0

3.0

4.0

2.9

4.1

2.8

4.1

2.4

4.2

2.4

Outdoor
air temp.
(DB, C)

Notes:
TC: Total Capacity(kW)

8 _ Console

SHC: Sensible Heat Capacity(kW)

30
22
TC SHC
kW
kW

32
24
TC SHC
kW kW

6. Capacity Tables
6.2 Heating Capacity

2.2

2.8

3.6

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0
-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7
-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.8
2.8
2.8
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.5
3.6
3.6
3.6
2.4
2.5
2.6
2.8
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.5
4.5
4.5

1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.5
2.5
2.6
2.7
2.7
2.7
2.7
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.3
3.4
3.4
3.4
3.4
3.4
2.4
2.5
2.6
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.1
4.2
4.3
4.3
4.3
4.3

1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.5
2.5
2.5
2.5
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.2
3.2
3.2
3.2
3.2
3.2
2.4
2.5
2.6
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
4.0
4.0
4.0
4.0
4.0
4.0

1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.1
3.1
3.1
3.1
3.1
3.1
3.1
2.4
2.5
2.6
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.9
3.9
3.9
3.9
3.9
3.9
3.9

1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.3
2.3
2.3
2.3
2.3
2.3
2.3
2.3
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.4
2.5
2.6
2.7
2.9
3.0
3.1
3.2
3.3
3.4
3.5
3.7
3.7
3.7
3.7
3.7
3.7
3.7
3.7

1.5
1.5
1.6
1.7
1.8
1.9
1.9
2.0
2.0
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.7
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.4
2.4
2.6
2.7
2.9
3.0
3.1
3.1
3.3
3.4
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5
3.5

Notes:
TC: Total Capacity(kW)

Console _ 9

Indoor Units

Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

Heating capacity

6. Capacity Tables

Indoor Units

Heating capacity
Outdoor air
temp.
Capacity
Index
DB(C) WB(C)

4.5

-19.8
-18.8
-16.7
-14.7
-12.6
-10.5
-9.5
-8.5
-7.0
-5.0
-3.0
0.0
3.0
5.0
7.0
9.0
11.0
13.0
15.0

-20.0
-19.0
-17.0
-15.0
-13.0
-11.0
-10.0
-9.1
-7.6
-5.6
-3.7
-0.7
2.2
4.1
6.0
7.9
9.8
11.8
13.7

Notes:
TC: Total Capacity(kW)

10 _ Console

Indoor air temp. (DB, C)


16.0

18.0

20.0

21.0

22.0

24.0

TC

TC

TC

TC

TC

TC

kW

kW

kW

kW

kW

kW

3.0
3.1
3.3
3.4
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.7
4.9
5.1
5.3
5.4
5.6
5.6
5.6

3.0
3.1
3.3
3.4
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.7
4.9
5.1
5.2
5.3
5.3
5.3
5.3

3.0
3.1
3.3
3.4
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.6
4.9
5.0
5.0
5.0
5.0
5.0
5.0

3.0
3.1
3.2
3.4
3.6
3.8
3.9
3.9
4.1
4.3
4.4
4.6
4.8
4.8
4.8
4.8
4.8
4.8
4.8

3.0
3.1
3.2
3.4
3.6
3.8
3.9
3.9
4.1
4.2
4.4
4.6
4.7
4.7
4.7
4.7
4.7
4.7
4.7

3.0
3.1
3.2
3.4
3.6
3.8
3.8
3.9
4.1
4.2
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4
4.4

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU07GQAA2
Cooling

Heating
Discharge angle:50

Air velocity [m/s]

2.7m

Air velocity [m/s]

0.3

0.5

2
0.

0.4

2.7m

0.2

1.0

0.2

0.4

0.1

0.5

0.3

1.0

0.2

0.1

2m
0.3

0.4

2m
0.2

1.0

0.1

0.1

0.3

0.
3

0.5
0.2
0.2 1.0

0.1

1m

5m

0.2

0.3

4m

3m

2m

0.2

0.2

0.2

0.3

0.4

0.2

0.2

0.5

1.5

0.2

1m

Temperature [C]

5m

2.7m

0.2
0.5

0.

0.1

0.2

0.1

0.3

0.1

1m

1.0

0.1

0.4

0.2

1.5

4m

3m

2m

2.0

0.2

1m

Temperature [C]

2.7m

36.7

36.6

36.7

.7

13.4

36

13.4

13.8

13.4

2m

2m
13.4

36.7
36.6
36.7

13.8

36.6

13.8

36

.6

36.6

12.2

13

36.7

11.5

13.9

13.8

13.8

36

.4

.7

36

.6

13
.8
11.3

4m

3m

2m

39.0

0
5m

1m

36.7

.6

5m

13.4

.8

36

13

13.4

1m

39.0
39.0 6.6 36.6
3

.8

36.6

36.6

1m
13

13.9

4m

3m

2m

1m

ARNU09GQAA2
Cooling

Heating

Discharge angle:40

Discharge angle:50

Air velocity [m/s]


0.3

2.7m

Air velocity [m/s]

2.7m

0.3

0.2

0.3

0.
2

0.3

0.2

0.5
0.5

0.3

0.3

0.2

03
0.3

0.2

0.3

0.2

2
0.

0.3

2.5

0.3

0.2

0.2

0.5

1m

2
0.
0.2

5m

4m

1.5

0.3

0.2

3m

2m

0.2

1m

.5
14

0.3

02

5m

2.7m

13.5

13.5

0.2

Temperature [C]
13.9

0.2

0.
2

0.2

0.
2

0.3

0.2

0.2

0.2

0.2

0.2

0.2

4m

3m

2m

0.5

1m

.2

39.2

2.7m

39.9

40.6

40.6

13.5

13.9

0
0

Temperature [C]
39

1m

0.2
0.2

0.2

0.3

2
0.

2
0.

0.3

0.2

0.2

0.2

2m

0.2

0.3

0.2

0.3

0.3

2m

0.5

0.3

0.2

0.3

0.2

0.2

40.6

2m

0.0

39.2
40.6

39.9

13.9

40.0

14.5

2m
14.5

39.9
13.9

14

13

.0

12.0

4m

3m

2m

1m

39.9

13.9

13.9

13.5

.5
13.5

40

40.6

40.0

.6

39.2

0
0

5m

4m

1m

39.9
43.0

9
9.

3m

.9

40

13

5m

39.9

39

14.5

43.0

1m

13.912.0

.9

.5

13.9

12.0

13.9

2m

43.0

1m

40.0

0
0

Console _ 11

Indoor Units

Discharge angle:40

7. Air Velocity and Temperature Distribution(Reference Data)


ARNU12GQAA2
Cooling

Heating
Discharge angle:50

Air velocity [m/s]


0.2

2.7m

0.5

Air velocity [m/s]

0.
2

2.7m
0.4

2
0.

0.4

0.5

0.5

0.4

0.4

0.5

0.2

0.2

0.3

2m

0.4

0.4

0.2

0.4

0.5

0.2

2m
0.2

0.2
0.2

0.3

0.5

0.5

0.2

0.2

0.2

1.3
0.3

2.2

0.
2

0.2

4m

3m

2m

1m

12.1

5m

2.7m

4m

3m

2m

0.2

0.2

0.2

0.4

0
0

0.4

Temperature [C]
42.6

42.5

2.7m

43.3

13

42.5

42.5

43.3

13.5

13.5

13

42

.8

2m

42.8

42

42.5

.8

.5

43.3

2m
13.6

42.5

13

43.3

13.5

42.5

1m

11.5

42.6

46.3

1m

46.3

42.5

.6

.5
13

.5

43.3

13.5

13.6

4m

3m

2m

42.5

43.3

.6

.5

13

13

5m

11.5

13

13

13.5

42.6

.5

11.5

13.6

1m

.5

13.5

13.6

0.2
0.2
0.4

1.3

Temperature [C]
13.6

0.2

0.2

0.2
0.2

0.2

5m

0.2

0.2

0.2

0.5

1m

0.4

0.2

2
0.

2
0.

0.2

1m

0.3
0.5

0.4

0.2

0.3

0.2

0.2

0.3

42.5

0
5m

1m

42.8

4m

3m

2m

43

.3

1m

ARNU15GQAA2
Cooling

Heating
Discharge angle:50

Air velocity [m/s]

2.7m

0.2

0.4

Air velocity [m/s]


0.2

0.3

0.
2
0.3

0.4

0.2

0.2

0.6

2.7m

1.0

0.4

0.4

1.0

Discharge angle:40

0.6

0.2

0.2

0.2

0.3

0.2

3.6
0.3

0.3

0.3

0.3

2m

1m

2.7m

3m

2m

0.2

0.6

03

1m

Temperature [C]
41.0

41.0

2.7m

14.3

40

.8

41.0

.0

14.1

4m

0.2

0.6

41

14.3

14.1

5m

0.2

0.3

0.3

0.6

Temperature [C]
14.3

0.3 2
0.

2
0.

3m

0.3

1.9

2
0.

4m

1m

0.3

0.3

0.2 0
0.2 .2
0.2 1.9

1.0

1.0

1.9

0.2

0.2

0.6

0.2

0.4

0.3
0.2

1m

0.4

0.4

5m

0.6

0.3

1.0

0.2

0.2

2m

0.3

0.4

0.2

0.3

0.4

0.4

1.0

0.2
0.2

0.6

0.2

2m
0.4

41.0

41.0

2m

2m

14.1

41.0

14.1

14.3

.8

1m

41

.1
14

12 _ Console

3m

2m

1m

40.9

14.3

12.4

40

.8

.8

4m

40.8

41.0

40

5m

40.8 43.8

14.3

14.1

1m

41.0

40.8
41.0

.0

14.3

40.8

12.4
.3
14

14.2

40

.0

.8

41
40.9

12.4

43

14.3

.9

14.2

.2

.3

41.0

14
14

40

.1

14.1

14

14.3

Indoor Units

Discharge angle:40

41.0

0
5m

4m

3m

2m

1m

8. Electric Characteristicss
Units
Model

Type
QA

ARNU09GQAA2

QA

Hz

50

Volts

220-240

Voltage Range MCA

IFM

Input(W)

MFA

kW

FLA

Cooling Heating

0.13

15

0.048

0.10

30

30

Min.:198,

0.13

15

0.048

0.10

30

30

Max.:264

0.13

15

0.048

0.10

30

30

ARNU12GQAA2

QA

ARNU15GQAA2

QA

0.13

15

0.048

0.10

30

30

ARNU07GQAA2

QA

0.13

15

0.048

0.10

30

30

ARNU09GQAA2

QA

Min.:198,

0.13

15

0.048

0.10

30

30

ARNU12GQAA2

QA

Max.:264

0.13

15

0.048

0.10

30

30

ARNU15GQAA2

QA

0.13

15

0.048

0.10

30

30

60

220

Symbols:
MCA : Minimum Circuit Amperes (A)
MFA : Maximum Fuse Amperes(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amperes(A)
IFM : Indoor Fan Motor
Note :
1. Voltage Range
Units are suitable for use on electrical system where voltage supplied to unit terminals is not below or above the
listed range limits.
2. Maximum allowable voltage unbalance between phase is 2%.
3. MCA/MFA
MCA = 1.25 x FLA
MFA 4 x FLA
( Next lower standard fuse rating. Minimum 15A)
4. Select wire size based on the larger value on the MCA.
5. Instead of fuse, use Circuit Breaker.

Console _ 13

Indoor Units

ARNU07GQAA2

Power Supply

9. Sound Levels

Notes:
- Data is valid at nominal operation condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The operating conditions are assumed to be standard.

1m
1m

Microphone

Sound Pressure Level


Sound Levels dB(A)

Model
H

ARNU07GQAA2

37

34

28

ARNU09GQAA2

37

34

28

ARNU12GQAA2

39

34

28

ARNU15GQAA2

42

37

31

ARNU09GQAA2

ARNU12GQAA2

80

80

70

70

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30

10

Approximate
Hearing
Threshold

63

NC-60
50

NC-50

250

500

1000

2000

4000

NC-45

40

NC-40
NC-35

30

NC-30

NC-20

125

NC-55

NC-25

20

NC-25

20

NC-65

60

NC-15
8000

10

Approximate
Hearing
Threshold
63

125

250

500

1000

2000

4000

NC-15
8000

70

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

10

Approximate
Hearing
Threshold
63

125

250

500

1000

2000

4000

NC-15
8000

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

NC-20

Octave Band Center Frequency (Hz)

14 _ Console

Octave Band Sound Pressure Level (dB re 20Pa )

80

10

Approximate
Hearing
Threshold
63

NC-60

NC-20

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

10

Approximate
Hearing
Threshold
63

NC-20

125

250

500

1000

2000

4000

Octave Band Center Frequency (Hz)

ARNU15GQAA2
80

NC-65

60

NC-20

Octave Band Center Frequency (Hz)

Octave Band Center Frequency (Hz)

Octave Band Sound Pressure Level (dB re 20Pa )

80

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU07GQAA2

Octave Band Sound Pressure Level (dB re 20Pa )

Indoor Units

Overall

NC-15
8000

NC-15
8000

10. Installation
Please read this instruction sheet completely before installing the product.
When the power cord is damaged, replacement work shall be performed by authorized personnel only.
Installation work must be performed in accordance with the national wiring standards by authorized personnel only.

There should not be any heat source or steam near the unit.
There should not be any obstacles to the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
The indoor unit must have the maintenance space.

More than 300


More than
300

More than
300

250 or below
from the Floor

(Unit : mm)

In case that the unit is installed near the sea, the installation parts may be corroded
by salt. The installation parts (and the unit) should be taken appropriate anti-corrosion measures.

Console _ 15

Indoor Units

10.1 Selection of the Best Location

10. Installation
10.2 Indoor unit installation
Indoor Units

1. Preparation / Removing front panel


1. Open the front grille by pulling forward

2. Then pull out the link of grille from groove in front panel.
3. Then pull out 2 hinges of grille from grooves in front panel.
4. Then remove 4 screws, dismount the front panel while pulling it forward.

2. Preparation / For Moldings , Side Piping, and Concealed Installation


2-1 For Moldings
1. Remove the slit portions on the Rear Panel.

Remove

Upper Deco cover

Side Deco cover

2-2 For Concealed Installation


1. Remove the 6 screws.
2. Remove the Upper Deco cover.
3. Remove the Side Deco covers.

2-3 For Side Piping (Reference 2-2.)


1. Remove the Deco Covers.
2. Remove the slit portions
3. Assemble the Deco Covers.

16 _ Console

10. Installation
3. Refrigerant Piping
1. The location of hole is different depending on which side of the pipe is taken out.
symbol in the illustration as below

Indoor Units

2. Drill a hole(70mm) in the point indicated by

Left bottom piping

60

45

Wall

90

75

Right bottom piping

40
Right back piping

Right back piping

50

75

45

90

45

Left back piping

Left/right piping

(Unit : mm)

NOTICE
- The suggested shortest pipe length is 5m,in order to avoid noise from the outdoor unit and vibration.

4. Installing Indoor unit


4-1 Installation on the Floor.
1. Fix up using 6 screws for floor installation.
(700)

180

159

26

64

(600)

140
170

574

140

647

170

0
21

30.5

6 screw (M4*25L)

0
16

30.5

(Unit : mm)

Console _ 17

10. Installation
4-2 Installation on the Wall
1. Fix up the installation plate using 5 screws and the indoor unit using 4 screws.
Indoor Units

2. The installation plate should be fixed on a wall which can support the weight of the indoor unit.
Installation Plate

Molding

4 screw (M4*25L)

4-3 Half concealed installation.


1. Make a wall hole of the size shown Fig-1.
45

Wall
670

Supplemental plate
(Field supply)

95

Supplemental plate
(Field supply)

Hole

200

200

150

150

585

(Unit : mm)

<Fig - 1>

18 _ Console

1) Normal concealed

2) Deep concealed

10. Installation
2. Installation of supplemental plate for attaching main unit
The rear of the unit can be fixed with screws at the points shown in the Fig-2.Be sure to install the
supplemental plate in accordance with the depth of the inner wall.
Indoor Units

647

140

140

170

170
(Unit : mm)
<Fig - 2>

3.Piping Hole
Wall

Right bottom Piping


35

50

Left bottom Piping

Left Piping
45

Wall

75

75

50

(Unit : mm)

4. Remove the Deco Covers and Fixing Indoor


Unit
1) Remove the Deco Covers.
2) Insert the Indoor Unit to the Wall hole.
3) Secure using 6 screws. (shown in the illustration)

Console _ 19

10. Installation

Indoor Units

NOTICE
- Check the horizon of Indoor unit with the wall. Please use the Leveler on the drain pan guide.

Leveler

Drain pan
Less than 5mm

Less than 5mm

20 _ Console

Less than 5mm

10. Installation
10.3 Connecting the Piping

Indoor Units

When you connect the refrigerant pipe, it is easier that you connect the gas pipe first.
1. Hold up the Sensor Link.
2. Separate the Pipe Bracket (2 screws)
3. Connect the refrigerant pipe. (Refer to next page)
4. Assemble the Pipe Bracket (2 screws)
5. Put down the Sensor Link
3

6. After connecting, check the pipe arrangement as per illustration.


7. The piping can be arranged in six ways as shown in the illustration below.
6

Pipe Guide

3
Connecting
Pipe

2
1
Pipe Guide
Connecting Pipe must be placed inner
than the pipe guide.

6
5

In case of ~ , The pipe bending can be used in hand-operated bending machine.


Make a pipe of the shape shown pic 8.

Console _ 21

Indoor Units

10. Installation
If the drain hose is routed inside the room insulate the hose with an insulation material* so
that dripping from sweating (condensation) will
not damage furniture or floors.
* Foamed polyethylene or equivalent is recommended.

Tape
Connecting
cable
Drain hose
Connecting pipe

Connecting the installation pipe and


drain hose to the indoor unit.
1. Align the center of the pipes and sufficiently
tighten the flare nut by hand.

Indoor unit tubing

Flare nut

Pipes

2. Tighten the flare nut with a wrench


Outside diameter
mm
inch
6.35
1/4
9.52
3/8
12.7
1/2
15.88
5/8
19.05
3/4

Torque
kgf.m
1.8~2.5
3.4~4.2
5.5~6.5
6.3~8.2
9.9~12.1

3. When needed to extend the drain hose of


indoor unit, assembly the drain pipe as shown
on the drawing

Open-end wrench (fixed)


Flare nut
Wrench

Connection pipe

Indoor unit tubing

Drain pipe

Indoor unit drain hose


Adhesive

Wrap the insulation material around


the connecting portion.
1. Overlap the connection pipe insulation material
and the indoor unit pipe insulation material.
Bind them together with vinyl tape so that there
may be no gap.
2. Wrap the area which accommodates the rear
piping housing section with vinyl tape.

Vinyl tape(narrow)

Insulation material

Indoor unit pipe

Connection pipe

Wrap with vinyl tape


Vinyl tape (wide)
Connecting cable
Pipe

3. Bundle the piping and drain hose together by


wrapping them with vinyl tape sufficient enough
to cover where they fit into the rear piping
housing section.

Vinyl tape(narrow)
Wrap with vinyl tape
Pipe

Vinyl tape(wide)
Drain hose

22 _ Console

10. Installation
10.4 Wiring Connection
Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

Terminal block of indoor unit


1(L)

2(N)

3(A)

4(B)

Outdoor unit Indoor unit

Central controller

SODU SODU IDU IDU INTERNET DRY1 DRY2 GND 12V

Indoor power input


220V 60Hz

Make sure that the screws of the terminal are free from looseness.

After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have separate power specially for the air conditioner. As for the method of wiring, follow the circuit diagram pasted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to
which the unit is subjected during the course of transportation. Check them and make sure that they are all
tightly fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Confirm the Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the
name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function
of a overload protection device.
Proper starting power is not given to the compressor.

Console _ 23

Indoor Units

Terminal block of outdoor unit

10. Installation

Indoor Units

WIRED REMOTE CONTROLLER INSTALLATION


Since the room temperature sensor is in the remote controller, the remote controller box should be installed in a place
away from direct sunlight, high humidity and direct supply of cold air to maintain proper space temperature.
Install the remote controller about 5ft(1.5m) above the floor in an area with good air circulation at an average temperature.

Do not install the remote controller where it can be affected by:


- Drafts, or dead spots behind doors and in corners.
- Hot or cold air from ducts.
- Radiant heat from sun or appliances.
- Concealed pipes and chimneys.
- Uncontrolled areas such as an outside wall behind the remote controller.
- This remote controller is equipped with a seven segment LED. display. For proper display of the remote controller
LED's, the remote controller should be installed properly as shown in Fig.1.
(The standard height is 1.2~1.5 m from floor level.)

TEMP

yes

Remote Controller

no

TEMP

Controller
Remote

TEMP

Remote Controller

5feet
(1.5meters)

no

no

Fig.1 Typical locations for remote controller

24 _ Console

11. Accessories
Standard Accessories
Drain Hose

Install Plate

Clamp
(Tie wrap)

Quantity

1 EA

1 EA

4 EA

Shape

Other

- Allergy Filter
- Fixing screw for installation
Plate 4*25 mm-5EA
- Wood screw for indoor
fixation -6EA
- Owner's Manual
- Installation Manual

Console _ 25

Indoor Units

Name

Indoor unit
Fresh Air Intake Unit
1. List of functions
2. Specifications
3. Dimensions & Gravity point
4. Piping Diagrams
5. Wiring Diagrams
6. Outlet temperature, expected capacity and air flow
7. External Static Pressure(E.S.P) & Air Flow
8. Electric Characteristics
9. Sound Levels
10. Operation range
11. Installation
12. Accessories

1. List of functions

Indoor Units

Category

Air flow

Air purifying

Installation

Reliability

Convenience

Individual
control

Special
function kit

Function
Air supply outlet
Airflow direction control(left & right)
Airflow direction control(up & down)
Auto swing(left & right)
Auto swing(up & down)
Airflow steps(fan/cool/heat)
Chaos swing
Chaos wind(auto wind)
Jet cool(Power wind)
Swirl wind
Deodorizing filter
Plasma air purifier
Prefilter(washable / anti-fungus)
Drain pump
E.S.P. control
Electric heater(operation)
High ceiling operation
Hot start
Self diagnosis
Soft dry operation
Auto changeover
Auto cleaning
Auto operation(artificial intelligence)
Auto restart operation
Child lock
Forced operation
Group control
Sleep mode
Timer(on/off)
Timer(weekly)
Two thermistor control
Standard wired remote controller
Wide Character wired remote controller
Picto wired remote controller
Deluxe wired remote controller
Simple wired remote controller
Wired remote controller(for hotel use)
Wireless remote controller(simple)
Wireless LCD remote control
Zone control
CTIE
Electro thermostat

ARNU48GBRZ2, URNU76GB8Z2,URNU96GB8Z2
1
2/2/2
X
X
O
O
O
X
O
O
O
X
O(only heat pump or cooling only)
O
O
O
X
O
O
X
Accessory
Accessory
Accessory
Accessory
Accessory
X
Accessory
Accessory
-

O : Applied
X : Not applied : No relation
Option : Model name & price are different according to options, and assembled in factory with main unit.
Accessory : Installed at field, ordered and purchased separately by the corresponding model name, supplied with separate
package.

1 _ Fresh Air Intake Unit

2. Specifications
Type
Model

ARNU48GBRZ2
14.1
Cooling Capacity
12,100
48,100
13.5
Heating Capacity
11,620
46,115
Casing
Galvanized Steel Plate
mm
1230 x 590 x 380
Dimensions(WxDxH) Body
inch
48.4 x 23.2 x 15
Rows
x
Columns
x
FPI
3 x 13 x 19
Coil
Face Area
m3
0.38
Type
Sirocco Fan
Motor Output x Number
W
195 x 1
Running Current
A
0.38
Air
Flow
Rate(H/M/L)
CMM
18.8/14.7/14.7
Fan
(High Mode-factory set)
cfm
664/519/519
External Static Pressure mmAq(Pa)
18
Drive
Direct
Motor type
BLDC
Microprocessor,
Temperature Control
Thermostat for cooling
and heating
Sound Absorbing Thermal Insulation Material
Foamed polystrene
Air Filter
Long Life Filter
Safety Device
Fuse
Liquid Side
mm(inch)
9.52(3/8)
Pipe Connections Gas Side
mm(inch)
15.88(5/8)
Drain Pipe(Internal Dia.)
mm
25
Net Weight
kg(lbs)
45(99)
Noise Level(Sound Press, 1.5m, H/M/L)
dB(A)
44/42/42
1,
220
- 240, 50
Power Supply
, V, Hz
1, 220, 60
Refrigerant Control
EEV
Power cable
mm2
CV1.5 x 3C
Transmission cable
mm2
VCTF-SB1.0 ~ 1.5 x 2C
Notes:1. Capacities are based on the following conditions:
Cooling
Outdoor temp. 33C[91.4F]DB/ 28C[82.4F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
Heating
Outdoor temp. 0C[32F]DB/ -2.9C[26.78F]WB
Interconnecting Piping Length 7.5m
Level Difference of Zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available Models
5. Indoor Unit Connection
No
1
2

Connection Condition
Fresh Air Intake Units only are connected with
outdoor units
Mixture connection with general Indoor unit and
Fresh Intake Unit

URNU96GB8Z2
28
24,100
95,900
26.7
23,000
91,360
Galvanized Steel Plate
1562 x 688 x 460
61.5 x 27.1 x 18.1
3 x 20 x 19
0.59
Sirocco Fan
375 x 1
2.15
35.7/23.7/23.7
1261/837/837
22
Direct
BLDC
Microprocessor,
Thermostat for cooling
and heating
Foamed polystrene
Long Life Filter
Fuse
9.52(3/8)
22.2(7/8)
25
73(161)
50/48/48
1, 220 - 240, 50
1, 220, 60
EEV
CV1.5 x 3C
VCTF-SB 1.0 ~ 1.5 x 2C

Conversion Formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60

Combination
1) The total capacity of Fresh Air Intake Unit should be 50~100% of outdoor unit.
2) The max quantity of Fresh Air Intake unit is 2 Units.
1) The total capacity of indoor units (standard Indoor Unit + Fresh Air Intake Unit) should be 50~100% of outdoor unit.
2) The total capacity of Fresh Air Intake Unit should be less than 30% of the total capacity of indoor units.

6. EEV : Electronic Expansion Valve


7. Noise Level is Standard Mode
(for actual High Mode(factory set) condition, Noise Level may exceed the standard level by 1.5dBA)

Fresh Air Intake Unit _ 2

Indoor Units

Unit
kW
kcal/h
Btu/h
kW
kcal/h
Btu/h

Fresh Air Intake Unit


URNU76GB8Z2
22.4
19,300
76,400
21.4
18,410
73,080
Galvanized Steel Plate
1562 x 688 x 460
61.5 x 27.1 x 18.1
3 x 20 x 19
0.59
Sirocco Fan
375 x 1
1.36
23.7/13.2/13.2
837/446/446
22
Direct
BLDC
Microprocessor,
Thermostat for cooling
and heating
Foamed polystrene
Long Life Filter
Fuse
9.52(3/8)
19.05(3/4)
25
73(161)
49/47/47
1, 220 - 240, 50
1, 220, 60
EEV
CV1.5 x 3C
VCTF-SB 1.0 ~ 1.5 x 2C

R6

60

198

312

380

25

303

32

140

590

50

185

168

241

621

279

1,230

118
1,004

1,284
1,230

1,092

120

114

477
590

1
2
135
190
260

115

101
83

Name

Air discharge
Air suction

4
5
6

Unit size(48k):25

Unit size(48k):15.88

Unit size(48k):9.52

Descripition

(unit : mm)

Gravity point

CHASSIS CODE: BR

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Power supply connection

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

Gas pipe connection


Drain pipe connection

Liquid pipe connection

Number
26

ARNU48GBRZ2

Fresh Air Intake Unit

72
123
221
122
144

3 _ Fresh Air Intake Unit


56

90
302

Indoor Units

3. Dimensions & Gravity point

Fresh Air Intake Unit _ 4

460

460

688

293

329

819

1,562

1,220

1,562

1,622

115

688
30

20

440

318

1,396

560
64

290
161

397

358

68

18

109

58

122 60 70 64

Air discharge
Air suction

Gravity point

CHASSIS CODE: B8

2. Unit shall be grounded in accordance with the local regulations or


applicable national codes.

1. Unit should be installed in compliance with the installation manual


in the product box.

Note

Unit size(76k):19.05
Unit size(96k):22.2

Unit size(76k, 96k):19.05

Descripition

(unit : mm)

Drain pipe connection


Unit size(76k, 96k): 22.2
Power supply connection
5

Gas pipe connection

Name
Liquid pipe connection

Number

76, Seongsan-dong, Changwon City, Gyeongnam,


641-713, Korea

99 14

70
120

URNU76GB8Z2
URNU96GB8Z2

Fresh Air Intake Unit

Indoor Units

3. Dimensions & Gravity point

4. Piping Diagrams

Indoor Units

Th4

EEV

Th3

Filter

Th2
Heat Exchanger
Distributor

Th1

Filter

Filter

Capillary Tube

Solenoid Valve

Check Valve

Fresh Air Intake Unit

Refrigerant pipe connection port diameter


[Unit: mm(inch)]

MODEL

GAS

LIQUID

ARNU48GBRZ2

15.88(5/8)

9.52(3/8)

URNU76GB8Z2

19.05(6/8)

9.52(3/8)

URNU96GB8Z2

22.2(7/8)

9.52(3/8)

LOC.

Description

Th1

Inlet Air Thermistor

Th2

Pipe In Thermistor

Th3

Pipe Out Thermistor

Th4

Outlet Air Thermistor

5 _ Fresh Air Intake Unit

Cooling
Heating

5. Wiring Diagrams
BR Chassis
Indoor Units

Accessory

B8 Chassis

Accessory

Fresh Air Intake Unit _ 6

6. Outlet temperature, expected capacity and air flow


6.1 Outlet Air Temperature
Indoor Units

ARNU48GBRZ2
Cooling
DB
21
23
25
27
29
31
33
35
37
40

59 WB
15 WB
CA
SHC
4.7
3.5
4.6
4.1
4.6
4.5
-

63 WB
17 WB
CA
SHC
5.2
3.1
5.0
3.7
4.9
4.3
4.9
4.9
-

69 WB
20 WB
CA
SHC
7.8
3.6
7.7
4.2
6.9
4.8
6.6
5.4
6.3
6.1
-

73 WB
23 WB
CA
SHC
10.4
4.6
9.9
5.2
9.0
5.7
8.8
6.3
8.6
6.9
-

79 WB
26 WB
CA
SHC
12.9
4.6
12.5
5.2
12.2
5.8
11.8
6.4
11.0
6.9
10.6
7.9

82 WB
28 WB
CA
SHC
14.2
5.1
13.6
5.5
13.1
5.9
12.7
6.5
12.4
7.5

86 WB
30 WB
CA
SHC
15.2
4.7
14.9
5.3
14.3
5.9
13.9
6.8

90 WB
32.0
CA
SHC
16.2
5.4
15.9
6.4

17.4

DB
21
23
25
27
29
31
33
35
37
40

59 WB
15 WB
DB
WB
11.8
9.9
11.9
10.0
12.0
10.1
-

63 WB
17 WB
DB
WB
12.7
11.8
13.0
12.0
13.3
12.0
13.8
12.0
-

69 WB
20 WB
DB
WB
13.5
12.7
13.7
12.8
14.0
13.5
14.2
13.8
14.3
14.0
-

73 WB
23 WB
DB
WB
14.7
14.0
14.8
14.4
15.5
15.2
15.7
15.3
15.8
15.5
-

79 WB
26 WB
DB
WB
16.7
15.7
16.9
16.0
17.2
16.2
17.5
16.5
17.7
17.2
17.9
17.5

82 WB
28 WB
DB
WB
17.5
17.4
18.2
17.9
18.9
18.2
19.2
18.5
19.5
18.7

86 WB
30 WB
WB
DB
20.5
19.5
20.7
19.7
20.9
20.1
21.2
20.3

90 WB
32.0
DB
WB
22.5
21.6
22.5
21.7

95 WB
35 WB
DB
WB
25.2
25.1

Outdoor
air tempreture
DB
70
73
77
81
84
88
91
96
99
104
Outdoor
air tempreture
DB
70
73
77
81
84
88
91
96
99
104

95 WB
35 WB
CA
SHC
-

Heating
Outdoor
air tempreture
DB
18
27
32
37
45
52
59
64
68

DB
-9
-3
0
3
7
11
15
18
20

Outdoor
air tempreture
DB
18
27
32
37
45
52
59
64
68

DB
-9
-3
0
3
7
11
15
18
20

23 WB

27 WB

32 WB

36 WB

39 WB

43 WB

50 WB

57 WB

-5 WB
SHC
14.9
-

-2.9 WB
SHC
14.0
-

0 WB
SHC
13.8
-

2 WB
SHC
14.0
12.5
-

4 WB
SHC
12.7
-

6 WB
SHC
12.6
11.2
-

10 WB
SHC
11.3
9.9
8.9
-

14 WB
SHC
10.1
9.0
8.1

23 WB

27 WB

32 WB

36 WB

39 WB

43 WB

50 WB

57 WB

-5 WB
DB
38.7
-

-2.9 WB
DB
39.2
-

0 WB
DB
42.1
-

2 WB
DB
42.7
42.6
-

4 WB
DB
43.2
-

6 WB
DB
43.3
42.8
-

10 WB
DB
43.0
43.2
43.2
-

14 WB
DB
43.7
43.5
43.1

Note)
CA: Total Capacity (kW), SHC: Sensible Heat Capacity (kW)
WB: Wet Bulb(), DB: Dry Bulb()
1. The data shown in the graph illustrates the supported operating ranges underthe following conditions:
- Indoor and Outdoor Unit
- Effective piping length: 7.5 m
- Height differential: 0 m
2. The actual temperature may not match the temperature setting under some circumstances due to
the outdoor-air processing load or mechanical protection controls.
3. The system will not operate in fan mode when the outdoor air temperature is -5C or below.

7 _ Fresh Air Intake Unit

5.5

6. Outlet temperature, expected capacity and air flow


URNU76GB8Z2
Cooling
63 WB

69 WB

73 WB

79 WB

82 WB

86 WB

90 WB

95 WB

20 WB
CA
SHC
11.9
5.5
11.4
6.4
11.1
7.2
10.8
7.9
10.7
8.8
-

23 WB
CA
SHC
14.8
6.6
14.4
7.3
14.1
8.1
13.7
8.9
13.4
9.7
-

26 WB
CA
SHC
18.2
6.9
17.9
7.7
17.6
8.5
17.3
9.3
15.1
14.8
16.2
11.1

28 WB
CA
SHC
20.7
7.3
20.3
8.0
19.9
8.8
19.3
9.4
19.1
10.6

30 WB
CA
SHC
22.2
7.3
21.5
7.9
21.2
8.7
20.7
9.8

32.0

DB
21
23
25
27
29
31
33
35
37
40

17 WB
CA
SHC
8.6
5.0
8.1
5.8
8.2
6.7
8.3
7.5
-

35 WB
CA
SHC
28.6
8.8

DB
70
73
77
81
84
88
91
96
99
104

59 WB

63 WB

69 WB

73 WB

79 WB

82 WB

86 WB

90 WB

DB
21
23
25
27
29
31
33
35
37
40

15 WB
DB
WB
10.6
8.3
10.7
8.4
10.8
8.5
-

17 WB
DB
WB
10.6
10.0
10.8
10.4
10.9
10.2
11.0
10.1
-

20 WB
WB
DB
11.5
11.0
11.6
11.3
11.8
11.5
12.0
11.7
12.0
11.7
-

23 WB
WB
DB
13.1
12.5
13.4
12.8
13.6
13.0
13.7
13.2
13.8
13.4
-

26 WB
DB
WB
14.4
14.2
14.5
14.3
14.7
14.5
14.9
14.6
15.1
14.8
15.5
15.3

28 WB
DB
WB
15.5
15.3
15.9
15.5
16.1
15.7
16.5
16.1
16.6
16.1

30 WB
DB
WB
17.6
17.4
18.1
17.8
18.3
17.9
18.5
18.1

32.0
DB
WB
19.4
18.9
19.5
19.0

Outdoor
air tempreture
DB
70
73
77
81
84
88
91
96
99
104

CA
24.4
24.0

SHC
8.2
9.4

95 WB
35 WB
DB
WB
21.1

21.1

Heating
Outdoor
air tempreture
DB
18
27
32
37
45
52
59
64
68
Outdoor
air tempreture
DB
18
27
32
37
45
52
59
64
68

DB
-9
-3
0
3
7
11
15
18
20

23 WB
-5 WB
SHC
20.5
-

27 WB
-2.9 WB
SHC
19.1
-

32 WB
0 WB
SHC
18.3
-

36 WB
2 WB
SHC
18.2
16.8
-

39 WB
4 WB
SHC
16.6
-

43 WB
6 WB
SHC
16.7
15.0
-

50 WB
10 WB
SHC
14.9
13.2
11.8
-

57 WB
14 WB
SHC
13.2
11.8
11.1

27 WB
-2.9 WB
DB
43.1
-

32 WB
0 WB
DB
44.3
-

36 WB
2 WB
DB
44.2
45.2
-

39 WB
4 WB
DB
44.5
-

43 WB
6 WB
DB
44.8
45.1
-

50
10

57
14

DB
-9
-3
0
3
7
11
15
18
20

23 WB
-5 WB
DB
43.2
-

WB
WB
DB
44.9
44.8
44.7
-

WB
WB
DB
45.0
44.8
45.2

Note)
CA: Total Capacity (kW), SHC: Sensible Heat Capacity (kW)
WB: Wet Bulb(), DB: Dry Bulb()
1. The data shown in the graph illustrates the supported operating ranges underthe following conditions:
- Indoor and Outdoor Unit
- Effective piping length: 7.5 m
- Height differential: 0 m
2. The actual temperature may not match the temperature setting under some circumstances due to
the outdoor-air processing load or mechanical protection controls.
3. The system will not operate in fan mode when the outdoor air temperature is -5C or below.

Fresh Air Intake Unit _ 8

Indoor Units

59 WB
15 WB
CA
SHC
7.7
5.0
7.5
5.8
7.4
6.7
-

Outdoor
air tempreture

6. Outlet temperature, expected capacity and air flow


URNU96GB8Z2
Indoor Units

Cooling
59 WB

63 WB

69 WB

73 WB

79 WB

82 WB

86 WB

90 WB

95 WB

17 WB
CA
SHC
11.1
6.7
10.3
7.9
10.6
9.2
10.6
10.5
-

20 WB
CA
SHC
16.0
7.5
15.3
8.8
14.8
10.0
14.3
11.2
14.2
12.5
-

23 WB
CA
SHC
20.5
9.2
19.7
10.3
19.2
11.4
18.7
12.7
18.2
13.9
-

26 WB
CA
SHC
25.4
9.6
25.0
10.9
24.4
12.0
24.0
13.2
23.5
14.3
22.2
15.9

28 WB
CA
SHC
29.0
10.3
28.5
11.3
27.9
12.4
26.9
13.4
26.5
15.2

30 WB
CA
SHC
31.1
10.2
30.0
11.1
29.6
12.3
28.8
14.0

32.0

DB
21
23
25
27
29
31
33
35
37
40

15 WB
CA
SHC
5.4
3.7
5.2
4.3
5.1
5.0
-

35 WB
CA
SHC
12.5
40.0

59 WB

63 WB

69 WB

73 WB

79 WB

82 WB

86 WB

90 WB

95 WB

DB
21
23
25
27
29
31
33
35
37
40

15 WB
WB
DB
11.7
9.4
11.8
9.5
11.9
9.6
-

17 WB
DB
WB
11.7
11.1
11.9
11.5
12.0
11.3
12.1
11.2
-

20 WB
DB
WB
12.6
12.1
12.7
12.4
12.9
12.6
13.1
12.8
13.1
12.8
-

23 WB
DB
WB
14.2
13.6
14.5
13.9
14.7
14.1
14.8
14.3
14.9
14.5
-

26 WB
DB
WB
15.5
15.3
15.6
15.4
15.8
15.6
16.0
15.7
16.2
15.9
16.6
16.4

28 WB
DB
WB
16.6
16.4
17.0
16.6
17.2
16.8
17.6
17.2
17.7
17.2

30 WB
DB
WB
18.7
18.5
19.2
18.9
19.4
19.0
19.6
19.2

32.0
DB
WB
20.5
20.0
20.6
20.1

35 WB
DB
WB
22.2
22.2

Outdoor
air tempreture
DB
70
73
77
81
84
88
91
96
99
104
Outdoor
air tempreture
DB
70
73
77
81
84
88
91
96
99
104

CA
34.4
33.8

SHC
11.6
13.4

Heating
Outdoor
air tempreture
DB
18
27
32
37
45
52
59
64
68

DB
-9
-3
0
3
7
11
15
18
20

WB

27

WB

-2.9

SHC
30.8
WB

27
-2.9

-5
DB
-9
-3
0
3
7
11
15
18
20

WB
WB

32

WB

36

WB

39

WB

43

WB

50

WB

WB

WB

WB

10 WB
SHC
22.5
19.8
17.6
-

SHC
28.7
-

WB
DB
43.1
-

23

Outdoor
air tempreture
DB
18
27
32
37
45
52
59
64
68

23
-5

WB

WB
DB
43.0
-

SHC
28.0
32
0

SHC
27.7
25.3
-

WB

36

WB
DB
45.3
-

SHC
25.0
-

WB

39

WB
DB
44.7
45.2
-

SHC
24.4
22.1
-

WB

43

WB
DB
44.6
-

9 _ Fresh Air Intake Unit

57

WB
DB
44.9
44.8
44.5
-

14

50
10

1. The data shown in the graph illustrates the supported operating ranges underthe following conditions:
- Indoor and Outdoor Unit
- Effective piping length: 7.5 m
- Height differential: 0 m
2. The actual temperature may not match the temperature setting under some circumstances due to
the outdoor-air processing load or mechanical protection controls.
3. The system will not operate in fan mode when the outdoor air temperature is -5C or below.

57

WB

14 WB
SHC
19.6
17.9
16.4

WB

WB

WB
DB
43.6
44.2
-

Note)
CA: Total Capacity (kW), SHC: Sensible Heat Capacity (kW)
WB: Wet Bulb(), DB: Dry Bulb()

WB

WB

WB
DB
44.5
45.0
44.7

6. Outlet temperature, expected capacity and air flow


6.2 Air flow
ARNU48GBRZ2

70
75
80
85
87
90
92
94
96
98
101
103
106
111
116
121
126
130
135
140

5
15.8
18.7
22.2
24.2
25.2
26.8
28.1
29
30.3
-

6
16
19.9
23.4
24.1
25.5
27
27
28.5
29.8
31.8
32.7
-

8
13.6
17.8
19.6
21.9
22.8
24
25
26.5
28
29.17
30.9
-

12
10.6
13.8
15.8
17.4
20.5
22
24.6
28.3
30.7
-

ESP (mmAq)
14
10.7
16
16.5
19.9
24.2
27.6
30.4
-

15
26.57
42.67
46.44
48.82
50.91
50.9
-

ESP (mmAq)
18
20.9
33.72
40.09
44.3
46.73
49.84
49.66
-

10
15.9
18.2
19.8
22.5
22.8
24.2
25.9
28.2
30.8
-

15
11.8
15.2
20.7
25.2
29.7
-

16
11.9
17.7
24.2
27.2
28.6
-

17
15.8
22.4
26.3
27.6
-

18
14.7
18.8
25.6
27.4
-

20
13.4
18.7
25.9
26.5
-

URNU76GB8Z2,URNU96GB8Z2
Setting
Value
55
60
65
70
75
80
85
88
90
92
94
96
98
100
102
105

6
25.39
33.65
40.01
46.43
50.93
55.77
-

9
30.29
35.81
45.35
51.91
54.22
-

12
17.31
35.57
42.86
49.74
52.72
52.54
-

20
23.07
23.46
39.65
44.04
48.09
48.23
-

22
13.87
24.17
39.72
42.56
46.41
-

23
23.63
25.28
40.34
45.92
46.51

25
14.49
15.47
38.6
45.44

Note) Setting Value : ESP value


The above table shows the correlation between the air rates and E.S.P.

Fresh Air Intake Unit _ 10

Indoor Units

Setting
Value

7. External Static Pressure (E.S.P) & Air Flow

Indoor Units

ARNU48GBRZ2
Capacity
(Btu/h)

Mode

Set value

High
High
(factory set) Mid

1,160

48k

1,110

Standard
ESP(mmAq(Pa))
18

CMM
18.8
14.7

Lower Limit of External


Static Pressure(mmAq(Pa))

Upper Limit of External


Static Pressure(mmAq(Pa))

10(98)

20(196)

Lower Limit of External


Static Pressure(mmAq(Pa))

Upper Limit of External


Static Pressure(mmAq(Pa))

12(118)

25(245)

12(118)

25(245)

URNU76GB8Z2,URNU96GB8Z2
Capacity
(Btu/h)

Mode

Set value

High
(factory set)

High

950

76k

Mid

930

96k

High
(factory set)

High

970

Mid

950

11 _ Fresh Air Intake Unit

Standard
ESP(mmAq(Pa))
22
22

CMM
23.7
13.2
35.7
23.7

8. Electric Characteristics
Units
Type

ARNU48GBRZ2

BR

URNU76GB8Z2

B8

URNU96GB8Z2

B8

ARNU48GBRZ2

BR

URNU76GB8Z2

B8

URNU96GB8Z2

B8

Hz
50

volts
220-240

Max: 264
Min: 198
60

Symbols:
MCA : Min, Circuit Amps(A)
MFA : Max. Fuse Amps(see note 5)
kW : Fan Motor Rated Output(kW)
FLA : Full Load Amps(A)
IFM : Indoor Fan Motor

Voltage Range

220

IFM

Input(W)

MCA

MFA

kW

FLA

Cooling Heating

1.5

15

0.39

0.38

169

169

2.7

15

0.38

1.36

230

230

3.7

15

0.38

2.15

360

360

1.5

15

0.39

0.38

169

169

2.7

15

0.38

1.36

230

230

3.7

15

0.38

2.15

360

360

Note :
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above the listed range limits,
2. Maximum allowable voltage unbalance between phases is 2%
3. MCA/MFA
MCA=1.25 x FLA
MFA 4 x FLA
(Next lower standard fuse rating. Min. 15A)
4. Select wire size based on the MCA
5. Instead of fuse, use Circuit Breaker.

Fresh Air Intake Unit _ 12

Indoor Units

Model

Power Supply

9. Sound Levels
Overall
Indoor Units

DISCHARGE

Notes:
- Sound measured at 1.5m away from the center of the unit.
- Data is valid at free field condition
- Data is valid at nominal operating condition
- Reference accoustic pressure OdB = 20Pa
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.

SUCTION

DUCT

DUCT
1.5m

2m

1m
1m

[dB(A)]
Sound Level

Model
ARNU48GBRZ2

H
44

M
42

L
42

URNU76GB8Z2

49

47

47

URNU96GB8Z2

50

48

48

Sound Pressure Level


URNU76GB8Z2

URNU96GB8Z2
80

70

70

70

NC-65

60

NC-60
NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
NC-25

20

10

Approximate
Hearing
Threshold
63

NC-60

125

250

500

Octave Band Center Frequency (Hz)

13 _ Fresh Air Intake Unit

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

NC-20
NC-15
1000 2000 4000 8000

NC-65

60

10

NC-25
Approximate
Hearing
Threshold
63

Octave Band Sound Pressure Level (dB re 20Pa )

80

Octave Band Sound Pressure Level (dB re 20Pa )

Octave Band Sound Pressure Level (dB re 20Pa )

ARNU48GBRZ2
80

NC-60

125

250

500

Octave Band Center Frequency (Hz)

NC-55

50

NC-50
NC-45

40

NC-40
NC-35

30

NC-30
20

NC-20
NC-15
1000 2000 4000 8000

NC-65

60

10

NC-25
Approximate
Hearing
Threshold
63

NC-20

125

250

500

NC-15
1000 2000 4000 8000

Octave Band Center Frequency (Hz)

10. Operation Details


Operation range

* FAU : Fresh Air Intake Unit


-5C
Cooling mode

5C

15C

Outdoor Air Temperature (Toa)


43 (1)

19C
Cooling

Fan operation (thermo off)

Cooling
Fan operation
Fan stop

Heating mode

6C

18C

Heating

Fan operation (thermo off)


Fan operation

Heating
16C

Automatic mode

Cooling

Heating

Cooling
Heating

18C
16C
(1)Normal model : 43C
Tropical model : 48C

Usage Limitations

-5C

15C

19C

(33.5)

43 (2)

(2)Normal model : 43C


Tropical model : 48C

Fresh Air Intake Unit _ 14

Indoor Units

FAU will operate in the below range. Hot outdoor temperature (over 43) or cold outdoor temperature (under 5) will make customer feel uncomfortable because FAU outlet discharge temperature might be not enough controlled in that region.

Indoor Units

11. Installation

Air outlet vents

Air filters

Air intake vents


Wired Remote Controller

Standard Accessories
Name

Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for
hanging backet
8 EA

Clamp
(Tie Wrap)

Insulation for
fitting

4 EA

1 SET

Others

Owner's manual
Installation manual
Shape

for gas pipe

for liquid pipe

15 _ Fresh Air Intake Unit

11. Installation
11.1 Installation Limit
Read completely, then follow step by step.

No
1

Connection Condition
Only Fresh Air Intake Unit installation

2 Mixture Installation with standard


indoor units and Fresh Intake Units

Combination
1) The total capacity of Fresh Air Intake Unit should be 50~100% of outdoor unit.
2) The max quantity of Fresh Air Intake unit is 2 Units.
1) The total capacity of indoor units (standard Indoor Unit + Fresh Air Intake Unit)
should be 50~100% of outdoor unit.
2) The total capacity of Fresh Air Intake Units should be less than 30% the total
capacity of indoor units.

Failure to comply with the above connection conditions for installation, it can cause cooling &
heating capacity down.

2. Connection of the Outdoor Unit


It is possible to connect Heat Pump Models.
It is not possible to connect Heat Recovery Models.
<Only Fresh Air Intake Unit install>

<Mixture Install>

Outdoor : 10HP

Outdoor : 20HP

FAU

FAU

FAU

Standard

Standard

Standard

5HP

5HP

5HP

5HP

5HP

5HP

<Wrong Install>
Outdoor : 20HP

FAU

Standard

Standard

Standard

Standard

5HP

5HP

5HP

5HP

5HP
* FAU : Fresh Air Intake Unit
Standard: Standard Indoor Unit

The total capacity of indoor units exceed 100% of outdoor unit

Fresh Air Intake Unit _ 16

Indoor Units

1. Fresh Air Intake Unit Combination

11. Installation
3. Installation of intake air duct

Indoor Units

Min. 2m

Inlet Hood
Intake Air Duct
Fresh Air Intake Unit
Exhaust Fan
Door

1/30 Slope
Outlet Air

Exhaust air

Inlet Hood
Inlet Hood should be installed such that no water enter inside the unit
Intake Air Duct
The Intake Air Duct must have down-slope about 1/30.
The length of Intake Air Duct should be longer than 2m.
Fresh Air Intake Unit
If wired remote controller is not connected, it will display strange value to the room temperature
Exhaust Fan
Fresh Air Intake Unit will make room the positive pressure.
Exhaust fan should be installed to maintain the room pressure.
Door
It would be possible to raise in the room air pressure because of Fresh Air Intake Unit.
In that case, the door could hurt someone in front of door.
So be careful of the positive pressure to design the door.

17 _ Fresh Air Intake Unit

11. Installation
4. The Control System

Standard

FAU

Standard

Standard

Slave

* FAU : Fresh Air Intake Unit


Standard: Standard Indoor Unit

Set one of the IDU to Master

2) In case of using central remote controller, mixture of indoor units and Fresh Air Intake Unit in
same zone is not possible.
Separate Fresh Air Intake Unit zone with Standard indoor units zone.

FAU

FAU

Standard

Standard

FAU

FAU

Standard

Standard

48 kBtu/h

48 kBtu/h

48 kBtu/h

48 kBtu/h

48 kBtu/h

48 kBtu/h

48 kBtu/h

48 kBtu/h

ZONE 1

ZONE 2

ZONE 1

ZONE 2

5. Cycle check and SVC


For Fresh Intake Unit cycle check and SVC, LG MV 5.8 or later version should be used.

Fresh Air Intake Unit _ 18

Indoor Units

1) In case of connecting with Standard indoor units, Standard indoor unit should be a master unit.
Separate Fresh Air Intake Unit with Standard indoor units
.Set only one Standard indoor units to Master,

11. Installation
Install the air conditioner in the location that satisfies the following conditions.
The place shall easily bear a load exceeding four times the indoor units weight.
The place shall be able to inspect the unit as the figure.
The place where the unit shall be leveled.
The place shall allow easy water drainage.(Suitable dimension H is necessary to get a slope to drain as
figure.)
The place shall easily connect with the outdoor unit.
The place where the unit is not affected by an electrical noise.
The place where air circulation in the room will be good .
There should not be any heat source or steam near the unit.

Top view

Inspection hole
(600X600)

(unit: mm)

Control box

600

1000

Indoor Units

11.2 Selection of the best location

600

Front

Front view

CAUTION : In case that the unit is installed near the sea, the installation parts
may be corroded by salt, The installation parts (and the unit) should be taken
appropriate anti-corrosion measures.

[Inspection Hole Standard]


Number of
Inspection hole

Distance between
False ceiling & Actual ceiling

More than 1000mm

Sufficient space in the ceiling for servicing.

200mm to 1000mm

Insufficient space. Difficult for servicing

Less than 200mm

Minimum height for motor replacement.

2
Hole size should be
more than the size of IDU.

19 _ Fresh Air Intake Unit

Remarks

11. Installation
11.3 Ceiling dimension and hanging bolt location
Installation of Unit
Install the unit above the ceiling correctly.

BR Chassis (48k)

CASE 1
C
E

POSITION OF SUSPENSION BOLT

Apply a joint-canvas between the unit and duct to


absorb unnecessary vibration.

(G)

(Unit:mm)
Dimension

(G)

477

56

590

30

120 1006 294

A
Capacity(Btu/h)

BR Chassis 1282 1230


(48k)

H
Drainage hole

(Unit:mm)

B8 Chassis (76/96k)

Dimension

Capacity(Btu/h)

B8 Chassis
(76/96k) 1680 1565 1160 330 460 580 700 1400 1635 390 445 15

CASE 2
Install the unit leaning to a drainage hole side as a figure for easy water drainage.
POSITION OF CONSOLE BOLT
A place where the unit will be leveled and that can
support the weight of the unit.
A place where the unit can withstand its vibration.
A place where service can be easily performed.

M10 Nut

X4

M10 washer

X4

M10 washer

X4

M10 Nut

X8

Fresh Air Intake Unit _ 20

Indoor Units

A
B

11. Installation
NOTICE
Indoor Units

Throughly study the following installation locations:


1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the
fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc.
In these cases, take the following actions:
Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that
it draws oily steam which should not flow into the suction of the air conditioner.
Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck
in oil steam.
2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in
factories, etc.
3. Avoid places where inflammable gas is generated, flows in, is stored or vented.
4. Avoid places where sulfurous acid gas or corrosive gas is generated.
5. Avoid places near high frequency generators.

11.4 Indoor Unit Installation


Select and mark the position for fixing bolts.
Drill the hole for set anchor on the face of ceiling.

Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the
ceiling.
Mount the suspension bolts to the set anchor firmly.
Secure the installation plates onto the suspension
bolts (adjust level roughly) using nuts, washers
and spring washers.

Old building

1 Set anchor
2 Plate washer
3 Spring washer
4 Nut

CAUTION : Tighten the nut and bolt


to prevent unit falling.

21 _ Fresh Air Intake Unit

5 Suspension
bolts

New building

11. Installation
11.5 Wiring Connection
Connect the wires to the terminals on the control board individually according to the outdoor unit connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively.

Indoor Units

BR Chassis (48k)
Terminal Block Indoor
1(L)

2(N)

3(A)

Central controller

Outdoor unit Indoor unit

4(B)

SODU SODU

IDU

Outdoor unit

IDU INTERNET DRY1 DRY2 GND 12V

INDOOR POWER INPUT

B8 Chassis (76/96k)
Terminal Block Indoor
1(L)

2(N)

3(A)

Terminal Block
4(B)

Outdoor unit Indoor unit


SODU SODU

IDU

Central controller

IDU INTERNET DRY1 DRY2 GND 12V

Outdoor
unit

Indoor Power Input

WARNING : Make sure that the screws of the terminal are free from looseness.

Clamping of cables
1) Arrange 2 power cables on the control panel.
2) First, fasten the steel clamp with a screw to the inner boss of control panel.
3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the
0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel.

INSULATION, OTHERS
THERMAL INSULATION

Insulate the joint and tubes completely.

All thermal insulation must comply with local requirement.

INDOOR UNIT

Union for liquid pipe


Refrigerant pipe and thermal
insulator(Local supply)
Hose crip for thermal insulator
(Local supply)
Thermal insulator for refrigerant pipe
(Local supply)
Union for gas pipe

Thermal insulator for refrigerant pipe


(Local supply) Thermal insulator for
piping(Local supply)

Overlap with thermal


insulator for piping.
Hose crip for thermal insulator(Local supply)
Make sure that there is no clearance here.

Fresh Air Intake Unit _ 22

11. Installation
11.6 Check the Drainage
Indoor Units

1. Remove the Air Filter.

2. Check the drainage.


Spray one or two glasses of water upon the
evaporator.
Ensure that water flows drain hose of indoor
unit without any leakage.

CAUTION
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.

Front of view
The unit must be horizontal or declined to the drain hose connected when finished installation.

1~3mm

Ceiling

Drain Pump unuse

Drainage hole

23 _ Fresh Air Intake Unit

Drain Pump use

Drainage hole

11. Installation
11.7 Indoor Unit Drain Piping

Piping material: Polyvinyl chloride pipe inner


diameter 25mm and pipe fittings

Upward
routing
not allowed

Pipe clamp

Indoor Units

Drain piping must have down-slope (1/50 to 1/100): be sure not to provide up-and-down slope to prevent reversal flow.
During drain piping connection, be careful not to exert extra force on the
drain port on the indoor unit.
The outside diameter of the drain connection on the indoor unit is 32mm.

Indoor unit

Maintenance
drain port

Be sure to install heat insulation on the drain piping.

1/50~1/100

Heat insulation material: Polyethylene foam with


thickness more than 8 mm.

MAX 700mm

Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Feed water

Flexible drain hose


(accessory)
Main
drain pipe

Drain Pump

Drain
port

Glue the joint

Drain hose connection


Use the clip (accessory)

Connect the main drain pipe to the exterior and leave it provisionally until the test comes to an end.
Feed water to the flexible drain hose and check the piping
for leakage.
Be sure to check the drain pump for normal operation and
noise when electrical wiring is complete.
When the test is complete, connect the flexible drain hose to
the drain port on the indoor unit.

Drain pan

The supplied flexible drain hose should not be strained.


A strained hose may cause leakage of water.

Hanger
distance
1~15m

Hanger Bracket
1/50~1/100 slope

Metal
clamp
Flexible drain hose

Max 700mm

Max 300mm

Insulation

Flexible drain hose


Flexible drain hose

Flexible drain hose

Fresh Air Intake Unit _ 24

11. Installation
CAUTION:
Indoor Units

After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As for the method of
wiring, be guided by the circuit diagram posted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screws which fasten the wiring in the casing of electrical fittings are liable to come loose
from vibrations to which the unit is subjected during the course of transportation. Check them
and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out
of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the normal function of an overload protection device.
Proper starting power is not given to the compressor.

HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual.
(air filter cleaning, temperature control, etc.)

25 _ Fresh Air Intake Unit

12. Accessories
Standard Accessories
Drain hose

Clamp metal

Quantity

1 EA

2 EA

Washer for
hanging backet
8 EA

Clamp
(Tie Wrap)

Insulation for
fitting

4 EA

1 SET

(Other)

Owner's manual
Installation manual
Shape

for gas pipe

for liquid pipe

CAUTION
Use only those accessories (Standard or optional) which have designated specifications.

Fresh Air Intake Unit _ 26

Indoor Units

Name

Indoor unit
Dip Switch & Group Control Setting
1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor
Standing, Console, Fresh Air Intake Unit
1.1 Dip Switch Setting
1.2 Group Control Setting
1.3 2 Remote Control
1.4 Accessories for group control setting

2. Wall Mounted, ART COOL Gallery, ART COOL Mirror


2.1 Master/Slave Setting
2.2 Group Control Setting
2.3 2 Remote Control
2.4 Accessories for group control setting

1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit
1.1 Dip Switch Setting
Dip Switch Setting of Indoor unit PCB
Function
Communication

Description
N/A (Default)

Setting Off
-

Setting On
-

Default
Off

SW2

Cycle

N/A (Default)

Off

SW3

Group Control

Selection of Master or Slave

Master

Slave

Off

Dry Contact Mode

Selection of Dry Contact


Mode

Wired/Wireless remote
controller
selection of Manual or Auto
operation Mode

Auto

Off

SW5

Installation

Fan continuous operation

Continuous operation Removal

Off

SW6

Heater linkage

N/A

Off

Ventilator linkage

Selection of Ventilator
linkage

Linkage Removal

Working

Vane selection
(Console)

Selection of up/down
side Vane

Up side + Down side Vane

Up side Vane
Only

Region selection

Selection tropical region

General model

Tropical model

Etc.

Spare

SW4

SW7

SW8

Off

Off

CAUTION
For Multi V Models, Dip switch 1, 2, 6, 8 must be set OFF.

Dip Switch & Group Control Setting _ 1

Indoor Units

SW1

1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit
1.2 Group Control 1
Indoor Units

(1) Group Control 1


Wired remote controller 1 + Standard Indoor Units
LGAP Network System

or

Master

Slave

Slave

Slave

Display Error Message


Only connect serial signal and GND lines
between slave indoor unit
Master

Dip Switch in PCB (Cassette and Duct Type indoor units)


- No. 3 Off

- No. 3 On

1. It is possible to 16 indoor units(Max) by one wired remote controller.


Set only one indoor unit to Master, set the others to Slave.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
- The Master indoor unit is possible to recognize Dry Contact and Central Controller only.
- In case of Central controller and Group controller at the same time, it is possible to connect
standard 2series indoor units or later since Feb. 2009.
- In case of Central controller setting, the Central controller can control indoor units after
setting only the address of master indoor unit.
- Slave indoor unit will be operated like master indoor unit.
- Slave indoor unit can not be individually controlled by Central controller.
- Some remote controller cant perform with Dry Contact and Central controller at the same
time. So contact us further information about it.

2 _ Dip Switch & Group Control Setting

GND
Signal
12 V

1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit
5. In case of any error occurs at indoor unit, display on the wired remote controller.
Exception of the error indoor unit, an individual indoor unit control possibility.

Indoor Units

6. In case of Group Control, it is possible to use following functions.


- Selection of operation options (operation/stop/mode/set temperature)
- Control of flow rate (High/Middle/Low)
- It is not possible at some functions.
Master/Slave setting of indoor units be set possible using a PCB Dip Switch.
It is possible to connect indoor units since Feb. 2009.
In the other cases, please contact LGE.
It can be the cause of malfuctions when there is no setting of master and slave.

(2) Group Control 2


Wired remote controllers + Standard Indoor Units
LGAP Network System

or

Slave

Master

Slave

Slave

GND
Signal
12 V

Dont connect serial 12V line

Display Error Message


Master

Slave

It is possible to control N indoor units by wired remote controller M units. (M+N17 Units)
Set only one indoor unit to Master, set the others to Slave.
Set only one wired remote controller to Master, set the others to Slave.
Other than those, it is same with the Group Control 1.

Dip Switch & Group Control Setting _ 3

1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit
(3) Group Control 3
Indoor Units

Mixture connection with indoor units and Fresh Air Intake Unit
LGAP Network System

or

FAU
Master

FAU
Slave

Master

Slave

GND
Signal
12 V

Display Error Message

Master

Master

In case of connecting with standard indoor unit and Fresh Intake Unit, separate Fresh Air Intake
Unit with standard units.
(Because setting temperature are different.)
Other than those, it is same with Group Control 1.

FAU

FAU

Standard

Standard

FAU

FAU

Standard

Standard

* FAU : Fresh Air Intake Unit


Standard: Standard Indoor Unit

4 _ Dip Switch & Group Control Setting

1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit
1.3 2 Remote Control
Wired remote controller 2 + Indoor unit 1

or

Master

Display Error Message


Master

Slave

1. It is possible to connect two wired remote controllers with one indoor unit.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case of any error occurs at indoor unit, display on the wired remote controller.
6. There isnt limits of indoor unit function.
Maximum 2wired remote controllers can be connected with 1 indoor unit.

Dip Switch & Group Control Setting _ 5

Indoor Units

LGAP Network System

1. Cassette, Duct, Ceiling & Floor, Ceiling Suspended, Floor Standing, Console, Fresh Air Intake Unit
1.4 Accessories for group control setting
Indoor Units

It is possible to set group control by using below accessories.


Indoor unit 2 EA +Wired remote controller
PZCWRCG3 cable used for connection

Indoor unit 1 EA +Wired remote controller 2EA


PZCWRC2 cable used for connection

S lave

Mas te r

PZC WRC 2
PZC WRC G3

Maste r

6 _ Dip Switch & Group Control Setting

Maste r

S lave

2. Wall Mounted, ART COOL Gallery, ART COOL Mirror


2.1 Master/Slave Setting

By using the TEMPERATURE SETTING button, set function code


and setting value. (Please refer the Installer Setting Code Table.)
Function Code

Setting Code

Press the ON/OFF button toward the indoor unit 1 time.

Reset the remote controller to use the general operation mode.

Installer Setting Code Table


No.

Function

Function Code

Setting Value

Remote Controller LCD

0 : Set to Master
1

Group Control

1 : Set to Slave
2 : Check Master/Slave

Dip Switch & Group Control Setting _ 7

Indoor Units

With the FAN SPEED button pressed, press the RESET button.

Indoor Units

2. Wall Mounted, ART COOL Gallery, ART COOL Mirror


Group Control Setting
- This function is only for group control.
- Please dont set this function in case of non-group control.
- This function is the Master or Slave setting function of indoor unit
- Set only one indoor unit to Master, set the others to slave.
- After setting Group Control of the product, turn off the power then turn it back on after
1 minute.
- Master checking whether the buzzer sounds, such as indoor rings below.
Master: Beep (Buzzer sound 1 time)
Slave: Beep, Beep, Beep, Beep, Beep (Buzzer sounds 5 times)

2.2 Group Control 1


(1) Group Control 1
Wired remote controller 1 + Standard Indoor Units
LGAP Network System

or

Master

Slave

Slave

Slave

Display Error Message


Only connect serial signal and GND lines
between slave indoor unit
Master

1. It is possible to 16 indoor units(Max) by one wired remote controller.


Set only one indoor unit to Master, set the others to Slave.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.

8 _ Dip Switch & Group Control Setting

GND
Signal
12 V

2. Wall Mounted, ART COOL Gallery, ART COOL Mirror

5. In case of any error occurs at indoor unit, display on the wired remote controller.
Exception of the error indoor unit, an individual indoor unit control possibility.
6. In case of Group Control, it is possible to use following functions.
- Selection of operation options (operation/stop/mode/set temperature)
- Control of flow rate (High/Middle/Low)
- It is not possible at some functions.
Indoor units be set possible using a wireless remote controller.
This indoor unit be set possible using a wireless remote controller for setting group control.
(type : Wall Mounted, ART COOL Gallery, ART COOL Mirror)
It is possible to connect indoor units since Feb. 2009.
In the other cases, please contact LGE.
It can be the cause of malfuctions when there is no setting of master and slave.

Dip Switch & Group Control Setting _ 9

Indoor Units

4. It is possible to connect with Dry Contact and Central controller at the same time.
- The Master indoor unit is possible to recognize Dry Contact and Central Controller only.
- In case of Central controller and Group controller at the same time, it is possible to connect
standard 2series indoor units or later since Feb. 2009.
- In case of Central controller setting, the Central controller can control indoor units after
setting only the address of master indoor unit.
- Slave indoor unit will be operated like master indoor unit.
- Slave indoor unit can not be individually controlled by Central controller.
- Some remote controller cant perform with Dry Contact and Central controller at the same
time. So contact us further information about it.

2. Wall Mounted, ART COOL Gallery, ART COOL Mirror


(2) Group Control 2
Indoor Units

Wired remote controllers + Standard Indoor Units


LGAP Network System

or

Slave

Master

Slave

Slave

Dont connect serial 12V line

Display Error Message


Master

Slave

It is possible to control N indoor units by wired remote controller M units. (M+N17 Units)
Set only one indoor unit to Master, set the others to Slave.
Set only one wired remote controller to Master, set the others to Slave.
Other than those, it is same with the Group Control 1.

10 _ Dip Switch & Group Control Setting

GND
Signal
12 V

2. Wall Mounted, ART COOL Gallery, ART COOL Mirror


(3) Group Control 3
Mixture connection with indoor units and Fresh Air Intake Unit

Indoor Units

LGAP Network System

or

FAU
Master

FAU
Slave

Master

Slave

GND
Signal
12 V

Display Error Message

Master

Master

In case of connecting with standard indoor unit and Fresh Intake Unit, separate Fresh Air Intake
Unit with standard units.
(Because setting temperature are different.)
Other than those, it is same with Group Control 1.

FAU

FAU

Standard

Standard

FAU

FAU

Standard

Standard

* FAU : Fresh Air Intake Unit


Standard: Standard Indoor Unit

Dip Switch & Group Control Setting _ 11

2. Wall Mounted, ART COOL Gallery, ART COOL Mirror


2.3 2 Remote Control
Indoor Units

Wired remote controller 2 + Indoor unit 1


LGAP Network System

or

Master

Display Error Message


Master

Slave

1. It is possible to connect two wired remote controllers with one indoor unit.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case of any error occurs at indoor unit, display on the wired remote controller.
6. There isnt limits of indoor unit function.
Maximum 2wired remote controllers can be connected with 1 indoor unit.

12 _ Dip Switch & Group Control Setting

2. Wall Mounted, ART COOL Gallery, ART COOL Mirror


2.4 Accessories for group control setting
It is possible to set group control by using below accessories.

PZCWRCG3 cable used for connection

Indoor unit 1 EA +Wired remote controller 2EA


PZCWRC2 cable used for connection

S lave

Mas te r

PZC WRC 2
PZC WRC G3

Maste r

Maste r

S lave

Dip Switch & Group Control Setting _ 13

Indoor Units

Indoor unit 2 EA +Wired remote controller

P/No.: MFL61741606

Air Conditioner
20 Yeouido-dong, Yeongdeungpo-gu,
Yeouido P.O.Box 335 Seoul,
150-721, Korea.
http://www.lgeaircon.com

All rights reserved


Printed in Korea March/2010
The specifications, designs, and
information in this brochure are subject to
change without notice.

The air conditioners manufactured by LG have received ISO9001 certificate for


quality assurance and ISO14001 certificate for environmental management system.