DATA SHEET

GV2ME & GV2P


MOTOR
CIRCUIT BREAKER
Based on Schneider DIA1ED2090201EN Catalogue

Thermal-magnetic motor circuit-breakers

Environment

Circuit-breaker type
Conforming to standards

GV2 ME
GV2 P
IEC 60947-1, 60947-2,
60947-4-1,
EN 60204, UL 508,
CSA C 22.2 n 14-05,
NF C 63-650, 63-120, 79-130,
VDE 0113, 0660

GV3 P
IEC/EN
60947-1,
60947-2,
60947-4-1,
UL 508 type E,
CSA C 22.2
n 14-05 type E

GV3 ME80
IEC/EN, NF
EN, BS EN,
DINEN60947-2,
60947-4-1

Product certifications

UL, CSA, CCC,


CEBEC,
GOST, TSE,
BV, GL, LROS ,
DNV, PTB,
EZU, SETI,
RINA, ATEX

UL, CSA,
CCC (pending),
GOST,
ATEX (pending)

UL, CSA,
LROS

TH
IP 20

TC
IP 20

2
3
Protective treatment
Degree of protection

Conforming to
IEC 60529

5
6

Shock resistance

Conforming to IEC 60068-2-27

Vibration resistance

Conforming to IEC 60068-2-6

Ambient air temperature

Storage
Operation

Open mounted
In enclosure
Temperature compensation
Open mounted
In enclosure
Flame resistance
Conforming to IEC 60695-2-1
Maximum operating altitude
Suitable for isolation
Conforming to IEC 60947-1 7-1-6
Resistance to mechanical impact

GV2 Mp01:
IP 41
GV2 Mp02:
IP 55
30 gn -11 ms

C
C
C
C
C
C
m
J

Sensitivity to phase failure

Technical characteristics
Circuit-breaker type

7
8
9
10

GV3 PC01 and


GV3 CE01:
GV3 PC02: IP 55 IP 55

On: 15 gn -11 ms
Off: 30 gn -11 ms
5 gn (5150 Hz)
4 gn
(5300 Hz)
- 40+ 80
- 40+ 80
- 40+ 80
- 20+ 60
- 20+ 60
- 20+ 60 (2)
- 20+ 40
- 20+ 40
- 20+ 40
- 20+ 60
- 20+ 60
- 20+ 60
- 20+ 40
- 20+ 40
- 20+ 40
960
960
2000
3000
Yes
Yes
0.5
0.5
10
IK 04
IK 09
(in enclosure)
Yes, conforming to IEC 60947-4-1 7-2-1-5-2
GV2 ME GV2 P

GV2 RT

GV7 R
IEC 60947-1,
60947-2,
60947-4-1,
EN 60947-1,
60947-2,
EN 60947-4-1,
NF C 63-650,
NF C 63-120,
79-130,
VDE 0113,
0660
UL, DNV,
CCC

TC
IP 405 with
terminal
shrouds

22 gn - 20 ms

15 gn -11 ms

2.5 gn
(025 Hz)
- 40+ 80
- 20+ 60
- 20+ 40
- 20+ 60
- 20+ 40
960
3000

0.5

2.5 gn (25 Hz)

GV3 P

GV3
ME80

A
AC-3
690

A
AC-3
690

A
AC-3
690

GV7
Rp20...
Rp100
A
AC-3
690

690

690

690

750

600

600

600

Hz

50/60

50/60

600
(B600)
50/60

kV

W
C.O.

2.5
100 000

8
50 000

8
30 000

5
50 000

Utilisation category

Conforming to IEC 60947-2


Conforming to IEC 60947-4-1
Rated operational voltage Conforming to IEC 60947-2
(Ue)
Rated insulation voltage
Conforming to IEC 60947-2
(Ui)
Rated voltage
Conforming to CSA C22-2 n 14,
UL 508
Rated operational
Conforming to IEC 60947-4-1
frequency
UL, CSA
Rated impulse withstand Conforming to IEC 60947-2
voltage (U imp)
Total power dissipated per pole
Mechanical durability
(C.O.: Close, Open)
Electrical durability
440 V In/2
for AC-3 duty
440 V In
Duty class (maximum operating rate)
Maximum conventional
Conforming to IEC 60947-4-1
rated thermal current (Ith)
Rated duty
Conforming to IEC 60947-4-1

UL (1), CSA,
PTB, EZU,
GOST, TSE,
DNV, LROS,
GL, BV, RINA,
CCC, ATEX

TH
IP 20

Open mounted
In enclosure

12486

TeSys protection components

Characteristics

- 55+ 95
- 25 + 70

- 25 + 55 (3)

960
2000
Yes
0.5

GV7
Rp150

GV7
Rp220

8.7
40 000

14.5
20 000

50/60

C.O.
C.O.
C.O./h
A

100 000

30 000
50 000
40 000
20 000

50 000

30 000
20 000
10 000
25
25
25
25
0.16
0.16
0.40
13
80
12
150
220
32
32
23
65
100
Continuous duty
(1) UL 508 type E for GV2 PppH7
(2) Leave a space of 9 mm between 2 circuit-breakers: either an empty space, or side mounting addon contact blocks. Side by side mounting is possible up to 40 C.
(3) For operation up to 70 C, please consult your Regional Sales Office.

Based on Schneider DIA1ED2090201EN Catalogue

Page 1 of 18

Characteristics (continued)

12486

TeSys protection components


Thermal-magnetic motor circuit-breakers

Mounting characteristics

90

90

90

90

Operating position
Without derating, in relation to normal vertical mounting plane (1)

Connection characteristics

Connection to screw clamp terminals or spring terminals


Bare cables

Circuit-breaker type
Connection to screw clamp terminals
(2)
Solid cable
(Max. number of
conductors x c.s.a.)
Flexible cable
without cable end
Flexible cable
with cable end
Tightening torque
Connection to spring terminals
Number of conductors x c.s.a.

mm2

GV2 ME
Min.
2x1

Max.
2x6

GV2 P
Min.
2x1

Max.
2x6

GV3 P
Min.
2x1

mm2

2 x 1.5

2x6

2 x 1.5

2x6

2x1

mm2

2x1

2x4

2x1

2x4

2x1

N.m

1.7

1.7

1.7

1.7

Solid cable

mm2

2 x 1 (3)

2x6

Flexible cable
without cable end

mm2

2 x 1.5 (3) 2 x 4

Max.
1 x 25 and
1 x 35
1 x 25 and
1 x 35
1 x 25 and
1 x 35
5: 25 mm2
8: 35 mm2

GV3 ME80
Min.
Max.
1 x 2.5
1 x 35
1 x 2.5

2 x 16

1 x 2.5

2 x 16

4
5

Connection by bars or lugs


Bars or lugs

e
Circuit-breaker type
Pitch

Bars or cables with lugs

L'

Without spreaders

mm

13.5

17.5

GV7
Rp20...Rp100
35

With spreaders

mm

45

45

45

mm

y6

y6

y6

y6

y6

mm

y 9.5

y 13.5

y 25

y 25

y 25

mm

y 9.5

y 16.5

mm

y 10

y 10

y 10

y 10

y 10

M4

M6

M6

M8

M8

Screws

Bare cables (copper or aluminium)


with connectors

GV2 MEpp6

GV3 Ppp6

GV7 Rp150

GV7 Rp220

35

35

Tightening torque

N.m

1.7

10

15

15

Height (h)

mm

20

20

20

C.s.a.

mm2

1.5...95

1.5...95

1.5...185

Tightening torque

N.m

15

15

15

(1) When mounting on a vertical rail, fit a stop to prevent any slippage.
(2) For motor circuit-breakers GV3 P: BTR hexagon socket head screws, EverLink system.
Require use of an insulated Allen key, in compliance with local electrical wiring regulations.
(3) For cross-sections 1 to 1.5 mm2, the use of an LA9 D99 cable end reducer is recommended.

Based on Schneider DIA1ED2090201EN Catalogue

7
8
9
10

Page 2 of 18

12486

TeSys protection components

Characteristics

Thermal-magnetic motor circuit-breakers


GV2 ME and GV2 P

Breaking capacity of GV2 ME and GV2 P

Circuit-breaker type

Rating

Breaking capacity
conforming to IEC 60947-2

A
230/240 V

Icu

kA

Ics % (1)
400/415 V

Icu

kA

Ics % (1)

440 V

Icu

kA

Ics % (1)
500 V

Icu

kA

Ics % (1)
690 V

Icu

kA

Ics % (1)

Associated fuses (if required)


if Isc > breaking capacity Icu
conforming to IEC 60947-2

230/240 V

400/415 V

6
440 V

500 V

690 V

GV2 ME
01 07 08
to
06
0.1 2.5 4
to
1.6
g g g

10

14

16

20

6.3 10

14

18

21
&
22
23
&
25
50

15

15

15

50

50

50

15

75

75

75

32
50

GV2 P
01 07 08
to
06
0.1 2.5 4
to
1.6
g g g

10

14

16

20

32

21
&
22
23
&
25
g

6.3 10

14

18

32
g

100 100 g

10

50

50

50

40

50

50

50

50

50

20

20

20

50

50

50

75

75

75

75

50

42

10

10

10

75

75

75

100 75

75

75

75

75

75

75

75

75

80

80 g

100 100 g

100 100 50
50

32

10

100 100 75

100 100 100 100 100 100 100 100

aM

gG

aM

63

63

100 100 100

gG

80

80 100 100 g

125 125 125

aM

50

50

50

50

63

63

50

63

gG

63

63

63

63

80

80

63

80 100 100

aM

50

50

50

50

50

50

50

50

50

50

50

gG

63

63

63

63

63

63

63

63

63

63

63

aM

16

25

32

32

40

40

40

40

20

25

40

40

50

50

50

50

gG

20

32

40

40

50

50

50

50

25

32

50

50

63

63

63

63

80

80

80

80

g > 100 kA.


(1) As % of Icu.

9
10

Based on Schneider DIA1ED2090201EN Catalogue

Page 3 of 18

TeSys protection components

Characteristics (continued)

12486

Thermal-magnetic motor circuit-breakers


GV2 ME and GV2 P

Breaking capacity of GV2 ME and GV2 P (used in association with current limiter GV1 L3)
Circuit-breaker type

GV2 ME
01 to 06 07
0.1 to
2.5
1.6

08
4

10
6.3

14
10

16
14

20
18

21
23

22
25

32
32

100

100

100

100

100

50

50

40

40

40

50

20

20

20

20

75

75

75

75

75

50

42

10

10

10

10

100

100

75

75

75

75

GV2 P
01 to 06 07
0.1 to
2.5
1.6

08
4

10
6.3

14
10

16
14

20
18

21
23

22
25

32
32

100

100

100

100

100

50

50

50

50

50

100

100

100

100

100

100

50

50

50

50

50

50

50

50

50

50

50

50

50

50

50

GV2 ME
01 to 06 07
0.1
2.5
to 1.6

08
4

10
6.3

14
10

16
14

20
18

21
23

22
25

32
32

1 mm2

y 10 kA y 6 kA

(2)

(2)

(2)

(2)

(2)

1.5 mm2

y 20 kA y 10 kA (2)

(2)

(2)

(2)

(2)

2.5 mm2

(2)

46 mm2

Rating
Breaking capacity
conforming to IEC 60947-2

A
230/240 V

Icu

kA

Ics % (1)
400/415 V

Icu

kA

Ics % (1)
440 V

Icu

kA

Ics % (1)
500 V

Icu

kA

Ics % (1)
Circuit-breaker type
Rating
Breaking capacity
conforming to IEC 60947-2

A
230/240 V

Icu

kA

Ics % (1)
400/415 V

Icu

kA

Ics % (1)
440 V

Icu

kA

Ics % (1)
500 V

Icu

kA

Ics % (1)
690 V (3)

Icu = Ics

kA

Circuit-breaker type
Rating
Cable protection against
thermal stress in the
event of short-circuit
(PVC insulated copper cables)

A
Minimum
c.s.a.
protected
at 40 C
at Isc max.

g > 100 kA
p Cable c.s.a. protected
(1) As % of Icu
(2) Cable c.s.a. not protected
(3) With limiter LA9 LB920

1
2
3
4
5
6
7
8
9
10

Based on Schneider DIA1ED2090201EN Catalogue

Page 4 of 18

12486

TeSys protection components

Characteristics

Thermal-magnetic motor circuit-breakers


Electric trips

Characteristics of electric trips

1
2

Circuit-breaker type
Type of trip
Rated insulation voltage (Ui)

Conforming to IEC 60947-1

Operational voltage

Conforming to CSA C22-2 n 14, V


UL 508
Conforming to IEC 60947-1
V

Operating time

4
5
6

600

600

600 (B600) 600 (B600) 600

600

0.7
1.1 Un
0.75
0.2 Un
14

0.85
1.1 Un
0.7
0.35 Un
12

0.81.1 Un

0.7
1.1 Un
0.2
0.75 Ue

12

0.85
1.1 Un
0.35
0.7 Ue
< 10

GV3 B
690

GV7 R
GV3 D
690

GV7 AU
690

GV7 AS
690

VA

10.5

<5

VA

3.5

3.5

<5

1.1

1.6

1.1

2.5

<5

ms

From the moment the voltage reaches its operational value until opening of the
circuit-breaker.
1015
10
15
< 50

Conforming to IEC 60947-1

On-load factor
Cabling

GV3 ME80

Sealed consumption

GV2 ME
only
GV AX (1)
500

0.85
1.1 Un
0.7
0.35 Un
12

Drop-out voltage
Inrush consumption

GV2 ME, GV2 P


GV3 P, GV3 L
GV AU
GV AS
690
690

Number of conductors

0.70.35 Un

100 %

100 %

100 %

2 or 4

1 or 2

Solid cable

mm2

12.5

12.5

1.5

Flexible cable without cable end

mm2

0.752.5

0.752.5

1.5

Flexible cable with cable end

mm2

0.751.5

0.752.5

Tightening torque

N.m

1.4 max

1.2

1.2

Mechanical durability
(C.O.: Close - Open)

C.O.

30 000 (GV2 ME and GV2 P)


50 % of the mechanical durability of the
10 000 (GV3 P and GV3 L)
circuit-breaker
(1) Wiring scheme of undervoltage trip for dangerous machines (conforming to INRS) on GV2 ME
only.

7
8
9
10

Based on Schneider DIA1ED2090201EN Catalogue

Page 5 of 18

Characteristics

TeSys protection components

12486

Thermal-magnetic and magnetic motor


circuit-breakers GV2 and GV3
Accessories

Characteristics of 3-pole busbars GV2 Gppp and GV3 Gp64


Rated insulation voltage (Ui)

Conforming to IEC 60947-1

GV2 Gppp
690

GV3 Gp64
690

Conventional
thermal current (Ith)
Permissible
peak current (I peak)
Permissible
thermal limit (I2t)
Degree of protection

Conforming to IEC 60439-1

63

115

kA

11

20

kA2s

104

300

IP 20

IP 20

Yes

Conforming to IEC 60529

Terminal block

1
2

Characteristics of terminal blocks GV2 G05 and GV1 G09 (for GV2 ME and GV2 P)
Rated insulation voltage (Ui)

Conforming to IEC 60947-1

690

Conventional
thermal current (Ith)
Degree of protection

Conforming to IEC 60439-1

63

Conforming to IEC 60529

Connection

IP 20

Solid cable

mm

1 x 1.5 to 25 conductor or 2 x 1.5 to 6 conductors

Flexible cable without cable end

mm2

1 x 1.5 to 16 conductor or 2 x 2.5 to 4 conductors

Flexible cable with cable end

mm

1 x 1.5 to 10 conductor or 2 x 1.5 to 2 conductors

Flexible or solid cable AWG


Tightening torque

3
4

1 AWG 4

Connector

N.m

2.2

Screw clamp terminals

N.m

1.7

Characteristics of current limiters (GV2 ME and GV2 P)


Type
Rated insulation voltage (Ui)
Conventional
thermal current (Ith)
Operating threshold

Conforming to IEC 60947-1

GV1 L3
690

LA9 LB920
690

Conforming to IEC 60947-1

63

63

rms current

1500 (non adjustable threshold)

1000 (non adjustable threshold)

1 conductor

2 conductors

1 conductor

2 conductors

Connection

Tightening torque

Solid cable

mm2

1.525

1.510

1.525

1.510

Flexible cable without cable end

mm2

1.525

2.510

1.525

1.510

Flexible cable with cable end

mm2

1.516

1.5 4

1.516

1.5 4

N.m

2.2

6
7
8
9
10

Based on Schneider DIA1ED2090201EN Catalogue

Page 6 of 18

TeSys protection components

Curves

12486

Thermal-magnetic motor circuit-breakers


GV2 ME and GV2 P

Thermal-magnetic tripping curves for GV2 ME and GV2 P

Average operating times at 20 C related to multiples of the setting current


Time (s)

10 000

2
3

1000

100

1
10

2
3

4
1

5
0,1

6
7

0,01

0,001

1,5

10

100
x the setting current (Ir)

1 3 poles from cold state


2 2 poles from cold state
3 3 poles from hot state

8
9
10

Based on Schneider DIA1ED2090201EN Catalogue

Page 7 of 18

TeSys protection components

Curves (continued)

12486

Thermal-magnetic motor circuit-breakers


GV2 ME and GV2 P

Current limitation on short-circuit for GV2 ME and GV2 P (3-phase 400/415 V)

Dynamic stress

I peak = f (prospective Isc) at 1.05 Ue = 435 V


Limited peak current (kA)

100

=0

.3

=0

.25

2
3

=0

.5

4
5

10

=0
.7

0.8

0.9

co

=0

.95

5
10

11

0,1
0,1

6
7

10

15 (12)

100
Prospective Isc (kA)

1 Maximum peak current


2 24 -32 A
3 20 -25 A
4 17 -23 A
5 13 -18 A
6 9 -14 A
7 6 -10 A
8 4 -6.3 A
9 2.5 -4 A
10 1.6 -2.5 A
11 1 -1.6 A
12 Limit of rated ultimate breaking capacity on short-circuit of GV2 ME (14, 18, 23 and 25 A ratings)

8
9
10

Based on Schneider DIA1ED2090201EN Catalogue

Page 8 of 18

TeSys protection components

Curves (continued)

12486

Thermal-magnetic motor circuit-breakers


GV2 ME

Thermal limit on short-circuit for GV2 ME

Thermal limit in kA2s in the magnetic operating zone


Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V
Sum of I2dt (kA2s)

100

2
3
4
5

6
7

10

9
1

5
6
7
8
9

10

0,1

0,01

0,1

10

100
Prospective Isc (kA)

1 24 -32 A
2 20 -25 A
3 17 -23 A
4 13 -18 A
5 9 -14 A
6 6 -10 A
7 4 -6.3 A
8 2.5 -4 A
9 1.6 -2.5 A
10 1 -1.6 A

10

Based on Schneider DIA1ED2090201EN Catalogue

Page 9 of 18

TeSys protection components

Curves (continued)

12486

Thermal-magnetic motor circuit-breakers


GV2 P

Thermal limit on short-circuit for GV2 P

Thermal limit in kA2s in the magnetic operating zone

Sum of I2dt = f (prospective Isc) at 1.05 Ue = 435 V


Sum of I2dt (kA2s)

100

1
2
3

4
5
6

10

0,1

0,01

1
1
2
3
4
5
6
7
8
9

6
7

0,1

10

24 -32 A
20 -25 A
17 -23 A
13 -18 A
9 -14 A
6 -10 A
4 -6.3 A
2.5 -4 A
1.6 -2.5 A
1 -1.6 A

100
Prospective Isc (kA)

8
9
10

Based on Schneider DIA1ED2090201EN Catalogue

Page 10 of 18

533886

3
4
5
6
7

Thermal-magnetic motor circuit-breakers


GV2 ME

Motor circuit-breakers from 0.06 to 15 kW / 400 V, with screw clamp terminals


GV2 ME with pushbutton control

1
2

12486

TeSys protection components

References

Standard power ratings of 3-phase motors


50/60 Hz in category AC-3
400/415 V
500 V
690 V
P
Icu Ics
P
Icu Ics (1) P
Icu
(1)
kW kA
%
kW kA
%
kW kA

Setting
range
of thermal
trips
Ics (1)
(2)

Magnetic
tripping
current
Id 20 %

A
0.10.16

A
1.5

GV2 ME01

kg
0.260

Reference

Weight

GV2 ME10
0.06

0.160.25

2.4

GV2 ME02

0.260

0.09

0.250.40

GV2 ME03

0.260

0.12
0.18

g
g

g
g

0.37 g

0.400.63

GV2 ME04

0.260

0.25

0.55 g

0.631

13

GV2 ME05

0.260

0.37
0.55

0.75

g
g

g
g

0.37
0.55
0.75
1.1

g
g
g
g

g
g
g
g

0.75
1.1
1.5

g
g
3

g
g
75

116

22.5

GV2 ME06

0.260

1.62.5

33.5

GV2 ME07

0.260

1.1
1.5

g
g

g
g

1.5
2.2

g
g

g
g

2.2
3

3
3

75
75

2.54

51

GV2 ME08

0.260

2.2

50

100

75

46.3

78

GV2 ME10

0.260

3
4

g
g

g
g

4
5.5

10
10

100
100

5.5
7.5

3
3

75
75

610

138

GV2 ME14

0.260

5.5

15

50

7.5

75

9
11

3
3

75
75

914

170

GV2 ME16

0.260

7.5

15

50

75

15

75

1318

223

GV2 ME20

0.260

15

40

11

75

18.5 3

75

1723

327

GV2 ME21

0.260

11

15

40

15

75

2025

327

GV2 ME22 (3)

0.260

15

10

50

18.5 4

75

22

75

2432

416

GV2 ME32

0.260

Motor circuit-breakers from 0.06 to 15 kW / 400 V, with lugs

8
9

To order thermal magnetic circuit-breakers with connection by lugs, add the digit 6 to the end of reference selected
above.
Example: GV2 ME08 becomes GV2 ME086.
Thermal magnetic circuit-breakers GV2 ME with built-in auxiliary contact block
With instantaneous auxiliary contact block :
b GV AE1, add suffix AE1TQ to the motor circuit-breaker reference selected above.
Example: GV2 ME01AE1TQ.
b GV AE11, add suffix AE11TQ to the motor circuit-breaker reference selected above.
Example: GV2 ME01AE11TQ.
b GV AN11, add suffix AN11TQ to the motor circuit-breaker reference selected above.
Example: GV2 ME01AN11TQ.
These circuit-breakers with built-in contact block are sold in lots of 20 units in a single pack.

10

(1)
1) As % of Icu.
(2) The thermal trip setting must be within the range marked on the graduated knob.
(3) Maximum rating which can be mounted in enclosures GV2 MC or MP, please consult your Regional Sales Office.
g > 100 kA.

Based on Schneider DIA1ED2090201EN Catalogue

Page 11 of 18

TeSys protection components

References (continued)

12486

Thermal-magnetic motor circuit-breakers


GV2 ME

533897

Motor circuit-breakers from 0.06 to 11 kW, with spring terminal connections


GV2 ME (1) with pushbutton control

Standard power ratings of 3-phase motors


50/60 Hz in category AC-3
P

Icu

Ics (2)

Icu

Ics (2)

Setting
range
of thermal
trips
(3)

kW

kA

kW

kA

A
0.10.16

A
1.5

GV2 ME013

kg
0.280

0.06

0.160.25

2.4

GV2 ME023

0.280

0.09

0.250.40

GV2 ME033

0.280

0.12
0.18
0.25
0.37
0.37
0.55

g
g
g
g
g
g

g
g
g
g
g
g

0.400.63

GV2 ME043

0.280

0.37

0.631

13

GV2 ME053

0.280

GV2 ME063

0.280

g
g
g
g

22.5

g
g
g
g

11.6

0.75

0.37
0.55
0.75
1.1

1.62.5

33.5

GV2 ME073

0.280

1.1
1.5
2.2

g
g
g

g
g
g

1.5
2.2
3

g
g

g
g

2.54

51

GV2 ME083

0.280

50

100

46.3

78

GV2 ME103

0.280

3
4
5.5

g
g

g
g

100
100
75

138

GV2 ME143

0.280

50

10
10
6

610

15

4
5.5
7.5

914

170

GV2 ME163

0.280

7.5

15

50

75

1318

223

GV2 ME203

0.280

9
11
11

15
15
15

40
40
40

11

75

1723

327

GV2 ME213

0.260

15

75

2025

327

GV2 ME223

0.260

Front

Maximum
number
1

LH side

Type of
contacts
N/O + N/C
N/O + N/O
N/O + N/C
N/O + N/O

400/415 V

GV2 MEpp3

500 V

Magnetic
tripping
current
Id 20 %

Reference

Weight

1
2
3
4
5

Contact blocks
Description
Instantaneous
auxiliary contacts

Mounting

Sold in
lots of
10
10
1
1

Unit
reference
GV AE113
GV AE203
GV AN113
GV AN203

Weight
kg
0.030
0.030
0.060
0.060

Sold in
lots of
20

Unit
reference

Weight
kg

Accessory
Description
Cable end reducer

Application
For connection of conductors from 1 to 1.5 mm2

LA9 D99

6
7

LA9 D99
(1) For connection of conductors from 1 to 1.5 mm2, the use of an LA9 D99 cable end reducer is recommended.
(2) Maximum rating which can be mounted in enclosures GV2 MC or MP, please consult your Regional Sales Office
(3) The thermal trip setting must be within the range marked on the graduated knob.
g > 100 kA.

8
9
10

Based on Schneider DIA1ED2090201EN Catalogue

Page 12 of 18

Thermal-magnetic motor circuit-breakers


GV2 P, GV3 P and GV3 ME80
0

Motor circuit-breakers from 0.06 to 30 kW / 400 V

510564

Standard power ratings of 3-phase motors


50/60 Hz in category AC-3
400/415 V
500 V
690 V
P
Icu Ics
P
Icu Ics
P
Icu
(1)
(1)
kW kA %
kW kA %
kW kA

GV2 P: control by rotary knob

12486

TeSys protection components

References

GV2 P10

510617

Screw clamp terminals

g
0.06 g

g
0.09 g

g
0.12 g

g
0.18 g

g
0.25 g

g
0.37 g
0.37
g
0.55 g
0.55
g
0.75 g
1.1
g
1.1 g
1.5
g
2.2 g
3
g
g
3
5
g
5.5 g
7.5

7.5 50 50
9
9
50 50
11
11
50 50
15
15
35 50
18.5

g
g
g
g
g

g
g
g
g
g

50
42

10
10
10
10

100
75

75
75
75
75

0.37

0.55

0.75
1.5
2.2
4
5.5
9
11
15
18.5

22

Ics
(1)
%

g
8
8
6
6
6
6
4
4

g
100
100
100
100
100
100
100
100

100

Setting
range
of thermal
trips
(2)

Magnetic
tripping
current
Id 20 %

0.10.16
0.160.25
0.250.40
0.400.63

1.5
2.4
5
8

GV2 P01
GV2 P02
GV2 P03
GV2 P04

0.350
0.350
0.350
0.350

0.631
11.6

13
22.5

GV2 P05
GV2 P06

0.350
0.350

1.62.5
2.54
46.3
610
914

33.5
51
78
138
170

GV2 P07
GV2 P08
GV2 P10
GV2 P14
GV2 P16

0.350
0.350
0.350
0.350
0.350

1318
1723
2025
2432

223
327
327
416

GV2 P20
GV2 P21
GV2 P22
GV2 P32

0.350
0.350
0.350
0.350

913
1218
1725
2332
3040
3750
4865

182
252
350
448
560
700
910

GV3 P13
GV3 P18
GV3 P25
GV3 P32
GV3 P40
GV3 P50
GV3 P65

0.960
0.960
0.960
0.960
0.960
0.960
0.960

Reference

Weight

kg

GV3 P: control by rotary knob


Connection by EverLink BTR screw connectors (3)
5.5 100 100
7.5 12 50
11
6
50
9
12 50
15
6
50
7.5 100 100
11
100 100
15
12 50
18.5 6
50
15
100 100
18.5 12 50
22
6
50
18.5 50 100
22
12 50
37
6
50
22
50 100
30
12 50
45
6
50
30
50 100
45
12 50
55
6
50

5
6

Connection by EverLink BTR screw connectors, for assembly with a contactor

GV3 P65

To assemble a GV3 P40 to P65 circuit-breaker with an LC1 D40A to D65A contactor, it is possible to use the
circuit-breaker supplied without downstream EverLink power terminal block. To order this product, add the
digit 1 to the end of the references selected above. Example: GV3 P65 becomes GV3 P651.
Connection by lugs

510992

To order thermal magnetic circuit-breakers with connection by lugs, add the digit 6 to the end of reference selected
above. Example: GV3 P18 becomes GV3 P186.
GV3 ME80: pushbutton control, screw clamp terminals
37

15

50

45

100

55

100

5680

GV3 ME80 (4)

0.700

Motor circuit-breakers up to 50 hp / 600 V, UL 508 type E

8
GV3 P651

9
10

GV2 (5)
To obtain a GV2 P motor circuit-breaker, UL 508 type E, combine:
b a circuit-breaker GV2 PppH7 (except 32 A),
b and a Large Spacing adapter GV2 GH7.
GV3 (6)
To obtain a motor-circuit-breaker GV3 P, UL 508 type E, use the following with the circuit-breaker:
b a Large Spacing cover GV3 G66,
b a short-circuit signalling contact GV AM11.
GV3 with connection by lugs (6)
To obtain a motor-circuit-breaker GV3 P, UL 508 type E, with connection by lugs, add the digit 6 to the end of
reference selected above and use the following with the circuit-breaker:
b two IP 20 covers LAD 96570,
b a short-circuit signalling contact GV AM11.
(1)
1) As % of Icu.
(2) The thermal trip setting must be within the range marked on the graduated knob.
(3) BTR screws: hexagon socket head. Require use of an insulated Allen key, in compliance with local wiring regulations.
(4) Recommended for use in association with a contactor.
(5) Accessory.
(6) Accessories.
g > 100 kA.

Based on Schneider DIA1ED2090201EN Catalogue

Page 13 of 18

TeSys protection components

Dimensions

Thermal-magnetic motor circuit-breakers


GV2 ME and GV2 P

Dimensions
GV2 ME

GV AD, AM, AN, AU,


AS, AX

GV AE

Block GV AD, AM, AN


Block GV AU, AS, AX

15

46
15,7

X1

45

10

67,2

GV AX

X1

11

12486

44,5

16

9,3

9,3

18

81(1)

b
GV2 MEpp
89
101
GV2 MEpp3
(1) Maximum
Maximum
X1
1 Electrical clearance = 40 mm for e y
Electrical clearance = 40 mm for e 690 V

GV2 P

GV AD, AM, AN, AU, AS

14

98

26
15

50
82

X2

61
=

45

89

32

X1

Block GV AD, AM, AN


Block GV AU, AS

GV2 AK00

44,5

9,3

9,3

18

81(1)

44,5

(1) Maximum
X1
1 Electrical clearance = 40 mm for e y 415 V, or 80 mm for e = 440 V,
Electrical clearance = 40 mm for e
or 120 mm for e = 500 and 690 V
X2 = 40 mm

GV2 GH7

15

70

44,5

Based on Schneider DIA1ED2090201EN Catalogue

Page 14 of 18

Mounting,
dimensions

12486

TeSys protection components


Thermal-magnetic motor circuit-breakers
GV2 ME and GV2 P

Mounting
GV2 ME

On 35 mm 5 rail

On panel with adapter plate GV2 AF02

On pre-slotted plate
AM1 PA

On rails DZ5 MB201

15

AF1 EA4

35

60

50

50/60

50/60

4,2

35

80

DZ5 ME8

35
GV2 AF02

DZ5 MB201

c = 78.5 on AM1 DP200 (35 x 7.5)


c = 86 on AM1 DE200, ED200 (35 x 15)

GV2 P
On rail AM1 DE200, ED200
(35 x 15)

Panel mounted

On pre-slotted plate
AM1 PA

Adapter plate GK2 AF01

45

135

84

106

13,5

Dimensions

35

45

44,5

84

105 5

55

44,5

35

AF1 EA4

13,5

24

9,5

GV2 AF3

Combination GV2 ME + TeSys k contactor

Combination GV2 ME + TeSys d contactor

Combination GV2 P + TeSys d contactor

152

GV2 AF01

54

79

45

c1

c1
c
d1
d

45

GV2 ME +
b
c1
c

Based on Schneider DIA1ED2090201EN Catalogue

LC1 D09
D18
176.4
94.1
99.6

LC1 D25
and D32
186.8
100.4
105.9

GV2 P +
b
c1
c
d1
d

45

LC1 D09
D18
176.4
100.1
105.6
95
100.5

LC1 D25
and D32
186.8
106.4
111.9
95
100.5

Page 15 of 18

12486

TeSys protection components

Dimensions,
mounting (continued)

Thermal-magnetic motor circuit-breakers


GV2 ME and GV2 P

Dimensions (continued)
GV2 AF4 + LAD 311
Combination GV2 ME + TeSys d contactor

Combination GV2 P + TeSys d contactor

GV2 ME +
b
c1
c
d1
d

c1
c

45

LC1 D09D18
176.4
103.1
135.6
107
112.5

LC1 D25 and D32


186.8
136.4
141.9
107
112.5

45

GV2 P +
b
c1
c

LC1 D09D18
176.4
136.5
141.6

LC1 D25 and D32


186.8
142.4
147.9

7.5 mm height compensation plate GV1 F03

40

39

X1

GV2 ME + GV1 L3 (current limiter)

35

129

89

45

13

44,5

X1

77

b
234

125 3

c1
c
d1
d

234

125 3

X1 = 10 mm for e = 230 V
or 30 mm for 230 V < Ue y 690 V

Mounting

Mounting of external operator GV2 AP01 or GV2 AP02 for motor circuit-breakers GV2 P

54

65

Door cut-out

1,5...5
53

=
135284

=
54

5,2
=

Based on Schneider DIA1ED2090201EN Catalogue

Page 16 of 18

TeSys protection components

Dimensions,
mounting (continued)

12486

Thermal-magnetic motor circuit-breakers


GV2 ME and GV2 P

GV2 ME, GV2 P

Sets of busbars GV2 G445, GV2 G454, GV2 G472, with terminal block GV2 G05
a
p

63

18

45
l
179
206
260

GV2 G445 (4 x 45 mm)


GV2 G454 (4 x 54 mm)
GV2 G472 (4 x 72 mm)

p
45
54
72

Number of tap-offs
GV2 G445
GV2 G454
GV2 G472

Sets of busbars GV2 Gppp with terminal block GV1 G09

a
5
224
260
332

6
269
314
404

7
314
368
476

8
359
422
548

Sets of busbars GV2 G245, GV2 G254, GV2 G272


l

38

GV1 G09

GV2 G245 (2 x 45 mm)


GV2 G254 (2 x 54 mm)
GV2 G272 (2 x 72 mm)

l
89
98
116

Sets of busbars GV2 G554

Sets of busbars GV2 G345 and GV2 G354


260

GV2 G345 (3 x 45 mm)


GV2 G354 (3 x 54 mm)

l
134
152

Based on Schneider DIA1ED2090201EN Catalogue

Page 17 of 18

TeSys protection components

Schemes

Thermal-magnetic motor circuit-breakers


GV2 ME, GV2 P, GV3 P and GV2 RT

3/L2

5/L3

4/T2

6/T3

5/L3
6/T3

1/L1

3/L2
4/T2

5/L3
6/T3

GV3 Ppp

1/L1

3/L2
4/T2

GV2 Ppp

2/T1

1/L1

GV2 MEpp and GV2 RT

2/T1

Schemes

2/T1

12486

Front mounting add-on contact blocks


Instantaneous auxiliary contacts

Front mounting add-on contact blocks


Instantaneous auxiliary contacts and fault signalling contacts

GV AE1

GV AED101

GV AE11

GV AE20

GV AED011

21
22

97

23
24

98

97
98

23

21
22

24

13
14

13

11
12

14

13
14

or

Side mounting add-on contact blocks


Instantaneous auxiliary contacts and fault signalling contacts

Current limiter

Connection
onnection of undervoltage trip for dangerous machines
(conforming to INRS) on GV2 ME only

D2

D1

5/L3

10Agl max

3/L2

GV AD10pp

1/L1

GV AM11

5/L3

D2
E2

Use
se of fault signalling contact
and short-circuit signalling contact

GV1 L3
3/L2

D1

D1
D2

GV AXppp

E1

D1
D2

GV ASppp

1/L1

Voltage trips
GV AUppp

51

08
06

43
(73)
44
(74)

05

(63)
33

GV AN20

(64)
34

43
(73)
44
(74)

GV AM11

(61)
31

Short-circuit signalling contacts

GV AN11

(62)
32

Instantaneous auxiliary contacts

52

98

53

97

GV AD1001

54

97

51
52

GV AD1010

98

95

53

GV AD0101

96

95
96

54

GV AD0110

Short-circuit
signalling

E2

Based on Schneider DIA1ED2090201EN Catalogue

6/T3

4/T2

N/C or N/O
Start-Stop contact

2/T1

Trip signalling

E1

Page 18 of 18