Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Test technique
IEC 60076-3
Test technique
IEC 60076-2
2. Impulse test
IEC 60076-3
Test technique
IEC 60076-1
As you can see in the tables the new type of MCSR testing is measurements of EMP parameters
during rated power absorption (table 1, it.7).
Testing with bringing MCSR EMP at rated power at factory is performed in mode of current
inductance-capacitance resonance with the usage as the source of AC voltage of low-cosine
synchronous generators with electric drive. The peculiarity of such generators is that they can
supply only active-inductive load. If there appears capacitive current in the stator windings
magnetic flux created by such windings coincides with the rotor magnetizing flux, generator will
self-excite and become uncontrolled. Test pattern is shown in figure 1.
2 | Testing of Magnetically Controlled Shunt Reactors
Using equipment shown in figure 1 the process of bringing of MCSR EMP into the mode of
rated power absorption is performed according to the following algorithm:
1. The operability of test pattern at no-load is checked. Thereto the rated voltage is supplied
from G1 generator through the matching transformer to PW, capacitor bank and biasing system
(SRT and ACS) are disconnected.
It checks the value of supplied voltage and EMP PW inductance with the IS measuring system.
After that G1 generator is disconnected.
2. The capacitor bank and the biasing system are connected. Initial biasing current which is
approx. 200 A is created in EMP CtrW with the help of ACS and SC of initial biasing supplied by
the auxiliaries.
At the same time control signals from ACS are signaled to the main SC, supplied from EMP CW,
and these signals move ACS thyristors into the diode mode.
3. G1 generator is turned on and through the matching transformer voltage is supplied to PW,
the value of this voltage is determined by the generator remanent voltage.
4. Voltage supplied to EMP PW is increased smoothly. At the same time the values of EMP PW
inductance, G1 generator current and EMP CtrW current are controlled all the time.
Figure 1 MCSR EMP test circuit diagram in the mode of rated power absorption
3 | Testing of Magnetically Controlled Shunt Reactors
Figure 2 Voltage-current characteristic of the elements of equipment during the MCSR EMP
testing at the rated power absorption mode
4 | Testing of Magnetically Controlled Shunt Reactors
Test technique
Manufacturers technique
Manufacturers technique
Manufacturers technique
Test technique
Manufacturers technique
Manufacturers technique
Manufacturers technique
Test technique
Test technique
Manufacturers technique
Manufacturers technique
Test technique
Manufacturers technique
Test technique
Checking of operation of measuring lines (table 7, it.2) is performed by transfer of model signals
from simulators of substation equipment to ACS inputs and control of the signal values at ACS
display equipment.
Checking of operation of control lines (table 7, it.3) is performed by measurement of ACS
command signals with standard measuring tools.
Checking of insulation resistance of electrically separated circuits (table 7, it.4) is perform by
measurement of resistance between them and also between them and the case with the help
of standard measuring tools.
Checking of system algorithms and software (table 8, it.1) is performed by transfer of test
signals from simulators of substation equipment to ACS inputs and control of the command
signal values at ACS outputs.
Testing of MCSR at Clients site
Second stage of MCSR tests is performed at electric power station (at Clients site) after
mounting and MCSR connection to the grid.
Operational program is agreed with the Client and the scope of tests is indicated in table 10.
Table 10 MSCR tests at site
Type of test
Test technique
During checking of ACS and SRT operation (table 10, it.2, it.3) SRT is disconnected from the
MCSR CtrW and is connected to active load. At the same time MCSR CtrW bushings are
grounded.
Checking the operation of ACS and SRT, connected to the auxiliary network of the substation
(table 10, it.2), is performed by transmitting ACS control signals to the SRT and controlling
active load voltage at the SRT outlet.
Checking the operation of ACS and SRT, connected to the CW of the MCSR (table 10, it.3) is
performed at no-load operation mode of MCSR by transmitting ACS control signals to the SRT
and controlling active load voltage at the SRT outlet.
Checking of MSCR operation at manually regulated operational mode (table 10, it.4) is
performed in accordance with MCSR main connection diagram by transmitting ACS control
signals to SRT at the manual mode of current regulation of MCSR PW and by controlling main
MCSR parameters by means of ACS and other substation equipment. During the checkup there
have to be performed adjustment of magnitude of MSCR initial biasing current, testing of
blocking of MCSR energizing in case of initial biasing failure, registration of MCSR regulation
characteristics, testing of differential protection.
Checking of MSCR automated operational modes (table 10, it.5) is performed by transmitting
ACS control signals to SRT at the automatic mode of current regulation of MCSR PW (or MCSR
power) and at the automatic voltage regulation at the point of MCSR connection to the grid
and by controlling main MCSR parameters by means of ACS and other substation equipment.
Testing of MCSR dynamic characteristics (table 10, it.5) is performed by introducing step
changes of set value of regulated variable (voltage or current in PW) in the ACS. Step changes
are intended to switch MCSR into power gain mode (from no-load mode to rated power
absorption mode) or into power reduction mode (from rated power absorption mode to noload mode) with maximum operation speed. Oscillograms of voltages and currents in MCSR PW
and CtrW are recordered with the help of MCSR ACS and other substation equipment (e.g.
figures 3 and 4).
MCSR line operation for 72 hours (table 10, it.6) is performed at standard automatic mode with
controlled values set by the Client (voltage at the point of MCSR connection to the grid or
MCSR current (power)). MCSR parameters are controlled by the means of ACS and other
substation equipment.
After successful operation within 72 hours MCSR is considered to be put into operation.
Figure 3 PW voltage, PW and CtrW current oscillgram during a three phase180 MVAr/500 kV
MCSR transfer from no-load mode to rated power absorption operation mode.
Figure 4 PW voltage, PW and CtrW current oscillgram during a three phase180 MVAr/500 kV
MCSR transfer from rated power absorption mode to no-load mode of operation.
9 | Testing of Magnetically Controlled Shunt Reactors
Testing methods described in this article are used at PJSC Zaporozhtransformator (Ukraine) for
more than 10 years and prove that magnetically controlled shunt reactors with voltage range
from 110 kV and up to 500 kV and power range from 25 MVAr up to 180 MVAr are reliable in
operation.
Copyright 2014 Zaporozhtransformator PJSC. The document, or parts thereof, should not be
copied, adapted, redistributed, or otherwise used without the prior written permission of
Zaporozhtransformator PJSC.
10 | Testing of Magnetically Controlled Shunt Reactors