- Risk of Sub-Standard
Cables
Presented By
Lokman A. Dahlan
Technical Advisor
Organized by:
www.mcma.org.my
PUBLICATION
MS 2108: 2007
MS 2109: 2007
MS 2110 :2007
MS 2111: 2007
MS 2113*
MS 2114*
MS 2115*
MS 2116*
MS 2117*
MS 2118*
MS 2119*
MS 2120*
MS 2104:2007
MS 2105:2007
MS 2106:2007
MS 2107: 2007
MS 2100:2006
MS 2101:2006
MS 2102:2007
MS 2103: 2007
MS 2112-1: 2009
MS 2112-2: 2009
MS 2112-3: 2009 **
MS 2112-4: 2009 **
MS 2112-5: 2009 **
MS 2112-6: 2009 **
MS 2121*
MS 2122*
MS 2123*
MS 2124*
MS 2125*
MS 2126*
DESCRIPTION/TITLE
REMARKS
Electric Cable : 6.35/11(12)kV single core XLPE insulated cables non-armoured
Electric Cable : 6.35/11(12)kV single core XLPE insulated cables armoured
Electric Cable : 19/33(36)kV single core XLPE insulated cables non-armoured
Electric Cable : 19/33(36)kV single core XLPE insulated cables armoured
Electric Cable : 12.7/22(24)kV single core XLPE insulated cables non-armoured
Electric Cable : 12.7/22(24)kV single core XLPE insulated cables armoured
MV-XLPE
Electric Cable : 6.35/11(12)kV three core XLPE insulated cables non-armoured
Electric Cable : 6.35/11(12)kV three core XLPE insulated cables armoured
Electric Cable : 12.7/22(24)kV three core XLPE insulated cables armoured
Electric Cable : 2.7/22(24)kV three core XLPE insulated cables armoured
Electric Cable : 19/33(36)kV three core XLPE insulated cables armoured
Electric Cable : 19/33(36)kV three core XLPE insulated cables armoured
Electric Cable and Wire: 600/1000(Um = 1200) V single core XLPE insulated cable non-armoured
Electric Cable and Wire: 600/1000(Um = 1200) V single core XLPE insulated cable armoured
LV-XLPE
Electric Cable and Wire: 600/1000(Um = 1200) V multi core XLPE insulated cable non-armoured
Electric Cable and Wire: 600/1000(Um = 1200) V multi core XLPE insulated cable armoured
Electric Cable and Wire: 600/1000(Um = 1200) V single core PVC insulated cable non-armoured
Electric Cable and Wire: 600/1000(Um = 1200) V single core PVC insulated cable armoured
LV-PVC
Electric Cable and Wire: 600/1000(Um = 1200) V multi core PVC insulated cable non-armoured
Electric Cable and Wire: 600/1000(Um = 1200) V multi core PVC insulated cable armoured
Electric Cable and Wire: Polyvinyl Chloride(PVC) insulated cables of rated voltages up to and including 450/750 V Part 1 : General requirements
Electric Cable and Wire: Polyvinyl Chloride(PVC) insulated cables of rated voltages up to and including 450/750 V Part 2 : Test Methods
Electric Cable and Wire: Polyvinyl Chloride(PVC) insulated cables of rated voltages up to and including 450/750 V Part 3 : Non-sheathed cables for
450/750V-PVC
Electric Cable and Wire: Polyvinyl Chloride(PVC) insulated cables of rated voltages up to and including 450/750 V Part 4 : Sheathed cables for fixed
Electric Cable and Wire: Polyvinyl Chloride(PVC) insulated cables of rated voltages up to and including 450/750 V Part 5 : Flexible cables
Electric Cable and Wire: Polyvinyl Chloride(PVC) insulated cables of rated voltages up to and including 450/750 V Part 6 : Cables for Lifts and flexible
Telecommunication Cable : Plastic Twin pair,triple and unit types, internal cable
Telecommunication Cable : Jumper cable
Telecoms
Telecommunication Cable : Self supporting drop wire
(draft)
Telecommunication Cable :Fully Filled Unit Twin moisture barrier polyethylene sheathed cable (FF PEUT)
Telecommunication Cable :Integral Barrier Unit Twin moisture barrier polyethylene sheathed cable (IB PEUT)
Telecommunication Cable :Polyethylene Insulated 25 Pair Unit Twin moisture barrier polyethylene sheathed cable (FS PEUT)
Above 170kV
37kV - 170kV
3.7kV - 36kV
1.2kV - 3.6kV
MV BS/IEC/Utility IEC/MS
LV BS/IEC/Owner IEC/MS
Low
Low
Below 1.2kV
ELV BS/MS
High
Minimum or no control
MS
CATEGORY
ITEM DETAILS
Insulated flexible cords and cables
PVC insulated cable (non-armoured) for electric power supply
Polyvinyl chloride (PC) insulated flexible cords
MS 140 : 1987
SUB-STANDARD CABLES
CONDUCTOR
determines base current ratings
INSULATION
determines voltage / stress
levels
PROTECTIVE LAYER
determines protection level
& installation conditions
CRITERIA
CRITERIA
Insulation material or type does not meet the required chemical and thermomechanical properties for long term ageing and environmental tests
Applied insulation does not meet the requirement on thickness and physical aspects
of the standards stipulated for the type and rated voltage of cable
Insulated conductors are not identified by markings or colours as stipulated by the
standards
IMPACT
The use of non-compliant insulation material or construction will result in
premature deterioration of the cable insulation in service
This condition may eventually lead to breakdown of cable insulation, joints or
connectors at installed positions or distribution boards
Condition of undetected exposure caused by deteriorated insulation will be
hazardous to users
CRITERIA
Material for protective layers do not meet the required chemical and/or thermomechanical properties for long term ageing and environmental tests
Applied protective layers do not meet the requirement on thickness and physical
aspects of the standards stipulated for the type and rated voltage of cable
Completed cables are not identified by markings as stipulated by the standards
IMPACT
Cables will not perform or its service life will be greatly reduced if the above
properties do not meet their intended installed conditions
Fire rated or alarm cables may be rendered inactive in fire related situations
Cables which are incorrectly identified or installed in unintended locations
may be hazardous to the environment or users
Item
Reference
Conductor
- number of wires
- resistance
- equiv area
- cond diam
- total weight
Insulation
- nominal thickness
- weight per core
- total weight
- core diam
- laidup diam
Sheath
- overall diam
- nominal thickness
- calc mass
- total weight
Cable overall weight
R
C
P
C
P
M
e fe re n c e
u p ric e
V C p ric e
u
V C
a te ria l c o s t
R O I
R O I
R O I
ohm/km
sqmm
mm
gm/m
40
26
0.731
1.061
19.490
39
29.8
0.638
0.991
17.004
38
69.3
0.274
0.650
7.312
38
112
0.170
0.511
4.524
mm
gm/m
gm/m
mm
mm
0.56
4.278
12.834
2.181
4.711
0.65
5.027
15.080
2.291
4.949
0.75
4.948
14.843
2.150
4.644
0.95
6.542
19.625
2.411
5.208
mm
mm
litre
gm/m
gm/m
6.4
0.84
14.739
21.371
53.7
7.07
1.06
20.023
29.034
61.1
6.89
1.12
20.347
29.504
51.7
7.36
1.08
21.240
30.798
54.9
M
M
M
M
M
y
y
y
y
y
r/k g
r/k g
r/m
r/m
r/m
C ase 1
C ase 2
C ase 3
S TD
30
4 .5
0 .5 8 5
0 .1 5 4
0 .7 3 9
07ED 100
30
4 .5
0 .5 1 0
0 .1 9 9
0 .7 0 9
07ED 099
30
4 .5
0 .2 1 9
0 .2 0 0
0 .4 1 9
07ED 098
30
4 .5
0 .1 3 6
0 .2 2 7
0 .3 6 3
10%
5%
0%
15%
9%
4%
94%
85%
76%
124%
114%
104%