HE693THM884/888
High Resolution
Thermocouple Module
Product Specifications
and Installation
1
DESCRIPTION
The Horner APG High Resolution Thermocouple Input Module allows thermocouple temperature sensors
to be directly connected to the PLC without external signal processing (transducers, transmitters, etc.).
All analog and digital processing of the thermocouple signal is performed on the module. This highresolution module (0.1C), can report values to the PLC I/O table in 0.5C, 0.5F, 0.1C, or 0.1F
increments. The module features eight thermocouple channels assigned to 8 %AI input registers. There
are 16 %I Alarm Bits, one open circuit alarm and one setpoint alarm for each channel. Alarm setpoints
are set for each channel through 8 %AQ registers. Open circuit alarm bits for each channel correspond
to the first eight successive %I bits, and the alarm setpoints for each channel correspond to the second
eight successive %I bits.
On the THM888, A feature available on Revision H or later is auto detected external AD592 cold junction
compensation. This allows cold junction compensation to be accomplished in a remote isothermal
terminal strip, with standard copper wire run from the remote terminal strip to the module. AD Converter
on THM888 hardware has been optimized for 60Hz rejection.
12/12/2013
Page 1 of 6
HE693THM884-45
MAN0095-14
SPECIFICATIONS
Accuracy Specifications
HE693THM884 Specifications
Power
Consumption
Number of
Channels
Types Supported
Input Range
(Temp.)
100mA @ 5VDC
Input Impedance
8
J, K
J: -210 to
+760c
K: -270 to
+1372C
Maximum
Sustained O/L
Common Mode
Rejection
A/D Conversion
Type
Operating
Temperature
0.1C
See Accuracy
Specifications table
Accuracy
Type
20Mohms
Rated
+ / - 1C
+/-35V
Range of
Rating
-210 to +760C
100dB
Type
18-Bit Integrating
Rated
+ / - 1C
+ / - 2C
5 ms
Range of
Rating
-100 to +1000C
-200 to +1372C
A/D Conversion
Time
Scan Rate
Resolution
Relative Humidity
40 channels per
second
0 to 60C (32 to
140F)
5% to 95% noncondensing
HE693THM888 Specifications
Power Consumption
100mA @ 5VDC
Number of Channels
Types Supported
Input Impedance
J, K, N, T, E, R, S, B, C, X
J: -210 to +760c
K: -270 to
+1372C
N: -270 to
+1300C
T: -270 to +400C
Resolution
E: -270 to +1000C
C: 0 to +2320C
R: 0 to +1768C
X: -178 to +982.3C
+/-35V
100dB
18-Bit
Integrating
S: 0 to +1768C
B: 0 to +1820C
Scan Rate
5 ms
Operating Temperature
0.1C
Accuracy
8%AI, 8%AQ,
16%I
20Mohms
Relative Humidity
Accuracy Specifications
Range of Rating
Type
-210 to +760C
R
Type
J
Rated
+ / - 1C
+ / - 1C
+ / - 2C
-100 to +1000C
-200 to +1372C
N
T
+ / - 1C
+ / - 1C
+ / - 2C
+ / - 1C
+ / - 2C
16 channels
per second
0 to 60C (32 to
140F)
5% to 95%
noncondensing
Rated
+ / - 1C
+ / - 2C
Range of Rating
+ / - 1C
+ / - 2C
0C to1300C
1300 to 1768C
-270 to +1300C
-100C to 400C
-240C to-100C
B
C
0C to 1000C
1000C to 1800C
1800C to 2320C
-100C to 1000C
-200C to-100C
+ / - 1C
+ / - 1C
+ / - 2C
+ / - 3C
+ / - 1C
Page 2 of 6
0C to1300C
1300C to 1768C
0 to +1820C
-178 to +982.3C
HE693THM884-45
MAN0095-14
CONFIGURATION
Configuration Parameters
Byte 1
Byte 2
Byte 3
Byte 4
Smart Module
Digital Filtering
Engr. Units
Up/Downscale Break
Bytes 5-12
T/C Type
00: J
00: 0.5C
01: K
00: Upscale Break
02: N
01: 0.5F
03: T
000004:
E
0111
1
02: 0.1C
(see
05: R
01: Downscale Break
Chart)
06: S
03: 0.1F
07: B
08: C
09: X
The necessary parameters are %I Size, %AI Size, %AQ Size, and Bytes 1-12.
Bytes 5-12
(THM 888)
T/C Type
08: C
09: X
Bytes 5-12
(THM 884)
T/C Type
00: J
01: K
100%
1
90%
10
11
80%
100
% Temperature
Change Completed
70%
101
60%
50%
110
40%
30%
111
20%
10%
0%
0.00
4.00
8.00
12.00
16.00
20.00
Page 3 of 6
HE693THM884-45
WIRING
4.1
MAN0095-14
HE693THM884-45
4.3
MAN0095-14
Isothermal
Block Screw
Terminal
TC-1
Isothermal
Block DB25
Pin
3
Isothermal
Block DB25
Pin
7
TC+1
16
TC+5
20
TC-2
TC-6
TC+2
17
TC+6
21
10
NC
SHIELD
25
19
NC
14
SHIELD
13
20
TC-3
11
TC-7
12
TC+3
18
13
TC+7
22
14
TC-4
15
TC-8
10
16
TC+4
19
17
TC+8
23
18
Module
Terminal
4
Page 5 of 6
HE693THM884-45
INSTALLATION
5.1
Installation Hints
MAN0095-14
Special care must be taken with grounded junction sensors to avoid applying a voltage potential to the
thermocouple junction.
Extension wire of the proper Thermocouple type must be used. Keep total wire resistance less than
100 to maintain rated accuracy.
Extension wiring should be routed in its own conduit. Shielded, twisted pair extension wiring offers best
noise immunity.
If shielded wiring is used, a good earth ground connection is critical. Terminals 19 and/or 20 may be
used as the shield ground point.
Short all unused channels to frame ground. (See Figure 5, pins 19 and 20).
For further installation information please go to : http://www.horner-apg.com/oem/tetrapak.aspx
TECHNICAL ASSISTANCE
For manual updates and assistance, contact Technical Support at the following locations:
North America
Phone
1-877-665-5666
Web
www.heapg.com
Europe
Phone
Web
Page 6 of 6