DEVELOPMENT CONSULTANTS

PRIVATE LIMITED
Reviewed for general conformance with Contract
drawings and specifications.
ACTION :

1 Approved

Disapproved.

For information/reference
only.

Information category with


comments. Resubmission
required.

Approved except as

2 noted. Forward final


drawing.
Approved except as

3 noted. Resubmission
required.

Approval of Contract documents by the Consultant shall


not relieve the Seller of his responsibility for any errors
and fulfilment of Contract requirements.

Digitally signed by Santanu


Chakraborty
DN: cn=Santanu Chakraborty,
o=DCPL, ou=Power Cell-B,
email=santanuc@in.dclgroup.co
m, c=IN
Date: 2015.02.23 16:54:05 +05'30'

Please provide circuit breakers with pre insertion


resistors for all the line & its tie breakers as per
requirement of contract specification. Accordingly
revise GTP as required for With PIR circuit breaker.
OWNER: ODISHA POWER GENERATION CORPORATION LTD
PROJECT: IB THERMAL POWER STATION, 2x660 MW UNITS 3 & 4
BOP CONTRACTOR - BGR Energy Systems Ltd
MANUFACTURER: CROMPTON GREAVES LIMITED
GUARANTED TECHNICAL DATA SHEET FOR 420kV CIRCUIT BREAKERS
SL.NO

TECHNICAL PARAMETER

UNIT

Guaranteed Technical Parameters

400kV SF6 Circuit Breakers


1

Name of the manufacturer

Manufacturer's designation

Reference standard

Type

Service

Pole

Crompton Greaves Ltd


400-SFM-50AA
IEC-62271-100
SF6, Individually operated single pole type
Outdoor
Nos.

3 Single Pole

a) Nominal / Maximum Voltage

kVrms

400 / 420

b) Rated voltage

kVrms

420

Rated frequency

Hz

50Hz 5%

Continuous current at 50C

10

System Neutral earthing

Amps

Effectively grounded.

11

Standard to be followed

IEC-62271-100

Upto 3150

Class
12

a) Mechanical Endurance Class

M2

b) Electrical Endurance Class

E1

c) Restrike Probability Class

C1

13

Electromagnetic Compatibility(EMC)

14

Rated Insulation Level

As per IEC

Rated Lightning Impulse withstand voltage


14.1

Please confirm which


one is used here &
delete the other one.

a) between phase to earth

kVpeak

b) between phases & CB open

kVpeak

1425

c) across isolating distance

kVpeak

1425 (+240) *

a) between phase to earth

kVpeak

1050

b) between phases

kVpeak

1575

c) across isolating distance

kVpeak

900 (+345) *

a) between phase to earth

kVrms

520

b) between phases

kVrms

c) across isolating distance


Corona extinction voltage
with CB Open or Close in normal
atmospheric condition

kVrms

520
610 for two breaks / 610 x 0.55 for single break

1425

Rated Switching Impulse withstand voltage


14.2

Rated one minute Power Frequency


withstand voltage KVrms
14.3

15

16

Maximum radio interference


voltage level at 1.1 Urated/3

17

Rated Normal Current at 50C ambient

18

Limit of Temperature rise

19

Design Ambient Temperature

KVrms (min)
346
Micro-Volts
</=1000 @ 267 kV
A

3150
As per IEC

50

Rated Making & Breaking Capacity


i) Short-circuit breaking current (Symm)

kArms

ii)Percentage D.C. component


iii)Rated short-circuit making current

kApeak

iv)Rated peak withstand current

kApeak

125

KA

50 KA for 1 sec

v)Rated short time withstand current for rated duration


20

50
As per IEC 62271-100 ( 55%)

viii)Rated line charging breaking current


vi) Rated Out of phase breaking current in% of rated short circuit
breaking current

Arms

125

600
25% of short-circuit breaking
current

Please check & clarify


the value w.r.t 20. (x) of
this data sheet.

OWNER: ODISHA POWER GENERATION CORPORATION LTD


PROJECT: IB THERMAL POWER STATION, 2x660 MW UNITS 3 & 4
BOP CONTRACTOR - BGR Energy Systems Ltd
MANUFACTURER: CROMPTON GREAVES LIMITED
GUARANTED TECHNICAL DATA SHEET FOR 420kV CIRCUIT BREAKERS
SL.NO
20

TECHNICAL PARAMETER

UNIT

Guaranteed Technical Parameters

kApeak

17.675

400kV SF6 Circuit Breakers


vii) Crest value of out of phase breaking current
ix) Characteristic for short line fault related to rated short circuit
breaking current
x) Rated capacitive switching breaking (Ams)/ in rush making current
(KApeak)

As per IEC 62271-100


400 Amps /20 Kapeak

xi) TRV Characteristics

As per IEC 62271-100

21

Inductive current breaking capability without exceeding over voltage by


2.0 pu

22

First pole to clear factor

315A
1.3

Operating mechanism
a) Type with functional description write-up

Spring -Spring

b) Whether trip free operation with anti pumping arrangement provided


23

Yes

c) Spring charged mechanism


KW

i) Rated Power
ii) Rated supply voltage, phase & frequency and operating range
iii) Spring Charging time

V & Hz

0.75
1 Ph, 240 Vac, 50Hz

sec

< 20

iv) Safety interlock provided

Yes

24

Opening time

msec

</= 40

25

Closing time

msec

</= 100

26

Auto reclosing

Single phase & Three phase

Rated Operating Sequence


27

i) For Auto Reclosing breakers

0 - 0.3"-CO-3'-CO

ii) For Non Auto Reclosing breakers

NA

28

Operating Duty

0 - 0.3"-CO-3'-CO

29

SF6 Gas

As per IEC 60376

Rated supply voltage & frequency for

30

i) Closing

220 (+ 10%/-15%) V D.C.

ii) Tripping

220 (+ 10%/-30%) V D.C.

iii) Spring Charge Motor

240 V, 1 Ph, 750W, 50 Hz

iv) Compressor/Pump Motor

NA

v) Heater/Lamp/Socket

240V, 1 Ph, 2W, 50Hz

31

Anti pumping

32

Minimum Creepage distance (@31 mm/KV)

mm

33

Phase to phase spacing of terminal conductor

mm

7000

34

Elevation of lower most terminal Conductor above Plinth level

mm

As per GA drawing

35

Rated Terminal Load

Kgf

36

Noise level at the base of CB

dB

37

Mounting Structure

38

Seismic Acceleration

39

SF6 Gas

40

Provided
13020

As per IEC 62271-100 or calculated value


140 dB
Hot Dip Galvanised Steel
0.3g
7 kg/cm2

Total break time measured from the instant of trip circuit


energisation
a) At 10% breaking capacity

msec

</=45

b) At 100% breaking capacity

msec

</=45

a) At 10% breaking capacity

msec

</=20

b) At 100% breaking capacity

msec

</=20
160

Arcing time
41
42

Total length of arc.

mm

43

Breaks per pole

No.

44

Length of break per pole

mm

2 x 160

45

a) Length of travel

(stroke-wipe)

Contact Travel

46

(stroke)

mm

b) Rate of travel

M/S

Make time

msec

2 x 140
Opening: 4.5 - 6.0

Closing:2.2 - 3.4
</=100

Please furnish the data in


this GTP.

OWNER: ODISHA POWER GENERATION CORPORATION LTD


PROJECT: IB THERMAL POWER STATION, 2x660 MW UNITS 3 & 4
BOP CONTRACTOR - BGR Energy Systems Ltd
MANUFACTURER: CROMPTON GREAVES LIMITED
GUARANTED TECHNICAL DATA SHEET FOR 420kV CIRCUIT BREAKERS
SL.NO

TECHNICAL PARAMETER

UNIT

Guaranteed Technical Parameters

sec

< 20

a) Minimum dead time for first auto reclose

msec

300

b) Range of adjustment for single auto reclose

msec

400kV SF6 Circuit Breakers


47

Spring charging time


Reclosing time with rated control voltage applied
measured from the instant of trip coil energisation

48

and

Recovery voltage distribution between breaks in % of single line to


earth fault
Type of devices, if any, to limit the rate of restriking voltage
Short circuit type test certificate furnished?
49
50

300
Tested full pole
NA

Yes/No

a) Certificate/Report No.

TTRs attached

b) Oscillogram No.

TTRs attached

Attachment is not found. Please


check & furnish the same.

Contacts
Type

50.1

a) Main

Multifinger crown

b) Arcing

Tulip

Material
50.2

a) Main

Copper-Ag alloy

b) Arcing
50.3

Whether the contacts are silver plated

50.4

Thickness of silver coating

50.5

Contact pressure

56

Type of Arc control device

57

Whether main air column and interrupters are pressurised ?

59

Maximum pressure developed in the arcing chamber at rated breaking


capacity
Kg/Cm2
Time limit for which the breaker can be kept open, if any

60

Auxiliary Contacts

58

Copper-Tungsten
Yes/No

Yes

mm

25 microns

Kg/cm2

0.3 kg/mm
puffer
Yes

Kg/cm2

10
NA

Total nos. of contacts furnished


60.1

a) Normally Open

Nos.

20

b) Normally Closed

Nos.

20

a) Normally Open

Nos.

10

b) Normally Closed

Nos.

Spare contacts available for interlocks in addition to those


required for breaker's own operation and indication
60.2

c) Contact type convertible or fixed?

10
Fixed

Contact Rating at
60.3

a) Make and Continuous


b) Break (Inductive)

Amps
Amps

15
7.5

Permissible variation of 220V D.C.


61

a) Closing

85% to 110%

b) Tripping

70% to 110%

Permissible variation of working pressure of Breaker


62

a) Closing

kg/cm2

6.0 - 7.0

b) Tripping

kg/cm2

6.0 - 7.0

in litres

Air Consumption
(At NTP)

63

a) Duty cycle (0 3 ' CO 3 ' CO)

NA

b) Closing

NA

c) Opening

NA

d) Total scavenging & leakage


Volume of air receiver per pole

NA
lit

NA

Ata

NA

Minimum blocking air pressure


64

a) Closing
b) Tripping

NA

Minimum clearance
65

a) Phase to ground

mm

As per GA drawing

b) Phase to phase

mm

As per GA drawing

Arrangement provided for


66

a) Pole discrepancy
b) Trip free/Fixed trip
c) Anti pumping

Yes
Trip free
Yes

Please furnish the data in


this GTP.

OWNER: ODISHA POWER GENERATION CORPORATION LTD


PROJECT: IB THERMAL POWER STATION, 2x660 MW UNITS 3 & 4
BOP CONTRACTOR - BGR Energy Systems Ltd
MANUFACTURER: CROMPTON GREAVES LIMITED
GUARANTED TECHNICAL DATA SHEET FOR 420kV CIRCUIT BREAKERS
SL.NO

TECHNICAL PARAMETER

UNIT

Guaranteed Technical Parameters

400kV SF6 Circuit Breakers


67

Operating mechanism

Spring - Spring

2 nos. trip coil per pole i.e total


6 nos. trip coils need to be
considered. BGR to check &
revise properly.

Power requirement at 220V D.C.


68

a) Closing coil

Watt

b) Tripping coil

Watt

3 x 606 W at 220 VDC

c) Spring charging motor

Watt

750w input 360w output

3 x 540 W at 220 VDC

Type of Interlocks Furnished


69

a)

NA

b)

NA

c)

NA

d)

NA

Accessories
70

a) Furnished as per Annexure? Yes /No

Not understood. BGR to


confirm that provision for
necessary interlocks with
breaker and isolator & earth
switch shall be considered.

Furnished as per P.O.

b) If not, Deviation sheet duly filled up? Yes/No


Bushings
a) Make

ABIL(BIRLA NGK)/IEC/ MODERN/JSI/WSI INSULATORS

b) Type

Hallow

c) Reference standard

71

d) Voltage class

kV

e) Momentary dry withstand voltage

kV

f) Visible discharge voltage

kV

g) One minute dry withstand voltage

kV

h) One minute wet withstand voltage

kV

i) Impulse withstand voltage

kVpeak

j) Under oil puncture voltage

kV

k) Creepage distance, total/ Protected

mm

l) Height required to remove the bushing

mm

m) Permissible safe cantilever loading on bushing


72

Nature of insulating medium of bushing

73

Volume of insulating medium of bushing

74

Overall dimensions of the circuit breaker complete with bushing,


mechanism box etc.
Circuit Breaker Weight

As per IEC 62155-2003

PROTECTED (35% OF TOTAL)


1500
As per IEC 62155-2003
NA
NA

mm

Kg

75

a) Total Weight

76

b) Impact for foundation design to include dead load plus impact value
on opening at max. interrupting rating in dead load
Shipping dimension of the largest package (L x B x H).

mm

77

Shipping weight of the heaviest package

Kg

78

Spare quantity of SF6 gas furnished? If so, indicate the total quantity

79

Please furnish all the


data for bushing.

Kg

As per GA drawing
WO PIR CB:7500
DOWNWARD 8000 ; UPWARD 5000
WO PIR: 1500 (Pole)
20% of total gas qty

Number of openings, the Circuit Breaker is capable of


performing without inspection, replacement of contacts or
other main parts.
a) At 50% rated current

6000

b) At 100% rated current

1500

c) At 50% rated breaking capacity

40

d) At 100% rated breaking capacity

10

NOTE: * Figures given in the bracket ()are peak value of the power frequency to be applied to the opposite terminal (across isolating distance)

Not understood. Please


clarify the matter. Also
furnish total creepage
distance.