Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
12.1
GENERAL REQUIREMENTS
12.1.1 SUPPLY MAINS: The nominal size of supply trunk mains and
branch mains shall be not less than the size of any installation
main distribution pipe, at its main installation control valve,
supplied by the trunk main.
12.1.2 INSTALLATION PIPEWORK: Individual sprinklers shall not be
connected directly to distribution and main distribution pipes,
except in the case of light-hazard installations where sprinkler
may be connected directly to pipes not exceeding 50mm
nominal bore.
12.1.3 In ordinary or high-hazard installations arm pipes or drop pipes
not exceeding 32 mm nominal bore shall be used to connect
individual sprinklers where these are fed from pipes larger than
65mm nominal bore,
12.1.4 Where upright or pendent conventional or spray sprinklers are
fitted within 400 mm of the pipe axis alongside a pipe of
nominal size greater than 65mm, the deflector shall be not more
than the appropriate distance given in Table 14 above the lower
edge of the pipe.
12.2
ORIFICE PLATES:
TABLE 14
Location of sprinklers alongside feed pipes
larger than 65 mm nominal size
Minimum
horizontal
distance from
pipe centre
line to the
sprinkler
centre line
(mm)
00
17
34
17
40
100
100
200
400
Orifice plate
thickness (mm)
Over
-80
150
80
150
200
3
6
9
12.3
CONCEALED SPACES
12.3.1
Precalculated
Fully
calculated
Concealed space
pipework
design
Concealed space
maximum area
per sprinkler, or
treat as hazard
class listed
(in m2)
Hazard
class
Nominal
size as for
hazard
class listed
AMAO as
for
hazard
class
listed
Light
Light
---
Light
Ordinary
Ordinary
---
21
High
Ordinary
Ordinary
Ordinary
---
Light
Light
Ordinary
21
Ordinary
Light
Ordinary
Ordinary
21
High
Ordinary
Ordinary
Ordinary
Ordinary
21
Ordinary
12.3.2 The feed pipe to the sprinklers in the concealed space shall be
arranged and sized as follows:
12.3.2.1 LIGHT HAZARD: The concealed space above or below shall be
protected by a separate pipe from the installation valve.
12.3.2.2 ORDINARY HAZARD: If the concealed space above a precalculated installation are fed individually from the pipework
below, the range and distribution pipes in the installation shall
be sized by taking the room and concealed space sprinklers
cumulatively. Alternatively if two feed pipes are used, one for
the concealed space and one for the room sprinklers, the
common feed pipe shall have a nominal bore of not less than 65
mm.
The concealed space below a pre-calculated installation shall be
fed by two feed pipes, one for the concealed space and one for
the room sprinklers, the common feed pipe shall have a nominal
bore of not less than 65 mm.
12.3.2.3 HIGH HAZARD: If the concealed space above or below a precalculated installation shall be fed by a separate feed pipe from
that feeding the sprinklers in the room. The concealed sprinkler
feed pipe shall be connected outside the room between the
installation valve set and any 48-sprinkler design point for a
high hazard sprinkler array outside the room concerned.
12.3.2.4 FULLY HYDRAULICALLY CALCULATED INSTALLATION: The
pressure and flow characteristics of the installation shall be
satisfactory under each of the following operating conditions:
i)
12.4.1 GENERAL:
12.4.1.1 The size of distribution feed pipes, including in light-hazard
installations any which are partly range pipes because of the
three sprinkler limitation, shall be as specified in the tables from
the terminal point(s) up to the design point(s).
12.4.1.2 The feed pipe between the installation main control valves and
the design point shall be hydraulically calculated on the basis of
a maximum flow loss (specified in the appropriate sub-clause),
corrected for static head gain for design points not at the
highest level, at a particular flow rate.
12.4.1.3 Where the number of sprinklers in an array in a room, or in an
area protected by a distinct group of sprinklers having its own
distribution pipe spur, is less than or equal to the number of
sprinklers for which the distribution pipes are hydraulically
designed, the design point shall be positioned at the point of
connection to the distribution pipe of the range of the array
which is hydraulically nearest to the installation control valves.
12.4.1.4 Where the number of sprinklers in an array in a room on a
distribution pipe terminal spur exceeds the number for which
the distribution pipes are hydraulically designed, the design
point shall be positioned at the point of connection to the range
or ranges immediately upstream of the group of ranges
containing not more than the maximum specified number of
sprinklers beyond the design point.
12.4.2.2
minimum size specified in table 17 for the range pipe fed from
the design point.
12.4.2.8 The layout of the sprinkler installation shall, by and large,
conform to the method shown in the Figure 20.
TABLE 17
Light hazard range and terminal distribution pipe sizes
Pipe
Size
(mm)
Maximum
length (in m)
Maximum
number of
20
25
N.A
Steel
MAXIMUM FRICTION
LOSS INCLUDING
CHANGES OF DIRECTION
(BARS)
DESIGN POINT
0.9
See Column A
and B of table
19
0.7
See Column B
of table 19
0.7
See Column B
of table 19
TABLE 19
Pressure loss per unit length for design flow rates in light
hazard installation
Pressure loss per unit length
Pipe
Material
Nominal size
(mm)
Steel
(IS-1239)
25
32
40
50
63
(in m bar/m)
Column A
Column B
44.0
12.0
5.5
1.7
0.5
200.0
51.0
25.0
7.8
2.2
NOTE-1
NOTE-2
12.4.3
ORDINARY HAZARD.
TABLE - 20
Maximum number
of sprinklers to be
fed by pipe of size
listed
25
32
1
2
in
25
32
2
3
25
32
40
50
2
3
4
9
25
32
40
50
3
4
6
9
TABLE - 21
65
80
100
150
200
35
16
4.4
0.65
0.16
Maximum number of
sprinklers to be fed by
pipe listed below
32
40
50
65
2
4
8
16
32
40
50
65
3
6
9
18*
Pipe layout
*This does not preclude the use of 65 mm nominal bore pipe between
the 16/18 sprinkler point and the installation valves if hydraulically
found in order.
10
12.4.3.5 The feed pipe for all the other design points (except the
highest design point) shall be similarly sized by hydraulic
calculation. In case of friction loss in any part of the feed pipe
not common with that feeding the highest design point,
allowance can be given to the static pressure gain in the
successive levels below the top most level. The nominal size of
the distribution pipe shall however not be less than the
minimum size specified in table 22 for the range pipe fed from
the design point.
11
Pipe
Maximum number
nominal size of sprinklers to be
(mm)
fed by pipe listed
below
a) Ranges at remote end of each distribution pipe spur 1. Last two ranges in two
end-side layout
25
32
1
2
25
32
2
3
25
32
40
2
3
4
25
32
3
4
12
TABLE - 24
RANGE PIPE NOMINAL SIZES FOR VARIOUS PIPES LAYOUTS
FOR HIGH HAZARD INSTALLATIONS WITH SPRINKLERS OF 15
MM NOMINAL BORE AND PRESSURE FLOW CHARACTERISTICS
AS GIVEN IN TABLE 7 OR OF 20 MM NOMINAL
SIZE AND PRESSURE FLOW CHARACTERISTICS AS GIVEN IN
TABLE 8
Pipe nominal
size
(mm)
Maximum number
of sprinklers to be
fed by pipe listed
40
50
65
1
3
6
2. Other ranges
32
40
50
65
1
2
4
6
b) End-center arrangements
1. Two end center layout
i)
ii)
Other ranges
32
40
32
32
40
50
1
2
2*
1
2
4
12.4.4.4
13
TABLE - 25
DISTRIBUTION PIPE NOMINAL SIZES FOR VARIOUS
NUMBERS OF SPRINKLERS DOWNSTREAM OF THE DESIGN
POINT IN
HIGH HAZARD INSTALLATIONS WITH SPRINKLERS
OF 15 MM NOMINAL BORE AND PRESSURE
FLOW CHARACTERISTICS AS
GIVEN IN TABLE 5.
Distribution pipe nominal Maximum number of sprinklers
size listed (mm)
to
be fed by the pipe of size
32
40
50
65
80
100
2
4
8
12
18
48*
*This does not preclude the use of 100 mm nominal size pipe
between the design point and the installation valve if it is
possible by hydraulic calculation requirements.( 12.4.4.4)
TABLE - 26
DISTRIBUTION PIPE NOMINAL SIZES FOR FEEDING VARIOUS
NUMBERS OF SPRINKLERS DOWNSTREAM OF THE DESIGN
POINT IN THE HIGH
HAZARD INSTALLATIONS WITH SPRINKLERS OF 15 MM
NOMINAL
SIZE AND PRESSURE FLOW CHARACTERISTICS AS GIVEN IN
TABLE 6 OR 7 OR SPRINKLERS OF 20 MM NOMINAL SIZE
AND PRESSURE FLOW CHARACTERISTICS AS
GIVEN IN TABLE - 8.
Distribution pipe
nominal size
(mm)
Maximum number of
sprinklers to be fed
by pipe listed
65
50
65
80
100
150
4
8
12
16
48*
14
*This does not preclude the use of 100 mm nominal size pipe
between the design point and the installation valve if it is
possible by hydraulic calculation requirements.
TABLE - 27
PRESSURE LOSS PER UNIT LENGTH OF PIPE FOR DESIGN FLOW
RATES
IN HIGH HAZARD INSTALLATIONS.
Pressure loss per unit length
(m bar/m)
Flow rate
LPM
2800
4550
5600
6750
9000
100 mm
nominal size
medium
grade pipe
(IS-1239)
150 mm
nominal
size
medium
grade pipe
(IS-1239)
200 mm
nominal
size
medium
graded
pipe (IS1239)
250 mm
nominal size
medium
grade pipe
(IS-1239)
34
72
115
160
250
5.1
11.0
16.0
23.0
36.0
1.3
2.7
4.1
5.8
9.1
0.43
0.90
1.40
1.85
3.00
NOTE-1 Where other grades of pipes are used, pressure loss data shall
accordingly change.
NOTE-2 The equivalent length of an elbow, bend or tee where the
water is turned through an angle shall be taken as 3 M when
using the data or in using Tables 29 or 30.
15
shall not be less than that of the first length, sized by the
pipe tables, of distribution pipe downstream of the design
point to which it is connected, or b) fitting an orifice plate
complying with rule 12.2 in the particular distribution pipe.
( see figures 22, 23, 24).
16
17
12.5
12.5.1 GENERAL
The requirements of this clause apply to pipe arrays sized by full
hydraulic calculation.
12.5.2 MINIMUM PIPE SIZES: The nominal bore of main and other
distribution pipes, and range pipes shall be not less than as
follows:
a) in a light-hazard installation
18
b) in an ordinary
installation
12.5.3
or
high-
hazard
25mm
19
= (A/a) + R
where
20
21
22
12.5.9
LOCATIONS OF AMAO
a) HYDRAULICALLY MOST UN-FAVOURABLE LOCATION:
Changes in sprinkler spacing, array design, elevation, range
centres, sprinkler nominal orifice size and pipe sizes, as well
as all possible locations, whether on the distribution pipes or
between distribution pipes where these are connected by
range pipes, shall be considered when determining the
hydraulically most un-favourable location of the AMAO.
b) HYDRAULICALLY MOST FAVOURABLE LOCATION:
All possible locations, whether on the distribution pipes, or
between distribution pipes where these are connected by
ranges, shall be considered for the hydraulically most
favourable location of the AMAO.
12.5.10
SHAPE OF AMAO
a) HYDRAULICALLY MOST UN-FAVOURABLE LOCATION.
23
24
25
26
12.6
++++++++++ +
27