Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Date: 01/05/2013
ECP 11-0506
Summary:
This procedure details the testing and commissioning procedures for distribution
transformers.
Originator:
Stephen Tucker
Date:
01/05/2013
Approved By:
Steve Mockford
Approved Date:
03/07/2013
Review Date:
31/03/2018
This document forms part of the Companys Integrated Business System and its requirements are mandatory throughout UK
Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset
Management. If you have any queries about this document please contact the originator of the current issue.
Document History
(The document history notes below are intended as a guide only and may not cover all of the changes. If you wish to make use
of this document it should be read in full.)
Version
Date
Details
Originator
3.0
02/05/2013
Stephen Tucker
2.0
04/11/2011
Stephen Tucker/
Sinad Hogan
1.2
13/09/2011
John Lowe
1.1
18/03/2011
Rebranded
Jerry Wells
1.0
24/09/2009
Original
Stephen Tucker
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Version: 3.0
Contents
1
Introduction ............................................................................................................. 3
Scope ....................................................................................................................... 3
References ............................................................................................................... 3
Equipment ................................................................................................................ 4
Inspection ................................................................................................................ 4
10
Energisation............................................................................................................. 6
11
12
13
Certification ............................................................................................................. 6
2 of 6
Introduction
1.1
This procedure details the testing and commissioning procedures for distribution
transformers that shall be satisfied before the transformer can be accepted as fit for
service and energisation.
1.2
1.3
This procedure shall be carried out in accordance with the requirements of the UK
Power Networks Distribution Safety Rules.
1.4
This procedure shall be carried out having regard to the requirements and
recommendations of the manufacturer. If conflict exists between the requirements
of the manufacturer and those of UK Power Networks the matter shall be referred
to Asset Management (or your UK Power Networks nominated contact).
1.5
This procedure assumes that the unit has been installed in accordance with the
appropriate procedures and that the equipment is isolated from the network.
1.6
The results of all observations, tests, adjustments and all relevant remarks shall be
recorded on the associated test form.
Scope
2.1
2.2
This procedure is intended for use by UK Power Networks field staff, contractors
and external connection providers.
References
3.1
3.2
3 of 6
4.1
Definition
ART
CDL
Equipment
5.1
The following test equipment is required to carry out the tests detailed in this
procedure:
1kV insulation resistance tester (e.g. Megger).
Inspection
6.1
6.2
Carry out a visual inspection of the transformer as detailed below referring to the
manufacturers manual where appropriate. If possible the Commissioning Engineer
shall rectify any non-conformances. However, all equipment defects shall be
referred to Asset Management (or your UK Power Networks nominated contact).
Check that the transformer is correctly installed and the stability foot fully
supported where applicable.
Check that the transformer is undamaged.
Check that all external surface finishes are undamaged and any damaged
paintwork has been repaired.
Check that the earthing terminal(s) are securely connected directly to the
substation earth electrodes and that paint has been removed from the earth
contact points.
Check that there are no oil leaks.
Check that the transformer oil level is satisfactory (if sight glass is available).
Check that any valves are securely closed.
Check that the desiccant dehydrating breather is correctly fitted (if applicable).
Check that the free breather is clear and the end cap has been removed on free
breathing transformers.
Check that the pressure relief device is not blocked and remove any packing if
labelled adjacent to device on sealed transformers.
Check that the HV bushings are satisfactory.
Check that the LV mono block/bushings are satisfactory.
Check the transformer ID labels are fitted (if applicable).
Check oil temperature gauge is fitted in position (if applicable).
For dual-ratio transformers check that the correct voltage ratio has been
selected and the position locked.
4 of 6
7.1
Carry out the following tap changer checks referring to the manufacturers manual
where appropriate:
Operate the tap changer through all positions while off-circuit.
Set the desired tap position.
Lock the tap changer.
7.2
8.1
8.2
5 of 6
9.1
9.2
9.3
Measure the HV resistance at both voltage positions. The resistance per phase at
11kV should be at least twice the resistance per phase at 6.6kV.
9.4
9.5
If there is any doubt that the internal winding selection mechanism is not operating
correctly the transformer shall not be energised and the defect reported to Asset
Management (or your UK Power Networks nominated contact).
10
Energisation
10.1
11
Asset Data
11.1
Complete the asset data form and either send it to the Asset Registration Team
(ART), email it to the appropriate mailbox (ART.EPN@ukpowernetworks.co.uk,
ART.LPN@ukpowernetworks.co.uk, ART.SPN@ukpowernetworks.co.uk) or send it
to your UK Power Networks nominated contact.
12
Test Equipment
12.1
Record the purpose, make, type and serial number of all test equipment used
during commissioning on the test form.
13
Certification
13.1
When the commissioning has been satisfactorily completed, sign and date the test
form. Place a copy of the test form on-site in a plastic wallet and in a secure
location.
6 of 6