CMLIB F
H

Reference Manual

OMICRON Test Universe

Article number VESD0102 - manual version: CMLIB F.AE.1


OMICRON electronics 2003. All rights reserved.
This Manual is a publication of OMICRON electronics GmbH.
All rights including translation reserved. Reproduction of any kind, e.g., photocopying, microfilming or
storage in electronic data processing systems, requires the explicit consent of OMICRON electronics.
Reprinting, wholly or in part, is not permitted.
This Manual represents the technical status at the time of printing. The product information,
specifications, and all technical data contained within this reference manual are not contractually
binding. OMICRON electronics reserves the right to make changes at any time to the technology and/or
configuration without announcement. OMICRON electronics is not to be held liable for statements and
declarations given in this reference manual. The user is responsible for every application described in
this reference manual and its results. OMICRON electronics explicitly exonerates itself from all liability
for mistakes in this manual.

Contents

Contents
Preface to the CMLIB F Hardware Reference Manual . . . . . . . . . . . . . . . . .5
Safety Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Designated Use. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
1

General Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
1.1

Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

1.2

Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

Construction and Functioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10


2.1

Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

2.2

Functioning of the LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

2.3

Connections and Interfaces. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11


2.3.1 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.3.2 16 Pin Sockets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.3.3 Block Diagram of CMLIB F . . . . . . . . . . . . . . . . . . . . . . . . . . .14

2.4

Operating CMLIB F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15


2.4.4 Operating the CMLIB F Hardware . . . . . . . . . . . . . . . . . . . . .15
2.4.5 Wiring Application of CMLIB F . . . . . . . . . . . . . . . . . . . . . . . .16
2.4.6 Operating the Test Universe Software . . . . . . . . . . . . . . . . . .17

Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19


3.1

Guaranteed Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

3.2

Electromagnetic Compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . . . . .19

3.3

Mechanical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

3.4

Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

3.5

Output Power CMA 156 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

3.6

Climate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

CMLIB F

3.7

Safety Standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

3.8

Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

Contact Information / Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . .23


Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

Preface to the CMLIB F Hardware Reference Manual

Preface to the CMLIB F Hardware


Reference Manual
The purpose of this manual is to familiarize users with CMLIB F, and to show
how to properly use it in various application areas.
The manual contains important tips on how to use CMLIB F safely, properly, and
efficiently to help avoid unnecessary repair costs, and down time due to
improper operation. It should be read and used by all people working with
CMLIB F.
The accepted technical procedures for work safety should be followed in
addition to the guidelines provided by this manual and the applicable regulations
for accident prevention depending on the country in which you are working in
and also depending on the site of operation.

CMLIB F

Safety Instructions
Please carefully read the following safety instructions before operating
CMLIB F.
CMLIB F should only be operated by trained personnel. It is not
recommended to operate CMLIB F without detailed knowledge of the
safety instructions.

Designated Use

CMLIB F should only be connected to SELV interfaces. A connection with the


front panel terminals of the CMC is not permitted due to safety reasons.

The 16 pin "CMC" interface should only be connected to the generator


outputs of a CMC 156 (Gen. Out 7 - 12) or a CMC 256 (LL out 1 - 6).

The 16 pin "Amplifier" interface should only be connected to an OMICRON


amplifier, if the interface labelled "CMC" is connected to a CMC test set.

Do operate CMLIB F in a safe manner.

Do avoid disruptions that could in turn affect the safety of the operation.

Do not operate CMLIB F if not in technically sound condition.

Do not operate CMLIB F under wet or moist conditions.

Do not operate CMLIB F when explosive gas or vapors are present.

CMLIB F should not be opened. All guarantees are invalidated if the device
is opened.

Preface to the CMLIB F Hardware Reference Manual

Glossary
The following symbols are used to highlight certain sections within this manual:

Note
Refers to sections containing additional information.

Caution
Refers to sections with special safety information.
Reference information
Refers to references with extensive and detailed information.

CMLIB F

General Information

1 General Information
1.1 Application
The typical applications is testing of E/M relays with a high burden zero
sequence current coil.

1.2 Function
CMLIB F forms the vectorial sum of the voltages of LL OUT 1-3 / CMC 256
(Gen OUT 7-9 / CMC 156). The value is put out at LL OUT 4 (Gen OUT 10) in
an inverted state and put out at LL OUT 5 (Gen OUT 11) in a non-inverted state.
These two signals control the current amplifiers B1 and B2 of a CMA 156 and
generate the zero sequence current that is injected to the corresponding relay
input tranformers. The LL OUT (Gen OUT 7-9) signals are looped through the
CMLIB F and control the three phase currents A1-N, A2-N, A3-N of a CMA 156.
Controlling a CMA 156 this way increases the output power and makes the
compliance voltage in the zero sequence current path significant and thus
makes it possible to test E/M relays that cannot be tested with a conventional
set-up.
Figure 1-1:
Wiring of CMLIB F

CMLIB F

2 Construction and Functioning


2.1 Components
CMLIB F consists of the following components:

CMLIB F unit (VEHZ1107)

Power supply unit 100-240VAC/18VDC including plug-in adaptor for


country-specific wall outlets. (VEHZ1103)

Connection cable CMLIB F - CMC test set (VEHK0003, identical with the
CMC amplifier connection cable)

Shorting connector

Carrying bag for CMLIB F (VEHP0020)

Reference manual

2.2 Functioning of the LED


The LED (ON when lit) indicates that the CMLIB F is supplied (external supply);
if a CMC 256 is connected via the LEMO connectors then no external supply is
necessary.
Figure 2-1:
CMLIB F LED

10

Construction and Functioning

2.3 Connections and Interfaces


2.3.1

Power Supply
The power supply of the CMLIB F is provided by means of a power supply unit
240VAC/18VDC that is equipped with an adapter for the various country specific
wall outlet.
The connector of this power supply is reverse polarity protected.

Note:

No external power supply is needed when a CMC256 is used.

Figure 2-2:
Power Supply input

11

CMLIB F

2.3.2

16 Pin Sockets
For the connection of CMLIB F with the CMC or with external amplifiers, the
connection cable VEHK0003 is used.

Figure 2-3:
Close-up view of lemo
plug for interface to
external amplifiers.

Table 2-1:
Pin layout of the
16 pin lemo plug for
interface to external
amplifier.

12

Connector

Function

pin 1

LL out 1

pin 2

LL out 2

pin 3

LL out 3

pin 4

GND connect to protective earth ground (PE)

pin 5

LL out 4* ( LL out 1-3 inverted)

pin 6

LL out 5* ( LL out 1-3)

pin 7

LL out 6

pin 8 ... 16

Reserved

Construction and Functioning

Figure 2-4:
Close-up view of the
lemo plug interface for
CMC.

Table 2-2:
Pin layout of the
16 pin lemo plug for
interface to CMC.

Connector

Function

pin 1

LL out 1

pin 2

LL out 2

pin 3

LL out 3

pin 4

GND connect to protective earth ground (PE)

pin 5

LL out 4

pin 6

LL out 5

pin 7

LL out 6

pin 8 ... 16

N.C.

13

CMLIB F

2.3.3
Figure 2-5:
Block diagram of
CMLIB F

14

Block Diagram of CMLIB F

Construction and Functioning

2.4 Operating CMLIB F


Please check for the availability of all components prior to operating the
CMLIB F
The standard scope of supply comprises of:

2.4.1

CMLIB F unit

Connection cable CMLIB F - CMC

Connection cable CMLIB F - CMA Amplifier

Power supply unit 100-240VAC/18VDC

Operating the CMLIB F Hardware


1. Check the power switches. The power switches of the CMA 156 and the
CMC X56 have to be in position 0 (=OFF).
2. Connect the mains cables, CMA 156 and CMC X56.
3. Connect the 25-pin D-Sub cable, connection PC and CMC X56.
4. Check the slide switches of the CMA 156.
A: Position II
B: Position I (refer to the CMA 156 manual)
5. Connect lemo cables
Connection cable CMLIB F - CMC
Connection cable CMLIB F - CMA amplifier
6. Connect external power supply to CMLIB F. The LED of the CMLIB F has
to be lit.
7. Connect protection relay. See Figure 1-1: Wiring of CMLIB F on page 9.
Do not forget to connect the SPA-Resistors; if you short the phase B_3
(CMA) to N, then no overload is indicated.
8. Switch on the CMC X56 and the CMA 156.

15

CMLIB F

2.4.2

Wiring Application of CMLIB F

Figure 2-6:
Wiring Application

* 1) shorting B_3 and B_N to switch off Overload Indication (LED).

16

Construction and Functioning

2.4.3

Operating the Test Universe Software


1. Start the Test Universe software and open the Quick CMC module.
2. Click user specific amplifier (HW-Configuration).
Note:

Gen.Out 7-9 has to be selected; use the performance date of


the CMA 156 (25A...)

Figure 2-7:
Selecting the amplifier.

3. Define the analog outputs.


Figure 2-8:
Defining the analogoutputs.

17

CMLIB F

4. Start the test.


Figure 2-9:
Quick CMC test.

18

Technical Data

3 Technical Data
3.1 Guaranteed Values
The values are valid for the period of one year after factory calibration, within
23C 5C at nominal value and after a warm-up phase greater than 5 minutes.
Related technical data can also be found in the CMC and CMA reference
manuals.

3.2 Electromagnetic Compatibility (EMC)


Table 3-1:
Electromagnetic
compatibility

EMC
CE comformity

The product complies with the normative


document about electromagnetic compatibility for
standardization of the laws of the member states
of the council of the European Union (EMC
standard 89/336/EWG).

Emission:
International

FCC Subpart B of Part 15 Class A

Europe

EN 50081-2

Susceptability
International

IEC-61000-4-2/3/4/6

Europe

EN-50082-2-1992

3.3 Mechanical Data


Table 3-2:
Data regarding size and
weight

Dimensions and Weight


Weight

approx. 500g

Dimensions
LxHxD

140 x 40 x 70mm

19

CMLIB F

3.4 Power Supply


The power supply of the CMLIB F is provided by means of a power supply
100...240VAC/18VDC unit that is equipped with an adapter for the various
specific wall outlet.

3.5 Output Power CMA 156


Figure 3-1:
Graphic showing the
output power of the
CMA 156.

3.6 Climate
Climate

20

Operating
temperature

32 ... 104F (0 ... 50C)

Storage and
transport

-13 ... 158F (-25 ... +70C)

Humidity range

5 ... 95% relative humidity, non-condensing

Technical Data

3.7 Safety Standards


Safety Standards and Certificates
International
standards

IEC 61010-1

European standards

EN 61010-1:1993

CAN/CSA-C22.2 No 1010.1-92

EN 60950 +A1: 1993-05


Certificates

CE

3.8 Accuracy
Accuracy for CMC, CMLIB F and CMA 156
Gain error

0.3 % guaranteed *)

Comes from the


CMLIB F

Phase

0.1 guaranteed *)

Comes from the


CMC 156 & CMA 156
(phase Error of the
CMLIB F negligibly)

*) Valid in the frequency range DC-100Hz..

21

CMLIB F

22

Contact Information / Technical Support

Contact Information / Technical


Support
Europe, Africa, Middle East
OMICRON electronics GmbH
Phone:

+43 5523 507-333

E-Mail:

info@omicron.at

Web:

www.omicron.at

Asia, Pacific
OMICRON electronics Asia Ltd, Hong Kong
Phone:

+852 2634 0377

E-Mail:

info@asia.omicron.at

Web:

www.omicron.at

North and South America


OMICRON electronics Corp. USA
Phone:

+1 713 830-4660 or 1 800 OMICRON

E-Mail:

info@omicronusa.com

Web:

www.omicronusa.com

For addresses of OMICRON offices with customer service centers, regional


sales offices or offices for training, consulting and commissioning please see our
website.

23

OMICRON Contact Addresses

24

Index

Index

F
Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

A
Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

G
B

Gain error . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Guaranteed values . . . . . . . . . . . . . . . . . . . . 19

Block diagram . . . . . . . . . . . . . . . . . . . . . . . . 14

H
C
calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
CE conformity . . . . . . . . . . . . . . . . . . . . . . . . 19
Certificates . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Climate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
contact information . . . . . . . . . . . . . . . . . . . . 23

hotline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Humidity range . . . . . . . . . . . . . . . . . . . . . . . 20

M
Mechanical data . . . . . . . . . . . . . . . . . . . . . . 19

D
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . 19

E
Electromagnetic compatibility . . . . . . . . . . . . 19
EMC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Emission
europe . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
international . . . . . . . . . . . . . . . . . . . . . . . 19

O
Opening the device . . . . . . . . . . . . . . . . . . . . 6
Operating . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Operating temperature . . . . . . . . . . . . . . . . . 20
Output Power . . . . . . . . . . . . . . . . . . . . . . . . 20

P
Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
pin layout . . . . . . . . . . . . . . . . . . . . . . . . 12, 13
Pin layout of the 16 pin Lemo plugs . . . . 12, 13
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . 20

25

CMLIB F

S
Safety standards . . . . . . . . . . . . . . . . . . . . . . 21
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Standards
european . . . . . . . . . . . . . . . . . . . . . . . . . 21
international . . . . . . . . . . . . . . . . . . . . . . . 21
safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Storage and transport . . . . . . . . . . . . . . . . . . 20
Susceptability
europe . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
international . . . . . . . . . . . . . . . . . . . . . . . 19

T
Technical data . . . . . . . . . . . . . . . . . . . . . . . . 19
technical support . . . . . . . . . . . . . . . . . . . . . . 23

W
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19