(R410A)
5BHW0-01A
1. Nomenclature
AC
A H
060 H B A A
Nomenclature
Serial
Communication method : A = Modbus
Product type : A = Module model
B = Independent model
C = Slave model
Power specification : H = 3, 460V, 60Hz
Cooling capacity (RT) : 060 = 60 RT
040 = 40 RT
020 = 20 RT
Compressor type : R = Scroll(Low pressure type)
H = Scroll(High pressure type)
AC = R410A / Chiller
Outdoor Unit _ 1
2. Selection Procedure
Selection
Procedure
n Selection guide
The product information required in various requirements is written in detail from Chapter 6.
If you need a product for special system application or product with the condition outside this PDB, please get
consultation from nearby sales office or specialty store.
n Selection procedure
1. Check usage condition
Before selecting the model, the following usage conditions must be decided.
- Cold and hot water in/out temperature and outdoor temperature
- Cold and hot water flow amount
(flow amount can be calculated if you know the freezing load and chilled water in/out temperature.)
2. Selecting candidate model
Required rated capability is selected through load calculation, and you can select the corresponding model
by looking at Chapter 8 Cooling/heating capability change table.
When you select the candidate model, do not select a model with less volume than the required rated capability, but select a model with the same or bigger volume.
3. Performance adjustment for fouling
The data in this technical data manual is based on chilled water fouling coefficient of 0.000018 m/W at
sea level.
If altitude or fouling coefficient is different, you have to apply appropriate adjustment coefficient form the following table to calculate data for the operation condition.
Altitude
Water in/out
temperature
difference ()
Sea level
(0m)
500 m
1,000 m
1,500 m
2 _ Outdoor Unit
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
4
5
6
7
8
Fouling coefficient
0.000018 m /W
Cooling capability
Power consumption
0.991
0.998
1.000
1.000
1.010
1.002
1.020
1.005
1.028
1.006
0.988
1.004
0.998
1.006
1.008
1.008
1.017
1.010
1.026
1.012
0.985
1.011
0.995
1.013
1.005
1.015
1.014
1.017
1.023
1.019
0.982
1.018
0.992
1.020
1.002
1.022
1.011
1.025
1.020
1.027
2
0.000054 m2/W
Cooling capability
Power consumption
0.979
0.996
0.990
0.998
1.001
1.000
1.010
1.003
1.019
1.004
0.979
1.002
0.988
1.004
0.998
1.006
1.008
1.008
1.017
1.010
0.977
1.008
0.985
1.010
0.995
1.012
1.005
1.014
1.014
1.016
0.974
1.016
0.983
1.018
0.993
1.020
1.003
1.023
1.011
1.025
2. Selection Procedure
Antifreeze Type
Methanol
Ethylene
glycol
Propylene
glycol
Item
Cooling
Pressure Drop
Cooling
Pressure Drop
Cooling
Pressure Drop
10 %
0.998
1.023
0.996
1.024
0.993
1.040
20 %
0.997
1.057
0.991
1.068
0.987
1.098
Antifreeze % by wt
30 %
0.995
1.091
0.987
1.124
0.980
1.174
40 %
0.993
1.122
0.983
1.188
0.974
1.273
50 %
0.992
1.160
0.979
1.263
0.968
1.405
Outdoor Unit _ 3
Procedure
Selection
& Limit
Model
Min.
Max.
ACAH020HBAA
15
ACAH040HBAA
15
ACAH060HBAA
15
Model
Min.
Max.
ACAH020HBAA
-10
48
ACAH040HBAA
-10
48
ACAH060HBAA
-10
48
n Operation Limit
Model
Voltage (V)
Capacity
Min.
Max.
Min.
Max.
Min.
Max.
ACAH020HBAA
414
506
10 %
100 %
126
250
ACAH040HBAA
414
506
10 %
100 %
252
500
ACAH060HBAA
414
506
10 %
100 %
378
750
4 _ Outdoor Unit
4. Specifications
n Main Units
ACAH020HBAA
20 RT
Model Name
Cooling
Capacity
Heating
Input
COP
Cooling
Heating
Cooling
Heating
, Wire, V, Hz
rated
Max
rated
Max
rated
rated
kW
kW
kW
kW
W/W
W/W
W/W
IPLV
Remote Control Type
Type
Number
EA
Compressor Oil Type
Oil Charge
cc
Sump Heater
W
Refrigerant Name
Refrigerant
Charge
kg
Type
Heat
Row x Column x Fins per inch
Exchanger
Fin type
Type
Fan
Number
EA
Air Flow Rate
CMM
Type
kPa
Head Loss
Evaporator Max. pressure
MPa
Flow rate (Cooling/Heating)
LPM
Inlet/Outlet
Piping Connections
Expansion Valve Type
Net Weight
kg
DxHxW
mm
Dimensions
DxHxW
inch
Circuit Breaker
A
Notes:
1. Due to our policy of innovation some specifications may be changed without prior notification.
2. Capacities and Inputs are based on the following conditions
Cooling : Outdoor air temp. 35C [95F]DB, Water inlet temp. 12C[53.6F], Water Outlet temp. 7C[44.6F]
Heating : Outdoor air temp. 7C [44.6F]DB, Water inlet temp. 40C[104F], Water Outlet temp. 45C[113F]
Outdoor Unit _ 5
Specifications
Power Supply
ACAH040HBAA
ACAH060HBAA
40 RT
60 RT
3, 3, 460, 60
65.0
130.0
195.0
70.0
140.0
210.0
21.7
43.3
65.0
3.0
3.0
3.0
5.0
5.0
5.0
Modbus, Interface
Scroll
2
4
6
FVC68D(PVE)
1,400 x 2
1,400 x 4
1,400 x 6
60 x 2
60 x 4
60 x 6
R410A
14 x 1
14 x 2
14 x 3
Aluminium fin & Copper tube
3 x 48 x 15
Wide Louver PLUS
BLDC Motor
2
4
6
210 x 2 @1 000 rpm
210 x 4 @1 000 rpm
210 x 6 @1 000 rpm
Plate
30
30
30
1
1
1
180/190
360/380
540/570
40A / 40A
65A /65A
65A / 65A
Electronic Expansion Valve
540
1,030
1,530
2,154 x 2,351 x 765
2,154 x 2,351 x 1,528 2,154 x 2,351 x 2,291
84-13/16 x 92-9/16 x 30-1/8 84-13/16 x 92-9/16 x 60-5/32 84-13/16 x 92-9/16 x 90-3/16
75
125
200
10
15
20
25
30
35
40
45
Classification
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
5
83.0
13.7
6.1
81.3
13.9
5.9
79.5
14.3
5.5
77.6
14.8
5.3
75.4
15.5
4.9
73.2
16.3
4.5
70.1
17.9
3.9
67.1
19.5
3.4
62.2
21.5
2.9
57.2
23.5
2.4
51.9
25.7
2.0
Notes:
1) Unit : Capacity/Power input (kW), COP (W/W)
2) Water flow rate of test condition : 180 LPM
6 _ Outdoor Unit
7
85.3
13.8
6.2
83.6
14.0
6.0
81.7
14.5
5.6
79.7
14.9
5.3
77.8
15.7
5.0
75.9
16.4
4.6
72.8
17.9
4.1
69.6
19.4
3.6
65.0
21.7
3.0
60.4
24.0
2.5
55.4
26.4
2.1
13
92.5
14.2
6.5
90.8
14.4
6.3
88.7
14.9
6.0
86.5
15.3
5.6
85.6
16.1
5.3
84.6
16.8
5.0
81.3
18.0
4.5
77.9
19.2
4.1
74.4
22.3
3.3
70.8
25.5
2.8
67.2
28.9
2.3
15
95.0
14.4
6.6
93.4
14.6
6.4
91.1
15.0
6.1
88.9
15.5
5.7
88.3
16.2
5.4
87.7
17.0
5.2
84.3
18.1
4.7
80.9
19.2
4.2
77.8
22.5
3.4
74.7
26.0
2.9
71.6
29.8
2.4
10
15
20
25
30
35
40
45
Classification
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
5
166.0
27.3
6.1
162.6
27.7
5.9
159.0
28.5
5.6
155.2
29.5
5.3
150.8
30.9
4.9
146.4
32.5
4.5
140.2
35.7
3.9
134.2
38.9
3.4
124.4
42.9
2.9
114.4
46.9
2.4
103.8
51.3
2.0
7
170.6
27.5
6.2
167.2
27.9
6.0
163.4
28.9
5.6
159.4
29.7
5.4
155.6
31.3
5.0
151.8
32.7
4.6
145.6
35.7
4.1
139.2
38.7
3.6
130.0
43.3
3.0
120.8
47.9
2.5
110.8
52.7
2.1
13
185.0
28.3
6.5
181.6
28.7
6.3
177.4
29.7
6.0
173.0
30.5
5.7
171.2
32.1
5.3
169.2
33.5
5.0
162.6
35.9
4.5
155.8
38.3
4.1
148.8
44.5
3.3
141.6
50.9
2.8
134.4
57.7
2.3
15
190.0
28.7
6.6
186.8
29.1
6.4
182.2
29.9
6.1
177.8
30.9
5.7
176.6
32.3
5.5
175.4
33.9
5.2
168.6
36.1
4.7
161.8
38.3
4.2
155.6
44.9
3.5
149.4
51.9
2.9
143.2
59.5
2.4
Notes:
1) Unit : Capacity/Power input (kW), COP (W/W)
2) Water flow rate of test condition : 360 LPM
Outdoor Unit _ 7
n ACAH040HBAA
10
15
20
25
30
35
40
45
Classification
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
Capacity
Power input
COP
5
249.0
41.0
6.1
243.9
41.6
5.9
238.5
42.8
5.6
232.8
44.3
5.3
226.2
46.4
4.9
219.6
48.8
4.5
210.3
53.6
3.9
201.3
58.4
3.4
186.6
64.4
2.9
171.6
70.4
2.4
155.7
77.0
2.0
Notes:
1) Unit : Capacity/Power input (kW), COP (W/W)
2) Water flow rate of test condition : 540 LPM
8 _ Outdoor Unit
7
255.9
41.3
6.2
250.8
41.9
6.0
245.1
43.4
5.6
239.1
44.6
5.4
233.4
47.0
5.0
227.7
49.1
4.6
218.4
53.6
4.1
208.8
58.1
3.6
195.0
65.0
3.0
181.2
71.9
2.5
166.2
79.1
2.1
13
277.5
42.5
6.5
272.4
43.1
6.3
266.1
44.6
6.0
259.5
45.8
5.7
256.8
48.2
5.3
253.8
50.3
5.0
243.9
53.9
4.5
233.7
57.5
4.1
223.2
66.8
3.3
212.4
76.4
2.8
201.6
86.6
2.3
15
285.0
43.1
6.6
280.2
43.7
6.4
273.3
44.9
6.1
266.7
46.4
5.7
264.9
48.5
5.5
263.1
50.9
5.2
252.9
54.2
4.7
242.7
57.5
4.2
233.4
67.4
3.5
224.1
77.9
2.9
214.8
89.3
2.4
40RT
20RT
Outdoor Unit _ 9
8. Dimensions
Dimensions
n Model : ACAH020HBAA
Water Outlet
(40A)
Water Inlet
(40A)
- Front view -
- Side view -
(Unit : mm)
Classification Dimension
- Rear view -
10 _ Outdoor Unit
765
2 198
2 351
2 154
240
610
190
8. Dimensions
n Model : ACAH040HBAA
Dimensions
Water Outlet
(65A)
Water Inlet
(65A)
A
- Front view -
- Side view -
(Unit : mm)
Classification Dimension
1 528
2 198
2 351
2 154
240
610
190
- Rear view -
Outdoor Unit _ 11
8. Dimensions
Dimensions
n Model : ACAH060HBAA
Water Outlet
(65A)
Water Inlet
(65A)
A
D
B
- Front view -
- Side view -
(Unit : mm)
Classification Dimension
- Rear view -
12 _ Outdoor Unit
2 291
2 198
2 351
2 154
240
610
190
9. Base of Installation
n Details to consider when installing the base
L1
Used drill
5/8 (M16)
125
70
22
65
22
273.5
50
A
B
E
F
D
C
100
65
Dimension
50
87
A
150
465
42 140
(Unit : mm)
20 RT
40 RT
60 RT
865
1,628
2,391
765
1,528
2,291
2,254
2,254
2,254
2,154
2,154
2,154
691
1,456
2,217
1,707
1,707
1,707
Drain
hole
Outdoor Unit _ 13
Base of Installation
9. Base of Installation
273.5
50
F
D
C
F
D
C
Base of Installation
A
B
E
50
87
273.5
50
A
B
E
50
85
539
100
100
A
150
539
14 _ Outdoor Unit
539
613
539
Drain
hole
150
Drain
hole
Voltage
(V)
Voltage range
(V)
MCA
(A)
MFA
(A)
020HBAA
040HBAA
060HBAA
60
60
60
460
460
460
414-506
414-506
414-506
65
123
181
90
150
200
Notes:
1. RLA is the current required when operated in the following
condition.
Cooling : Outdoor air temp. 27C DB / 19.0C WB,
Water inlet / Outlet temp. 12C / 7C
Heating : Outdoor air temp. 7C DB / 6.0C WB,
Water inlet / Outlet temp. 40.0C / 45.0C
2. Voltage range
The chiller must be operated at the voltage within the upper
and lower limit supplied from the power terminal to operate
normally.
3. Maximum voltage variance permitted between phases is 2%.
Inv. Comp
Qty
RLA
2
14.05
4
14.05
6
14.05
Fan Motor
Qty
RLA
2
3
4
3
6
3
Outdoor Unit _ 15
Electric Characteristics
ACAH
Wiring Diagrams
n ACAH020HBAA
16 _ Outdoor Unit
Wiring Diagrams
18 _ Outdoor Unit
Outdoor Unit _ 19
Installation of Chiller
20 _ Outdoor Unit
When installing the chiller near the coast, make sure that it is not directly exposed to the coastal wind.
When installing the chiller directly exposed to the coastal wind, separate anti-corrosive treatment must be
done on the condenser of the chiller.
Coastal wind
Coastal wind
If the product has to be installed inevitably facing the coast, install a wall around the outdoor unit.
Wall
Coastal wind
Outdoor Unit _ 21
Installation of Chiller
CAUTION
Air
(Unit: mm)
Wall
h1
800
800+h1/2
Reference
If the side of the chiller is near the wall and the height of the wall is less than 800mm, the distance between the wall
and the chiller must be at least 800mm. If the side of the chiller is near the wall and the wall is 800mm or higher,
space of half of h1 must additionally be secured on top of the 800mm for the distance between the wall and the chiller.
(Unit: mm)
Ceiling
Air
5,000
Installation of Chiller
When installing the product, secure minimum space as shown below considering the service, suction and discharge of air flow.
Wall
800
Reference
If there is a ceiling on the top part of the chiller, the distance from the chiller to the ceiling must be 5000mm or above.
If the front or rear side of the chiller is close to the wall, the distance from the wall to the chiller must be 800mm or
above.
22 _ Outdoor Unit
There must be sufficient space for maintenance and repair work around the chiller.
Service space
800 mm
800 mm
800 mm
600 mm
Service space
800 mm
800 mm
800 mm
Outdoor Unit _ 23
Installation of Chiller
Water management
The water quality of the cold (hot) water is described as follows. The water quality must not fall below the
following standard. If so, it can be judged to have risk within relatively short period of time.
Item
Cold water
6.5 - 8.0
6.5 - 8.0
500 or below
200 or below
100 or below
50 or below
Hardness (PPM)
100 or below
50 or below
100 or below
50 or below
100 or below
50 or below
Iron (PPM)
0.1 or below
0.3 or below
Not detected
Not detected
0.5 or below
0.2 or below
Silica (PPM)
50 or below
30 or below
PH(25C)
Reference
Water
24 _ Outdoor Unit
T1
P1
T1
T2
P2
P1
T2
P2
LG supplied
LG supplied
Symbol
Description
Symbol
Description
Valve
T1
Strainer
P1
Flexible joint
Outdoor Unit _ 25
T1
P1
P2
P2
T2
T2
T1
Installation of Chiller
Installation mode B
P1
LG supplied
LG supplied
Symbol
Description
Symbol
Description
Valve
T1
Strainer
P1
Flexible joint
26 _ Outdoor Unit
20 RT
65 A
40 RT
80 A
60 RT
Full product capacity
Common pipe size
20 RT
Product 40 RT
60 RT
60 RT
100 A
80 RT
100 A
100 RT
125 A
120 RT
125 A
140 RT
125 A
160 RT
150 A
180 RT
150 A
200 RT
150 A
220 RT
200 A
240 RT
200 A
260 RT
200 A
280 RT
200 A
300 RT
200 A
Outdoor Unit _ 27
Installation of Chiller
If the winter outdoor temperature is 0C or below, take following measures to prevent the pipe from
freezing as shown below.
- If the outdoor temperature is low, the circulation water can freeze to damage the heat exchanger of
the product when the product is stopped.
If there is possibility of damage from low outdoor temperature, operate the pump to prevent the
water from freezing.
- If the product does not operate for a long period of time during the winter season, remove all the circulation water to prevent the damage of heat exchanger and pipe from freezing.
- Add anti-freeze additive to prevent the circulation water from freezing during the winter season.
Maintain the cold water flux within the designed flux to ensure appropriate chiller performance and
reduce the tube damage from rusting, scaling and corrosion. LG is not responsible for any damage of
chiller from poor water quality management or inappropriate processing water.
Installation of Chiller
Unit Combination
Master unit
Slave unit
Terminal
Block
11A
11B
Slave unit
Terminal
Block
Terminal
Block
11A
11A
11B
11B
HMI controller
: Field wiring
WARNING
Electric work using special circuit based on the overall regulation and this manual must be done by
qualified electrician.
If the capacity of the power supply circuit is insufficient or if there is a defect, it can cause electric shock
or fire.
28 _ Outdoor Unit
2. Compressor
1) R410A refrigerant should be used, case shape should be sealed type, format should be the combination of two
inverter scroll compressors, it should be flexible to respond to load, and it should be a high efficiency system that
can optimize energy efficiency through inverter control.
2) Vibration prevention rubber should be used to prevent transfer of noise and vibration during operation.
3) The frequency variable boundary of inverter scroll compressor should be minimum 15Hz and maximum 125Hz.
4) Alternating operation should be possible to have the uniform average operation time of the compressors.
3. Condenser
1) Condenser heat pipe should use purity 99.9 % or above Phosphorus Deoxidized Copper without joint, and it should
have the structure with Al fin attached to increase the heating area. (Cross fin & Tube type)
2) Use wide louver fin for Al fin, and pipe extension should be carried out for efficient heat transfer.
3) Condenser air cooled type heat exchanger arrangement should be 3 rows 48 levels 15FPI.
4) The pressure endurance test for high pressure part refrigerant side should be carried out at 4.18 MPa or above
(designed pressure 3.8 MPa), and there should be problems such as leakage or deformation.
Outdoor Unit _ 29
Specification of Production
1) Use the parts and material of KS standard products or equivalent products for those not specified in this specification,
and all parts should be designed with structure that is easy for replacement, repair, and inspection.
Specification of Production
5. Evaporator
1) Evaporator should be blazing plate type heat exchanger type, and the material should be stainless steel.
2) There should be no water leakage, and the durability should be guaranteed.
3) It should have the structure that can connect to chilled water pipe.
4) Heat exchanger should be sensible heat exchange structure that the refrigerant and coolant are not mixed.
5) It should be a structure that each of coolant and refrigerant are flown into countercurrem structure heat exchanger
and after heat is exchanged with each other through the thin valve inside heat exchanger, discharged outside heat
exchanger.
6) In the destruction test, it should endure 18 MPa pressure.
6. Control equipment
1) It is the controller to operate overall system in optimal condition with the microcomputer unit installed in the freezer,
and based on the 4 measurement values including intake refrigerant gas pressure, discharged refrigerant gas
pressure, discharged refrigerant gas temperature, and heat exchanger refrigerant temperature, it should be able to
control electronic expansion valve, compressor(inverter), etc.
2) There should be a function that can check all sensors connected to the freezer and various operation statuses.
3) It should be equipped with self protection equipment and system protection function.
4) Module type control interface should be applied so that simple product control is possible in series installation, and
relocation and re-installation of HMI controller should be possible without separate control equipment.
7. Ref. Piping
1) Refrigerant pipe should be purity 99.9% or above Phosphorus Deoxidized Copper without joint, and it should be
piped for fluent refrigerant flow between each component.
2) Install check valve at compressor discharge side to prevent reverse flow of the discharged refrigerant.
3) Install strainer in the pipe to absorb moisture inside the pipe and to filter foreign objects.
4) The pipe from expansion valve to evaporator should be insulated to prevent moisture condensation on the surface
of the pipe and to prevent flash gas generation of refrigerant fluid at the same time.
30 _ Outdoor Unit
8. Safety devices
1) Refrigerant pressure (Normal refrigerant pressure)
A. High pressure switch
B. High voltage protection (Sensor)
2) Temperature
A. compressor discharge temperature overheating detection (Sensor)
B. IPM temperature detection (Sensor)
C. Freeze and burst protection (Sensor)
D. Power Module application (Sensor)
3) Chilled water flow
A. Chilled water flow switch)
4) Voltage and current (control logic)
A. Revere phase detection and protection (Voltage monitoring system)
B. Compressor over-current protection
C. Fan motor over-current protection
5) Fuse
Outdoor Unit _ 31
Specification of Production
5) Liquid injection pipe that activates electronic valve to flow fluid refrigerant to the suction pipe when discharged gas
temperature is above the rated temperature should be installed to protect compressor and freezer.
6) After completing the piping, carry out the pressure endurance test on refrigerant side at 4.18 MPa or above
(designed pressure 3.8 MPa), and there should be no leakage or deformation.
7) After carrying out air-tight test, completely vacuum inside so that there is absolutely no moisture.
Item
Cooling
Methanol
Pressure Drop
Cooling
Ethylene glycol
Pressure Drop
Cooling
Propylene glycol
Pressure Drop
10%
20%
30%
40%
50%
0.998
0.997
0.995
0.993
0.992
1.023
1.057
1.091
1.122
1.160
0.996
0.991
0.987
0.983
0.979
1.024
1.068
1.124
1.188
1.263
0.993
0.987
0.98
0.974
0.968
1.040
1.098
1.174
1.273
1.405
Correction Factor
0.980
0.970
0.960
0.950
Methanol
Ethylene glycol
Prlpylene glycol
0.940
0.930
0%
10%
20%
30%
Antifreeze % by wt
32 _ Outdoor Unit
40%
50%
Cooling
Air Cooled
Condensor
Sub-cooler
Fan motor
4 way valve
Pressure sensor
Pressure switch
S
Temperature sensor
S
Solenoid valve
Check valve
Water outlet
PHEX
Accumulator
Strainer
Inverter
Compressor 1
Water inlet
Receiver
Inverter
Compressor 2
Electonic expantion
Valve
Expansion valve
Outdoor Unit _ 33
Appendix
Introduction
Piping Diagram
n ACAH020HBAA
34 _ Outdoor Unit
Water
inlet
Water
outlet
PHEX
Sub-cooler
Receiver
Accumulator
Inverter
Compressor 1
Air Cooled
Condensor
Inverter
Compressor 2
Water
inlet
Water
outlet
PHEX
Sub-cooler
Receiver
Accumulator
Inverter
Compressor 1
Air Cooled
Condensor
Inverter
Compressor 2
Cooling
S
S
Fan motor
4 way valve
Pressure sensor
Pressure switch
Temperature sensor
Solenoid valve
Check valve
Strainer
Electonic expantion
Valve
Expansion valve
Water
inlet
Water
outlet
PHEX
Sub-cooler
Receiver
Accumulator
Inverter
Compressor 1
Inverter
Compressor 2
Water
inlet
Water
outlet
PHEX
Sub-cooler
Receiver
Accumulator
Inverter
Compressor 1
Air Cooled
Condensor
Inverter
Compressor 2
Water
inlet
Water
outlet
PHEX
Sub-cooler
Receiver
Accumulator
Inverter
Compressor 1
Air Cooled
Condensor
Inverter
Compressor 2
n ACAH060HBAA
Cooling
S
S
Fan motor
4 way valve
Pressure sensor
Pressure switch
Solenoid valve
Temperature sensor
Appendix
Introduction
Piping Diagram
Air Cooled
Condensor
Check valve
Electonic expantion
Valve
Expansion valve
Strainer
Outdoor Unit _ 35
Memo
Memo
36 _ Outdoor Unit
P/No.: MFL67285207
Air Conditioner
20 Yeouido-dong, Yeongdeungpo-gu,
Yeouido P.O.Box 335 Seoul,
150-721, Korea.
http://www.lgeaircon.com