DUPLEX 15000
Indoor type
B
C
T
CHF
CHW
Rooftop type
N-B
N-C
N-T
N-CHF
N-CHW
i1
e2
i2
e1
1. Equal-pressure
ventilation with
heating or cooling
i1
e1
e2
i1
e2
i2
i1
e2
i2
e1
4. Ventilation without
heat recovery
(via by-pass)
3. Circulation heating
or cooling
SELECTION SOFTWARE
s a v e
y o u r
e n e r g y
N I T
V E N T I L A T O R S
&
H E A T
R E C O V E R Y
D I V I S I O N
PERFORMANCE CURVES
INDOOR TYPE
ROOFTOP TYPE
fan type
Fan protection
supply air max. 1)
exhaust air max. 1)
heat recovery efficiency
number of configurations
weight 2)
number of fans
max. power input
voltage
frequency
speed
max. heating capacity T 4)
max. cooling capacity CHW 4)
max. cooling capacity CHF 4)
filtration class (standard)
1)
2)
DUPLEX 15000
M020
M021
IP54
IP10
13 500
15 000
13 500
15 000
55 65
55 65
8
8
690 870
690 870
2
2
2x 3,7
2x 5,8
400
400
50
60 3)
1 390
1 600 3)
185
229
59
70
65
77
G4
G4
m3h-1
m3h-1
%
kg
kW
V
Hz
rpm-1
kW
kW
kW
fan type
Fan protection
supply air max. 1)
exhaust air max. 1)
heat recovery efficiency
number of configurations
weight 2)
number of fans
max. power input
voltage
frequency
speed
max. heating capacity T 4)
max. cooling capacity CHW 4)
max. cooling capacity CHF 4)
filtration class (standard)
3)
4)
m3h-1
m3h-1
%
kg
kW
V
Hz
min-1
kW
kW
kW
DUPLEX-N 15000
M020
M021
IP54
IP10
13 500
15 000
13 500
15 000
55 65
55 65
2
2
1 100 1 300 1 100 1 300
2
2
2x 3,7
2x 5,8
400
400
50
60 3)
1 390
1 600 3)
185
229
59
70
65
77
G4
G4
the parameters of DUPLEX 15 000 with the M021 fans are valid
only when used with 60 Hz / 400 V inventer control !
according to coil and fluid type
1 200
Supply and extraction section
(supply without registers, withG4 filters)
Supply section with T.2
Supply section with CHW.3, CHF.3
Supply section with T.2+CHW.3, T.2+CHF.3
1 100
DUP
1 000
900
LEX
1500
0, M
0
21, 6
0 Hz
DUPL
, K.9
EX 15
00.A
000,
M020
/ M0
21, 5
0 Hz,
K.900
.A
800
700
600
500
D U P LE
400
X 1500
0, M02
0
300
DUPLEX
200
100
0
0
1 000
15000,
M 020 /
2 000
/ M 02
M 021, 2
3 000
1, 35 H
0 Hz, K.9
4 000
z, K.90
0.A
00.A
5 000
6 000
7 000
8 000
Note: for the summary performance overview for the rooftop version see a separate catalogue sheet
6
5
4
3
2
1
0
M021, 60 Hz
M020 / M021, 50 Hz
M020 / M021, 35 Hz
M020 / M021, 20 Hz
1 000
2 000
3 000
4 000
5 000
6 000
7 000
8 000
150
Heating capacity T applies for water tepm. drop 80/60 C; inlet air (after
recovery) +5,5 C, rh 30 %
Max. cooling capacity CHW applies for water tepm. rise 6/12 C;
inlet air 30 C, rh 50 %.
100
tin
water hea
g coil T.2
(two-row)
F.3 (three-row)
ion (DX) coil CH
direct expans
W.3 (three-row)
ter cooling coil CH
50
wa
Heat recovery
efficiency (%)
0
80
Low limit is without condensation and with
equal air volume flow rate (Mi = Me)
70
heat recovery core K.9
00
.A
60
50
1 000
2 000
3 000
4 000
5 000
6 000
7 000
8 000
9 000
10 000
11 000
DIMENSIONS
INDOOR TYPE
ROOFTOP TYPE
455
UT1,2 CH1,2
Ki
L0/L1/L2
500
L0/L1/L2
Fi
T
Ke
Me
Fe
Mi
Mi
Fi
Me
CH
200
200
Ki
695
455
Fe
475
Ke
695
CH
B
K
695
Access door
Access door
L - 20
200
alt. CHF1,2
B - 20
Base frame
standard
part of delivery
(consists of two
assembled parts)
200
675
UT1,2
CH1,2
DUPLEX
length L0/L1 (without / only T)
length L2 (T / 2 coils)
depth B
height H
connection ports Y x X 1)
1)
DUPLEX-N
length L0/L1 (without / only T)
length L2 (T / 2 coils)
depth B
height H
connection ports Y x X 1)
15000
3 000
3 400
1 380
2 350
710 x 710
mm
mm
mm
mm
mm
15000
3 140
3 540
1 420
2 390
710 x 710
mm
mm
mm
mm
mm
Y+20
X+20
X
Access door
Rectangular
150
80
alter.
port with
flexible
connection
(max. length)
(inlet, outlet)
P0 / P1 / P2
P 200
100
alter.
260
2x 50
80
port
with damper
and flexible
connection
(inlet only)
n x 100
n x 100
110
1 310
100
port
with damper
(inlet only)
100
1 710
100
50
1 270
basic port
(inlet, outlet)
DUPLEX-N
P0 / P1 (without / only T)
P2 (T / 2 coils)
mm
mm
15000
3 130
3 520
INSTALLATION CONFIGURATION
POSITION AND CONNECTION PORTS
CONFIGURATION
INDOOR TYPE
e2
i1
e2
i1
i1
e2
12/0
12/2
i2
e1
12/4
i2
e1
12/0
12/6
i2
e1
12/2
12/6
i2
i1
i2
13/4
e1
13/0
i1
e2
13/2
e1
e2
i1
i1
13/0
i2
e1
12/4
e2
e2
e2
i1
i2
13/6
e1
13/2
13/4
i2
e1
13/6
ROOFTOP TYPE
i2
e1
i2
e1
1/3
2/3
e2
e2
i1
1/3
i1
2/3
MANIPULATION SPACE
MANIPULATION SPACE
INDOOR TYPE
ROOFTOP TYPE
hinges
Service space is needed at the front of the unit for opening access
door, filter removal and service access for T and CH coil
replacement.
Minimum manipulation space on the control panel side is 600 mm
for all units.
Units equipped with heating/cooling coil hydraulic kit require free
manipulation on the kit side.
hinges
T CH
i2
e1
floor
min. 1 500 mm
SOUND POWER LEVEL L
min. 1000
e2
min. 600 mm
min. 600 mm
i1
Access
door
(dB)
2 kHz 4 kHz
56,3 45,9
85,2 78,9
83,0 75,6
53,3 43,0
81,1 75,0
78,8 69,3
S O U N D P R E S S U R E L E V E L L D1 ( d B )
(dB)
D1
2 kHz 4 kHz
43,9 33,7
70,8 64,0
69,4 61,1
34,0 27,1
55,8 47,5
49,1 40,4
(dB)
MODIFICATIONS
DUPLEX BASIC CONFIGURATION
DUPLEX 15000
Basic configuration
The compact unit consists of supply and exhaust centrifugal fans with electric motors in anti-vibration mounting,
removable cross-flow air-to-air heat recovery core assembled from thin plastic plates, removable G4 (or F7) supply
and exhaust air filters, and a condensate pan with DN 32 flexible hose. The unit casing consists of steel frame and
sandwich side panels made of painted aluminum sheets and filled with 22 mm of polyurethane insulation with thermal
2
-1
resistance R = 1,05 m KW , (rooftop units with insulation of 45 mm). The sandwich panels are fixed to the frame.
A front door enables easy access to all built-in components and filters.
Me.xxx; Mi.xxx
Fans
For the DUPLEX unit different fan types of different manufacturers may be used. They differ in airflow, external
pressure, IP protection, control type, speed, noise and power input. All fans are 3-phase direct-driven.
Air-to-air heat recovery exchanger
The DUPLEX 15000 unit is now available only with one heat recovery exchanger type.
A heat recovery exchanger in a casing with LO and L1 length must be equipped with
a droplet eliminator.
K.900.A
B.x
By-pass (B)
By-pass of the plate heat recovery core on supply air side. By-pass consists of an opposed-blade damper
and an actuator.
It is fitted next to the recovery core inside the unit; it does not increase size of the unit.
The standard actuator is BELIMO 230 V; other types are available upon request.
C.x
Mixing damper (C)
Built-in opposed-blade damper including BELIMO 230 V actuator. It enables to mix fresh and stale (internal)
air in 0 to 100 % range. Along with a mixing damper the e1 shutoff damper without spring-return function must always
be installed. Should the unit be equipped with a heating coil (DUPLEX-TC) and draft could occur in the duct system
during power failure with the damper stuck open, it is necessary to install separate shutoff damper with spring-return
function into the duct close to an air intake. The damper is controlled by the unit control.
T.x
Hot water heating coil (T)
Built-in water-to-air two-row (possibly three-row) heating coil; made of copper pipes and aluminum fins. Designed
for systems up to 110 C and 1,0 MPa. The coil is standardly equipped with flexible connection and a steam-gas
capillary thermostat for freeze protection. Units in modification T (with heating coil) must be equipped with e1 supply
air shutoff damper; an actuator with spring-return function (BELIMO LF 230 V) is reccommended. A coil hydraulic
kit for heating capacity control of R-TPO, R-TPO-3 or RS-TPO type can be supplied with the coil upon request.
Attention the coil of rooftop units must always be protected against freezing by a water-glycol mixture.
CHP
Provision for cooling (CHP)
Provision to build in a chilled water cooling coil or a DX coil.
This provision consist of a coil chamber, condensate drain pan, optionally a droplet eliminator.
Warning - in case the cooling coil is built in later, provide safety access and enough manipulation space.
A unit in the CHP modification has always L2 length.
CHF.x
Direct expansion (DX) coil (CHF)
A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate drainage
and a pressure switch for freeze alarm. Two-row- or three-row coils are chosen depending on capacity required,
refrigerant type and air parameters. A DX coil may be equipped with accessories mounted on unit housing.
A cooling coil must be equipped with a droplet eliminator. A unit in CHF configuration has always L2 length.
CHW.x
Chilled water cooling coil (CHW)
A built-in coil made of copper pipes and aluminum fins, including a condensate pan with individual condensate
drainage. Two-row or three-row coils are chosen depending on capacity required, cooling medium type and air
parameters.
The cooling coil can be equipped with the R-CHW hydraulic kit on request.
A cooling coil must be equipped with a droplet eliminator. A unit in CHW configuration has always L2 length.
ACCESSORIES
OTHER OPTIONAL ACCESSORIES (BASIC OVERVIEW)
Ke.xxx; Ki.xxx
S h u t o f f d a m p e r e 1; i 1
Shutoff dampers standardly fitted with BELIMO
actuators are located in the air inlet port.
The following damper types are available:
fresh air damper e1 mandatory for C
modification (with mixing damper)
fresh damper e1 LF mandatory for T
modification (with heating coil)
exhaust air damper i1
Fe.xxx; Fi.xxx
Air filtration
All DUPLEX units can be equipped with supply air
filtration of F7 class instead of standard G4
class. Pressure drop of the filter is then 50
to 100 Pa (clean filter) depending on air flow
rate, unit type and dirt accumulated.
Prefilters made of multilayer pulled metal
can be supplied.
R-TPO.x; RS-TPO.x
Heating coil
hydraulic kit
Its function is to control heating capacity of
a heating coil. It consists of a three-speed pump,
two globe shutoff valves and connection pipes.
Further equipment depends on the type:
R-TPO-4 four-way mixing valve with
an actuator for digital control system
R-TPO-3 three-way mixing valve with
an actuator for digital control system
RS-TPO three-way diverting valve with
a thermostatic valve for electric control system
R-CHW.x
Cooling coil
hydraulic kit
Its function is to control cooling capacity
of a chilled-water cooling coil. It always consists
of two globe shutoff valves and connection pipes.
Further equipment depends on the type:
R-CHW-2 throttling valve with an actuator
for digital control system
Double insulation
It is possible to increase polyurethane insulation
2
-1
to 45 mm thickness (R = 2,1 m KW ). Then
outer dimensions of the unit are 40 mm larger
in all directions compared to catalogue
dimensional data.
CHF
A
B,C D
RCHF.x
Accessories
for DX coil
It is possible to equip the DX coils with
refrigeration circle components: expansion valve
with nozzle (A), solenoid valve (B, C),
sight glass (D), filter-drier (E),
eventually with evaporating pressure controller.
H.P
Flexible
connections
Rectangular ports may optionally be equipped
with flexible connection.
NFT.x
Spare filter
textiles (NFT)
Spare filter textiles in sizes depending on unit
type. They are available in the filtration
of G4 and F7 class.
CONTROL SYSTEMS
DUPLEX units are delivered with basic control components
or with complete control systems. There are three types
of control systems available (electric, digital and control for
kitchens) according to customer needs and an application.
The systems also include variety of sensors (temperature,
humidity, air quality, CO2) for effective operation control.
Use
Type
Characteristics
A basic
simple system
two-speed fan control (MIN, MAX)
(exact volume flow rate can
individually be set for each fan
during commissioning)
on/off control of by-pass and
mixing damper
on/off remote control of heating
coil: temperature is set on the
thermostatic valve of hot water coil
or directly on the electric coil
RG
OP
SM
E DC-series
digital control
basic function
+
elect. heater control
(SR module)
Electric heater
(basic modification)
DUPLEX-T
basic function
+
water heating coil
(SR-T module)
HYG, QPA, PS
(humidity sensors,
air quality, movement)
DUPLEX
230 V
50 Hz
DUPLEX
basic control
kitchen hood /
ventilation ceiling SKV
OP controller
(OP-T, OP-T-BP
options)
D for kitchens
OPS
basic version
(fans, actuators, thermostats,
pressure switches
and others on request)
RG junction box
B electric
control module
SM
Controllers
DC-p1, DC-p2
DUPLEX
DC control
(module DC-XS)
(module DC EXPc)
Communication
protocols
KNX, Modbus,
TCP/IP
External
components