Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
MDCC_T30.0.11.doc
BRAGA MORO has the right to change these data with no pre-advice
125V-48V
I #1
DC-DC #1
2P 20A
I #2
Spare Slot
2P 20A
M #1
I #3
S #1
2P 63A
Id #110
10x
2P 20A
Spare Slot
2P 20A
#3 output
terminals
for external
DCDP
125V-48V
I #4
DC-DC #2
2P 20A
I #5
Spare Slot
2P 20A
M #2
I #6
S #2
2P 63A
10x
2P 10A
Spare Slot
2P 20A
Id #1120
#3 output
terminals
for external
DCDP
DC Distribution Panel
BRAGA MORO has the right to change these data with no pre-advice
Temperature
Altitude
Protection Degree
IP20B
125Vdc / 110Vdc
99Vdc 138Vdc
16A
92%
1584W
6x 20A 2P
OUTPUT
48Vdc
38Vdc
< 1%
0.7mV psofom
30A
27A 33A
0.1%
Dynamic Regulation for step load change between 10% and 90%
5%
58Vdc
30mV eff
100mVpp
135kcal/h
Cooling
600x420x820
Weight
88 Kg
255 Kg/m2
STANDARD REFERENCES
Safety
EN 60950
Conducted emissions
EN55022
EN 61000-4-3 (3V/m)
Surge immunity
BRAGA MORO has the right to change these data with no pre-advice
The System Control Unit communicates with all the modules by means of a CAN BUS connection.
All the modules are continuously monitored to detect alarms and events that are associated to the relevant time
reference and recorded (up to 1000 events can be stored).
The System Control Unit continuously monitors the input and output parameters, and consequently adjusts the
converters voltage/current set-points.
Standard remote-alarm interface is provided by Relay Card (RL Card) equipped with six potential-free contact
relays, fully software configurable. Two Additional RL Cards can be provided as option.
The LAN Ethernet 10 Base T interface allows the connection to the TLC network for the remote management of the
system and the automatic transmission of SNMP traps, e-mail or SMS.
The Battery Management Option can be included to manage independently and separately different battery strings
selectively protected, the measured and estimated parameters are:
Battery temperature;
Battery voltage;
Battery current;
Battery Available Capacity;
Battery Discharge Condition;
Battery Residual Capacity;
Battery Discharge Level.
The battery floating voltage is adjusted according to the temperature and some software configurable parameters.
BRAGA MORO has the right to change these data with no pre-advice
Positioning
BRAGA MORO has the right to change these data with no pre-advice
DC Module BMD4830
Protections
Features
Parallel operation;
Load sharing;
Selective disconnection in case of fault;
Soft-start;
Hot-plug;
Plug and play;
Current calibration and voltage limitation.
LED
Upper
LED
Status
Description
GREEN
RD Module ON
YELLO
W
RED
RD Module OFF
Lower
RED
Generic Alarm
LED
OFF
Normal operation
BRAGA MORO has the right to change these data with no pre-advice
BMD4830
ELECTRICAL FEATURES
INPUT
Input voltage
125Vdc / 110Vdc
99Vdc 138Vdc
16A
92%
1584W
OUTPUT
Rated output voltage
48Vdc
38Vdc
< 1%
0.7mV psofom
30A
27A 33A
0.1%
Dynamic Regulation for step load change between 10% and 90%
5%
58Vdc
30mV eff
100mVpp
ACOUSTIC NOISE
50dB
135kcal/h
Cooling
MECHANICAL FEATURES
Dimensions W x D x H
231 mm x 350 mm x 1U
Weight
4Kg
Electrical connection
Insertion
Frontal