Table of content
Page
Products
Introduction
Explanations
Technical
information
10
12
14
Technical catalogues:
Current transformers IMB
17
33
41
53
Optional
PQSensor
60
64
66
68
Product range
All instrument transformers supplied by ABB are tailormade to meet the needs of our customers.
An instrument transformer must be capable of
withstanding very high stresses in all climatic conditions.
We design and manufacture our products for a service life
of at least 30 years. Actually, most last even longer.
Type
IMB 36 - 800
36 - 800
EMF 52 - 170
52 - 170
CPB 72 - 800
72.5 - 800
CCB 72 - 800
72.5 - 800
We are flexible and tailor make each instrument transformer to our customers needs.
Sizes other than those mentioned above can be supplied upon request.
Explanations
mm/kV
mm/kV
a - Very light
22.0
b - Light
27.8
16
c - Medium
34.7
20
d - Heavy
43.3
25
e - Very Heavy
53.7
31
Rated frequency
The rated (power) frequency is the nominal frequency of the
system expressed in Hz, which the instrument transformer is
designed to operate in.
Wind load
The specified wind loads for instrument transformers intended for
outdoor normal conditions are based on a wind speed of 34 m/s.
Pollution level
Current transformers
Currents
The rated currents are the values of primary and secondary
currents on which performance is based.
Rated primary current
The rated current (sometimes referred to as rated current,
nominal current or rated continuous current) is the maximum
continuous current the equipment is allowed to carry.
The current is expressed in A rms.
Secondary reconnection
Extra secondary terminals (taps) are taken out from the secondary winding. The load capacity drops as the ampere-turns
decrease on the taps, but the short-circuit capacity remains
constant. Each core can be individually reconnected.
It should be selected about 10 - 40% higher than the estimated operating current. Closest standardized value should
be chosen.
Accuracy
The accuracy class for measuring cores is according to the
IEC standard given as 0.2, 0.2S, 0.5, 0.5S or 1.0 depending
on the application. For protection cores the class is normally
5P or 10P. Other classes are quoted on request, e.g. class
PR, PX, TPS, TPX or TPY.
Rct
The secondary winding resistance at 75 C
Explanations
Voltage transformers
Voltages
The rated voltages are the values of primary and secondary
voltages on which the performance is based.
Voltage factor (FV)
It is important that the voltage transformer, for thermal and
protection reasons, can withstand and reproduce the continuous fault overvoltages that can occur in the net. The overvoltage factor is abbreviated as F V.
The IEC standard specifies a voltage factor of 1.2 continuously and simultaneously 1.5/30 sec. for systems with effective grounding with automatic fault tripping, and 1.9/8 hrs for
systems with insulated neutral point without automatic ground
fault systems.
Accuracy, according to IEC, for measuring windings is fulfilled
between 0.8 and 1.2 x rated voltage and for protection windings up to the voltage factor (1.5 or 1.9 x rated voltage).
Reconnection
The voltage transformer can be designed with secondary
reconnection.
Secondary reconnection means that extra secondary terminals (taps) are taken out from the secondary winding(s).
Burden and accuracy class
Burden
The external impedance in the secondary circuit in ohms at
the specified power factor. It is usually expressed as the apparent power in VA -, which is taken up at the rated secondary voltage.
(See Current Transformers above).
The accuracy class for measuring windings, according to IEC,
is given as 0.2, 0.5 or 1.0 depending on the application. A
rated burden of around 1.3-1.5 times the connected burden
will give maximum accuracy at the connected burden.
For protection purposes the class is normally 3P or 6P
Simultaneous burden (IEC)
Metering windings and protection windings not connected in
open delta are considered as simultaneously loaded. A protection winding connected in open delta is not considered as
a simultaneous load.
IMB 36 - 800 kV
VT
EMF 52 - 170 kV
CVT
CPB 72 - 800 kV
CC
CCB 72 - 800 kV
Completed tests
The silicone material used for ABB Instrument Transformers is
approved according to IEC and ANSI/IEEE standards.
Non-brittle
Minimum risk for handling and transport damages
Minimum risk for vandalism
Light-weight
Explosion safety
Excellent pollution performance
Minimum maintenance in polluted areas
Hydrophobic
Tests performed:
Accelerated ageing test (1000 h)
Lightning impulse test, wet power frequency test and wet
switching impulse test
Short circuit test
Temperature rise test
Color
The (SIR) insulators for the instrument transformers are supplied in a light gray color.
Deliveries
ABB in Ludvika has supplied instrument transformers with
(SIR) insulators for the most severe conditions, from marine
climate to desert and/or polluted industrial areas.
A reference list can be provided on request.
EP-rubber
Silicone
Brittle
Low
Excellent
Excellent
Insulation
Fair
Good
Excellent
Good
Excellent
Excellent
Excellent
Good
Excellent
Safety
Good
Good
Excellent
Earthquake
Good
Excellent
Excellent
Handling
Good
Excellent
Excellent
Maintenance
Fair
Fair
Excellent
Ageing
Fair
Good
Excellent
Good
Good
Excellent
Weight
Mechanical strength
UV-resistance
Experience of material
ABB has used silicone rubber (SIR) insulators since 1985,
starting with surge arresters, and has gained considerable
experience thereof.
IMB
Impregnation
Heating in a vacuum dries the windings. After assembly all
free space in the transformer (approx. 60%) is filled with clean
and dry quartz grain. The assembled transformer is vacuumtreated and impregnated with degassed mineral oil. The transformer is always delivered oil-filled and hermetically sealed.
Tank and Insulator
The lower section of the transformer consists of an aluminum
tank in which the secondary windings and cores are mounted.
The insulator, mounted above the transformer tank, consists
as standard of high-grade brown-glazed porcelain. Designs
using light gray porcelain or silicon rubber can be quoted on
request.
The sealing system consists of O-ring gaskets.
Expansion system
The IMB has an expansion vessel placed on top of the insulator. A hermetically sealed expansion system, with a nitrogen
cushion compressed by thermal expansion of the oil, is used
in the IMB as the standard design. An expansion system with
stainless steel expansion bellows can be quoted on request.
On request Capacitive voltage tap
The capacitive layers in the high voltage insulation can be
utilized as a capacitive voltage divider. A tap is brought out
from the second to last capacitor layer through a bushing on
the transformer tank (in the terminal box or in a separate box,
depending on the IMB tank design). An advantage of the capacitive terminal is that it can be used for checking the condition of the insulation through dielectric loss angle (tan delta)
measurement without disconnecting the primary terminals.
The tap can also be used for voltage indication, synchronizing
or similar purpose, but the output is limited by the low capacitance of the layers.
The load connected must be less than 10 kohms and the tap
must be grounded when not in use.
One model of IMB 72 - 123 is provided with a DDF (Dielectric Dissipation Factor) terminal in the secondary terminal box. The
terminal must be connected to ground during normal service, but
can be disconnected from ground and used for checking the
dielectric dissipation factor of the internal high voltage insulation
between primary terminals and ground
Climate
The transformers are designed for, and are installed in, widely
shifting conditions, from polar to desert climates all over the
world.
8
9
Service life
The IMB transformer is hermetically sealed and the low and
even voltage stress in the primary insulation gives a reliable
product with expected service life of more than 30 years. The
IMB and its predecessors have since the 1930s been supplied
in more than 170000 units.
10
3
Expansion system
The expansion system, with a nitrogen gas cushion, increases
operating reliability and minimizes the need of maintenance
and inspections. This type of expansion system can be used
in the IMB since the quartz filling reduces the oil volume and a
relatively large gas volume minimizes pressure variations.
Flexibility
The IMB covers a wide range of primary currents up to 4000 A.
It can easily be adapted for large and/or many cores by increasing the volume of the tank.
Resistance to corrosion
The selected aluminum alloys give a high degree of resistance
to corrosion, without the need of extra protection. Anodized
parts for IMB 36-170 kV can be offered on request, for use in
extreme environments.
IMB >170 kV can be delivered with a protective painting.
Seismic strength
The IMB has a mechanically robust construction, designed to
withstand high demands of seismic acceleration without the
need of dampers.
11
Gas cushion
Quartz filling
Expansion vessel
Paper-insulated primary
conductor
10
Primary terminal
Cores/secondary windings
11
Ground terminal
(on request)
EMF
Expansion system
The EMF has an expansion vessel placed on the top section
of the porcelain. The EMF has a closed expansion system,
without moving parts and with a nitrogen cushion, that is
compressed by the expansion of the oil. A prerequisite for this
is that the quartz sand filling reduces the oil volume, and the
use of a relatively large gas volume, which gives small pressure variations in the system.
Primary windings
The primary winding is designed as a multi-layer coil of double
enamelled wire with layer insulation of special paper.
Both ends of the windings are connected to metal shields.
Secondary and tertiary windings
In its standard design the transformer has a secondary
measurement winding and a tertiary winding for ground fault
protection, but other configurations are available as required.
(2 secondary windings in a design according to IEEE standard)
The windings are designed with double enamelled wire and
are insulated from the core and the primary winding with
pressboard (presspahn) and paper.
The windings can be equipped with additional terminals for
other ratios (taps).
Core
The transformer has a core of carefully selected material, to
give a flat magnetization curve. The core is over-dimensioned
with a very low flux at operating voltage.
Impregnation
Heating in a vacuum dries the windings. After assembly, all
free space in the transformer (approximately 60%) is filled with
clean and dry quartz grains. The assembled transformer is
vacuum-treated and impregnated with degassed mineral oil.
The transformer is always delivered oil-filled and hermetically
sealed.
Tank and insulator
EMF 52-170: The lower section of the transformer consists of
an aluminum tank in which the winding and core are placed.
The tank consists of selected aluminum alloys that give a high
degree of resistance to corrosion, without the need of extra
protection. Anodized aluminum can be offered on request.
The sealing system consists of O-ring gaskets.
Ferro-resonance
The design of the EMF notably counteracts the occurrence of
ferro-resonance phenomena:
The low flux in the core at the operating voltage gives a
large safety margin against saturation if ferro-resonance
oscillations should occur.
The flat magnetization curve gives a smooth increase of
core losses, which results in an effective attenuation of the
ferro-resonance.
If the EMF transformer will be installed in a network with
a high risk for ferro-resonance, it can, as a further safety
precaution, be equipped with an extra damping burden, on a
delta connected tertiary winding. See the figure below.
R
S
T
A
da
dn
da
dn
da
dn
60 ohm, 200 W
Damping of ferro-resonance
Climate
These transformers are designed for, and are installed in a
wide range of shifting conditions, from polar to desert climates all over the world.
Service Life
The low and even voltage stresses in the primary winding give
a reliable product with a long service life. EMF and its predecessors have been supplied in more than 60000 units since
the 1940s.
Expansion system
The expansion system based on the nitrogen cushion gives
superior operating reliability and minimizes the need of maintenance and inspection of the transformer.
1
9
2
4
5
Quartz filling
Minimizes the quantity of oil and provides a mechanical support to the cores and primary winding.
Resistance to corrosion
EMF 52-170: The selected aluminum alloys give a high degree
of resistance to corrosion without the need of extra protection.
Anodized aluminum can be offered on request.
Seismic strength
EMF is designed to withstand the high demands of seismic
acceleration.
10
1
Primary terminal
Expansion system
10
Paper insulation
Oil
11
Tank
Quartz filling
12
Primary winding
Insulator
13
Secondary windings
Lifting lug
14
Core
15
Secondary terminals
16
Ground connection
11
12
13
14
15
8
16
CPB
Climate
These transformers are designed for, and are installed in
widely varying conditions, from arctic to desert climates, on
every continent.
Ferro-resonance
The low induction, combined with an efficient damping circuit,
gives a safe and stable damping of ferro-resonance at all
frequencies and voltages up to the rated voltage factor; see
page 40.
Life time
The low voltage stress within the capacitor elements ensures
a safe product with an expected service life of more than 30
years. The long term reliability and performance is further
ensured by the state of the art, automated manufacture and
processing of the capacitor elements and units.
Transient properties
The high intermediate voltage and high capacitance result in
good transient properties.
Adjustment
The adjustment windings for ratio adjustment are accessible
in the terminal box, under a sealed cover.
Power Line Carrier (PLC)
The CPB is designed with the compensating reactor connected on the high voltage side of the primary winding, providing
the option of using higher frequencies (> 400 kHz) for power
line carrier transmission.
Stray capacitance
The design with the compensating reactor on the high voltage
side of the main winding ensures less than 200 pF stray capacitance, which is the most stringent requirement in the IEC
standard for carrier properties.
Stability
The CPB has a high Quality Factor as a result of the comparatively high capacitance combined with the high intermediate
voltage. The Quality Factor = Cequivalent x U2intermediate is a measure of the accuracy stability and the transient response. The
higher this factor, the better the accuracy, and the better the
transient response.
Capacitor Voltage Divider
10
11
7
12
Electromagnetic unit
4
Compensating reactor
Expansion system
Capacitor elements
Gas cushion
11
10
12
Core
Buyers Guide | Outdoor Instrument Transformers 13
CCB
Capacitor design
The coupling capacitor consists of one up to four capacitor
units, assembled on top of each other. Each unit contains
a large number of series-connected, oil-insulated capacitor
elements. The units are completely filled with synthetic oil,
hermetically sealed with stainless steel bellows and incorporated o-ring seals are used throughout the design.
The capacitor insulators and elements are designed with
respect to the same demands as for the capacitor part of
revenue metering CVT and thus also share the same conservative design philosophy. This conservative philosophy results
in a design with low voltage stress that makes the coupling
capacitors capable of handling a voltage factor up to 1.9/8
hrs although this is not required by the IEC coupling capacitor
standard.
Their active component consists of aluminum foil, insulated
with paper/polypropylene film, impregnated by a PCB-free
synthetic oil which has better insulating properties than mineral oil and is a perfect matching for the mixed dielectric. Due
to its proportions between paper and polypropylene film this
dielectric has proven itself much more insensitive to temperature changes in contradiction to e.g. full film capacitors.
The automated processing of the capacitor units further contributes to the long term high reliability and performance of the CCB.
Climate
These coupling capacitors are designed for being installed in
widely varying conditions, from arctic to desert climates, on
every continent.
Life time
The low voltage stress within the capacitor elements ensures
a safe product with an expected service life of more than 30
years.
Power Line Carrier (PLC)
The CCB are designed for use within the entire power line
carrier transmission frequency range from 30 kHz to 500 kHz.
However, the light capacitance CCB 72 - 245 is not designed
for line trap on the top.
Expansion system
Capacitor elements
Rating plate (For low capacitance CCB 72-245 its placed on the
4
5
expansion cover)
5
IMB 36-800 kV
Outdoor
Design
Insulation
Oil-paper-quartz
36 - 800 kV
Up to 4000 A
Short-circuit current
Up to 63 kA/1 sec
Insulators
Porcelain
25 mm/kV
(Longer on request)
Service conditions
Ambient temperature
-40 C to +40 C
(Others on request)
Design altitude
Maximum 1000 m
(Others on request)
IMB 36-800 kV
Material
All external metal surfaces are made of an aluminum alloy,
resistant to most known environment factors. Bolts, nuts,
etc. are made of acid-proof steel. The aluminum surfaces do
not normally need painting. We can, however, offer anodized
aluminum or a protective paint.
Creepage distance
As standard, IMB is offered with creepage distance 25 mm/kV.
Longer creepage distance can be provided on request.
Mechanical stability
The mechanical stability gives sufficient safety margins for
normal wind loads and terminal forces. Static force on primary
terminal may be up to 6000 N in any direction. The IMB will
also withstand most cases of seismic stress.
Rating plates
Rating plates of stainless steel with engraved text and the wiring diagram are mounted on the cover of the terminal box.
Transport - storage
The IMB 36 - 145 is normally transported (3-pack) and stored
vertically. If horizontal transport is required this must be stated
on the order.
The IMB 170 - 800 is packed for horizontal transport (1-pack).
The transformer(s) must be stored on a flat and stable surface
with a suitable load capacity, and if possible, in its original
packaging.
For extended storage, the contact surfaces should be protected from corrosion. Before placing in service, ensure that
all contact surfaces are thoroughly cleaned.
If the transformer(s) is stored horizontally, under unfavorable
climatic conditions, corrosion can occur on secondary terminals and accessories in the terminal box due to drainage not
functioning properly in the horizontal position. When stored
horizontally, the terminal box must be checked for condensation and penetrating moisture. Before long-term storage,
appropriate measures must be taken, such as connecting
heating elements, if available, or providing the terminal box
with silica gel or an equivalent drying agent. This applies for
storage of up to two years. For longer storage, up to five
years, the transformer must be stored indoors or under roof.
The maximum time when stored in its original crate without
any protection is six months. If the transformer is stored protected, make sure the building is very well ventilated.
Make sure that the transformer(s) is put in vertical position at
least 48 h prior to energizing (96 h for 800 kV).
18 Outdoor Instrument Transformers | Buyers Guide
20
100
75
135
50
40
40
14
Primary terminals
IMB 36 800 is as standard equipped with aluminum bar
terminals, suitable for IEC and NEMA specifications. Other
customer specific solutions can be quoted on request.
Maximum static and dynamic force on the terminal is up to
6000 and 8400 N respectively, depending on type of IMB.
Maximum torsional moment is 1000 Nm.
IMB 36-800 kV
Normal current
Cooling flanges
Cooler
Maximum short-time
Maximum short-time
current 1 sec
current 3 sec
Maximum dynamic
current
kA
kA
kA peak value
108
IMB 36-72
1)
1200
40
31.5
IMB 36-72
1)
2000
40
31.5
108
31.5
12.5
78.8
IMB 84-123
1)
720
IMB 84-123
1)
1440
40
31.5
108
IMB 36-170
2)
2400
3150
63
40
170
1200
1500
40
40
108
400
31.5
18
85
150
16
43
IMB 245
2)
1600
2000
40
40
108
IMB 245
3)
2000
2400
3150
63
63
170
1000
1200
1500
40
40
108
300
31.5
18
85
150
16
45
3150
63
63
170
IMB 300-420
3)
2500
1200
1500
40
40
108
IMB 420-550
4, 5)
2500
4000
63
40
170
IMB 800
1)
1200
2000
40
40
108
4000
63
40
170
5)
Light tank,
2)
Standard tank,
3)
Heavy tank,
4)
Octagon tank,
5)
HV tank
(Min. values)
Type
Total creepage
Protected creepage
Flashover
Total creepage
Protected creepage
distance
distance
distance
distance
distance
distance
mm
mm
mm
mm
mm
mm
660
1813
800
IMB 361)
635
1813
762
IMB 721)
660
1813
800
1005
3075
1300
IMB 721)
635
1813
762
980
3160
1307
IMB 841)
1005
3075
1300
IMB 36
1)
980
3160
1307
IMB 1231, 6)
1005
3075
1300
1215
3625
1600
IMB 1231)
980
3160
1307
1190
3880
1634
IMB 362)
630
2248
1020
1020
IMB 841)
1)
6)
7)
(Min. values)
Flashover
IMB 722)
630
2248
IMB 842)
630
2248
1020
IMB 1232)
1120
3625
1400
1120
4495
1860
IMB 1452)
1120
3625
1400
1120
4495
1860
IMB 1702)
1330
5270
2200
IMB 1702, 7)
1600
6525
2740
IMB 2452, 3)
1915
6740
2850
2265
8490
3685
IMB 3003)
2265
8250
3495
2715
10430
4645
IMB 3623)
2715
10430
4645
3115
12480
5630
IMB 420
3115
12480
5630
3635
14325
6465
IMB 4204, 5)
3215
11550
4800
3820
15280
6870
IMB 5504, 5)
3820
15280
6870
4715
18944
8340
IMB 8005)
5520
20000
8405
3)
3)
4)
5)
IMB 36-800 kV
AC voltage test,
Lightning impulse
Switching impulse
RIV test
Max RIV
equipment (Um)
1 minute, wet/dry
1.2/50 s
250/2500 s
voltage
level
kV
kV
kV
kV
kV Max.
IMB 36
36
70/70
170
IMB 72
72.5
140/140
325
IMB 123
123
230/230
550
78
2500
IMB 145
145
275/275
650
92
2500
IMB 170
170
325/325
750
108
2500
IMB 245
245
460/460
1050
156
2500
IMB 300
300
-/460
1050
850
191
2500
IMB 362
362
-/510
1175
950
230
2500
IMB 420
420
-/630
1425
1050
267
2500
IMB 550
550
-/680
1550
1175
334
2500
IMB 800
800
-/975
2100
1550
486
2500
Test Voltages IEEE C 57.13, RIV test values according to IEEE C 57.13.5
Type
Highest system
Power frequency
AC-test Wet,
Lightning impulse
Chopped
RIV test
Max RIV
voltage
10 sec
(BIL) 1.2/50 s
impulse
voltage
level 1)
V
kV
kV
kV
kV Max.
kV
kV
IMB 36
36.5
70
70
200
230
IMB 72
72.5
140
140
350
400
IMB 123
123
230
230
550
630
71
200
IMB 145
145
275
275
650
750
84
200
IMB 170
170
325
315
750
865
98
200
IMB 245
245
460
445
1050
1210
142
250
IMB 362
362
575
1300
1500
209
250
IMB 550
550
800
1800
2070
303
350
IMB 800
800
920
2050
2360
462
500
1)
Test procedure according to IEC. Test voltages above applies at 1000 meters above sea level
Burdens
Our current transformer IMB has a very flexible design allowing large burdens. However, it is important to determine the
real power consumption of connected meters and relays including the cables. Unnecessary high burdens are often specified for modern equipment. Note that the accuracy for the
measuring core, according to IEC, can be outside the class
limit if the actual burden is below 25% of the rated burden.
Over-voltage protection across primary winding
The voltage drop across the primary winding of a current
transformer is normally very low. At rated primary current it
is only a couple of volts and at short-circuit current a few
hundred volts.
Class
Application
Class
Application
0.2
0.15
0.2S
0.15S
0.5
0.3
0.5S
0.6
Metering
1.0
1.2
Metering
3.0
Instruments
C100
Protection
5.0
Instruments
C200
Protection
5P
Protection
C400
Protection
5PR
Protection
C800
Protection
10P
Protection
Protection
10PR
Protection
PX
Protection
PXR
Protection
TPS
Protection
TPX
Protection
TPY
Protection
IMB 36-800 kV
Dimensions
Type
Total
Height to
Ground
Flashover
Length across
Dimension of
distance
primary terminal
bottom tank
height
primary
level
terminal
height
Height to
Spacing for
bushing
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
IMB 36
1)
1718
1424
611
660
359
197.5
279
395
138
335
IMB 36
1)
1718
1424
636
635
359
197.5
279
395
138
335
IMB 72
1)
1718
1424
611
660
359
197.5
279
395
138
335
IMB 72
1)
1718
1424
636
635
359
197.5
279
395
138
335
IMB 84
1)
2063
1769
611
1005
359
197.5
279
395
138
335
IMB 84
1)
2063
1769
636
980
359
197.5
279
395
138
335
IMB 123
1)
2063
1769
611
1005
359
197.5
279
395
138
335
IMB 123
1)
2063
1769
636
980
359
197.5
279
395
138
335
IMB 36
2)
2000
1635
840
630
470
235
335
595
110
410
IMB 72
2)
2000
1635
840
630
470
235
335
595
110
410
IMB 84
2)
2000
1635
840
630
470
235
335
595
110
410
IMB 123
2)
2490
2125
840
1120
470
235
335
595
110
410
IMB 145
2)
2490
2125
840
1120
470
235
335
595
110
410
IMB 170
2)
2700
2335
840
1330
470
235
335
595
110
410
IMB 245
2)
3320
2950
865
1915
440
235
335
595
110
410
IMB 245
3)
3640
3050
965
1915
440
270
370
750
475
450
IMB 300
3)
4150
3405
965
2265
490
270
370
750
475
450
IMB 362
3)
4600
3855
965
2715
490
270
370
750
475
450
IMB 420
3)
5000
4255
965
3115
490
270
370
750
475
450
IMB 420
4)
5505
4760
1365
3215
490
320
380
1040
783
500
IMB 420
5)
5580
4790
1390
3215
526
360
410
1105
805
600
IMB 550
4)
6100
5360
1365
3820
490
320
380
1040
783
500
IMB 550
5)
6180
5390
1390
3820
526
360
410
1105
805
600
IMB 800
5)
8840
7090
1390
5520
526
360
410
1105
805
600
1)
Light tank,
2)
Standard tank,
3)
Heavy tank,
4)
Octagon tank,
5)
HV tank
IMB 36 - 123
IMB 36 - 170
20
K
H
IMB 36-800 kV
IMB 245
IMB 245
1)
2)
25
K
H
K
H
K
2)
3)
25
30
K
IMB 36-800 kV
4)
30
K
IMB 800
4)
30
K
IMB 36-800 kV
A, B, C
Cooling flange
Cooler
Horizontal transport
mm
mm
mm
mm
mm
10
210
255
193
210 or 420
210
35 / 240 * )
Light tank
Standard tank
Heavy tank
150
440
200 or 400
400 ** )
Octagon tank
HV tank
Oil
Shipping weight
Shipping dimensions
Shipping volume
kg
kg
1-pack/3-pack
1-pack/3-pack
1-pack/3-pack
kg
LxWxH m
1)
m3
200
IMB 36 1)
240
25
340 / 730
1.97x0.65x1.08 / 1.73x0.79x1.93
1.4 / 2.6
26
380 / 850
1.97x0.65x1.08 / 1.73x0.79x1.93
IMB 72 1)
1.4 / 2.6
200
25
340 / 730
1.97x0.65x1.08 / 1.73x0.79x1.93
1.4 / 2.6
IMB 72 1)
240
26
380 / 850
1.97x0.65x1.08 / 1.73x0.79x1.93
1.4 / 2.6
IMB 84 1)
240
27
395 / 870
2.31x0.65x1.08 / 1.73x0.79x2.42
1.6 / 3.3
IMB 84 1)
290
28
445 / 1020
2.31x0.65x1.08 / 1.73x0.79x2.42
1.6 / 3.3
IMB 123 1)
240
27
395 / 870
2.31x0.65x1.08 / 1.73x0.79x2.42
1.6 / 3.3
IMB 123
IMB 36
290
28
445 / 1020
2.31x0.65x1.08 / 1.73x0.79x2.42
1.3 / 3.3
IMB 36 2)
420
45
530 / 1350
2.26x0.6x0.94 / 1.67x0.8x2.21
1.3 / 3
IMB 72 2)
420
45
530 / 1350
2.26x0.6x0.94 / 1.67x0.8x2.21
1.3 / 3
IMB 84 2)
420
45
530 / 1350
2.26x0.6x0.94 / 1.67x0.8x2.21
1.3 / 3
IMB 123 2)
490
50
620 / 1580
2.75x0.6x0.94 / 1.67x0.8x2.7
1.5 / 3.6
IMB 145 2)
490
50
620 / 1580
2.75x0.6x0.94 / 1.67x0.8x2.7
1.5 / 3.6
IMB 170 2)
550
55
700 / -
2.96x0.6x0.94 / -
1.7 / -
IMB 245 2)
750
80
970 / -
3.48x0.6x0.94 / -
2.0 / -
IMB 245
3)
1100
110
1460 / -
3.91x1.06x1.26 / -
5.2 / -
IMB 300 3)
1400
170
1815 / -
4.5x1.06x1.26 / -
5.2 / -
IMB 362 3)
1500
180
1915 / -
4.7x1.06x1.26 / -
6.3 / -
IMB 420 3)
1600
190
2050 / -
5.1x1.05x1.31 / -
7.0 / -
IMB 420 4)
2500
300
3120 / -
5.82x1.23x1.22 / -
8.8 / -
IMB 420 4)
2600
290
3220 / -
5.74x1.06x1.47 / -
9.0 / -
IMB 550 4)
2800
330
3480 / -
6.42x1.23x1.22 / -
9.7 / -
IMB 550 5)
3500
510
4180 / -
6.34x1.06x1.47 / -
9.9 / -
IMB 800 5)
4200
670
6400 / -
8.71x1.06x1.47 / -
13.5 / -
1)
1)
Light tank
2)
Standard tank
3)
Heavy tank
4)
Octagon tank
5)
HV tank
IMB 36-800 kV
Reconnection
General
The current transformer can be reconnected to adapt for varying currents. The IMB type can be delivered in a configuration
that permits reconnection either on primary or secondary side,
or a combination of the two.
The advantage of primary reconnection is that the ampereturns remains the same and thereby the output (VA). The disadvantage is that the short-circuit capability may be reduced
for the lower ratio(s).
Primary reconnection
Two primary ratios for two turns
C1
C2
C1
C2
Secondary reconnection
P2
P1
S1
S2
S3
S4
S5
Caution!
Never leave an unused secondary winding open.
Very high-induced voltages are generated across the
terminals and both the user and the transformer are
subjected to danger.
EMF 52-170 kV
Outdoor
Design
Inductive type
Insulation
Oil-paper-quartz
52 - 170 kV
Up to 1.9/8 hrs
Insulators
Porcelain
On request silicon rubber (SIR)
Creepage distance
25 mm/kV
(Longer on request)
Service conditions
Ambient temperature
-40 C to +40 C
(Others on request)
Design altitude
Maximum 1000 m
(Others on request)
EMF 52-170 kV
Material
EMF 52-170: All external metal surfaces are made of an
aluminum alloy, resistant to most known environment factors.
Bolts, nuts, etc. are made of acid-proof steel. The aluminum
surfaces do not normally need painting. We can, however, offer a protective paint or anodized aluminum.
Creepage distance
EMF is available as standard with normal or long creepage
distances according to the table on page 36. Longer creepage distances can be quoted on request.
Mechanical stability
The mechanical stability gives a sufficient safety margin for
normal wind loads and stress from conductors. EMF can also
withstand high seismic forces.
Rating plates
Rating plates of stainless steel, with engraved text and wiring
diagrams are mounted on the transformer enclosure.
Transport - storage
The EMF 52-84 is always transported (3-pack) and stored
vertically.
The EMF 123-170 is normally transported (3-pack) and stored
vertically. If horizontal transport is required this must be stated
on the order.
The transformer(s) must be stored on a flat and stable surface
with a suitable load capacity, and if possible, in its original
packaging.
For extended storage, the contact surfaces should be protected from corrosion. Before placing in service, ensure that
all contact surfaces are thoroughly cleaned.
If the transformer(s) is stored horizontally (only EMF 123-170),
under unfavorable climatic conditions, corrosion can occur on
secondary terminals and accessories in the terminal box due
to drainage not functioning properly in the horizontal position.
When stored horizontally, the terminal box must be checked
for condensation and penetrating moisture. Before long-term
storage, appropriate measures must be taken, such as connecting heating elements, if available, or providing the terminal
box with silica gel or an equivalent drying agent. This applies
for storage of up to two years. For longer storage, up to five
years, the transformer must be stored indoors or under roof.
The maximum time when stored in its original crate without
any protection is six months. If the transformer is stored protected, make sure the building is very well ventilated.
34 Outdoor Instrument Transformers | Buyers Guide
Primary terminals
EMF 52-170 is as standard equipped with an aluminum bar
terminal, suitable for IEC and NEMA specifications.
The primary terminal is a voltage terminal and should therefore,
according to standards, withstand static force of 1000 N for Um
(system voltage) 123 170 kV and 500 N for lower voltages.
Withstand dynamic force is 1400 and 700 N respectively.
EMF 52-170
EMF 123-170
EMF 52-84
EMF 123-170
EMF 52-170 kV
Design data
Flash-over
Creepage
Protected creepage
Flash-over
Creepage
Protected creepage
distance
distance
distance
distance
distance
distance
mm
mm
mm
mm
mm
mm
EMF 52
630
2248
1020
EMF 72
630
2248
1020
EMF 84
630
2248
1020
Others on request.
EMF 123
1200
3625
1400
EMF 145
1200
3625
1400
EMF 170
1330
5270
2200
1 min
LIWL
RIV test
equipment
wet/dry
1.2/50 s
voltage
RIV level
(Um)
kV
kV
kV
kV Max.
EMF 52
52
95
250
30
125
EMF 72
72.5
140
325
46
125
EMF 84
84
150
380
54
125
EMF 123
123
230
550
78
2500
EMF 145
145
275
650
92
2500
EMF 170
170
325
750
108
2500
Test voltages above are valid for altitudes 1000 meters above sea level.
AC test
AC test
BIL
(Um)
dry, 1 min
wet, 10 sec
1.2/50 s
kV
kV
kV
kV Max.
EMF 52
52
95
95
250
EMF 72
72.5
140
175
350
EMF 123
121 (123)
230
230
550
EMF 145
145
275
275
650
EMF 170
169 (170)
325
315 (325)
750
Values within brackets refer to CAN/CSA 60044-2. Test voltages above are valid for altitudes 1000 meters above sea level.
100 VA class 3P
100 VA class 3P
100 VA class 3P
The standards state as standard values for rated voltage factor 1.5/30 sec.
for effectively earthed systems, 1.9/30 sec. for systems without effective
earthing with automatic earth fault tripping and 1.9/8 hrs for systems with
insulated neutral point without automatic earth fault tripping.
Since the residual voltage winding is not loaded except during a fault, the effect of its load on the accuracy of the other
windings is disregarded in accordance with IEC.
Please note that modern meters and protection
require much lower burdens than those above, and
to achieve best accuracy you should avoid specifying
burdens higher than necessary; see page 6.
0.6 WXYZ
1.2/3P WXYZ
Rated burdens:
W = 12.5 VA power factor 0.1
X = 25 VA power factor 0.7
Y = 75 VA power factor 0.85
YY = 150 VA power factor 0.85
Z = 200 VA power factor 0.85
ZZ = 400 VA power factor 0.85
EMF 52-170 kV
Design data
Total
Flash-over
Height to
Fixing hole
Ground level
Expansion
height
distance
terminal box
dimensions
height
vessel diameter
mm
mm
mm
mm
mm
mm
EMF 52
1464
630
114
335 x 335
540
324
EMF 72
1464
630
114
335 x 335
540
324
Type
EMF 84
1464
630
114
335 x 335
540
324
EMF 123
2360
1200
65
410 x 410
760
416
EMF 145
2360
1200
65
410 x 410
760
416
EMF 170
2490
1330
65
410 x 410
760
416
135
EMF 52-84
Note: Primary terminal will be mounted at site
20
20
135
EMF 123-170
Note: Primary terminal will be mounted at site
EMF 52-170 kV
Shipping data
Oil
Porcelain insulator
kg
kg
Shipping weight
Shipping dimensions
Shipping volume
3-pack
3-pack, L x W x H
3-pack
kg
m3
EMF 52
300
40
1040
2.5
EMF 72
300
40
1040
2.5
EMF 84
300
40
1040
2.5
EMF 123
570
80
1975
5.2
EMF 145
570
80
1975
5.2
EMF 170
610
83
2130
5.4
EMF 52 - 84 must not be tilted more than 60 during transport and storage.
EMF 123 - 170 is normally packed for vertical transport (3-pack). However, it can be transported in a horizontal position and is
available on request for horizontal transport (1-pack).
Oil
Porcelain insulator
Shipping weight
Shipping dimensions
Shipping volume
1-pack
1-pack, L x W x H
1-pack
kg
kg
kg
m3
EMF 123
570
80
720
2.0
EMF 145
570
80
720
2.1
610
83
765
2.1
670
86
810
2.2
EMF 170
EMF 170
1)
1)
CPB 72-800 kV
Outdoor
Design
Insulation
CVD
Aluminum-foil / paper /
polypropylene-film, synthetic oil
EMU
72 - 800 kV
Up to 1.9/8 hrs
Insulators
Creepage distance
Service conditions
Ambient temperature
Design altitude
Maximum 1000 m
(Other altitude on request)
CPB 72-800 kV
Material
All external metal surfaces are made of an aluminum alloy,
resistant to most known environment factors. Bolts, nuts, etc.
are made of acid-proof stainless steel. The aluminum surfaces
do not normally need painting. We can however offer anodization or protective paint, (normally light gray).
Creepage distance
As standard the CPB is offered with creepage distance
25 mm/kV. Longer creepage distances can be offered on
request.
Silicone Rubber Insulators
The complete CPB range is available with silicone rubber
insulators. Our SIR insulators are produced with a patented
helical extrusion molding technique, which gives completely
joint-free insulators with outstanding performance. All CVTs
with this type of insulators have the same high creepage distance, 25 mm/kV phase-phase, as porcelain.
Mechanical stability
The mechanical stability gives sufficient safety margin for
normal wind loads and conductor forces. For all combinations
except CPB(L), it is possible to mount line traps on top of the
capacitor divider. The CPB will also withstand most cases of
seismic stress.
Ferroresonance damping circuit
All CVTs need to incorporate some kind of ferro-resonance
damping, since the capacitance in the voltage divider, in
series with the inductance of the transformer and the series
reactor, constitutes a tuned resonance circuit.
This circuit can be brought into resonance, that may saturate
the iron core of the transformer by various disturbances in
the network. This phenomenon can also overheat the electromagnetic unit, or lead to insulation breakdown.
The CPB use a damping circuit, connected in parallel with
one of the secondary windings (see diagram on page 51). The
damping circuit consists of a reactor with an iron core, and
an oil-cooled resistor in series. Under normal use, the iron
core of the damping reactor is not saturated, yielding a high
impedance, so that practically no current is flowing through
this circuit.
The damping circuit has two bridged terminals; d1- d2, behind a sealed covering hood in the terminal box. In particular
cases, and after agreement, this bridge can be opened, to
check that the circuit is intact, by resistance measurement.
Ratio adjustment
The transformer of the electromagnetic unit has five adjustment windings on the earth side of the primary winding. The
numbers of turns of these windings have been chosen so that
the ratio can be adjusted 6.05% in steps of 0.05%. These
windings are externally accessible, behind a sealed covering hood in the secondary terminal box. The CVT is delivered
adjusted for a specified burden and class, and normally no
further adjustment is necessary.
If needed, the adjustment windings enable exchange of the
voltage divider on site, and readjustment of the transformer
for the new combination of voltage divider/electromagnetic
unit.
Rating plates
Corrosion resistant rating plates with text and wiring diagrams
are used. General data can be found on the door of the terminal box, connection diagrams and secondary winding data on
the inside.
Each capacitor unit is marked with measured capacitance at
the top.
Potential Grounding Switch
A potential grounding switch can be included in the EMU.
Power Line Carrier (PLC)
As an option all CVTs can be equipped with Carrier Accessories. Modern PLC equipment are adapted for a wide range
of coupling capacitors. No specific capacitance is required.
Only minimum capacitance must be specified due to choice of
frequency.
14
20
100
75
135
50
40
40
Primary terminal
The CPB is normally delivered with a flat 4-hole aluminum pad,
suitable for bolts with C-C from 40 to 50 mm and for connecting
normal aluminum cable clamps.
Other primary terminals can be offered on request, such as a
round aluminum studs, =30 mm.
Test forces at the primary terminal as per IEC 61869-5
Highest voltage for
equipment Um (kV)
CPB(L)
CPB
72.5 to 100
500
2500
123 to 170
1000
3000
245
1250
2500
300 to 362
1250
420
1500
Ground terminals
The transformer is normally equipped with a ground clamp with a
cap of nickel-plated brass for IEC conductors 8 16 mm
(area 50 200 mm2) and for ANSI conductors # 2 SOL to 500
MCM, which can be moved to either mounting foot.
A stainless steel bar, 80 x 145 x 8 mm, can be quoted on request.
The bar can be supplied drilled according to IEC or NEMA standards.
Grounding terminals for the secondary circuits are placed inside
the terminal box.
CPB 72-800 kV
Unpacking
Please check the crates and their contents for damage during
transportation upon receipt. Should there be any damage,
please contact ABB for advice before the goods are handled
further. Any damage should be documented (photographed).
Storage
The following have to be considered during storage:
The transformer(s) must be stored on a flat and stable surface
with a suitable load capacity, and if possible, in its original
packaging.
For extended storage, the contact surfaces should be protected from corrosion. Before placing in service, ensure that
all contact surfaces are thoroughly cleaned.
If the transformer(s) is stored horizontally, under unfavorable
climatic conditions, corrosion can occur on secondary terminals and accessories in the terminal box due to drainage not
functioning properly in the horizontal position. When stored
horizontally, the terminal box must be checked for condensation and penetrating moisture. Before long-term storage up
to two years, appropriate measures must be taken, such as
connecting heating elements, if available, or providing the
terminal box with silica gel or an equivalent drying agent.
For longer storage, up to five years, the transformer must be
stored indoors or under roof.
The maximum time when stored in its original crate without
any protection is six months. If the transformer is stored protected, make sure the building is well ventilated.
Capacitors not energized for a long period of time may show
increased power losses. After energizing the capacitors with
rated voltage the power losses starts to decrease back. The
power loss will recover to original values after some time of
continuous operation at rated voltage. Note that although the
trend of increasing power loss is counteracted after some
time in operation the on-site power loss measurements may
still show a slight discrepancy to factory values due to the
much lower test voltage usually applied on site.
Assembly
The electromagnetic unit and the capacitor voltage divider are
delivered as one unit for all CVTs for which only one capacitor
unit is used.
CVTs with higher system voltages, having more than one CVD
part, are delivered with the bottom unit of the CVD assembled
onto the EMU.
The EMU, with the bottom CVD unit should be installed first,
before the top part(s) of the CVD is (are) mounted in place.
Lifting instructions are included in each package.
Check that the capacitor units have the same serial number
(for CVDs with more than one capacitor unit).
Maintenance
The CPB is designed for a service life of more than 30 years,
and are practically maintenance-free. We recommend however the following checks and measurements.
Visual check
We recommend a periodic inspection, to check for oil leakages and also to inspect the insulator for collection of dirt.
Control measurements of the CVD
Since the voltage dividers are permanently sealed it is not
possible to take oil samples from them.
Under normal service conditions, no noticeable ageing will
occur within the capacitors (verified by ageing tests). However discrepancies between the secondary voltages in parallel
phases can be an indication of a fault in a capacitor part of
one of the CVT, which is why such a comparison is recommended. In such a case a further measurement of the capacitance value is recommended. Readings can be taken between
the top and the L terminal in the secondary terminal box.
Control measurements of the EMU
An easily performed test is to measure the insulation resistance
in mega-ohms (max. test voltage 1000 VDC) of the secondary
windings.
Since the high voltage winding of the transformer is not capacitively graded, a measurement of the loss angle (tan delta)
will give no significant result.
What is possible, however, is to take an oil sample, for gas
chromatography analysis from the electromagnetic unit to assess its condition.
The tank of the electromagnetic unit can, on request, be
equipped with a sampling valve, and we can deliver suitable sampling equipment. An easier method is to take the oil
sample from the oil-filling hole. Sampling intervals will vary,
depending on service conditions; generally, no oil analysis
should be necessary during the first 20 years of service.
CPB 72-800 kV
Environmental Aspects
Impregnant
Both Faradol 810 (the synthetic oil in the voltage dividers),
and the standard transformer oil in the electromagnetic unit are
free from PCB and other strongly harmful substances, and pose
a low impact to the environment.
Destruction
After draining the oils, these can be burnt in an appropriate
plant. In this respect, Faradol has similar combustion properties as normal mineral oil.
CPB(L)
CPB
CPB(L)
0.2
50
100
40
CPB
80
0.5
100
200
80
200
1.0/3P T1
200
400
120
400
100
100
100
100
*) The IEC standards state as standard values for effectively earthed systems 1.5/30 sec. For systems without effective earthing with automatic earth fault tripping, a rated voltage
factor 1.9/30 sec. is stated. For systems with insulated neutral point without automatic earth fault tripping 1.9/8 hrs is stated.
The above values are total maximum values for the secondary
winding(s), voltage 100/3 or 110/3 V and one or no residual
voltage winding, class 3P, intended for connection in open
delta, voltage 100 or 110 (100/3 or 110/3) V.
For other configurations please consult ABB.
If the transformer has more than one continuously loaded
winding, possibly with different classes, the table above must
be applied to the sum of these burdens and the highest accuracy class.
Since the residual voltage winding is not loaded except during a fault, the effect of its load on the accuracy of the other
windings is disregarded in accordance with IEC.
Stated values should only be considered as maximum values.
Please note that modern meters and protection require much
lower burdens than those above and to achieve best accuracy
burdens should not be specified higher than necessary.
Other standards
Quoted on request.
CPB 72-800 kV
Test voltages
Highest voltage
1 min
LIWL
Switching impulse
PD test
Max.
RIV test
for equipment
wet/dry
1.2/50 s
250/2500 s
voltage
PD level
voltage
RIV level
(Um)
kV
kV
kV
kV
kV
pC*)
kV Max.
CPB 72
72.5
140/140
325
1.2 x Um
10
CPB 123
123
230/230
550
1.2 x U m
10
78
2500
CPB 145
145
275/275
650
1.2 x Um
10
92
2500
CPB 170
170
325/325
750
1.2 x Um
10
108
2500
CPB 245
245
460/460
1050
1.2 x Um
10
156
2500
CPB 300
300
460/460
1050
850
1.2 x Um
10
190
2500
CPB 362
362
510/510
1175
950
1.2 x Um
10
230
2500
CPB 420
420
630/630
1425
1050
1.2 x Um
10
267
2500
CPB 550
525
680/680
1550
1175
1.2 x Um
10
333
2500
CPB 800
800
975/975
2100
1550
1.2 x Um
10
486
2500
Test voltages above are valid for altitudes 1000 meters above sea level.
*) 5 pC at test voltage 1.2 x Um/3
Other standards
Quoted on request.
CPB 72-800 kV
Type
Number of
Standard
capacitor units
capacitance
Extra long
creepage distance
Protected
creepage distance
1)
CPB 72
1)
CPB 72
2)
pF (+10; - 5%)
mm
mm
mm
18200
680/660
1813
800
24900
635
1813
762
24900
635
1813
762
mm
CPB 123
1)
11200
1025/1005
3075
1300
CPB 123
1)
15400
980
3160
1307
CPB 123
2)
15400
980
3160
1307
CPB 145
1)
9100
1235/1215
3625
1600
CPB 145
1)
12900
1190
3880
1634
CPB 145
2)
12900
1190
3880
1634
CPB 145
2)
20200
1400
4650
1960
CPB 170
1)
7800
1445/1425
4250
1786
CPB 170
1)
10800
1400
4650
1960
CPB 170
2)
10800
1400
4650
1960
CPB 170
2)
17000
1400
4650
1960
CPB 245
1)
5600
2005/1985
6125
2619
CPB 245
1)
7700
1960
6510
2723
Normally insula-
CPB 245
2)
7700
1960
6510
2723
CPB 245
2)
12100
1960
6320
2560
higher voltage.
CPB 300
1)
6400
2380
7760
3268
CPB 300
2)
6400
2380
7760
3268
CPB 300
2)
10100
2800
9300
3920
CPB 362
1)
5400
2800
9300
3920
CPB 362
2)
5400
2800
9300
3920
CPB 362
2)
8500
2800
9300
3920
CPB 420
1)
4800
3220
10630
4356
CPB 420
2)
4800
3220
10630
4356
CPB 420
2)
8800
4200
13950
5505
CPB 550
1)
3700
4200
13980
5882
CPB 550
2)
3700
4200
13980
5882
CPB 550
2)
5800
4200
13950
5505
CPB 800
2)
6060
21080
8500
1)
4
2)
4400
3)
4)
Others on request.
CPB 72-800 kV
Dimensions
CPB 72 - 245
Note! The number of capacitor divider units can, for some voltages, be higher than in the drawings above.
Please check in the table on the next page
Number of
Standard
capacitor
capacitance
divider units
Total
Flashover distance
Height to
Mounting hole
Diameter
height
flange
3)
4)
distance
Polymer/Porcelain
expansion
Polymer/Porcelain
tank
mm
mm
mm
voltages
CPB 72
1)
CPB 72
1)
CPB 72
2)
pF (+10; - 5%)
mm
mm
mm
18200
1580
680/660
225
335
640/650
335
24900
1615
635
225
335
675
355
24900
1690
635
305
335
750
355
CPB 123
1)
11200
1925
1025/1005
225
335
640/650
335
CPB 123
1)
15400
1960
980
225
335
675
355
CPB 123
2)
15400
2035
980
305
335
750
355
CPB 145
1)
9100
2135
1235/1215
225
335
640/650
335
CPB 145
1)
12900
2170
1190
225
335
675
355
CPB 145
2)
12900
2245
1190
305
335
750
355
CPB 145
2)
20200
2455
1400
305
335
750
355
CPB 170
1)
7800
2345
1445/1425
225
335
640/650
335
CPB 170
1)
10800
2380
1400
225
335
675
355
CPB 170
2)
10800
2455
1400
305
335
750
355
CPB 170
2)
17000
2455
1400
305
335
750
355
CPB 245
1)
5600
2905
2005/1985
225
335
640/650
335
CPB 245
1)
7700
2940
1960
225
335
675
355
CPB 245
2)
7700
3015
1960
305
335
750
355
CPB 245
2)
12100
3405
1960
305
335
750
355
CPB 300
1)
6400
3750
2380
225
335
675
355
CPB 300
2)
6400
3825
2380
305
335
750
355
CPB 300
2)
10100
4245
2800
305
335
750
355
CPB 362
1)
5400
4170
2800
225
335
675
355
CPB 362
2)
5400
4245
2800
305
335
750
355
CPB 362
2)
8500
4245
2800
305
335
750
355
CPB 420
1)
4800
4590
3220
225
335
675
355
CPB 420
2)
4800
4665
3220
305
335
750
355
CPB 420
2)
8800
6035
4200
305
335
750
355
CPB 550
1)
3700
5570
4200
225
335
675
355
CPB 550
2)
3700
5645
4200
305
335
750
355
CPB 550
2)
5800
6035
4200
305
335
750
355
CPB 800
2)
4400
7825
6060
305
335
750
355
1)
4
2)
3)
4)
CPB 72-800 kV
Shipping data
Standard
capacitance
oil
For IEC
Polymer/
Shipping dimensions
Shipping
3-pack
3-pack
3-pack
volume
Total
test volltage
Porcelain
Polymer
Porcelain
LxWxH
pF (+10; - 5%)
kg
kg
kg
kg
m3
CPB 72
1)
18200
190/200
38
710
740
0.94x1.67x1.98
3)
3.1
3)
CPB 72
1)
24900
210/240
44
770
860
0.94x1.67x1.98
3)
3.1
3)
CPB 72
2)
24900
280/310
62
980
1070
0.94x1.67x1.98
3)
3.1
3)
CPB 123
1)
11200
200/220
40
750
810
0.94x1.67x2.33
3)
3.6
3)
CPB 123
1)
15400
230/280
45
840
990
0.94x1.67x2.33
3)
3.6
3)
CPB 123
2)
15400
300/350
63
1050
1200
0.94x1.67x2.33
3)
3.6
3)
CPB 145
1)
9100
210/280
41
785
995
0.94x1.67x2.54
3)
4.0
3)
CPB 145
1)
12900
230/300
47
845
1055
0.94x1.67x2.54
3)
4.0
3)
CPB 145
2)
12900
300/370
65
1055
1265
0.94x1.67x2.54
3)
4.0
3)
CPB 145
2)
20200
350/440
78
3x520
3x610
CPB 170
1)
7800
220/250
43
3x385
CPB 170
1)
10800
240/320
48
CPB 170
2)
10800
320/400
CPB 170
2)
17000
350/440
CPB 245
1)
5600
CPB 245
1)
CPB 245
2)
CPB 245
2)
CPB 300
CPB 300
3x(2.73x0.65x1.08)
4)
3x1.9
4)
3x415
3x(2.73x0.65x1.08)
4)
3x1.9
4)
3x410
3x490
3x(2.73x0.65x1.08)
4)
3x1.9
4)
66
3x490
3x570
3x(2.73x0.65x1.08)
4)
3x1.9
4)
76
3x520
3x610
3x(2.73x0.65x1.08)
4)
3x1.9
4)
240/280
47
3x435
3x475
3x(3.29x0.65x1.08)
4)
3x2.3
4)
7700
280/390
53
3x475
3x585
3x(3.29x0.65x1.08)
4)
3x2.3
4)
7700
350/460
71
3x545
3x655
3x(3.29x0.65x1.08)
4)
3x2.3
4)
12100
410/540
92
1080+475
1300+670
1)
6400
330/470
63
845+485
2)
6400
400/540
81
1070+470
CPB 300
2)
10100
460/650
108
CPB 362
1)
5400
360/520
CPB 362
2)
5400
CPB 362
2)
CPB 420
CPB 420
0.94x1.67x2.33 + 1.76x1.54x0.72
5)
4.0 + 1.9
5)
1085+695
0.94x1.67x2.54 + 1.97x1.54x0.72
5)
4.0 + 2.2
5)
1310+680
0.94x1.67x2.54 + 1.97x1.54x0.72
5)
4.0 + 2.2
5)
3x505 + 1x570
3x600 + 1x855
3x(2.73x0.65x1.08) + 2.18x1.54x0.72
6)
3x1.9 + 2.4
6)
67
3x415 + 1x540
3x495 + 1x780
3x(2.73x0.65x1.08) + 2.18x1.54x0.72
6)
3x1.9 + 2.4
6)
430/590
85
3x490 + 1x525
3x570 + 1x765
3x(2.73x0.65x1.08) + 2.18x1.54x0.72
6)
3x1.9 + 2.4
6)
8500
460/650
104
3x505 + 1x570
3x600 + 1x855
3x(2.73x0.65x1.08) + 2.18x1.54x0.72
6)
3x1.9 + 2.4
6)
1)
4800
380/560
71
3x440 + 1x600
3x530 + 1x870
3x(2.94x0.65x1.08) + 2.39x1.54x0.72
6)
3x2.1 + 2.6
6)
2)
4800
450/630
89
3x515 + 1x 585
3x605 + 1x855
3x(2.94x0.65x1.08) + 2.39x1.54x0.72
6)
3x2.1 + 2.6
6)
CPB 420
2)
8800
570/860
138
3x500 + 2x555
3x600 + 2x845
3x(2.73x0.65x1.08) + 2x(2.18x1.54x0.72)
CPB 550
1)
3700
430/670
75
3x480 + 1x700
3x600 + 1x1060
3x(3.43x0.65x1.08) + 2.88x1.54x0.72
6)
CPB 550
2)
3700
500/740
93
3x555 + 1x685
3x675 + 1x1045
3x(3.43x0.65x1.08) + 2.88x1.54x0.72
6)
CPB 550
2)
5800
690/1070
160
3x540 + 2x675
CPB 800
2)
4400
720/1170
164
3x525 + 3x610
3x635 + 3x945
1)
2)
3)
4)
5)
6)
3x(2.94x0.65x1.08) + 3x(2.39x1.54x0.72)
6)
3x1.9 + 2x2.4
3x2.4 + 3.2
6)
3x2.4 + 3.2
6)
6)
6)
3x1.9 + 2x2.4
6)
6)
3x2.1 + 3x2.6
6)
CPB 72-800 kV
Schematic diagram
BN
Ground
1.
2.
3.
4.
5.
6.
CCB 72-800 kV
Coupling capacitors
Outdoor
Design
Column type
Insulation
Aluminum-foil / paper /
polypropylene-film, synthetic oil
72 - 800 kV
Up to 1.9/8 hrs
Insulators
Porcelain
On request silicon rubber (SIR)
Creepage distance
25 mm/kV
(Longer on request)
Service conditions
Ambient temperature
-40 C to +40 C
(Others on request)
Design altitude
Maximum 1000 m
(Others on request)
CCB 72-800 kV
Coupling capacitors
Material
All external metal surfaces are made of aluminium alloy resistant to most known environment factors.
Bolts, nuts, etc. are made of acid-proof stainless steel.
The aluminium surfaces do not normally need painting.
Creepage distance
As standard, CCB is offered with creepage distance 25 mm/kV
phase-phase (IEC pollution class Heavy).
Longer creepage distances can be offered on request.
Maximum static test force on the primary terminal in all directions is:
Highest voltage for
CCB 1)
CCB
500
2500
123 to 170
1000
3000
245
1250
2500
300 to 362
1250
420
1500
1)
72.5 to 100
equipment Um (kV)
CCB 72-800 kV
Transport - storage
The CCB 72-800 is packed for horizontal transport (3-pack).
If 1-pack horizontal transport is required this must be stated
on the order.
Maintenance
The CCB is designed for a service life of more than 30 years,
and is practically maintenance-free. We recommend however,
the following checks and measures.
Visual check
We recommend a periodic inspection, to check for oil leakages and also to inspect the insulator for possible damage
and collection of dirt.
For extended storage, the contact surfaces should be protected from corrosion. Before placing in service, ensure that
all contact surfaces are thoroughly cleaned.
This applies for storage of up to two years. For longer storage, up to five years, the coupling capacitor(s) must be stored
indoors or under roof.
The maximum time when stored in its original crate without
any protection is six months. If the coupling capacitor(s) is
stored protected, make sure the building is very well ventilated.
Capacitors not energized for a long period of time may show
increased power losses. After energizing the capacitors with
rated voltage the power losses starts to decrease back. The
power loss will recover to original values after some time of
continuous operation at rated voltage. Note that although the
trend of increasing power loss is counteracted after some
time in operation the on-site power loss measurements may
still show a slight discrepancy to factory values due to the
much lower test voltage usually applied on site.
Unpacking
Please check the crates and their contents for damage during
transportation upon receipt. Should there be any damage,
please contact ABB for advice before the goods are handled
further. Any damage should be documented (photographed).
Assembly
The capacitor units, whenever the coupling capacitor consists
of more than one unit, are always delivered as separate units
and assembled at installation.
Environmental aspects
Impregnant
Faradol 810 (the synthetic oil in the capacitor units) is free
from PCB and other strongly harmful substance and poses
low impact to the environment.
Destruction
After draining the oil, it can be burnt in an appropriate plant.
In this respect Faradol has similar combustion properties as
normal mineral oil. The disposal should be carried out in accordance with local legal requirements and regulations.
The porcelain can be deposited after it has been crushed.
Aluminium parts are labelled with material specifications. The
metals in the housings of the capacitor units can be recycled.
Regarding the aluminium in the capacitor elements, with their
combination of foil, paper and polypropylene film, it can be
recycled after the insulation has been burnt; the plastic film
will not emit any harmful substances during this process.
CCB 72-800 kV
Technical data
CCB: Number of capacitor units, capacitance, heights, flashover and creepage distance
Minimum nominal values
Type
Number of
Standard
Total height
Height each
Diameter
Flashover distance
Creepage
capacitor
capacitance
divider unit
Expansion
Polymer/porcelain
distance
tank
2)
2)
units
CCB 72
1)
CCB 72
CCB 123
1)
CCB 123
Protected
creepage
distance
pF (+10; -5%)
mm
mm
mm
mm
mm
mm
18200
1130
N/A
335
680/660
1813
800
24900
1165
N/A
355
635
1813
762
11200
1475
N/A
335
1025/1005
3075
1300
15400
1720
N/A
355
980
3160
1307
N/A
1
9100
1685
335
1235/1215
3625
1600
CCB 145
12900
1720
N/A
355
1190
3880
1634
CCB 145
20200
1930
N/A
355
1400
4650
1960
CCB 145
1)
7800
1895
N/A
335
1445/1425
4250
1786
CCB 170
10800
1930
N/A
355
1400
4650
1960
CCB 170
17000
1930
N/A
355
1400
4650
1960
CCB 170
1)
5600
2455
N/A
335
2005/1985
6125
2619
CCB 245
7700
2490
N/A
355
1960
6510
2723
CCB 245
12100
2892
1510 / 1382
355
1960
6320
2560
CCB 245
1)
CCB 300
6400
3310
1718 / 1592
355
2380
7760
3268
CCB 300
10100
3732
1930/1802
355
2800
9300
3920
CCB 362
5400
3732
1930 / 1802
355
2800
9300
3920
CCB 362
8500
3732
1930 / 1802
355
2800
9300
3920
CCB 420
4800
4152
2140 / 2012
355
3220
10630
4356
CCB 420
8800
5534
355
4200
13950
5505
CCB 550
3700
5132
2630 / 2502
355
4200
13980
5882
CCB 550
5800
5534
355
4200
13950
5505
CCB 800
4400
7796
355
6060
21080
8500
1)
2)
If longer creepage distance than standard is needed, please choose the higher voltage that corresponds to the wanted creepage distance.
Note the capacitance for the higher voltage level will normally be used.
2)
CCB 72-800 kV
Number of
capacitor
Polymer/porcelain
Oil
units
CCB 72
1)
CCB 72
CCB 123
1)
CCB 123
Shipping dimensions
Package weight
Shipping volume
One CCB
One CCB
One CCB
kg
kg
kg
m3
80/90
1.45x0.65x0.75
71
0.8
90/130
13
1.45x0.65x0.75
71
0.8
90/110
10
1.80x0.65x0.75
80
0.9
105/170
16
1.80x0.65x0.75
80
0.9
100/120
11
2.00x0.65x0.75
85
1.0
CCB 145
115/190
18
2.00x0.65x0.75
85
1.0
CCB 145
140/250
25
2.20x0.65x0.75
91
1.1
CCB 145
1)
105/140
13
2.20x0.65x0.75
91
1.1
CCB 170
130/210
19
2.20x0.65x0.75
91
1.1
CCB 170
140/250
25
2.20x0.65x0.75
91
1.1
CCB 170
1)
130/170
17
2.75x0.65x0.75
115
1.4
CCB 245
150/270
24
2.75x0.65x0.75
115
1.4
CCB 245
220/360
40
2 x (1.80x0.65x0.75)
2 x 80
2 x 0.9
CCB 245
1)
CCB 300
230/410
43
2 x (1.80x0.65x0.75)
2 x 80
2 x 0.9
CCB 300
270/470
55
2 x (2.00x0.65x0.75)
2 x 85
2 x 1.0
CCB 362
230/410
39
2 x (2.00x0.65x0.75)
2 x 85
2 x 1.0
CCB 362
270/470
50
2 x (2.00x0.65x0.75)
2 x 85
2 x 1.0
CCB 420
250/450
43
2 x (2.40x0.65x0.75)
2 x 106
2 x 1.2
CCB 420
390/690
80
2.20x1.55x0.75
195
2.6
CCB 550
300/560
50
2 x (2.90x0.65x0.75)
2 x 118
2 x 1.45
CCB 550
390/700
75
2.20x1.55x0.75
194
2.6
CCB 800
560/1020
110
2.40x1.55x0.75 +
106 + 223
2.8 + 1.2
2.40x0.65x0.75
CCB 72-800 kV
Test voltages
Highest voltage
1 min
LIWL
Switching impulse
PD test
Max.
RIV test
for equipment
wet/dry
1.2/50 s
250/2500 s
voltage
PD level
voltage
RIV level
(Um)
kV
kV
kV
kV
kV
pC
kV Max.
CCB 72
72.5
140/140
325
1.1 x Um/3
10
CCB 123
123
230/230
550
1.1 x Um/3
10
78
2500
CCB 145
145
275/275
650
1.1 x Um/3
10
92
2500
CCB 170
170
325/325
750
1.1 x Um/3
10
108
2500
CCB 245
245
460/460
1050
1.1 x Um/3
10
156
2500
CCB 300
300
- /460
1050
850
1.1 x Um/3
10
191
2500
CCB 362
362
- /510
1175
950
1.1 x Um/3
10
230
2500
CCB 420
420
- /630
1425
1050
1.1 x Um/3
10
267
2500
CCB 550
550
- /680
1550
1175
1.1 x Um/3
10
349
2500
CCB 800
800
- /975
2100
1550
1.1 x Um/3
10
486
2500
Test voltages above are valid for altitudes 1000 meters above sea level.
When ANSI/IEEE standard is required, please choose the CCB size that cover the required test voltages
CCB 72-800 kV
Dimensions
CCB 72 - 245
CCB 72 - 245
D=355
D=355
80
D=335
410
230
410
510
510
510
230
410
510
410
Note! The number of capacitor units can, for some voltages, be higher than in the drawings above. See the table on page 56.
PQSensor
1.0
0.0
50
100
200
500
1000
2000
5000
Frequency
PQSensor
C1
C2
Primary Voltage
CVT Output
2.5
2.5
2
1.5
0.5
1.5
0.5
0
3
11
13
15
17
19
21
23
25
27
29
31
33
35
37
11
13
15
17
19
21
23
25
27
29
31
33
35
37
Harmonic Order
Harmonic Order
Using a CVT for harmonic voltage measurements can result in errors as large as 300%. At some harmonic frequencies the
levels reported by the CVT will be higher than those present in the input voltage and for others they will be lower. These results,
based on actual site measurements show that 35th & 37th harmonics present on the input do not appear on the CVT output and
the level of 13 th harmonic on the CVT output is three times higher than the actual level in the substation.
Using a CVT equipped with PQSensor
Input voltage
PQSensor Output
3
2.5
2.5
2
1.5
PQSensor
0.5
Primary Voltage
3
2
1.5
0.5
11
13
15
17
19
21
Harmonic Order
23
25
27
29
31
33
35
37
11
13
15
17
19
21
23
25
27
29
31
33
35
37
Harmonic Order
Using a CVT equipped with a PQSensor gives the correct values for voltage harmonics up to and beyond the 100th harmonic
with accuracy levels exceeding the requirements of IEC 61000-4-7. The output signal from the PQSensor does not contain
any of the harmonic errors present in the conventional CVT output.
PQSensor
Installation
Main Terminal
C1
Electromagnetic Unit
(EMU)
CVT Output
Measurement Unit
C2
PQSensor
SCM
Wide bandwidth
voltage output
(63.5V ac)
PQSensor
Technical data
Frequency response
10 Hz 10 kHz
< 5%
< 3
100 kohm
-40 to +55 C
Optional
Simple maintenance
A Roxtec CF 16 can be opened and closed repeatedly for
easy installations and simple maintenance. Another benefit is
a built in spare capacity for possible new cables in the future.
Multidiameter
The CF 16 uses adaptable Multidiameter technology. This enables cables of a wide range of diameters to be sealed with a
perfect fit, even when tolerances and deviations from nominal
dimensions are considered. The modules are delivered with a
center core as a substitute for a cable. This means the entry
kit is adaptable to different cable sizes, and to different numbers of penetrations.
Benefit summary
Seals several cables and diameters
Quick and easy installation
Cable retention
Rodent proof
IP 66/67
Halogen-free
UL/NEMA 4, 4X, 12, 13
Fire retardant material UL 94-V0
Kit supplied
The Roxtec CF 16 kits are available in two versions: Each one
with a customized set of sealing modules to suit the most
common cables sizes and numbers in the junction boxes (as
shown below).
For other dimensions, please contact:
ABB, HV Components, Ludvika, Sweden.
Customer notes
Type tests
The type tests reports for tests performed on transformers
types similar to customer specifications are available.
IEC 61869-2
a. Verification of terminal marking and polarity
IEC 61869-3
a. Verification of terminal marking and polarity
Routine tests
The following tests are performed on each transformer as
standard before delivery in accordance with applicable standards:
e. Determination of errors
g. Determination of errors
(One transformer in each batch is type-tested for accuracy.
Remaining units at a reduced number of burdens. Complete
error curves on all transformers must be ordered separately.)
The membership and supervision of SATS ensures the independency of the laboratory.
We are, with these testing resources, able to claim that we
are at the forefront in developing new and safe products for
the 21st century.
Ordering data
Test voltages
Lightning impulse 1.2/50 s
Power frequency dry/wet
Switching surge 250/2500 s (For Um 300 kV, wet)
Test voltages
Lightning impulse 1.2/50 s
Power frequency dry/wet
Currents
Ratio (primary and secondary currents)
Reconnection (primary or/and secondary)
Rated continuous thermal current (Rf)
Short time current, Ith 1 sec (3 sec)
Dynamic current, Idyn
Burden and accuracy
Number of cores
For each core please state:
Burden/class/overcurrent factor
Special requirements
Silicone rubber insulator (gray)
Creepage distance (ABB standard: 25 mm/kV)
Light gray porcelain (ABB standard: brown)
Special primary terminals
Special secondary terminals
Heater
Secondary overvoltage protection:
(spark gaps, protection gaps)
Anodized tank, terminal box and expansion system
(IMB 36-170)
1-pack, vertical transport (IMB 36-145)
Horizontal transport (IMB 36-145)
Other?
Additional requirements
Capacitive voltage tap
Adapter (for replacing old type IMB)
Ambient temperature
Height above sea level if >1000 m
Please state normal system and test voltages
according to actual standard when 1000 m a.s.l.
Other requirements?
Voltages
Ratio (primary and secondary voltages)
Reconnection (secondary)
Voltage factor (Vf) and time
Burden and accuracy
Number of secondary winding(s)
For each winding please state:
Connection: Star or broken delta
Burden/class
Thermal limit burden (if requested)
Special requirements
Silicone rubber insulator (gray)
Creepage distance (ABB standard: 25 mm/kV)
Light gray porcelain (ABB standard: brown)
Special primary terminal
Special secondary terminals
Secondary fuses
Heater
Anodized tank, terminal box and expansion system
1-pack vertical transport (EMF 52-84)
1-pack, horizontal transport (EMF 123-170)
Other requirements?
Additional requirements
Ambient temperature
Height above sea level if >1000 m
Please state normal system and test voltages according
to actual standard when 1000 m a.s.l.
Other requirements?
Test voltages
Lightning impulse 1.2/50 s
Power frequency dry/wet
Switching surge 250/2500 s (For Um 300 kV, wet)
Test voltages
Lightning impulse 1.2/50 s
Power frequency dry/wet
Switching surge 250/2500 s (For Um 300 kV, wet)
Voltages
Ratio (primary and secondary voltages)
Reconnection (secondary)
Voltage factor FV (Vf) and time
Special requirements
Silicone rubber insulator (gray)
Creepage distance (ABB standard: 25 mm/kV)
Light gray porcelain (ABB standard: brown)
Special primary terminal
Additional requirements
Capacitance - high or extra high
Ambient temperature
Height above sea level if >1000 m
Please state normal system and test voltages according
to actual standard when 1000 m a.s.l.
Other requirements?
Special requirements
Silicone rubber insulator (gray)
Creepage distance (ABB standard: 25 mm/kV)
Light gray porcelain (ABB standard: brown)
Special primary terminal
Special secondary terminals
Secondary fuses
Heater
Protection for PLC equipment
Horizontal transport
Other requirements?
Additional requirements
Capacitance - high or extra high
Ambient temperature
Height above sea level if >1000 m
Please state normal system and test voltages according
to actual standard when 1000 m a.s.l.
Other requirements?
Customer notes
ABB AB
High Voltage Products
www.abb.com
Publication 1HSM 9543 42-00en, Edition 7, 2012-09 Oil insulated, Outdoor Instrument Transformers, Buyers Guide, Photo: Hasse Eriksson